TradesandApprenticeshipDivision WorkplacePartnershipsDirectorate NationalOccupationalClassification: Disponibleenfranaissousletitre:
Youcanorderthispublicationbycontacting: PublicationsServices HumanResourcesandSkillsDevelopmentCanada 140PromenadeduPortage PhaseIV,5thFloor Gatineau,QuebecK1A0J9 Online:www.redseal.ca Thisdocumentisavailableondemandinalternativeformats(LargePrint,Braille,Audio Cassette,AudioCD,eTextDiskette,eTextCD,orDAISY),bycontacting1800OCanada (18006226232).Ifyouhaveahearingorspeechimpairmentanduseateletypewriter(TTY), call18009269105. HerMajestytheQueeninRightofCanada,2011 Paper Cat.No.:HS421/202011E ISBN:9781100179704 PDF Cat.No.:HS421/202011EPDF ISBN:9781100179711
FOREWORD
TheCanadianCouncilofDirectorsofApprenticeship(CCDA)recognizesthisNational OccupationalAnalysisasthenationalstandardfortheoccupationofIndustrialElectrician. Background ThefirstNationalConferenceonApprenticeshipinTradesandIndustries,heldinOttawain 1952,recommendedthatthefederalgovernmentberequestedtocooperatewithprovincialand territorialapprenticeshipcommitteesandofficialsinpreparinganalysesofanumberofskilled occupations.Tothisend,HumanResourcesandSkillsDevelopmentCanada(HRSDC)sponsors aprogram,undertheguidanceoftheCCDA,todevelopaseriesofNationalOccupational Analyses(NOAs). TheNOAshavethefollowingobjectives: todescribeandgroupthetasksperformedbyskilledworkers; toidentifywhichtasksareperformedineveryprovinceandterritory; todevelopinstrumentsforuseinthepreparationofInterprovincialRedSeal Examinationsandcurriculafortrainingleadingtothecertificationofskilledworkers; tofacilitatethemobilityofapprenticesandskilledworkersinCanada;and, tosupplyemployers,employees,associations,industries,traininginstitutionsand governmentswithanalysesofoccupations.
ACKNOWLEDGEMENTS
TheCCDAandHRSDCwishtoexpresssincereappreciationforthecontributionofthemany tradespersons,industrialestablishments,professionalassociations,labourorganizations, provincialandterritorialgovernmentdepartmentsandagencies,andallotherswhocontributed tothispublication. SpecialacknowledgementisextendedbyHRSDCandtheCCDAtothefollowing representativesfromthetrade. DonBemko Ontario MathewCollins PrinceEdwardIsland LeoDoran InternationalBrotherhoodof ElectricalWorkers(IBEW) SalGagliano InternationalBrotherhoodof ElectricalWorkers(IBEW) PeterKing NewfoundlandandLabrador PaulAndrLebrun Quebec GregMcFarlane Manitoba MichelleMcInnis NovaScotia StevenRoy NewBrunswick AlanC.Stewart BritishColumbia ThisanalysiswaspreparedbytheWorkplacePartnershipsDirectorateofHRSDC.The coordinating,facilitatingandprocessingofthisanalysiswereundertakenbyemployeesofthe NOAdevelopmentteamoftheTradesandApprenticeshipDivision.LoreenBarbourforthe hostjurisdictionofOntarioalsoparticipatedinthedevelopmentofthisNOA.
II
TABLE OF CONTENTS
FOREWORD ACKNOWLEDGEMENTS TABLEOFCONTENTS LISTOFPUBLISHEDNATIONALOCCUPATIONALANALYSES STRUCTUREOFANALYSIS DEVELOPMENTANDVALIDATIONOFANALYSIS I II III VI VIII X
ANALYSIS SAFETY SCOPEOFTHEINDUSTRIALELECTRICIANTRADE OCCUPATIONALOBSERVATIONS ESSENTIALSKILLSSUMMARY BLOCKA BLOCKB COMMONOCCUPATIONALSKILLS Task1 Task2 Task3 Task4 Performssafetyrelatedfunctions. Usesandmaintainstoolsandequipment. Organizeswork. Performsroutinetradeactivities. 10 13 16 20 3 4 6 7
Task6
27
Task7 Task8
30 33
III
BLOCKC
Task9 Task10
Maintainsgroundingandbondingsystems. Maintainspowergeneratingsystems.
36 38
ELECTRICALEQUIPMENT Task11 Maintainsequipment,wiring,cablingand terminations. Maintainslightingsystems. Maintainsprotectiondevices. Maintainsrotatingequipmentandassociated controls. Maintainsdrivesandassociatedcontrols. Maintainsnonrotatingequipmentandassociated controls. 43
46 49 51
Task15 Task16
54 57
BLOCKD
BLOCKE
Task18
64
BLOCKF
Task22
77
IV
BLOCKG
Task26 Task27
94 97
APPENDICES
TITLE AgriculturalEquipmentTechnician(2007) ApplianceServiceTechnician(2011) AutomotivePainter(2009) AutomotiveServiceTechnician(2009) Baker(2006) Boilermaker(2008) Bricklayer(2007) Cabinetmaker(2007) Carpenter(2010) ConcreteFinisher(2006) ConstructionCraftWorker(2009) ConstructionElectrician(2008) Cook(2008) ElectricalRewindMechanic(1999) ElectronicsTechnicianConsumerProducts(1997) FloorcoveringInstaller(2005) Glazier(2008) Hairstylist(2009) HeavyDutyEquipmentTechnician(2009) IndustrialElectrician(2011) IndustrialMechanic(Millwright)(2009) InstrumentationandControlTechnician(2010) Insulator(HeatandFrost)(2007) Ironworker(Generalist)(2010) Ironworker(Reinforcing)(2010) Ironworker(Structural/Ornamental)(2010) LandscapeHorticulturist(2010)
NationalOccupationalClassification VI
TITLE Lather(InteriorSystemsMechanic)(2007) Machinist(2010) MetalFabricator(Fitter)(2008) MobileCraneOperator(2009) MotorcycleMechanic(2006) MotorVehicleBodyRepairer(MetalandPaint)(2010) OilHeatSystemsTechnician(2006) PainterandDecorator(2007) Partsperson(2010) Plumber(2010) PowerlineTechnician(2009) RecreationVehicleServiceTechnician(2006) RefrigerationandAirConditioningMechanic(2009) RigTechnician(2008) Roofer(2006) SheetMetalWorker(2010) SprinklerSystemInstaller(2009) Steamfitter/Pipefitter(2010) Tilesetter(2010) ToolandDieMaker(2010) TransportTrailerTechnician(2008) TruckandTransportMechanic(2010)
NOC Code 7284 7231 7263 7371 7334 7322 7331 7294 1472 7251 7244 7383 7313 8232 7291 7261 7252 7252 7283 7232 7321 7321
Welder(2009) 7265 RequestsforprintedcopiesofNationalOccupationalAnalysesmaybeforwardedto: TradesandApprenticeshipDivision WorkplacePartnershipDirectorate HumanResourcesandSkillsDevelopmentCanada 140PromenadeduPortage,PhaseIV,5thFloor Gatineau,QuebecK1A0J9 Thesepublicationscanbeorderedordownloadedonlineat:www.redseal.ca.Linksto EssentialSkillsProfilesforsomeofthesetradesarealsoavailableonthiswebsite.
VII
STRUCTURE OF ANALYSIS
Tofacilitateunderstandingoftheoccupation,theworkperformedbytradespersonsisdivided intothefollowingcategories: Blocks largestdivisionwithintheanalysisthatiscomprisedofadistinct setoftradeactivities distinctactionsthatdescribetheactivitieswithinablock distinctactionsthatdescribetheactivitieswithinatask activitiesthatapersonshouldbeabletodoinordertobecalled competentinthetrade
Theanalysisalsoprovidesthefollowinginformation: Trends changesidentifiedthatimpactorwillimpactthetradeincluding workpractices,technologicaladvances,andnewmaterialsand equipment listofproducts,items,materialsandotherelementsrelevantto theblock categoriesoftoolsandequipmentusedtoperformalltasksinthe block;thesetoolsandequipmentarelistedinAppendixA informationtoclarifytheintentandmeaningoftasks elementsofknowledgethatanindividualmustacquireto adequatelyperformatask
RelatedComponents
ToolsandEquipment
Context RequiredKnowledge
VIII
Theappendiceslocatedattheendoftheanalysisaredescribedasfollows: AppendixA ToolsandEquipment AppendixB Glossary AppendixC Acronyms AppendixD BlockandTask Weighting nonexhaustivelistoftoolsandequipmentusedinthistrade
IX
Development of Analysis Adraftanalysisisdevelopedbyacommitteeofindustryexpertsinthefieldledbyateamof facilitatorsfromHRSDC.Thisdraftanalysisbreaksdownallthetasksperformedinthe occupationanddescribestheknowledgeandabilitiesrequiredforatradespersonto demonstratecompetenceinthetrade. Draft Review TheNOAdevelopmentteamthenforwardsacopyoftheanalysisanditstranslationto provincialandterritorialauthoritiesforareviewofitscontentandstructure.Their recommendationsareassessedandincorporatedintotheanalysis. Validation and Weighting Theanalysisissenttoallprovincesandterritoriesforvalidationandweighting.Participating jurisdictionsconsultwithindustrytovalidateandweightthedocument,examiningtheblocks, tasksandsubtasksoftheanalysisasfollows: BLOCKS Eachjurisdictionassignsapercentageofquestionstoeachblockforan examinationthatwouldcovertheentiretrade. Eachjurisdictionassignsapercentageofexamquestionstoeachtaskwithina block.
TASKS
SUBTASKS Eachjurisdictionindicates,withaYESoraNO,whetherornoteachsubtask isperformedbyskilledworkerswithintheoccupationinitsjurisdiction. TheresultsofthisexercisearesubmittedtotheNOAdevelopmentteamwhothenanalyzesthe dataandincorporatesitintothedocument.TheNOAprovidestheindividualjurisdictional validationresultsaswellasthenationalaveragesofallresponses.Thenationalaveragesfor blockandtaskweightingguidetheInterprovincialRedSealExaminationplanforthetrade. ThismethodforthevalidationoftheNOAalsoidentifiescommoncoresubtasksacross Canadafortheoccupation.Ifatleast70%oftherespondingjurisdictionsperformasubtask,it shallbeconsideredcommoncore.InterprovincialRedSealExaminationsarebasedonthe commoncoresubtasksidentifiedthroughthisvalidationprocess.
Definitions for Validation and Weighting YES subtaskperformedbyqualifiedworkersintheoccupationinaspecific jurisdiction NO NV ND NOT COMMON CORE(NCC) NATIONAL AVERAGE% subtasknotperformedbyqualifiedworkersintheoccupationina specificjurisdiction analysisNotValidatedbyaprovince/territory tradeNotDesignatedinaprovince/territory subtask,taskorblockperformedbylessthan70%ofresponding jurisdictions;thesewillnotbetestedbytheInterprovincialRedSeal Examinationforthetrade averagepercentageofquestionsassignedtoeachblockandtaskin InterprovincialRedSealExaminationforthetrade
Provincial/Territorial Abbreviations NL NewfoundlandandLabrador NS NovaScotia PE PrinceEdwardIsland NB NewBrunswick QC Quebec ON Ontario MB Manitoba SK Saskatchewan AB Alberta BC BritishColumbia NT NorthwestTerritories YT YukonTerritory NU Nunavut
XI
ANALYSIS
SAFETY
Safeworkingproceduresandconditions,accidentprevention,andthepreservationofhealth areofprimaryimportancetoindustryinCanada.Theseresponsibilitiesaresharedandrequire thejointeffortsofgovernment,employersandemployees.Itisimperativethatallpartiesare awareofcircumstancesandconditionsthatmayleadtoinjuryorharm.Safelearning experiencesandworkenvironmentscanbecreatedbycontrollingthevariablesandbehaviours thatmaycontributetoaccidentsorinjury. Itisgenerallyrecognizedthatsafetyconsciousattitudesandworkpracticescontributetoa healthy,safeandaccidentfreeworkenvironment. ItisimperativetoapplyandbefamiliarwiththeOccupationalHealthandSafety(OH&S)Acts andWorkplaceHazardousMaterialsInformationSystem(WHMIS)regulations.Aswell,itis essentialtodetermineworkplacehazardsandtakemeasurestoprotectoneself,coworkers,the publicandtheenvironment. Safetyeducationisanintegralpartoftraininginalljurisdictions.Assafetyisanimperativepart ofalltrades,itisassumedandthereforeitisnotincludedasaqualifierofanyactivities. However,thetechnicalsafetytasksandsubtasksspecifictothetradeareincludedin thisanalysis.
Electrician(Non Construction)
Industrial Electrician Industrialelectriciansinstall,maintain,test,troubleshoot,serviceandrepairindustrialelectrical equipmentandassociatedelectricalcontrols.Theseincludeequipmentorcomponentsdirectly orindirectlyexposedtoelectricalpowersuchasmotors,generators,pumpsandlighting systems.Industrialelectriciansareemployedbyelectricalcontractorsandmaintenance departmentsoffactories,plants,mines,fabricationfacilitiesandgovernment,andother industrialestablishments. Industrialelectriciansmustreadandinterpretprints,drawingsandcodespecificationsfor layoutandinstallationofelectricalequipment.Theyinstall,serviceandmaintainelectrical componentssuchaslightingfixtures,switches,conduitandelectricalcontrols.Theytest electricalsystemsandcontinuityofcircuitsusingtestequipmenttoensuresystemsafetyand compatibility.Theyconductpreventativeandpredictivemaintenanceprogramsandkeep maintenancerecords.Someindustrialelectriciansspecializeinmaintenancefunctionsinareas suchashighvoltageandprocesscontrols. Industrialelectriciansmustpossessmanualdexterity,andgoodplanning,organizationaland communicationskills.Theyalsorequirestronganalytical,mathematicalandproblemsolving skillsinordertoreadandinterpretschematics,drawingsandspecifications.Theyshouldhave goodmechanicalaptitudetoinstall,troubleshootandrepairequipment.Theymustalsohave goodvisionandhearing,theabilitytodistinguishcoloursandawillingnesstokeepupwith newdevelopmentsinthetrade. Theworkenvironmentofindustrialelectricianscanexposethemtohazards.Theirworkis performedindoorsoroutdoorsinextremeclimateconditions,andmaybeatvariableheightsor inconfinedspaces.Otheroccupationalrisksincludeelectricalshocks,arcflashes,falls,and injuryfromliftingandkneeling.
OCCUPATIONAL OBSERVATIONS
Technologicaladvancementshavealteredthewayindustrialelectriciansperformtheirworkon adailybasis.Computersareincreasinglybeingusedforresearch,communication, programming,ordering,recordkeepinganddiagnostics.Testingequipmentisbecomingmore preciseanduserfriendlyallowingfortroubleshootingtobelesstimeconsuming. Inthemaintenanceofindustrialelectricalequipmentandsystems,inspectionisevolvingintoa morecriticalareaoffocus.Infact,inspectionisgainingmoreimportanceinassuringthehealth andsafetyofemployeesandthecontinuedsmoothandsafeoperationofmachinery andcomponents. Thecombinationofvariousfactorsinthepresenceofafaultmaycauseanarcflash,anextreme explosion,whichcouldresultinseriousinjuryordeath.Injuriescausedbyarcflashhaveledto heightenedsafetymeasures.Newpractices,procedures,safetyequipmentandjurisdictional regulationshavebeencreatedandimplementedinordertoaddresstheissue. Predictiveandpreventativemaintenanceprograms,usingcomputerizedmaintenance managementsystems(CMMSs),arebecomingmoreprevalentintheworkplace.Thesesystems haveenhancedefficiencyandorganizationofthetasksrequiredformaintenanceofelectrical systems.Theyalsocentralizeotherfunctionssuchastrends,componentordering,project control,history,costing,workhoursandtoolcribs. Programmablelogiccontrollers(PLCs)anddistributedcontrolsystems(DCSs)facilitatethe monitoringandcontrolofindustrialprocessesandbuildingcontrols.Thisequipmenthas becomemoreuserfriendlyandaffordable.Smallerunitsarereadilyavailableforavariety ofapplications. Digitaltechnologyhasfacilitatedtheuseofnewcomponents,makingthetrackingofenergy usagemorereliableandefficient.Itissimplertoreplacemanyoftheoldpartsanddevicesnow thattheyaresmallerandavailableindigitalformat. Inmanysectorsofindustry,robotictechnologyisbeingutilized.Therefore,someindustrial electriciansarenowrequiredtodevelopspecializedskillstokeepabreastofthis newtechnology. Theworkloadforindustrialelectricianshasincreasedinprocesscontrol,environmentalcontrol andbuildingcontrolsystems.Thereisnowanincreasedemphasisonaccountabilityforsafety intheworkplace.
