User manual Energy meter for single, two, and three-phase networks
2011-05-19
UM EN EEM-MA600 00
This user manual is valid for: Designation EEM-MA600 Revision Order No. 2901366
104413_en_00
PHOENIX CONTACT
EEM-MA600
PHOENIX CONTACT
104413_en_00
General terms and conditions of use for technical documentation Phoenix Contact reserves the right to alter, correct, and/or improve the technical documentation and the products described in the technical documentation at its own discretion and without giving prior notice, insofar as this is reasonable for the user. The same applies to any technical changes that serve the purpose of technical progress. The receipt of technical documentation (in particular data sheets, installation instructions, manuals, etc.) does not constitute any further duty on the part of Phoenix Contact to furnish information on alterations to products and/or technical documentation. Any other agreement shall only apply if expressly confirmed in writing by Phoenix Contact. Please note that the supplied documentation is product-specific documentation only and that you are responsible for checking the suitability and intended use of the products in your specific application, in particular with regard to observing the applicable standards and regulations. Although Phoenix Contact makes every effort to ensure that the information and content are accurate, up-to-date, and state-of-the-art, technical inaccuracies and/or printing errors in the information cannot be ruled out. Phoenix Contact does not offer any guarantees as to the reliability, accuracy or completeness of the information. All information made available in the technical data is supplied without any accompanying guarantee, whether expressly mentioned, implied or tacitly assumed. This information does not include any guarantees regarding quality, does not describe any fair marketable quality, and does not make any claims as to quality guarantees or guarantees regarding the suitability for a special purpose. Phoenix Contact accepts no liability or responsibility for errors or omissions in the content of the technical documentation (in particular data sheets, installation instructions, manuals, etc.). The aforementioned limitations of liability and exemptions from liability do not apply, in so far as liability must be assumed, e.g., according to product liability law, in cases of premeditation, gross negligence, on account of loss of life, physical injury or damage to health or on account of the violation of important contractual obligations. Claims for damages for the violation of important contractual obligations are, however, limited to contract-typical, predictable damages, provided there is no premeditation or gross negligence, or that liability is assumed on account of loss of life, physical injury or damage to health. This ruling does not imply a change in the burden of proof to the detriment of the user.
104413_en_00
PHOENIX CONTACT
EEM-MA600 Statement of legal authority This manual, including all illustrations contained herein, is copyright protected. Use of this manual by any third party is forbidden. Reproduction, translation, and public disclosure, as well as electronic and photographic archiving and modification, require written consent by Phoenix Contact. Violators are liable for damages. Phoenix Contact reserves all rights in the case of patent award or listing of a registered design. Third-party products are always named without reference to patent rights. The existence of such rights shall not be excluded. How to contact us Internet Up-to-date information on Phoenix Contact products and our Terms and Conditions can be found on the Internet at: www.phoenixcontact.com. Make sure you always use the latest documentation. It can be downloaded at: www.phoenixcontact.net/catalog. Subsidiaries If there are any problems that cannot be solved using the documentation, please contact your Phoenix Contact subsidiary. Subsidiary contact information is available at www.phoenixcontact.com.
Published by PHOENIX CONTACT GmbH & Co. KG Flachsmarktstrae 8 32825 Blomberg DEUTSCHLAND Telefon +49 - (0) 52 35 - 3-00 Telefax +49 - (0) 52 35 - 3-4 12 00 Should you have any suggestions or recommendations for improvement to the contents and layout of our manuals, please send your comments to: tecdoc@phoenixcontact.com
PHOENIX CONTACT
104413_en_00
Table of contents
1 2 Safety notes ............................................................................................................................1-1 Device description ..................................................................................................................2-1
2.1 2.2 2.3 Displaying measured values............................................................................... 2-2 Characteristics.................................................................................................... 2-4 Extension modules ............................................................................................. 2-5 2.3.1 Communication modules ....................................................................2-5 2.3.2 Special function modules ....................................................................2-5
3 4
4.5
Configuration ..........................................................................................................................5-1
5.1 5.2 5.3 5.4 Configuration mode (PROG) COdE 100 .......................................................... 5-3 Example: configuring the device for a three-phase network with an asymmetrical load .................................................5-4 Current transformers .......................................................................................... 5-5 Voltage transducer ............................................................................................. 5-6 5.4.1 Voltage transducer primary side .........................................................5-7 5.4.2 Voltage transducer secondary side ..................................................... 5-8 Measuring time of the currents ........................................................................... 5-9 Measuring time of voltages............................................................................... 5-10 Frequency measuring time ............................................................................... 5-11 Power measuring time ......................................................................................5-12 Reset ................................................................................................................ 5-13 Configuring the LCD .........................................................................................5-14 Operating hours counter...................................................................................5-15 Changing the configuration mode access code................................................ 5-16
104413_en_00
PHOENIX CONTACT
EEM-MA600 5.13 5.14 Displaying the software version and serial number.................................................. 5-17 Exiting configuration mode ............................................................................... 5-17
7.2
8 9
10.2
ii
PHOENIX CONTACT
104413_en_00
Table of contents 10.2.5 10.2.6 10.2.7 10.3 Access to MODBUS register ...........................................................10-18 "Read" and "Write" function ............................................................ 10-18 Web server ..................................................................................... 10-18
PROFIBUS .....................................................................................................10-19 10.3.1 Basics .............................................................................................10-19 10.3.2 Connecting and installing communication modules EEM-PB-MA600 and EEM-PB12-MA600 .......................................10-19 10.3.3 Configuring communication modules EEM-PB-MA600 and EEM-PB12-MA600 .......................................10-20 10.3.4 PROFIBUS register tables ..............................................................10-23 10.3.5 Starting a PROFIBUS configuration ................................................10-23
12.10 Module 9 "Specific Data" ................................................................................ 12-18 12.10.1 Configuration of the outputs ............................................................ 12-18 12.10.2 User-defined table .......................................................................... 12-21 12.11 Module 10 (not available) ...............................................................................12-27 12.12 Module 11 "Specific short data"......................................................................12-28 12.13 Diagnostics.....................................................................................................12-29
13 Technical data ......................................................................................................................13-1 A B Specifications according to IEC 61557-12 .............................................................................. A-1 Abbreviations.......................................................................................................................... B-1
104413_en_00
PHOENIX CONTACT
iii
EEM-MA600
Safety notes
DANGER: Risk of electric shocks, burns or explosions The "attention symbol" on the device label means: Carefully read through the installation note. Follow the installation note to avoid impairing the intended protection. Only qualified specialist personnel may install, start up, and operate the device. Observe the national safety and accident prevention regulations. When working on the device, always disconnect it from the power supply. Short circuit the secondary side of each current transformer. Use an appropriate voltage measuring device to ensure that no voltage is present. Mount all equipment, doors, and covers before switching on the device again. Installation should be carried out following the instructions provided in the operating instructions. Access to circuits within the device is not permitted. The device does not require maintenance. Repairs may only be carried out by the manufacturer.
NOTE: Risk of damage to the device Provide a switch/circuit breaker close to a device, which is labeled as the disconnect device for this device. Provide overcurrent protection (I 16 A) in the installation. Observe the maximum permissible values for the device supply (440 V AC/420 V DC), mains frequency (50/60 Hz), maximum voltage at connection terminal blocks (700 V AC phase/phase or 404 V AC phase/neutral conductor). Observe a maximum current of 10 A at the power supply connection terminal blocks (I1, I2, and I3).
1-1
PHOENIX CONTACT
104413_en_00
Device description
Device description
The EEM-MA600 is a highly accurate energy meter for measuring electrical parameters in low voltage installations up to 700 V. It is designed for front-panel installation and supports the measurement, counting, and display of all electrical parameters in 1-, 2, and 3-phase networks with and without neutral conductors (symmetrical and asymmetrical). The buttons located on the front of the device allow fast, direct access to the required parameters as well as device configuration. The device can be expanded using the special function and communication modules and can be configured using communication modules (Ethernet, PROFIBUS, MODBUS, see page 2-5). The device can also be used to record the total harmonic distortion (THD) of the currents and voltages as well as the content of individual harmonic (odd) vibrations. Values up to the 25thharmonic can be shown on the display. The display up to the 63rdharmonic is possible via the MODBUS registers. A trend calculation can be performed for the real and reactive power, and alarm management can be activated (extension module EEM-2DIO-MA600 required). The following parameters can be measured or monitored:
Current
Actual values I1, I2, I3, IN Average value/maximum value I1, I2, I3, IN Harmonic content and content of individual odd harmonics (displays up to 25th) Actual phase/phase value (U12, U23, U31) Actual phase/N value (V1, V2, V3) Average value/maximum value for phase/phase (U12, U23, U31) and phase/N (V1, V2, V3) Harmonic content and content of individual odd harmonics (displays up to 25th) F Actual value for each phase (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3) Total actual value (P, Q, S) Average value/maximum value (P, Q, S) Trend (PPR, QPR, SPR) Actual value for each phase (PF1, PF2, PF3) Total actual value (PF) Average value/maximum value (PF) Real energy (EA +/-) Reactive energy (ER +/-) Apparent energy (ES)
Voltages
Power factor
104413_en_00
PHOENIX CONTACT
2-1
EEM-MA600 Harmonics Total harmonic distortion of currents I1, I2, I3, IN Total harmonic distortion of line voltage U12, U23, U31 Total harmonic distortion of line voltage against N V1, V2, V3 Individual harmonic content up to 63rd For currents I1, I2, I3 For line voltages (U12, U23, U31) For line voltages against N (V1, V2, V3) Internal External via 3 PT100 temperature sensors For all parameters (extension module EEM-2DIO-MA600 required)
Temperature
Alarm setting
2.1
To switch over to the next measured values within a menu, the corresponding button must be pressed once again. I/C button Currents (I1, I2, I3, IN), real energy (EA) Currents (I1, I2, I3, IN) average value (I), real energy (EA) Temperatures (when extension module EEM-TEMP-MA600 is connected) Line voltages (U12, U23, U31), frequency (F), real energy (EA) Line voltages against N (V1, V2, V3), frequency (F), real energy (EA) Line voltages (U12, U23, U31), average value (U), real energy (EA) Line voltages against N (V1, V2, V3), average value (V), real energy (EA) Real power for each phase (P1, P2, P3), total real power (P), real energy (EA) Reactive power for each phase (Q1, Q2, Q3), total reactive power (Q), real energy (EA) Apparent power for each phase (S1, S2, S3), total apparent power (S), real energy (EA) Power factor for each phase (PF1, PF2, PF3) total power factor (PF), real energy (EA) Real power trend (PPR) Reactive power trend (QPR) Apparent power trend (SPR)
U/F button
P/PF button
2-2
PHOENIX CONTACT
104413_en_00
Device description MAX/AVG button H button E button Average value/maximum value for currents (I1, I2, I3, IN), real energy (EA) Average value/maximum value for line voltages phase/phase (U12, U23, U31), average frequency value (F), real energy (EA) Average value/maximum value for line voltages phase/N (V1, V2, V3), average frequency value (F), real energy (EA) Average value/maximum real power value (P) Average value/maximum reactive power value (Q) Average value/maximum apparent power value (S) Total harmonic distortion of currents (THD I1, THD I2, THD I3, THD IN), real energy (EA) Total harmonic distortion of phase/phase (THD U12, THD U23, THD U31) conductor voltages, real energy (EA) Total harmonic distortion of phase/N (THD V1, THD V2, THD V3) conductor voltages, real energy (EA) Harmonic content for currents (I1, I2, I3, IN), real energy (EA) Harmonic content for conductor voltages L/L (U12, U23, U31), real energy (EA) Harmonic content for line voltages L/N (V1, V2, V3), real energy (EA) Positive real energy (EA +) Positive reactive energy (ER +) Apparent energy (ES) Negative real energy (EA-) Negative reactive energy (ER-) Operating hours
104413_en_00
PHOENIX CONTACT
2-3
EEM-MA600
2.2
Current measurement (TRMS)
Characteristics
9999 A 1 or 5 A 10 mA 0 ... 11 kA < 0.3 VA 1s 0.2% (10 ... 110% IN) 10 A 10 x IN for 1 s 18 ... 700 V AC 11 ... 404 V AC up to 500 kV 60, 100, 110, 115, 120, 173, 190 V AC 1s 0.2% (140 ... 700 V AC) 0 ... 8000 MW/Mvar/MVA 1s 0.5% (-90 ... +90C) 1s 0.5% (0.5 < LF < 1) 45 ... 65 Hz 1s 0.1% (45 ... 65 Hz) Class 0.5 S Class 2
Current transformer primary Current transformer secondary Minimum measured current Display Intrinsic consumption Measured value update Accuracy Continuous overload Short-term overload
Direct phase/phase Direct phase/N Voltage transducer primary Voltage transducer secondary Measured value update Accuracy Display Measured value update Accuracy Measured value update Accuracy Measuring range Measured value update Accuracy Real energy (IEC 62053-22) Reactive energy (IEC 62053-23)
Power measurement
2-4
PHOENIX CONTACT
104413_en_00
Device description
2.3
Extension modules
The device can be extended by means of extension modules. The extension modules are plugged into the back of the device and also secured in place with screws.
The description of the maximum number of individual extension modules and the slots to be used can be found at "Installation" on page 4-4.
2.3.1
Communication modules
To be able to adjust the device to various communication interfaces, the following communication modules are available: JBUS/MODBUS communication (EEM-RS 485-MA600, Order No. 2901367): Serial RS485 JBUS/MODBUS connection in RTU mode with a speed of up to 38,400 baud PROFIBUS-DP communication (EEM-PB-MA600, Order No. 2901368) Serial RS485 PROFIBUS DP connection with a speed of up to 1.5 MBd PROFIBUS-DP communication (EEM-PB12-MA600, Order No. 2901418): serial connection RS485 PROFIBUS with D-SUB connector and a speed of up to 12 MBd Ethernet communication (EEM-ETH-MA600, Order No. 2901373): 100 base-T connection (RJ45), MODBUS TCP protocol, integrated web server Ethernet communication (EEM-ETH-RS485-MA600, Order No. 2901374): MODBUS TCP (RJ45) Ethernet connection or JBUS/MODBUS RTU (RS485) via TCP (gateway function), to 247 JBUS/MODBUS slaves
2.3.2
The functional scope of the device can be extended with the following special function modules: Memory (EEM-MEMO-MA600, Order No. 2901370): Storage of the last 10 alarms with date and time Storage of the last undervoltages, surge voltages and voltage failures with date and time Storage of current minimum and maximum measured values for I, IN, U, V, F, PF, P, Q, S, THD U, THD V, THD I, THD IN Storage of real and reactive P+/- and Q+/- up to 62 days with an internal or external synchronization impulse for an adjustable measurement period of 5, 8, 10, 15, 20 and 30 minutes Storage of course of average values U, V, and F based on the measurement duration (maximum of 60 days) Digital inputs/outputs (EEM-2DIO-MA600, Order No. 2901371): Two switching outputs as alarm for voltage, currents, power, power factor, frequency and harmonic content Two inputs for counting the impulses or for position checking (for example, switch setting)
104413_en_00
PHOENIX CONTACT
2-5
EEM-MA600 Analog outputs (EEM-2AO-MA600, Order No. 2901374): Two analog outputs 4 20 mA or 0 20 mA can be set according to current, voltage, power and power factor Two modules with a maximum of four outputs can be installed Temperature inputs (EEM-TEMP-MA600, Order No. 2901949) Module for measuring temperature from up to three PT100 temperature sensors from -20C ... + 150C. The ambient temperature in the direct vicinity of the module can be acquired from -10C ... +55C.
2-6
PHOENIX CONTACT
104413_en_00
2 3 4 8 9 0
6 7 ! "
Figure 3-1 1.
Pushbuttons with dual functionality: Normal mode: display measured values Programming mode: change configuration 2. Backlit LCD 3. Display measured values in relevant conductor 4. Measured value 5. Unit 6. Current measurement as a % bar indicator 7. Frequency display 8. Alarm relay 1 (if installed) 9. Alarm relay 2 (if installed) 10. Energy display 11. Display of active communication (if optional communication module is installed) 12. Display for recording the real energy (flashes for every kWh)
104413_en_00
PHOENIX CONTACT
3-1
EEM-MA600
4.1
Cutout dimensions
45 0 6 0 8
Figure 4-1
Cutout dimensions
4-1
PHOENIX CONTACT
104413_en_00
4.2
Mounting
Figure 4-2
Mounting
To ensure that the device is securely placed on the front panel, the device must be pressed into the mounting slot from the front and then secured from behind using the four clamps provided. To mount the device, proceed as follows: 1. 2. 3. Press the device into the mounting slot from the front and hold it in this position. Secure the device from behind with the four clamps, as shown in Figure 4-2. Push the clamps as far as they will go onto the latch, until the device is securely positioned and the clamps snap into place.
104413_en_00
PHOENIX CONTACT
4-2
EEM-MA600
4.3
Pin assignment
s1 s2 s1 s2 s1 s2
I1
I2
I3
V1
V2
V3
VN
AUX
2 1
Figure 4-3 Pin assignment 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC Connection of measured currents: S1 (input) S2 (output) Connection of measured voltage
DANGER: Risk of electric shock When you disconnect the device, you must short-circuit the secondary side of the current transformer. A URTK6 (Order No. 3026272) transformer disconnect terminal block can be used.
4-3
PHOENIX CONTACT
104413_en_00
4.4
Installation
The device is intended for connection to various mains types in two, three or four wire mains networks with symmetrical or asymmetrical load. When measuring by means of transformers, the accuracy is greatly influenced by the quality of the transformers used.
4.4.1
When selecting the current transformer, the secondary nominal current must be 1 A or 5 A. The primary nominal current is determined by the current consumption of the load. Appropriate PACT current transformers can be found in the Phoenix Contact INTERFACE catalog. DANGER: Risk of electric shock Only install current transformers and corresponding measuring devices when the power supply is disconnected. Observe the order in which the current transformers are connected when wiring them (direction of current flow). Primary circuit: K-P1 -> L-P2; secondary circuit: k-S1 -> I-S2 When the current transformer is operated with an open secondary circuit, hazardous voltages may occur at the secondary terminal blocks.
4.4.2
Figure 4-4
Three-phase network with asymmetrical load (4NBL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC
104413_en_00
PHOENIX CONTACT
4-4
EEM-MA600
4.4.3
Figure 4-5
Figure 4-6
110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC
4-5
PHOENIX CONTACT
104413_en_00
Figure 4-7
110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC
The solution with two current transformers reduces the degree of accuracy of phases by 0.5%, whereby their current is calculated vectorially (without current transformer).
104413_en_00
PHOENIX CONTACT
4-6
EEM-MA600
4.4.4
Figure 4-8
Three-phase network with symmetrical load (3BL/4BL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC
The solution with a current transformer reduces the accuracy of phases by 0.5%, whereby their current is calculated vectorially (without current transformer).
4-7
PHOENIX CONTACT
104413_en_00
4.4.5
Figure 4-9
Two-phase network (2BL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC
4.4.6
Figure 4-10
Single-phase network (1BL) 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC
104413_en_00
PHOENIX CONTACT
4-8
EEM-MA600
4.4.7
Voltage transducer
AUX
Figure 4-11
Voltage transducer 110 400 V AC 10% at 50/60 Hz 120 350 V DC 20% 0.5 A gG/BS 88 2A gG/0.5 A class CC
4-9
PHOENIX CONTACT
104413_en_00
4.5
The extension modules are plugged into the back of the device and also secured in place with screws.
1 2 3 4
Figure 4-12
You can find information about configuring the communication and extension modules in Section "Communication modules" on page 10-1.
Installation overview Order No. 2901367 2901373 2901374 2901368 2901418 2901371 2901370 2901475 2901949 Max. number 1 1 1 1 1 3 1 2 1 Space requirements 1 slot 2 slots 2 slots 2 slots 2 slots 1 slot 1 slot 1 slot 1 slot No. slots 1 ... 4 1 ... 4 1 ... 4 1 ... 4 1 ... 4 1 ... 4 2 or 3 1 or 2 2 or 3
104413_en_00
PHOENIX CONTACT
4-10
EEM-MA600
Configuration
The device can be configured via pushbuttons. The configuration is described in the following subsections. To configure the EEM-MA600, press the gray buttons consecutively, as described in the respective example. The corresponding configuration menu is displayed for the extension/communication module used. You will find the necessary configuration settings in Section "Communication modules" on page 10-1.
Button PROG or or or OK
Description Open configuration mode (press and hold for 3 seconds) Select the next menu item Open edit mode In edit mode: select parameters/values to be changed In edit mode: change parameters/values Confirm setting
5-1
PHOENIX CONTACT
104413_en_00
Configuration
100 4NBL, 3NBL, 4BL, 3BL, 2BL , 1BL Set primary current Set secondary current Set value 1 A; 5A Set value
Voltage transformer: NO
YES
Primary side:
Secondary side:
20' min; 30' min; 60' min; 2' sec; 10' sec; 5' min; 8' min; 10' min; 15' min
20' min; 30' min; 60' min; 10' sec; 5' min; 8' min; 10' min; 15' min
Measuring time for frequency to calculate MAX and average values: Measuring time for power to calculate MAX and average values:
20' min; 30' min; 60' min; 10' sec; 5' min; 8' min; 10' min; 15' min
20' min; 30' min; 60' min; 10' sec; 5' min; 8' min; 10' min; 15' min
MAX4I: Maximal value of the currents MAXU: Maximal value of the conductor voltages (1-2 / 2-3 / 3-1) MAXV: Maximal value of the conductor voltages against N (1 / 2 / 3) MAXF: Maximal value of the frequncy MAXP+: Maximal value of positive real power MAXP-: Maximal value of negative real power MAXQ+: Maximal value of positive reactive power MAXQ-: Maximal value of negative reactive power MAXS: Maximal value of appearent power HOUR: Operating hours counter EA+: Positive active energy (+kWh) ER+: Positive reactive power (+kVArh) ES: Appearent power (-kVAh) EA-: Negative active energy (+kWh) ER-: Negative reactive power (+kVArh)
Yes; No
LCD display:
AUX: illuminated, if supply voltage is available I: illuminated, if current is being measured U: illuminated, if voltage is being measured for AUX: Illumination goes out automatically after 2 minutes. The display is illuminated again after pressing any key.
AUX: activated, if supply voltage is available I: activated, if threshold value is set (input current) U: activated, if threshold value is set (input voltage) E1: activated, if digital input 1 is connected E2: activated, if digital input 2 is connected E3: activated, if digital input 3 is connected E4: activated, if digital input 4 is connected E5: activated, if digital input 5 is connected E6: activated, if digital input 6 is connected Threshold value: I/U Set value
Access code:
Set value Press until you reach menu item Ser l : serial number is displayed Press until you reach menu item SOFt: software version is displayed
Serial number:
Software version:
Figure 5-1
Flowchart
104413_en_00
PHOENIX CONTACT
5-2
EEM-MA600
5.1
Once the appropriate setting has been made and confirmed by pressing "OK", the next menu item is called automatically. To switch to configuration mode, press and hold the "PROG" button for a minimum of 3 seconds. Follow the instructions and enter "Code 100". Confirm with "OK".
