Contents

3 - Protection components Motor circuit-breakers

TeSys protection components for the motor protection Thermal-magnetic motor circuit-breakers
Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/2 b General characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6 b GV2 ME and GV2 P v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/8 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/22 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/45 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/62

b GV3 ME v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/10 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/26 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/47 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65 b GV7 R v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/11 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/29 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/48 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/65 b GV2 RT v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/6 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/34 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/49 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/64 b Accessories v For circuit-breakers GV2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/59 v For circuit-breakers GV3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55 v For circuit-breakers GV7 . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/57 and 3/61

Magnetic motor circuit-breakers


Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3/4 b GV2 LE and GV2 L v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/12 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/35 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/50 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/70 b GK3 v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/14 v Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/41 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/51 v Dimensions, mounting, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/72 b Accessories v For circuit-breakers GV2 . . . . . . . . . . . . . . . . . . . . . . . . . . pages 3/53 and 3/59 v For circuit-breakers GK3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/55

3/0

Thermal-magnetic circuit-breakers for the protection of control circuits, solenoid valves and transformers
Selection guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/74 b Thermal-magnetic circuit-breaker GB2 for the protection of industrial equipment control circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/76 v Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/77 v References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/80 v Dimensions, schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3/81

3/1

Selection guide

TeSys protection components


Thermal-magnetic motor circuit-breakers

Applications

Protection of motors

Tripping threshold on short-circuit

13 In on average

Standard motor power ratings in AC-3, 415 V

Up to 15 kW

Up to 37 kW

Operational current at 415 V

0.132 A

180 A

Breaking capacity at 415 V (Icu) to IEC 60947-2

10100 kA

35100 kA

Door interlock mechanism

Without

With

Without

Circuit-breaker type

GV2 ME

GV2 P

GV3 ME

Pages

3/45 and 3/46

3/45

3/47

3/2

Protection of motors with high current peak on starting

20 In on average

7.5110 kW

Up to 11 kW

12220 A

0.2523 A

35 and 36 kA

70 kA

15100 kA

With

With

GV7 RE

GV7 RS

GV2 RT

3/48

3/49

3/3

Selection guide

TeSys protection components


Magnetic motor circuit-breakers

Applications

Protection of motors Magnetic circuit-breakers provide short-circuit protection. They must be combined with thermal overload relays to provide motor overload protection.

Tripping threshold on short-circuit

13 In on average

Standard motor power ratings in AC-3, 415 V

Up to 15 kW

Operational current at 415 V

0.432 A

Breaking capacity at 415 V (Icu) to IEC 60947-2

10100 kA

35100 kA

Door interlock mechanism

With

Device type

GV2 LE

GV2 L

Pages

3/50

3/4

614 In

813 In

6.312.5 In

1137 kW

0.37250 kW

4080 A

1.5500 A

35 and 50 kA

25.7 and 150 kA

35.7150 kA

45.7150 kA

GK3 EF

NS 80

NS 100 to NS 250

NS 400 and NS 630

3/51

Please consult the Merlin Gerin catalogue - Low Voltage Distribution

3/5

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers

Environment
Circuit-breaker type Conforming to standards GV2 ME GV2 P IEC 60947-1, 60947-2, 60947-4-1, EN 60204, UL 508, CSA C22-2 n 14, NF C 63-650, 63-120, 79-130, VDE 0113, 0660 GV3 ME IEC 60947-2, 60947-4-1, NF EN, BS EN, DIN EN 60 947. GV7 R IEC 60947-1, 60947-2, 60947-4-1, EN 60947-1, 60947-2, EN 60947-4-1, NF C 63-650, NF C 63-120, 79-130, VDE 0113, 0660 DNV, UL

Product certifications

Protective treatment Degree of protection conforming to IEC 60529 Openmounted In enclosure

CSA, CEBEC, GOST, TSE, UL, BV, GL, LROS , DNV, PTB, EZU, SETI, RINA, TH IP 20 GV2 Mp01: IP 41 GV2 Mp02: IP 55 30 gn -11 ms 5 gn (5150 Hz) C C C C C C m - 40+ 80 - 20+ 60 - 20+ 40 - 20+ 60 - 20+ 40 960 2000 Yes J

