1 Filtered Differential Element Characteristic_Figure 1
1.1 Differential element settings SLP1 Bias O87P Operate Value Stage1 Operate Value Stage2 Time Delay Stage 2 Operate Val.Alarmst. Time Delay Alarmst. 50% 0.4A 4A 10S 0.1A 5S NOTE: If setting is temporarily changed for simplified simulation testing, After testing it should be back to the origianl one
1.2 Calculation equation IRT1 =I01CF+I02CF+ +I0nCF IOP1 =I01CF + I02CF + + I0nCF 1.21 Manual Calculation 1. Take Point P for example 2. Please refer to 1.3 3. Supposing the following I1 = I2 = I4
P
0.8
1.2
I3 = 3I1 = 3I2 = 3I4 1.22 Supposing BUS I_Phase A differential fault 3I1 +I3=IRT= 1.2 3I1 - I3= IOP = 1.2 X 50% I1 = I2 = I4 = 0.3, I3 = 0.3 1.23 Repeat the above manual calculation for selecting more points, we can draw the line through these so many points.
I1 Diameter1_Q03
I2 Diameter2_Q03
I3 Diameter3_Q03
I4 Diameter4_Q03
NBE 132KV Busbar II Protection Test Sheet
P1
2 Testing Device CMC 256 to Cabinet Connection for Bus Differential Protection and 50BF Tripping Bus Zone
2.1 CMC 256 TO F11_DRS-C2BB, Single phase current injction to each Bay_Phase A CMC 256 CABLE TERMINALS DESCRIPTION Ia Yellow D1_Q03_Phase A X01:2 Ib Green D2_Q03_Phase A X01:8 Ic Red D3_Q03_Phase A X01:14 I'a Blue D4_Q03_Phase A X01:20 In Black X01:1 X01:7 Neutral Jumper X01:13 X01:19 BIA_1 BIA_2 OUT01 X02:201 X02:203 X01:113 IN01: Jumper X01:149 Feedback_Trip D1_Q03/C1 Repeat to other terminals for D2/D3/D4
Repeat to other terminals for D2/D3/D4, jumper these 2 terminals only for 50BF tripping bus Zone
2.2 CMC 256 TO F12_DRS-C2BB, Single phase current injction to each Bay_Phase B CMC 256 CABLE TERMINALS DESCRIPTION Ia Yellow D1_Q03_Phase B X01:4 Ib Green D2_Q03_Phase B X01:10 Ic Red D3_Q03_Phase B X01:16 I'a Blue D4_Q03_Phase B X01:22 In Black X01:3 X01:9 Neutral Jumper X01:15 X01:21 BIA_1 BIA_2 OUT03 X02:209 X02:211 X01:114 X01:158 Feedback_Trip D2_Q03/C1 50BF Initiates D02_Q03 Repeat to other terminals for D1/D3/D4 Repeat to other terminals for D1/D3/D4, jumper these 2 terminals only for 50BF tripping bus Zone
IN02: Jumper
P2
2.3 CMC 256 TO F13_DRS-C2BB, Single phase current injction to each Bay_Phase C CMC 256 CABLE TERMINALS DESCRIPTION Ia Yellow D1_Q03_Phase C X01:6 Ib Green D2_Q03_Phase C X01:12 Ic Red D3_Q03_Phase C X01:18 I'a Blue D4_Q03_Phase C X01:24 In Black X01:5 X01:11 Neutral Jumper X01:17 X01:23 BIA_1 BIA_2 OUT05 X02:217 X02:219 X01:116 X01:168 Feedback_Trip D3_Q03/C1 Repeat to other terminals for D1/D2/D4
IN04: Jumper
Repeat to other terminals for D1/D2/D4, jumper these 2 terminals only for 50BF tripping bus Zone
t=0.0167s (1.3 Pick) Selecting more points to test function operation and draw the line through these points to form the characteristics 3.2 Simulating Bus II Phase B differential element operation, F12_DRS-C2BB Manual calculation operation test P1: I1=I2=I4=0.30 0, I3=0.3 180