I C
U F
P PF MAX AVG
1x 3 seconds
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-2
5-3
PHOENIX CONTACT
104413_en_00
Configuration
5.2
Example: configuring the device for a three-phase network with an asymmetrical load
NET = 3NBL
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x 6x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-3
104413_en_00
PHOENIX CONTACT
5-4
EEM-MA600
5.3
Current transformers
Enter the ratio of the current transformers used as shown in the following example. Example: transformer ratio CT = 1500/5A
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-4
5-5
PHOENIX CONTACT
104413_en_00
Configuration
5.4
Voltage transducer
Select whether the connection is to be established via voltage transducers. Example: connection via voltage transducers (YES/NO) Vt = YES
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-5
104413_en_00
PHOENIX CONTACT
5-6
EEM-MA600
5.4.1
Set the primary side voltage as shown in the following example. Example: primary side voltage = 20,000 V PR = 20,000
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-6
5-7
PHOENIX CONTACT
104413_en_00
Configuration
5.4.2
Set the secondary side voltage as shown in the following example. Example: secondary side voltage 110 V SE = 110
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x 6x 7x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-7
104413_en_00
PHOENIX CONTACT
5-8
EEM-MA600
5.5
This value specifies over which period the currents are to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME 4I = 20
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x 6x 7x 8x 9x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-8
5-9
PHOENIX CONTACT
104413_en_00
Configuration
5.6
This value specifies over which period the voltages are to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME U/V = 20
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x 6x 7x 8x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-9
104413_en_00
PHOENIX CONTACT
5-10
EEM-MA600
5.7
This value specifies over which period the frequency is to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME F = 20
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x 6x 7x 8x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-10
5-11
PHOENIX CONTACT
104413_en_00
Configuration
5.8
This value specifies over which period the power is to be measured for determining the average and maximum values. Example: measuring time of 20 minutes tIME P/Q/S = 20
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x 6x 7x 8x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-11
104413_en_00
PHOENIX CONTACT
5-12
EEM-MA600
5.9
Reset
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
0 x MAX4I maximum current value 1 x MAX U maximum conductor voltage value (1-2 / 2-3 / 3-1) 2 x MAX V maximum value of conductor voltages against N (1 / 2 / 3) 3 x MAX F maximum frequency value 4 x MAX P+ maximum positive real power value 5 x MAX P- maximum negative real power value 6 x MAX Q+ maximum positive reactive power value 7 x MAX Q- maximum negative reactive power value 8 x MAX S maximum apparent power value 9 x HOUR operating hours counter
10 x 11 x 12 x 13 x 14 x 16 x 17 x 18 x 19 x 20 x 21 x
*
EA+ positive real power (+kWh) ER+ positive reactive energy (+kVArh) ES apparent energy (-kVAh) EA- negative real energy (+kWh) ER- negative reactive energy (+kVArh) E1 digital input 1* E2 digital input 2* E3 digital input 3* E4 digital input 4* E5 digital input 5* E6 digital input 6*
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-12
5-13
PHOENIX CONTACT
104413_en_00
Configuration
5.10
The LCD lighting can be configured in various ways. Configuration options The display is illuminated if: Supply voltage is applied (AUX) Current is measured (I) Voltage is measured (U) For the AUX option (supply voltage is applied) , the display automatically goes out after 2 minutes. Press any button to illuminate the display again. Example: the display is illuminated if supply voltage is applied bACLIT = AUX
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-13
104413_en_00
PHOENIX CONTACT
5-14
EEM-MA600
5.11
Example: operating hours counter depending on the current flow. The counter is activated if the current is greater than 1000 A.
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
0x 1x 2x 3x 4x
*
AUX supply voltage I input current U input voltage E1 digital input 1* E2 digital input 2*
5x 6x 7x 8x
I C
U F
P PF MAX AVG
1x Confirm
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-14
5-15
PHOENIX CONTACT
104413_en_00
Configuration
5.12
In order to change the configuration mode access code, proceed as follows: Example: COdE = 200
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 5-15
104413_en_00
PHOENIX CONTACT
5-16
EEM-MA600
5.13
I C
U F
P PF MAX AVG
1 x SOFt 2 x SEr2 3 x SEr1
Figure 5-16
5.14
Exit configuration mode by pressing and holding the "PROG" button for at least 3 seconds.
I C
U F
P PF MAX AVG
1x 3 seconds
Figure 5-17
5-17
PHOENIX CONTACT
104413_en_00
Press the following pushbuttons to display the desired measured values: Table 6-1 Pushbutton
I C
Pushbutton functions in operating mode Displays... Currents, temperatures (with extension module EEM-TEMP-MA600)
U F
Voltages, frequency
P PF
Energy, operating hours, Date and time (with expansion module EEM-MEMO-MA600) Measured values via pulse input (with function module EEM-2DIO-MA600)
By pressing the appropriate pushbutton several times, further measured values can be displayed within the selected menu (see also "Displaying measured values" on page 2-2). The figures in the following subsections explain the various measured value displays by means of pressing the pushbuttons several times.
104413_en_00
PHOENIX CONTACT
6-1
EEM-MA600
6.1
Press button:
I C
1x
EMpro
Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Real energy (EA)
I C
U F
P PF MAX AVG
2x
EMpro
Currents in conductors (I1, I2, I3) ISYS average current value (I1 + I2 + I3) / 3 Real energy (EA)
I C
U F
P PF MAX AVG
3x
EMpro
I C
U F
P PF MAX AVG
6-2
PHOENIX CONTACT
104413_en_00
6.2
Press button:
U F
1x
EMpro
Phase/phase conductor voltages (U12 + U23 + U31) Frequency (F) Real energy (EA)
I C
U F
P PF MAX AVG
2x
EMpro
Phase/N conductor voltages (V1, V2, V3) Frequency (F) Real energy (EA)
I C
U F
P PF MAX AVG
3x
EMpro
Phase/N conductor voltages (V1, V2, V3) USYS average conductor voltage value (U12 + U23 + U31)/3 Real energy (EA)
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-3
EEM-MA600
4x
EMpro
Phase/N conductor voltages (V1, V2, V3) Phase/N VSYS average conductor voltage value (V1 + V2 + V3)/3 Real energy (EA)
I C
U F
P PF MAX AVG
6-4
PHOENIX CONTACT
104413_en_00
6.3
Press button:
P PF
1x
EMpro
Real power per phase (P1, P2, P3) Total real power (P) Real energy (EA)
I C
U F
P PF MAX AVG
2x
EMpro
Reactive power per phase (Q1, Q2, Q3) Total reactive power (Q) Real energy (EA)
I C
U F
P PF MAX AVG
3x
EMpro
Apparent power per phase (S1, S2, S3) Total apparent power (S) Real energy (EA)
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-5
EEM-MA600
4x
EMpro
Power factor per phase (PF1, PF2, PF3) Total power factor (PF) Real energy (EA)
= inductive = capacitive
I C
U F
P PF MAX AVG
5x
EMpro
I C
U F
P PF MAX AVG
6x
EMpro
I C
U F
P PF MAX AVG
7x
EMpro
I C
U F
P PF MAX AVG
6-6
PHOENIX CONTACT
104413_en_00
6.4
Press button:
MAX AVG
1x
EMpro
Maximum current value (I1, I2, I3, IN) Real energy (EA)
I C
U F
P PF MAX AVG
2x
EMpro
Maximum phase/phase (U12, U23, U31) conductor voltage value Maximum frequency (F) value Real energy (EA)
I C
U F
P PF MAX AVG
3x
EMpro
Maximum phase/N conductor voltage value (V1 + V2 + V3) Maximum frequency (F) value Real energy (EA)
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-7
EEM-MA600
4x
EMpro
I C
U F
P PF MAX AVG
5x
EMpro
I C
U F
P PF MAX AVG
6x
EMpro
I C
U F
P PF MAX AVG
7x
EMpro
Average current (I1, I2, I3, IN) value Real energy (EA)
I C
U F
P PF MAX AVG
6-8
PHOENIX CONTACT
104413_en_00
8x
EMpro
Average phase/phase conductor voltage (U12 + U23 + U31) value Average frequency value (F) Real energy (EA)
I C
U F
P PF MAX AVG
9x
EMpro
Average phase/N conductor voltage (V1, V2, V3) value Average frequency value (F) Real energy (EA)
I C
U F
P PF MAX AVG
10 x
EMpro
I C
U F
P PF MAX AVG
11 x
EMpro
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-9
EEM-MA600
12 x
EMpro
I C
U F
P PF MAX AVG
6-10
PHOENIX CONTACT
104413_en_00
6.5
By pressing the "H" button, the following values are displayed: 1 touch: 2 touches: 3 touches: 4 touches: 5...15 touches: 16 touches: 17...27 touches: 28 touches: 29...39 touches: THDI: total harmonic distortion of currents (THD I1, THD I2, THD I3, THD IN), real energy (EA) Total harmonic distortion of phase/phase (THD U12, THD U23, THD U31) conductor voltages, real energy (EA) Total harmonic distortion of phase/N (THD V1, THD V2, THD V3) conductor voltages, real energy (EA) Content of 3rd harmonic for current (I1, I2, I3, IN), real energy (EA) Content of 5th - 25th harmonic for currents (I1, I2, I3, IN), real energy (EA) Content of 3rd harmonic for conductive voltages (U12, U23, U31), real energy (EA) Content of 5th - 25th harmonic for conductor voltages L/L (U12, U23, U31), real energy (EA) Content of 3rd harmonic for conductor voltages phase/N (V1, V2, V3), real energy (EA) Content of 5th - 25th harmonic of phase/N (V1, V2, V3) conductor voltages, real energy (EA)
Press button:
H
1x
EMpro
Total harmonic distortion of currents (THD I1, THD I2, THD I3, THD IN) Real energy (EA)
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-11
EEM-MA600
2x
EMpro
Total harmonic distortion of phase/phase (THD U12, THD U23, THD U31) conductor voltages, Real energy (EA)
I C
U F
P PF MAX AVG
3x
EMpro
Total harmonic distortion of phase/N (THD V1, THD V2, THD V3) conductor voltages Real energy (EA)
I C
U F
P PF MAX AVG
4x
EMpro
Content of 3rd harmonic for currents (I1, I2, I3, IN) Real energy (EA)
I C
U F
P PF MAX AVG
18 x
EMpro
Content of 7th harmonic of L/L (U12, U23, U31) conductor voltages Real energy (EA)
I C
U F
P PF MAX AVG
6-12
PHOENIX CONTACT
104413_en_00
31 x
EMpro
Content of 9th harmonic for phase/N (V1, V2, V3) conductor voltages Real energy (EA)
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-13
EEM-MA600
6.6
Press button:
E
1x
EMpro
Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Absorbed (positive) real energy (EA+)
I C
U F
P PF MAX AVG
2x
EMpro
Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Absorbed (positive) reactive energy
I C
U F
P PF MAX AVG
3x
EMpro
Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Apparent energy
I C
U F
P PF MAX AVG
6-14
PHOENIX CONTACT
104413_en_00
4x
EMpro
Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Supplied (negative) real energy (EA-)
I C
U F
P PF MAX AVG
5x
EMpro
Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Supplied (negative) reactive energy (ER-)
I C
U F
P PF MAX AVG
6x
EMpro
Currents in conductors (I1, I2, I3) Current in neutral conductor (IN) Operating hours
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-15
EEM-MA600
6.7
Press button:
E
The display is only possible when the EEM-MEMO-MA600 storage module is connected.
7x
EMpro
Date
I C
U F
P PF MAX AVG
8x
EMpro
Time
I C
U F
P PF MAX AVG
6-16
PHOENIX CONTACT
104413_en_00
6.8
Press button:
E
You can display the counter pulses of the connected pulse input by pressing the E key several times. The display is only possible when function module EEM-2DIO-MA600 is connected. E 3, E 4 can be displayed when two EEM-2DIO-MA600 function modules are connected. E 5, E 6 can be displayed when three EEM-2DIO-MA600 function modules are connected.
1x
EMpro
Counter pulses E1
I C
U F
P PF MAX AVG
2x
EMpro
Counter pulses E2
I C
U F
P PF MAX AVG
3x
EMpro
Counter pulses E3
I C
U F
P PF MAX AVG
104413_en_00
PHOENIX CONTACT
6-17
EEM-MA600
4x
EMpro
Counter pulses E4
I C
U F
P PF MAX AVG
5x
EMpro
Counter pulses E5
I C
U F
P PF MAX AVG
6x
EMpro
Counter pulses E6
I C
U F
P PF MAX AVG
6-18
PHOENIX CONTACT
104413_en_00
Function test
Function test
To perform the function test, the device must be connected and ready for operation. The power factor (PF) of the system must be between 0.6 > PF < 1. If the power factor is not within this range, this function cannot be used. The connections (without neutral conductors) are checked using the setting 4 BL/3 BL/2BL/1 BL. All connections (with neutral conductors) are checked using the 4 NBL and 3 NBL setting.
The following errors are displayed by the EEM-MA600: Error Err 0 Err 1/2/3 Err 4 Err 5 Err 6 Description No error Current transformer connection phase 1/phase 2/phase 3 Voltage between V1/V2 Voltage between V2/V3 Voltage between V3/V1
To eliminate Err 1, Err 2, and Err 3, change the order of the current connections. To eliminate Err 4, Err 5, and Err 6, change the order of the voltage connections of the measuring transducer.
104413_en_00
PHOENIX CONTACT
7-1
EEM-MA600
7.1
Press button
I C
The test menu is opened when the "test button" is pressed and held down for at least three seconds. The function test is started automatically if a test has not yet been performed.
EMpro
I C
U F
P PF MAX AVG
1x 3 seconds
Figure 7-1
Hold down the "test button" for at least three seconds. The test starts automatically, and there are no errors in the example.
I C
U F
P PF MAX AVG
1x 3 seconds
Figure 7-2
Press and hold down the "test button" again for at least three seconds; the device switches to display mode again.
I C
U F
P PF MAX AVG
1x 3 seconds
Figure 7-3
7-2
PHOENIX CONTACT
104413_en_00
Function test
7.1.1
If the direction of current flow is mixed up due to the connection order being incorrect, the measurement signals can be corrected automatically. It is not necessary to rewire connection terminal blocks S1 (input) and S2 (output). Example: Err 2 Current transformer connection phase 2
I C
U F
P PF MAX AVG
Selecting correction
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
Activating correction
1x
Confirming entry
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
Figure 7-4
104413_en_00
PHOENIX CONTACT
7-3
EEM-MA600
7.2
This menu is only displayed if the device has already been tested.
I C
U F
P PF MAX AVG
I C
U F
P PF MAX AVG
I C
U F
P PF MAX AVG
Figure 7-5
7-4
PHOENIX CONTACT
104413_en_00
Troubleshooting
Troubleshooting
This section contains a list of possible problems that may occur when working with the device. The action to be taken and the way in which the user must respond in order to solve the issue are described for each individual problem.
Error/fault Device not ready for operation Backlighting goes out Voltages = 0 Currents = 0 or faulty Incorrect display of power, power factor, and energy No display of phases
Remedy Check the power supply Check the configuration of the backlighting (see page 5-14) Check the voltage input Check the current input Check the configuration of the current transformer ratios Start the function test Check the configuration of the device (see page 5-4)
104413_en_00
PHOENIX CONTACT
8-1
EEM-MA600
8-2
PHOENIX CONTACT
104413_en_00
9.1
You can find information about connecting and installing the special function modules in the associated package inserts at www.phoenixcontact.net/catalog.
9.2
Configuration
The special function modules can be configured using the pushbuttons on the front side of the EEM-MA600. The configuration is shown in the following subsections. To configure the special function modules, press the gray buttons consecutively, as shown in the respective example. In configuration mode, the labeling below the pushbuttons applies.
Button PROG or or or OK
Description Open configuration mode (press and hold for 3 seconds) Select the next menu item Open edit mode In edit mode: select parameters/values to be changed In edit mode: change parameters/values Confirm setting
104413_en_00
PHOENIX CONTACT
9-1
EEM-MA600
9.2.1
EEM-MEMO-MA600 configuration
EEM-RS485-MA600 EEM-ETH-RS485-MA600
Storing positive real power P+: Storing negative real power P-: Storing positive reactive power Q+: Storing negative reactive power Q-: Internal or external synchronization impulse: Measuring time for storing P+/- und Q+/-:
YES; NO
YES; NO
YES; NO
YES; NO
INT; EXT
Undervoltage hysteresis:
2; 3; 4; 5 %
2; 3; 4; 5 %
YES; NO
Set value
Set value
Figure 9-1
Flowchart
9-2
PHOENIX CONTACT
104413_en_00
Choose which power you would like to save. Example: MEMO P+ = YES
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x Yes 2 x No
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-2
The same procedure applies for negative real power P-, positive reactive power Q+, and negative reactive power Q-. Storing P+, P-, Q+ and Q- for 31 days with an internal or external 10-minute synchronization impulse. Storage can be for 62 days when either just the real power or the reactive power is stored. Real and reactive energy values are stored in registers 3005...7655 (see "3000 hex: Course of reactive and real energy over set measurement duration (without consideration of transmission ratios)" on page 11-68). These must be allocated by the set measurement duration in order to determine the real and reactive power.
104413_en_00
PHOENIX CONTACT
9-3
Select whether synchronization should take place via an internal or external impulse. Example: MEMO TOP = External
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x EXT 2 x INT
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-3
9-4
PHOENIX CONTACT
104413_en_00
Special function modules 9.2.1.3 Setting the synchronization time (measurement duration)
Set the measurement duration as shown in the following example. Example: MEMO TIME = 10 minutes
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x 6x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-4
104413_en_00
PHOENIX CONTACT
9-5
5 ... 95% of the nominal voltage is set as the undervoltage threshold value. Set the threshold value as shown in the following example. Example: dAtA SAG = 15%
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-5
9-6
PHOENIX CONTACT
104413_en_00
The undervoltage hysteresis can be set for 2%, 3%, 4% or 5%. Set the hysteresis as shown in the following example. Example: dAtA HYSt = 5%
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-6
104413_en_00
PHOENIX CONTACT
9-7
The surge voltage threshold value can be set for 110 ... 150% of the nominal voltage. Set the threshold value as shown in the following example. Example: dAtA SWELL = 115%
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
5x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-7
9-8
PHOENIX CONTACT
104413_en_00
The surge voltage hysteresis can be set at 2%, 3%, 4% or 5%. Set the hysteresis as shown in the following example. Example: dAtA HYSt = 5%
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-8
104413_en_00
PHOENIX CONTACT
9-9
Activate the date/time function as shown in the following example. Example: dAtE tIME = YES
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x YES 2 x NO
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-9
9-10
PHOENIX CONTACT
104413_en_00
Set the date as shown in the following example. Example: dAtE = 19-07-05
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
9x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
7x
Figure 9-10
104413_en_00
PHOENIX CONTACT
9-11
EEM-MA600
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
5x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-11
9-12
PHOENIX CONTACT
104413_en_00
Set the time as shown in the following example. Example: tIME = 14 h 02 min 30 sec
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
4x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
2x
Figure 9-12
104413_en_00
PHOENIX CONTACT
9-13
EEM-MA600
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-13
9-14
PHOENIX CONTACT
104413_en_00
9.2.2
EEM-2DIO-MA600 configuration
EEM-2DIO-MA600
Output type:
I: I1, I2, I3 current In: neutral conductor current U: conductor voltages (1-2/2-3/3-1) V: conductor voltages against N (1/2/3) P+: total positive real power P-: total negative real power Q+: total positive reactive power Q-: total negative reactive power S: total apparent power PFL: total inductive power factor PFC: total capacitve power factor F: frequency HOUr: operating hours counter THDI: total harmonic distortion of I1, I2, I3 currents THDIN: total harmonic distortion of neutral conductor current THDU: total harmonic distortion of conductor voltages (1-2 / 2-3 / 3-1) THDV: total harmonic distortion of conductor voltages against N (1 / 2 / 3) TC1: EEM-TEMP-MA600 temperature module input TC2: EEM-TEMP-MA600 temperature module input TC3: EEM-TEMP-MA600 temperature module input TC4: EEM-TEMP-MA600 internal temperature PPR: total effective power (trend) QPR: total reactive power (trend) SPR: total apparent power (trend) CDE: control relay state via RS-485 CD-t: control relay state RS-485, return of relay to idle state
Set value
Set value
Hysteresis:
Set value
Relay output:
NO; NC
Figure 9-14
Flowchart
104413_en_00
PHOENIX CONTACT
9-15
Set the output type for the relay output as shown in the following example. Example: Out I A-Cd type = I
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x I: current I1, I2, I3 2 x In: neutral conductor current 3 x U: conductor voltages (1-2/2-3/3-1) 4 x V: conductor voltages against N (1/2/3) 5 x P+: total positive real power 6 x P-: total negative real power 7 x Q+: total positive reactive power 8 x Q-: total negative reactive power 9 x S: total apparent power 10 x PFL: total inductive power factor 11 x PFC: total capacitive power factor 12 x F: frequency 13 x HOUr: operating hours counter 14 x THDI: total harmonic distortion of I1, I2, I3 currents 15 x THDIN: total harmonic distortion of neutral conductor current 16 x THDU: total harmonic distortion of conductor voltages (1-2/2-3/3-1) 17 x THDV: total harmonic distortion of conductor voltages against N (1/2/3) 18 x TC1: EEM-TEMP-MA600 temperature module input 19 x TC2: EEM-TEMP-MA600 temperature module input 20 x TC3: EEM-TEMP-MA600 temperature module input 21 x TC4: EEM-TEMP-MA600 internal temperature 22 x PPR: total real power (trend) 23 x QPR: total reactive power (trend) 24 x SPR: total apparent power (trend) 25 x CDE: control relay state via RS-485 26 x CD-t: control relay state via RS-485, return of relay to idle state
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-15
9-16
PHOENIX CONTACT
104413_en_00
Set the upper switching threshold for the relay as shown in the following example. Example: Out I Ht = 100 kA
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-16
104413_en_00
PHOENIX CONTACT
9-17
Set the lower switching threshold for the relay as shown in the following example. Example: Out I Lt = 10 kA
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-17
9-18
PHOENIX CONTACT
104413_en_00
Set the hysteresis (10 ... 90%) for the relay as shown in the following example. Example: Out I HYST = 20%
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-18
104413_en_00
PHOENIX CONTACT
9-19
Set the trigger delay (in seconds) for the relay as shown in the following example. Example: Out I TEMPO = 30 s
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-19
9-20
PHOENIX CONTACT
104413_en_00
Set the output relay idle state as shown in the following example. NO: relay open in idle state NC: relay closed in idle state Example: Out I RELAY = NO
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-20
Repeat the settings for the other relay outputs Out 2, Out 3, Out 4, Out 5, Out 6.
104413_en_00
PHOENIX CONTACT
9-21
EEM-MA600
9.2.3
EEM-2AO-MA600 configuration
EEM-2AO-MA600
Output signal:
Output type:
I1: I1 current I2: I2 current I3: I3 current In: neutral conductor current U12: conductor voltage (1-2) U23: conductor voltage (2-3) U31: conductor voltage (3-1) V1: conductor voltage against N V2: conductor voltage against N V3: conductor voltage against N P: total real power Q: total reactive power S: total apparent power PFL: total inductive power factor PFC: total capacitive power factor F: frequency ISYS: average value of currents (I1+I2+I3) / 3 USYS: average value of conductor voltages phase/phase (U12 + U23 + U31 ) / 3 VSYS: average value of conductor voltages phase/N (V1 + V2 + V3 ) / 3 PPR: total real power (trend) QPR: total reactive power (trend) SPR: total apparent power (trend) TC1: EEM-TEMP-MA600 temperature module input TC2: EEM-TEMP-MA600 temperature module input TC3: EEM-TEMP-MA600 temperature module input TC4: EEM-TEMP-MA600 temperature module input
Assigning measured value to lower output value 0/4 mA: Assigning measured value to upper output value 20 mA:
Set value
Set value
Figure 9-21
Flowchart
9-22
PHOENIX CONTACT
104413_en_00
Set the output signal as shown in the following example. Example: Out I 20 MA = 0/20 mA
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x 0/20 mA 2 x 30 V DC 3 x 4/20 mA
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-22
104413_en_00
PHOENIX CONTACT
9-23
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
0 x I1: current I1 1 x I2: current I2 2 x I3: current I3 3 x In: neutral conductor current 4 x U12: conductor voltages (1-2) 5 x U23: conductor voltages (2-3) 6 x U31: conductor voltages (3-1) 7 x V1: conductor voltages against N 8 x V2: conductor voltages against N 9 x V3: conductor voltages against N 10 x P: total real power 11 x Q: total reactive power 12 x S: total apparent power 13 x PFL: total inductive power factor 14 x PFC: total capacitive power factor 15 x F: frequency 16 x ISYS: average current (I1+I2+I3)/3 value 17 x USYS: average phase/phase conductor voltage value (U12 + U23 + U31 )/3 18 x VSYS: average phase/N conductor voltage value (V1 + V2 + V3 )/3 19 x PPR: total real power (trend) 20 x QPR: total reactive power (trend) 21 x SPR: total apparent power (trend) 22 x TC1: EEM-TEMP-MA600 temperature module input 23x TC2: EEM-TEMP-MA600 temperature module input 24 x TC3: EEM-TEMP-MA600 temperature module input 25 x TC4: EEM-TEMP-MA600 internal temperature
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-23
9-24
PHOENIX CONTACT
104413_en_00
Special function modules 9.2.3.3 Assignment of measured values to lower output value 0 or 4 mA
Set the lower measured value for 0 or 4 mA. Example: Out I 20 mA LV = 1000 kA
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
4x
I C
U F
P PF MAX AVG
1 x K: Kilo 2 x /: A 3 x M: Mega A
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-24
104413_en_00
PHOENIX CONTACT
9-25
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
4x
I C
U F
P PF MAX AVG
1 x K: Kilo 2 x /: A 3 x M: Mega A
I C
U F
P PF MAX AVG
1x Confirm
Figure 9-25
If the lower and the upper output values are the same, the output value is 0. Configuring the frequency output value: if value is 40 Hz, for example, set value to 4000 Hz. Configuring the power factor output value: if value is 0.5, for example, set to 500; if value is 1, for example, set to 1000. If you assign an alarm to a temperature input, it is automatically triggered if a temperature sensor is not connected. Repeat the settings for the other outputs Out 2, Out 3, Out 4.