CSA, UL, PTB, EZU, GOST, TSE, DNV, LROS, GL, BV, RINA

CSA, UL, LROS

TC IP 20 GV3 CE01: IP 55 22 gn -20 ms 2.5 gn (025 Hz) - 40+ 80 - 20+ 60 - 20+ 60 - 40+ 80 - 20+ 60 - 20+ 40 - 20+ 60 - 20+ 40 960 3000

TC IP 405 with terminal shields 30 gn -11 ms 2.5 gn (25 Hz) - 55+ 95 - 25 + 70 - 25 + 55 (1) 960 2000 Yes 0.5

Shock resistance conforming to IEC 60068-2-27 Vibration resistance conforming to IEC 60068-2-6 Ambient air temperature Storage Operation

Openmounted In enclosure Openmounted In enclosure

Temperature compensation

Flame resistance conforming to IEC 60695-2-1 Maximum operating altitude Suitable for isolation conforming to IEC 60947-1 7-1-6 Resistance to mechanical impact Sensitivity to phase failure

0.5 0.5 0.5 In enclosure: 6 Yes, conforming to IEC 60947-4-1 7-2-1-5-2

Technical characteristics
Circuit-breaker type GV2 ME Conforming to IEC 60947-2 Conforming to IEC 60947-4-1 V V V Hz kV W C.O. 440 V In/2 440 V In C.O. C.O. C.O./h A A AC-3 690 690 600 50/60 6 2.5 100 000 100 000 25 0.16 0.16 32 32 Continuous duty 0.40 23 GV2 P GV2 RT GV3 GV3 GV3 ME06 ME40 ME80 ME25 ME63 A AC-3 690 690 600 (B600) 50/60 6 3 6 8 30 000 30 000 GV7 Rp20... Rp100 A AC-3 690 750 600 50/60 8 5 50 000 50 000 30 000 25 40 63 80 12 100 150 220 8.7 40 000 40 000 20 000 14.5 20 000 20 000 10 000 GV7 Rp150 GV7 Rp220

Utilisation category

Rated operational voltage (Ue) conforming to IEC 60947-2 Rated insulation voltage Conforming to IEC 60947-2 (Ui) Conforming to CSA C22-2 n 14, UL 508 Rated operational frequency conforming to IEC 60947-2 Rated impulse withstand voltage (U imp) conforming to IEC 60947-2 Total power dissipated per pole Mechanical durability (C.O.: Closing - Opening) Electrical durability for AC-3 duty

100 000 50 000 100 000 50 000 25 1.6 25

Duty class (maximum operating rate) Maximum conventional rated thermal current (Ith) conforming to IEC 60947-4-1 Rated duty conforming to IEC 947-4-1

(1) For operation up to 70 C, please consult your Regional Sales Office. References : pages 3/44 to 3/49 Dimensions : pages 3/62 to 3/67 Schemes : pages 3/68 and 3/69

3/6

Characteristics (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers

Mounting characteristics
Operating position Without derating, in relation to normal vertical mounting plane

Side view GV3 ME: preferably vertical

Front view

Connection characteristics
Circuit-breaker type Connection to screw clamp terminals Number of conductors and c.s.a. Solid cable Flexible cable without cable end Flexible cable with cable end Tightening torque Connection to spring terminals Number of conductors and c.s.a. Solid cable Flexible cable without cable end Connection to bars, cables with lugs or bare cables mm 2 mm 2 mm 2 N.m mm 2 mm 2 GV2 ME Min. 2x1 2 x 1.5 2x1 1.7 2 x 1 (1) Max. 2x6 2x6 2x4 1.7 2x6 GV2 P Min. 2x1 2 x 1.5 2x1 1.7 Max. 2x6 2x6 2x4 1.7 GV3 ME06ME20 Min. Max. 2x1 2x6 2x1 2x1 1.7 2x6 2x4 1.7 GV3 ME25ME80 Min. Max. 1 x 2.5 1 x 35 1 x 2.5 1 x 2.5 5 2 x 16 2 x 16 5

2 x 1.5 (1) 2 x 4

Circuit-breaker type Pitch

Without spreaders With spreaders

mm mm mm mm mm

GV7 Rp20...Rp100 35 45 y6 y 25 y 10 M6

GV7 Rp150 35 45 y6 y 25 y 10 M8 15 20 1.5...95 15

GV7 Rp220 35 45 y6 y 25 y 10 M8 15 20 1.5...185 15

Bars or cables with lugs

e L d

Screws Tightening torque Bare cables (copper or aluminium) with connectors Height (h) C.s.a. Tightening torque N.m mm mm 2 N.m

10 20 1.5...95 15

(1) For cross-sections 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.