Writing Industrialelectriciansusewritingskillstorecordcommentsornotesinlogbooksorwork records.Theywritemessagestocolleaguesormanagementtogiveworkdetailsorreplyto requestsfortechnicalinformation.Theyalsowritelongerservicereportstodescribeproblems andtheirsolutions. OralCommunication Industrialelectriciansuseoralcommunicationskillstocoordinateworkwithproductioncrews andequipmentoperators.Clearcommunicationoftechnicalandcomplexinformationisvery importanttoavoidinjuriesandpromoteefficiency.Industrialelectriciansalsouse communicationskillsworkingwithcoworkersandsupervisors,andmentoringapprenticesin thetrade.Goodlisteningskillsarealsorequiredofindustrialelectriciansforcomprehension andunderstandingsuchastheabilitytorepeatbackclearlywhathasbeenstatedorlearned. Numeracy Industrialelectriciansusearangeofcomplexmathskillsintheirdaytodaywork.These includescheduling,measurement,conversionsandcalculations.Theyuseelectricaltheoryby applyingformulasfromelectricalcodestodetermineequipmentandwiringspecificationsand toanalyzemeasurements. ThinkingSkills Industrialelectriciansrequirestronganalyticalskillstotroubleshootanddiagnosemalfunctions inequipment.Theyuselogicandmemorytodeterminethefaults.Theymustuse decisionmakingskillstoperformworkplanningandprioritizing.Decisionsaboutwhento performshutdownshaveimportantimplicationsonsafetyintheirworkplace. Industrialelectriciansorganizethemosteffectiveuseoftheirtimewithintheframeworkof assignedtasks.Routinetasksaregenerallyassignedbysupervisorsordictatedbyaprocedure establishedbytheemployer.Muchoftheirotherworkisinresponsetobrokenor malfunctioningequipment.Theyoftenhavetoreprioritizetasksseveraltimesaday.Industrial electricianscoordinatetheirworkwithothertradesandproductionstaff,allofwhomhave differentneedsandpriorities. WorkingwithOthers Industrialelectriciansworkaspartofateamthatincludesothertradespeopleandprofessionals toinstall,repairandmaintainindustrialelectricalsystemsandequipment.Theymostoften workindependently,coordinatingtheirworkwiththeworkofothers,butforlargejobsthey workwithapartnerorcrew. ComputerUse Computerskillsareincreasinglyimportantforindustrialelectricians.Theyusegeneral applicationssuchasemails,Internet,wordprocessing,databasesandoriginalequipment manufacturer(OEM)softwaretocommunicate,performresearchandorganizetheirwork. Moretradespecificapplicationsincludecomputerassisteddesign(CAD)andcomputeraided manufacturing(CAM)softwareandlogiccontrollers. 8
BLOCK A
Trends
Task1
Context
Performssafetyrelatedfunctions.
Safetyisextremelyimportantintheworkofindustrialelectricians.Whileall tasksinthisanalysismustbeperformedsafely,thistaskdescribesactivities thatareperformedspecificallytopromoteasafeworkplace.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 OH&Sregulations WHMISsymbolsandMSDS workersrightsandresponsibilities companyandsitesafetypoliciesandprocedures sitespecificfiresafetyandworkpermitprocedures emergencyproceduressuchasforevacuation,fireandhazardouschemical alarms locationofonsitefirstaidstationsandequipment typesofPPEsuchashardhats,safetyglasses,safetyfootwear,insulating gloves,arcflashequipment,andfallarrestandrespiratoryprotection equipment CanadianStandardsAssociation(CSA)approvedequipment typesofsafetyequipmentsuchasfirstaidkits,fireextinguishersandeye washstations certificationandtrainingrequirementsforPPEandsafetyequipment 10
K9 K10 K11
jurisdictionalcertificationandtrainingrequirements typesandoperationoffireextinguishingequipment locationofPPEandsafetyequipment shelflifeofPPEandsafetyequipment confinedspaceprocedures TDGregulations lockoutandtaggingprocedures AtomicEnergyControlBoard(AECB)regulations Codessuchasbuildingcodes,theCanadianElectricalCode(CEC)and jurisdictionalcodes
Subtask A1.01
NL yes NS yes
Maintainssafeworkenvironment.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A1.01.01 A1.01.02 A1.01.03 A1.01.04 A1.01.05 A1.01.06 A1.01.07 A1.01.08 A1.01.09 A1.01.10 A1.01.11 performhousekeepingpractices identify,reportandcorrectpotentialandexistinghazardssuchasarcflash testradiationsourcesusingmeasurementinstrumentssuchas Geigercounters testforgassessuchashydrogensulfide(H2S)andsulfurdioxide(SO2) accordingtositepolicyandlocalregulations calibrategasmonitorsaccordingtosafetyregulations informsurroundingcoworkersconcerningsafetyandwellbeing safelystorematerialsandequipment identifyandrespectphysicallimitationsofselfandothers setuporidentifylocationofsafetyzonecontainingcomponentssuchasfirst aidkits,fireextinguishers,MSDSandeyewashstations documentitemssuchasinspections,potentialhazards,safetymeetings, injuriesandtrainingaccordingtojurisdictionalregulations attendtoolboxmeetings
11
Subtask A1.02
NL yes NS yes
Usespersonalprotectiveequipment(PPE)andsafetyequipment.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A1.02.01 A1.02.02 A1.02.03 A1.02.04 A1.02.05 A1.02.06 A1.02.07 identifysitehazardsandregulationsrequiringtheuseofPPEand safetyequipment locateandselectPPEandsafetyequipmentsuchasarcflashclothing,fire extinguishersandsignageappropriateforindividualtasksandsituations ensureproperfitofPPEsuchasrespiratorsandfaceshields recognizeworn,damagedordefectivePPEandsafetyequipmentsuchas excessivelywornbootsandcrackedsafetyglasses reportandreplacedamagedorfaultyequipment organize,cleanandstorePPEandsafetyequipmentaccordingtoOEM specifications applysafetyregulationssuchasWHMISandOH&S
Subtask A1.03
NL yes NS yes
Performslockoutandtaggingprocedures.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A1.03.01 A1.03.02 A1.03.03 A1.03.04 A1.03.05 A1.03.06 A1.03.07 12 coordinatelockoutandtaggingrequirementswithappropriateauthorities andothertrades identifyequipmentforlockoutandtagging selectapprovedlocksandtags performbumptestonenergizedequipmenttoensureworkwillbe performedoncorrectpieceofequipment deenergizeequipmentandperformbumptesttoconfirmdeenergization testsystemforzeropotentialusingequipmentsuchasvoltmetersandhigh voltagetesters verifyproperlockoutandtagging
Task2
Context
Usesandmaintainstoolsandequipment.
Industrialelectriciansmusthavetheabilitytoselect,useandmaintainthe appropriatetoolsandequipmentforspecifictasks.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 typesandlimitationsofhandtoolssuchasscrewdrivers,pliers,wrenches andmeasuringtapes types,functions,capabilities,limitationsandoperatingproceduresof portablepneumatic,electricandhydraulicpowertools types,functions,capabilities,limitationsandoperatingproceduresof stationarypowertoolssuchasdrillpresses,benchgrindersandbeltsanders types,functions,capabilities,limitationsandoperatingproceduresof powderactuatedtools fastenerspecificationsforpowderactuatedtools trainingandcertificationrequirementstooperatepowderactuatedtools powderactuatedtoolcomponents typesandoperatingproceduresofmechanicalmeasuringequipmentsuchas micrometers,torquewrenchesandfeelergauges types,functions,capabilities,limitationsandoperatingproceduresof equipmentusedformeasuringhighvoltageand/orfrequency types,functions,applications,limitationsandratingsofelectricaltestingand diagnostictoolssuchasmultimeters,voltagetesters,noncontactvoltage testers,megohmmetersandclampammeters electricaltestinganddiagnostictoolaccessoriessuchasleads,fuses andbatteries maintenanceschedules environmentalfactorsthataffectreadings OEMspecificationsforoperatingandmaintenanceinstructions,andfor calibrationschedules typesofaccessequipmentsuchasscissorlifts,platformliftsandarticulated boomlifts typesofscaffoldingsuchastubularandframe capabilitiesandlimitationsofscaffoldingandaccessequipment loadbearingcapacityofaccessequipment certificationrequirementsandregulationsforscaffoldingand accessequipment fallprotectionrequirementswhenworkingonaccessequipment 13
K11 K12 K13 K14 K15 K16 K17 K18 K19 K20
Subtask A2.01
NL yes NS yes
Maintainstoolsandequipment.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A2.01.01 A2.01.02 A2.01.03 A2.01.04 A2.01.05 A2.01.06 A2.01.07 A2.01.08 organizeandstoretoolsandcomponentsaccordingtoOEMspecifications clean,sharpen,lubricateandadjusttoolstoOEMspecifications ensurecalibrationofmeasuringequipmenttoOEMspecifications identifyworn,damagedordefectivetools changetoolcomponentssuchaschucks,bitsandblades replacetoolcomponentssuchascords,attachmentplugsandairlines repairtoolsaccordingtoOEMspecifications identifyhazardsassociatedwithtools
14
Subtask A2.02
NL yes NS yes
Usesaccessequipment.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A2.02.01 A2.02.02 A2.02.03 A2.02.04 A2.02.05 A2.02.06 A2.02.07 A2.02.08 identifytrafficareasandpotentialhazardssuchasconfinedspaces andtrenches installbarricadesandsignagetocontainworkzoneifrequired selectaccessequipmentsuchasladders,scissorliftsandarticulated boomlifts setupandsecurestepladdersandextensionladders erectvarioustypesofscaffoldingifrequired visuallyandmechanicallyinspectforworn,damagedordefectivescaffolding andaccessequipmentaccordingtoOEMspecifications report,taganddecommissionunsafe,worn,damagedordefective scaffoldingandaccessequipment organizeandstoreaccessequipmentaccordingtoOEMspecifications
Subtask A2.03
NL yes NS yes
Usesrigging,tugging,hoistingandliftingequipment.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A2.03.01 A2.03.02 A2.03.03 A2.03.04 A2.03.05 A2.03.06 identifytrafficareasandpotentialhazardssuchasconfinedspaces andtrenches installbarricadesandsignagetocontainworkzone useandunderstandhandsignals selectandsecurerigging,tugging,hoistingandliftingequipmentaccording toapplication ensurecalibrationofrigging,tugging,hoistingandliftingequipment accordingtoOEMspecificationsandjurisdictionalregulations visuallyandmechanicallyinspectforworn,damagedordefectiverigging, tugging,hoistingandliftingequipmentaccordingtoOEMspecifications 15
Task3
Context
Organizeswork.
Organizingworkallowsindustrialelectricianstointerpret,locateandmodify documentation,aswellasorganizenecessarymaterials,planprojecttasks andpreparetheworksiteinordertodotheirjobssafelyandeffectively.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 codessuchasbuildingcodes,theCECandjurisdictionalcodes OH&Sregulations standardssuchasCSAandUnderwritersLaboratoriesofCanada(ULC) codeandregulationupdates featuresofplans,schematics,drawingsandspecificationssuchasscale, legend,details,abbreviationsandsymbols standardsymbolanddrawingconventions CADsystems documentationrequirementsformodifyingdrawings typesofdocumentationsuchasmanuals,workorders,preventative maintenancesheets,regulations,technicalbulletins,shopdrawings andcatalogues companypoliciesandprocedures typesofequipment WHMISsymbolsandMSDS OEMspecifications tradeterminology projectortasktobecompleted worksitelocation,conditionsandrestrictions deliverydates,inventorycontrolandavailabilityofmaterials sequenceofoperations buildingstructuressuchaswalls,ceilingsandfloors 16
K10 K11 K12 K13 K14 K15 K16 K17 K18 K19
Subtask A3.01
NL yes NS yes
Interpretscodesandregulations.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
Subtask A3.02
NL yes NS yes
Usesplans,schematics,drawingsandspecifications.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A3.02.01 A3.02.02 A3.02.03 A3.02.04 A3.02.05 A3.02.06 A3.02.07 crossreferenceplans,drawingsandspecifications locateinformationonplans,drawingsandspecifications scaledimensions interpretthreedimensionalstructuresandcircuits performmathematicalcalculationssuchasconduitfill,andsingleand threephasecircuitcalculations applyschematicsandwiringdiagramstoperformtaskssuchas troubleshooting,maintainingandinstallingsystems determinewhetherplans,schematicsanddrawingsareuptodateaccording toasbuilt 17
A3.02.08 A3.02.09
Subtask A3.03
NL yes NS yes
Selectsmaterialsandsupplies.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A3.03.01 A3.03.02 A3.03.03 A3.03.04 A3.03.05 A3.03.06 identifyrequiredmaterialsandsuppliesaccordingtoapplication,plans, specifications,codesandenvironment performmathematicalcalculationssuchasscaling,ratiosanddetermining segmentlengthsofcablingandwiring interpretsitemeasurementsandinstructions quantifymaterialsaccordingtoplans performinventorycontrol ordermaterialsandsupplies
Subtask A3.04
NL yes NS yes
Plansprojecttasksandprocedures.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A3.04.01 A3.04.02 A3.04.03 A3.04.04 A3.04.05 A3.04.06 18 visuallyinspectworkenvironmenttodeterminescopeofwork determinelabourandequipmentrequirementsaccordingtospecifications suchaswiresizes,loadrequirementsandlocations establishandmaintainassignedschedules coordinateworkwithothertradessuchasshutdownrequirementsand installationsequencing drawandsketchlayouts followinstallationandoperationalsequences
Subtask A3.05
NL yes NS yes
Preparesworksite.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A3.05.01 A3.05.02 A3.05.03 A3.05.04 A3.05.05 visuallyinspecttoidentifytrafficareasandpotentialhazardssuchas confinedspacesandtrenches installbarricadesandsignagetocontainworkzone createopeningsandpenetrationsinstructuresandequipment ensuresufficientlightingandventilationofworkarea ensureallrequiredmaterialsandequipmentareonsite
Subtask A3.06
NL yes NS yes
Documentsmaintenancework.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A3.06.01 A3.06.02 A3.06.03 A3.06.04 A3.06.05 A3.06.06 A3.06.07 retrieve,recordandinterprettestdataforfuturereference recordfaultsandfailedcomponentstoaidindiagnosis recordserviceperformedandrequiredrepairstokeepalogonthatpiece ofequipment recordcorrectiveactionstospeeduprepairsandtomonitor equipmenttrends recorddateandpartsusedtoreplaceorrepairdefectiveorrecalleddevices, tokeepalogonthatpieceofequipmentandforbudgetingpurposes recordidentifiedpotentialandexistinghazardsforsafetypurposesandto helpprioritizethework recordmodificationsforinspectionpurposesfromlocalauthorities,torepeat successfulmodificationonothercommonpiecesofequipmentandfor troubleshootingpurposes identifyandrecordworkneededtobeperformedtoprioritizethetasks
A3.06.08
19
A3.06.09 A3.06.10
recordindustryalertstoreplaceorrepairdefectiveorrecalleddevices recordcalibrationdataasfoundandasleftforauditingpurposes
Task4
Context
Performsroutinetradeactivities.
Theseareactivitiesthatareperformedthroughoutthetrade.Industrial electriciansperformthesetasksinasafeandefficientmanner.These tasksidentifyspecificskillsandfunctionsthataretypicallyperformed byindustrialelectriciansinthenormalcourseoftheirwork.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 electricalclassificationofworksitelocation buildingstructuressuchaswalls,ceilingsandfloors equipmentsuchaspanelboards,switchgearandMCCs worksitehazardssuchasexistingutilities,explosiveatmosphere,dust, temperature,chemicalsandweather impactofperformingtaskduringprocessoperations startupandcommissioningproceduressuchasrotationaltesting,voltage readingsandcurrentreadings requireddocumentation OEMspecifications sequenceofoperationofequipment types,styles,purposesandsizesoffasteners,fittingsandconnectorssuchas expansionjoints,explosionproofandwaterproof installationandreplacementprocedures,andcapabilitiesandlimitationsof fasteners,fittingsandconnectors firestoppingtechniques
20
Subtask A4.01
NL yes NS yes
Installsfasteners,fittingsandconnectors.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A4.01.01 A4.01.02 A4.01.03 A4.01.04 selectandusetoolsandequipmentsuchashandtools,threaders,pipe wrenches,knockoutsets,stepdrills,holesawsandweldingequipment determinethreadsizeaccordingtosizeofraceway cutandthreadfittingsaccordingtomeasurementsofinstallation selectfasteners,fittings,groundbushingsandconnectorstomatchthe installationrequirements,andverifycompatibilityaccordingtoengineered drawings,electricalclassificationofworksiteandenvironmentsuchas undergroundandwetlocation locateandmountfasteners,fittings,groundbushingsandconnectors,and ensureaccessibilityoffittingsaccordingtoinstallationrequirements torqueandtightenfastenersandconnectorstoengineeredspecifications applylubricant,sealant,antiseizeandantioxidantcompoundsaccordingto engineeringspecificationsandindustrypractices
Subtask A4.02
NL yes NS yes
Conductsoperationaltests.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies A4.02.01 A4.02.02 A4.02.03 A4.02.04 selectandusetoolsandequipmentsuchasmultimeters,handtools,scope metersandcalibrators performsensoryinspectiontocheckforambienttemperature,abnormalheat, equipmentdamage,andpresenceofcorrosion,smokeorunusualodours takemeasurementssuchasvoltages,current,frequency,temperature,speed andpressuretoverifysystemoperationandparameters retrieve,readandinterprethistoricaldata,OEMspecifications,and engineereddrawingsanddatatoassistinthetesting
21
disconnect/reconnectcomponentstoallowaccesstocircuitryaccordingto industrypractices puttheprocessinManualmodetopreventupsetandtoaidintesting procedure,andputbacktoAutomaticuponcompletion calibratedevicesandsensorsaccordingtoplantrequirements comparehistoricalandasfounddatatointerprettendenciesandtrendsand changemaintenancefrequencyaccordingly makecalculationsandconversionssuchaspowerfactorandpowerusageto verifythatequipmentisworkingcorrectlyandtoaidintheselectionof componentsaccordingtoengineeringspecifications testequipmenttospecificationssuchasmotoroverloadprotectionand adjustabletripmechanismcircuitbreakers ensuresequencingandsafetycircuitoperationaftertesting
A4.02.10 A4.02.11
22
BLOCK B
Trends
Related Components (including,butnot limitedto) Toolsand Equipment SeeAppendixA. Disconnects,MCCs,distributionpanels,breakers,relays,fuses, overloads,protectiverelays,capacitors,transformers,contactors, motors,alternators,generators,cables,raceways,cabletrays,bus systems,insulators,synchronisers,arrestors,groundrods,grids,solar cellmats,groundfaultsystems,windturbines.