9-26
PHOENIX CONTACT
104413_en_00
Communication modules
10 Communication modules
The EEM-MA600 can be extended with different function modules. Module EEM-RS485-MA600 EEM-ETH-MA600 EEM-ETH-RS485-MA600 EEM-PB-MA600 EEM-PB12-MA600 Technology MODBUS Ethernet PROFIBUS Description in... Section "MODBUS" on page 10-1 Section "Ethernet" on page 10-12 Section "PROFIBUS" on page 10-19
10.1
10.1.1
MODBUS
Basics
The data is transmitted for each MODBUS RTU (Remote Terminal Unit) protocol. Communication takes place according to the master-slave procedure. Communication begins when requested by the master (PLC). Each slave (EEM-MA600) has a one-time address (valid range 1 ... 247). If a slave detects that its address is addressed by the master, the slave always sends an answer. The slaves never communicate with each other. They are not able to initiate communication with the master. Connected extension modules write, for example, the analog/digital input and output values to an internal register. The MODBUS master (PLC) can read the individual registers using the PLC address. The data to be transmitted is always present in a fixed frame and is defined as follows: Frame Slave address Function code Address Data Description Here, the slave address is given (valid range 1 ... 247) Here, it is established whether parameters are read or written. Register Address - for example, from the master: which parameters are addressed? - for example, from the slave: content of addressed parameters CRC (Cyclic Redundancy Check) The cyclic redundancy check: test value for data in order to detect errors in data transmission.
Example: read device parameters (initiated by the master) Function 03 High quality address C6 Low quality address 5C No. High quality words 00 No. Low quality words 02 CRC 16 3915
104413_en_00
PHOENIX CONTACT
10-1
EEM-MA600
Example: answer from a slave (initiated by slave) Function 03 Number of bytes 04 Low quality register value 0011 High quality register value IDDD CRC 16 2FAF
Example: write device parameters Function 06 High quality address E0 Low quality address 00 High quality register value 00 Low quality register value 05 CRC 16 7F8D
Each bus device must have a unique address. Slave address 0 is reserved for a broadcast. Function codes in MODBUS Several function codes are defined in MODBUS. They are as follows: Function code 03 Hex 06 Hex 16 Hex Name Read hold register Write single register Write multiple registers Abbreviation R W Description Read device parameters Write individual device parameters word by word, write several device parameters word by word
There are still other function codes, but these are not supported.
10.1.2
You can find information about connecting and installing the EEM-RS485-MA600 communication module from the associated package inserts at www.phoenixcontact.net/catalog.
10-2
PHOENIX CONTACT
104413_en_00
Communication modules
10.1.3
The module can be configured using the pushbutton on the front side of the measuring instrument. The configuration is shown in the following subchapters. Button PROG or or or OK Description Open configuration mode (hold down for 3 seconds) Select the next menu item Open edit mode In edit mode: Select parameters/values to be changed In edit mode: change parameters/values Confirm setting
EEM-RS485-MA600
MODBUS address:
0 ... 254 2,4 kBit/s; 4,8 kBit/s; 9,6 kBit/s; 19,2 kBit/s; 38,4 kBit/s Odd; Even; nO
Transmission speed:
Parity:
Stop bits:
1; 2
Figure 10-1
Flow chart
104413_en_00
PHOENIX CONTACT
10-3
Set the MODBUS address as shown in the following example. Example: COM ADR = 7
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x Confirm
Figure 10-2
10-4
PHOENIX CONTACT
104413_en_00
Set the transmission speed as shown in the following example. All MODBUS devices must be set to the same transmission speed.
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x 2x 3x 4x 5x
2.4 kbps 4.8 kbps 9.6 kbps 19.2 kbps 38.4 kbps
I C
U F
P PF MAX AVG
1x Confirm
Set the parity as shown in the following example. Example: COM PAR = Even
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x Odd 2 x Even 3 x No
Figure 10-4
104413_en_00
PHOENIX CONTACT
10-5
Set the stop bits as shown in the following example. Example: COM STOP = 2
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x 2 bits 2 x 1 bits
I C
U F
P PF MAX AVG
1x Confirm
Figure 10-5
10.1.4
You can find the MODBUS/JBUS register tables at Section "MODBUS register" on page 11-1.
10-6
PHOENIX CONTACT
104413_en_00
Communication modules
10.1.5
In the following example, some points for testing the MODBUS structure with the "Modbus Poll" simulation software are described. The simulation software is a freeware tool and can be downloaded from the Internet at http://www.modbustools.com/. 10.1.5.1 1. Settings
2.
104413_en_00
PHOENIX CONTACT
10-7
EEM-MA600 3. Enter the desired serial interface parameters in the fields below. Set "Mode" to RTU.
4.
10.1.5.2 1. 2. 3. 4. 5.
Open the MODBUS register access settings as follows: "Setup, Read/Write Definition". Set the desired "Slave ID". Under "Function," you can choose the register access type (Read "03" or write "06"/"16"). Under "Address", enter the start address for the desired register. Under "Quantity", enter the register length.
10-8
PHOENIX CONTACT
104413_en_00
Communication modules Example: "Read" function Main measured values read based on current and voltage transducer (see "C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios)" on page 11-2): Hour counter Line voltage U12 1. 2. 3. Data word/decimal address 50512/50513 Data word/decimal address 50514/50515
After you have entered the "Slave ID', choose the "Function" "03 Read Holding Registers". Enter start address 50512 under "Address". Under "Quantity", enter 4 as the number of data words.
4.
In order to be able to further use register contents, these must be converted into the corresponding units (see "C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios)" on page 11-2).
104413_en_00
PHOENIX CONTACT
10-9
EEM-MA600 Register 50513 content (hour counter ) = 47032 47032 : 100 = 470.32 h Register 50515 content (line voltage U12) = 35655 35655 : 100 = 356.57 V Example: "Write" function Date time configuration (see "E100 hex: date/time configuration" on page 11-21): 1. After entering the "Slave ID", choose "Function" "16 Write Multiple Registers". 2. Enter start address 57600 under "Address". 3. Enter 6 as the number of data words under "Quantity".
4.
10-10
PHOENIX CONTACT
104413_en_00
Communication modules 5. Enter the desired date and time in the lines listed below.
Value 22 2 11 9 29 30
104413_en_00
PHOENIX CONTACT
10-11
EEM-MA600
10.2
10.2.1
Ethernet
Connecting and installing communication modules EEM-ETH-MA600 and EEM-ETH-RS485-MA600
You can find information about connecting and installing the EEM-ETH-MA600 and EEM-ETH-RS485-MA600 communication modules from the associated package inserts at www.phoenixcontact.net/catalog.
10.2.2
The modules can be configured using the pushbutton on the front side of the measuring instrument. The configuration is shown in the following subchapters. Button PROG or or or OK Description Open configuration mode (hold down for 3 seconds) Select the next menu item Open edit mode In edit mode: Select parameters/values to be changed In edit mode: change parameters/values Confirm setting
The default settings are: IP address: Subnet mask: Gateway: DHCP activation: 192.168.1.1 255.255.255.0 0.0.0.0 No
10-12
PHOENIX CONTACT
104413_en_00
Communication modules
EEM-ETH-RS485-MA600 EEM-ETH-MA600
Ethernet address: Set CL. A Repeat setting for CL. B, CL. C, CL. D
Set value
Subnet mask: Set CL. A Repeat setting for CL. B, CL. C, CL. D
Set value
Gateway address: Set CL. A Repeat setting for CL. B, CL. C, CL. D
Set value
DHCP activation:
YES; NO
Set the IP address as shown in the following example. Example: IP address 191.158.1.7 CLASS A = 191
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
Figure 10-7
104413_en_00
PHOENIX CONTACT
10-13
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
Figure 10-8
I C
U F
P PF MAX AVG
3x
Figure 10-9
10-14
PHOENIX CONTACT
104413_en_00
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
6x
I C
U F
P PF MAX AVG
1x
Set the subnet mask as shown in the following example. Example: Setting subnet mask 255.255.255.0 The principle is the same as with the IP address (see Section "Setting the IP Address" on page 10-13).
I C
U F
P PF MAX AVG
4x
Figure 10-11
104413_en_00
PHOENIX CONTACT
10-15
Set the gateway address as shown in the following example. Example: Gateway address 0.0.0.0 The principle is the same as with the IP address (see Section "Setting the IP Address" on page 10-13).
I C
U F
P PF MAX AVG
4x
Setting DHCP
Activate the DHCP as shown in the following example. DHCP activation is not recommended. If necessary, contact your network administrator.
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1x
Figure 10-13
Setting DHCP
10-16
PHOENIX CONTACT
104413_en_00
Communication modules
10.2.3
The register tables are the same as for MODBUS/JBUS communication (see Section "MODBUS register" on page 11-1).
10.2.4
In the following example, some points for testing the Ethernet MODBUS structure with the "Modbus Poll" simulation software are described. The simulation software is a freeware tool and can be downloaded from the Internet at http://www.modbustools.com/. 1. Open the interface settings via "Connection, Connect".
2.
104413_en_00
PHOENIX CONTACT
10-17
EEM-MA600 3. Enter the desired IP addresses in the fields below (the first three address areas for the IP addresses must be the same for the PC and the EEM-MA600 when 255.255.255.0 is set as the subnet mask). Set the port to 502 (direct access to the connected measuring instrument EEM-MA600 with Ethernet extension module) or 503 (access via the gateway to connected Modbus devices).
4.
5.
10.2.5
10.2.6
10.2.7
Web server
You can have the most important current and average measured values and tallies displayed via the web server. By entering the device IP address in the Internet browser, you can access the web server. Example: IP address of measuring instrument EEM-MA600: URL address: 192.168.1.0 http://192.168.1.0/index.htm
10-18
PHOENIX CONTACT
104413_en_00
Communication modules
10.3
10.3.1
PROFIBUS
Basics
The PROFIBUS is a serial bus system that transmits data between control systems and spatially distributed I/O terminals, to which sensors and actuators are connected. The PROFIBUS has a star/tree structure. In the PROFIBUS topology, the individual devices are differentiated on the basis of their addressing. The communication profiles determine how the devices transmit their data serially via the bus. The PROFIBUS DP (distributed I/O) is typically a single-master system, i.e. all devices of a PROFIBUS DP are controlled by one master. PROFIBUS DP is optimized for the straightforward transmission of input and output data and is specifically designed for communication between automation systems and distributed I/O devices. The characteristic communication features of a PROFIBUS DP device are defined in the form of an electronic device data sheet (GSD, device database file). The required GSD file for the measuring instrument is available at www.phoenixcontact.net/catalog.
10.3.2
You can find information about connecting and installing communication modules EEM-PB-MA600 and EEM-PB12-MA600 from the associated package inserts at www.phoenixcontact.net/catalog.
104413_en_00
PHOENIX CONTACT
10-19
EEM-MA600
10.3.3
Install the GSD file first. The communication module automatically adjusts itself to the speed specified by the PROFIBUS master. The module can be configured using the pushbutton on the front side of the measuring instrument. The configuration is shown in the following subchapters. Button PROG or or or OK Description Open configuration mode (hold down for 3 seconds) Select the next menu item Open edit mode In edit mode: select parameters/values to be changed In edit mode: change parameters/values Confirm setting
EEM-PB-MA600 EEM-PB12-MA600
PROFIBUS adress:
Set value
Diagnostics:
YES; NO
YES; NO
Figure 10-14
10-20
PHOENIX CONTACT
104413_en_00
Set the PROFIBUS address as shown in the following example. Example: COM ADR = 7
I C
U F
P PF MAX AVG
3x
I C
U F
P PF MAX AVG
2x
I C
U F
P PF MAX AVG
1x Confirm
Figure 10-15
104413_en_00
PHOENIX CONTACT
10-21
The diagnostic function shows the following: Availability of extension modules Serial number of the device Availability of an alarm or overrun Example: COM DIAG = No
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x NO 2 x YES
I C
U F
P PF MAX AVG
1x Confirm
With this function, you can activate or deactivate EEM-MA600 parameterization via the PROFIBUS DP master. YES When the measuring instrument is restarted, the device settings are loaded from the GSD file. The information from the GSD file is sent by the PROFIBUS master to the slaves. The last device settings are saved upon restarting.
NO
10-22
PHOENIX CONTACT
104413_en_00
I C
U F
P PF MAX AVG
1x
I C
U F
P PF MAX AVG
1 x NO 2 x YES
I C
U F
P PF MAX AVG
1x Confirm
Figure 10-17
10.3.4
The PROFIBUS register tables are at Section "PROFIBUS register" on page 12-1.
10.3.5
In the following example, some points about PROFIBUS configuration startup are described. This includes hardware implementation (EEM-MA600), calling the variable tables with parameter reading/controlling and importing/transferring parameters in the software. 10.3.5.1 Installing a GSD file
In a new or existing project, the EEM-MA600 should be inserted. The GSD file must be installed first. The required GSD file for the measuring instrument is available at www.phoenixcontact.net/catalog. It can be added in the HW configuration under "Extras".
104413_en_00
PHOENIX CONTACT
10-23
Load your master project after the GSD file installation is successfully implemented. Under the path on the right-hand side, you will find measuring instrument EEM-MA600 under "PROFIBUS DP, Additional field devices, General". This can be linked to the bus through "Drag&Drop". Then a window will automatically be displayed where the module is assigned an address and a name/description for the EEM-MA600 can be given. If the EEM-MA600 already has an assigned address, this should be chosen. When delivered, the EEM-MA600 has address 5.
10-24
PHOENIX CONTACT
104413_en_00
Communication modules 3. After you add the measuring instrument to your PROFIBUS configuration, the EEM-MA600 must still be assigned the desired register tables (see Section "Module 1 "Main values"" on page 12-5, Section "Module 2 "Additional values"" on page 12-11, etc.) and the addresses for the particular inputs and outputs. Only the start address is given, since the prefabricated tables have fixed lengths and the end results from this length. The register tables are available on the right side under "MA600".
104413_en_00
PHOENIX CONTACT
10-25
EEM-MA600 4. You can drag the desired register tables via "Drag&Drop" from the right to the lower left area. The maximum table size is 155 bytes (Input: 95 bytes, output 60 bytes).
5.
Double-click on the green-highlighted area to open the "Properties - DP slave" window. Here, you can determine the start address for input and output registers (for example, start address output: 256, start address input: 256).
6. 7.
Save the changes described above with "Save and compile". Load the changes with "Download to module" in the controller.
10-26
PHOENIX CONTACT
104413_en_00
After the new configuration is loaded, switch to the Simatic Manager window. Under "S7 program", right-click on "Function blocks". In the next window, choose "Insert New Object, Variable Table".
4.
In the variable table, the outputs for previously entered modules can be controlled and the inputs read back. Access takes place via the input and output addresses set in the hardware configuration. The necessary quantities (bytes, words, double words) for the read and displayed data are described in the register tables.
You can, for example, read back the voltages for the individual phases as shown in the following example, Module 1: "Main values" (see Section "Module 1 "Main values"" on page 12-5). Example start address 0 (Register size 2 bytes) IW 14 IW 16 W 18 V1: Conductor voltage against N (V/ 100) V2: Conductor voltage against N (V/ 100) V3: Conductor voltage against N (V/ 100) Measured value: 110,10 V Measured value: 109,97 V Measured value: 109,93 V
Example start address 10 If you have set the start address from 0 to 10 instead, you will find the three words to be read back in the variable tables under: IW 24 IW 26 IW 28 Abbreviations for the tables include: (when English is the set language, these abbreviations can deviate for other language settings) IB IW ID Input byte Input word Input double word QB QW QD Output byte Output word Output double word Input word 10+14=24
104413_en_00
PHOENIX CONTACT
10-27
EEM-MA600 To display the measured values in the table under input words, you must first create a connection to the connected PROFIBUS device. Establish a connection with the "Set Up Connection to Directly Connected CPU" button. When you click on the "Monitor variable" button, the measured values for the values delivered from EEM-MA600 will be specified in the register upon updating.
10.3.5.4
With Module 9, you can compile a specific table from the values from the special tables. This has a length of 33 bytes, with the first byte reserved for the table number. You can freely choose the table number (bit 0...6). In order to write values in the special table and/or have them read out from the table, bit 7 from input byte 1 for the output value must be set to 1. 16 words can be compiled with the desired data. Then, the addresses for the chosen values are written in the following, up to 16 output words, and the table is defined. The readout then takes place as with all other tables. Set output values using the "Modify variable" command. You can activate this by rightclicking on a value or with Ctrl+F9 or the "Variable, Modify" tab. With the help of the "Insert, Range of variables" menu item, a set of input/output values can be added, such as when several values should be added for a type consecutively (for example, IW 0 to IW 27, QW 0 to QW 27).
10-28
PHOENIX CONTACT
104413_en_00
Communication modules Example Tables No. 0 Bit 7 Binary Decimal 1 128 Bit 6 0 Bit 5 0 Bit 4 0 Bit 3 0 Bit 2 0 Bit 1 0 Bit 0 0
Bit 7 must always be set to 1 in order to write values in the special tables and/or to have the table read back.
104413_en_00
PHOENIX CONTACT
10-29
EEM-MA600
10-30
PHOENIX CONTACT
104413_en_00
MODBUS register
11 MODBUS register
In this section, you will find the following registers. Table 11-1 Start address C550 hex C650 hex C750 hex C850 hex 370 hex 741 hex C900 hex C950 hex CB00 hex E000 hex E100 hex E110 hex E200 hex 7700 hex 100 hex 200 hex 400 hex C10 hex D00 hex Register overview Description Display of current main measured values based on current and voltage transducer (under consideration of transmission ratios) Energy values display Display of average values based on current and voltage transducer via the set measurement duration (under consideration of transmission ratios) Display of current main measured values not based on current and voltage transducer (without consideration of transmission ratios) Display of current average current/voltage value based on current and voltage transducer (under consideration of transmission ratios) Display of current average current/voltage value not based on current and voltage transducer (without consideration of transmission ratios) Temperature inputs display Display of current harmonic distortion and harmonics Status of inputs/outputs Measuring instrument terminal configuration Date/time configuration Ethernet communication module configuration Saving configuration and restart for measuring instrument Display of last alarm to digital outputs (EEM-2DIO-MA600) Information about connected extension modules Extension module display and configuration Reset measured values Alarm history display (course of last 10 alarms) Undervoltage (course of last 10 SAG threshold value undervoltages) On page... Table 11-2 on page 11-2 Table 11-3 on page 11-3 Table 11-4 on page 11-5 Table 11-5 on page 11-7 Table 11-6 on page 11-8 Table 11-7 on page 11-9 Table 11-8 on page 11-9 Table 11-9 on page 11-10 Table 11-10 on page 11-20 Table 11-11 on page 11-20 Table 11-13 on page 11-21 Table 11-14 on page 11-22 Table 11-15 on page 11-23 Table 11-17 on page 11-24 Table 11-18 on page 11-28 Table 11-19 on page 11-29 Table 11-20 on page 11-39 Table 11-21 on page 11-42 Table 11-22 on page 11-47
104413_en_00
PHOENIX CONTACT
11-1
EEM-MA600 Table 11-1 Start address E00 hex F00 hex 1000 hex 3000 hex 8000 hex 9000 hex Register overview [...] Description Surge voltage (course of last 10 SWELL surge voltages) Current minimum and maximum measured values (measurement duration of 1 s) Supply voltage failure (course of last 10 voltage interruptions) Course of reactive and real energy over set measurement duration (without consideration of transmission ratios) Course of average values for voltages over the set measurement duration Course of average values for frequency over the set measurement duration On page... Table 11-23 on page 11-53 Table 11-24 on page 11-58 Table 11-25 on page 11-65 Table 11-26 on page 11-68 Table 11-27 on page 11-68 Table 11-28 on page 11-69
Table 11-2
C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios) Hexadecimal address C550 C552 C554 C556 C558 C55A C55C C55E C560 C562 C564 C566 C568 C56A C56C C56E C570 C572 C574 C576 Number of data words 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Designation Unit Register access R R R R R R R R R R R R R R R R R R R R Available through extension module
Decimal address 50512 50514 50516 50518 50520 50522 50524 50526 50528 50530 50532 50534 50536 50538 50540 50542 50544 50546 50548 50550
Hour: operating hours counter U12: line voltage (1-2) U23: line voltage (2-3) U31: line voltage (3-1) V1: line voltage against N V2: line voltage against N V3: line voltage against N F: frequency I1: current I2: current I3: current In: neutral conductor current P: total real power +/Q: total reactive power +/S: total apparent power PF: total power factor -: capacitive and + : inductive P1: real power phase 1 +/P2: real power phase 2 +/P3: real power phase 3 +/Q1: reactive power phase 1 +/-
h/100 V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 mA mA mA mA kW/100 kvar/100 kVA/100 0.001 kW/100 kW/100 kW/100 kvar/100
11-2
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-2 C550 hex: display of current main measured values based on current and voltage transducer (under consideration of transmission ratios) [...] Hexadecimal address C578 C57A C57C C57E C580 C582 C584 C586 C588 C58A C58C Number of data words 2 2 2 2 2 2 2 2 2 2 2 Designation Unit Register access R R R R R R R R R R R Available through extension module
Decimal address 50552 50554 50556 50558 50560 50562 50564 50566 50568 50570 50572
Q2: reactive power phase 2 +/Q3: reactive power phase 3 +/S1: apparent power phase 1 S2: apparent power phase 2 S3: apparent power phase 3 PF1: power factor phase 1 -: capacitive and + : inductive PF2: power factor phase 2 -: capacitive and + : inductive PF3: power factor phase 3 -: capacitive and + : inductive Not available Not available Not available
Table 11-3 Decimal address 50768 50770 50772 50774 50776 50778 50780 50782 50784 50786 50788 50790 50792 50794 50796 50798
C650 hex: energy value display Hexadecimal Number Designation address of data words C650 C652 C654 C656 C658 C65A C65C C65E C660 C662 C664 C666 C668 C66A C66C C66E 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Hour: operating hours counter Not available Not available Not available Not available Not available Ea+: current positive real energy Er +: current positive reactive energy Es: current apparent energy Ea-: current negative real energy Er -: current negative reactive energy No. digital inputs (max 6) Counter reading digital input DI 1 Counter reading digital input DI 2 Counter reading digital input DI 3 Counter reading digital input DI 4 Unit Register Available through access extension module R R R R R R R R R R R R R R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600
104413_en_00
PHOENIX CONTACT
11-3
EEM-MA600 Table 11-3 Decimal address 50800 50802 50804 50806 50808 50810 50812 50814 50816 50818 50820 50822 50824 50826 50828 50829 50830 50831 50832 C650 hex: energy value display [...] Hexadecimal Number Designation address of data words C670 C672 C674 C676 C678 C67A C67C C67E C680 C682 C684 C686 C688 C68A C68C C68D C68E C68F C690 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 Counter reading digital input DI 5 Counter reading digital input DI 6 Not available Not available Not available Not available PPR: total real power over set measurement duration (trend) QPR: total reactive power over set measurement duration (trend) SPR: total apparent power over set measurement duration (trend) Ea+: current positive real energy over set measurement duration Ea-: current negative real energy over set measurement duration Er+: current positive reactive energy over set measurement duration Er-: current negative reactive energy over set measurement duration Not available Not available Not available Not available Not available Not available Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R EEM-2DIO-MA600 EEM-2DIO-MA600
Range extension: 65 words (decimal) or 41 words (hexadecimal). Example: In order to read the positive real energy from address C65C, the following data sequence must be sent: Slave address 05 Function 03 High quality address C6 Low quality address 5C No. High quality words 00 No. Low quality words 02 CRC 16 3915
11-4
PHOENIX CONTACT
104413_en_00
MODBUS register EEM-MA600 answer: the register contents correspond to a positive real energy of 177645 kWh. Slave address 05 Function 03 Number of bytes Low quality register value 04 0011 17 High quality register value IDDD 7645 CRC 16 2FAF
Table 11-4
C750 hex: display of average values based on current and voltage transducer via the set measurement duration (under consideration of transmission ratios) Hexadecimal Number Designation address of data words C750 C752 C754 C756 C758 C75A C75C C75E C760 C762 C764 C766 C768 C76A C76C C76E C770 C772 C774 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Avg U12: average line voltage value Avg U23: average line voltage value Avg U31: average line voltage value Avg V1: average line voltage value against N Avg V2: average line voltage value against N Avg V3: average line voltage value against N Avg F: average frequency value Avg I1: current average value Avg I2: current average value Avg I3: current average value Avg In: neutral conductor current average value Avg P+: average total positive real power value Avg P-: average total negative real power value Avg Q+: average total positive reactive power value Avg Q-: average total negative reactive power value Avg S: average total apparent power value Avg U12: average line voltage value Avg U23: average line voltage value Avg U31: average line voltage value Unit Register access R R R R R R R R R R R R R R R R R R R Available through extension module
Decimal address 51024 51026 51028 51030 51032 51034 51036 51038 51040 51042 51044 51046 51048 51050 51052 51054 51056 51058 51060
V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 mA mA mA mA kW/100 kW/100 kvar/100 kvar/100 kVA/100 V/100 V/100 V/100
104413_en_00
PHOENIX CONTACT
11-5
EEM-MA600 Table 11-4 C750 hex: display of average values based on current and voltage transducer via the set measurement duration (under consideration of transmission ratios) [...] Hexadecimal Number Designation address of data words C776 C778 C77A C77C C77E C780 C782 C784 C786 C788 C78A C78C C78E C790 C791 C792 C793 C794 C795 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 Max/avg V1: maximum value for line voltage against N Max/avg V2: maximum value for line voltage against N Max/avg V3: maximum value for line voltage against N Unit Register access R R R R R R R R R R R R R R R R R R R Available through extension module
Decimal address 51062 51064 51066 51068 51070 51072 51074 51076 51078 51080 51082 51084 51086 51088 51089 51090 51091 51092 51093
Max/avg F: maximum frequency value Hz/100 Max/avg I1: maximum current value Max/avg I2: maximum current value Max/avg I3: maximum current value Max/avg In: maximum current value Max/avg P+: maximum total positive real power value Max/avg P-: maximum total negative real power value Max/avg Q+: maximum total positive reactive power value Max/avg Q-: maximum total negative reactive power value Max/avg S: maximum total apparent power value Not available Not available Not available Not available Not available Not available mA mA mA mA kW/100 kW/100 kvar/100 kvar/100 kVA/100 -
11-6
PHOENIX CONTACT
104413_en_00
MODBUS register
When you use this table, you must multiply the values by the transmission ratios for the converter used.