References : pages 3/44 to 3/49

Dimensions : pages 3/62 to 3/67

Schemes : pages 3/68 and 3/69

3/7

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

Breaking capacity of GV2 ME and GV2 P


Circuit-breaker type GV2 ME 01 07 08 to 06 0.1 2.5 4 to 1.6 g g g g g g 10 14 16 20 21 & 22 23 & 25 50 32 GV2 P 01 07 08 to 06 0.1 2.5 4 to 1.6 g g g g g 10 14 16 20 21 & 22 23 & 25 g g 32

Rating

6.3 10

14

18

32

6.3 10

14

18

32

Breaking capacity conforming to IEC 60947-2

230/240 V

Icu Ics % (1)

kA

g g

g g

g g

g g

50

g g

g g

g g

g g

g g

100 100 g

400/415 V

Icu Ics % (1)

kA

g g

g g

g g

g g

g g

15 50

15 50

15 40

10 50

g g

g g

g g

g g

g g

g g

50 50

50 50

50 50

440 V

Icu Ics % (1)

kA

g g

g g

g g

50

15

8 50

6 50

6 50

g g

g g

g g

g g

g g

50 75

20 75

20 75

20 75

100 100 50

500 V

Icu Ics % (1)

kA

g g

g g

g g

50

10

6 75

4 75

4 75

g g

g g

g g

g g

50

42

10 75

10 75

10 75

100 100 75

100 75

690 V

Icu Ics % (1)

kA

g g

3 75

3 75

3 75

3 75

3 75

3 75

3 75

3 75

g g

100 100 100 100 100 100 100 100

Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2

230/240 V

aM gG

A A

g g

g g

g g

g g

g g

g g

g g

80

80 g

g g

g g

g g

g g

g g

g g

g g

g g

100 100 g

400/415 V

aM gG

A A

g g

g g

g g

g g

g g

63 80

63 80

80

80

g g

g g

g g

g g

g g

100 100 100 125 125 125

100 100 g

440 V

aM gG

A A

g g

g g

g g

50 63

50 63

50 63

50 63

63 80

63 80

g g

g g

g g

g g

g g

50 63

63 80

80

80

100 100

500 V

aM gG

A A

g g

g g

g g

50 63

50 63

50 63

50 63

50 63

50 63

g g

g g

g g

g g

50 63

50 63

50 63

50 63

50 63

690 V

aM gG

A A

g g

16 20

25 32

32 40

32 40

40 50

40 50

40 50

40 50

g g

20 25

25 32

40 50

40 50

50 63

50 63

50 63

50 63

g > 100 kA.


(1) As % of Icu.

R e fe re n c e s : p a g e s 3 /4 4 to 3 /4 9

D im e n s io n s : p a g e s 3 /6 2 to 3 /6 7

S chem es : p a g e s 3 /6 8 a n d 3 /6 9

3/8

Characteristics (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

Breaking capacity of GV2 ME and GV2 P (used in association with current limiter GV1 L3)
Circuit-breaker type Rating A GV2 ME 01 to 06 07 0.1 to 2.5 1.6 g g kA g g kA g g kA g g g g g g g g g g 08 4 10 6.3 14 10 16 14 20 18 21 23 22 25 32 32

Breaking capacity conforming to IEC 60947-2

230/240 V

Icu Ics % (1)

kA

g g g g g g g g

g g g g g g g g

g g g g g g 50 100

g g 100 50 50 75 42 100

g g 100 50 20 75 10 75

g g 100 40 20 75 10 75

g g 100 40 20 75 10 75

g g 100 40 20 75 10 75

400/415 V

Icu Ics % (1)

440 V

Icu Ics % (1)

500 V

Icu Ics % (1)