Task5
Context
Maintainshighvoltagepowerdistributionsystems.
Highvoltagepowerdistributionsystemsareusedinpowerlines,plantsand substationsforlongdistancetransmissionatlowercurrents.Industrial electriciansmustbeabletoinstall,serviceandrepairthesesystemsinorder toensuretheirefficientoperationandreduceunscheduleddisruptions. Maintaininghighvoltagepowersystemsisamongthemosthazardoustasks forindustrialelectriciansandextremecautionmustbeusedinthese environments.
23
inspection,maintenance,troubleshooting,repair,replacementand adjustmentproceduresandOEMspecifications safetyproceduresandequipmentrequiredtomaintainhighvoltage powersystems systemandcomponentoperation potentialcausesofpowerlosssuchasphasetophaseshorts,overcurrentand underfrequency eventsthatleadtosystemfailure performancehistoryofequipment preventativeandpredictivemaintenanceschedules calibrationaccordingtoOEMspecificationsforcomponentssuchasbreakers, relaysandswitchgear
Subtask B5.01
NL yes NS no
Installshighvoltagepowerdistributionsystems. (NOTCOMMONCORE)
PE yes NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B5.01.01 B5.01.02 B5.01.03 B5.01.04 B5.01.05 B5.01.06 B5.01.07 selectandusetoolsandequipmentsuchaswrenches,knivesandpliers ensureproperegressarounddistributionsystemaccordingto coderequirements assembleandtorquecomponentsinappropriatelocationsaccordingto OEMspecifications shimandlevelthecabinets spliceandterminatecableaccordingtoOEMspecifications followinstallationproceduresandspecifications verifysystemoperation
24
Subtask B5.02
NL yes NS no
Serviceshighvoltagepowerdistributionsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B5.02.01 B5.02.02 B5.02.03 B5.02.04 B5.02.05 B5.02.06 B5.02.07 B5.02.08 B5.02.09 B5.02.10 B5.02.11 identifyhazardsofstoredenergyincapacitors,cablingandtransformers deenergizesystemfromallpowersources testsystemforzeropotentialusinghighvoltagetester applygroundsetstophaseconductorstodraincapacitancecharge selectandusetoolsandequipmentsuchasvacuumcleanersand torquewrenches visuallyinspecthighvoltagecomponentsfordeteriorationsuchascorrosion, corona,loosetorqueanddiscolouration selectandusediagnostictoolsandequipmentsuchashipottestingtoolsand ultrasonicdetectors identifyworn,damaged,defectiveorhazardouscomponentsusingmethods suchasoilsamplings identifycomponentsthatrequirerepairorreplacement cleanandlubricatecomponents verifysystemoperation
Subtask B5.03
NL yes NS no
Troubleshootshighvoltagepowerdistributionsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B5.03.01 B5.03.02 B5.03.03 B5.03.04 identifyhazardsofstoredenergyincapacitors,cablingandtransformers performsensoryinspectionofcomponentdeteriorationsuchascorrosion, corona,loosetorqueanddiscolouration selectandusediagnostictoolsandequipmentsuchashipottestingtools, thermalgraphiccamerasandultrasonicdetectors isolatefaultsbydeenergizingsourceofenergy 25
Subtask B5.04
NL yes NS no
Repairshighvoltagepowerdistributionsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B5.04.01 B5.04.02 B5.04.03 B5.04.04 B5.04.05 B5.04.06 B5.04.07 B5.04.08 B5.04.09 B5.04.10 B5.04.11 identifyhazardsofstoredenergyincapacitors,cablingandtransformers determinewhethercomponentsrequirerepairorreplacement selectandusetoolsandequipmentsuchastorquewrenches,pliers andknives selectreplacementcomponentsaccordingtoOEMspecificationsand coderequirements deenergizesystemfromallpowersources testsystemforzeropotentialusinghighvoltagetester applygroundsetstophaseconductorstodraincapacitancecharge disassemble/reassemblecomponentsaccordingtoOEMspecificationsto accessrepairarea replace,adjustandmodifycomponentssuchasbushingsandswitches cleancomponentsbeforeterminatingtoensuregoodcontactandcontinuity verifyoperationofcomponents
26
Task6
Context
Maintainslowvoltagepowerdistributionsystems.
Lowvoltagepowerdistributionsystemsprovidepowertotheplant. Industrialelectriciansmustbeabletoinstall,serviceandrepairthesesystems inordertoensuretheirefficientoperationandreduceunscheduled disruptions.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 codesandregulationsregardingtheinstallationoflowvoltage powersystems typesoflowvoltagepowersystems,singleandthreephase typesofcomponentssuchasdisconnects,MCCs,powertransformers andcabling installation,inspection,maintenance,testing,troubleshootingandrepair proceduresandspecifications rating,sizingandcompatibilityofcomponentssuchasbusbars,breakers, fusesanddistributionpanels hazardsassociatedwithlowvoltagepowersystems systemandcomponentoperation eventsthatleadtosystemfailure performancehistoryofequipment safetyproceduresrequiredforserviceandrepair
Subtask B6.01
NL yes NS yes
Installslowvoltagepowerdistributionsystems.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B6.01.01 B6.01.02 B6.01.03 selectandusetoolsandequipmentsuchasphasemeters,compressiontools, wirestrippersandbenders ensureproperegressarounddistributionsystemaccordingtocode requirements performphasingtoachieverequiredrotationofthreephaserotating equipment
27
Subtask B6.02
NL yes NS yes
Serviceslowvoltagepowerdistributionsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B6.02.01 B6.02.02 B6.02.03 B6.02.04 B6.02.05 B6.02.06 B6.02.07 B6.02.08 B6.02.09 B6.02.10 selectandusediagnostictoolsandequipmentsuchasmegohmmetersand multimeters identifyhazardsofstoredenergyincapacitors deenergizesystemfromallpowersources testsystemforzeropotentialusingmultimeter selectandusetoolsandequipmentsuchasvacuumcleanersand torquewrenches visuallyinspectcomponentsfordeteriorationsuchascorrosion,loosetorque anddiscolourationusingmethodssuchasthermographyforhotspots identifycomponentsthatrequirerepairorreplacement cleanandlubricatecomponents performadjustmentssuchastripsettingsandtapchanges verifysystemoperation
28
Subtask B6.03
NL yes NS yes
Troubleshootslowvoltagepowerdistributionsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B6.03.01 B6.03.02 B6.03.03 B6.03.04 B6.03.05 B6.03.06 B6.03.07 selectandusediagnostictoolsandequipmentsuchasmultimeters,clampon ammetersandmegohmmeters identifyhazardsofstoredenergyincapacitorsaccordingtoindicatorssuch ashazardstickersordrawings visuallyinspectcomponentsfordeteriorationsuchascorrosion,loosetorque anddiscolouration isolatefaultsbydeenergizingsourceofenergy deenergizesystemfromallpowersources testsystemforzeropotentialusingmultimeter identifycomponentsthatrequirerepairorreplacement
Subtask B6.04
NL yes NS yes
Repairslowvoltagepowerdistributionsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B6.04.01 B6.04.02 B6.04.03 B6.04.04 B6.04.05 B6.04.06 B6.04.07 B6.04.08 B6.04.09 B6.04.10 selectandusetoolsandequipmentsuchasscrewdrivers,wrenchesandpliers determinewhethercomponentsrequirerepairorreplacement selectreplacementcomponentssuchasrelays,contactorsandfusesaccording toOEMspecificationsandcoderequirements deenergizesystemfromallpowersources disassemble/reassemblecomponentsaccordingtoOEMspecifications replace,adjustandmodifycomponentssuchasrelays,contactorsandfuses testsystemforzeropotentialusingmultimeter identifyhazardsofstoredenergyincapacitors,cablingandtransformers cleancomponentsbeforeterminatingtoensuregoodcontactandcontinuity verifyoperationofcomponents 29
Task7
Context
Maintainsalternatingcurrent(AC)systems.
ACsystemsareusedtosupplyloadpowertobranchcircuitequipment. Therefore,itisimportanttomaintainthesesystemsbyinstallingupgrades, performingpreventativemaintenanceandmakingnecessaryrepairsinan expedientmanner.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 codesandregulationsregardingtheinstallationofACsystems typesofACsystemssuchassingleandthreephase ACsystemcomponents,controls,capabilitiesandspecifications componentoperation OEMinstallation,maintenance,inspection,troubleshootingand repairspecifications loadbalancing powerfactorcorrection lineandlowvoltagecontrols eventsthatleadtosystemfailure performancehistoryofequipment preventativemaintenancetechniques,testsandprocedures
Subtask B7.01
NL yes NS yes
Installsalternatingcurrent(AC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B7.01.01 B7.01.02 B7.01.03 B7.01.04 B7.01.05 selectandusetoolsandequipmentsuchaswrenches,wirestrippers andpliers ensureproperegressarounddistributionsystemaccordingtocode requirements determinecircuitloadingcapacity assembleandtorquecomponentsinappropriatelocationsaccordingto OEMspecifications shimandlevelthecabinets 30
Subtask B7.02
NL yes NS yes
Servicesalternatingcurrent(AC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B7.02.01 B7.02.02 B7.02.03 B7.02.04 B7.02.05 B7.02.06 B7.02.07 B7.02.08 B7.02.09 B7.02.10 selectandusediagnostictoolsandequipmentsuchasmegohmmeters andmultimeters deenergizesystemfromallpowersources testsystemforzeropotentialusingmultimeter selectandusetoolsandequipmentsuchasvacuumcleanersand torquewrenches visuallyinspectcomponentsfordeteriorationsuchascorrosion,loosetorque anddiscolourationusingmethodssuchasthermographyforhotspots identifycomponentsthatrequirerepairorreplacement disassemble/reassemblecomponentsaccordingtoOEMspecifications cleanandlubricatecomponents performadjustmentssuchastripsettingsandoverloads verifysystemoperation
31
Subtask B7.03
NL yes NS yes
Troubleshootsalternatingcurrent(AC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B7.03.01 B7.03.02 B7.03.03 B7.03.04 B7.03.05 B7.03.06 B7.03.07 selectandusediagnostictoolsandequipmentsuchasmultimeters,clampon ammetersandmegohmmeters performsensoryinspectionofcomponentsfordeteriorationsuchas corrosion,loosetorqueanddiscolouration isolatefaultsbydeenergizingsourceofenergy deenergizesystemfromallpowersources testsystemforzeropotentialusingmultimeter disassemble/reassemblecomponentsaccordingtoOEMspecifications identifycomponentssuchasfuses,breakersandcontactorsthatrequire repairorreplacement
Subtask B7.04
NL yes NS yes
Repairsalternatingcurrent(AC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B7.04.01 B7.04.02 B7.04.03 B7.04.04 B7.04.05 B7.04.06 B7.04.07 B7.04.08 B7.04.09 32 selectandusetoolsandequipmentsuchasscrewdrivers,wrenchesandpliers determinewhethercomponentsrequirerepairorreplacement selectreplacementcomponentssuchasrelays,contactorsandfusesaccording toOEMspecificationsandcoderequirements deenergizesystemfromallpowersources testsystemforzeropotentialusingmultimeter disassemble/reassemblecomponentsaccordingtoOEMspecifications replace,adjustandmodifycomponentssuchasrelays,contactorsandfuses cleancomponentsbeforeterminatingtoensuregoodcontactandcontinuity verifyoperationofcomponents
Task8
Context
Maintainsdirectcurrent(DC)systems.
DCsystemsprovidepowertospecializedequipmentfoundinindustry. Industrialelectriciansmustbeabletoinstall,serviceandrepairthesesystems inordertoensuretheirefficientoperationandreduceunscheduled disruptions.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 codesandregulationsregardingtheinstallationofDCsystems typesandapplicationsofDCsystemssuchaspower,control,cathodic protectionandlighting rectificationandDCpowergeneration systemandcomponentoperation ratingandcompatibilityofcomponentssuchasbusbars,breakersand distributionpanels hazardsassociatedwithDCsystems OEMspecificationsforinspection,maintenance,installation,troubleshooting, repair,replacement,adjustmentandmodification specifications,characteristics,typesandsizesofDCsystemcomponentssuch asbrushes,relays,breakersandbusbars typesandcausesoffailureofDCsystemcomponents eventsthatleadtosystemfailure safetyproceduresrequiredtotroubleshoot,serviceandrepairDCsystems batterysystemsandtheirmaintenancerequirements
Subtask B8.01
NL yes NS yes
Installsdirectcurrent(DC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
Subtask B8.02
NL yes NS yes
Servicesdirectcurrent(DC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B8.02.01 B8.02.02 B8.02.03 B8.02.04 B8.02.05 selectandusediagnostictoolsandequipmentsuchasmegohmmeters andmultimeters deenergizesystemfromallpowersources testsystemforzeropotentialusingmultimeter selectandusetoolsandequipmentsuchasvacuumcleanersand torquewrenches performsensoryinspectiononcomponentssuchasgenerators,commutators andbatteriesfordeteriorationsuchascorrosion,loosetorqueand discolourationusingmethodssuchasthermographyforhotspots identifypresenceofpoweranomaliessuchasripple,noiseandspikes identifycomponentsthatrequirerepairorreplacement disassemble/reassemblecomponentsaccordingtoOEMspecifications cleanandlubricatecomponents performadjustmentssuchasaddingdistilledwatertobattery verifysystemoperation
34
Subtask B8.03
NL yes NS yes
Troubleshootsdirectcurrent(DC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B8.03.01 B8.03.02 B8.03.03 B8.03.04 B8.03.05 B8.03.06 B8.03.07 B8.03.08 selectandusediagnostictoolsandequipmentsuchasmultimeters,scope meters,clamponammetersandmegohmmeters performsensoryinspectiononcomponentsfordeteriorationsuchas corrosion,loosetorqueanddiscolouration isolatefaultsbydeenergizingsourceofenergy deenergizesystemfromallpowersources testsystemforzeropotentialusingmultimeter identifypresenceofpoweranomaliessuchasripple,noiseandspikes identifycomponentsthatrequirerepairorreplacement disassemble/reassemblecomponentsaccordingtoOEMspecifications
Subtask B8.04
NL yes NS yes
Repairsdirectcurrent(DC)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B8.04.01 B8.04.02 B8.04.03 B8.04.04 B8.04.05 B8.04.06 B8.04.07 B8.04.08 B8.04.09 selectandusetoolsandequipmentsuchasscrewdrivers,wrenchesandpliers determinewhethercomponentsrequirerepairorreplacement selectreplacementcomponentssuchasrelays,brushes,batteriesandfuses accordingtoOEMspecificationsandcoderequirements deenergizesystemfromallpowersources disassemble/reassemblecomponentsaccordingtoOEMspecifications replace,adjustandmodifycomponentssuchasrelays,brushes,batteries andfuses testsystemforzeropotentialusingmultimeter cleancomponentsbeforeterminatingtoensuregoodcontactandcontinuity verifyoperationofcomponents 35
Task9
Context
Maintainsgroundingandbondingsystems.
Groundingandbondingsystemsareusedtocompleteasafepathforfault current.Theirprimaryuseisasasafeguardintheoperationofelectrical systems.Industrialelectriciansmustbeabletoinstall,serviceandrepair thesesystemsinordertoensuretheirefficientoperationandreduce unscheduleddisruptions.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 codesandregulationsregardingtheinstallationofgroundingandbonding systems methodsofgrounding methodsofbonding systemandcomponentoperation components,controls,ratingsandcapabilities OEMspecificationsforinstallation,inspection,troubleshooting,repair, replacement,modificationandpreventativemaintenance specifications,characteristics,typesandsizesofcomponentssuchasground rods,groundgridsandplates electricaltheory eventsthatleadtosystemfailure equipmentperformancehistory potentialhazardssuchasshocksandpotentialdifference safetyproceduresandequipmentrequiredforrepairandservice methodsandproceduresfortestingandverificationofgroundingand bondingsystemsandcomponents
Subtask B9.01
NL yes NS yes
Installsgroundingandbondingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
Subtask B9.02
NL yes NS yes
Servicesgroundingandbondingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B9.02.01 B9.02.02 B9.02.03 B9.02.04 B9.02.05 B9.02.06 assesstorque,cleanlinessandcorrosionofbondingterminations ensuregroundingandbondingterminationsaresecure selectandusetoolsandequipmentsuchastorquewrenches,hammersand wirebrushes visuallyinspectcomponentsforwear,oxidationandlooseconnections identifycorroded,damagedordefectivebondingcomponentsby discolourationandnicking cleancomponentstoensuregoodcontactandlowestresistance
Subtask B9.03
NL yes NS yes
Troubleshootsgroundingandbondingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
37
Subtask B9.04
NL yes NS yes
Repairsgroundingandbondingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B9.04.01 B9.04.02 B9.04.03 B9.04.04 B9.04.05 B9.04.06 selectreplacementcomponentsaccordingtocoderequirementssuchastype, size,capacityandenvironment selectandusetoolsandequipmentsuchascompressiontools,exothermal weldingequipmentandtorquewrenches replacedamagedconductors cleanconductorsandmetalsurfacesbeforeterminatingtoensuregood contactandcontinuity locateandsecuregroundingandbondingcomponentsinappropriate locationstopreventfurtherdamage verifyfaulthasbeencorrected
Task10
Context
Maintainspowergeneratingsystems.
