UK/Norway Co-operation Implementation Group

Gas & Infrastructure Action Group


Recommendation 8 Gas Quality

CONTENTS 1.0 INTRODUCTION 1.1 Recommendation 8 1.2 Workgroup Structure 1.3 Additional Input COMPARISON BETWEEN UK AND NORWEGIAN SPECIFICATIONS 2.1 UK Specifications 2.1.1 GS(M)R 2.1.2 Transco Indicative Specifications 2.2 Norwegian Specification 2.3 Areas of Potential Differences between UK and Norwegian Specifications 2.3.1 Gross Calorific Value (GCV) 2.3.2 CO2 2.3.3 Wobbe Index 2.3.4 Incomplete Combustion Factor and Soot Index CAN THE UK SPECIFICATIONS BE CHALLENGED AND AMENDED 3.1 GCV 3.2 CO2 3.3 Wobbe Index 3.4 ICF and SI HOW COULD NCS GAS ACHIEVE/COMPLY WITH UK SPECIFICATIONS 4.1 Blending 4.2 Further Processing 4.3 Nitrogen Injection 4.4 CO2 Removal GLOBAL COST ESTIMATES FOR OPTIONS DISCUSSED 5.1 Blending 5.2 Further Processing 5.3 Nitrogen Injection 5.4 Changing Specifications 5.5 Burner Upgrades 5.6 CO2 Removal OPTION RANKING UK GOVERNMENT POSITION CONCLUSIONS AND FORWARD ACTION PLAN

2.0

3.0

4.0

5.0

6.0 7.0 8.0

APPENDIX A: APPENDIX B: APPENDIX C: APPENDIX D: APPENDIX E:

UK Gas Specifications GASSCO presentation Gas quality coming from the NCS to UK Powerpoint presentation Advantica Presentation Advantica Proposal, Impact of UK Interchangeability Methodology on Future Natural Gas Supplies

1.0 1.1

INTRODUCTION Recommendation 8 of the UK/Norway Co-operation Implementation Group Promote the need for improved compatibility of UK, Norwegian and Continental gas sales specifications by dialogue between respective ministries and stakeholders. This Recommendation suggests that there is a mismatch between the specifications for UK Sales Gas and the Norwegian Continental Shelf (NCS). The aim of this report is to summarise the workgroup findings. The report covers the following topics: Comparison between Norwegian and UK gas specifications Areas of potential differences Can the UK specifications be changed? How can Norwegian gas comply with UK sales gas requirements? Ranking UK Government Perspective Conclusions Forward action plan

This report is designed to accompany a series of PowerPoint presentation slides, contained in Appendix C. 1.2 Workgroup Structure A Workgroup was set up in January 2003 comprising:

David Hainsworth Jonathan Maughan Mike Wade David Elmes Tor Erik Hanson

TFEEUK (Leader) TRANSCO ConocoPhillips UK Shell UK TFE Norge (Meeting 3)

1.3

Additional Input It was felt that although this Gas and Infrastructure Action Group was set up to look at the UK and Norway, any findings, recommendations or forward actions from the Workgroup should take account of the wider picture. The UK will become a net importer of gas in 2005/6 and the same specification issues may arise for other import routes, eg Interconnectors and LNG imports. Consequently we have made informal contact with the following stakeholders in order to establish whether they have similar issues:

Interconnector UK, Operator of the Bacton/Zeebrugge Interconnector Centrica, a major supplier of gas in the UK who are also likely to import more gas. Members of the EASEE-Gas (European Association for Streamlining of Energy Exchange) group Advantica Technology, formally British Gas Research

Their feedback supports the findings drawn in this report. We have also made contact with the UK DTI, which has proved to be very timely as during the Workgroup process the UK Government issued an Energy White Paper which has raised the issue of misalignment of imported gas specifications. A meeting was held with the DTI to allow this to be explored in more detail so that any potential impact on this Workgroups conclusions could be assessed and included (see section 7.0).

2.0 2.1

COMPARISON BETWEEN UK AND NORWEGIAN SPECIFICATIONS UK Specifications The UK specifications are made up of two parts, those which are specified in law (GS[M]R) and those indicative specifications which are given by Transco as operator of the UK onshore system. The specifications given in GS(M)R are fixed and have to be met until such time as the legislation is changed, whereas Transco may have some flexibility in how they apply their indicative specifications.

2.1.1 Existing Gas Processing Terminals Each Gas Processing Terminal in the UK has a gas quality specification based on commercial agreements between gas buyers and producers and if these terminals were in existence before the introduction of the Network Code in 1996, these gas specifications are contained within the gas entry provisions described in the Network Code. Any changes required to these specifications will need to be agreed with Transco and the UK Shippers. 2.1.2 New Entry Connections Each year, Transco issues a Ten Year Statement (on www.uktransco.com) that amongst other things describes the indicative gas quality specifications (see Appendix A) that Transco can accept at any new landing point. From time to time new suppliers of gas will not be able to comply with these specifications and Transco may be able to provide some flexibility on a case by case basis. However, under no circumstances will Transco agree to a gas quality specification that does not meet the requirements of GS(M)R (as described in Appendix A). 2.2 Norwegian specifications The NCS specification has been derived from operation of the Gassco system and delivery specifications to existing locations. The specifications are included in Appendix A. It should be noted that the Gassco system has many options for blending and as such Gassco may accept gas streams into the system which do not meet the delivery specifications. 2.3 Areas of Potential Differences between UK and Norwegian Specifications The following Table describes the differences between UK (Transco indicative) and Norwegian Specifications. An indicative European specification has also been included in the table for information, which shows that there are further differences to be managed if a wider European perspective is taken on gas specifications. There are many different specifications in use within Europe, we are aware that EASEE-Gas group has just set up a workgroup to look at how European gas specifications could be harmonised.

Is it a problem?
Designation Norwegian Continental Shelf (NCS) GS(M)R Typical National Transmission System (NTS) Europe (for info.) Variations against GS(M)R Variations against Typical NTS spec. Typically there is higher CV gas in the Northern part of the NTS so as a general guide Norwegian gas being input at Northerly terminals is likely to be accommodated at varying CVs. Not likely to be a significant issue. Unlikely Transco does accept some gases into the network with CO2 levels above 2% so it is likely that gas with the CO2 level of up to 2.5% can be accommodated at Northerly terminals. It is possible that Transco could not accept gas at Southerly terminals such as Bacton due to existing contractual commitments. NO

Options for overcoming problems, (Note 2)


Options to meet G(S)MR Options to meet typical NTS spec.

Gross Calorific Value

38.1 to 43.7 3 MJ/Sm

36.9 to 42.3 3 MJ/Sm

38.9 to 44.6 3 MJ/Nm

NO

To deliver gas at a GCV higher than 42.3 MJ/SCM would require a change to the high end of the Wobbe specification

Oxygen

Less than 0.1 mole%

Less than 0.2% (molar)

No more than 10 parts per million

No more than 10 parts per million

NO

Carbon Dioxide

Less than 2.5 mole%

Maximum 2 mol %

Maximum 2 mol %

NO

Subject to Network Analysis by Transco. Ensure that NW deliveries are kept below 2 mol% by bending or CO2 removal. Potential to remove CO2 at receiving Terminal -

H2S

Less than 5 3 mg/Nm Less than 15 parts per million 18 C at 69 barg 10 C at any pressure above 50 barg
O O

Less than or equal to 3 5 mg/m Less than or equal to 3 50 mg/m See Note 1 See Note 1

Max 3.3 parts per million Max 15 parts per million 10 C at the delivery pressure 2 C at 75 barg
O O

Max 3.3 parts per million Max 15 parts per million -10 C at 69 barg 2 C at 69 barg
O O

NO

Total sulphur Water dewpoint Hydrocarbon dewpoint

NO NO NO

NO NO NO

Is it a problem?
Designation Norwegian Continental Shelf (NCS) GS(M)R Note 2) (See Typical National Transmission System (NTS) Europe (for info.) Variations GS(M)R against Variations against Typical NTS spec.