Circuit-breaker type Rating A

GV2 P 01 to 06 07 0.1 to 2.5 1.6 g g g g g g g g g g 50

08 4

10 6.3

14 10

16 14

20 18

21 23

22 25

32 32

Breaking capacity conforming to IEC 60947-2

230/240 V

Icu Ics % (1)

kA

g g g g g g g g 50

g g g g g g g g 50

g g g g g g 100 50 50

g g g g 100 50 100 50 50

g g g g 100 50 100 50 50

g g g g 100 50 100 50 50

g g g g 100 50 100 50 50

g g g g 100 50 100 50 50

400/415 V

Icu Ics % (1)

kA

g g

440 V

Icu Ics % (1)

kA

g g

500 V

Icu Ics % (1)

kA

g g

690 V (3)

Icu = Ics

kA

Circuit-breaker type Rating A

GV2 ME 01 to 06 07 0.1 2.5 to 1.6 p p p p p p p p

08 4

10 6.3

14 10

16 14

20 18

21 23

22 25

32 32

Cable protection against thermal Minimum c.s.a. 1 mm2 stress in the event of short-circuit protected (PVC insulated copper cables) at 40 C 1.5 mm2 at Isc max. 2.5 mm2 46 mm2

p p p p

y 10 kA y 6 kA (2) y 20 kA y 10 kA (2) p p p p p p

(2) (2) p p

(2) (2) p p

(2) (2) p p

(2) (2) (2) p

g > 100 kA p Cable c.s.a. protected


(1) As % of Icu (2) Cable c.s.a. not protected (3) With limiter LA9 LB920

References : pages 3/44 to 3/49

Dimensions : pages 3/62 to 3/67

Schemes : pages 3/68 and 3/69

3/9

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers GV3 ME

Breaking capacity of GV3 ME


Circuit-breaker type Rating A GV3 ME 06 & 07 08 1.6 & 2.5 4 10 6 14 10 20 16 25 25 40 40 63 63 80 80

Breaking capacity conforming to IEC 60947-2

230/240 V

Icu Ics % (1)

kA

100 100

100 100 100 100 100 100 100 100 4 100

100 100 100 100 100 100 100 100 4 100

100 100 100 100 25 100 8 100 4 100

100 100 100 50 25 60 8 100 4 100

100 100 100 50 25 60 8 100 4 100

100 100 35 50 25 60 8 75 4 75

100 100 35 50 25 60 8 75 4 75

100 100 15 50 10 60 4 100 2 100

400/415 V

Icu Ics % (1)

kA

100 100

440 V

Icu Ics % (1)

kA

100 100

500 V

Icu Ics % (1)

kA

100 100

690 V

Icu Ics % (1)

kA

100 100

Associated fuses, if required if lsc > breaking capacity Icu

230/240 V

aM gG

A A A A A A A A A A

g g g g g g g g g g

g g g g g g g g 40 50

g g g g g g g g 50 63

g g g g 125 160 80 100 80 100

g g g g 160 200 100 125 100 125

g g g g 200 250 125 160 125 160

g g 250 315 250 315 160 200 160 200

g g 315 400 315 400 200 250 200 250

g g 315 400 315 400 200 250 200 250

400/415 V

aM gG

440 V

aM gG

500 V

aM gG

690 V

aM gG

g Fuse not required: breaking capacity Icn > Isc. (1) As % of Icu.

References : pages 3/44 to 3/49

Dimensions : pages 3/62 to 3/67

Schemes : pages 3/68 and 3/69

3/10

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

Breaking capacity of GV7 R


Circuit-breaker type Rating A GV7 RE20RE100 RS20RS100 1220 to 60100 RE150 90150 RS150 90150 RE220 132220 RS220 132220

Breaking capacity conforming to IEC 60947-2

230/240 V

lcu Ics % (1)

kA

85 100

100 100 70 100 65 100 50 100 10 100

85 100 35 100 35 100 30 100 8 100

100 100 70 100 65 100 50 100 10 100

85 100 35 100 35 100 30 100 8 100

100 100 70 100 65 100 50 100 10 100

400/415 V

Icu Ics % (1)

kA

36 100

440 V

Icu Ics % (1)

kA

36 100

500 V

Icu Ics % (1)

kA

18 100

690 V

Icu Ics % (1)

kA

8 100

Cable protection against thermal stress in the event of short-circuit (PVC insulated copper cables)

Minimum c.s.a. 4 mm 2 protected at 40 C 6 mm 2 at Isc max. 1050 mm2

y 6 kA p p

y 6 kA y 25 kA p

(2) (2) p

(2) (2) p

(2) (2) p

(2) (2) p

p Cable c.s.a. protected.