Table 11-5
C850 hex: display of current main measured values not based on current and voltage transducer (without consideration of transmission ratios) Hexadecimal Number address of data words C850 C851 C852 C853 C854 C855 C856 C857 C858 C859 C85A C85B C85C C85D C85E C85F C860 C861 C862 C863 C864 C865 C866 C867 C868 C869 C86A C86B 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Designation Unit Register access R R R R R R R R R R R R R R R R R R R R R R R R R R R R Available through extension module
Decimal address 51280 51281 51282 51283 51284 51285 51286 51287 51288 51289 51290 51291 51292 51293 51294 51295 51296 51297 51298 51299 51300 51301 51302 51303 51304 51305 51306 51307
Hour: operating hours counter U12: line voltage U23: line voltage U31: line voltage V1: line voltage against N V2: line voltage against N V3: line voltage against N F: frequency I1: current I2: current I3: current In: neutral conductor current P: total real power +/Q: total reactive power +/S: total apparent power PF: total power factor -: capacitive and + : inductive P1: real power phase 1 +/P2: real power phase 2 +/P3: real power phase 3 +/Q1: reactive power phase 1 +/Q2: reactive power phase 2 +/Q3: reactive power phase 3 +/S1: apparent power phase 1 S2: apparent power phase 2 S3: apparent power phase 3 PF1: power factor phase 1 -: capacitive and + : inductive PF2: power factor phase 2 -: capacitive and + : inductive PF3: power factor phase 3 -: capacitive and + : inductive
h/100 V/100 V/100 V/100 V/100 V/100 V/100 Hz/100 mA mA mA mA kW/100 kvar/100 kVA/100 0.001 kW/100 kW/100 kW/100 kvar/100 kvar/100 kvar/100 kVA/100 kVA/100 kVA/100 0.001 0.001 0.001
104413_en_00
PHOENIX CONTACT
11-7
EEM-MA600 Table 11-5 C850 hex: display of current main measured values not based on current and voltage transducer (without consideration of transmission ratios) [...] Hexadecimal Number address of data words C86C C86D C86E C86F C870 C871 C872 1 1 1 1 1 1 1 Designation Unit Register access R R R MWh R R MWh R R Available through extension module
Not available Not available Not available EA+: Total positive real energy since startup (cannot be reset) Not available EA-: total negative real energy since startup (cannot be reset) Not available
Range extension: 35 words (decimal) or 23 words (hexadecimal). Example: To have all values from table C850 with a length of 35 words read out with one query, the following data sequence must be sent: Slave address 05 Function 03 High quality address C8 Low quality address 50 No. High quality words 00 No. Low quality words 35 CRC 16 BA28
Table 11-6
370 Hex: display of current average current/voltage value based on current and voltage transducer (under consideration of transmission ratios) Hexadecimal address 370 372 374 Number of data words 2 2 2 Designation Unit Register Available through access extension module R R R -
ISYS: current average value ( I1+I2+I3)/3 USYS: line voltages (U12 + U23 + U31)/3 average value
mA V/100
11-8
PHOENIX CONTACT
104413_en_00
MODBUS register
When you use this table, you must multiply the values by the transmission ratios for the converter used.
Table 11-7
741 hex: display of current average current/voltage value not based on current and voltage transducer (without consideration of transmission ratios) Hexadecimal address 741 742 743 Number of data words 1 1 1 Designation Unit Register Available through access extension module R R R -
ISYS: current average value ( I1+I2+I3)/3 USYS: line voltages (U12 + U23 + U31)/3 average value VSYS: average value of line voltages against N (V1 + V2 + V3 )/3
mA V/10 V/10
Table 11-8 Decimal address 51456 51457 51458 51459 51460 51461 51462 51463
C900 hex: temperature inputs display Hexadecimal Number address of data words C900 C901 C902 C903 C904 C905 C906 C907 1 1 1 1 1 1 1 1 Designation Unit Register access R R R R R R R R EEM-TEMP-MA600 EEM-TEMP-MA600 EEM-TEMP-MA600 EEM-TEMP-MA600 Available through extension module
Internal temperature sensor available Internal module temperature Number of temperature sensors (0-3 max) connected External temperature 1 External temperature 2 External temperature 3 Not available Not available
Yes(1)/No(0) C C C C -
104413_en_00
PHOENIX CONTACT
11-9
EEM-MA600
C950 hex: display of current harmonic distortion and harmonics Hexadecimal address Number Designation of data words Unit Register Available through access extension module
Total THD harmonic distortion 51536 51537 51538 51539 51540 51541 51542 51543 51544 51545 C950 C951 C952 C953 C954 C955 C956 C957 C958 C959 1 1 1 1 1 1 1 1 1 1 THD U12: total harmonic distortion of line voltage THD U23: total harmonic distortion of line voltage THD U31: total harmonic distortion of line voltage THD V1: total harmonic distortion of line voltage against N THD V2: total harmonic distortion of line voltage against N THD V3: total harmonic distortion of line voltage against N THD I1: total harmonic distortion of current THD I2: total harmonic distortion of current THD I3: total harmonic distortion of current THD In: total harmonic distortion of neutral conductor current 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R R R
Range extension: 10 words (decimal) or A words (hexadecimal). Individual harmonic content for currents: I 51546 51547 51548 51549 51550 51551 51552 51553 51554 51555 51556 51557 51558 51559 51560 C95A C95B C95C C95D C95E C95F C960 C961 C962 C963 C964 C965 C966 C967 C968 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Highest ascertainable harmonic (63) Content of 3rd harmonic I1 Content of 3rd harmonic I2 Content of 3rd harmonic I3 Content of 3rd harmonic IN Content of 5th harmonic I1 Content of 5th harmonic I2 Content of 5th harmonic I3 Content of 5th harmonic IN Content of 7th harmonic I1 Content of 7th harmonic I2 Content of 7th harmonic I3 Content of 7th harmonic IN Content of 9th harmonic I1 Content of 9th harmonic I2 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R R R R R R R
11-10
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-9 Decimal address 51561 51562 51563 51564 51565 51566 51567 51568 51569 51570 51571 51572 51573 51574 51575 51576 51577 51578 51579 51580 51581 51582 51583 51584 51585 51586 51587 51588 51589 51590 51591 51592 51593 51594 51595 51596 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C969 C96A C96B C96C C96D C96E C96F C970 C971 C972 C973 C974 C975 C976 C977 C978 C979 C97A C97B C97C C97D C97E C97F C980 C981 C982 C983 C984 C985 C986 C987 C988 C989 C98A C98B C98C Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 9th harmonic I3 Content of 9th harmonic IN Content of 11th harmonic I1 Content of 11th harmonic I2 Content of 11th harmonic I3 Content of 11th harmonic IN Content of 13th harmonic I1 Content of 13th harmonic I2 Content of 13th harmonic I3 Content of 13th harmonic IN Content of 15th harmonic I1 Content of 15th harmonic I2 Content of 15th harmonic I3 Content of 15th harmonic IN Content of 17th harmonic I1 Content of 17th harmonic I2 Content of 17th harmonic I3 Content of 17th harmonic IN Content of 19th harmonic I1 Content of 19th harmonic I2 Content of 19th harmonic I3 Content of 19th harmonic IN Content of 21st harmonic I1 Content of 21st harmonic I2 Content of 21st harmonic I3 Content of 21st harmonic IN Content of 23rd harmonic I1 Content of 23rd harmonic I2 Content of 23rd harmonic I3 Content of 23rd harmonic IN Content of 25th harmonic I1 Content of 25th harmonic I2 Content of 25th harmonic I3 Content of 25th harmonic IN Content of 27th harmonic I1 Content of 27th harmonic I2 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
104413_en_00
PHOENIX CONTACT
11-11
EEM-MA600 Table 11-9 Decimal address 51597 51598 51599 51600 51601 51602 51603 51604 51605 51606 51607 51608 51609 51610 51611 51612 51613 51614 51615 51616 51617 51618 51619 51620 51621 51622 51623 51624 51625 51626 51627 51628 51629 51630 51631 51632 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C98D C98E C98F C990 C991 C992 C993 C994 C995 C996 C997 C998 C999 C99A C99B C99C C99D C99E C99F C9A0 C9A1 C9A2 C9A3 C9A4 C9A5 C9A6 C9A7 C9A8 C9A9 C9AA C9AB C9AC C9AD C9AE C9AF C9B0 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 27th harmonic I3 Content of 27th harmonic IN Content of 29th harmonic I1 Content of 29th harmonic I2 Content of 29th harmonic I3 Content of 29th harmonic IN Content of 31st harmonic I1 Content of 31st harmonic I2 Content of 31st harmonic I3 Content of 31st harmonic IN Content of 33rd harmonic I1 Content of 33rd harmonic I2 Content of 33rd harmonic I3 Content of 33rd harmonic IN Content of 35th harmonic I1 Content of 35th harmonic I2 Content of 35th harmonic I3 Content of 35th harmonic IN Content of 37th harmonic I1 Content of 37th harmonic I2 Content of 37th harmonic I3 Content of 37th harmonic IN Content of 39th harmonic I1 Content of 39th harmonic I2 Content of 39th harmonic I3 Content of 39th harmonic IN Content of 41st harmonic I1 Content of 41st harmonic I2 Content of 41st harmonic I3 Content of 41st harmonic IN Content of 43rd harmonic I1 Content of 43rd harmonic I2 Content of 43rd harmonic I3 Content of 43rd harmonic IN Content of 45th harmonic I1 Content of 45th harmonic I2 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
11-12
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-9 Decimal address 51633 51634 51635 51636 51637 51638 51639 51640 51641 51642 51643 51644 51645 51646 51647 51648 51649 51650 51651 51652 51653 51654 51655 51656 51657 51658 51659 51660 51661 51662 51663 51664 51665 51666 51667 51668 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C9B1 C9B2 C9B3 C9B4 C9B5 C9B6 C9B7 C9B8 C9B9 C9BA C9BB C9BC C9BD C9BE C9BF C9C0 C9C1 C9C2 C9C3 C9C4 C9C5 C9C6 C9C7 C9C8 C9C9 C9CA C9CB C9CC C9CD C9CE C9CF C9D0 C9D1 C9D2 C9D3 C9D4 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 45th harmonic I3 Content of 45th harmonic IN Content of 47th harmonic I1 Content of 47th harmonic I2 Content of 47th harmonic I3 Content of 47th harmonic IN Content of 49th harmonic I1 Content of 49th harmonic I2 Content of 49th harmonic I3 Content of 49th harmonic IN Content of 51st harmonic I1 Content of 51st harmonic I2 Content of 51st harmonic I3 Content of 51st harmonic IN Content of 53rd harmonic I1 Content of 53rd harmonic I2 Content of 53rd harmonic I3 Content of 53rd harmonic IN Content of 55th harmonic I1 Content of 55th harmonic I2 Content of 55th harmonic I3 Content of 55th harmonic IN Content of 57th harmonic I1 Content of 57th harmonic I2 Content of 57th harmonic I3 Content of 57th harmonic IN Content of 59th harmonic I1 Content of 59th harmonic I2 Content of 59th harmonic I3 Content of 59th harmonic IN Content of 61st harmonic I1 Content of 61st harmonic I2 Content of 61st harmonic I3 Content of 61st harmonic IN Content of 63rd harmonic I1 Content of 63rd harmonic I2 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
104413_en_00
PHOENIX CONTACT
11-13
EEM-MA600 Table 11-9 Decimal address 51669 51670 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C9D5 C9D6 Number Designation of data words 1 1 Content of 63rd harmonic I3 Content of 63rd harmonic IN Unit Register Available through access extension module R R
0.10% 0.10%
Range extension: 125 words (decimal) or 7D words (hexadecimal) Individual harmonic content for line voltages: U (phase/phase) 51671 51672 51673 51674 51675 51676 51677 51678 51679 51680 51681 51682 51683 51684 51685 51686 51687 51688 51689 51690 51691 51692 51693 51694 51695 51696 51697 51698 51699 51700 51701 51702 C9D7 C9D8 C9D9 C9DA C9DB C9DC C9DD C9DE C9DF C9E0 C9E1 C9E2 C9E3 C9E4 C9E5 C9E6 C9E7 C9E8 C9E9 C9EA C9EB C9EC C9ED C9EE C9EF C9F0 C9F1 C9F2 C9F3 C9F4 C9F5 C9F6 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Highest ascertainable harmonic (63) Content of 3rd harmonic U12 Content of 3rd harmonic U23 Content of 3rd harmonic U31 Content of 5th harmonic U12 Content of 5th harmonic U23 Content of 5th harmonic U31 Content of 7th harmonic U12 Content of 7th harmonic U23 Content of 7th harmonic U31 Content of 9th harmonic U12 Content of 9th harmonic U23 Content of 9th harmonic U31 Content of 11th harmonic U12 Content of 11th harmonic U23 Content of 11th harmonic U31 Content of 13th harmonic U12 Content of 13th harmonic U23 Content of 13th harmonic U31 Content of 15th harmonic U12 Content of 15th harmonic U23 Content of 15th harmonic U31 Content of 17th harmonic U12 Content of 17th harmonic U23 Content of 17th harmonic U31 Content of 19th harmonic U12 Content of 19th harmonic U23 Content of 19th harmonic U31 Content of 21st harmonic U12 Content of 21st harmonic U23 Content of 21st harmonic U31 Content of 23rd harmonic U12 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
11-14
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-9 Decimal address 51703 51704 51705 51706 51707 51708 51709 51710 51711 51712 51713 51714 51715 51716 51717 51718 51719 51720 51721 51722 51723 51724 51725 51726 51727 51728 51729 51730 51731 51732 51733 51734 51735 51736 51737 51738 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address C9F7 C9F8 C9F9 C9FA C9FB C9FC C9FD C9FE C9FF CA00 CA01 CA02 CA03 CA04 CA05 CA06 CA07 CA08 CA09 CA0A CA0B CA0C CA0D CA0E CA0F CA10 CA11 CA12 CA13 CA14 CA15 CA16 CA17 CA18 CA19 CA1A Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 23rd harmonic U23 Content of 23rd harmonic U31 Content of 25th harmonic U12 Content of 25th harmonic U23 Content of 25th harmonic U31 Content of 27th harmonic U12 Content of 27th harmonic U23 Content of 27th harmonic U31 Content of 29th harmonic U12 Content of 29th harmonic U23 Content of 29th harmonic U31 Content of 31st harmonic U12 Content of 31st harmonic U23 Content of 31st harmonic U31 Content of 33rd harmonic U12 Content of 33rd harmonic U23 Content of 33rd harmonic U31 Content of 35th harmonic U12 Content of 35th harmonic U23 Content of 35th harmonic U31 Content of 37th harmonic U12 Content of 37th harmonic U23 Content of 37th harmonic U31 Content of 39th harmonic U12 Content of 39th harmonic U23 Content of 39th harmonic U31 Content of 41st harmonic U12 Content of 41st harmonic U23 Content of 41st harmonic U31 Content of 43rd harmonic U12 Content of 43rd harmonic U23 Content of 43rd harmonic U31 Content of 45th harmonic U12 Content of 45th harmonic U23 Content of 45th harmonic U31 Content of 47th harmonic U12 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
104413_en_00
PHOENIX CONTACT
11-15
EEM-MA600 Table 11-9 Decimal address 51739 51740 51741 51742 51743 51744 51745 51746 51747 51748 51749 51750 51751 51752 51753 51754 51755 51756 51757 51758 51759 51760 51761 51762 51763 51764 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA1B CA1C CA1D CA1E CA1F CA20 CA21 CA22 CA23 CA24 CA25 CA26 CA27 CA28 CA29 CA2A CA2B CA2C CA2D CA2E CA2F CA30 CA31 CA32 CA33 CA34 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 47th harmonic U23 Content of 47th harmonic U31 Content of 49th harmonic U12 Content of 49th harmonic U23 Content of 49th harmonic U31 Content of 51st harmonic U12 Content of 51st harmonic U23 Content of 51st harmonic U31 Content of 53rd harmonic U12 Content of 53rd harmonic U23 Content of 53rd harmonic U31 Content of 55th harmonic U12 Content of 55th harmonic U23 Content of 55th harmonic U31 Content of 57th harmonic U12 Content of 57th harmonic U23 Content of 57th harmonic U31 Content of 59th harmonic U12 Content of 59th harmonic U23 Content of 59th harmonic U31 Content of 61st harmonic U12 Content of 61st harmonic U23 Content of 61st harmonic U31 Content of 63rd harmonic U12 Content of 63rd harmonic U23 Content of 63rd harmonic U31 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
Range extension: 94 words (decimal) or 5E words (hexadecimal) Individual harmonic content for line voltages against N: V (phase/N) 51765 51766 51767 51768 51769 51770 51771 51772 CA35 CA36 CA37 CA38 CA39 CA3A CA3B CA3C 1 1 1 1 1 1 1 1 Highest ascertainable harmonic (63) Content of 3rd harmonic V1 Content of 3rd harmonic V2 Content of 3rd harmonic V3 Content of 5th harmonic V1 Content of 5th harmonic V2 Content of 5th harmonic V3 Content of 7th harmonic V1 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% R R R R R R R R
11-16
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-9 Decimal address 51773 51774 51775 51776 51777 51778 51779 51780 51781 51782 51783 51784 51785 51786 51787 51788 51789 51790 51791 51792 51793 51794 51795 51796 51797 51798 51799 51800 51801 51802 51803 51804 51805 51806 51807 51808 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA3D CA3E CA3F CA40 CA41 CA42 CA43 CA44 CA45 CA46 CA47 CA48 CA49 CA4A CA4B CA4C CA4D CA4E CA4F CA50 CA51 CA52 CA53 CA54 CA55 CA56 CA57 CA58 CA59 CA5A CA5B CA5C CA5D CA5E CA5F CA60 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 7th harmonic V2 Content of 7th harmonic V3 Content of 9th harmonic V1 Content of 9th harmonic V2 Content of 9th harmonic V3 Content of 11th harmonic V1 Content of 11th harmonic V2 Content of 11th harmonic V3 Content of 13th harmonic V1 Content of 13th harmonic V2 Content of 13th harmonic V3 Content of 15th harmonic V1 Content of 15th harmonic V2 Content of 15th harmonic V3 Content of 17th harmonic V1 Content of 17th harmonic V2 Content of 17th harmonic V3 Content of 19th harmonic V1 Content of 19th harmonic V2 Content of 19th harmonic V3 Content of 21st harmonic V1 Content of 21st harmonic V2 Content of 21st harmonic V3 Content of 23rd harmonic V1 Content of 23rd harmonic V2 Content of 23rd harmonic V3 Content of 25th harmonic V1 Content of 25th harmonic V2 Content of 25th harmonic V3 Content of 27th harmonic V1 Content of 27th harmonic V2 Content of 27th harmonic V3 Content of 29th harmonic V1 Content of 29th harmonic V2 Content of 29th harmonic V3 Content of 31st harmonic V1 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
104413_en_00
PHOENIX CONTACT
11-17
EEM-MA600 Table 11-9 Decimal address 51809 51810 51811 51812 51813 51814 51815 51816 51817 51818 51819 51820 51821 51822 51823 51824 51825 51826 51827 51828 51829 51830 51831 51832 51833 51834 51835 51836 51837 51838 51839 51840 51841 51842 51843 51844 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA61 CA62 CA63 CA64 CA65 CA66 CA67 CA68 CA69 CA6A CA6B CA6C CA6D CA6E CA6F CA70 CA71 CA72 CA73 CA74 CA75 CA76 CA77 CA78 CA79 CA7A CA7B CA7C CA7D CA7E CA7F CA80 CA81 CA82 CA83 CA84 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 31st harmonic V2 Content of 31st harmonic V3 Content of 33rd harmonic V1 Content of 33rd harmonic V2 Content of 33rd harmonic V3 Content of 35th harmonic V1 Content of 35th harmonic V2 Content of 35th harmonic V3 Content of 37th harmonic V1 Content of 37th harmonic V2 Content of 37th harmonic V3 Content of 39th harmonic V1 Content of 39th harmonic V2 Content of 39th harmonic V3 Content of 41st harmonic V1 Content of 41st harmonic V2 Content of 41st harmonic V3 Content of 43rd harmonic V1 Content of 43rd harmonic V2 Content of 43rd harmonic V3 Content of 45th harmonic V1 Content of 45th harmonic V2 Content of 45th harmonic V3 Content of 47th harmonic V1 Content of 47th harmonic V2 Content of 47th harmonic V3 Content of 49th harmonic V1 Content of 49th harmonic V2 Content of 49th harmonic V3 Content of 51st harmonic V1 Content of 51st harmonic V2 Content of 51st harmonic V3 Content of 53rd harmonic V1 Content of 53rd harmonic V2 Content of 53rd harmonic V3 Content of 55th harmonic V1 Unit Register Available through access extension module R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
11-18
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-9 Decimal address 51845 51846 51847 51848 51849 51850 51851 51852 51853 51854 51855 51856 51857 51858 C950 hex: display of current harmonic distortion and harmonics [...] Hexadecimal address CA85 CA86 CA87 CA88 CA89 CA8A CA8B CA8C CA8D CA8E CA8F CA90 CA91 CA92 Number Designation of data words 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Content of 55th harmonic V2 Content of 55th harmonic V3 Content of 57th harmonic V1 Content of 57th harmonic V2 Content of 57th harmonic V3 Content of 59th harmonic V1 Content of 59th harmonic V2 Content of 59th harmonic V3 Content of 61st harmonic V1 Content of 61st harmonic V2 Content of 61st harmonic V3 Content of 63rd harmonic V1 Content of 63rd harmonic V2 Content of 63rd harmonic V3 Unit Register Available through access extension module R R R R R R R R R R R R R R
0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10% 0.10%
Range extension: 94 words (decimal) or 5E words (hexadecimal) Total range extension: 323 words (decimal) or 143 words (hexadecimal)
104413_en_00
PHOENIX CONTACT
11-19
EEM-MA600
CB00 hex: status of inputs/outputs Hexadecimal address CB00 CB01 Number of data words 1 1 Designation Unit Register access R R EEM-2DIO-MA600 Available through extension module
No. Digital inputs (max. 6) Bit 0: state input 1 high or low Bit 1: state input 2 high or low Bit 2: state input 3 high or low Bit 3: state input 4 high or low Bit 4: state input 5 high or low Bit 5: state input 6 high or low No. Digital outputs (max. 6) Bit 0: state output 1 high or low Bit 1: state output 2 high or low Bit 2: state output 3 high or low Bit 3: state output 4 high or low Bit 4: state output 5 high or low Bit 5: state output 6 high or low
51970 51971
CB02 CB03
1 1
R R EEM-2DIO-MA600
E000 hex: measuring instrument terminal configuration Hexadecimal Number address of data words E000 1 Designation Unit Register Available through access extension module R/W
Network type: 0: 1BL 1: 2BL 2: 3BL 3: 3NBL 4: 4BL 5: 4NBL Current transformer's secondary side: 1: 1 A/5: 5 A Current transformer's primary side Not available Not available Not available Voltage transducer present? 0: No 1: Yes
57345
E001
R/W
1 1 1 1 1
R/W
11-20
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-11 Decimal address 57351 E000 hex: measuring instrument terminal configuration [...] Hexadecimal Number address of data words E007 1 Designation Unit Register Available through access extension module R/W
Voltage transducer's secondary side: 60: 60 V 100: 100 V 110: 110 V 115: 115 V 120: 120 V 173: 173 V 190: 190 V Voltage transducer's primary side Synchronization impulse start signal Measurement duration for saving the averaged real and reactive power P+/- and Q+/-: 5 min, 8 min, 10 min, 15 min, 20 min, 30 min
2 1 1
V 1:external/ 0:internal s
Example: Table 11-12 Slave address 05 Configuring a 4 line network with an asymmetrical load (4 NBL) for the EEM-MA600 Function 06 High quality address E0 Low quality address 00 High quality register value 00 Low quality register value 05 CRC 16 7F8D
Table 11-13 Decimal address 57600 57601 57602 57603 57604 57605
E100 hex: date/time configuration Hexadecimal Number address of data words E100 E101 E102 E103 E104 E105 1 1 1 1 1 1 Designation Unit Register access R/W R/W R/W R/W R/W R/W Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
104413_en_00
PHOENIX CONTACT
11-21
EEM-MA600
E110 hex: Ethernet communication module configuration Hexadecimal address E110 Number of data words 1 Designation Unit Register access R/W Available through extension module EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 EEM-ETH-MA600 / EEM-ETH-RS485-MA600 Yes(1) / No(0) 0: 2400 bps 1: 4800 bps 2: 9600 bps 3: 19200 bps 4: 38400 bps R/W EEM-ETH-RS485-MA600 R/W EEM-ETH-MA600 / EEM-ETH-RS485-MA600