Options for overcoming problems


Options G(S)MR to meet Options to meet typical NTS spec. Challenge validity of spec. Process, Norway or UK terminal Blend gases offshore or at, UK terminal. Inject nitrogen, to suppress WI Change out burners in UK to make compatible with wider quality Can easily heat gas on arrival

Wobbe Index

48.3 to 52.8 3 MJ/Sm

47.2 to 51.41 3 MJ/Sm

48.14 to 51.41 3 MJ/Sm

50.9 to 54.0 3 MJ/Nm

Norwegian gas at the top of the Wobbe range is not compatible with some UK domestic appliances on a stand alone basis

Norwegian gas at the top of the Wobbe range is not compatible with some UK domestic appliances on a stand alone basis

Challenge validity of spec. Process, Norway or UK terminal Blend gases offshore or at UK terminal. Inject nitrogen, to suppress WI Change out burners in UK to make compatible with wider quality Can easily heat gas on arrival

Temperature Less than or equal to 0.1%(molar)

Hydrogen

Not less than O 1 C. Not more than O 38 C Less than or equal to 0.1 mol %

Not less O than 2 C. Not more O than 38 C

Maybe a problem but easy to resolve Maybe, further investigation required Yes, should be treated with Wobbe, depending on Dutton envelope can be more restrictive than Wobbe. ICF limits Wobbe envelope and therefore Norwegian gas outside the ICF range will not be compatible with UK appliances

Maybe a problem but easy to resolve Maybe, further investigation required Yes, should be treated with Wobbe, depending on Dutton envelope can be more restrictive than Wobbe. ICF limits Wobbe envelope and therefore Norwegian gas outside the ICF range will not be compatible with UK appliances

Incomplete Combustion Factor

Less than 0.48

Less than 0.48

Challenge validity of spec. Process, Norway or UK terminal Blend gases offshore or at, UK terminal. Inject nitrogen, to suppress WI Change out burners in UK to make compatible with wider quality

Challenge validity of spec. Process, Norway or UK terminal Blend gases offshore or at, UK terminal. Inject nitrogen, to suppress WI Change out burners in UK to make compatible with wider quality

Is it a problem?
Soot Index Less than 0.60 Less than 0.60 Yes, should be treated with Wobbe depending on Dutton envelope can be more restrictive than Wobbe. ICF limits Wobbe envelope and therefore Norwegian gas outside the ICF range will not be compatible with UK appliances Yes, should be treated with Wobbe depending on Dutton envelope can be more restrictive than Wobbe. ICF limits Wobbe envelope and therefore Norwegian gas outside the ICF range will not be compatible with UK appliances

Options for overcoming problems


Challenge validity of spec. Process, Norway or UK terminal Blend gases offshore or at, UK terminal. Inject nitrogen, to suppress WI Change out burners in UK to make compatible with wider quality Challenge validity of spec. Process, Norway or UK terminal Blend gases offshore or at, UK terminal. Inject nitrogen, to suppress WI Change out burners in UK to make compatible with wider quality

Inerts

Nitrogen

Not more than 7 mol % Not more than 5 mol %

No

Unlikely

No

Unlikely

Note 1

Shall be at such levels they do not interfere with the integrity or operation of pipes or any gas appliance which a consumer could reasonably be expected to operate. Where options have been identified to resolve a problem then it is intended that CAPEX and OPEX estimates are developed at a high level for each option so that they can be ranked.

Note 2

It can be seen that there is potential for non-interoperability for some of the specifications, particularly GCV, Wobbe Index (together with the related ICF and SI) and CO2, but this will depend on the actual composition of the gas being transported from Norway to the UK. Gassco have plotted a number of gas compositions for potential gas steams to the UK against these three key specifications. These are shown in Figures 2.2.12.22. GCV: GCV is anticipated to be within the UK specifications for the Easington pipeline, but a number of the potential streams to Vesterled exceed the UK high limit. CO2: most potential streams are within the UK limit of 2%, although some in both in both the Easington pipeline and Vesterled are predicted to reach above 3%. Wobbe Index: almost all potential streams expected at Easington are within the UK maximum limit, but most of the streams through Vesterled exceed the limit. To complete the comparison against key UK specification limits, we have plotted the 16 potential streams on a Dutton envelope, as shown in Figure 2.2.2. The Dutton Envelope is a 3-dimensional area within a plot showing Wobbe Index against ICF and SI. Any gas streams which fall outside the 3-dimensional area are deemed unacceptable within the UK framework.

Figure 2.2.1: GASSCO plot of GCV against UK/NCS Specifications for various gases which may be routed to the UK

Gross Calorific Value (GCV)


45.00 44.00 43.00 42.00 [MJ/Sm] 41.00 40.00 39.00 38.00 37.00 36.00 11 14

New Southern Pipeline


NCS Max GCV

Vesterled

UK Max GCV

NCS Min GCV UK Min GCV

NCS max GCV UK min GCV

UK max GCV GCV

NCS min GCV

16

10

12

13

15

Figure 2.2.2: GASSCO plot of Wobbe indices against UK/NCS Specifications for various gases which may be routed to the UK

Wobbe Index
54.00 53.00 52.00

New Southern Pipeline


NCS Max WI

Vesterled

UK Max WI

[MJ/Sm]

51.00 50.00 49.00 NCS Min WI 48.00 UK Min WI 47.00 1 2 3 4 5 6 7 8 9 10 11 12 13 14 WI 15 16 High WI

NCS max WI

UK max WI

NCS min WI

UK min WI

Figure 2.2.3: Plot of various Norwegian gas compositions onto a Dutton Envelope

Gas Interchangeability Diagram


54 Wobbe Number (MJ/m3) 53 52 51 50 49 48 47 46 45 0 4 8 12 16 20 24 28 32 36 40 44 48 Non Methane Component in Equivalent Mixture (%)
NCS 1 NCS 2 NCS 3 NCS 4 NCS 5 NCS 6 NCS 7 NCS 8 NCS 9 NCS 10 NCS 11 NCS 12 NCS 13 NCS 14 Low er Emergency Wobbe Methane-Nitrogen Soot Index Methane-Propane Upper Emergency Wobbe

Upper Wobbe Incomplete Combustion Factor

Low er Wobbe

3.0

CAN THE UK SPECIFICATIONS BE CHALLENGED AND AMENDED? There is potential for Norwegian gas to be different from the requirements of the UK and the aim of this section is to explain how this process could be undertaken.

3.1

GCV Provided that the GCV of Norwegian gas meets the current upper limit of 42.3 MJ/SCM then it is unlikely that any further GCV restrictions will need to be applied.

3.2

CO2 Transco imposes a CO2 limit at entry to ensure that the integrity of its assets is not compromised and to ensure it can meet any exit requirements. These limits are not contained in GS(M)R and hence are not limited for safety reasons. Transco may be able to discuss different CO2 limits at some locations from the indicative specification of 2% but this can only be done on a case by case basis and where it can be demonstrated that such flexibility is required.