(1) As % of Icu. (2) Cable c.s.a. not protected.

References : pages 3/44 to 3/49

Dimensions : pages 3/62 to 3/67

Schemes : pages 3/68 and 3/69

3/11

Characteristics

TeSys protection components


Magnetic motor circuit-breakers GV2 LE and GV2 L

Environment
Type Conforming to standards Product certifications Protective treatment Shock resistance Vibration resistance Ambient air temperature Conforming to IEC 60068-2-27 Conforming to IEC 60068-2-6 Storage Operation Flame resistance Conforming to IEC 60695-2-1 C C C m GV2 LE GV2 L IEC 60947-1, 60947-2, EN 60204, NF C 63-650, NF C63-120, 79-130, VDE 0113, 0660, UL 1077. UL, CSA BV, GL, LROS, DNV, RINA, UL, CSA TH TH 30 gn 5 gn (5 to 150 Hz) - 40+ 80 - 20+ 60 960 2000 30 gn 5 gn (5 to 150 Hz) - 40+ 80 - 20+ 60 960 2000

Maximum operating altitude Operating position

Cabling Number of conductors and c.s.a.

Solid cable

mm2

Max. 2x6 2x6 2x4 Yes

Min. 2x1 2 x 1.5 2x1

Max. 2x6 2x6 2x4 Yes 1.7 0.5 A AC-3 690 690 50/60 6 1.8 100 000 100 000 40 Continuous duty

Min. 2x1 2 x 1.5 2x1

Flexible cable without cable end mm2 Flexible cable with cable end Suitable for isolation Tightening torque Resistance to mechanical impact Utilisation category Conforming to IEC 60947-2 Conforming to IEC 60947-4-1 Rated operational voltage (Ue) Rated insulation voltage (Ui) Rated operational frequency Conforming to IEC 60947-2 Conforming to IEC 60947-2 Conforming to IEC 60947-2 V V Hz kV W C.O. For AC-3 duty C.O. C.O./h Conforming to IEC 60947-4-1 Conforming to IEC 60947-1 7-1-6 N.m J mm2

1.7 0.5 A AC-3 690 690 50/60 6 1.8 100 000 100 000 40 Continuous duty

Rated impulse withstand Conforming to IEC 60947-2 voltage (U imp) Total power dissipated per pole Mechanical durability (C.O. : Closing - Opening) Electrical durability Duty class (maximum operating rate) Rated duty

References : pages 3/50 and 3/51

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/12

Characteristics (continued)

TeSys protection components


Magnetic motor circuit-breakers GV2 LE and GV2 L

Breaking capacity of GV2 LE and GV2 L


Type GV2 LE 03 07 08 10 14 to 06 0.4 2.5 4 6,3 10 to 1.6 g g g g g g kA g g kA g g kA g g kA g g A A A A A A A A A A kA kA g g g g g g g g g g p p p p g g g g g g g 3 g g g g g g g 3 g g g 50 g g g 15 16 20 22 32 GV2 L 03 07 08 to 06 0.4 2.5 4 to 1 g g g g g g g g g g 4 g g g g g g g 4 10 14 16 20 22 32

Rating

14 18 25

32

6,3 10

14

18

25

32

Breaking capacity conforming to IEC 60947-2

230/240 V

Icu Ics % (1)

kA

g g

g g

50

50

g g g g g g g g 4

g g g g 20 75 10

g g 50 50 20 75 10

g g 50 50 20 75 10 75 4

50

50

100 100 g 10 50 6 50 4 75 3 75 80 g g g g g g g g g

100 100 50 50 20 75 10 75 4 50 50 20 75 10 75 4

400/415 V

Icu Ics % (1)

15 15 15 50 50 40 8 8 6

440 V

Icu Ics % (1)