Powergeneratingsystemssuchassolarcell,windturbineandcogeneration produceelectricitytoavarietyofapplications.Industrialelectriciansmustbe abletoinstall,serviceandrepairthesesystemsinindustrialplantsinorderto ensuretheirefficientoperationandreduceunscheduleddisruptions.
hazardsassociatedwithpowergeneratingsystems methodsandproceduresforinstallingpowergeneratingsystems preventativeandpredictivemaintenanceschedules inspection,maintenance,troubleshooting,repair,replacementand adjustmentproceduresandspecifications safetyproceduresandequipmentrequiredtoaccess,inspectandservice powergeneratingsystems systemandcomponentoperation potentialcausesofpowerlosssuchasphasetophaseshorts,overcurrentand underfrequency eventsthatleadtosystemfailure historyofequipmentperformance
Subtask B10.01
NL yes NS no
Installspowergeneratingsystems.(NOTCOMMONCORE)
PE yes NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B10.01.01 B10.01.02 B10.01.03 B10.01.04 B10.01.05 B10.01.06 B10.01.07 B10.01.08 B10.01.09 selectandusetoolsandequipmentsuchaswrenches,knivesandpliers ensureproperegressarounddistributionsystemaccordingto coderequirements ensureproperlocationanddirectionofcomponentsuchassolarcelland windturbine performphasingtoachieverequiredrotationofthreephaserotating equipment ensurecablesareconnectedaccordingtopolarityandgroundedasrequired assembleandtorquecomponentsinappropriatelocationsaccordingto OEMspecifications terminatecableaccordingtocodeandOEMspecifications followinstallationproceduresaccordingtocodeandOEMspecifications verifysystemoperation
39
Subtask B10.02
NL yes NS no
Servicespowergeneratingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B10.02.01 B10.02.02 B10.02.03 B10.02.04 B10.02.05 B10.02.06 B10.02.07 B10.02.08 B10.02.09 B10.02.10 B10.02.11 identifyhazardsofpowergeneratingsystem isolatesystemfromdynamicandkineticenergy testsystemforzeropotentialusingtoolssuchasmultimetersandhigh voltagetesters applygroundsetstophaseconductorstodraincapacitancecharge selecttoolsandequipmentsuchaspliersandtorquewrenches performsensoryinspectionofcomponentsfordeteriorationsuchas corrosion,loosetorqueanddiscolouration selectandusediagnostictoolsandequipmentsuchasmegohmmetersand thermalgraphiccameras identifyworn,damaged,defectiveorhazardouscomponents identifycomponentsthatrequirerepairorreplacement cleanandlubricatecomponents verifysystemoperation
Subtask B10.03
NL yes NS no
Troubleshootspowergeneratingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B10.03.01 B10.03.02 B10.03.03 B10.03.04 B10.03.05 identifyhazardsofstoredenergyincapacitors,cablingandtransformers performsensoryinspectionofcomponentsdeteriorationsuchascorrosion, corona,loosetorqueanddiscolouration selectandusediagnostictoolsandequipmentsuchashipottestingtools, thermalgraphiccamerasandultrasonicdetectors isolatefaultsbydeenergizingsourceofenergy testsystemforzeropotentialusinghighvoltagetesterandmultimeter 40
B10.03.06 B10.03.07
Subtask B10.04
NL yes NS no
Repairspowergeneratingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies B10.04.01 B10.04.02 B10.04.03 B10.04.04 B10.04.05 B10.04.06 B10.04.07 B10.04.08 B10.04.09 B10.04.10 B10.04.11 identifyhazardsofstoredenergyincapacitors,cablingandtransformers determinewhethercomponentsrequirerepairorreplacement selectandusetoolsandequipmentsuchastorquewrenches,pliers andknives selectreplacementcomponentsaccordingtoOEMspecificationsand coderequirements deenergizesystemfromallpowersources testsystemforzeropotentialusinghighvoltagetesterandmultimeter applygroundsetstophaseconductorstodraincapacitancecharge disassemble/reassemblecomponentsaccordingtoOEMspecifications replace,adjustandmodifycomponentssuchasbushingsandswitches cleancomponentsbeforeterminatingtoensuregoodcontactandcontinuity verifyoperationofcomponents
41
BLOCK C
Trends
ELECTRICAL EQUIPMENT
Lightingsystemloadsheddingdevicessuchasoccupancydetectors, tasklighting,automaticdimmersandbuildingautomationsystemsare increasinglybeingusedtoconserveelectricity.Safetyhasdriven advancesinthedesignofelectricalequipmentsuchastamperproof receptaclesandarcfaultinterrupters. Installationofelectricalequipmentandwiringmustnowinclude considerationoffirestoppingratingsinbuildingdesign.
Related Components (including,butnot limitedto) Electricalwiring,cablingandterminations. Lightingsystems:lightemittingdiode(LED),highintensity discharge(HID),fluorescentlighting,compactfluorescentlamp(CFL), plasma,breakers,photocells,timers,conduits,cables,fasteners,cable traysandsupports,contactors,transformers,switches. Protectiondevices:fuses,breakers,overloads,arcfaultprotection, groundfaultcircuitinterrupters(GFCIs),overcurrentdevices, disconnects,switches,voltageregulators,synchronizers. Rotatingequipment:ACandDCmotors,generators,alternators,eddy currentbrakes/clutches,frictionbrakes/clutches,centrifugalswitches, governors. Drivesandassociatedcontrols:variablefrequencydrives(VFDs),DC drives,softstart,siliconcontrolledrectifiers(SCRs). Nonrotatingequipment:transformers,encoders,scales,start/stop stations,starters. Toolsand Equipment SeeAppendixA.
42
Task11
Context
Maintainsequipment,wiring,cablingandterminations.
Equipment,wiring,cablingandterminationsaretheelectricalcomponents linkingthesourcetotheload.Thistaskalsoincludesmaintenanceofseismic restraintsystems,asrequiredincertaingeographiclocations.Maintaining thesecomponentsincludesinstallationandrepair.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 regulationsandcoderequirementsregardingtheinstallationofelectrical wiring,cablingandterminations typesandfunctionsofelectricalwiring,cablingandterminations capabilitiesandlimitationsofelectricalwiring,cablingandterminations installationproceduresandtechniquesforelectricalwiring,cabling andterminations sizesofelectricalwiresandcables terminationproceduresandconsiderationsfordissimilarmetals types,functions,capabilitiesandlimitationsofraceways,cabletrays, buswaysandassociatedcomponents bendingandconnectingtechniquesforconduitapplicationsincludingrigid, electricalmetallictubing(EMT)andpolyvinylchloride(PVC) installationproceduresandtechniques,andsupportingandsecuring methodsforraceways,cabletrays,buswaysandassociatedcomponents jurisdictionalregulationsregardingseismicrestraintsystems typesofseismicrestraintsystems risksofseismicevents equipmentthatcontainsseismicrestraintsystemssuchasbatterybanks,trays andcontrolpanels
43
Subtask C11.01
NL yes NS yes
Installselectricalwiring,cablingandterminations.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C11.01.01 installcableandconductorsthroughracewaysaccordingtoCECandOEM specificationsinordertopreventdamagetocableandconductorsand toseparatepowerfromcontrolwiringtoeliminatenoiseandinduction C11.01.02 C11.01.03 C11.01.04 C11.01.05 C11.01.06 C11.01.07 C11.01.08 selectanduselubricantasrequiredbyapplication selectandusetoolsandequipmentsuchasrollers,wheels,tuggers,pulleys andsheaves determineterminationmethodtobeusedaccordingtomaterialand OEMspecifications prepareterminationofconductorsusingmethodssuchascutting,crimping andtorquing terminatecablesandconductorsusingmethodssuchasnutandbolt,and compressionconnections checkforcontinuityandinsulationofelectricalwiresandcables label,verifyandrecordinstallationofelectricalwiringandcabling
Subtask C11.02
NL yes NS yes
Installsraceways,cabletrays,buswaysandassociatedcomponents.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C11.02.01 C11.02.02 selectandsizeraceways,cabletrays,buswaysandassociatedcomponents accordingtocode,standards,environmentsandOEMspecifications layoutrouteofraceways,cabletrays,buswaysandassociatedcomponents accordingtocoderequirementssuchasnumberofbendsallowed,and locationandsizeofpullboxandfittings performmathematicalcalculationssuchasscaling,ratiosandinstallation trigonometry
C11.02.03
44
Subtask C11.03
NL yes NS yes
Repairselectricalwiring,cablingandterminations.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C11.03.01 C11.03.02 C11.03.03 C11.03.04 C11.03.05 C11.03.06 replacefaultyelectricalwiringandcabling selectandusetoolsandequipmentsuchasthermalgraphiccameras, megohmmetersandreflectometerstolocatefaultsandverifyrepair performvisualinspectionstorepairorreplacewornorcrackedcoverings repairconductorcoveringsandconductorusingmanufacturerspecific repairkit replace,tightenandcleanterminationstoavoidoverheatingandto lowerresistance securesupportsystems,enclosuresandadjacentequipmenttoavoid vibrationofwiresandterminations
Subtask C11.04
NL yes NS no
Maintainsseismicrestraintsystems.(NOTCOMMONCORE)
PE no NB no QC yes ON no MB yes SK ND AB ND BC yes NT ND YT NV NU ND
Task12
Context
Maintainslightingsystems.
Variousdevicesandfixturesaremaintainedbyindustrialelectricianstomeet thepowerandlightingrequirementsoftheendusers.Lightingsystemsare usedtoproperlyilluminatespecifiedareasaccordingtousersneeds.DC poweredlightingisusedinlimitedapplicationssuchasemergencylighting. Maintaininglightingsystemsincludestheinstallationofnewcomponents, upgradingofexistingsystems,servicing,troubleshootingandrepairing.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 codesandregulationsregardingtheinstallationoflightingsystems typesoflightingsystemssuchasLED,HID,CFL,fluorescentand incandescent lightingsystemcomponentsandcontrols componentoperation installation,inspection,troubleshooting,repairandpreventative maintenanceproceduresandtechniques lightingspecifications eventsthatleadtosystemfailure historyofequipmentperformance DClightingsystemforemergencylights
46
Subtask C12.01
NL yes NS yes
Installslightingsystems.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C12.01.01 C12.01.02 C12.01.03 C12.01.04 C12.01.05 C12.01.06 C12.01.07 selectandusetoolsandequipmentsuchashandandpowertools selectandinspectcomponentsrequiredforinstallationaccordingtobuilding system,specificationsandcoderequirements identifysupportrequirementsforlightingsystemsaccordingto OEMspecifications locate,mountandsecurelightingcomponentsinlocationsspecifiedby drawings,plansandcoderequirements produceasbuiltdrawings assemblelightingcomponentsaccordingtoOEMspecifications verifyoperationoflightingsystem
Subtask C12.02
NL yes NS yes
Serviceslightingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C12.02.01 C12.02.02 C12.02.03 C12.02.04 C12.02.05 C12.02.06 47 followpreventativemaintenancescheduleforchanginglighting systemcomponents cleanlightingsystemcomponentssuchaslensesandlenscovers recognizedamage,faultsordegradationofcomponentsinthelighting systemsuchasleakingballastsandburntwiring assessfunctionalityoflightingsystemsandassociatedcontrols disposeoflightingcomponentssuchasfluorescentsandballastsaccordingto environmentalregulations identifypotentialhazardssuchasdustbuildup,firehazards,heat andmoisture
Subtask C12.03
NL yes NS yes
Troubleshootslightingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
Subtask C12.04
NL yes NS yes
Repairslightingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C12.04.01 C12.04.02 C12.04.03 C12.04.04 C12.04.05 C12.04.06 selectandusetoolsandequipmentsuchastelescopicbulb removers/extractors,handtoolsandmultimeters verifyoperatingvoltageaccordingtofixturespecifications interpretwiringschemetoupgradewiringoflightingsystem selectreplacementcomponentsaccordingtofactorssuchastype,desired lightcolour,compatibility,sizeandcapacity replacecomponentsaccordingtosocketstyleandspecifications verifysystemoperation
48
Task13
Context
Maintainsprotectiondevices.
Protectiondevicesincludefuses,relays,overloadsandovercurrentdevices. Theyprotecttheequipmentfromfaultdamageandprovideinjuryprotection. Industrialelectriciansmustbeabletoinstall,service,troubleshootandrepair thesedevicesatvariousvoltages.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 codesandregulationsregardingtheinstallationofprotectiondevices typesofprotectiondevicessuchasfuses,relays,phaseloss,solidstate controls,surgeprotection,overloadsandovercurrentdevices componentcharacteristicssuchasratings,controlsandsizes compatibilityofcomponents installation,inspection,troubleshooting,maintenanceandrepairprocedures andtechniques devicesandcomponentoperation potentialhazardsrelatedtoprotectiondevices probablecausesoffaultandappropriatecorrectivemethods eventsthatleadtosystemfailure historyofequipmentperformance safetyproceduresrequiredtorepairprotectiondevices
Subtask C13.01
NL yes NS yes
Installsprotectiondevices.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C13.01.01 C13.01.02 C13.01.03 C13.01.04 determinetypeandmodelofprotectiondevicerequiredaccordingtoservice requirementssuchasvoltage,currentandtorque selectandusetoolsandequipmentsuchashandandpowertools locate,mountandsecureprotectiondevicesaccordingtodrawings,plansand coderequirements produceasbuiltdrawings
49
C13.01.05 C13.01.06
Subtask C13.02
NL yes NS yes
Servicesprotectiondevices.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C13.02.01 C13.02.02 C13.02.03 C13.02.04 C13.02.05 C13.02.06 C13.02.07 selectandusetoolsandequipmentsuchasthermalgraphiccamerasand handtools followpreventativemaintenancescheduleforcheckingresistance,gapsand mechanicalaction simulatefaulttotestandcalibrateprotectiondevices performsensoryinspectiontoidentifydamageandfaultsofprotection devices,andconditionssuchasburntsmell,vibrationsanddiscolouration checktorqueofterminations cleanprotectiondevicestoremovedust,animalsandmoisture verifysettingsofprotectiondevices
Subtask C13.03
NL yes NS yes
Troubleshootsprotectiondevices.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C13.03.01 C13.03.02 C13.03.03 50 selectandusetoolsandequipmentsuchasammeters,megohmmeters, proximitytesters,multimetersandfusepullers identifyworn,faultyanddegradedcomponentssuchasburntwires,hot breakers,malfunctioningcomponentsandloosebreakers simulatefaulttotestprotectiondevicessuchassafetyswitches,GFCIs,fuses andbreakers
Subtask C13.04
NL yes NS yes
Repairsprotectiondevices.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C13.04.01 C13.04.02 C13.04.03 C13.04.04 C13.04.05 C13.04.06 selectandusetoolsandequipmentsuchashandtoolsandmultimeters performresistancepretesttoensurethatreplacementfuseisoperational selectreplacementcomponentsbasedontype,size,capacityand environment determinewhethercomponentsrequirerepairorreplacement replace,adjustandmodifycomponentswithproceduressuchaschanging coils,dielectricoilandpittedcontacts,andreplacingfuseholders verifydeviceoperation
Task14
Context
Maintainsrotatingequipmentandassociatedcontrols.
Rotatingequipmentandassociatedcontrolstransformelectricalenergyinto mechanicalenergy(motors)orviceversa(generators)dependingon application.Thesemayincludeheating,ventilation,runningacompressor,or manufacturingprocesses.Industrialelectriciansmustbeabletoinstall, service,troubleshootandrepairthesesystemsinordertoensureefficient operationandreduceunscheduleddisruptions.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 codesandregulationsregardingthemaintenanceofrotatingequipmentand associatedcontrols typesandoperationofrotatingequipmentandassociatedcontrols controls,ratings,capabilitiesandcharacteristicsofcomponents installation,inspection,troubleshooting,maintenanceandrepairprocedures andtechniques eventsthatleadtosystemfailure historyofequipmentperformance potentialhazardsrelatedtorotatingequipmentandassociatedcontrols safetyproceduresrequiredforserviceandrepair 51
Subtask C14.01
NL yes NS yes
Installsrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C14.01.01 C14.01.02 C14.01.03 selectandusetoolsandequipmentsuchashandandpowertools determinetypeandmodelofrotatingequipmentandcontrolsrequired accordingtoapplication assembleandconnectcomponentssuchasresistancetemperaturedetectors (RTDs),vibrationprobesandovertemperaturecontactsaccordingto OEMspecifications recognizehazardsrelatedtorotatingequipmentandassociatedcontrols locate,mountandsecurerotatingequipmentandassociatedcontrols accordingtoOEMspecificationsandcoderequirements commissionrotatingequipmentandassociatedcontrolsbychecking connections,rotationdirection,torque,voltage,andstartupand fullloadcurrent ensurethatsafetyfeaturesofequipmentsuchasguards,controlsandlimits areoperational verifysequenceofoperationsforequipment produceasbuiltdrawings
Subtask C14.02
NL yes NS yes
Servicesrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C14.02.01 C14.02.02 C14.02.03 selectandusetoolsandequipmentsuchasdatamonitors,thermalgraphic cameras,airblowersandtemperatureguns followpreventativemaintenancescheduleforcheckingbrushlength,seating andspringtensionofbrushholders performvibrationanalysisonrotatingequipmentinordertoassessproblems suchasmisalignmentandwornbearings 52
C14.02.04
C14.02.05
C14.02.06 C14.02.07
Subtask C14.03
NL yes NS yes
Troubleshootsrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C14.03.01 C14.03.02 C14.03.03 C14.03.04 C14.03.05 C14.03.06 selectandusetoolsandequipmentsuchashipottesters,vibrationanalyzers, ammeters,megohmmetersandmultimeters performsensoryinspectiontoidentifyabnormalheat,sounds,odours, vibrationsandarcing/sparkingsources performresistancechecksonwindingforphaseloss performmegohmmetertesttodetermineground identifyworn,damagedordefectivecomponentssuchasbearings,sliprings andcommutators checkseating,brushlengthandspringtensionofbrushholders
53
Subtask C14.04
NL yes NS yes
Repairsrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C14.04.01 C14.04.02 C14.04.03 C14.04.04 C14.04.05 C14.04.06 C14.04.07 selectandusetoolsandequipmentsuchasbearingpullers,bearingheaters, springtensiongauges,commutatorstonesandfeelergauges selectreplacementcomponentsbasedontype,size,capacityand environment determinewhethercomponentsrequirerepairorreplacement replacecomponentssuchasbrushholders,springs,capacitorsandbearings performequipmentrepairssuchasrecoating,andresurfacingbrushends andmotorbrake runDCcurrentthroughmotortoremovemoisturefromwindingsand improvetheohmicvalueofthewindings verifysystemoperationbyperformingload,hipot,neutralplaneand dynamicrotationtests
Task15
Context
Maintainsdrivesandassociatedcontrols.