3.3

Wobbe Index, Incomplete Combustion Factor (ICF) and Soot Index (SI) These three specifications are strongly linked as they all relate to the safe burning of gas in domestic appliances. The UK is the only European country to have specifications for ICF and SI, as other countries either adopt a different approach or have a different make-up of domestic appliances. These three specifications were generated based on research work undertaken by British Gas and subsequent development of the Dutton Envelope. Advantica Technologies gave the Workgroup a presentation covering this in some detail; we have included this as Appendix B of this report. The issue for the UK surrounds the performance of older domestic appliances, some of which will have been converted from town gas to natural gas in the 1970s. It is believed that all appliances which meet current specifications (1990 Gas Appliance Directive 90/396/CEE [GAD]), would operate safely with the higher Wobbe Index of most stand alone NCS gases. Consequently there will be scope to change the specification if all UK domestic appliances could be shown to meet current standards. However, it is likely that many appliances in the UK today will date from prior to 1990 and therefore the following steps would be required: Conduct an appliance survey (it is over 10 years since the last one was carried out and no organisation in the UK is currently planning to carry out any further surveys). Demonstrate to the HSE and gain their agreement for a change to GS(M)R that there are no safety risks to consumers by changing the Wobbe range. Such a demonstration may require the changing or upgrading of many appliances.

For such a process to be successful it is believed that Transco, HSE, Ofgem and the DTI would have to work closely together. The potential costs would largely depend on the number of domestic appliances which would require modification or replacement.

4.0 4.1

HOW COULD NCS GAS ACHIEVE/COMPLY WITH UK SPECIFICATIONS? Blending Blending is clearly a good solution because it costs nothing technically; however it can be reliant on the availability of particular fields or facilities. If one of these key fields or facilities is unavailable then the loss of blending capacity can result in a significant loss of gas availability. Blending could take place in one or more of three possible ways: Within the Gassco Infrastructure At a UK Receiving Terminal Within the Transco system

4.1.1 Blending within the Gassco System The Gassco system is ideally set up for the blending of gases as there are several hubs within the system which receive gas from various fields and terminals. However it should be noted that each delivery pipeline potentially has a different delivery specification to meet, consequently although this provides for flexibility it also imposes potential constraints. Gassco already blends gases in order to meet delivery specifications and is familiar with that mode of operation. See Figure 4.1.1 below.

Figure 4.1.1: GASSCO schematic showing their Network and blending options
Nyhamna Volume

Heimdal Volume

Oseberg Volume

Kollsnes Volume Etanor Volume

Frigg Volume HRP

Krst Volume

St. Fergus Volume

Grane Volume

Sleipner Volume

SLR

Draupner

South UK Volume

Ekofisk Volume Volume ERF Dunkerque Volume Zeebrugge Volume Emden 1 (NPT) Volume Emden 2 (EMS) Volume Dornum Volume

4.1.2 Blending at a UK receiving Terminal If other pipelines land at the same terminal as Norwegian gas then there may be the potential for blending of gases, however this must be done upstream of the Transco NTS, otherwise Transco may not meet their Safety requirements (GS[M]R). 4.1.3 Blending within the Transco system Transco are currently unable to offer a blending service for any specification outside of GS(M)R as all gas in Transcos network covered by the safety case must comply by law with at least GS(M)R. 4.2 Further processing It is possible to build processing facilities to chill any incoming gas such that the heavier components can be removed, thus lowering the gas GCV and Wobbe index. It is anticipated that to meet the UK delivery specifications it would be necessary to chill the gas to 45 Deg C which implies the use of some form of mechanical expansion or refrigeration plant rather than a simple Joule/Thompson expansion. 4.3 Nitrogen injection It is also possible to suppress the Wobbe index of a gas by the injection of nitrogen in order to dilute the gas. Historically this technique has been used either on a continuous basis or intermittently in conjunction with blending. The continuous production of nitrogen is an energy intensive process and hence can result in significant operating costs. Nitrogen injection from storage as an occasional back-up for blending outages is a more financially attractive alternative. 4.4 CO2 removal The removal of relatively small percentages of CO2 from large volumes of gas is technically feasible but tends to be relatively expensive due to the size of process equipment required. As this is unlikely to be a significant issue we have not looked at this topic in detail.

5.0 5.1

GLOBAL COST ESTIMATES FOR OPTIONS DISCUSSED Blending The most attractive property of the blending option is that it could well be achieved at no cost. The NCS pipeline system is ideally set up for blending, eg at Heimdal, Sleipner, etc. However there are two potential limitations: Much of the gas available for blending will be required for fulfilling already existing sales obligations to European buyers. If key producers/facilities are unavailable then blending gas may not be available. This could impact on gas deliveries and result in financial exposure for shippers.

Gassco have carried out a series of blending runs in order to predict the potential Wobbe index at Easington/Dimlington during normal and upset conditions, Figure 5.1.1. It can be seen that from 2007 onwards the gas has the potential to be above the existing UK Wobbe Index upper limit.

Figure 5.1.1: GASSCO plot of potential Wobbe Index range of gas to be delivered to UK over time taking into account blending

Expected Wobbe Index development towards Easington/Dimlington via SLR

53.00 52.00

NCS Max WI

UK Max WI
[MJ/Sm3]

51.00 50.00 49.00 NCS Min WI 48.00 UK Min WI 47.00 2006 WI High NCS WI Max Spec 2007 WI low NCS WI Min Spec 2008 2009 2010 WI UK Min Spec WI High-low

WI UK Max Spec WI High-high

Figure 5.1.2: GASSCO plot of potential CO2 range of gas to be delivered to UK over time taking into account blending

Expected CO 2 development towards Easington/Dimlington via SLR

3.0 NCS Max CO2 2.5 2.0


[mol%]

UK Max CO2

1.5 1.0

0.5 0.0 2006 CO2 (WI High) 2007 2008 CO2 (WI low) 2009 UK CO2 Spec 2010 NCS CO2 Spec

5.2

Further Processing Further processing would require capital expenditure on a plant and ongoing operating costs. Based on assessment of potential projects an indicative cost has been estimated in the range of 0.5 to 1.0 million/year for an annual daily gas throughput capacity of 1 million sm3 (about 0.5p/therm). (This needs a capital cost estimate to be meaningful.)

5.3

Nitrogen Injection Nitrogen injection has been used in the past for compressing the Wobbe mdsc of gas. It has also been studied at a high level in connection with possible future LNG imports to the UK. It is potentially capital and operating cost intensive, a high level estimate of 0.3 million/year for an annual daily gas throughput capacity of one million sm3 has been estimated (about 0.25p/therm). Nitrogen injection can either be used on a continuous basis or intermittently (from storage for example). However it is not a favoured long term solution for Transco as it results in the requirement to transport greater volumes of gas around the network than would be necessary if the gas was not diluted. (As above a capital cost estimate needs to be included.)

5.4

Specification Change The initial costs associated with challenging/changing specifications tend to be relatively low as this tends to be restricted to study work. In the event, however, that modifications were required to domestic appliances, costs could become enormous. It is understood that there are approximately 43 million domestic gas appliances in the UK. Early estimates suggest that an exercise as comprehensive as that carried out in the 1970s would run into billions of pounds, but until a survey has been carried out it is difficult to be precise. A scope of work is set out in Appendix E. On the positive side, a wider specification should ensure that gas can be brought in at a competitive price and hence there will also be a potential payback as well as cost.

6.0

OPTION RANKING We have made a simple qualitative analysis, ranking each option against cost and security of supply. The aim of this exercise is to give an overall feel as to the pros and cons of each option.

6.1

Wobbe, ICF & Soot Indexes Cost Low Medium Low/High Medium Security of Supply Poor Neutral Good Neutral

Blending Processing Specification Change Nitrogen Injection

6.2

Ranking Conclusions It can be seen from the above ranking exercise that the most attractive option in terms of security of supply is to change the specifications, however until the true cost to the domestic customer can be verified and balanced against the potential reduction in supply cost it is difficult to conclude whether this would be the best overall option for Norwegian gas. The three other options: blending, processing and nitrogen injection, are similar, all having advantages and disadvantages. The Gassco system has great potential for blending and therefore we asked Gassco to carry out some blending analyses in order to establish how easily the UK specification could be achieved, in the short, medium and long term. Further processing at a receiving terminal obviously has a cost, although this may be offset by potential revenue from NGLs created during the processing. However, Norwegian gas tends to be dry, offering only the potential for relatively low liquid yields and depending on the loading point delivering the NGLs economically to an end user could be an issue. Continuous nitrogen injection offers the least elegant solution, as it is a potentially energy intensive process, however using nitrogen from storage as a back-up to blending may be of some merit.