Ic Current fixed, change the other ones(Ia, Ib, I'a) simutaneousely Bus II Phase B DIF Pick-up value / A Ia Ib Ic
0.31 0.45
0 0
0.31 0.45
0 0
0.3 0.3
180 180
0.31 0.45
0 0
I'a
t=0.0167s (1.3 Pick) Selecting more points to test function operation and draw the line through these points to form the characteristics
0.31 0.45
0 0
0.31 0.45
0 0
0.3 0.3
180 180
0.31 0.45
P3
0 0
t=0.0167s (1.3 Pick) Selecting more points to test function operation and draw the line through these points to form the characteristics 4 50BF Tripping Bus Zone Testing_F11/F12/F13_DRS-C2BB
4.1 Simulating Bus II Phase A 50BF Tripping Bus Zone Operation, F11_DRS-C2BB 50BF Tripping Bus Zone: D1-D4_Q03-C1/C2 50BF initiates DRS-C2BB OUT1 OUT2 OUT3 OUT4 OUT5 IN01: Jumper or from F14 operation IN02: Jumper or from F15 operation IN04: Jumper or from F16 operation IN05: Jumper or from F17 operation Time Testing t= 0.023S 0.023S 0.023S 0.023S 0.023S 4.2 Simulating Bus II Phase B 50BF Tripping Bus Zone Operation, F12_DRS-C2BB 50BF Tripping Bus Zone: D1-D4_Q03-C1/C2 50BF initiates DRS-C2BB OUT1 OUT2 OUT3 OUT4 OUT5 IN01: Jumper or from F14 operation IN02: Jumper or from F15 operation IN04: Jumper or from F16 operation IN05: Jumper or from F17 operation Time Testing t= 0.023S 0.023S 0.023S 0.023S 0.023S 4.3 Simulating Bus II Phase C 50BF Tripping Bus Zone Operation, F13_DRS-C2BB 50BF Tripping Bus Zone: D1-D4_Q03-C1/C2 50BF initiates DRS-C2BB OUT1 OUT2 OUT3 OUT4 OUT5 IN01: Jumper or from F14 operation IN02: Jumper or from F15 operation IN04: Jumper or from F16 operation IN05: Jumper or from F17 operation Time Testing t= 0.023S 0.023S 0.023S 0.023S 0.023S
0.31 0.45
0 0
0.31 0.45
0 0
0.3 0.3
180 180
0.31 0.45
0 0
OUT6 0.023S
OUT7 0.023S
OUT8 0.023S
OUT6 0.023S
OUT7 0.023S
OUT8 0.023S
OUT6 0.023S
OUT7 0.023S
OUT8 0.023S
P4
5 Testing Device CMC 256 to Cabinet Connection for 50BF Testing to Each Feeder
5.1 CMC 256 TO F14_DRS-LA4, Single phase current injction to feeder D1_Q03 CMC 256 CABLE TERMINALS DESCRIPTION Ia Yellow D1_Q03_Phase A X01:26 Ib Green D1_Q03_Phase B X01:28 Ic Red D1_Q03_Phase C X01:30 In Black X01:25 Neutral Jumper X01:27 X01:29 BIA_1 BIA_2 BIA_1 BIA_2 BIA_1 BIA_2 OUT03.1 K19: 11-14 K11: 31-34 X02:277 X02:279 X02:293 X02:295 X02:329 X02:331 X01:129 X01:173 Feedback_50BF Initiation D1_Q03/C1 Feedback_Re-Trip D1_Q03/C1 Feedback_50BF Trip D1_Q02/C1 50BF Start from bus or line protection
IN01: Jumper
5.2 CMC 256 TO F15_DRS-LA4, Single phase current injction to feeder D2_Q03 CMC 256 CABLE TERMINALS DESCRIPTION Ia Yellow D2_Q03_Phase A X01:32 Ib Green D2_Q03_Phase B X01:34 Ic Red D2_Q03_Phase C X01:36 In Black X01:31 Neutral Jumper X01:33 X01:35 BIA_1 BIA_2 BIA_1 BIA_2 BIA_1 BIA_2 OUT03.1 K20: 11-14 K13: 31-34 X02:281 X02:283 X02:301 X02:303 X02:341 X02:343 X01:134 X01:178 Feedback_50BF Initiation D2_Q03/C1 Feedback_Re-Trip D2_Q03/C1 Feedback_50BF Trip D2_Q02/C1 50BF Start from bus or line protection
