DATA SHEET HIGH VOLTAGE SQUIRREL CAGE INDUCTION MOTOR PURCHASER'S DATA

A. Site conditions 1 Ambient temperature, minimum: maximum: design: 1 46.1 45 85 C C C % 3 4 5 6 17 18 19 20 21 22 Atmospheric condition: Altitude: Location:

Datasheet No. 6922-520-XZ-DS-6018 Rev.No. A Page 1 of 1

Humid & highly corrosive < 1000 m

2 B. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Relative humidity: Technical particulars Motor tag no.: Driven equipment name: Voltage: Phase: Frequency: Fault level: Fault duration: System earthing: Duty: Method of starting: Cable size: Cable type: Temperature rise: Cooling: Insulation class:

10% Three 50 Hz 3% 40 kA 0.25 sec. Resistance 24 Continuous 25 DOL 26 mm 27 Cu/ Al cond. XLPE insulated 28 C
6.6. kV

Hazardous area classification: Gas group: Type of explosion protection: Type of ingress protection:

IP 55

Reacceleration:
Diff. protection CTs: CT specs.: Color shade: Thermisters: RTD: BTD: RTD/BTD monitoring device:

632 as per IS 5 As per spec As per spec As per spec Required/ Not required

F with temp rise limited to B

Make: EIL spec. 6-51-0031 29 Applicable specification: 30

DRIVEN EQUIPMENT MANUFACTURER's DATA


1 2 3 4 5 6 7 8 Suggested motor rating: Manufacturer: Type of driver mounting: Driven equipment: Shaft kW: kW at maximum load: Speed: Rotation of eqpt. from coupling end: kW 9 Coupling type: 10 Torque required, starting: 11 maximum: including flywheel: 12 GD2 of eqpt., excluding flywheel: 13 Maximum thrust: 14 Pulsation rate: 15 Starting condition: mkg mkg kgm2 kgm2 kg

kW kW RPM

MOTOR MANUFACTURER's DATA


1 2 3 4 5 6 7 8 9 10 11 12 13 14 Rating: Manufacturer: Frame designation: No. of poles: Full load speed: Mounting: Full load torque (FLT): Starting torque: Break down or pull out torque: Full load current (FLC): Starting current at 100% voltage: Rotation viewed from coupling end: Starting time at 80%/100% voltage: Locked rotor withstand time (cold/hot) at, 80% voltage: 100% voltage: 15 Efficiency at 75%/100% voltage: 16 Power factor at 75%/100% load: 17 18 19 20 RPM 21 22 mkg 23 % of FLT 24 % of FLT A 25 % of FLC 26 sec. 27 sec. 28 sec. 29 % 30 kW Space heater - voltage & power: Moment of inertia, GD2: kgm2

DE/NDE bearing type & no.:


Type of lubrication:

Type of main terminal box: Type of neutral terminal box:


Weight of motor: Thermisters, make: RTD, make: BTD, make: Shaft voltage:

quantity:
type:

kg no. no. no. V RPM


Not applicable

quantity:
type:

quantity:
type:

1. Recommended list of maintenance spares for two years operation shall include the follwing as minimum: a) Bearing DE/NDE one set b) Terminal box cover with screws c) Fan d) Terminal block 2. Starting time calculations shall be based on operating conditions specified in Material Requisition eg. open valve condition/closed valve condition, at no load/under load, as applicable.

Critical speed, 1st/2nd stage: Pressurization panel: Applicable Canopy for outdoor motors: Required

Not required

3. All unfilled data shall be filled by contractor/ vendor.

A Rev.

26.05.2008 Date

ISSUED FOR BIDS Purpose

MHR Prepared

PB Checked

PB Approved

Format No. EIL-1650-687H Rev.3

Copyrights EIL - All rights reserved