7.0

GOVERNMENT POSITION In February 2003 the UK Government published an Energy White Paper (cm 5761), in which paragraph 6.21 states: It is possible that gas imports from some sources, particularly LNG, will vary in energy content and may require blending with other gases in the system, special processing on import, or the modification of certain gas appliances. We will keep developments here closely under review. In particular we will monitor the likely effects on gas quality. It is clear that the DTI has recognised the same issues identified by this workgroup with respect to Wobbe Index, ICF and SI. We met with the DTI to investigate if they have a compatible strategy with the results of this work. The DTI explained that they have recently held a meeting with Ofgem and the HSE. From the meeting they have agreed to work together on the following 2 stage exercise: Stage 1: Study to confirm whether the Wobbe number of imported gas is likely to increase. Stage 2 (contingent): Public consultation on: the problem (compatibility of high Wobbe gas with certain appliances); the policy response (treat the gas or modify/remove the appliances).

Timing approximately one year Clearly the NCS Wobbe Index has the potential to be higher that the current UK specification and therefore this information should be fed into the exercise being initiated by the DTI. It is also believed that significant quantities of LNG available on the open market will have gas with a relatively high Wobbe index. Consequently we can anticipate that there is a high probability that Stage 2 will be initiated, noting the timescale of one year mentioned this would be compatible with the impact of significant additional volumes of gas from Norway to the UK.

8.0 8.1

CONCLUSIONS AND FORWARD ACTION PLAN Conclusions This report identifies the potential areas of conflict between the UK and Norwegian gas specifications. As a result of the work completed by the sub-group we believe that we can draw the following conclusions. A forward action plan has also been identified, which is necessary before it will be possible to identify the final optimal solution. Wobbe Index, ICF and SI are the main areas of concern. Norwegian gas has the potential to have a higher Wobbe Index than the UK Specification in the future. There are several ways of tackling the problem, o Blending o Further processing o Nitrogen Injection o Change the Specification There is a bigger UK picture as a result of the need to import gas from other sources A change in specification has the potential to be the most elegant solution but it is not possible to quantify the cost/benefit at this time. The UK DTI has recognised the specification issue and is working together with Ofgem and HSE.

8.2

Forward Action Plan The following forward actions have been identified during this work: a) A scope of work to challenge the UK specifications has been prepared, this includes potential costs and timescales of such a study and conclusions would result in a global cost estimate of the change-out or modification of domestic appliances (see Appendix E). b) Follow up DTI, Ofgem and HSE initiative on specifications.

APPENDIX A SUMMARY OF UK AND NORWEGIAN GAS SPECIFICATIONS


1. Gas Safety (Management) Regulations The following is an extract from the Gas Safety (Management Regulations) 1996 which is applicable to any person conveying gas in the UK. Content and other characteristics of gas (1) No person shall, subject to paragraphs (2) to (4), convey gas in a network unless the gas conforms with the requirements specified in Part I of Schedule 3. The network emergency co-ordinator may, where it is necessary to prevent a supply emergency and in accordance with the arrangements specified in his safety case pursuant to paragraph 3(d) of Schedule 2, authorise, for the period specified in the authorisation, gas not conforming with the requirements specified in Part I of Schedule 3 to be conveyed in the network if the gas conforms with the requirements specified in Part II of that Schedule. An authorisation under paragraph (2) may be given orally or in writing and may be withdrawn at any time. Where only one person conveys gas in a network, he may, where it is necessary to prevent a supply emergency and in accordance with the arrangements specified in his safety case pursuant to paragraph 19 of Schedule I, convey gas which does not conform with the requirements specified in Part I of Schedule 3 if the gas conforms with the requirements specified in Part II of that Schedule.

(2)

(3)

(4)

SCHEDULE 3, Regulation 8 CONTENT AND OTHER CHARACTERISTICS OF GAS PART I REQUIREMENTS UNDER NORMAL CONDITIONS 1. The content and characteristics of the gas shall be in accordance with the values specified in the following table. Content or Value characteristic hydrogen content sulphide <=5 mg/m3

total sulphur content <=50 mg/m3 (including H2S) hydrogen content oxygen content impurities <=0.1% (molar) <=0.2% (molar) shall not contain solid or liquid material which may interfere with the integrity or operation of pipes or any gas appliance (within the meaning of regulation 2(1) of the 1994 Regulations) which a consumer could reasonably be expected to operate

shall be at such levels that they do not interfere with the integrity or hydrocarbon operation of pipes or any gas appliance (within the meaning of dewpoint and water regulation 2(1) of the 1994 Regulations) which a consumer could dewpoint reasonably be expected to operate WN ICF SI 2. (i) (ii) <=51.41 MJ/m3, and >=47.20 MJ/m3

<=0.48 <=0.60

The gas shall have been treated with a suitable stenching agent to ensure that it has a distinctive and characteristic odour which shall remain distinctive and characteristic when the gas is mixed with gas which has not been so treated, except that this paragraph shall not apply where the gas is at a pressure of above 7 barg. The gas shall be at a suitable pressure to ensure the safe operation of any gas appliance (within the meaning of regulation 2(1) of the 1994 Regulations) which a consumer could reasonably be expected to operate. (1) (2) Expressions and the abbreviations used in this Part shall have the meanings assigned to them in Part III of this Schedule. ICF and SI shall be calculated in accordance with Part III of this Schedule.

3.

4.

2.

Transco Indicative Specifications The following is an extract from Transcos Ten Year Statement that describes the gas entry conditions for new gas entry connections. For any new Entry connection to the Transco System, the connecting party should notify Transco as soon as possible as to the likely gas composition. Transco will then discuss whether this is feasible, on a case by case basis. In some cases, network analysis may be required and this will be based on the existing system taking into account Transcos existing statutory and contractual obligations. Therefore, due to continuous changes being made to the system any undertaking made by Transco on gas quality prior to signing a Network Entry Agreement will only be indicative. Transcos ability to accept gas into the system is affected, inter alia, by the gas quality, by the location of the entry point on the system, by the volumes entered and by the quality and volume of gas already being transported on the system. In assessing the acceptability of any proposed gas composition, Transco will take account of: a) b) c) Its ability to continue to meet its statutory obligations with respect to gas quality (including, but not limited to, the Gas Safety (Management) Regulations 1996); The implications of the proposed gas composition on system running costs; and Its ability to continue to meet its contractual obligations.

For indicative purposes, the specification set out below is usually acceptable for most locations. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Hydrogen Sulphide - not more than 5mg/m. Total Sulphur - not more than 50mg/m. Hydrogen not more than 0.1% (molar). Oxygen not more than 0.001% (molar). Hydrocarbon Dewpoint - not more than -2C at any pressure up to 85 bar g. Water Dewpoint - not more than -10C at 85 bar g (or the actual delivery pressure). Wobbe Number (real gross dry) within 48.14 to 51.41 MJ/m range, and in compliance with ICF & SI limits listed below. Incomplete Combustion Factor (ICF) - not more than 0.48. Soot Index (SI) not more than 0.60. Gross Calorific Value (real gross dry) a value will be set within the band 36.9 to 42.3 MJ/m, in compliance with the Wobbe Number, ICF and SI limits described above, subject to a 1 MJ/m variation. Inerts - not more than 7.0% (molar) subject to Carbon Dioxide: not more than 2.0% (molar) or Nitrogen: not more than 5.0% (molar) Contaminants the gas shall not contain solid, liquid or gaseous material that may interfere with the integrity or operation of pipes or any gas appliance within the meaning of regulation 2(1) of the Gas Safety (Installation and Use) Regulations 1998 that a consumer could reasonably be expected to operate. Delivery Temperature between 1C and 38C. Odour gas delivered shall have no odour that might contravene the statutory obligation not to transmit or distribute any gas at a pressure below 7 bar g which does not possess a distinctive and characteristic odour.