IP = CL. A, B, C, D Ethernet IP address CL. A (0-255) Ethernet IP address CL. B (0-255) Ethernet IP address CL. C (0-255) Ethernet IP address CL. D (0-255)
0 - 255
57617 57618 57619 57620 57621 57622 57623 57624 57625 57626 57627
E111 E112 E113 E114 E115 E116 E117 E118 E119 E11A E11B
1 1 1 1 1 1 1 1 1 1 1
R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W
Ethernet gateway0 - 255 address - CL. A (0-255) Ethernet gateway0 - 255 address - CL. B (0-255) Ethernet gateway0 - 255 address - CL. C (0-255) Ethernet gateway0 - 255 address - CL. D (0-255) Ethernet subnet mask CL. A (0-255) Ethernet subnet mask CL. B (0-255) Ethernet subnet mask CL. C (0-255) Ethernet subnet mask CL. D (0-255) DHCP activated Not available Not available Ethernet gateway: JBUS/MODBUS interface speed 0: 2400 bps 1: 4800 bps 2: 9600 bps 3: 19200 bps 4: 38400 bps 0 - 255 0 - 255 0 - 255 0 - 255
1 1 1 1
11-22
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-14 Decimal address 57632 E110 hex: Ethernet communication module configuration [...] Hexadecimal address E120 Number of data words 1 Designation Unit Register access R/W Available through extension module EEM-ETH-RS485-MA600
Ethernet gateway: JBUS/MODBUS interface parity 0: none 1: even 2: odd Ethernet gateway: JBUS/MODBUS interface stop bit Not available Ethernet gateway: JBUS/MODBUS slave address
57633
E121
R/W
EEM-ETH-RS485-MA600
57634 57635
E122 E123
1 1
R/W
EEM-ETH-RS485-MA600
Table 11-15
E200 hex: saving configuration and restart for measuring instrument Unit Register access W Available through extension module
Decimal Hexadecimal Number Designation address address of data words 57856 E200 1 Action: 0xA1: save settings in EEPROM 0xB2: restart measuring instrument
Example: Table 11-16 Slave address 05 After changing the configuration parameters, the following command lets them be saved Function 06 High quality address E2 Low quality address 00 High quality register value 00 Low quality register value A1 CRC 16 7F8E
104413_en_00
PHOENIX CONTACT
11-23
EEM-MA600
7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) Hexadecimal Number Designation address of data words Unit Register Available through access extension module
R
0: / 1: mA 2: mA 3: mA 4: mA 5: mV 6: mV 7: mV 8: mW 9: mvar 10: mVA 11: Hz/1000 12: SPFL 15: /1000 16: /1000 17: /1000 18: /1000 19: /1000 20: /1000 21: h/100 22: mV 23: mV 24: mV 25: /1000 26: /1000 27: /1000 28: /1000 31: SPFL 32: C 33: C 34: C 35: C 36: kW/100 37: kvar/100 38: kVA/100
EEM-2DIO-MA600
11-24
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-17 Decimal address 30465 30467 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7701 7703 2 1 OUT 1 Current alarm: lowest measured value OUT 1 Current alarm, upper threshold: output types, see lower threshold current alarm OUT 1 Current alarm: highest measured value OUT 1 Current alarm: duration OUT 1 Alarm n-1: lower threshold: output types, see lower threshold current alarm Unit Register Available through access extension module R R EEM-2DIO-MA600 EEM-2DIO-MA600
/ Units, see lower threshold current alarm / s Units, see lower threshold current alarm / /
2 1 1
R R R
30472 30474
7708 770 A
2 1
OUT 1 Alarm n-1: lowest measured value OUT 1 Alarm n-1: upper threshold: output types, see lower threshold current alarm OUT 1 Alarm n-1: highest measured value OUT 1 Alarm n-1: duration OUT 1 Alarm n-2: lower threshold: output types, see lower threshold current alarm
R R
EEM-2DIO-MA600 EEM-2DIO-MA600
2 1 1
R R R
30479 30481
770F 7711
2 1
OUT 1 Alarm n-2: lowest measured value OUT 1 Alarm n-2: upper threshold: output types, see lower threshold current alarm OUT 1 Alarm n-2: highest measured value OUT 1 Alarm n-2: duration OUT 1 Alarm n-3: lower threshold: output types, see lower threshold current alarm
R R
EEM-2DIO-MA600 EEM-2DIO-MA600
2 1 1
R R R
30486
7716
EEM-2DIO-MA600
104413_en_00
PHOENIX CONTACT
11-25
EEM-MA600 Table 11-17 Decimal address 30488 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7718 1 OUT 1 Alarm n-3: upper threshold: output types, see lower threshold current alarm OUT 1 Alarm n-3: highest measured value OUT 1 Alarm n-3: duration Unit Register Available through access extension module R EEM-2DIO-MA600
30489 30491
7719 771B
2 1
/ s
R R
EEM-2DIO-MA600 EEM-2DIO-MA600
OUT 2: Alarm to digital extension module 2 30492 30493 30495 771C 771D 771F 1 2 1 OUT 2 Current alarm: output types, see OUT 1 OUT 2 Current alarm: lowest measured value OUT 2 Current alarm: upper threshold: output types, see OUT 1 OUT 2 Current alarm: highest measured value OUT 2 Current alarm: duration OUT 2 Alarm n-1: lower threshold: output types, see OUT 1 OUT 2 Alarm n-1: lowest measured value OUT 2 Alarm n-1: upper threshold: output types, see OUT 1 OUT 2 Alarm n-1: highest measured value OUT 2 Alarm n-1: duration OUT 2 Alarm n-2: lower threshold: output types, see OUT 1 OUT 2 Alarm n-2: lowest measured value OUT 2 Alarm n-2: upper threshold: output types, see OUT 1 OUT 2 Alarm n-2: highest measured value OUT 2 Alarm n-2: duration OUT 2 Alarm n-3: lower threshold: output types, see OUT 1 OUT 2 Alarm n-3: lowest measured value OUT 2 Alarm n-3: upper threshold: output types, see OUT 1 / / / / / s / / / s Units, see OUT 1 / / R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600
30496 30498 30499 30500 30502 30503 30505 30506 30507 30509 30510 30512 30513 30514 30516
7720 7722 7723 7724 7726 7727 7729 772 A 772B 772D 772E 7730 7731 7732 7734
2 1 1 2 1 2 1 1 2 1 2 1 1 2 1
/ s
R R R R R R R R R R R R R R R
EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600
11-26
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-17 Decimal address 30517 30519 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7735 7737 2 1 OUT 2 Alarm n-3: highest measured value OUT 2 Alarm n-3: duration Unit Register Available through access extension module R R EEM-2DIO-MA600 EEM-2DIO-MA600
/ s
OUT 3: Alarm to digital extension module 3 30520 30521 30523 30524 30526 7738 7739 773B 773C 773E 1 2 1 2 1 OUT 3 Current alarm: output types, see OUT 1 OUT 3 Current alarm: lowest measured value OUT 3 Current alarm: upper threshold: output types, see OUT 1 OUT 3 Current alarm: highest measured value OUT 3 Current alarm: duration Units, see OUT 1 / / / s R R R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600
OUT 4: Alarm to digital extension module 4 30527 30528 30530 773F 7740 7742 1 2 1 OUT 4 Current alarm: output types, see OUT 1 OUT 4 Current alarm: lowest measured value OUT 4 Current alarm: upper threshold: output types, see OUT 1 OUT 4 Current alarm: highest measured value OUT 4 Current alarm: duration Units, see OUT 1 / / R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600
30531 30533
7743 7745
2 1
/ s
R R
EEM-2DIO-MA600 EEM-2DIO-MA600
OUT 5: Alarm to digital extension module 5 30534 30535 30537 7746 7747 7749 1 2 1 OUT 5 Current alarm: output types, see OUT 1 OUT 5 Current alarm: lowest measured value OUT 5 Current alarm: upper threshold: output types, see OUT 1 OUT 5 Current alarm: highest measured value OUT 5 Current alarm: duration Units, see OUT 1 / / R R R EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600
30538 30540
774 A 774C
2 1
/ s
R R
EEM-2DIO-MA600 EEM-2DIO-MA600
OUT 6: Alarm to digital extension module 6 30541 30542 774D 774E 1 2 OUT 6 Current alarm: output types, see OUT 1 OUT 6 Current alarm: lowest measured value Units, see OUT 1 / R R EEM-2DIO-MA600 EEM-2DIO-MA600
104413_en_00
PHOENIX CONTACT
11-27
EEM-MA600 Table 11-17 Decimal address 30544 7700 hex: display of last alarm to digital outputs (EEM-2DIO-MA600) [...] Hexadecimal Number Designation address of data words 7750 1 OUT 6 Current alarm: upper threshold: output types, see OUT 1 OUT 6 Current alarm: highest measured value OUT 6 Current alarm: duration Unit Register Available through access extension module R EEM-2DIO-MA600
30545 30547
7751 7753
2 1
/ s
R R
EEM-2DIO-MA600 EEM-2DIO-MA600
100 hex: information about connected extension modules Hexadecimal Number Designation address of data words 100 101 102 1 1 1 Not available Manufacturer code Slot 1 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600 Slot 2: see slot 1 Slot 3: see slot 1 Slot 4: see slot 1 Software version Serial number R R Unit Register Available through access extension module
1 1 1 1 4
R R R R R
11-28
PHOENIX CONTACT
104413_en_00
MODBUS register
Table 11-19
200 hex: extension module display and configuration Designation Unit Register access R/W Available through extension module
1 1 1 2
Current transformer's secondary side: A 1: 1 A/5: 5 A Current transformer's primary side Voltage transducer present? 0: No 1: Yes Voltage transducer's secondary side: 60: 60 V 100: 100 V 110: 110 V 115: 115 V 120: 120 V 173: 173 V 190: 190 V Voltage transducer's primary side Measurement duration to average value/maximum accumulation of value for current: (2 s, 10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Measurement duration to average value/maximum accumulation of value for P,Q,S power: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Not available s A
R/W R/W
518 519
206 207
1 1
R/W
520
208
R/W
Analog extension module EEM-2AO-MA600 527 20F 1 Output signal AO OUT 1: 0: 0/20 mA 1: 4/20 mA 2: 30 V R/W EEM-2AO-MA600
104413_en_00
PHOENIX CONTACT
11-29
EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W 0: A 1: A 2: A 3: A 4: V 5: V 6: V 7: W 8: var 9: VA 10: 1/1000 11: V 12: V 13: V 14: Hz 15: 1/1000 16: A 17: V 18: V 19: W 20: var 21: VA 22: C 23: C 24: C 25: C R/W R/W EEM-2AO-MA600 EEM-2AO-MA600 Available through extension module EEM-2AO-MA600
Output type AO OUT 1: 0: I1: power 1: I2: power 2: I3: power 3: In: neutral conductor power 4: U12: line voltages (1-2) 5: U23: Line voltages (2-3) 6: U31: Line voltages (3-1) 7: P: Real power sum 8: Q: Reactive power sum 9: S: Apparent power sum 10: PFL: Inductive power factor sum 11: V1: Line voltages against N 12: V2: Line voltages against N 13: V3: Line voltages against N 14: F: Frequency 15: PFC: Capacitive power factor sum 16: I: Power I1, I2, I3 17: U: Line voltage (1-2/2-3/3-1) 18: V: Line voltage against N (1/2/3) 19: PPR: Total real power (trend) 20: QPR: Total reactive power (trend) 21: SPR: Total apparent power (trend) 22: TC1: Temperature module input EEM-TEMP-MA600 23: TC2: Temperature module input EEM-TEMP-MA600 24: TC3: Temperature module input EEM-TEMP-MA600 25: TC4: internal temperature EEMTEMP-MA600 AO OUT 1 output value for 0 or 4mA AO OUT 1 unit of output value for 0 or 4 mA: 0: / 1: k 2: M Output value AO OUT 1 for 20 mA AO OUT 1 unit of output value for 20 mA: 0: / 1: k 2: M
529 530
211 212
1 1
531 532
213 214
1 1
R/W R/W
EEM-2AO-MA600 EEM-2AO-MA600
11-30
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2AO-MA600
Output signal AO OUT 2: 0: 0/20 mA 1: 4/20 mA 2: 30 V Output type AO OUT 2: see AO OUT 1 AO OUT 2 output value for 0 or 4 mA AO OUT 2 unit of output value for 0 or 4 mA: 0: / 1: k 2: M AO OUT 2 output value for 20 mA AO OUT 2 unit of output value for 20 mA: 0: / 1: k 2: M Output signal AO OUT 3: 0: 0/20 mA 1: 4/20 mA 2: 30 V Output type AO OUT 3: see AO OUT 1 AO OUT 3 output value for 0 or 4 mA AO OUT 3 unit of output value for 0 or 4 mA: 0: / 1: k 2: M Output value AO OUT 3 for 20 mA AO OUT 2 unit of output value for 20 mA: 0: / 1: k 2: M Output signal AO OUT 4: 0: 0/20 mA 1: 4/20 mA 2: 30 V Output type AO OUT 4: see AO OUT 1 AO OUT 4 output value for 0 or 4 mA
1 1 1
537 538
219 21 A
1 1
R/W R/W
EEM-2AO-MA600 EEM-2AO-MA600
539
21B
R/W
EEM-2AO-MA600
1 1 1
543 544
21F 220
1 1
R/W R/W
EEM-2AO-MA600 EEM-2AO-MA600
545
221
R/W
EEM-2AO-MA600
546 547
222 223
1 1
R/W R/W
EEM-2AO-MA600 EEM-2AO-MA600
104413_en_00
PHOENIX CONTACT
11-31
EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2AO-MA600
AO OUT 4 unit of output value for 0 or 4 mA: 0: / 1: k 2: M Output value AO OUT 4 for 20 mA AO OUT 4 unit of output value for 20 mA: 0: / 1: k 2: M
549 550
225 226
1 1
R/W R/W
EEM-2AO-MA600 EEM-2AO-MA600
11-32
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access Available through extension module
Digital extension module EEM-2DIO-MA600 551 227 1 Output type DO OUT 1: 0: CDE: Controlling relay state via RS485 1: I: Current I1, I2, I3 2: U: Line voltages (1-2/2-3/3-1) 3: P+: Total positive real power 4: Q+: Total positive reactive power 5: S: Total apparent power 6: F: Frequency 7: PFL: Total inductive power factor 8: THDI: Total harmonic distortion for currents I1, I2, I3 9: THDU: Total harmonic distortion for line voltages (1-2/2-3/3-1) 10: In: Neutral conductor current 11: HOUr: Operating hours counter 12: V: Line voltages against N (1/2/3) 13: THD In: Total harmonic distortion of neutral conductor current 14: THDV: Total harmonic distortion of line voltages against N (1 / 2 / 3) 15: P-: Total negative real power 16: Q-: Total negative reactive power 17: PFC: Total capacitive power factor 18: CDT: Controlling relay status via RS485, resetting relay to idle 19: TC1: Input temperature module EEM-TEMP-MA600 20: TC2: Input temperature module EEM-TEMP-MA600 21: TC3: Input temperature module EEM-TEMP-MA600 22: TC4: Internal temperature EEMTEMP-MA600 23: PPR: Total real power (trend) 24: QPR: Total reactive power (trend) 25: SPR: Total apparent power (trend) DO OUT 1 alarm output value for lower switching threshold DO OUT 1 output value unit for the lower switching threshold 0: / 1: k 2: M R/W 0: / 1: A 2: V 3: W 4: var 5: VA 6: 1/10 Hz 7: 1/100 8: % 9: % 10: A 11: h 12: V 13: % 14: % 15: W 16: var 17: 1/100 18: / 19: C 20: C 21: C 22: C 23: W 24: var 25: VA R/W R/W EEM-2DIO-MA600 EEM-2DIO-MA600
552 553
228 229
1 1
104413_en_00
PHOENIX CONTACT
11-33
EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W R/W Available through extension module EEM-2DIO-MA600 EEM-2DIO-MA600
Decimal Hexadecimal Number address address of data words 554 555 22 A 22B 1 1
DO OUT 1 alarm output value for upper switching threshold DO OUT 1 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 1 hysteresis (0-99) DO OUT 1 response delay (0-999) DO OUT 1 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 2: see DO OUT 1 DO OUT 2 alarm output value for lower switching threshold DO OUT 2 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 2 alarm output value for upper switching threshold DO OUT 2 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 2 hysteresis (0-99) DO OUT 2 response delay (0-999) DO OUT 2 relay idle: 0: NO (open) 1: NC (closed) Not available Not available Not available Not available Not available Not available % s % s
1 1 1
1 1 1
562 563
232 233
1 1
R/W R/W
EEM-2DIO-MA600 EEM-2DIO-MA600
1 1 1
1 1 1 1 1 1
11-34
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2DIO-MA600
Measurement duration to average value/maximum accumulation of value for line voltages U: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Measurement duration to average value/maximum accumulation of value for frequency F: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Save averaged positive real power P+: 0: No 1: Yes Save averaged negative real power P+: 0: No 1: Yes Store averaged positive reactive power Q+: 0: No 1: Yes Store averaged negative reactive power Q-: 0: No 1: Yes Synchronization impulse start signal Measurement duration for saving the averaged real and reactive power P+/- and Q+/-: 5 min, 8 min, 10 min, 15 min, 20 min, 30 min Output type DO OUT 3: see DO OUT 1 DO OUT 3 alarm output value for lower switching threshold DO OUT 3 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 3 alarm output value for upper switching threshold
574
23E
R/W
EEM-2DIO-MA600
575
23F
R/W
EEM-MEMOMA600
576
240
R/W
EEM-MEMOMA600
577
241
R/W
EEM-MEMOMA600
578
242
R/W
EEM-MEMOMA600
579 580
243 244
1 1
1:external/ 0:internal s
R/W R/W
EEM-MEMOMA600 EEM-MEMOMA600
1 1 1
584
248
R/W
EEM-2DIO-MA600
104413_en_00
PHOENIX CONTACT
11-35
EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2DIO-MA600
DO OUT 3 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 3 hysteresis (0-99) DO OUT 3 response delay (0-999) DO OUT 3 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 4: see DO OUT 1 DO OUT 4 alarm output value for lower switching threshold DO OUT 4 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 4 alarm output value for upper switching threshold DO OUT 4 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 4 hysteresis (0-99) DO OUT 4 response delay (0-999) DO OUT 4 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 5: see DO OUT 1 DO OUT 5 alarm output value for lower switching threshold DO OUT 5 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 5 alarm output value for upper switching threshold % s % s
24 A 24B 24C
1 1 1
1 1 1
592 593
250 251
1 1
R/W R/W
EEM-2DIO-MA600 EEM-2DIO-MA600
1 1 1
1 1 1
600
258
R/W
EEM-2DIO-MA600
11-36
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W Available through extension module EEM-2DIO-MA600
DO OUT 5 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 5 hysteresis (0-99) DO OUT 5 response delay (0-999) DO OUT 5 relay idle: 0: NO (open) 1: NC (closed) Output type DO OUT 6: see DO OUT 1 DO OUT 6 alarm output value for lower switching threshold DO OUT 6 output value unit for the lower switching threshold 0: / 1: k 2: M DO OUT 6 alarm output value for upper switching threshold DO OUT 6 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 6 hysteresis (0-99) DO OUT 6 response delay (0-999) DO OUT 6 relay idle: 0: NO (open) 1: NC (closed) % s % s
25 A 25B 25C
1 1 1
1 1 1
608 609
260 261
1 1
R/W R/W
EEM-2DIO-MA600 EEM-2DIO-MA600
1 1 1
Memory module EEM-MEMO-MA600 613 614 615 616 617 265 266 267 268 269 1 1 1 1 1 Threshold value for acquiring undervoltages (SAG) Hysteresis of threshold value undervoltages (SAG) Threshold value for acquiring surge voltages (SWELL) Hysteresis of threshold value surge voltages (SWELL) Not available % % % % R/W R/W R/W R/W R/W
104413_en_00
PHOENIX CONTACT
11-37
EEM-MA600 Table 11-19 200 hex: extension module display and configuration [...] Designation Unit Register access R/W R/W Available through extension module
Decimal Hexadecimal Number address address of data words 618 619 26 A 26B 1 1
11-38
PHOENIX CONTACT
104413_en_00
MODBUS register
400 hex: reset measured values Hexadecimal address 400 Number of data words 1 Designation Unit Register Available through access extension module W
Reset: / max/avg I1,I2,I3: maximum value of current (I1, I2, I3): 0x1 max/avg P+: maximum total positive real power value: 0x2 max/avg P-: maximum total negative real power value: 0x4 max/avg Q+: maximum total positive reactive power value: 0x8 max/avg Q-: maximum total negative reactive power value: 0x10 max/avg S: maximum total apparent power value: 0x20 HOUr: Operating hours counter: 0x40 EA+: current positive real energy kWh+: 0x80 ER+: current positive reactive energy kvarh+: 0x100 ES: current apparent energy kVAh: 0x200 EA-: current negative real energy kWh-: 0x400 ER-: current negative reactive energy kvarh-: 0x800 All measured values: 0x1000 max/avg U12, U23, U31: maximum line voltage value (U12, U23, U31): 0x2000 max/avg V1, V2, V3: maximum value of line voltages against N (V1, V2, V3): 0x4000 max/avg F: maximum frequency value: 0x8000
104413_en_00
PHOENIX CONTACT
11-39
EEM-MA600 Table 11-20 Decimal address 1025 400 hex: reset measured values [...] Hexadecimal address 401 Number of data words 1 Designation Unit Register Available through access extension module W
Reset: / E1: Counter status digital input 1: 0x1 E2: Counter status digital input 2: 0x2 E3: Counter status digital input 3: 0x4 E4: Counter status digital input 4: 0x8 E5: Counter status digital input 5: 0x10 E6: Counter status digital input 6: 0x20 Min./Max. I: Min./Max. current from I1, I2, or I3: 0x40 Min./Max. In: Min./Max. neutral conductor current: 0x80 Min./Max. U: Min./Max. line voltage from U12, U23, or U31: 0x100 Min./Max. F: Min./Max. frequency value: 0x200 Min./Max. PF: Min./Max. power factor (total): 0x400 Min./Max. P: Min./Max. positive and negative real power (total): 0x800 Min./Max. Q: Min./Max. positive und negative reactive power (total): 0x1000 Min./Max. THD I: Min./Max. total harmonic distortion of currents from I1, I2, or I3: 0x2000 Min./Max. THD IN: Min./Max. total harmonic distortion of current from neutral conductor current: 0x4000 Min./Max. THD U: Min./Max. total harmonic distortion of line voltages from U12, U23, or U31: 0x8000
11-40
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-20 Decimal address 400 hex: reset measured values [...] Hexadecimal address Number of data words Designation Unit Register Available through access extension module
1026
402
Reset: / Min/Max S: Min./Max. apparent power (total) 0x0001 Min/Max V: Min./Max. line voltage against N from V1, V2, or V3: 0x0002 Min/Max THD V: Min./Max. total harmonic distortion of line voltages against N from V1, V2, or V3: 0x0004 External input (storage module): 0x0008 10 last saved alarms (storage module): 0x0010 10 last saved undervoltages (storage module): 0x0020 10 last saved surge voltages (storage module): 0x0040 10 last saved voltage failures (storage module): 0x0080
If you want to reset several parameters concurrently, you must add the numbers to the "Designation" column, for example: Resetting max. P+ and kvarh +: 2 + 100 = 102. (Hex)" Example: The following data sequence allows all saved values to be reset:" Slave address 05 Function 06 High quality address 04 Low quality address 00 High quality register value 10 Low quality register value 00 CRC 16 84BE
104413_en_00
PHOENIX CONTACT
11-41
EEM-MA600
Table 11-21
C10 hex: alarm history display (course of last 10 alarms) Number of data words Designation Unit Register access Available through extension module
Decimal Hexadecimal address address Stored alarm n-1 3088 3089 C10 C11
1 1
Output 1-6 alarm Alarm n-1: lower threshold (output type): 0: no alarm 1: I1: current 2: I2: current 3: I3: current 4: In: neutral conductor current 5: U12: line voltages (1-2) 6: U23: line voltages (2-3) 7: U31: line voltages (3-1) 8: P: total real power 9: Q: total reactive power 10: S: total apparent power 11: F: frequency 12: PFL: total inductive power factor 15: THD I1: total harmonic distortion of current 16: THD I2: total harmonic distortion of current 17: THD I3: total harmonic distortion of current 18: THD U12: total harmonic distortion of line voltage 19: THD U23: total harmonic distortion of line voltage 20: THD U31: total harmonic distortion of line voltage 21: HOUr: operating hours counter 22: V1: line voltages against N 23: V2: line voltages against N 24: V3: line voltages against N 25: THD IN: total harmonic distortion of neutral conductor current Alarm n-1: lowest measured value Alarm n-1: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-1: highest measured value Duration Day Month Year Hour s
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
3090 3092
C12 C14
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 1 1 1 1 1
R R R R R R
11-42
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 1 Designation Unit Register access R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600
Minute Second
Stored alarm n-2 3102 3103 C1E C1F 1 1 Output 1-6 alarm Alarm n-2: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-2: lowest measured value Alarm n-2: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-2: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600
3105 3106
C21 C22
