Beruflich Dokumente
Kultur Dokumente
IJA Series
Fan
Double flanged casing is produced in mild steel or
galvanised Steel.
Impeller is made of PPG, PAG or Aluminum with
manually adjustable pitch blades.
C
L
Silencer
Outer casing made of galvanized steel sheet and
inner casing made of galvanized steel perforated
sheet.
Dimensions
Model
IJA 315
315
415
355
1125
IJA 355
355
455
355
1225
IJA 400
410
510
450
1394
IJA 450
460
560
450
1510
All Dimensions in mm.
Technical Data
Model
IJA 315
IJA 355
IJA 400
IJA 450
Flow Rate
m3/h
2250
4500
3240
6480
4500
9000
6000
12000
Outlet Velocity
m/s
8.0
16.0
9.1
18.2
10.0
20.0
10.5
21.0
Installed Power
kW
0.11
0.75
0.2
1.5
0.6
3.6
0.6
3.6
Phase
Hz
Voltage
3
3
3
3
3
3
3
3
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
400/380
400/380
400/380
400/380
400/380
400/380
400/380
400/380
dB(A) at
3m
38/38
54/54
43/42
58/58
44/46
60/62
46/47
62/62
RPM
1450/1750
2850/3450
1450/1750
2850/3450
1450/1750
2850/3450
1450/1750
2850/3450
Accessories
Hanger
Mounting Feet
2 x 10
2 x 10
C
D
A
B
Dimensions
Mounting Feet
Hanger
Model
A
Wt/set (kg)
Wt/set (kg)
IJA 315
265
315
25
50
209
355
263
2.2
IJA 355
290
355
25
50
237
395
263
2.2
IJA 400
304
400
25
50
265
2.5
440
263
2.2
IJA 450
375
450
25
50
288
490
288
2.4
IJA Series
IJA315
IJA355
IJA400
IJA450
10
12
14
16
18
20
22
24
0.85
1.70
2.55
3.40
4.25
5.10
5.95
6.80
7.65
8.50
9.35
10.20
IJA 315
5.62
3.47
2.42
1.86
1.51
1.27
1.09
0.91
0.73
0.55
0.37
0.25
IJA 355
6.42
4.35
3.05
2.35
1.91
1.61
1.39
1.22
1.09
0.96
0.83
0.70
IJA 400
7.41
5.26
3.72
2.87
2.33
1.97
1.70
1.50
1.34
1.21
1.10
1.01
IJA 450
7.82
5.73
4.37
3.36
2.74
2.32
1.77
1.58
1.43
1.3
1.2
26
28
30
32
34
36
38
40
42
44
46
48
11.05
11.90
12.75
13.60
14.45
15.30
16.15
17.00
17.85
18.70
19.56
20.41
IJA 315
IJA 355
0.57
0.44
0.24
IJA 400
0.94
0.84
0.74
0.64
0.54
0.44
0.26
IJA 450
1.11
1.03
0.97
0.91
0.85
0.81
0.77
0.67
0.57
0.47
0.37
0.27
Center Line
Velocity (m/s)
Center Line
Velocity (m/s)
TESTING
Tested by Warrington Fire Research which is UKs
largest independent specialist in fire safety testing,
consultancy and research.
IJA series were tested in accordance with BS7346 Part
2: 1990 and satisfied the performance criteria for Class
B as defined in BS standard.
Class
Temperature
(C)
Duration
(hrs)
150
5.0
250
2.0
300
0.5
300
1.0
400
2.0
600
1.5
650
1.0
840