11. 12.

13. 14.

APPENDIX B GASSCO PRESENTATION Gas Quality Coming from the NCS to UK

North Sea Cooperation Gas & Infrastructure Work Group


Recommendation 8 - Gas quality coming from the NCS to UK
Presentation to the UK and Norwegian Work groups

Stavanger March 20th

Introduction
North Sea Cooperation Gas & Infrastructure Work Group Norwegian Work Group

Recommendation 7
NTS charges and Auction system

Recommendation 8
Gas Specifications

Recommendation 11
Code of Practice

Sub - Group
Define Scenarios for the gas quality coming from NCS to UK

Summary

Challenges present in the NCS system


CO2 in Dornum GCV in Zeebrugge H2S in Emden WI in St Fergus

NTS specs as of today will introduce additional challenges in the future

What gas quality can the UK market see coming from NCS? Focus on:
Wobbe Index
CO2 GCV

Challenges in the NCS


Nyhamna Volume

Heimdal Volume

Oseberg Volume

Kollsnes Volume Etanor Volume

Frigg Volume HRP

Krst Volume

St. Fergus Volume

Grane Volume

WI
Sleipner Volume SLR Draupner

South UK Volume

Ekofisk Volume Volume ERF Dunkerque Volume Zeebrugge Volume Emden 1 (NPT) Volume Emden 2 (EMS) Volume Dornum Volume

WI CO2

GCV

H2S

CO2

Assumptions

Dedicated pipeline from NCS to Easington/Dimlington in 2006 Sleipner as tiein node for Ormen Lange (2007) and starting point for the new pipeline to UK Volumes and qualities are taken from the input submitted to Gassco by Shippers in the NCS systems for the annual Gas Transport Infrastructure Development Plan conducted in 2002

Sources to UK
New Pipeline to Easington/Dimlington
WI Ormen Lange CO2 Sleipner Kollsnes CO2 Huldra

Vesterled
WI Oseberg

SLR

HRP

Draupner

Grane

Easington/Dimlington

St Fergus

Wobbe Index - Fields New pipeline to Easington/Dimlington and Vesterled


Wobbe Index
54.00 53.00 52.00
[MJ/Sm]

New Southern Pipeline


NCS Max WI

Vesterled

UK Max WI

51.00 50.00 49.00 NCS Min WI 48.00 UK Min WI 47.00 1 2 3 4 5 6 7 8 9 10 11 12 13 14 WI 15 16 High WI

NCS max WI

UK max WI

NCS min WI

UK min WI

Wobbe Index Commingling results New pipeline to Easington/Dimlington


Expected Wobbe Index development towards Easington/Dimlington via SLR

53.00 52.00

NCS Max WI

UK Max WI
[MJ/Sm3]

51.00 50.00 49.00 NCS Min WI 48.00 UK Min WI 47.00 2006 WI High NCS WI Max Spec 2007 WI low NCS WI Min Spec 2008 2009 2010 WI UK Min Spec WI High-low

WI UK Max Spec WI High-high

CO2 - Fields New pipeline to Easington/Dimlington and Vesterled


CO2
5.00 4.50

New Southern Pipeline

Vesterled

St. Fergus Max CO2


4.00 3.50 3.00

[MJ/Sm]

NCS Max CO2


2.50 2.00 1.50 1.00 0.50 0.00

UK Max CO2

10

11

12

13

14

15

NCS max CO2

UK max CO2

St. Fergus max CO2

CO2

16

CO2 Commingling results New pipeline to Easington/Dimlington


Expected CO2 development towards Easington/Dimlington via SLR

3.0 NCS Max CO2 2.5 2.0


[mol%]

UK Max CO2

1.5 1.0

0.5 0.0 2006 CO2 (WI High) 2007 2008 CO2 (WI low) 2009 UK CO2 Spec 2010 NCS CO2 Spec

GCV - Fields New pipeline to Easington/Dimlington and Vesterled


Gross Calorific Value (GCV)
45.00 44.00 43.00 42.00
[MJ/Sm]

New Southern Pipeline


NCS Max GCV

Vesterled

UK Max GCV

41.00 40.00 39.00 38.00 37.00 36.00


1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

NCS Min GCV

UK Min GCV

NCS max GCV UK min GCV

UK max GCV GCV

NCS min GCV

16

Conclusion The gas that will be transported to UK from the NCS system can in normal operations have the following maximum values:
Easington/Dimlington
Wobbe Index: CO2: 52 MJ/Sm 2.5 mole%

Vesterled
Wobbe Index: CO2: GCV: 51.8 MJ/Sm 3.3 mole% 42.6 MJ/Sm

Commingling required to satisfy the NTS spec.

Further work

Other issues to be handled:


H2S COS Total sulphur O2 Slight discrepancy Not in UK spec. Further clarification required Further clarification required

APPENDIX C POWERPOINT PRESENTATION

UK/Norway Co-operation Implementation Group

Gas & Infrastructure Action Group


SPECIFICATIONS Sub-Group

Unlocking Value Through Closer Relationships


Workgroup Recommendation Nr. 8

Promote the need for improved compatibility of UK, Norwegian and continental gas sales specifications by dialogue between respective Ministries and stakeholders.

Contents
Process Comparison between UK and Norwegian specifications Can the UK specifications be amended? How can we achieve compliance Costs/ranking UK Government position Conclusions/Forward action plan

Process
Participation - Conoco Phillips UK Mike Wade - Shell UK David Elmes - TotalFinaElf UK David Hainsworth - Transco UK Jonathan Maughan Review and Analysis - Comparison of UK and Norwegian Specifications - Highlight the differences - Establish if/how UK specs may be changed - How could NCS gas meet UK specs? - Brief cost/ranking exercise - Look at the bigger picture - Conclusions/Forward actions

Objectives
Evaluate whether the UK gas quality specs may restrict/hider the supply of Norwegian gas to the UK market. Establish the best option to allow significantly extra volumes of Norwegian gas to reach the UK market whilst respecting the prevailing gas quality specifications. Look for an approach that will also be compatible with other supply sources.

Comparison between UK and Norwegian specs


Process GS(M)R
The law Safety Compliance with the Law Other limitations

Transco indicative specs

Issues Transco have some flexibility with specs not included in GS(M)R, subject to Network Analysis

Areas of potential difference between UK and Norwegian specs


Gross calorific value (GCV) CO2 Wobbe Index Incomplete Combustion Factor (ICF) and Soot Index (SI)

Issues Some or all of these topics may or may not be an issue for Norway depending on gas availability

GASSCO Plot of Various Gases which may be exported to the UK against WI


Wobbe Index
54.00 53.00 52.00

New Southern Pipeline


NCS Max WI

Vesterled

UK Max WI

[MJ/Sm]

51.00 50.00 49.00 NCS Min WI 48.00 UK Min WI 47.00 1 2 3 4 5 6 7 8 9 10 11 12 13 14 WI 15 16 High WI

NCS max WI

UK max WI

NCS min WI

UK min WI

Can the UK specs be challenged and amended?