Drivesandassociatedcontrolsprovidespeed,frequency,torque,current, timeandbrakingcontroltomotors.Industrialelectriciansmustbeableto install,service,troubleshootandrepairthesesystemsinordertoensure efficientoperationandreduceunscheduleddisruptions.
Subtask C15.01
NL yes NS yes
Installsdrivesandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C15.01.01 C15.01.02 C15.01.03 C15.01.04 C15.01.05 C15.01.06 C15.01.07 selectandusetoolsandequipmentsuchashandandpowertools determinetypeandmodelofdrivesandassociatedcontrolsrequired accordingtoapplicationandmotor identifyhazardsrelatedtodrivesandassociatedcontrols locate,mountandsecuredrivesandassociatedcontrolsaccordingto OEMspecifications programandconfiguredrivesandassociatedcontrolsaccordingto OEMspecifications verifydeviceoperationtoconfirmperformancewithinparameterssuchas deceleration,loadingandacceleration produceasbuiltdrawings
55
Subtask C15.02
NL yes NS yes
Servicesdrivesandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C15.02.01 C15.02.02 C15.02.03 C15.02.04 selectandusetoolsandequipmentsuchashandtools,datamonitors, thermalgraphiccameras,airblowersandtemperatureguns followpreventativemaintenancescheduleforreplacingfilters,torquinglugs, backingupprogramsandcheckingfans cleandustfromdrivesandassociatedcontrolsusingairblowerto preventoverheating checkwiringandcableconnections,andtorqueofterminations
Subtask C15.03
NL yes NS yes
Troubleshootsdrivesandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C15.03.01 C15.03.02 C15.03.03 C15.03.04 C15.03.05 C15.03.06 readandinterpreterrorcodesbycheckinghumanmachineinterface(HMI) andreferringtotroubleshootingmanual verifyforfaultssuchasloosecables,lowvoltageanddiscolouration identifyproblemswithsequenceofoperationthataffecttheperformanceof thedriveandmotor verifyforrequiredgroundaccordingtoOEMspecifications identifycommunicationsproblems determineissuesrelatingtothelengthoftheconductorssuchasdistanceof motorfromdriveandtheequallengthofconductorsformultiplemotors
56
Subtask C15.04
NL yes NS yes
Repairsdrivesandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C15.04.01 C15.04.02 C15.04.03 C15.04.04 C15.04.05 C15.04.06 C15.04.07 replacefaultydrivesusinghandtools selectandusetoolsandequipmentsuchasmultimeters,calibratorsand signalgenerators programcardsusingmethodssuchasinsertingintegratedcircuit(IC)with loadedprogram,copyingfromHMIandmanuallyenteringprogram replacedrivecomponentssuchasbackupbatteries,SCRs,cardsand coolingfans adjustcontrolparameterssuchasspeed,accelerationandoverloadsettings documentchangestoparameters verifydeviceoperation
Task16
Context
Maintainsnonrotatingequipmentandassociatedcontrols.
Nonrotatingequipmentincludestransformers,weldingequipment,heat tracing,electromagnets,linearinductionmotorsandtheirassociated controls.Industrialelectriciansmustinstall,service,troubleshootandrepair thisequipment.
RequiredKnowledge K1 K2 K3 K4 K5 K6 codesandregulationsrelatedtononrotatingequipmentand associatedcontrols types,specificationsandoperationofnonrotatingequipmentand associatedcontrols controls,ratings,capabilitiesandcharacteristicsofnonrotatingequipment andassociatedcontrols installation,inspection,troubleshooting,maintenanceandrepairprocedures andtechniques eventsthatleadtosystemfailure historyofequipmentperformance 57
K7 K8
potentialhazardsrelatedtononrotatingequipmentandassociatedcontrols safetyproceduresrequiredforserviceandrepair
Subtask C16.01
NL yes NS yes
Installsnonrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C16.01.01 C16.01.02 C16.01.03 C16.01.04 C16.01.05 C16.01.06 C16.01.07 selectandusetoolsandequipmentsuchashandandpowertools determinetypeandmodelofnonrotatingequipmentandcontrolsrequired accordingtoapplication assemblecomponentsaccordingtoOEMspecifications identifyhazardsrelatedtononrotatingequipmentandassociatedcontrols anddischargewhenrequired locate,mountandsecurenonrotatingequipmentandassociatedcontrols accordingtoOEMspecifications commissionnonrotatingequipmentandassociatedcontrolsbychecking connections,voltage,currentandsequenceofoperations produceasbuiltdrawings
Subtask C16.02
NL yes NS yes
Servicesnonrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C16.02.01 C16.02.02 C16.02.03 selectandusetoolsandequipmentsuchasdatamonitors,thermalgraphic cameras,airblowersandtemperatureguns completescheduledpreventativemaintenancetaskssuchastighteningloose connectionsandcheckingforexcessiveheat,discolourationandodours identifydamageandfaultsofnonrotatingequipmentandassociated controlsbyobservingconditionssuchasabnormalheatanddiscolouration
58
Subtask C16.03
NL yes NS yes
Troubleshootsnonrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C16.03.01 C16.03.02 C16.03.03 C16.03.04 C16.03.05 selectandusetoolsandequipmentsuchashipottesters,ammeters, megohmmetersandmultimeters performsensoryinspectiontoidentifyabnormalheat,soundsandodours monitorstatusofnonrotatingequipmentusingphasestatusindicators checkvoltageandcurrentlevelsforeachphase performmegohmmetertesttocheckinsulationintegrity
Subtask C16.04
NL yes NS yes
Repairsnonrotatingequipmentandassociatedcontrols.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies C16.04.01 C16.04.02 C16.04.03 C16.04.04 C16.04.05 selectandusetoolsandequipmentsuchasmultimetersandhandtools selectreplacementcomponentsbasedontype,size,capacityand environment determinewhethercomponentsrequirerepairorreplacement replace,adjustandmodifyequipmentwithproceduressuchastightening looseconnectionsandchangingdielectricoil verifysystemoperation
59
BLOCK D
Trends
Related Components (including,butnot limitedto) Toolsand Equipment SeeAppendixA. Batteries,inverters,solidstatedevices,heatsinks,circuitboards, cabling,capacitors,rectifiers,relays,transferswitches,primemovers, meters,bearings,brushes,sliprings.
Task17
Context
Maintainsuninterruptiblepowersupply(UPS)systems.
UPSsystemsareusedinindustrialandinstitutionalbuildingstoprovide constantvoltageforessentialdevicesandtomaintainpowertocritical equipmentduringpoweroutages.Theyensureseamlessandbumpless transferofpower.Industrialelectriciansmustbeabletoinstall,service, troubleshootandrepairUPSsystems.
60
invertersystemfaultindicatorssuchasnooutput,alarms,odour,noiseand breakerfailure batteryfaultssuchaslowbatteryvoltage,bulgingcells,lowelectrolytelevel, incorrectchargingrateandfailedsolidstatedevices eventsthatleadtosystemfailuresuchasambienthightemperatureanddirty ventilationfilters safetyproceduresforUPSsystems historyofequipmentperformance optimumperformanceofsystemandequipment effectsofstaticelectricityonICs potentialhazardsofinstallationandrepairsuchasbatteryacid,hydrogen dischargeandstoredelectricalenergy compatibilityofsolventswithUPScomponents
Subtask D17.01
NL yes NS yes
Installsuninterruptiblepowersupply(UPS)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies D17.01.01 selectandusetoolsandequipmentsuchascompressiontools,torque wrenches,handtools,isolatedtools,powertools,knockoutcutters,hole saws,thermalgraphiccamerasandmultimeters determinelocationandinstallationprocedureofcomponentsbyreadingand interpretingprints,OEMmanualsandcoderequirements selectinterconnectionelectricalfittingsaccordingtoengineereddrawings andbuildingcodes visuallyinspectequipmenttobeinstalledtocheckfordamageandtoensure nameplatedatamatchesengineereddrawings assemblesystemcomponentsaccordingtoOEMspecificationsand engineereddrawings connectsystemcomponentssuchascables,batteries,inverters,alarmsand solarpanelsaccordingtocoderequirements terminateandtorqueallconnectionsaccordingtoOEMspecificationsand coderequirements checkandfillnonmaintenancefreebatterieswithelectrolyte
61
D17.01.09
D17.01.10
Subtask D17.02
NL yes NS yes
Servicesuninterruptiblepowersupply(UPS)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies D17.02.01 D17.02.02 D17.02.03 D17.02.04 D17.02.05 D17.02.06 D17.02.07 D17.02.08 D17.02.09 D17.02.10 D17.02.11 D17.02.12 D17.02.13 D17.02.14 selectandusetoolsandequipmentsuchasfrequencymeters,multimeters, thermalgraphiccameras,hydrometersandtorquewrenches checkandcorrectelectrolytelevelsaccordingtoOEMspecifications checkallbatteryconnectiontorquesaccordingtoOEMspecifications checkandsetsystemvoltagessuchasfloatvoltageandinverteroutput voltageaccordingtoOEMspecifications recordindividualcellvoltages,SGandtemperatures,andcompareto OEMspecifications checkandsetchargingcurrentlimitaccordingtoOEMspecifications changeHVACandinverterfiltersaccordingtoOEMspecifications checkandsetinverteroutputfrequencyaccordingtolocalconditionsand OEMspecifications testalarmsaccordingtoengineereddrawings checkambienttemperatureaccordingtoengineereddrawingsand OEMspecifications testtransferswitchtoensureseamlessandbumplesstransferaccordingto OEMspecifications performbatteryloadtesttocheckdischargetimeaccordingto OEMspecifications identifycalendarlifeofbatteriestoreplaceaccordingtoOEMspecifications verifysystemoperation
62
Subtask D17.03
NL yes NS yes
Troubleshootsuninterruptiblepowersupply(UPS)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies D17.03.01 D17.03.02 D17.03.03 D17.03.04 D17.03.05 D17.03.06 D17.03.07 D17.03.08 selectandusetestequipmentsuchasclamponammeters,multimeters, thermalgraphiccamerasandhydrometers performsensoryinspectiontoverifyambienttemperature,equipment damage,andpresenceofsmokeorunusualsoundsandodours measureinput/output(I/O)voltagesandfrequency checkifbreakersareopened,closedortripped verifypanelmetersareoperational closebreakersinsequencetoverifysystemoperation compareandinterpretprevioushistoricaldatawithdatafrom troubleshooting identifyfaultycomponentssuchasrectifiers,capacitors,batteriesandSCRs
Subtask D17.04
NL yes NS yes
Repairsuninterruptiblepowersupply(UPS)systems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies D17.04.01 selectandusetoolsandequipmentsuchasmultimeters,frequencymeters, hydrometers,scopemeters,thermalgraphiccameras,torquewrenchesand handtools selectandverifyreplacementcomponentaccordingtoOEMspecifications isolateanddeenergizefaultycomponenttoallowsafeaccess removeloadfrombatterybankbeforeremovingfaultycellorinverter dischargecapacitorstoallowsafeaccesstocomponent replaceandcleanfaultycomponentaccordingtoindustrypractices replacecoldsolderconnectionsusingsolderingiron powerupsystemsequentiallytoverifyitsproperoperation 63
D17.04.09 D17.04.10
Task18
Context
Maintainsstandbypowergeneratingsystems.
Standbypowergeneratingsystemsprovideanalternatesourceofenergyfor poweroutages,energymanagementandsafeplantshutdowns.These systemsmayalsobeusedtosupplementutilitypower.Industrialelectricians mustbeabletosafelyinstall,service,troubleshootandrepairthesesystems toensuretheyarereadyforuse.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16 64 codesandregulationsregardingthemaintenanceofstandbypower generatingsystemssuchasforgroundingandbonding types,sizes,ratingsandcapabilitiesofalternatestandbypowergenerating systemssuchasdiesel,naturalgas,solarandwind componentssuchasgenerators,excitersandregulators typesofgeneratorssuchassingleandthreephase inspection,servicing,troubleshooting,repairandcommissioningprocedures andtechniques loadrequirementssuchasvoltage,phaseandkilovoltampere(kVA) automaticandmanualchangeoversystems electricalprotectionforgenerators environmentalissuessuchasfuelcontainment,exhaustandnoise hazardsininstallingstandbypowergeneratingsystems componentsrequiringinspectionsuchasbelts,louversandfilters systemfaultindicatorssuchasnooutputandalarms eventsthatleadtosystemfailure historyofequipmentperformance hazardsofrepairsuchasbatteryacid,storedenergyinbattery,rotating equipmentandaccidentalstartupofsystem controlparameterssuchasspeedandsynchronization
Subtask D18.01
NL yes NS yes
Installsstandbypowergeneratingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies D18.01.01 selectandusetoolsandequipmentsuchascompressiontools,torque wrenches,handtools,insulatedtools,phasemeters,powertools,knockout cutters,holesaws,hoistingandriggingequipment,thermalgraphiccameras andmultimeters determinelocationandinstallationprocedureofcomponentsbyreadingand interpretingprints,OEMmanualsandcoderequirements selectinterconnectionelectricalfittingsaccordingtoengineereddrawings andbuildingcodes visuallyinspectequipmenttobeinstalledtocheckfordamageandtoensure nameplatedatamatchesengineereddrawings assemblesystemcomponentsaccordingtoOEMspecificationsand engineereddrawings connectsystemcomponentssuchascables,batteriesandalarmsaccordingto coderequirements terminateandtorqueallconnectionsaccordingtoOEMspecificationsand coderequirements checkelectrolytelevelandSGofnonmaintenancefreebatteries verifyphasingmatchesutilitypower commissionstandbypowergeneratingsystemtoensurecorrectvoltages, frequencyandoperationoftransferswitch,alarms,isolatingbreakersand ventilationsystem produceasbuiltdrawings
D18.01.11
65
Subtask D18.02
NL yes NS yes
Servicesstandbypowergeneratingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies D18.02.01 selectandusetoolsandequipmentsuchasfrequencymeters,multimeters, scopemeters,thermalgraphiccameras,hydrometers,pressuregauges, pneumatictools,handtools,andtorqueandimpactwrenches checkandcorrectelectrolytelevelsandSGonstartingsystemaccordingto OEMspecifications inspectbatterychargingsystemonstartingsystemtoensureproper currentrate checkfuellevels,fluidlevelsandSGofcoolant,andchangeaccordingto maintenanceschedule cleanandlubricatecomponents changefilterssuchasair,fuelandoilaccordingtoOEMspecifications performsensoryinspectiontorecognizeabnormalheat,sounds,odours, vibrationsandarcingsources,andworn,damagedordefectivecomponents suchasbearings,brushesandsliprings ensureguardsareinplace checkwiringandcableconnections checkandsetgensetoutputvoltageandfrequencyaccordingto OEMspecifications testalarmsaccordingtoengineereddrawings checkambienttemperatureaccordingtoengineereddrawingsand OEMspecifications testtransferswitchtoensuretransferaccordingtoOEMspecifications verifysystemoperation performgeneratorruntestaccordingtoOEMspecifications
66
Subtask D18.03
NL yes NS yes
Troubleshootsstandbypowergeneratingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies D18.03.01 D18.03.02 D18.03.03 D18.03.04 D18.03.05 D18.03.06 D18.03.07 D18.03.08 D18.03.09 D18.03.10 D18.03.11 selectandusetestequipmentsuchasfrequencymeters,multimeters,thermal graphiccamerasandhydrometers performsensoryinspectiontoverifyambienttemperature,equipment damage,andpresenceofsmokeorunusualsoundsandodours reviewandanalyzesequenceofeventsthatledtotheproblemsuchasalarm andfaulthistory,andtrends measureoutputvoltageandfrequencytoensurecorrectoperation checkifbreakersareopened,closedortripped verifypanelmetersareoperational compareandinterpretprevioushistoricaldatawithdatafrom troubleshooting identifyfaultycomponentssuchasbatteries,voltageregulators,exciters, brushes,ignitionsystems,governorsandswitchgear identifyfaultssuchasshortcircuit,excessiveloadsandlooseconnections performtransferfunctionandloadtestsaccordingtoOEMand sitespecifications teststartingsystemaccordingtoOEMandsitespecifications
Subtask D18.04
NL yes NS yes
Repairsstandbypowergeneratingsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
D18.04.02
67
isolateandlockoutstandbysystemtoallowaccessandreplacement ofcomponent replaceandcleanfaultycomponentaccordingtoindustrypractices replacecoldsolderconnectionsusingsolderingiron measureandsetvoltagesandfrequencyaccordingtoOEMand sitespecifications verifyphasingmatchesutilitypowerbeforestandbysystemgoesonline verifystartingsystemafterbatteryreplacementaccordingtoOEMand sitespecifications performbatteryloadtesttocheckdischargetimeaccordingto OEMspecifications powerupsystemsequentiallytoverifyitsproperoperation
68
BLOCK E
Trends
COMMUNICATION SYSTEMS
ThereisagreateruseofInternetbasedinterfacesforcommunication systems. Thereisatrendtowardsmorewirelessalarm,networkcommunication andvideocommunication.