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 1 1 1 1 1 1 1
R R R R R R R R
Stored alarm n-3 3116 3117 C2C C2D 1 1 Output 1-6 alarm Alarm n-3: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-3: lowest measured value: Alarm n-3: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-3: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600
3118 3119
C2E C2F
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
1 2 1 1 1 1 1 1
R R R R R R R R
104413_en_00
PHOENIX CONTACT
11-43
EEM-MA600 Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 Designation Unit Register access R Available through extension module EEM-MEMO-MA600
Alarm n-4: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-4: lower threshold value: Alarm n-4: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-4: highest measured value Duration Day Month Year Hour Minute Second s
3132 3134
C3C C3D
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
1 2 1 1 1 1 1 1
R R R R R R R R
Stored alarm n-5 3144 3145 C48 C49 1 1 Output 1-6 alarm Alarm n-5: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-5: lowest measured value: Alarm n-5: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-5: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600
3146 3147
C4A C4B
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
1 2 1 1 1 1 1 1
R R R R R R R R
Stored alarm n-6 3158 3159 C56 C57 1 1 Output 1-6 alarm Alarm n-6: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-6: lowest measured value: R R EEM-MEMO-MA600 EEM-MEMO-MA600
3160
C58
EEM-MEMO-MA600
11-44
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 2 Designation Unit Register access R Available through extension module EEM-MEMO-MA600
Alarm n-6: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-6: highest measured value Duration Day Month Year Hour Minute Second s
1 2 1 1 1 1 1 1
R R R R R R R R
Stored alarm n-7 3172 3173 C64 C65 1 1 Output 1-6 alarm Alarm n-7: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-7: lowest measured value: Alarm n-7: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-7: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600
3174 3175
C66 C67
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
1 2 1 1 1 1 1 1
R R R R R R R R
Stored alarm n-8 3186 3187 C72 C73 1 1 Output 1-6 alarm Alarm n-8: lower threshold: Output types, see alarm n-1: lower threshold Alarm n-8: lowest measured value: Alarm n-8: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-8: highest measured value Duration s R R EEM-MEMO-MA600 EEM-MEMO-MA600
3188 3189
C74 C75
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
3191 3192
C77 C78
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
104413_en_00
PHOENIX CONTACT
11-45
EEM-MA600 Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 1 1 1 1 1 Designation Unit Register access R R R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Decimal Hexadecimal address address 3194 3195 3196 3197 3198 3199 C7A C7B C7C C7D C7E C7F
Stored alarm n-9 3200 3201 C80 C81 1 1 Output 1-6 alarm Alarm n-9: lower threshold: Output types, see alarm n-1 lower threshold Alarm n-9: lowest measured value: Alarm n-9: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-9: highest measured value Duration Day Month Year Hour Minute Second s R R EEM-MEMO-MA600 EEM-MEMO-MA600
3202 3203
C82 C83
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
1 2 1 1 1 1 1 1
R R R R R R R R
Stored alarm n-10 3214 3215 C8E C8F 1 1 Output 1-6 alarm Alarm n-10: lower threshold: Output types, see alarm n-1 lower threshold Alarm n-10: lowest measured value Alarm n-10: upper threshold: Output types, see alarm n-1: lower threshold Alarm n-10: highest measured value Duration Day Month Year Hour s R R EEM-MEMO-MA600
3216 3217
C90 C91
1 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
1 2 1 1 1 1
R R R R R R
11-46
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-21 C10 hex: alarm history display (course of last 10 alarms) [...] Number of data words 1 1 Designation Unit Register access R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600
Minute Second
D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) Hexadecimal address Number Designation of data words Unit Register access Available through extension module
Threshold value shortfall n-1 3328 D00 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3329 3331
D01 D03
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value shortfall n-2 3342 D0E 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value R EEM-MEMO-MA600
3343
D0F
EEM-MEMO-MA600
104413_en_00
PHOENIX CONTACT
11-47
EEM-MA600 Table 11-22 Decimal address 3345 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D11 Number Designation of data words 1 Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms Unit Register access R Available through extension module EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value shortfall n-3 3356 D1C 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3357 3359
D1D D1F
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
11-48
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-22 Decimal address D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address Number Designation of data words Unit Register access Available through extension module
Threshold value shortfall n-4 3370 D2A 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3371 3373
D2B D2D
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value shortfall n-5 3384 D38 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year ms R EEM-MEMO-MA600
3385 3387
D39 D3B
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1
R R R R R
104413_en_00
PHOENIX CONTACT
11-49
EEM-MA600 Table 11-22 Decimal address 3395 3396 3397 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D43 D44 D45 Number Designation of data words 1 1 1 Hour Minute Second Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Threshold value shortfall n-6 3398 D46 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3399 3401
D47 D49
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value shortfall n-7 3412 D54 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration ms R EEM-MEMO-MA600
3413 3415
D55 D57
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
3416 3418
D58 D5A
2 2
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
11-50
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-22 Decimal address 3420 3421 3422 3423 3424 3425 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D5C D5D D5E D5F D60 D61 Number Designation of data words 1 1 1 1 1 1 Day Month Year Hour Minute Second Unit Register access R R R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Threshold value shortfall n-8 3426 D62 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3427 3429
D63 D65
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value shortfall n-9 3440 D70 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value R EEM-MEMO-MA600
3441
D71
EEM-MEMO-MA600
104413_en_00
PHOENIX CONTACT
11-51
EEM-MA600 Table 11-22 Decimal address 3443 D00 hex: undervoltage (course of last 10 SAG threshold value undervoltages) [...] Hexadecimal address D73 Number Designation of data words 1 Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms Unit Register access R Available through extension module EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value shortfall n-10 3454 D7E 1 Threshold value shortfall on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value shortfall on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3455 3457
D7F D81
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
11-52
PHOENIX CONTACT
104413_en_00
MODBUS register
Table 11-23
E00 hex: surge voltage (course of last 10 SWELL surge voltages) Number of data words Designation Unit Register access Available through extension module
Threshold value exceedance n-1 3584 E00 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3585 3587
E01 E03
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value exceedance n-2 3598 E0E 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month ms R EEM-MEMO-MA600
3599 3601
E0F E11
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1
R R R R
104413_en_00
PHOENIX CONTACT
11-53
EEM-MA600 Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 1 1 1 1 Designation Unit Register access R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Decimal Hexadecimal address address 3608 3609 3610 3611 E18 E19 E1A E1B
Threshold value exceedance n-3 3612 E1C 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3614 3615
E1D E1F
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value exceedance n-4 3626 E2A 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value R EEM-MEMO-MA600
3627 3629
E2B E2D
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
3630
E2E
EEM-MEMO-MA600
11-54
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 2 1 1 1 1 1 1 Designation Unit Register access R R R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Decimal Hexadecimal address address 3632 3634 3635 3636 3637 3638 3639 E30 E32 E33 E34 E35 E36 E37
ms
Threshold value exceedance n-5 3640 E38 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3641 3642
E39 E3B
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value exceedance n-6 3654 E46 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value R EEM-MEMO-MA600
3655
E47
EEM-MEMO-MA600
104413_en_00
PHOENIX CONTACT
11-55
EEM-MA600 Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 1 Designation Unit Register access R Available through extension module EEM-MEMO-MA600
Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value exceedance n-7 3668 E54 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3669 3671
E55 E57
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
11-56
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words Designation Unit Register access Available through extension module
Threshold value exceedance n-8 3682 E62 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R EEM-MEMO-MA600
3683 3685
E63 E65
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
Threshold value exceedance n-9 3696 E70 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year ms R EEM-MEMO-MA600
3697 3699
E71 E73
2 1
R R
EEM-MEMO-MA600 EEM-MEMO-MA600
2 2 1 1 1
R R R R R
104413_en_00
PHOENIX CONTACT
11-57
EEM-MA600 Table 11-23 E00 hex: surge voltage (course of last 10 SWELL surge voltages) [...] Number of data words 1 1 1 Designation Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Decimal Hexadecimal address address 3707 3708 3709 E7B E7C E7D
Threshold value exceedance n-10 3710 E7E 1 Threshold value exceedance on line voltage 0: none 5: U12 6: U23 7: U31 3711 3713 E7F E81 2 1 Value Threshold value exceedance on line voltage against N 0: none 22: V1 23: V2 24: V3 Value Duration Day Month Year Hour Minute Second ms R R EEM-MEMO-MA600 EEM-MEMO-MA600 R EEM-MEMO-MA600
2 2 1 1 1 1 1 1
R R R R R R R R
F00 hex: current minimum and maximum measured values (measurement duration of 1 s) Hexadecimal address F00 F02 F03 F04 F05 Number of data words 2 1 1 1 1 Designation Unit Register access R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module
mA
11-58
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-24 Decimal address 3846 3847 3848 3850 3851 3852 3853 3854 3855 3856 3858 3859 3860 3861 3862 3863 3864 3866 3867 3868 3869 3870 3871 3872 3874 3875 3876 3877 3878 3879 3880 3882 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F06 F07 F08 F0A F0B F0C F0D F0E F0F F10 F12 F13 F14 F15 F16 F17 F18 F1A F1B F1C F1D F1E F1F F20 F22 F23 F24 F25 F26 F27 F28 F2A Number of data words 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 Designation Unit Register access R R mA R R R R R R R mA R R R R R R R mA R R R R R R R V / 100 R R R R R R R V / 100 R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600
Minute Second Max. I: maximum current from I1, I2 or I3 Day Month Year Hour Minute Second Min. IN: minimum neutral conductor current IN Day Month Year Hour Minute Second Max. IN: maximum neutral conductor current IN Day Month Year Hour Minute Second Min. U: minimum line voltage from U12, U23 or U31 Day Month Year Hour Minute Second Max. U: maximum line voltage from U12, U23 or U31 Day
104413_en_00
PHOENIX CONTACT
11-59
EEM-MA600 Table 11-24 Decimal address 3883 3884 3885 3886 3887 3888 3890 3891 3892 3893 3894 3895 3896 3898 3899 3900 3901 3902 3903 3904 3906 3907 3908 3909 3910 3911 3912 3914 3915 3916 3917 3918 3919 3920 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F2B F2C F2D F2E F2F F30 F32 F33 F34 F35 F36 F37 F38 F3A F3B F3C F3D F3E F3F F40 F42 F43 F44 F45 F46 F47 F48 F4A F4B F4C F4D F4E F4F F50 Number of data words 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Designation Unit Register access R R R R R V / 100 R R R R R R R V / 100 R R R R R R R Hz / 100 R R R R R R R Hz / 100 R R R R R R R 1 / 1000 R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Month Year Hour Minute Second Min. V: minimum line voltage against N from V1, V2 or V3 Day Month Year Hour Minute Second Max. V: maximum line voltage against N from V1, V2 or V3 Day Month Year Hour Minute Second Min. F: minimum frequency F Day Month Year Hour Minute Second Max. F: maximum frequency F Day Month Year Hour Minute Second Min. PF: minimum power factor (total)
11-60
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-24 Decimal address 3922 3923 3924 3925 3926 3927 3928 3930 3931 3932 3933 3934 3935 3936 3938 3939 3940 3941 3942 3943 3944 3946 3947 3948 3949 3950 3951 3952 3954 3955 3956 3957 3958 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F52 F53 F54 F55 F56 F57 F58 F5A F5B F5C F5D F5E F5F F60 F62 F63 F64 F65 F66 F67 F68 F6A F6B F6C F6D F6E F6F F70 F72 F73 F74 F75 F76 Number of data words 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 Designation Unit Register access R R R R R R 1 / 1000 R R R R R R R kW / 100 R R R R R R R kW / 100 R R R R R R R kW / 100 R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Day Month Year Hour Minute Second Max. PF: maximum power factor (total) Day Month Year Hour Minute Second Min. P+: minimum positive real power (total) Day Month Year Hour Minute Second Max. P+: maximum positive real power (total) Day Month Year Hour Minute Second Min. P-: minimum negative real power (total) Day Month Year Hour Minute
104413_en_00
PHOENIX CONTACT
11-61
EEM-MA600 Table 11-24 Decimal address 3959 3960 3962 3963 3964 3965 3966 3967 3968 3970 3971 3972 3973 3974 3975 3976 3978 3979 3980 3981 3982 3983 3984 3986 3987 3988 3989 3990 3991 3992 3994 3995 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F77 F78 F7A F7B F7C F7D F7E F7F F80 F82 F83 F84 F85 F86 F87 F88 F8A F8B F8C F8D F8E F8F F90 F92 F93 F94 F95 F96 F97 F98 F9A F9B Number of data words 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 Designation Unit Register access R kW / 100 R R R R R R R kvar / 100 R R R R R R R kvar / 100 R R R R R R R kvar / 100 R R R R R R R kvar / 100 R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600
Second Max. P-: maximum negative real power (total) Day Month Year Hour Minute Second Min. Q+: minimum positive reactive power (total) Day Month Year Hour Minute Second Max. Q+: maximum positive reactive power (total) Day Month Year Hour Minute Second Min. Q-: minimum negative reactive power (total) Day Month Year Hour Minute Second Max. Q-: maximum negative reactive power (total) Day Month
11-62
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-24 Decimal address 3996 3997 3998 3999 4000 4002 4003 4004 4005 4006 4007 4008 4010 4011 4012 4013 4014 4015 4016 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address F9C F9D F9E F9F FA0 FA2 FA3 FA4 FA5 FA6 FA7 FA8 FAA FAB FAC FAD FAE FAF FB0 Number of data words 1 1 1 1 2 1 1 1 1 1 1 2 1 1 1 1 1 1 2 Designation Unit Register access R R R R kVA / 100 R R R R R R R kVA / 100 R R R R R R R 0.10% R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Year Hour Minute Second Min. S: minimum apparent power (total) Month Day Year Hour Minute Second Max. S: maximum apparent power (total) Day Month Year Hour Minute Second Min. THD I: minimum total harmonic distortion of currents from I1, I2 or I3 Day Month Year Hour Minute Second Max. THD I: maximum total harmonic distortion of currents from I1, I2 or I3 Day Month Year Hour Minute Second 0.10%
1 1 1 1 1 1 2
R R R R R R R
1 1 1 1 1 1
R R R R R R
104413_en_00
PHOENIX CONTACT
11-63
EEM-MA600 Table 11-24 Decimal address 4032 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address FC0 Number of data words 2 Designation Unit Register access R Available through extension module
Min. THD IN: minimum total harmonic distortion of neutral conductor current Day Month Year Hour Minute Second Max. THD IN: maximum total harmonic distortion of neutral conductor current Day Month Year Hour Minute Second Min. THD U: minimum total harmonic distortion of line voltages from U12, U23 or U31 Day Month Year Hour Minute Second Max. THD U: maximum total harmonic distortion of line voltages from U12, U23 or U31 Day Month Year Hour Minute Second
0.10%
1 1 1 1 1 1 2
R R R R R R 0.10% R
1 1 1 1 1 1 2
R R R R R R 0.10% R
1 1 1 1 1 1 2
R R R R R R 0.10% R
1 1 1 1 1 1
R R R R R R
11-64
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-24 Decimal address 4064 F00 hex: current minimum and maximum measured values (measurement duration of 1 s) [...] Hexadecimal address FE0 Number of data words 2 Designation Unit Register access R Available through extension module
Min. THD V: minimum total harmonic distortion of line voltages against N from V1, V2 or V3 Day Month Year Hour Minute Second Max. THD V: maximum total harmonic distortion of line voltages against N from V1, V2 or V3 Day Month Year Hour Minute Second
0.10%
1 1 1 1 1 1 2
R R R R R R 0.10% R
1 1 1 1 1 1
R R R R R R
1000 hex: supply voltage failure (course of last 10 voltage interruptions) Hexadecimal Number address of data words Designation Unit Register access Available through extension module
Voltage interruption n-1 4096 4097 4098 4099 4100 4101 1000 1001 1002 1003 1004 1005 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-2 4102 4103 1006 1007 1 1 Day Month R R EEM-MEMO-MA600 EEM-MEMO-MA600
104413_en_00
PHOENIX CONTACT
11-65
EEM-MA600 Table 11-25 Decimal address 4104 4105 4106 4107 1000 hex: supply voltage failure (course of last 10 voltage interruptions) [...] Hexadecimal Number address of data words 1008 1009 100A 100B 1 1 1 1 Designation Unit Register access R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-3 4108 4109 4110 4111 4112 4113 100C 100D 100E 100F 1010 1011 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-4 4114 4115 4116 4117 4118 4119 1012 1013 1014 1015 1016 1017 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-5 4120 4121 4122 4123 4124 4125 1018 1019 101A 101B 101C 101D 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-6 4126 4127 4128 4129 4130 4131 101E 101F 1020 1021 1022 1023 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-7 4132 4133 4134 1024 1025 1026 1 1 1 Day Month Year R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
11-66
PHOENIX CONTACT
104413_en_00
MODBUS register Table 11-25 Decimal address 4135 4136 4137 1000 hex: supply voltage failure (course of last 10 voltage interruptions) [...] Hexadecimal Number address of data words 1027 1028 1029 1 1 1 Designation Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-8 4138 4139 4140 4141 4142 4143 102A 102B 102C 102D 102E 102F 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-9 4144 4145 4146 4147 4148 4149 1030 1031 1032 1033 1034 1035 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltage interruption n-10 4150 4151 4152 4153 4154 4155 1036 1037 1038 1039 103A 103B 1 1 1 1 1 1 Day Month Year Hour Minute Second R R R R R R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
The indicator is a continuous counter that gives the status of the register in which the last value was saved via the set measurement duration. When you use this table, you must multiply the values by the transmission ratios for the converter used. Real and reactive energy values are saved in registers 3005...7655. These must be allocated by the set measurement duration in order to determine the real and reactive power (see "Example: readout of contents of address 3051" on page 11-70, "Storage register entries" on page 11-70).
104413_en_00
PHOENIX CONTACT
11-67
EEM-MA600
Table 11-26
3000 hex: Course of reactive and real energy over set measurement duration (without consideration of transmission ratios) Hexadecimal address 3000 3001 3002 3005 4199 532D 64C1 7655 Number of data words 1 1 3 4500 4500 4500 4500 End of range Designation Unit Register access R R R kWh/100 kWh/100 kvarh/100 kvarh/100 R R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Decimal address 12288 12289 12290 12293 16793 21293 25793 30293
Indicator for average value real power P+/PIndicator for average value reactive power Q+/QDate/time indicator update Range P.1 average value for real power P+/PRange P.2 average value for real power P+/PRange Q.1 average value for reactive power Q+/QRange Q.2 average value for reactive power Q+/Q-
The indicator is a continuous counter that gives the status of the register in which the last value was saved via the set measurement duration. When you use this table, you must multiply the values by the transmission ratios for the converter used.
8000 hex: course of average values for voltages over the set measurement duration Hexadecimal address 8000 8001 8004 Number of data words 1 3 875 Designation Unit Register Available through access extension module R R V/10 R EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Voltages indicator Date/time indicator update Value of line voltages (3U) Value of line voltages against N (3V)
33647
836F
End of range
11-68
PHOENIX CONTACT
104413_en_00
MODBUS register
The indicator is a continuous counter that gives the status of the register in which the last value was saved via the set measurement duration.
9000 hex: course of average values for frequency over the set measurement duration Hexadecimal address 9000 9001 9004 B200 Number of data words 1 3 8700 End of range Designation Frequency indicator Date/time indicator update Value of frequency F Hz/100 Unit Register access R R R Available through extension module EEM-MEMO-MA600 EEM-MEMO-MA600 EEM-MEMO-MA600
Example: readout of register 3002 hex "Date/time indicator update" The register shows the date/time of the last indicator update (last save). Slave address 01 Function 03 High quality address 30 Low quality address 02 The answer for EEM-MA600 is: Slave address 01 Function 03 Number of bytes 06 Register value word 1 071F 07 (month July) / 31. (Day) Register value word 2 100A 16:10 time (16 hour / 10 minutes) Register value word 3 000B 0 (seconds) / 2011 (year) CRC 16 5D0 No. High quality words 00 No. Low quality words 03 CRC 16 AB0B
Example: readout of register 3000 hex "indicator address for real power P+/PThe indicator shows the place in the register where the last value was stored. Slave address 01 Function 03 High quality address 30 Low quality address 00 The answer for EEM-MA600 is: Slave address 01 Function 03 Number of bytes 02 Register value word 1 004C CRC 16 B9B1 No. High quality words 00 No. Low quality words 01 CRC 16 8B0A
The last value was stored in address 3051 (address 3005 + 4C indicator counter).