Process Basis of the specifications
British gas research GS(M)R came into force to coincide with de-regulation

Issues UK the only country to use ICF & SI 10 years since last appliance survey New appliances probably OK for a wider spec. range

GASSCO Plot showing Likely Range of WI over Time for Gas Deliveries to Easington
Expected Wobbe Index development towards Easington/Dimlington via SLR

53.00 52.00

NCS Max WI

UK Max WI
[MJ/Sm3]

51.00 50.00 49.00 NCS Min WI 48.00 UK Min WI 47.00 2006 WI High NCS WI Max Spec 2007 WI low NCS WI Min Spec 2008 2009 2010 WI UK Min Spec WI High-low

WI UK Max Spec WI High-high

How could NCS gas achieve/comply with UK specs?


Blending Further processing Nitrogen injection CO2 removal Issues Costs Nitrogen dilution What is the bigger picture?

Global cost estimates/Ranking


Blending, virtually zero cost Further processing, 0.5p/therm Nitrogen injection, 0.25p/therm Challenge the specifications
Small cost, unless you have to change/modify appliances, then potentially large Cost difficult to estimate at this time

Ranking
Process Security of supply Cost Results 1. Specification change best for security of supply 2. Too early to say what overall cost of specification change will be 3. Blending is the lowest cost option but raises issues on Security of Supply

UK Government position.
Process We were aware that there is a bigger picture, Interconnectors, LNG imports Energy White Paper DTI proposed way forward Issues UK the only country to use ICF & SI 10 years since last appliance survey New appliances probably OK for a wider spec. range

Conclusions
Wobbe Index, ICF and SI are the main concern Norwegian gas has the potential for a higher Wobbe than the current UK Spec. There are several methods for tackling the problem There is a bigger picture due to the need for alternative gas import sources DTI, Ofgem have recognised this Difficult to quantify at this time the potential cost of a specification change

Forward action plan


Scope of work established to challenge UK Specs, agree with other stakeholders? Follow-up DTI, Ofgem, HSE initiative Lobby DTI for a meeting of all stakeholders to clarify strategy, timetable, deliverables, etc

APPENDIX D ADVANTICA PRESENTATION

UK Situation Regarding Gas Quality

Presentation to the Marcogaz Gas Quality WG Dave Lander 28th June 2002

Overview

Gas (Calculation of Thermal Energy) Regulations

Calorific Value measurement Customer billing Policed by OfGem

Gas Safety (Management) Regulations

Content and characteristics of gas Network entry Policed by Health and Safety Executive British Gas Corporation

Legacy Agreements inherited by Transco

Gas Safety (Management) Regulations

Duties of Gas Transporter Regulation 8:

(1) No person shall , convey gas in a network unless the


gas conforms with the requirements specified in Part I of Schedule 3. (Emergency gas may comply with Part II of Schedule 3)

Schedule 3: Content and characteristics

Hydrogen sulphide content

</= 5mg/m

Total sulphur content (including H2S)

</=50 mg/m

Hydrogen content

</=0.1 mol% </=0.2 mol%

Oxygen content Impurities

Shall not contain solid or liquid material which may interfere


with the integrity or operation of pipes or any gas appliance which a customer could reasonably be expected to operate

Schedule 3: Content and characteristics

Hydrocarbon dewpoint and water dewpoint

Shall be at such levels that they do not interfere with the


integrity or operation of pipes or any gas appliance which a consumer could reasonably be expected to operate

Wobbe number

</=51.41 MJ/m and >/=47.20 MJ/m </=0.48 </=0.60

Incomplete Combustion Factor Sooting Index

Schedule 3: Content and characteristics

Odorant

The gas shall have been treated with a suitable stenching


agent to ensure that it has a distinctive and characteristic odour which shall remain distinctive and characteristic when the gas is mixed with gas which has not so been treated, except that this paragraph shall not apply where the gas is at a pressure of above 7 barg.

Legacy Agreements

Inherited from British Gas at privatisation Specific to producer/source field Summer relaxation of water and hydrocarbon dewpoint

Hydrocarbon dewpoint could be as high as 10oC, normally


2oC Water dewpoint (crycondentherm) could be as high as 4.4oC

Interconnector has adopted a hydrocarbon dew temperature limit of 2oC


from different sources

Requires gas transporter to use the network to blend gases

UK Specific Gas Quality Parameters

Presentation to the Marcogaz Gas Quality WG Dave Lander 28th June 2002 (Revised 13th February 2003)

Overview

Context British Gas Corporations approach

Method of Dutton

Privatisation

Gas Safety (Management) Regulations Gas Interchangeability Diagram

Context

1970s, 1980s Southern North Sea fields

anticipated decline replaced by other sources (different, more variable) eventually manufactured SNGs Safety - domestic appliances have limited tolerance to
variation in combustion characteristics Commercial reduced gas treatment costs

Drivers for interchangeability method

British Gas Corporations approach

Dutton

Watson House, Research and


Development Division IGE Communication 1246 (1984)

Duttons method

Tailored to natural gases Testing was wide-ranging

Gases expected to be supplemented by SNG Test gases contained hydrogen, carbon monoxide and
alkenes

New Approach

Appliance effects and flame phenomena related to gas


composition Previous approach related to calculated functions (usually related to burning velocity) Consistent with developments in gas analysis

Equivalent Composition

Gas regarded as:

methane other hydrocarbons hydrogen inerts hydrocarbons expressed as an equivalent amount of a


standard hydrocarbon inerts expressed as an equivalent amount of a standard inert

Equivalent composition:

Results expressed as a 3-dimensional diagram

The higher hydrocarbon group

Hydrocarbons other than methane

Equivalent gas is mixture of methane and propane Same ideal volume Same average number of carbon atoms per molecule
2C2H6 2C4H10 = + C3H8 + CH4 = CH4 3C3H8

Equivalence factors - hydrocarbons


Equivalent Gas methane ethane propane butane pentane hexane propene butene CH4 1.0 0.5 -0.5 -1.0 -1.5 -0.5 C3H8 0.5 1.0 1.5 2.0 2.5 1.0 1.5

The inert group

Nitrogen is the standard inert Equivalent nitrogen

that amount which, when mixed with all of the non-inert


components, gives a mixture with the same Wobbe number as the original mixture

The 3-dimensional diagram

Y-axis: Wobbe number X-axis: propane+nitrogen of the equivalent gas (Z-axis: hydrogen content)
90 80 Wobbe number, MJ/m3

Appliance performance plotted as indices experimentally-derived

70 60 50 40 30 20 10

propane/methane nitrogen/methane

0 0 20 40 60 80 100 propane + nitrogen, mol%

Appliance Malfunction

Experimentally determined indices

Real appliances, not test burners

Empirical relationships Choose one value of each index to be limiting Limits: normal, emergency, extreme emergency Indices:

Lift index Incomplete combustion factor Soot index Light back (not studied deferred until hydrogen containing
gases distributed)

Lift index

Test appliance: cooker Assessment of flame detachment from the burner port

Lift number: 0 to 6 0 no visible detachment of flame base and burner 6 complete detachment of 50-100% of the flames

LI is the average lift number for all burners on test bed

LI = 3.25 2.41 tan-1{[0.122+0.0009H2][WN-36.8-0.0119PN+(0.775-0.118PN1/3)H2]}

Incomplete combustion factor

Test appliance: instantaneous water heater Plot CO/CO2 ratio against appliance heat input Average separation between test gas curve and that of reference gas (methane) ICF is number of times the CO/CO2 ratio of the reference gas has to be doubled to give that of the test gas.