Related Components (including,butnot limitedto) Alarmsystems:Firealarms,gasdetectors,pullstation,smokedetectors, floats,pressuresensors,limitswitches,fasteners,cameras,speakers, heatdetectors,infraredsensors,motionsensors,bells,whistles, annunciators,tamperswitches,endofline(EOL)resistors, ductdetectors Pagingsystems:amplifiers,speakers,microphones,musicsystem, Multimediasystems:cameras,monitors,microphones,screens, projectors,powersupplies. Networksystems:computers,monitors,switches,routers,printers, harddrives,foil,balluns,antennae,jacks,cabinets,patchpanels, modules,conduits,boxes. Toolsand Equipment SeeAppendixA.
Task19
Context
Maintainsalarmsystems.
Alarmsystemsareinstalledtoprovidetimelywarningstoaidinthesafetyof personnel,environmentandfacilities.Theyalsonotifyauthoritiesandcontrol equipmentinemergencysituations.Theyneedtobemaintainedtothe higheststandardstoensurefunctionality.
K5 K6 K7 K8
Subtask E19.01
NL yes NS yes
Installsalarmsystems.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E19.01.01 E19.01.02 E19.01.03 E19.01.04 E19.01.05 E19.01.06 E19.01.07 E19.01.08 selectandusetoolsandequipmentsuchashandtools,multimetersand batterytesters assemblealarmsystemcomponentssuchasdetectors,indicatingdevicesand annunciatorsaccordingtoOEMspecifications locateandmountcomponentsinappropriatelocationsaccordingtodrawings andspecifications configurecircuitryandpanelforalarmsystemssuchasaddressable andconventional connectalarmsystemstocommunicationsystemsfornotificationof authoritiessuchassecuritycompaniesandfiredepartments testandverifyalarmsysteminordertocomplywithcoderequirements recordandsignoffpanelandwiringdocumentation ensurerecordoffloorplanmatchestheinformationinthepanel
70
Subtask E19.02
NL yes NS yes
Servicesalarmsystems.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E19.02.01 E19.02.02 E19.02.03 E19.02.04 E19.02.05 E19.02.06 E19.02.07 E19.02.08 E19.02.09 selectandusetoolsandequipmentsuchashandtools,smokecans,pull stationsandportableheatingelements cleanalarmsystemcomponentsofdusttoensureaccurateoperation checkthatparameterssuchastiming,EOLresistorandcalibrationare operatingaccordingtoOEMspecifications selectreplacementcomponentsbasedontype,compatibility,size, environmentandcapacity replacecomponentsaccordingtomanufacturerspecifiedlifecycleand legislatedrequirements recognizeworn,damagedordefectivecomponents checkwiringandcableconnectionstoensuregoodcontinuity verifysystemsoperationalrequirementssuchasaudibility,visualalarms andconnectionswithsprinklersystem documentfaultsandtestdata
Subtask E19.03
NL yes NS yes
Troubleshootsalarmsystems.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E19.03.01 E19.03.02 E19.03.03 E19.03.04 E19.03.05 selectandusetoolsandequipmentsuchashandtools,multimetersand smokecans isolatefaultsinalarmsystemsbyreferringtopanels determinezone,typeandstatusofalarmsuchastroubleandalarm performsensoryinspectiontoidentifypresenceofconditionssuchassmoke, corrosionandwaterdamage performandinterpretdiagnostictestssuchasinternaldiagnostics,battery tests,powersupplytestsandresistancetests 71
Subtask E19.04
NL yes NS yes
Repairsalarmsystems.
PE yes NB yes QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E19.04.01 E19.04.02 E19.04.03 E19.04.04 E19.04.05 E19.04.06 E19.04.07 E19.04.08 selectandusetoolsandequipmentsuchashandtools,magnets andmultimeters selectreplacementcomponentsbasedoncharacteristicssuchastype,size, environmentandcapacity replacefaultycomponentssuchasbatteries,powersupplies,sensors,remote displaysandpullstations remountcomponentsinpreviouslocations adjustlocationsforalarmsystemsaccordingtocoderegulationsand operationalrequirements reverifyfirealarmsystemoperation verifyalarmsystemoperation documentrepairsperformed
Task20
Context
Maintainspagingsystems.
Pagingsystemsallowforcommunicationbetweenvariouslocations throughoutthefacility.Industrialelectriciansinstall,service,inspect, troubleshootandrepairthesesystemsinordertoensuresecurity,safetyand production.
K6 K7
eventsthatleadtosystemfailure historyofequipmentperformance
Subtask E20.01
NL yes NS yes
Installspagingsystems.
PE yes NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E20.01.01 E20.01.02 E20.01.03 E20.01.04 E20.01.05 E20.01.06 E20.01.07 E20.01.08 selectandusetoolsandequipmentsuchashandtoolsandmultimeters determinewiringtypesandmethodsaccordingtospecificationsandcode assemblepagingsystemcomponentssuchasamplifiersandannunciation equipmentaccordingtoOEMspecifications locateandmountcomponentsinappropriatelocationsaccordingtodrawings andspecifications configurecircuitryandpanelforpagingsystems balanceimpedanceforspeakers connectpagingsystemtoUPS testandverifypagingsysteminordertocomplywithcoderequirements
Subtask E20.02
NL yes NS yes
Servicespagingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E20.02.01 E20.02.02 E20.02.03 E20.02.04 selectandusetoolsandequipmentsuchasdecibel(dB)meters,multimeters andhandtools ensurethatpagingsystemisheardinallrequiredareas selectreplacementcomponentsbasedontype,compatibility,size, environmentandcapacity replacecomponentsaccordingtoOEMspecifications
73
E20.02.05 E20.02.06
checkwiringconnectionstoensuregoodcontinuity documentfaultsandtestdata
Subtask E20.03
NL yes NS yes
Troubleshootspagingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
Subtask E20.04
NL yes NS yes
Repairspagingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E20.04.01 E20.04.02 E20.04.03 E20.04.04 E20.04.05 E20.04.06 selectandusetoolsandequipmentsuchashandtoolsandmultimeters selectreplacementcomponentsbasedoncharacteristicssuchastype,size, environmentandcapacity replacefaultycomponentssuchasspeakers,microphonesandamplifiers adjustlocationsforpagingsystemsaccordingtocoderequirements verifysystemoperation documentrepairsperformed
74
Task21
Context
Maintainsmultimediasystems.(NOTCOMMONCORE)
Multimediasystemsareusedtotransmitaudioandvideoinformation.These systemscanbeusedmainlyforadministrativepurposes(orientation, meetingsandsafety).Theyneedtobemaintainedonaregularbasisby industrialelectricianstoensuretheirfunctionandreliability.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 codesandregulationsregardingtheinstallation,servicingandrepairof multimediasystems typesofmultimediasystemssuchasanaloganddigital componentssuchasspeakers,receivers,screens,projectors,monitors, computersandcameras componentoperation installation,maintenance,inspection,troubleshootingandrepairprocedures andtechniques typesofcablessuchasfibreoptic,coaxial,category5(CAT5),andshielded andunshieldedcables multimediasystemcontrolsandparameters eventsthatleadtosystemfailure historyofequipmentperformance
Subtask E21.01
NL yes NS no
Installsmultimediasystems.(NOTCOMMONCORE)
PE no NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E21.01.01 E21.01.02 E21.01.03 E21.01.04 E21.01.05 75 selectandusetoolsandequipmentsuchashandtools,signalinjectors,colour bargeneratorsandmultimeters determinewiringtypesandmethodsaccordingtospecificationsandcodes locateandmountcomponentssuchasspeakers,receivers,monitorsand screensinappropriatelocationsaccordingtodrawingsandspecifications configurecircuitryformultimediasystems testandverifymultimediasystem
Subtask E21.02
NL yes NS no
Servicesmultimediasystems.(NOTCOMMONCORE)
PE no NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E21.02.01 E21.02.02 E21.02.03 E21.02.04 E21.02.05 E21.02.06 selectandusetoolsandequipmentsuchasmultimeters,analyzersand handtools ensurethatmultimediasystemisheardandseeninallrequiredareas selectreplacementcomponentsbasedontype,compatibility,size, environmentandcapacity replacecomponentsaccordingtoOEMspecifications checkwiringconnectionstoensuregoodcontinuity documentfaultsandtestdata
Subtask E21.03
NL yes NS no
Troubleshootsmultimediasystems.(NOTCOMMONCORE)
PE no NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E21.03.01 E21.03.02 E21.03.03 E21.03.04 selectandusetoolsandequipmentsuchascolourbargenerators,signal injectorsandoscilloscopes isolatefaultsinmultimediasystemsusingproceduressuchasdisconnecting power,replacingcablesandinterchangingcomponents testsystemperformanceandfunctionality checkpowersupplyandwiringconnectionstoensuregoodcontinuity
76
Subtask E21.04
NL yes NS no
Repairsmultimediasystems.(NOTCOMMONCORE)
PE no NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E21.04.01 E21.04.02 E21.04.03 E21.04.04 E21.04.05 E21.04.06 selectandusetoolsandequipmentsuchashandtoolsandmultimeters selectreplacementcomponentsbasedoncharacteristicssuchastype,size, environmentandcapacity replacefaultycomponentssuchaslampsandcables adjustlocationsformultimediasystems verifysystemoperation documentrepairsperformed
Task22
Context
Maintainsnetworksystems.
Networksystemsaredesignedtomanagevoice,videoanddatathrough opticalandcoppercablingaswellaswirelessdatatransfer.Applicationsof networksystemsincludeprocesscontrolandtelecommunications.To minimizedowntime,thesesystemsneedtobemaintainedbyindustrial electricians.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 codesandregulationsregardingthemaintenanceofnetworksystems typesofnetworksystemssuchasEthernet,peertopeerandwireless typesofnetworkcablingsuchasfibreopticandcopper telecommunicationindustrystandardsforfibreopticcables installationconsiderationsforfibreopticnetworkssuchasterminations, location,pullingforces,lubricantsandturningradius componentssuchasmodems,routersandswitches,andtheiroperation installation,maintenance,inspection,troubleshootingandrepair proceduresandtechniquesaccordingtoengineereddrawingsandindustry standardpractices networksystemcontrols,parametersandcapabilities
K8
77
K9 K10
eventsthatleadtosystemfailure historyofequipmentperformance
Subtask E22.01
NL yes NS yes
Installsnetworksystems.
PE yes NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E22.01.01 E22.01.02 E22.01.03 E22.01.04 selectandusetoolsandequipmentsuchastensiongauges,pullingeyes, multimeters,opticalmetersandpunchdowntools selectanduselubricantsaccordingtoOEMspecifications determinewiringtypesandmethodsaccordingtospecificationsandcodes locate,mountandfastennetworksystemcomponentssuchasracks,cabinets andterminationdevicesinappropriatelocationsaccordingtodrawings andspecifications testandverifynetworksystem
E22.01.05
Subtask E22.02
NL yes NS yes
Servicesnetworksystems.
PE yes NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E22.02.01 E22.02.02 E22.02.03 E22.02.04 E22.02.05 E22.02.06 78 selectandusetoolsandequipmentsuchasmultimeters,analyzers, punchdowntoolsandhandtools selectreplacementcomponentsbasedontype,compatibility,size, environmentandcapacity replacecomponentsaccordingtoOEMspecifications checkwiringandfibreopticterminationsusinganalyzers cleandustfromnetworksystemcomponentstoensureaccurateoperation performvisualcheckofcomponentsforfaultssuchassupportstootightand kinksincable
Subtask E22.03
NL yes NS yes
Troubleshootsnetworksystems.
PE yes NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E22.03.01 E22.03.02 E22.03.03 E22.03.04 E22.03.05 E22.03.06 selectandusetoolsandequipmentsuchasanalyzersforcopperandfibre opticcables,punchdowntoolsandhandtools determinedistanceandconnectionintegrityusinganalyzers performintegritycheckofcomponentsforfaultssuchassupportstootight, andkinksandnicksincable checkterminationsandconnectorsaccordingtoindustrystandards checkinterconnectionsforlooseordisconnectedcable verifycomponentscommunicatewitheachother
Subtask E22.04
NL yes NS yes
Repairsnetworksystems.
PE yes NB no QC yes ON yes MB no SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies E22.04.01 E22.04.02 E22.04.03 E22.04.04 selectandusetoolsandequipmentsuchashandtools,analyzersand multimeters selectreplacementcomponentssuchasswitches,routersandtransceivers basedoncharacteristicssuchastype,size,environmentandcapacity replacefaultycomponentssuchascablesandinterconnectcables documentrepairsperformed
79
BLOCK F
Trends
Related Components (including,butnot limitedto) I/Odevices:transducers,transmitters,indicatorlights,timers, converters,photocells,valves,potentiometers,controllers,actuators, solenoids,pushbuttons,horns,buzzers,meters,switches(proximity, selector,limit). Controlsystems:DCSs,PLCs,screens,racks,cards,modules (communication,historyandprocessmanagement),cabling,computers, keyboards,monitors,mouse,HMI. Toolsand Equipment SeeAppendixA.
Task23
Context
Maintainsinput/output(I/O)fielddevices.
I/Ofielddevicesareusedincontrolsystems.Theremaybeanalogordigital (discrete)fielddevices.Industrialelectriciansmustbeabletoinstall,service, troubleshootandrepairthesedevices.
installation,inspection,troubleshooting,servicingandrepairprocedures andtechniques eventsthatleadtosystemfailure historyofequipmentperformance compatibilityofreplacementcomponents typesofconnectors,cablingandshielding typesoflubricantsandanticorrosioncompounds communicationprotocols ladderandlogicdiagrams networking typesofconverterssuchascurrenttopressure(I/P)andtemperatureto pressure(T/P)
Subtask F23.01
NL yes NS yes
Installsinput/output(I/O)fielddevices.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F23.01.01 F23.01.02 F23.01.03 F23.01.04 F23.01.05 F23.01.06 F23.01.07 F23.01.08 F23.01.09 selectandusetoolsandequipmentsuchasmultimeters,calibrators,hand tools,personalcomputersandcommunication/configurationdevices visuallyinspectequipmenttobeinstalledtocheckfordamageandtoensure nameplatedatamatchesengineereddrawings locateanaloganddigitalI/Odevicesbyreadingandinterpretingprints,OEM manualsandcodes connectgrounding,shielding,pipingandwiringaccordingtoOEMandsite specifications,andcodes alignsensors,transmittersandreceiversaccordingtoOEMspecifications ensurepolarityofwiringtofielddevices programandconfiguredevicebysettingprotocolandmappingPLCs accordingtoOEMspecificationsandengineereddrawings ensurecalibrationdataforexternaldevicesmatchesthosepreprogrammed inthePLCs calibrateanalogfielddeviceaccordingtoengineereddrawings
81
F23.01.10 F23.01.11
Subtask F23.02
NL yes NS yes
Servicesinput/output(I/O)fielddevices.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F23.02.01 F23.02.02 F23.02.03 F23.02.04 F23.02.05 F23.02.06 F23.02.07 F23.02.08 selectandusetoolsandequipmentsuchasmultimeters,protocol communicators,calibratorsandnetworkanalyzers detectI/Ofielddevicedefectssuchascorrosion,loosewiringandcabling, mechanicaldamageandwear performsensoryinspectionofcomponentssuchaslimitswitches,photocells andtransmittersfordamage,wearormisalignment reviewandanalyzetrendsfrominputdevicesignalforaspecifiedtime periodtoverifyintegrityofsignal checknetworkprotocolstoverifypropernetworkcommunication checkandsetpowersupplyvoltages changewirelessoutputdevicebatteryaccordingtoOEMspecifications calibrateanaloginputdevices(temperature,speed,flowandpressure) accordingtoengineereddrawings,andOEMandsitespecifications,and recordasfoundandasleft calibrateanalogoutputdevices(current,millivolts,voltsandresistance) accordingtoengineereddrawings,andOEMandsitespecifications,and recordasfoundandasleft performI/O(on/off)testondiscretedevice verifyoperationofI/Ofielddevicesfollowingservice
F23.02.09
F23.02.10 F23.02.11
82
Subtask F23.03
NL yes NS yes
Troubleshootsinput/output(I/O)fielddevices.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F23.03.01 F23.03.02 F23.03.03 F23.03.04 F23.03.05 F23.03.06 F23.03.07 F23.03.08 F23.03.09 F23.03.10 F23.03.11 F23.03.12 selectandusetoolsandequipmentsuchasmultimeters,protocol communicators,calibratorsandnetworkanalyzers performsensoryinspectiontocheckforambienttemperature,abnormalheat, equipmentdamage,andpresenceofcorrosion,smokeorunusualodours verifypresenceofdeviceandwirecontinuityaccordingtoengineered drawings measurevoltage,current,distance,gapsandalignmentofI/Ofielddevices accordingtoengineereddrawings performcalibrationtestonanalogdevicetoverifysignal ensurecalibrationdataforexternaldevicesmatchesthosepreprogrammed inthePLCs performI/O(on/off)testondiscretedevicetoverifyoperation applyForcetooutputdevicefromPLCorDCStoverifyoperationand removeForceuponcompletion reviewandanalyzesignaltrendstoorfromfielddevice isolateI/Odevicestoaidindeterminingthefault puttheloopinManualmodetopreventprocessupsetandputbackto Automaticmodeuponcompletion viewthePLCandDCSprogramorthealertwhileprocessisrunningto determinetheI/Ofault
83
Subtask F23.04
NL yes NS yes
Repairsinput/output(I/O)fielddevices.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F23.04.01 F23.04.02 F23.04.03 F23.04.04 F23.04.05 selectandusetoolsandequipmentsuchasmultimeters,protocol communicators,calibratorsandnetworkanalyzers selectandverifyreplacementcomponentaccordingtoOEMspecifications andengineereddrawings replacefaultywiringandcheckforcontinuityaccordingtolocalregulations andsitespecifications applyForcetooutputdevicefromPLCorDCStobypassalarmsand shutdownswhiledoingthereplacement,andtakeForceoutuponcompletion puttheloopinManualmodetopreventprocessupset,andbypassalarms andshutdownswhiledoingthereplacementandputbacktoAutomatic modeuponcompletion isolatepowerandprocesstothedevicepriortoreplacement cleanandrealignsensortoensureproperoperationoffielddevices replacefielddeviceaccordingtoOEMspecificationsandengineered drawings programandconfiguredevicebysettingprotocolaccordingtoOEM specificationsandengineereddrawings calibrateanaloginputdevices(temperature,speed,flowandpressure) accordingtoengineereddrawings,andOEMandsitespecifications,and recordasfoundandasleft calibrateanalogoutputdevices(current,millivolts,voltsandresistance) accordingtoengineereddrawings,andOEMandsitespecifications,and recordasfoundandasleft performI/O(on/off)testondiscretedeviceafterrepairorreplacement verifyoperationofreplaced,aligned,adjustedandcalibrateddevices
F23.04.11
F23.04.12 F23.04.13
84
Task24
Context
Maintainscontrolsystems.