104413_en_00
PHOENIX CONTACT
11-69
EEM-MA600 Example: readout of contents of address 3051 Measurement duration 10 minutes. Slave address 01 Function 03 High quality address 30 Low quality address 51 No. High quality words 00 No. Low quality words 01 CRC 16 DADB
Address 3005 + 4C = 3051 EEM-MA600's answer is: Slave address 01 Function 03 Number of bytes 02 Register value word 1 statement: 16FA kWh (hex) 5882 kWh/100 (decimal) not based on current and voltage transducer (without consideration of transmission ratios) 58.82 kWh x (1000 A/5 A) = 11764 kWh (for a measurement duration set for 10 minutes at 16:10) Determination of power: P= E/t For a measurement duration of 10 min, you must divide the measured energy by the measurement duration: 11764 kWh/6 (1 h/10 min) = 1960 kW Register value word 1 16FA CRC 16 3667
Storage register entries Table 11-29 Storage of the real energy (measurement duration of 10 minutes) Date/time Register value1 58.28 47.96 35.97 54.67 58.82 Register value2 11656 9592 7194 10934 11764 Calculated Calculated Calculated real power3 real energy4 real power5 9.7 7.9 5.9 9.1 9.8 11656 9592 7194 10934 11764 1942 1598 1199 1822 1960
Hexadecimal Measured value address (decimal) kWh/100 304D 304E 304F 3050 3051
1 2 3
without consideration of transmission ratios (kWh) under consideration of the current transformer transmission ratios 1000 A/5 A (kWh) without consideration of the transmission ratios (kW): Determination of power P= E/t (for example, 58.82 kWh/6 (1 h/10 min) = 9.8 kW under consideration of the current transformer transmission ratios 1000 A/5 A (kWh) under consideration of current transformer transmission ratios 1000 A/5 A (kW): Determination of power P= E/t (for example, 11764 kWh/6 (1 h/10 min) = 1960 kW
4 5
11-70
PHOENIX CONTACT
104413_en_00
MODBUS register Register date/time readout when supply voltage fails Example: moment of deactivation The first word starts with $E Address + 0 Address + 1 Address + 2 $Emdd $hhnn $ssyy 1 word 1 word 1 word m: month 112 dd: day 131 hh: hour 023 nn: minute 060 ss: second 059 yy: year 0255
Example: switch-on moment The first word starts with $F Address + 0 Address + 1 Address + 2 $Fmdd $hhnn $ssyy 1 word 1 word 1 word m: month 112 dd: day 131 hh: hour 023 nn: Minute 060 ss: second 059 yy: year 0255
104413_en_00
PHOENIX CONTACT
11-71
EEM-MA600
11-72
PHOENIX CONTACT
104413_en_00
PROFIBUS register
12 PROFIBUS register
In this section, you will find the following registers. Table 12-1 Description Configuration Module 1 "Main values" Module 2 "Additional values" Module 3 "Undervoltage/Interrupt/Pow&Freq" Module 4 "Overvoltage/Avg U&V/Max&Avg IN" Module 5 "3I&IN harmonics Module 6 "3U harmonics" Module 7 "3V harmonics" Module 8 "Instantaneous MinMax" Module 9 "Specific Data" Module 10 (not available) Module 11 "Specific short data" Diagnostics Register overview For further information See Table 12-2 on page 12-1 See page 12-5 See page 12-11 See page 12-13 See page 12-13 See page 12-14 See page 12-16 See page 12-17 See page 12-18 See page 12-18 See page 12-27 See page 12-28 See page 12-29
12.1
Configuration
Configuration (user prm data) Register size (bytes) 1 1 Register access W W Available through extension module
Not available Note: register content is always zero Network type : 0 : 1BL 1 : 2BL 2 : 3BL 3 : 3NBL 4 : 4BL 5 : 4NBL Current transformer secondary side (A) 1:1A 5:5A Current transformer primary side (A)
104413_en_00
PHOENIX CONTACT
12-1
EEM-MA600 Table 12-2 Designation Voltage transducer present? 0 : No 1 : Yes Voltage transducer primary side (V) Voltage transducer secondary side (V) : 60 : 60 V 100 : 100 V 110 : 110 V 115 : 115 V 120 : 120 V 173 : 173 V 190 : 190 V Measurement duration for average value/maximum value accumulation for currents: ( 2 s, 10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Measurement duration for average value/maximum value accumulation for P, Q, S power: (10 s, 5 min, 8 min, 10 min, 15 min, 20 min, 30 min, 60 min) Not available Not available Not available Not available Not available Not available Output signal AO OUT 1: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Configuration (user prm data) [...] Register size (bytes) 1 Register access W Available through extension module
4 1
W W
1 1 1 1 1 1 1
W W W W W W W EEM-2AO-MA600
12-2
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-2 Designation Output type AO OUT 1: 0: I1: current 1: I2: current 2: I3: current 3: In: neutral conductor current 4: U12: line voltages (1-2) 5: U23: line voltages (2-3) 6: U31: line voltages (3-1) 7: P: total real power 8: Q: total real power 9: S: total apparent power 10 : PFL: total inductive power factor 11 : V1: line voltages against N 12 : V2: line voltages against N 13 : V3: line voltages against N 14: F: frequency 15: PFC: total capacitive power factor 16: I: current I1, I2, I3 17: U: line voltages (1-2/2-3/3-1) 18: V: line voltages against N (1/2/3) 19: PPR: total real power (trend) 20: QPR: total reactive power (trend) 21: SPR: total apparent power (trend) 22: TC1: temperature module input EEM-TEMP-MA600 23: TC2: temperature module input EEM-TEMP-MA600 24: TC3: temperature module input EEM-TEMP-MA600 25: TC4: internal temperature EEM-TEMP-MA600 Output value AO OUT 1 for 0 or 4 mA AO OUT 1 unit of output value for 0 or 4 mA: 0: / 1:k 2:M Output value AO OUT 1 for 20 mA AO OUT 1 unit of output value for 20 mA: 0:/ 1:k 2: M Output signal AO OUT 2: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output type AO OUT 2: see AO OUT 1 AO OUT 2 output value for 0 or 4 mA AO OUT 2 unit of output value for 0 or 4 mA: 0:/ 1:k 2:M Configuration (user prm data) [...] Register size (bytes) 1 Register access W Available through extension module EEM-2AO-MA600
2 1
W W
EEM-2AO-MA600 EEM-2AO-MA600
2 1
W W
EEM-2AO-MA600 EEM-2AO-MA600
EEM-2AO-MA600
1 2 1
W W W
104413_en_00
PHOENIX CONTACT
12-3
EEM-MA600 Table 12-2 Designation AO OUT 2 output value for 20 mA AO OUT 2 unit of output value for 20 mA: 0:/ 1:k 2: M Output signal AO OUT 3: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output type AO OUT 3: see AO OUT 1 AO OUT 3 output value for 0 or 4 mA AO OUT 3 unit of output value for 0 or 4 mA: 0:/ 1:k 2: M AO OUT 3 output value for 20 mA AO OUT 2 unit of output value for 20 mA: 0:/ 1:k 2: M Output signal AO OUT 4: 0 : 0/20 mA 1 : 4/20 mA 2 : 30 V Output type AO OUT 4: see AO OUT 1 AO OUT 4 output value for 0 or 4 mA AO OUT 4 unit of output value for 0 or 4 mA: 0:/ 1:k 2:M AO OUT 4 output value for 20 mA AO OUT 4 unit of output value for 20 mA: 0:/ 1:k 2:M Current transformer secondary side (A) 1:1A 5:5A Current transformer primary side (A) Length : 54 bytes Configuration (user prm data) [...] Register size (bytes) 2 1 Register access W W Available through extension module EEM-2AO-MA600 EEM-2AO-MA600
EEM-2AO-MA600
1 2 1
W W W
2 1
W W
EEM-2AO-MA600 EEM-2AO-MA600
EEM-2AO-MA600
1 2 1
W W W
2 1
W W
EEM-2AO-MA600 EEM-2AO-MA600
12-4
PHOENIX CONTACT
104413_en_00
PROFIBUS register
NOTE: Check whether the setting data matches the data provided in the device. When a slave is not recognized by the PROFIBUS master, the master sends GSD file parameters or the default settings. Two options are specified for this procedure: Deactivate the EEM-MA600 programming via the master Configure the EEM-MA600 via the master and then open the "Programming" menu on the front side of the measuring instrument and close again.
12.2
Example:
In order to change the idle state for relay 1, you must set bit 4 and bit 0 to 1. Table 12-3 Designation Relay change of state If bit 4 and the allocated bit for the desired relay output is at 1, the relay's idle state can be changed. Bit 0 : relay 1 Bit 1 : relay 2 Bit 2 : relay 3 Bit 3 : relay 4 Bit 4 : changing relay configuration Bit 5 : resetting a size Bit 6 : not available Bit 7 : not available DO OUT 1 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 2 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 3 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 4 relay idle state: 0 : NO (open) 1 : NC (closed) Output table Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600
EEM-2DIO-MA600
EEM-2DIO-MA600
EEM-2DIO-MA600
EEM-2DIO-MA600
104413_en_00
PHOENIX CONTACT
12-5
EEM-MA600 Table 12-3 Designation DO OUT 1 output type : 0 : CDE: Controlling relay state via RS485 1 : I: current I1, I2, I3 2 : U: line voltages (1-2/2-3/3-1) 3 : P+: total positive real power 4 : Q+: total positive reactive power 5 : S: total apparent power 6 : F: frequency 7 : PFL: total inductive power factor 8 : THDI: total harmonic distortion of currents I1, I2, I3 9 : THDU: total harmonic distortion of the conductor voltages (1-2/2-3/3-1) 10 : IN: neutral conductor current 11 : HOUr: operating hours counter 12 : V: conductor voltages against N (1/2/3) 13 : THDIN: total harmonic distortion of neutral conductor current 14 : THDV: total harmonic distortion of conductor voltages against N (1/2/3) 15 : P-: total negative real power 16 : Q-: total negative reactive power 17 : PFC: total capacitative power factor 18 : CDT: control of relay state via RS485, resetting relay with idle state 19 : TC1: temperature module input EEM-TEMP-MA600 20 : TC2: temperature module input EEM-TEMP-MA600 21 : TC3: temperature module input EEM-TEMP-MA600 22 : TC4: internal temperature EEM-TEMP-MA600 23 : PPR: total real power (trend) 24 : QPR: total reactive power (trend) 25 : SPR: total apparent power (trend) DO OUT 1 alarm output value lower switching threshold DO OUT 1 unit of output value for the lower switching threshold 0: / 1: k 2: M DO OUT 1 alarm output value upper switching threshold DO OUT 1 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 1 hysteresis (0-99%) DO OUT 1 trigger delay (0-999 s) Output type DO OUT 2: see DO OUT 1 DO OUT 2 alarm output value lower switching threshold Output table [...] Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600
2 1
W W
EEM-2DIO-MA600 EEM-2DIO-MA600
2 1
W W
EEM-2DIO-MA600 EEM-2DIO-MA600
1 2 1 2
W W W W
12-6
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-3 Designation DO OUT 2 unit of output value for the lower switching threshold 0: / 1: k 2: M DO OUT 2 alarm output value upper switching threshold DO OUT 2 unit of output value for upper switching threshold 0: / 1: k 2: M DO OUT 2 hysteresis (0-99%) DO OUT 2 trigger delay (0-999 s) Output table [...] Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600
2 1
W W
EEM-2DIO-MA600 EEM-2DIO-MA600
1 2
W W
EEM-2DIO-MA600 EEM-2DIO-MA600
104413_en_00
PHOENIX CONTACT
12-7
EEM-MA600 Table 12-3 Designation Output resetting (Reset) Bit 0 : max/avg I1,I2,I3: maximum value for currents (I1, I2, I3) Bit 1 : max/avg P+: maximum value of total positive real power Bit 2 : max/avg P-: maximum value of total negative real power Bit 3 : max/avg Q+: maximum value of total positive reactive power Bit 4 : max/avg Q-: maximum value of total negative reactive power Bit 5 : max/avg S: maximum value of total apparent power Bit 6 : HOUr: operating hours counter Bit 7 : EA+: current positive real energy kWh+ Bit 8 : ER+: current positive reactive energy kvarh+ Bit 9 : ES: current apparent energy kVAh Bit 10 : EA-: current negative real energy kWhBit 11 : ER-: current negative reactive energy kvarhBit 12 : all measured values Bit 13 : E1: counter state for digital input 1 Bit 14 : E2: counter state for digital input 2 Bit 15 : not available Output resetting (Reset) Bit 0 : E1: counter state for digital input 1 Bit 1 : E2: counter state for digital input 2 Bit 2 : E3: counter state for digital input 3 Bit 3 : E4: counter state for digital input 4 Bit 4 : not available Bit 5 : not available Bit 6 : min./max. I: min./max. power from I1, I2 or I3 Bit 7 : min./max. In: min./max. neutral conductor current Bit 8 : min./max. U: min./max. line voltage from U12, U23 or U31 Bit 9 : min./max. F: min./max. frequency value Bit 10 : min./max. PF: min./max. power factor (total) Bit 11 : min./max. P: min./max. positive and negative real power (total) Bit 12 : min./max. Q: min./max. positive and negative reactive power (total) Bit 13 : min./max. THD I: min./max. total harmonic distortion of currents from I1, I2, or I3 Bit 14 : min./max. THD IN: min./max. total harmonic distortion of neutral conductor current Bit 15 : min./max. THD U: min./max. total harmonic distortion of line voltages from U12, U23 or U31 Length : 29 bytes Output table [...] Register size (bytes) 2 Register access W Available through extension module
12-8
PHOENIX CONTACT
104413_en_00
PROFIBUS register
When you use this table, you must multiply the values by the transformation ratios for the converters used. This module contains the measured values for the currents, voltages, power, frequencies, power factors, positive energy and operating hour counter values.
Table 12-4
Display of main measured values not based on current transformer and voltage transducer (without consideration of transformation ratios) input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Available through extension module
Designation I1: current (mA) I2: current (mA) I3: current (mA) In: neutral conductor current (mA) U12: line voltage (V/100) U23: line voltage (V/100) U31: line voltage (V/100) V1: line voltage against N (V/100) V2: line voltage against N (V/100) V3: line voltage against N (V/100) F: frequency (Hz/100) P: total real power +/- (kW/100) Q: total reactive power +/- (kvar/100) S: total apparent power (kVA/100) PF: total power factor -: capacitive and +: inductive (0.001) Max/avg I1: maximum current value (mA) Max/avg I2: maximum current value (mA) Max/avg I3: maximum current value (mA) Max/avg P+: maximum total positive real power value (W) Max/avg P-: maximum total negative real power value (W) Max/avg Q+: maximum total positive reactive power value (var) Max/avg Q-: maximum total negative reactive power value (var) Max/avg S: maximum total apparent power value (VA) Ea+: current positive real energy < 10,000 kWh Ea+: current positive real energy > 10,000 kWh Er +: current positive reactive energy < 10,000 kvarh Er +: current positive reactive energy > 10,000 kvarh ES: current apparent energy < 10,000 kVAh ES: current apparent energy > 10,000 kVAh ISYS: average current value (I1+I2+I3)/3 (mA)
104413_en_00
PHOENIX CONTACT
12-9
EEM-MA600 Table 12-4 Display of main measured values not based on current transformer and voltage transducer (without consideration of transformation ratios) input table [...] Register size (bytes) 2 Register access R R R R Available through extension module
Designation USYS: average line voltage value (U12 + U23 + U31)/3 (V/10)
VSYS: average line voltage value against N (V1 + V2 + V3 )/3 (V/10) 2 Operating hours counter < 10,000 (h/100) Operating hours counter > 10,000 (h/100) Length: 68 bytes Calculation of affected values 2 2
The currents must be multiplied by the SW ratio, the currents with the SpW ratio (for high voltage) and the power by the SW x SpW ratio. Example: SW = 100/5 = 20 SpW = 20,000/100 = 200 SW x SpW = 20 x 200 = 4000 All power is multiplied by 4000 (without SpW, SpW = 1), currents by 20 and voltages by 200. Description: I system= I1 + I2 + I3 / 3 U system = U12 + U21 + U31 / 3 V system = V1 + V2 + V3 / 3 Conversion of values with and without sign bits When the current, voltages or energy is negative, the following rule must be applied: use the opposite bit per data bit Add 1 to this opposite bit Example Negative value -28864 mV In binary format Opposite corresponds to Opposite +1 corresponds to or 366.72 V in decimal figures 0111 0000 1100 0000 1000 1111 0011 1111 1000 1111 0100 0000
12-10
PHOENIX CONTACT
104413_en_00
PROFIBUS register
12.3
When you use this table, you must multiply the values by the transformation ratios for the converters used. This module contains the measurements per phase, average values, - energy and states (on/off input). The output table is identical to the output table from module 1.
Table 12-5
Display of additional measured values not based on current transformer and voltage transducer (without consideration of transformation ratios), input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R R R EEM-2DIO-MA600 Available through extension module
Designation P1: real power phase 1 +/- (kW/100) P2: real power phase 2 +/- (kW/100) P3: real power phase 3 +/- (kW/100) Q1: reactive power phase 1 +/- (kvar/100) Q2: reactive power phase 2 +/- (kvar/100) Q3: reactive power phase 3 +/- (kvar/100) S1: apparent power phase 1 (kVA/100) S2: apparent power phase 2 (kVA/100) S3: apparent power phase 3 (kVA/100) PF1: power factor phase 1 -: capacitive and +: inductive (0.001) PF2: power factor phase 2 -: capacitive and +: inductive (0.001) PF3: power factor phase 3 -: capacitive and +: inductive (0.001) Avg I1: average current value (mA) Avg I2: average current value (mA) Avg I3: average current value (mA) Avg P+: average total positive real power value (W) Avg P-: average total negative real power value (W) Avg Q+: average total positive reactive power value (var) Avg Q-: average total negative reactive power value (var) Avg S: average total apparent power value (VA) EA-: negative real energy < 10,000 kWh EA-: negative real energy > 10,000 kWh ER-: negative reactive energy < 10,000 kvarh ER-: negative reactive energy > 10,000 kvarh Counter state digital input DI 1 < 10,000
104413_en_00
PHOENIX CONTACT
12-11
EEM-MA600 Table 12-5 Display of additional measured values not based on current transformer and voltage transducer (without consideration of transformation ratios), input table [...] Register size (bytes) 2 2 2 2 2 2 2 2 Register access R R R R R R R R Available through extension module EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600 EEM-2DIO-MA600
Designation Counter state digital input DI 1 > 10,000 Counter state digital input DI 2 < 10,000 Counter state digital input DI 2 > 10,000 Counter state digital input DI 3 < 10,000 Counter state digital input DI 3 > 10,000 Counter state digital input DI 4 < 10,000 Counter state digital input DI 4 > 10,000 Status of digital inputs 1, 2, 3, 4. Length: 66 bytes Note
The currents must be multiplied by the SW ratio, the currents with the SpW ratio (for high voltage) and the power by the SW x SpW ratio. Example: SW = 100/5 = 20 SpW = 20,000/100 = 200 SW x SpW = 20 x 200 = 4000 All power is multiplied by 4000 (without SpW, SpW = 1), currents by 20 and voltages by 200. Status of the inputs Input 1 = 0 bit Input 2 = 1 bit Input 3 = 2 bit Input 4 = 4 bit When active, bit 1 When inactive, bit 0 Conversion of values with and without sign bits When the current, voltages or energy is negative, the following rule must be applied: use the opposite bit per data bit Add 1 to this opposite bit
12-12
PHOENIX CONTACT
104413_en_00
PROFIBUS register Example Negative value -28864 mV In binary format Opposite corresponds to Opposite +1 corresponds to or 366.72 V in decimal format 0111 0000 1100 0000 1000 1111 0011 1111 1000 1111 0100 0000
12.4
Module 3 "Undervoltage/Interrupt/Pow&Freq"
12.5
104413_en_00
PHOENIX CONTACT
12-13
EEM-MA600
12.6
This module contains the THD values I and THD IN as well as the individual harmonic content for currents: I up to 15. harmonic. The output table is identical to the output table from module 1.
Display of total harmonic distortion (THD) and harmonics for currents, input table Register size (bytes) 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Available through extension module
THD I1: total harmonic distortion of current (0.1%) THD I2: total harmonic distortion of current (0.1%) THD I3: total harmonic distortion of current (0.1%)
THD In: total harmonic distortion of neutral conductor current (0.1%) 2 Content of 3rd harmonic I1 (0.1%) Content of 3rd harmonic I2 (0.1%) Content of 3rd harmonic I3 (0.1%) Content of 3rd harmonic IN (0.1%) Content of 5th harmonic I1 (0.1%) Content of 5th harmonic I2 (0.1%) Content of 5th harmonic I3 (0.1%) Content of 5th harmonic IN (0.1%) Content of 7th harmonic I1 (0.1%) Content of 7th harmonic I2 (0.1%) Content of 7th harmonic I3 (0.1%) Content of 7th harmonic IN (0.1%) Content of 9th harmonic I1 (0.1%) Content of 9th harmonic I2 (0.1%) Content of 9th harmonic I3 (0.1%) Content of 9th harmonic IN (0.1%) Content of 11th harmonic I1 (0.1%) Content of 11th harmonic I2 (0.1%) Content of 11th harmonic I3 (0.1%) Content of 11th harmonic IN (0.1%) Content of 13th harmonic I1 (0.1%) Content of 13th harmonic I2 (0.1%) Content of 13th harmonic I3 (0.1%) Content of 13th harmonic IN (0.1%) Content of 15th harmonic I1 (0.1%) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
12-14
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-6 Designation Content of 15th harmonic I2 (0.1%) Content of 15th harmonic I3 (0.1%) Content of 15th harmonic IN (0.1%) Length: 64 bytes Display of total harmonic distortion (THD) and harmonics for currents, input table [...] Register size (bytes) 2 2 2 Register access R R Available through extension module
104413_en_00
PHOENIX CONTACT
12-15
EEM-MA600
12.7
This module contains the THD values as well as the individual harmonic content for line voltages up to 11th harmonic. The output table is identical to the output table from module 1.
Display of total harmonic distortion (THD) and harmonics for line voltages U (phase/phase), input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R Available through extension module
THD U12: total harmonic distortion of line voltage (0.1%) THD U23: total harmonic distortion of line voltage (0.1%) THD U31: total harmonic distortion of line voltage (0.1%) Content of 3rd harmonic U12 (0.1%) Content of 3rd harmonic U23 (0.1%) Content of 3rd harmonic U31 (0.1%) Not available Content of 5th harmonic U12 (0.1%) Content of 5th harmonic U23 (0.1%) Content of 5th harmonic U31 (0.1%) Not available Content of 7th harmonic U12 (0.1%) Content of 7th harmonic U23 (0.1%) Content of 7th harmonic U31 (0.1%) Not available Content of 9th harmonic U12 (0.1%) Content of 9th harmonic U23 (0.1%) Content of 9th harmonic U31 (0.1%) Not available Content of 11th harmonic U12 (0.1%) Content of 11th harmonic U23 (0.1%) Content of 11th harmonic U31 (0.1%) Not available Length: 48 bytes
12-16
PHOENIX CONTACT
104413_en_00
PROFIBUS register
12.8
This module contains the THD values as well as the individual harmonic content for line voltages against N up to 11th harmonic. The output table is identical to the output table from module 1.
Display of total harmonic distortion (THD) and harmonics for line voltages against N (V), input table Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R R R R R R R R R R Available through extension module
THD V1: total harmonic distortion of line voltage against N (0.1%) THD V2: total harmonic distortion of line voltage against N (0.1%) THD V3: total harmonic distortion of line voltage against N (0.1%) Content of 3rd harmonic V1 (0.1%) Content of 3rd harmonic V2 (0.1%) Content of 3rd harmonic V3 (0.1%) Not available Content of 5th harmonic V1 (0.1%) Content of 5th harmonic V2 (0.1%) Content of 5th harmonic V3 (0.1%) Not available Content of 7th harmonic V1 (0.1%) Content of 7th harmonic V2 (0.1%) Content of 7th harmonic V3 (0.1%) Not available Content of 9th harmonic V1 (0.1%) Content of 9th harmonic V2 (0.1%) Content of 9th harmonic V3 (0.1%) Not available Content of 11th harmonic V1 (0.1%) Content of 11th harmonic V2 (0.1%) Content of 11th harmonic V3 (0.1%) Not available Length: 48 bytes
104413_en_00
PHOENIX CONTACT
12-17
EEM-MA600
12.9
When bit 7 of byte 1 is at 0, the table can be used as standard to configure the outputs.
