Sie sind auf Seite 1von 2

A TOGNUM GROUP BRAND

DIESEL GENSET - 50 HZ WATER CHARGE-AIR COOLING


1170 - 1285 kVA 400V BENEFITS
// // // // //

Low installment cost Best fuel consumption values Long maintenance intervals High-efciency components Best-in-class reliability and availability

SYSTEM RATINGS
Standby Power
Genset Type DS1285 D5S Engine Type 18V 2000 G65 TB Nominal Rating kVA 1) 1285 Emissions kVA 2) 1285 Fuel optimized

Prime Power
Genset Type DP 1170 D5S Engine Type 18V 2000 G65 TB Nominal Rating kVA 1) 1170 Emissions kVA 2) 1170 Fuel optimized

//

REFERENCE CONDITIONS 1) 2)
31C (88F) 70C (158F) 1000 mbar 400 m 25C (77F) 70C (158F) 1000 mbar 100 m

//

ENGINE DATA
130/150 mm (5.1/5.9 in) 90V 1.99 lit. (121 cu in) 18V: 35.8 lit. (2185 cu in) EN 590, Grade No.1-D/2-D (ASTM D975-00)

Ambient air temp.: Charge air coolant temp.: Ambient air pressure: Altitude above sea level:

Bore/Stroke Cyl. conguration Cyl. displacement Displacement, total Fuel specication

Application 3B

Denition Prime Power Continuous operation with variable load Standby Power Standby operation with variable load

3D

Load factor: < 75 % Operating hours/year: unrestricted Overload: 10 % capability (ICXN) Load factor: < 85 % Operating hours/year: max. 500 Overload: Fuel stop power (IFN)

Gensets available also with Air Charge Air Cooling All Gensets are available with optional Voltages 380V and 415V. Ratings can variate please contact your MTU distributor.

Genset Type Engine Type Generator type Fuel Consumption * 100% load g/kWh (l/h) 203 (269) 75% load g/kWh (l/h) 200 (199) 50% load g/kWh (l/h) 201 (133) Electrical Radiator, for remote installation Max. air temperature on fan C TBD Ambient temperature C 40 Fan air ow (77F and 29.22Hg) m3/s 22.52 Fan power kW Air ow restriction Pascal Heat dissipated by engine cool. kW Water ow engine cool. circuit m3/h Cool. temp. at engine outlet Charge air heat dissipation Water ow eng. charge air circ. Cool. temp. before intercooler Dimensions (LxWxH) Weight, wet Air Intake Intake air depression Intake air ow Exhaust System Exhaust gas ow Exhaust gas temperature Exhaust back pressure Generator Temperature rise Lube System Engine oil capacity Emissions Air born noise level at 1m Exhaust noise level at 1 m Dimensions Length Width Height Total weight, wet C kW m3/h C mm kg mbar m3/s m3/s C mbar K l dB(A) dB(A) mm mm mm kg 32.3 200 445

Fuel Optimized Standby DS1285D5SFW 18V 2000 G65 TB 742RSL7048

Prime DP1170D5SFW 18V 2000 G65 TB 742RSL7048 202 (243) 200 (181) 204 (123) TBD 40 22.52 32.3 200 425 40 95 215 14 60 1850x2100x2550 1550 15 1.15 3.3 555 50 125 (H) 130 105 107 4380 1660 1880 7708

40 95 250 14 60 1850x2100x2550 1550 15 1.25 3.6 550 50 125 (H) 130 103 108 4380 1660 1880 7708

Power requirement for cooling fan is not included in rating. * Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml. Note: This drawing is provided for reference only and should not be used for planning installation. Please contact your local distributor for more detailed information. Materials and specications subject to change without notice.

// Tognum Group Companies: Europe / Middle East / Africa / Latin America / MTU Onsite Energy / 88040 Friedrichshafen / Germany / Phone +49 7541 90 7060 / Fax +49 7541 90 7084 / powergenregion1@mtu-online.com // Asia / Australia / Pacic / MTU Onsite Energy / 1, Benoi Place / Singapore 629923 / Republic of Singapore / Phone +65 6861 5922 / Fax +65 6861 3615 / powergenregion2@mtu-online.com // USA / Canada / Mexico / MTU Onsite Energy Corporation / 100 Power Drive / Mankato, MN 56001 / USA / Phone +1 507 625 7973 / Fax +1 507 625 2968 / powergenregion3@mtu-online.com // Worldwide for HotModule / MTU Onsite Energy / 81663 Munich / Germany / Phone +49 89 20 30 42 800 / Fax +49 89 20 30 42 900 / info@mtu-online.com // www.mtu-online.com

Subject to change. | 3233361 | 1/11 | VMC 2011-05.