Controlsystemsareusedtoefficientlyoperateprocessesandassembly operations.Thesesystemsarecontrolledbycomputerandmaybemadeup ofDCSsandPLCs.Theyallowflexibilityinthereconfigurationofprocess variables.Themaintenanceofcontrolsystemsimpliesinstallation,servicing, troubleshooting,repairandoptimizationofPLCsandDCSs.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16 K17 K18 K19 K20 85 codesandregulationsregardingthemaintenanceofcontrolsystems typesandfunctionsofcontrolsystemsandcomponentssuchasmonitors, CPUsandI/Oracks powersupplycriteriasuchastype,sizeandrating maintenance,installation,inspection,troubleshootingandrepairprocedures andtechniques interferencesuchasharmonicsandelectromagneticinterference(EMI),and effectsofstaticelectricityonsystemcomponents groundingandbondingaccordingtoOEMspecificationsandlocal regulations typesofoutputrelayssuchassolidstateandmechanical typesofhardwareusedforconstructingcontrolsystemssuchasraildevices andwirechannels industrialprocessoperationandrequirements causesoffaultssuchasoverloadedpowersupply,faultycommunication cardandboardfailure eventsthatleadtosystemfailure historyofequipmentperformance softwareprogram,andupgradeandbackupprocedures OEMsystemcapabilitiessuchasreplacementofcomponentswhensystem isenergized typesofPLCs PLCcapabilitiessuchasonlineandofflineprogramming capabilities,limitationsandperformanceparametersofsystemsand components typesofcardssuchasanalogI/O,anddigitalI/O softwareandhardwaremodificationprocedures HMIusage,editing,interpretationandmodifications
Subtask F24.01
NL yes NS yes
Installscontrolsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F24.01.01 F24.01.02 F24.01.03 F24.01.04 F24.01.05 F24.01.06 F24.01.07 F24.01.08 F24.01.09 F24.01.10 F24.01.11 F24.01.12 F24.01.13 selectandusetoolsandequipmentsuchasmultimeters,handtools,and torqueandspecialtywrenches visuallyinspectequipmenttobeinstalledtocheckfordamageandtoensure nameplatedatamatchesengineereddrawings locateandmountcomponentssuchaspowersupplies,racksandCPUsby readingandinterpretingprints,OEMmanualsandcoderequirements connectgrounding,shieldingandwiringaccordingtoOEMandsite specifications,andcoderequirements ensurepolarityofwiringtocontrolsystemcomponents powerupthesystemsequentiallytoensureproperfunctionalityofall systemblocks configureCPUbysettingprotocolaccordingtoOEMspecificationsand engineereddrawings ensurecontrolsystems/HMIaccessisenabledviaremoteWebaccess ensurecorrectcommunicationtoallthesystemblockssuchasHMI, IPdevices,analogblocksandI/Oblocks uploadandexecutesystemprogramaccordingtoOEMandengineering specifications,andsystemapplication testfielddevicestoensuretheyreportproperlytoCPUandhavecorrect rangevalues commissioncontrolsystem,andmodifythesettingsifrequired,accordingto processrequirements,engineereddrawingsandsitespecifications produceasbuiltdrawingsandbackupprogramaccordingto sitespecifications
86
Subtask F24.02
NL yes NS yes
Servicescontrolsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F24.02.01 F24.02.02 selectandusetoolsandequipmentsuchashandtoolsandmultimeters performsensoryinspectionofcomponentsforloosewiringandcabling,burn marks,stains,excessiveheat,odours,unusualnoises,evidenceofrodentsand waterdamage check,setandrecordpowersupplyvoltages tightenallterminationsaccordingtoOEMspecifications changepanelfiltersandcleancomponents changeCPUbattery backupprogrambeforeandafterinstallationofupdates installprogramupdatesandensureproperoperationofsystemafterwards monitorfaultlightsandalarms
Subtask F24.03
NL yes NS yes
Troubleshootscontrolsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F24.03.01 F24.03.02 selectandusetoolsandequipmentsuchashandtoolsandmultimeters performsensoryinspectionofcomponentsforloosewiringandcabling,burn marks,stains,excessiveheat,odours,unusualnoises,evidenceofrodentsand waterdamage verifypowersupplyvoltagesandcurrentaccordingtoengineering specifications monitorfaultlightsandalarms inspectfortrippedbreakersandblownfuses checkforcommunicationerrorsbetweenindividualcomponents
87
F24.03.07 F24.03.08 F24.03.09 F24.03.10 F24.03.11 F24.03.12 F24.03.13 F24.03.14 F24.03.15 F24.03.16 F24.03.17
puttheloopinManualmodetopreventprocessupsetandtoaidin determiningthefault,andputbacktoAutomaticmodeuponcompletion verifyreadingsofanaloginputdevicesattheHMIaccordingtoengineering specifications produceanalogoutputsfromcontrolsystemtotestoutputloop performI/O(on/off)testoneachdigitalI/Osequentially applyForcetoI/OtoverifyoperationofcontrolsystemandremoveForce uponcompletion bypassalarmsandshutdownswhileperformingthetroubleshootingand removeuponcompletion reviewandanalyzesignaltrendstoorfromfielddevicetoaidindetermining thefault isolateI/Odevicestoaidindeterminingthefault viewPLCandDCSprogramoralertwhileprocessisrunningtodetermine theI/Ofault verifysoftwareversionstodetermineifupdateisrequired viewprogramminglogiconlinetoidentifypossibleerrors
Subtask F24.04
NL yes NS yes
Repairscontrolsystems.
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F24.04.01 F24.04.02 F24.04.03 F24.04.04 F24.04.05 F24.04.06 selectandusetoolsandequipmentsuchasmultimeters,clamponammeters, handtools,protocolcommunicators,calibratorsandnetworkanalyzers selectandverifyreplacementcomponentaccordingtoOEMspecifications andengineereddrawings replacefaultywiring,andreseatconnectorsandplugsinthecontrolpanel accordingtolocalregulationsandsitespecifications replacecommunicationcomponentsandconnectorsaccordingto engineereddrawings applyForcetooutputdevicefromPLCorDCStoverifyoperationand removeForceoutuponcompletion puttheloopinManualmodetopreventprocessupset,andbypassalarms andshutdownswhiledoingthereplacement,andputbacktoAutomatic modeuponcompletion 88
Subtask F24.05
NL yes NS yes
Optimizesprogrammablelogiccontroller(PLC).
PE yes NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies F24.05.01 F24.05.02 F24.05.03 F24.05.04 F24.05.05 F24.05.06 ensuretheversionoftheOEMmanualmatchestheversionofthe OEMsoftware reviewandmodifyexistingprogramandsystemparameterstomatchthe changesoftheprocess,andtoensureefficiencyofprogram ensuresequentialprogramminglogictominimizescantimeandadd commentstorecordthechanges runprogramintestmode,anduploadandexecuteprogramsrequiredto updatethesystem tunecontrolloopstooptimizeprocess createbackupforeverychangemade
89
BLOCK G
Trends
Toolsand Equipment
Task25
Context
Maintainselectricalcomponentsofheatingandcooling systems.
Industrialelectriciansworkonelectricalcomponentsofheatingandcooling systemsinordertooptimizetheoperationandtoensurethereliabilityofthe system.Industrialelectriciansmustbeabletoinstall,serviceandrepairthese systems.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 codesandregulationsrelatedtotheelectricalcomponentsofheatingand coolingsystems typesofheatingsystemssuchasheatpumps,boilersandresistivetypes typesofcoolingsystemssuchasheatpumps,chillersandexchangers operationofheatingandcoolingsystems buildingapplicationssuchasrefinerylabs,hospitals,foodprocessingplants andcommercialbuildings airflowbalancing buildingconstructionsuchasbrick,woodandcorrugatedpanel systemsizing 90
confinedspaceentryandegressregulations types,ratingsandoperationofelectricalcomponents faultssuchasfailedzoneactuatorsanddamagedelements eventsthatleadtosystemfailure physicalpropertiesandhazardsofrefrigerants historyofequipmentperformance repair,replacement,inspection,calibration,adjustmentandmaintenance proceduresandtechniques compatibilityofreplacementcomponents typesoflubricants
Subtask G25.01
NL yes NS yes
Installselectricalcomponentsofheatingandcoolingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G25.01.01 G25.01.02 G25.01.03 G25.01.04 G25.01.05 G25.01.06 G25.01.07 G25.01.08 selectandusetoolsandequipmentsuchascompressiontools,wirestrippers andpliers ensureproperegressaroundheatingandcoolingsystemaccordingto coderequirements assemblecomponentstobuildingmanagementcontrollersaccordingto OEMspecifications shimandlevelthecabinets terminatecableaccordingtocoderequirements followinstallationproceduresaccordingtoOEMspecificationsand coderequirements performadjustmentssuchassettinghighandlowlimits,fanspeeds andtemperature verifysystemoperation
91
Subtask G25.02
NL yes NS yes
Serviceselectricalcomponentsofheatingandcoolingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G25.02.01 G25.02.02 G25.02.03 G25.02.04 G25.02.05 G25.02.06 G25.02.07 G25.02.08 G25.02.09 G25.02.10 G25.02.11 G25.02.12 G25.02.13 selectandusediagnostictoolsandequipmentsuchashandtools,pressure simulatorsandmultimeters identifyhazardswhenconductinginspectionssuchaslivevoltages, dangerousgases,andrestrictedaccessandegress deenergizesystemfrompowersource testsystemforzeropotentialusingmultimeter performandinterpretdiagnostictestsforconditionssuchasairqualityand humiditylevels selecttoolsandequipmentsuchaspliers,screwdriversandtorquewrenches disassemble/reassemblecomponentsaccordingtoOEMspecifications visuallyinspectcomponentsfordeteriorationsuchascorrosion,loosetorque anddiscolourationusingmethodssuchasthermographyforhotspots identifyabnormalheat,soundsandodours identifycomponentsthatrequirerepairorreplacement cleanandlubricatecomponents performadjustmentssuchassettinghighandlowlimits,fanspeeds andtemperature verifysystemoperation
92
Subtask G25.03
NL yes NS yes
Troubleshootselectricalcomponentsofheatingandcooling systems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G25.03.01 G25.03.02 G25.03.03 G25.03.04 G25.03.05 G25.03.06 G25.03.07 G25.03.08 G25.03.09 identifyhazardswhenconductinginspectionssuchaslivevoltages, dangerousgases,andrestrictedaccessandegress selectandusediagnostictoolsandequipmentsuchasmultimeters,clampon ammetersandmegohmmeters visuallyinspectcomponentsfordeteriorationsuchascorrosion,loosetorque anddiscolouration performandinterpretdiagnostictestsforconditionssuchasairqualityand humiditylevels deenergizesystemfrompowersource isolatefaultsbydeenergizingsourceofenergy testsystemforzeropotentialusingmultimeter identifycomponentsthatrequirerepairorreplacement performadjustmentssuchassettinghighandlowlimits,fanspeeds andtemperature
Subtask G25.04
NL yes NS yes
Repairselectricalcomponentsofheatingandcoolingsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G25.04.01 G25.04.02 G25.04.03 G25.04.04 G25.04.05 identifyhazardswhenconductingrepairssuchaslivevoltages,dangerous gases,andrestrictedaccessandegress selectandusetoolsandequipmentsuchasscrewdrivers,wrenchesandpliers determinewhethercomponentsrequirerepairorreplacement selectreplacementcomponentssuchasrelays,contactorsandfusesaccording toOEMspecificationsandcoderequirements deenergizesystemfrompowersource 93
Task26
Context
Maintainsbuildingautomationsystems.
Buildingautomationsystemsincludeenergy,HVACandsecuritysystems. Industrialelectriciansprogram,performsoftwareupdatesandbackup programs.Theymustbeabletoinstall,serviceandrepairthesesystemsin ordertoensuretheirefficientoperationandreduceunscheduleddisruptions.
RequiredKnowledge K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 codesandregulationsrelatedtobuildingautomationsystems components,operationandtypesofbuildingautomationsystemssuchas energyandsecurity proceduresandtechniquesforservicingbuildingautomationsystems types,ratingsandoperationofelectricalcomponentssuchastemperature sensorsandactuators calibrationdevicessuchasairsupplyandcurrentsourcepotentiometers historyofequipmentperformance calibration,repair,replacement,programming,adjustmentandinspection proceduresandtechniques buildingautomationsystemsandsoftware faultssuchastemperatureimbalanceandunresponsivesystem effectsoffaultsonthesystem eventsthatleadtosystemfailure typesofbuildingsusingautomatedsystemssuchasofficebuildings, manufacturingplantsandhospitals cablingandshielding
94
Subtask G26.01
NL yes NS yes
Installsbuildingautomationsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G26.01.01 G26.01.02 G26.01.03 G26.01.04 G26.01.05 G26.01.06 G26.01.07 G26.01.08 selectandusetoolsandequipmentsuchascompressiontools,wirestrippers andpliers ensureproperegressaroundbuildingautomationsystemaccordingto coderequirements assemblecomponentstobuildingmanagementcontrollersaccordingto OEMspecifications shimandlevelthecabinets terminatecableaccordingtocoderequirements followinstallationproceduresaccordingtoOEMspecificationsand coderequirements performadjustmentssuchassettinghighandlowlimits,fanspeeds andtemperature verifysystemoperation
Subtask G26.02
NL yes NS yes
Servicesbuildingautomationsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G26.02.01 G26.02.02 G26.02.03 G26.02.04 G26.02.05 G26.02.06 interpretbuildingautomationsystemsoftwareinformation selectandusediagnostictoolsandequipmentsuchasammeters,computers andmultimeters identifyhazardswhenconductinginspectionssuchaslivevoltages, dangerousgases,andrestrictedaccessandegress deenergizesystemfrompowersource testsystemforzeropotentialusingmultimeter performandinterpretdiagnostictests 95
Subtask G26.03
NL yes NS yes
Troubleshootsbuildingautomationsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G26.03.01 G26.03.02 G26.03.03 G26.03.04 G26.03.05 G26.03.06 G26.03.07 G26.03.08 identifyhazardswhenconductinginspectionssuchaslivevoltages, dangerousgases,andrestrictedaccessandegress selectandusediagnostictoolsandequipmentsuchasmultimeters, diagnosticequipmentandclamponammeters performsensoryinspectionofcomponentsforconditionssuchascorrosion, discolouration,abnormalheat,soundsandodours performandinterpretdiagnostictests deenergizesystemfrompowersource isolatefaultsbydeenergizingsourceofenergy testsystemforzeropotentialusingmultimeter identifycomponentsthatrequirerepairorreplacement
96
Subtask G26.04
NL yes NS yes
Repairsbuildingautomationsystems.
PE yes NB no QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G26.04.01 G26.04.02 G26.04.03 G26.04.04 G26.04.05 G26.04.06 G26.04.07 G26.04.08 G26.04.09 G26.04.10 identifyhazardswhenconductingrepairssuchaslivevoltages,dangerous gases,andrestrictedaccessandegress selectandusetoolsandequipmentsuchasscrewdrivers,wrenchesandpliers determinewhethercomponentsrequirerepairorreplacement selectreplacementcomponentssuchasrelays,sensorsandfusesaccordingto OEMspecificationsandcoderequirements deenergizesystemfrompowersource testsystemforzeropotentialusingmultimeter disassemble/reassemblecomponentsaccordingtoOEMspecifications replace,adjustandmodifycomponentssuchasrelays,sensorsandfuses cleancomponentsbeforeterminatingtoensuregoodcontactandcontinuity verifyoperationofcomponents
Task27
Context
Maintainsenvironmentalcontrolsystems.