Example: In order to change the idle state for relay 1, you must set bit 4 and bit 0 to 1. Table 12-9 Designation Relay change of state If bit 4 and the allocated bit for the desired relay output is at 1, the relay's idle state can be changed. Bit 0 : relay 1 Bit 1 : relay 2 Bit 2 : relay 3 Bit 3 : relay 4 Bit 4 : changing relay configuration Bit 5 : resetting a size Bit 6 : not used Bit 7 : 0 > activate table for parameterization of digital outputs DO OUT 1 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 2 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 3 relay idle state: 0 : NO (open) 1 : NC (closed) DO OUT 4 relay idle state: 0 : NO (open) 1 : NC (closed) Special table, output table Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600
EEM-2DIO-MA600
EEM-2DIO-MA600
EEM-2DIO-MA600
EEM-2DIO-MA600
12-18
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-9 Designation Output type DO OUT 1: 0: CDE: controlling relay state via RS485 1: I: current I1, I2, I3 2: U: line voltages (1-2/2-3/3-1) 3: P+: total positive real power 4: Q+: total positive reactive power 5: S: total apparent power 6: F: frequency 7: PFL: total inductive power factor 8: THDI: total harmonic distortion for currents I1, I2, I3 9: THDU: total harmonic distortion for line voltages (1-2/2-3/3-1) 10: In: neutral conductor current 11: HOUr: operating hours counter 12: V: line voltages against N (1/2/3) 13: THDIN: total harmonic distortion of neutral conductor current 14: THDV: total harmonic distortion of line voltages against N (1/2/3) 15: P-: total negative real power 16: Q-: total negative reactive power 17: PFC: total capacitive power factor 18: CDT: controlling relay state via RS485, resetting relay to idle 19: TC1: temperature module input EEM-TEMP-MA600 20: TC2: temperature module input EEM-TEMP-MA600 21: TC3: temperature module input EEM-TEMP-MA600 22: TC4: internal temperature EEM-TEMP-MA600 23: PPR: total real power (trend) 24: QPR: total reactive power (trend) 25: SPR: total apparent power (trend) DO OUT 1 alarm output value lower switching threshold DO OUT 1 unit of output value for the lower switching threshold 0: / 1: k 2: M DO OUT 1 alarm output value upper switching threshold DO OUT 1 output value unit for the upper switching threshold 0: / 1: k 2: M DO OUT 1 hysteresis (0-99%) DO OUT 1 trigger delay (0-999 s) Output type DO OUT 2: see DO OUT 1 DO OUT 2 alarm output value lower switching threshold DO OUT 2 unit of output value for the lower switching threshold 0: / 1: k 2: M Special table, output table [...] Register size (bytes) 1 Register access W Available through extension module EEM-2DIO-MA600
2 1
W W
EEM-2DIO-MA600 EEM-2DIO-MA600
2 1
W W
EEM-2DIO-MA600 EEM-2DIO-MA600
1 2 1 2 1
W W W W W
104413_en_00
PHOENIX CONTACT
12-19
EEM-MA600 Table 12-9 Designation DO OUT 2 alarm output value upper switching threshold DO OUT 2 unit of output value for upper switching threshold 0: / 1: k 2: M DO OUT 2 hysteresis (0-99%) DO OUT 2 trigger delay (0-999 s) Special table, output table [...] Register size (bytes) 2 1 Register access W W Available through extension module EEM-2DIO-MA600 EEM-2DIO-MA600
1 2
W W W
EEM-2DIO-MA600 EEM-2DIO-MA600
Resetting outputs (reset) 2 Bit 0 : max/avg I1,I2,I3: maximum value of currents (I1, I2, I3) Bit 1 : max/avg P+: maximum total positive real power value Bit 2 : max/avg P-: maximum total negative real power value Bit 3 : max/avg Q+: maximum total positive reactive power value Bit 4 : max/avg Q-: maximum total negative reactive power value Bit 5 : max/avg S: maximum total apparent power value Bit 6 : HOUr: operating hours counter Bit 7 : EA+: current positive real energy kWh+ Bit 8 : ER+: current positive reactive energy kvarh+ Bit 9 : ES: current apparent energy kVAh Bit 10 : EA-: current negative real energy kWhBit 11 : ER-: current negative reactive energy kvarhBit 12 : all measured values Bit 13 : E1: counter state digital input 1 Bit 14 : E2: counter state digital input 2 Bit 15 : not available Resetting outputs (reset) Bit 0 : E1: counter state digital input 1 Bit 1 : E2: counter state digital input 2 Bit 2 : E3: counter state digital input 3 Bit 3 : E4: counter state digital input 4 Bit 4 : not available Bit 5 : not available Bit 6 : Min./Max. I: min./max. current from I1, I2, or I3 Bit 7 : Min./Max. In: min./max. neutral conductor current Bit 8 : Min./Max. U: min./max. line voltage from U12, U23 or U31 Bit 9 : Min./Max. F: min./max. frequency value Bit 10 : Min./Max. PF: min./max. power factor (total) Bit 11 : Min./Max. P: min./max. positive and negative real power (total) Bit 12 : Min./Max. Q: min./max. positive and negative reactive power (total) Bit 13 : Min./Max. THD I: min./max. total harmonic distortion of currents from I1, I2 or I3 Bit 14 : Min./Max. THD IN: min./max. total harmonic distortion of neutral conductor current Bit 15 : Min./Max. THD U: min./max. total harmonic distortion of line voltages from U12, U23 or U31 Not available Length: 33 bytes 2
12-20
PHOENIX CONTACT
104413_en_00
PROFIBUS register
Users can take advantage of Module 9 by compiling their own specific tables from "all" values. If bit 7 of byte 1 is at 1, the user can assign the outputs. The table number is an identification number that refers to the module table. You can create a table with 16 registers with addresses from module table 9.
Special table, output table Register size (bytes) 1 Register access W Available through extension module
Table number Bit 0-6 : table number Bit 7 : 1 > address table Value 1 address Value 2 address Value 3 address Value 4 address Value 5 address Value 6 address Value 7 address Value 8 address Value 9 address Value 10 address Value 11 address Value 12 address Value 13 address Value 14 address Value 15 address Value 16 address
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
W W W W W W W W W W W W W W W W
MSB: most significant byte (for example, 8-bit number with the MSB as bit 0) LSB: least significant byte (for example, 8-bit number with LSB as bit 0)
104413_en_00
PHOENIX CONTACT
12-21
EEM-MA600
List of values (assignment of addresses to corresponding measured values), input table Register size (bytes) Decimal address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Hexadecimal Register Available through address access extension module 0000 0001 0002 0003 0004 0005 0006 0007 0008 0009 000 A 000B 000C 000D 000E 000F 0010 0011 0012 0013 0014 0015 0016 0017 0018 0019 001 A 001B 001C R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
I1: current (mA) I2: current (mA) I3: current (mA) In: neutral conductor current (mA) U12: line voltage (V/100) U23: line voltage (V/100) U31: line voltage (V/100) V1: line voltage against N (V/100) V2: line voltage against N (V/100) V3: line voltage against N (V/100) F: frequency (Hz/100) P: total real power +/- (kW/100) Q: total reactive power +/- (kvar/100) S: total apparent power (kVA/100) PF: total power factor -: capacitive and +: inductive (0.001) Max/avg I1: maximum current value (mA) Max/avg I2: maximum current value (mA) Max/avg I3: maximum current value (mA) Max/avg P+: maximum total positive real power value (kW/100) Max/avg P-: maximum total negative real power value (kW/100) Max/avg Q+: maximum total positive reactive power value (kvar/100) Max/avg Q-: maximum total negative reactive power value (kvar/100) Max/avg S: maximum total apparent power value (kVA/100) EA+: current positive real energy < 10,000 (kWh) EA+: current positive real energy > 10,000 (kWh) ER +: current positive reactive energy < 10,000 (kvarh) ER +: current positive reactive energy > 10,000 (kvarh) ES: current apparent energy < 10,000 (kVAh) ES: current apparent energy > 10,000 (kVAh)
12-22
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 Hexadecimal Register Available through address access extension module 001D 001E 001F 0020 0021 0022 0023 0024 0025 0026 0027 0028 0029 002 A 002B 002C 002D 002E 002F 0030 0031 0032 0033 0034 0035 0036 0037 0038 0039 003 A R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
P1: real power phase 1 +/- (kW/100) P2: real power phase 2 +/- (kW/100) P3: real power phase 3 +/- (kW/100) Q1: reactive power phase 1 +/- (kvar/100) Q2: reactive power phase 2 +/- (kvar/100) Q3: reactive power phase 3 +/- (kvar/100) S1: apparent power phase 1 (kVA/100) S2: apparent power phase 2 (kVA/100) S3: apparent power phase 3 (kVA/100) PF1: power factor phase 1 -: capacitive and +: inductive (0.001) PF2: power factor phase 2 -: capacitive and +: inductive (0.001) PF3: power factor phase 3 -: capacitive and +: inductive (0.001) Avg I1: average current value (mA) Avg I2: average current value (mA) Avg I3: average current value (mA) Avg P+: average total positive real power value (W) Avg P-: average total negative real power value (W) Avg Q+: average total positive reactive power value (var) Avg Q-: average total negative reactive power value (var) Avg S: average total apparent value (VA) EA-: current negative real energy < 10,000 (kWh) EA-: current negative real energy > 10,000 (kWh) ER -: current negative reactive energy < 10,000 (kvar) ER -: current negative reactive energy > 10,000 (kvar) Counter state digital input DI 1 < 10,000 Counter state digital input DI 1 > 10,000 Counter state digital input DI 2 < 10,000 Counter state digital input DI 2 > 10,000 Counter state digital input DI 3 < 10,000 Counter state digital input DI 3 > 10,000
104413_en_00
PHOENIX CONTACT
12-23
EEM-MA600 Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 Hexadecimal Register Available through address access extension module 003B 003C 003D 003E 003F 0040 0041 0042 0043 0044 0045 0046 0047 0048 0049 004 A 004B 004C 004D 004E 004F 0050 0051 0052 0053 0054 0055 0056 0057 0058 0059 005 A 005B R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Counter state digital input DI 4 < 10,000 Counter state digital input DI 4 > 10,000 Status of digital inputs 1, 2, 3, 4 THD I1: total harmonic distortion of current (0.1%) THD I2: total harmonic distortion of current (0.1%) THD I3: total harmonic distortion of current (0.1%) THD In: total harmonic distortion of neutral conductor current (0.1%) Content of 3rd harmonic I1 (0.1%) Content of 3rd harmonic I2 (0.1%) Content of 3rd harmonic I3 (0.1%) Content of 3rd harmonic IN (0.1%) Content of 5th harmonic I1 (0.1%) Content of 5th harmonic I2 (0.1%) Content of 5th harmonic I3 (0.1%) Content of 5th harmonic IN (0.1%) Content of 7th harmonic I1 (0.1%) Content of 7th harmonic I2 (0.1%) Content of 7th harmonic I3 (0.1%) Content of 7th harmonic IN (0.1%) Content of 9th harmonic I1 (0.1%) Content of 9th harmonic I2 (0.1%) Content of 9th harmonic I3 (0.1%) Content of 9th harmonic IN (0.1%) Content of 11th harmonic I1 (0.1%) Content of 11th harmonic I2 (0.1%) Content of 11th harmonic I3 (0.1%) Content of 11th harmonic IN (0.1%) Content of 13th harmonic I1 (0.1%) Content of 13th harmonic I2 (0.1%) Content of 13th harmonic I3 (0.1%) Content of 13th harmonic IN (0.1%) Content of 15th harmonic I1 (0.1%) Content of 15th harmonic I2 (0.1%)
12-24
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 Hexadecimal Register Available through address access extension module 005C 005D 005E 005F 0060 0061 0062 0063 0064 0065 0066 0067 0068 0069 006 A 006B 006C 006D 006E 006F 0070 0071 0072 0073 0074 0075 0076 0077 0078 0079 007 A 007B R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R
Content of 15th harmonic I3 (0.1%) Content of 15th harmonic IN (0.1%) THD U12: total harmonic distortion of line voltage (0.1%) THD U23: total harmonic distortion of line voltage (0.1%) THD U31: total harmonic distortion of line voltage (0.1%) Content of 3rd harmonic U12 (0.1%) Content of 3rd harmonic U23 (0.1%) Content of 3rd harmonic U31 (0.1%) Content of 5th harmonic U12 (0.1%) Content of 5th harmonic U23 (0.1%) Content of 5th harmonic U31 (0.1%) Content of 7th harmonic U12 (0.1%) Content of 7th harmonic U23 (0.1%) Content of 7th harmonic U31 (0.1%) Content of 9th harmonic U12 (0.1%) Content of 9th harmonic U23 (0.1%) Content of 9th harmonic U31 (0.1%) Content of 11th harmonic U12 (0.1%) Content of 11th harmonic U23 (0.1%) Content of 11th harmonic U31 (0.1%) Content of 13th harmonic U12 (0.1%) Content of 13th harmonic U23 (0.1%) Content of 13th harmonic U31 (0.1%) Content of 15th harmonic U12 (0.1%) Content of 15th harmonic U23 (0.1%) Content of 15th harmonic U31 (0.1%) THD V1: total harmonic distortion of line voltage against N (0.1%) THD V2: total harmonic distortion of line voltage against N (0.1%) THD V3: total harmonic distortion of line voltage against N (0.1%) Content of 3rd harmonic V1 (0.1%) Content of 3rd harmonic V2 (0.1%) Content of 3rd harmonic V3 (0.1%)
104413_en_00
PHOENIX CONTACT
12-25
EEM-MA600 Table 12-11 Designation List of values (assignment of addresses to corresponding measured values), input table [...] Register size (bytes) Decimal address 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 Hexadecimal Register Available through address access extension module 007C 007D 007E 007F 0080 0081 0082 0083 0084 0085 0086 0087 0088 0089 008 A 008B 008C 008D 008E 008F 0090 0091 0092 R R R R R R R R R R R R R R R R R R R R R R R
Content of 5th harmonic V1 (0.1%) Content of 5th harmonic V2 (0.1%) Content of 5th harmonic V3 (0.1%) Content of 7th harmonic V1 (0.1%) Content of 7th harmonic V2 (0.1%) Content of 7th harmonic V3 (0.1%) Content of 9th harmonic V1 (0.1%) Content of 9th harmonic V2 (0.1%) Content of 9th harmonic V3 (0.1%) Content of 11th harmonic V1 (0.1%) Content of 11th harmonic V2 (0.1%) Content of 11th harmonic V3 (0.1%) Content of 13th harmonic V1 (0.1%) Content of 13th harmonic V2 (0.1%) Content of 13th harmonic V3 (0.1%) Content of 15th harmonic V1 (0.1%) Content of 15th harmonic V2 (0.1%) Content of 15th harmonic V3 (0.1%) ISYS: average current value (I1 + I2 + I3)/3 (mA) USYS: average line voltage value (U12 + U23 + U31)/3 (V/10) VSYS: average line voltage value against N (V1 + V2 + V3 )/3 (V/10) Operating hours counter < 10,000 (h/100) Operating hours counter > 10,000 (h/100)
The table number is an identification number that refers to the module table. You can create a table with 16 registers with addresses from module table 9.
Input table Register size (bytes) 1 2 2 Register access R R R Available through expansion module
12-26
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-12 Designation Value 3 Value 4 Value 5 Value 6 Value 7 Value 8 Value 9 Value 10 Value 11 Value 12 Value 13 Value 14 Value 15 Value 16 Length: 33 bytes Input table [...] Register size (bytes) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Register access R R R R R R R R R R R R R R Available through expansion module
104413_en_00
PHOENIX CONTACT
12-27
EEM-MA600
The table number is an identification number that refers to the module table. You can create a table with 4 registers with addresses from module table 9.
Limited special table, output table Register size (bytes) 1 2 2 2 2 W W W W Register access Available through expansion module
Value 1 address Value 2 address Value 3 address Value 4 address Length: 9 bytes
You can read out the assigned addresses using the input table.
Input table Register size (bytes) 1 2 2 2 2 Register access R R R R R Available through expansion module
Length: 9 bytes
12-28
PHOENIX CONTACT
104413_en_00
PROFIBUS register
12.13 Diagnostics
The diagnostics function includes the display of an extension module, serial number, measuring instrument product code as well as of an alarm or value overrun.
Diagnostics Register size (bytes) 1 Register access R Available through expansion module
Slot 1 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600
Slot 2 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600 Slot 3 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600
104413_en_00
PHOENIX CONTACT
12-29
EEM-MA600 Table 12-15 Designation Slot 4 0xFF: No module connected 0x0: JBUS/MODBUS EEM-RS485-MA600 0x1: Not available 0x02: Not available 0x03: Not available 0xF0: Not available 0x20: Input/Output EEM-2DIO-MA600 0x30: Analog output EEM-2AO-MA600 0x40: Memory EEM-MEMO-MA600 0x50: PROFIBUS, EEM-PB-MA600 or EEM-PB12-MA600 0x60: Temperature EEM-TEMP-MA600 0x70: Ethernet EEM-ETH-MA600 or EEM-ETH-RS485-MA600 Serial number Manufacturer code Diagnostics [...] Register size (bytes) 1 Register access R Available through expansion module
4 1
R R
12-30
PHOENIX CONTACT
104413_en_00
PROFIBUS register Table 12-15 Designation Diagnostics [...] Register size (bytes) Register access R Available through expansion module
OUT 1 Current alarm lower threshold 4 (output types): Bit 0: I: Total current Bit 1: In: Neutral conductor current Bit 2: U: Line voltages (1-2/2-3/3-1) Bit 3: V: Line voltage against N (1/2/3) Bit 4: P+: Total positive real power Bit 5: Q+: Total positive reactive power Bit 6: S: Total apparent power Bit 7: F: Frequency Bit 8: PFL: Total inductive power factor Bit 9: HOUr: operating hours counter Bit 10: THD I: Total harmonic distortion of current Bit 11: THD IN: Total harmonic distortion of neutral conductor current Bit 12: THD U: Total harmonic distortion of line voltage (1-2/2-3/31) Bit 13: THD V: Total harmonic distortion of line voltage against N (1/2/3) Bit 14: P-: Total negative real power Bit 15: Q-: Total negative reactive power Bit 16: PFC: Total capacitative power factor Bit 17...31: not available OUT 1 threshold exceeded 4 (output types): Bit 0: I: Total current Bit 1: In: Neutral conductor current Bit 2: U: Line voltages (1-2/2-3/3-1) Bit 3: V: Line voltage against N (1/2/3) Bit 4: P+: Total positive real power Bit 5: Q+: Total positive reactive power Bit 6: S: Total apparent power Bit 7: F: Frequency Bit 8: PFL: Total inductive power factor Bit 9: HOUr: Operating hours counter Bit 10: THD I: Total harmonic distortion of current Bit 11: THD IN: Total harmonic distortion of neutral conductor current Bit 12: THD U: Total harmonic distortion of line voltage (1-2/2-3/31) Bit 13: THD V: Total harmonic distortion of line voltage against N (1/2/3) Bit 14: P-: Total negative real power Bit 15: Q-: Total negative reactive power Bit 16: PFC: Total capacitative power factor Bit 17...31: not available Length: 17 bytes
104413_en_00
PHOENIX CONTACT
12-31
EEM-MA600
13 Technical data
Input data
Measuring principle Measured value True r.m.s. value measurement (TRMS) up to 63 Harmonic AC sine (45 Hz ... 65 Hz)
Power measurement
Measuring range Accuracy Real energy (IEC 62053-22) Reactive energy (IEC 62053-23) 0 ... 8000 MW/Mvar/MVA 0.5% Class 0.5S Class 2
Output data
Optional for special function/communication module
Supply
Supply voltage range Nominal power consumption 110 400 V AC 10% 120 ... 350 V DC 20% < 10 VA (without extension modules) < 20 VA (with extension modules)
Display
Type Refresh Backlit LCD 1s
General data
Dimensions W/H/D Installation depth without extension module Installation depth with extension module Degree of protection Front Back Weight IP52 IP30 400 g 96 x 96 x 82 mm 60 mm 80 mm
13-1
PHOENIX CONTACT
104413_en_00
Technical data
Electrical isolation
Rated insulation voltage < 300 V AC (L/N) surge voltage category III
Connection data
Conductor cross section (current) Conductor cross section (voltage and other) Connection method Tightening torque 0.5 mm ... 6 mm 0.5 mm ... 2.5 mm Screw connection 0.4 Nm
Ambient conditions
Ambient temperature (operation) Ambient temperature (storage/transport) Permissible humidity (operation) -10C ... 55C (14F ... 131F) -20C ... +85C (-4F ... 185F) 95%
Conformance/approvals
Conformance CE-compliant
104413_en_00
PHOENIX CONTACT
13-2
EEM-MA600
13-3
PHOENIX CONTACT
104413_en_00
Additional features
-
Functional features Symbols Measuring range Function-related accuracy class in accordance with IEC 61557-12
0.5 1 1 0.5 1 0.5 0.02 0.2
Additional features
Total real power Total reactive power (arithmetic or vectorial) Total apparent power (arithmetic or vectorial) Total real energy Total reactive energy (arithmetic or vectorial) Total apparent energy (arithmetic or vectorial) Frequency Phase current
0 ... 99999999 kW/h 0 ... 99999999 kVar/h 0 ... 99999999 kW/h 45 .. 65 Hz 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase
-90 ... +90 0.02 ... 1.2 In with PF = 0.5 L or 0.8 C 0.1 ... 1.2 In with SinPhi = 0.5 L or 0.5 C 10 ... 110% of In (In = 1 or 5 A depending on current transformer) 10 ... 110% of In (In = 1 or 5 A depending on current transformer) for PF 0.5 ... 1 -
IN, INc
0.2
Voltage Power factor (arithmetic or vectorial) Flicker (short-term, long-term) Voltage dips Excessive voltage
Voltage interrupts Voltage asymmetry in terms of amplitude Voltage asymmetry in terms of phase and amplitude Voltage harmonics Voltage THD (based on ground)
104413_en_00
PHOENIX CONTACT
A-1
EEM-MA600 Table A-2 Function Functional features (...) Symbols Measuring range Function-related accuracy class in accordance with IEC 61557-12
1 1 -
Additional features
Voltage THD (based on harmonic) Current harmonic Current THD (based on ground) Current THD (based on harmonic) Mains signal voltage
0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer -
Functional features for evaluating mains quality Symbols Measuring range Function-related accuracy class in accordance with IEC 61557-12
0.02 0.2 0.5 0.2 0.2 or 0.5 0.2 or 0.5 0.5 1 1 -
Additional features
Frequency Phase current Neutral conductor current Voltage Flicker (short-term, long-term) Voltage dips Excessive voltage Voltage interrupts Voltage asymmetry in terms of amplitude Voltage asymmetry in terms of phase and amplitude Voltage harmonics Current harmonic Mains signal voltage
f I In, Inc U Pst, Plt Udip Uswl Uint Unba Unb Uh Ih Msv
45 ... 65 Hz 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 50 ... 600 V phase/phase 0.1 ... 1.2 A for 1 A current transformer 0.5 ... 6 A for 5 A current transformer -
A-2
PHOENIX CONTACT
104413_en_00
B Abbreviations
1BL 2BL 3BL 3NBL 4BL 4NBL AUX AVG bACLIt Ct Ct In EAEA+ ERER+ ES HOUr ISYS MAX MAX PMAX P+ MAX QMAX Q+ MAX S nEt PF Single-phase network, 2-wire with 1 current transformer Two-phase network, 2-wire with 1 current transformer Three-phase network with symmetrical load, 3-wire with 1 current transformer Three-phase network with asymmetrical load, 3-wire with 2 or 3 current transformers Three-phase network with symmetrical load, 4-wire with 1 current transformer Three-phase network with asymmetrical load, 4-wire with 3 current transformers Supply voltage Average values Backlighting Current transformer Current transformer for neutral conductor Negative real energy (-kWh) Positive real energy (+kWh) Negative reactive energy (-kvarh) Positive reactive energy (+kvarh) Apparent energy (-kVAh) Hour counter Average current value (I1+I2+I3)/3 Maximum values Maximum value of negative real power within the measuring time Maximum value of positive real power within the measuring time Maximum value of negative reactive power within the measuring time Maximum value of positive reactive power within the measuring time Maximum value of the apparent power within the measuring time Network type Power factor
104413_en_00
PHOENIX CONTACT
B-1
EEM-MA600 rSET SErI SOFt THD I THD In THD U THD V tIME 4I tIME F tIME P/Q/S tIME U TRMS Ut Ut PR Ut SE USYS VSYS Reset Serial number Software version Total harmonic distortion of currents Total harmonic distortion of neutral conductor current Total harmonic distortion of conductor voltages (1-2/2-3/3-1) Total harmonic distortion of conductor voltages against N (1/2/3) Measuring time to determine the average and maximum current values Measuring time to determine the average and maximum frequency values Measuring time to determine the average and maximum power values Measuring time to determine the average and maximum voltage values True r.m.s. value measurement (True Root Mean Square) Voltage transducer Voltage transducer primary side Voltage transducer secondary side Average value of the phase/phase conductor voltages (U12 + U23 + U31)/3 Average value of the phase/N conductor voltages (V1 + V2 + V3)/3 Hour counter
B-2
PHOENIX CONTACT
104413_en_00