IN01: Jumper
P5
5.3 CMC 256 TO F16_DRS-LA4, Single phase current injction to feeder D3_Q03 CMC 256 CABLE TERMINALS DESCRIPTION Ia Yellow D3_Q03_Phase A X01:38 Ib Green D3_Q03_Phase B X01:40 Ic Red D3_Q03_Phase C X01:42 In Black X01:37 Neutral Jumper X01:39 X01:41 BIA_1 BIA_2 BIA_1 BIA_2 BIA_1 BIA_2 OUT03.1 K21: 11-14 K15: 31-34 X02:285 X02:287 X02:309 X02:311 X02:353 X02:355 X01:139 X01:183 Feedback_50BF Initiation D3_Q03/C1 Feedback_Re-Trip D3_Q03/C1 Feedback_50BF Trip D3_Q02/C1 50BF Start from bus or line protection
IN01: Jumper
5.4 CMC 256 TO F17_DRS-LA4, Single phase current injction to feeder D4_Q03 CMC 256 CABLE TERMINALS DESCRIPTION Ia Yellow D4_Q03_Phase A X01:44 Ib Green D4_Q03_Phase B X01:46 Ic Red D4_Q03_Phase C X01:48 In Black X01:43 Neutral Jumper X01:45 X01:47 BIA_1 BIA_2 BIA_1 BIA_2 BIA_1 BIA_2 OUT03.1 K22: 11-14 K17: 31-34 X02:289 X02:291 X02:317 X02:319 X02:365 X02:367 X01:144 X01:188 Feedback_50BF Initiation D4_Q03/C1 Feedback_Re-Trip D4_Q03/C1 Feedback_50BF Trip D4_Q02/C1 50BF Start from bus or line protection
IN01: Jumper
P6
6.2 Using jumper to connect terminals: X01: 129, X01: 173, simulating F14_Q01 50BF start signal (IN01) Using jumper to connect terminals: X01: 134, X01: 178, simulating F15_Q01 50BF start signal (IN01) Using jumper to connect terminals: X01: 139, X01: 183, simulating F16_Q01 50BF start signal (IN01) Using jumper to connect terminals: X01: 144, X01: 188, simulating F17_Q01 50BF start signal (IN01) 6.3 Using single phase current injection to simulat fault current, repeat to other phases and other bays. F14_D1_Q03 50BF element Ia Ib Setting value / A 0.4 0.4 0 -120 Pick-up value / A 0.41 0.41 0 -120
Ic
0.65 0.65
Ia
0 3 0 0 0 3
Ia
0.65 0.65
Ib
0 0 0 3 0 0 0 3
P7
P8
F11/F12/F13_DRS-C2BB 5 IN04=1, than move next 6 OUT01=OUT02=OUT03=OUT04=OUT05=OUT06=OUT07=OUT08=1, then D1_Q03="Off" AND D2_Q03="Off" AND D3_Q03="Off" AND D4_Q03="Off" OUT018=OUT19=OUT20=OUT21=1, then Lockout trip: D1_Q03 AND D2_Q03 AND D3_Q03 AND D4_Q03 7 Fault is cleared, all outputs and signals are reset to Zero. 7.4 D4_Q03 50BF Sequence Analysis F17_DRS-LA4 1 IN01=1, AND I >"I> CBF" 2 If T> "t1", then OUT01=1, K22 Operate, D1_Q03= "Off" or " On" If D4_Q03= "Off", then its over 3 If D4_Q03= "On", then move next step 4 If T> "t2-t1", then OUT03.1=1 AND OUT02=1, K17/K18 Operate, D4_Q02= "Off" F11/F12/F13_DRS-C2BB 5 IN05=1, than move next 6 OUT01=OUT02=OUT03=OUT04=OUT05=OUT06=OUT07=OUT08=1, then D1_Q03="Off" AND D2_Q03="Off" AND D3_Q03="Off" AND D4_Q03="Off" OUT018=OUT19=OUT20=OUT21=1, then Lockout trip: D1_Q03 AND D2_Q03 AND D3_Q03 AND D4_Q03 7 Fault is cleared, all outputs and signals are reset to Zero.
P9