ICF = [WN-50.73+0.03PN]/1.56 0.01H2

Soot index

Test appliance: gas fires Primary aeration reduced in stages SI is aeration that gives soot divided by the natural aeration of the burner (previously measured)

SI = 0.896 tan-1(0.0255C3H8-0.0233N2-0.0091H2+0.617)

Building up the diagram


55

propane/methane nitrogen/methane

53

51

49

47

45

43 0 20 40 60 80 100

Building up the diagram


55

53

55

SI = 0.60

51

53

49

51
47

45

49

43 0

47
20 40 60 80 100

45

43 0 20 40 60 80 100

Building up the diagram


55
55

53
53

ICF=0.48
55 53

51
51

49
49

47
47

51

45
45

49
40 60 80
60

43 0 20 43
0

100
80 100

47
20 40

45

43 0 20 40 60 80 100

Building up the diagram


55
55

53
55

Heat Service Limit


55

53

51
53

51

49
51

49

53

47
49

47

45
47

51

45

43 0 20 43
0

40 45
20 43
0

60
40

49

80
60

100
80
40 60

100
80 100

47
20

45

43 0 20 40 60 80 100

Duttons Diagram
55

Normal Limits Emergency Limits Extreme emergency Limits

53

51

49

47

45

43 0 20 40 60 80 100

Interchangeability volume

Privatisation

Separation of main businesses

Gas Trading Gas Transporter

Gas Safety (Management) Regulations 1996

Policed by Health and Safety Executive Schedule 3 Content and other characteristic of gas

Gas Safety (Management) Regs

Adopted the method of Dutton with some simplifications:

Normal ICF, SI and flame lift limits retained Emergency SI limit scrapped. Normal SI line extended to
methane/propane line and down to flame lift limit Emergency and extreme emergency ICF limits scrapped (triangular emergency zone) Emergency flame lift limits replaced by single line at 46.5 MJ/m

GS(M)R interchangeability diagram


55

55

53

53

51

51

49

49

47

47

45

45

43 0 10 20 30 40 50 60

43 0 10 20 30 40 50 60

Dutton

GS(M)R

GS(M)R interchangeability diagram


53.6 (+8%)
55

55

52.1 (+5%)
53

51.2 (1978 survey)

53

51

51

49

49

47

47

45

45

47.3 (-5%)
43 0 10 20 30 40 50 60

43 0 10 20 30 40 50 60

Dutton
44.9 (Portsmouth low WN trial)

GS(M)R

European Activity

Dave Lander 28th June 2002

European WG Structure
European Gas Regulators Forum Madrid Forum Easee-Gas Gas Quality Harmonisation WG Marcogaz Gas Quality WG
Position Paper (Draft)

Gas Transporters Europe

Position Paper

Marcogaz Position Paper

Current limits set nationally

Reflect type, age and condition of local population

Since 1993, European appliances must comply with Gas Appliance Directive (GAD)

Tolerate wider range of gas quality

Future common European specification should reflect the performance of modern GAD-compliant appliances

Co-operative work to establish details of the specification Wobbe alone is not sufficient - flashback & sooting Transitional arrangements to ensure each nations population
can accept gas to the new specification (or when)

European Gases
Gas Safety (Management) Regulations 1996 Natural Gas Interchangeability Diagram
56 UK 54 Wobbe Number (MJ/m3) Dk F 52 I S

50

48

46

44 0 10 20 30 40 50 60

% non-CH4 component (equivalent C3H8 + N2)

European Gases
Delbourg Gas Interchangeability Diagram

15000 Adjusted Wobbe Number (kcal/m3)

14000

13000

Gas Safety (Management) Regulations 1996 Natural Gas Interchangeability Diagram


56 UK 54 Dk F Wobbe Number (MJ/m3) 52 I S

12000 UK Dk 10000 F I S 9000 25 35 45 55 65 75 85 95

11000

50

48

46

44 0 10 20 30 40 50 60

Combustion potential

% non-CH4 component (equivalent C3H8 + N2)

UK Transition

Drivers

Security of supply Capacity of the UK network (in energy terms) European Commission desire for removal of barriers Appliance improvement
Reduction of CO-related incidents ? Energy efficiency Reduced emissions

Timescale

2003 development of robust case to present to HSE 2004 regulatory change

APPENDIX E ADVANTICA PROPOSAL, IMPACT OF UK INTERCHANGEABILITY METHODOLOGY ON FUTURE NATURAL GAS SUPPLIES

Impact of UK Interchangeability Methodology on Future Natural Gas Supplies


Natural gases in use throughout Europe show a relatively wide variation in gas quality and many do not comply with the more-restrictive GS(M)R requirements of the UK. In the long term this will lead to difficulties in pipeline supply from mainland Europe. In the short term it may also cause difficulties for LNG importation projects currently being planned. Background Natural gas entering UK natural gas networks currently has to meet the minimum gas quality requirements set out in Schedule 3 of the Gas Safety (Management) Regulations 1996 (or GS(M)R). One of the key requirements set out in this schedule refers to the interchangeability of natural gases. Gases that are deemed to be interchangeable can be freely used, commingled, or blended with other natural gases within a network without risk of unsafe combustion. The current methodology within GS(M)R for defining interchangeability is based on the method employed by the then British Gas Corporation and developed by Dutton in the 1970s and 1980s. The method considers, for a particular natural gas, its Wobbe number (WN) and three characteristics defined by Dutton and calculated from its composition: Incomplete Combustion Factor (ICF), Sooting Index (SI) and Flame Lift Index (LI). These values are then compared with limiting values established by Dutton. The normal and emergency limit values for WN, ICF, SI (and emergency value of LI) were based on tests performed on domestic appliances representative of the population of the 1970s and a survey of gas appliances carried out in 1978. The limit value for LI was subsequently replaced with a single lower WN value for emergency operation. It must be stressed that all European appliances sold since 1993 are required to comply with the 1990 Gas Appliance Directive 90/396/CEE (GAD), and would be able to tolerate a much wider range in gas quality. The current UK limits are dictated by a relatively small fraction of older appliances. Regulatory Changes Regulatory changes will therefore be required for continued supplies of natural gas to the UK and it will be necessary to develop a robust case for such changes. UK appliance surveys were carried out in 1978 and 1990. The results of the earlier survey led to the upper WN limiting value and those of the later survey failed to justify raising the upper WN limit, despite a 12-year interval for turnover of the older at-risk appliances (felt to be largely those converted from towns gas use). A robust case for regulatory change is therefore likely to require compilation of information on the current UK domestic appliance population and possibly development of schemes to drive out any at-risk appliances remaining since 1990. Methods for compilation of such data might include: A further UK appliance survey. Development of schemes designed to acquire appliance information as part of other visits to domestic premises, such as those made by Transco emergency personnel, meter readers, CORGI service engineers. Customer returns, using a return form issued along with energy bills.

This will in turn require co-operation across UK Government departments and gas industry stakeholders to a degree not seen in recent times. Commercial Factors Removal or mitigation of commercial risk and financial impact of such changes to all stakeholders is an additional key issue. Widening of difference between highest and lowest WN natural gases may increase the frequency of calorific value cap applied under the Flow-Weighted Average CV billing regime, which would directly reduce transportation revenue