Environmentalcontrolsystemsregulateandmonitoremissions.These emissionsaretypicallyfromindustrialprocessesbutmayalsocomefrom residential,institutionalandcommercialbuildings.Industrialelectricians mustbeabletoinstall,serviceandrepairthesesystemsinordertoensure theirefficientoperationandreduceunscheduleddisruptions.
K3
97
inspection,installation,operation,calibrationandpreventativemaintenance proceduresandschedulesofenvironmentalcontrolsystems hazardssuchaschemicals,gases,ultravioletlightandhighvoltage impactofenvironmentalcontrolsystemshutdown causesoffaults eventsthatleadtosystemfailure diagnosticequipmentsuchasleakdetectors,metersandstackmonitors historyofequipmentperformance responseandcontainmentofenvironmentaldischarge environmentalregulations
Subtask G27.01
NL yes NS yes
Installsenvironmentalcontrolsystems.
PE no NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G27.01.01 G27.01.02 G27.01.03 G27.01.04 G27.01.05 G27.01.06 G27.01.07 G27.01.08 selectandusetoolsandequipmentsuchascompressiontools,wirestrippers andpliers ensureproperegressaroundenvironmentalcontrolsystemaccordingto coderequirements assemblecomponentsofenvironmentalcontrolsystemsaccordingto OEMspecifications shimandlevelthecabinets terminatecableaccordingtocoderequirements followinstallationproceduresaccordingtoOEMspecificationsand coderequirements store,contain,handleanddisposeofhazardousmaterialsaccording toregulations verifysystemoperation
98
Subtask G27.02
NL yes NS yes
Servicesenvironmentalcontrolsystems.
PE no NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G27.02.01 G27.02.02 G27.02.03 G27.02.04 G27.02.05 G27.02.06 G27.02.07 G27.02.08 G27.02.09 G27.02.10 G27.02.11 G27.02.12 G27.02.13 selectandusediagnostictoolsandequipmentsuchasleakdetectors, megohmmetersandmultimeters identifyhazardswhenconductinginspectionssuchaschemicals,ultraviolet light,residueandhighvoltage deenergizesystemfrompowersource testsystemforzeropotentialusingmultimeter performandinterpretdiagnostictestssuchasleakandfaulttests selecttoolsandequipmentsuchaspliers,screwdriversandtorquewrenches disassemble/reassemblecomponentsaccordingtoOEMspecifications performsensoryinspectionofcomponentsforconditionssuchascorrosion, loosetorque,discolouration,andabnormalheat,soundsandodours identifycomponentsthatrequirerepairorreplacement cleanandlubricatecomponents performadjustmentssuchascalibration,andhighandlowlimits store,contain,handleanddisposeofhazardousmaterialsaccording toregulations verifysystemoperation
Subtask G27.03
NL yes NS yes
Troubleshootsenvironmentalcontrolsystems.
PE no NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
disassemble/reassemblecomponentsaccordingtoOEMspecifications performsensoryinspectionofcomponentsforconditionssuchascorrosion, loosetorque,discolouration,andabnormalheat,soundsandodours performandinterpretdiagnostictestsforconditionssuchasairqualityand humiditylevels deenergizesystemfrompowersource isolatefaultsbydeenergizingsourceofenergy testsystemforzeropotentialusingmultimeter identifycomponentsthatrequirerepairorreplacement store,contain,handleanddisposeofhazardousmaterialsaccording toregulations
Subtask G27.04
NL yes NS yes
Repairsenvironmentalcontrolsystems.
PE no NB yes QC yes ON yes MB yes SK ND AB ND BC yes NT ND YT NV NU ND
KeyCompetencies G27.04.01 G27.04.02 G27.04.03 G27.04.04 G27.04.05 G27.04.06 G27.04.07 G27.04.08 G27.04.09 G27.04.10 G27.04.11 identifyhazardswhenconductingrepairssuchaschemicals,ultravioletlight, residueandhighvoltage selectandusetoolsandequipmentsuchasscrewdrivers,wrenchesandpliers disassemble/reassemblecomponentsaccordingtoOEMspecifications determinewhethercomponentsrequirerepairorreplacement selectreplacementcomponentssuchasrelays,contactorsandfusesaccording toOEMspecificationsandcoderequirements deenergizesystemfrompowersource testsystemforzeropotentialusingmultimeter replace,adjustandmodifycomponentssuchaspressureswitches,samplers andparticulateanalyzers cleancomponentsbeforeterminatingtoensuregoodcontactandcontinuity store,contain,handleanddisposeofhazardousmaterialsaccording toregulations verifyoperationofcomponents
100
APPENDICES
APPENDIX A
adjustablewrenches cablesplice/strippertool cabletiegun calculator chisels coaxialstripperandcrimper crimpingpliers drillbits files fishtape flashlight fusepuller groundingset hacksaw hammers hexkeys(metric/imperialorSocietyof AutomotiveEngineers[SAE]) holesaw jumpers knives knockoutcutters linesmanpliers needlenosepliers nutdrivers(metric/imperialorSAE) picks pipebenders
pipethreader pullers punch scraper screwdrivers screwstarter scribe semiconductorextactor sidecutters slidelockpliers socketset(metric/imperialorSAE) splinekeys staticdischargewristbandsand antistaticmats taps(metric/imperialorSAE)anddies tapemeasures telescopicmagnet telescopicmirror torch(butane,propane,oxyacetylene) troublelight voicedatacrimptools voicedatapunchdowntool wirestrippers wrenches
PortablePowerTools circularsaw cutoffsaw drill grinder hammerdrill heatgun holesaw hydrauliccrimper hydraulicknockoutpunch impactgun jigsaw magneticbasedrillpress powerpipebender pipethreadingmachine PVCbender reciprocatingsaw solderingequipment stepdrill wirepuller
103
StationaryPowerTools bandsaw bearingheater beltsander benchgrinder buffer chopsaw drillpress grinder hydraulicpowerunit hydraulicpress partswasher sandblaster threadingmachine undercuttingmachine ElectricalTestandDiagnosticEquipment chartrecorder circuittracer clamponammeter conductivitytester contactresistancemeter frequencymeter Geigercounter groundfaultfinder hipottester instrumentationloopcalibrator insulationresistancetester (megohmmeter/megger) laptopcomputerandsoftware luminmeter(testinglight) multimeter networkanalysers noncontactvoltagetester opticalpowermeterandlightsource opticaltimedomainreflectometer(OTDR) oscilloscope personaldigitalassistant(PDA) phasesequencetester potentialtester pressurecalibrationpump signalgenerator soundmeter temperaturegun thermalgraphiccamera thermalgraphicequipment timedomainreflectometer(TDR) timer voltagetester Wheatstonebridge
MechanicalMeasuringEquipment alignmenttools dialindicators distancemeasuringwheel feelergauges hydrometer Micrometers pressuregauges protractor tachometer torquewrench verniercalipers vibrationsensor(accelerometer,velocity, proximity)
104
Rigging,Tugging,Hoisting,LiftingMaterial articulatedboomlift beamclamps blockandtackle cablepuller(handorelectricpowered) cablepullinggrips(wiremeshgrips) chainfall/comealong hoists liftingeyes platformlift pulley ropes scissorlift shackles slings strainrelief towmotor/forklift
ScaffoldingandAccessEquipment aerialmanlift extensionladder manbaskets portablestairs scaffolds stepladder PersonalProtectiveEquipmentandSafetyEquipment arcflashPPE earprotectors faceshield fallarrestequipment fallrestraintequipment fireretardantclothing gasdetectors groundingstick hardhat harness highvisibilityvests highvoltagegloves
highvoltagetestequipment hotgloves hotpad hotstick kneepads protectiveapron protectivegloves/gauntlets respirator safetyfootwear safetyglasses/goggles SelfContainedBreathingApparatus(SCBA)
105
APPENDIX B
GLOSSARY
arcflash
electricalexplosionthatoccursonliveequipmentresultingfromalow impedanceconnectiontogroundoranothervoltagephaseinanelectrical system.Theintensityoftheblastisdependentontheenergysourceandthe sizeoftheconductors lowimpedancepathobtainedbypermanentlyjoiningallnoncurrent carryingmetalpartstoassureelectricalcontinuityandhavingthecapacity toconductsafelyanycurrentlikelytobeimposedonit afunctionaltestusedonrotatingequipmentthatinitiatesastartto determinea)ifthecorrectequipmentwillturn,b)thedirectionofrotationor c)ifthecorrectequipmentisdeenergized insulatedorsheathed,wireorfibre,carryingcurrentorlight,itcanbe comprisedofoneormoreconductors protectiontechniquetocontrolthecorrosionofametalsurfacebymaking thatsurfacethecathodeofanelectrochemicalcell
bonding
bumptest
cable
cathodic protection
commissionning initialstartupofnewequipmentsystematicallytoOEMspecifications Force manualvirtualbypassthatisplacedincontrolsystemprogramlogic,that canbeOnorOff,itcanbeusedfortroubleshooting,temporaryrepairs, servicinganddiagnostics.AForcewillflagupinthesystemaslongasitis ineffect permanentandcontinuousconductivepathtotheearthwith sufficientampacitytocarryanyfaultcurrentliabletobeimposedonit,and ofasufficientlylowimpedancetolimitthevoltageriseabovegroundand tofacilitatetheoperationoftheprotectivedevicesinthecircuit anyvoltageexceeding750volts,asperCEC anyvoltagefrom31to750volts,asperCEC anelectronicallydeliveredcombinationofmediaincludingvideo,still images,audio,textinsuchawaythatcanbeaccessedinteractively anychanneldesignedforholdingwires,cables,orbusbars,and, unlessotherwisequalifiedbyrulesoftheCEC,thetermincludesconduit (rigid,flexible,metal,nonmetallic)electrical,metallicandnonmetallic tubing,underfloorraceways,cellularfloors,surfaceraceways,wireways, cabletrays,busways,andauxiliarygutters
grounding
106
APPENDIX C
ACRONYMS
AC AECB CAD CAM CAT5 CEC CFL CMMS CPR CPU CSA dB DC DCS EMI EMT EOL GFCI H2S HID HMI HVAC I/O
alternatingcurrent AtomicEnergyControlBoard computerassisteddesign computeraidedmanufacturing category5cable CanadianElectricalCode compactfluorescentlamp computerizedmaintenancemanagementsystem cardiopulmonaryresuscitation centralprocessingunit CanadianStandardsAssociation decibel directcurrent distributedcontrolsystem electromagneticinterference electricalmetallictubing endofline groundfaultcircuitinterrupter hydrogensulfide highintensitydischarge humanmachineinterface heating,ventilation,andairconditioning input/output
107
I/P IC IP kVA LED MCC MSDS OEM OH&S PPE PLC PVC RTD SCR SG SO2 T/P TDG ULC UPS VFD WHMIS
currenttopressure integratedcircuit internetworkingprotocol kilovoltampere lightemittingdiode motorcontrolcentre materialsafetydatasheets originalequipmentmanufacturer OccupationalHealthandSafety personalprotectiveequipment programmablelogiccontroller polyvinylchloride resistancetemperaturedetector siliconcontrolledrectifier specificgravity sulfurdioxide temperaturetopressure transportationofdangerousgoods UnderwritersLaboratoriesofCanada uninterruptiblepowersupply variablefrequencydrive WorkplaceHazardousMaterialsInformationSystem
108
APPENDIX D
BLOCKA
31%
Task2
21%
Task3
26%
Task4
NL NS PE NB QC ON MB SK AB BC NT YT NU % 0 25 30 25 30 25 25 ND ND 15 ND NV ND BLOCKB POWERDISTRIBUTIONANDGENERATINGSYSTEMS
22%
NL NS PE NB QC ON MB SK AB BC NT YT NU % 25 21 20 20 20 14 14 ND ND 22 ND NV ND Task5 Maintainshighvoltagepowerdistributionsystems. NL NS PE NB QC ON MB SK AB BC NT YT NU % 8 0 10 0 10 5 20 ND ND 16 ND NV ND
9%
109
Task6
Task7
Task8
Task9
Task10
NL NS PE NB QC ON MB SK AB BC NT YT NU % 6 0 15 0 10 10 16 ND ND 8 ND NV ND BLOCKC ELECTRICALEQUIPMENT
16%
Task12
NL NS PE NB QC ON MB SK AB BC NT YT NU % 8 10 15 10 20 10 16 ND ND 10 ND NV ND Maintainsprotectiondevices.
12%
Task13
NL NS PE NB QC ON MB SK AB BC NT YT NU % 20 20 10 20 10 15 16 ND ND 15 ND NV ND 110
16%
Task14
Maintainsrotatingequipmentandassociatedcontrols.
NL NS PE NB QC ON MB SK AB BC NT YT NU % 20 20 30 20 20 25 16 ND ND 20 ND NV ND Maintainsdrivesandassociatedcontrols.
Task15
NL NS PE NB QC ON MB SK AB BC NT YT NU % 12 20 20 20 15 25 16 ND ND 15 ND NV ND Maintainsnonrotatingequipmentandassociatedcontrols.
Task16
NL NS PE NB QC ON MB SK AB BC NT YT NU % 20 20 15 20 15 10 16 ND ND 15 ND NV ND BLOCKD EMERGENCYANDSTANDBYSYSTEMS
National Average 9%
53%
Task18
NL NS PE NB QC ON MB SK AB BC NT YT NU % 50 40 20 50 55 60 50 ND ND 50 ND NV ND BLOCKE COMMUNICATIONSYSTEMS
47%
National Average 9%
44%
111
Task20
Maintainspagingsystems.
NL NS PE NB QC ON MB SK AB BC NT YT NU % 10 25 25 0 25 25 50 ND ND 10 ND NV ND Maintainsmultimediasystems.(NOTCOMMONCORE)
Task21
NL NS PE NB QC ON MB SK AB BC NT YT NU % 10 0 0 0 25 5 50 ND ND 10 ND NV NV Maintainsnetworksystems.
Task22
NL NS PE NB QC ON MB SK AB BC NT YT NU % 40 45 50 0 25 30 0 ND ND 30 ND NV ND BLOCKF PROCESSCONTROLSYSTEMS
53%
Task24
NL NS PE NB QC ON MB SK AB BC NT YT NU % 50 45 40 30 50 50 50 ND ND 60 ND NV ND BLOCKG BUILDINGANDENVIRONMENTALCONTROLSYSTEMS
47%
National Average 9%
37%
Task26
Maintainsbuildingautomationsystems.
25% 38%
NL NS PE NB QC ON MB SK AB BC NT YT NU % 20 30 30 0 30 25 34 ND ND 30 ND NV ND Maintainsenvironmentalcontrolsystems.
Task27
NL NS PE NB QC ON MB SK AB BC NT YT NU % 40 30 0 100 40 30 33 ND ND 30 ND NV ND *NCC=Notcommoncore
113
APPENDIX E
PIE CHART*
G 9% F 19%
A 13% B 19%
E 9%
D 9%
C 22%
TITLESOFBLOCKS BLOCKA BLOCKB BLOCKC BLOCKD CommonOccupational Skills PowerDistributionand GeneratingSystems ElectricalEquipment EmergencyandStandby Systems BLOCKE BLOCKF BLOCKG CommunicationSystems ProcessControlSystems BuildingandEnvironmental ControlSystems
114
APPENDIX F
BLOCKS
TASKS
1.Performs safetyrelated functions.
SUBTASKS
1.03Performslock outandtagging procedures.
2.02Usesaccess equipment.
3.Organizes work.
3.05Prepares worksite.
4.02Conducts operationaltests.
115
BLOCKS
TASKS
7.Maintains alternating current(AC) systems.
SUBTASKS
7.03Troubleshoots alternatingcurrent (AC)systems. 7.04Repairs alternating current(AC) systems.
CELECTRICAL EQUIPMENT
12.Maintains lightingsystems.
12.01Installs lightingsystems.
12.02Services lightingsystems.
12.03Troubleshoots lightingsystems.
12.04Repairs lightingsystems.
13.03Troubleshoots protectiondevices.
116
BLOCKS
TASKS
15.Maintains drivesand associated controls.
SUBTASKS
15.03Troubleshoots drivesand associatedcontrols. 15.04Repairs drivesand associated controls.
ECOMMUNICA TIONSYSTEMS
19.Maintains alarmsystems.
19.01Installs alarmsystems.
19.02Services alarmsystems.
19.03Troubleshoots alarmsystems.
19.04Repairs alarmsystems.
20.Maintains pagingsystems.
20.01Installs pagingsystems.
20.02Services pagingsystems.
20.03Troubleshoots pagingsystems.
20.04Repairs pagingsystems.
22.Maintains networksystems.
22.01Installs networksystems.
22.02Services networksystems.
22.03Troubleshoots networksystems.
117
BLOCKS
TASKS
23.Maintains input/output(I/O) fielddevices.
SUBTASKS
23.03Troubleshoots input/output(I/O) fielddevices. 23.04Repairs input/output (I/O)field devices.
24.Maintains controlsystems.
24.01Installs controlsystems.
24.02Services controlsystems.
24.03Troubleshoots controlsystems.
24.04Repairs controlsystems.
118