to Transco. Increase in WN of transported gas could make the increase pipeline capacity in energy terms, however. Secondary effects would also need to be considered, such as the changes in density accompanying shift to higher WN gases and subsequent impact on compression costs. LNG importation projects are at an advanced stage of planning (importation starting 2005/6, bids for capacity are being sought now). Such LNG is likely to be outside of current GS(M)R requirements, having too high a Wobbe number. Nitrogen injection is currently being planned to reduce the Wobbe number, which will increase capital and operating costs. Capital expenditure is probably not avoidable through regulatory change, but savings in future operating costs could be made. Some industries (eg glassmaking) are particularly sensitive to changes in natural gas quality. Any widening of the range in Wobbe number of gas delivered to these industries could lead to larger swings in Wobbe number and calorific value and affect quality or quantity of the process output. Mitigation strategies (eg improved process control) may need to be communicated to and adopted by such industries. National and European Activity The UK is not alone in having national Wobbe limits that are more restrictive than modern appliances complying with GAD and similar (although less extreme) difficulties will need to be addressed. There are a number of European Working Groups addressing the broader inter-operability issues raised by the European Commissions desire to remove technical and commercial barriers to natural gas trade across national borders. The Marcogaz working group on Gas Quality is currently addressing interchangeability and other gas quality issues. The working group is likely to propose in the long-term movement towards unified national limits based on GAD-compliant appliances and suggesting a generic strategy or route map for national gas industries to follow in order make the transition. Timescales for the transition will be country-specific, because their situations are unique. Continued representation at European working groups is important in order to ensure that realistic and attainable strategies emerge with no disadvantage to the UK. Government and Regulators participate at European level through the European Gas Regulatory (Madrid) Forum and are aware of the output from the working groups. Acceptance by the European Commission may strengthen the case for governmental support for UK regulatory change. The UK DTI has recently issued its Energy White Paper that contains an acknowledgement of gas quality issues. It is understood that DTI, HSE and Ofgem are in informal discussion already. A suggested way forward Further discussions between stakeholders are clearly required and a UK forum is being proposed to consider a programme of work that will address changes in regulatory framework. The main issues to be addressed will be: Changes that are required and the type and volume of evidence required to support such changes. Appliance population information and prospects for population management initiatives if felt to be necessary. Mechanisms for funding any change.

Most stakeholders and suitable representatives have been identified within the industry and a forum is to be arranged. A phased programme of work addressing UK gas quality is suggested and this is summarised below. Further details for Phases 1 and 2 are given Appendix E-1. Phase 1 Assessment and quantification (Indicative cost 27,000 and 6 weeks to complete) Assessment of what can be done in the short term at lowest cost. This would include: technical re-assessment of the Dutton approach, as incorporated in the GS(M)R; study of recent incident statistics and any other available information; study to assess the scale of appliance survey that would be required to give statistically significant results. Output from this phase would be a report detailing scope for changes to the current limits, the scale, cost and timescales for a UK appliance survey.

Phase 2 UK Appliance Survey (Indicative cost 619,000 and 9 months to complete, based on a survey of 5,000 Appliances) Execution of a UK Appliance survey to establish: CO/CO2 ratio of all appliances, as found; valid appliance population data; appliance types, models and ages most susceptible incomplete combustion and whether sooting is a factor; appliances to select for withdrawal for laboratory tests. Laboratory tests on high Wobbe number gases on ex-district appliances and on new appliances (as control). Data analysis, liaison with HSE and presentation of conclusions and recommendations to UK forum and HSE. Output from this phase would be a report and database detailing: the effects of any proposed changes to the interchangeability diagram, particularly on older appliances operating at the high Wobbe limit; options showing the trade off in Wobbe limits against likely number of appliances thought to be at risk to ensure safety levels are not compromised and recommendations for Phase 3 (population management options). Phase 3 UK appliance population management (Cost and timescale output from Phase 2) Based on the output from Phase 2, targeted withdrawal of appliances to achieve an agreed revised UK interchangeability specification without compromise of safety levels. Liaison and assistance with changes in GS(M)R. Depending on the results and conclusions of the UK appliance survey in Phase 2, the revised UK specification should be consistent with that suggested for a Common European Gas Specification (based on post 1993, GAD-compliant appliances, see below). However, if the numbers of at-risk appliances is excessive, an intermediate stage of appliance withdrawal may be necessary (at a correspondingly reduced Wobbe number range) or desirable. The merits of single- or multiple- staged withdrawal will be assessed during Phase 2. Output from this phase will be a UK appliance population able to cope with a wider range of gas quality and revised GS(M)R that recognise the new appliance population. Ideally the new GS(M)R would be consistent with the future Common European Gas Specification. Phase 4 Common European Gas Specification In parallel with Phases 1-3 European activity will need to develop and agree a Common European Gas Specification. The current view is that such a specification would be based on the performance of post 1993, GAD-compliant appliances. However such a specification could not be written today. Agreement has not been agreed for the interchangeability parameters (one might hope that the UK approach could form the basis of the new specification, but the rest of Europe has no experience of it and some demonstration of its validity is probably required). In addition tests on modern GAD-compliant appliances will need to be conducted to establish limits in the interchangeability parameters agreed. This activity could be a collaborative programme co-ordinated through GERG (Groupe Europen de Recherche Gazeuse) and the European Framework Programme.

Appendix E-1 - Scope of work for Interchangeability Joint Industry Project Introduction Short term work during 2003/2004 would be directed at examining the upper Wobbe Number limit as set in the Gas Safety & Management Regulations (following Dutton) by the incomplete combustion factor (ICF), irrespective of possible sooting effects of some high CV non-methane gases on some appliances. A previous exercise performed in 1998 concluded that there would be an increase in risk of an incident of 26.5% per MJ/m increase in Wobbe Number. This was based on 1998 (and older) appliance data, 1990-95 incident statistics and the calculation method used in 1978 and 1991 analyses of national combustion surveys. Another rule of thumb from previous work has been that CO/CO2 ratio doubles for every + 1.5MJ/m increase in Wobbe. These figures could be re-assessed in the light of the new appliance population and the latest incident statistics. The following bullet points indicate a scope of work for both a technical re-assessment of the original Dutton Diagram for Interchangeability (aimed primarily at examining the incomplete combustion limit) and a survey of appliances to identify the volume of at risk appliances and to validate assumptions made on the tolerance of older appliances to higher Wobbe limits. The following activities should be included: Stage 1: Interchangeability Diagram: Gather the basic assumptions made in the Dutton Diagram. (3m.days) Validate the assumptions against latest data on appliance population and types. (5 m.days) Reassessment of the Dutton model (particularly in respect of incomplete combustion). (8 m.days) Test any proposed modifications to the Interchangeability limits with UK industry and European utilities. (4 m.days) Study of recent incident statistics, to identify appliance types and models. (3 m.days) Plan survey scale to give statistically significant results. (5 m.days)

Stage 1 output would be a report detailing the proposed changes to the Interchangeability Diagram, particularly to incorporate higher Wobbe limits. Stage 2: Appliance Survey: Planning and executing an X,000 appliance survey to find out: o CO/CO2 ratio of all X,000 appliances, as found o Valid appliance population data o Appliance types, models and ages most susceptible to incomplete combustion, and whether soot build-up is a factor o Appliances to select for withdrawal for laboratory tests (service engineers assumed at 2 appliances per household and 3 households per day + technical support at 10 m.days per 1000 appliances) Laboratory tests on high Wobbe Number gases on ex-district appliances, ongoing throughout the survey (Assume 10 appliances at 5 m.days per appliance) Laboratory tests on new appliances as control (Assume 10 appliances at 5 m.days per appliance) Data analysis and reporting (15 m.days)

Stage 2 output would be a report and database detailing the effects of the proposed changes to the Interchangeability Diagram, particularly on older appliances operating at the high Wobbe limit. Options would be given regarding the recommended Wobbe limits against the volume of at risk appliances to ensure safety levels are not compromised. Costs Stage 1 Technical Effort Consumables/Admin Travel/Subs Stage 1 cost Stage 2 20 m.days 24,752 600

1,500 26,852

Assume a 5,000 appliances (2,500 household scale survey): Service Engineer Effort Technical Effort Consumables/Admin Travel/Subs Stage 2 cost ESTIMATED 833m.days 173m.days 466,667 145,860 5,000 1,500

619,027

TOTAL COST 645,879

Timescales Stage 1 Stage 2 Completed over a 6-week period. With 10 service engineers and 2 technical support completed over a 9-month period.