100 100 50 50 50 50 10 6 6 4

500 V

Icu Ics % (1)

100 100 75 75 75 3 3 75 g g g g 50 63 50 63 32 40 3 3 3

100 75 4 4

690 V

Icu Ics % (1)

75 75 75 g g g g g g g g g g g g g g g g g g g g 50 63 50 63

75 75 75 g g g g 80

100 100 100 100 100 100 100 100 g g g g g g g g 20 25 p p p p g g g g g g g g 25 32 p p p p g g g g g g g g 40 50 g g g g 50 63 50 63 40 50 g g 80 g g 100 100 125 125

Associated fuses (if required) if Isc > breaking capacity Icu conforming to IEC 60947-2 amendment 1

230/240 V

aM gG

100 100 g 80 g

400/415 V

aM gG

63 63 80

100 100 100

80 80 100 100 g 50 50 63 63 63 80 50 50 50 63 63 63 40 40 40 50 50 50 63 80 50 63 40 50 g g g g g g

100 125 125 125 63 80 50 63 50 63 80 80 80

440 V

aM gG

100 100 100 50 63 50 63 50 63 50 63 50 63 50 63

500 V

aM gG

690 V

aM gG

16 25 32 20 32 40 p p p p p p p p

Cable protection against thermal 1 mm 2 stress in the event of short-circuit (PVC insulated copper cables) 1.5 mm2 Minimum c.s.a. protected at 40 C and at Isc max. 2.5 mm2 46 mm2

y 10 y 6 (2) (2) (2) (2) p y 20 y 10 (2) (2) (2) (2) p p p p p p p p p p p (2) p p p

y 10 y 6 (2) (2) (2) (2) y 20 y 10 (2) (2) (2) (2) p p p p p p p p p p (2) p

g > 100 kA pCable c.s.a. protected


(1) As % of Icu (2) Cable c.s.a. not protected

References : pages 3/50 and 3/51

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/13

Characteristics

TeSys protection components


Magnetic motor circuit-breakers GK3

Environment
Conforming to standards Protective treatment Degree of protection Shock resistance Vibration resistance Flame resistance Ambient air temperature Conforming to IEC 60529 Conforming to IEC 60068-2-27 Conforming to IEC 60068-2-6 Conforming to IEC 60695-2-1 Storage Operation IEC 60947-2. EN 60-204 TC GK3 EF basic unit: IP 20 22 gn for 20 ms 2.5 gn (025 Hz) Conforms for 960 C C C m - 40+ 80 - 20 + 70 open-mounted 3000 Any Solid cable Flexible cable without cable end Flexible cable with cable end Tightening torque Suitable for isolation mm2 mm2 mm2 N.m 1 x 2.5 to 35 conductor 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors 5 Yes, conforming to IEC 60947-17-1-6

Maximum operating altitude Operating position Cabling

Technical characteristics
Rated insulation voltage (Ui) Rated impulse withstand voltage (U imp) Rated operational voltage (Ue) Rated operational frequency Conforming to IEC 60947-2 Conforming to IEC 60947-2 Conforming to IEC 60947-2 V kV V Hz C.O. C.O. C.O./h 750 10 690 5060 1500 20 000 40 About 13 times the rating of the GK3 EF selected (non adjustable threshold) Conforming to IEC 60947-2 A

Electrical durability for AC-23/400 V duty (C.O.: Closing - Opening) Mechanical durability Maximum operating rate Operating threshold of magnetic trips Utilisation category

References : pages 3/50 and 3/51

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/14

Characteristics (continued)

TeSys protection components


Magnetic motor circuit-breakers GK3

Type Breaking capacity of the circuit-breaker only or of the circuit-breaker combined with a thermal overload relay

230/240 V

Icu Ics % (1)

kA

GK3 EF40 100 20

GK3 EF65 50 40 35 25 25 30 15 30 6 50 200 315 200 250 160 250 160 200 125 160

GK3 EF80 50 40 35 25 25 30 15 30 6 50 200 315 200 250 160 250 160 200 125 160

400/415 V

Icu Ics % (1)

kA

50 30

440 V

Icu Ics % (1)

kA

30 30

500 V

Icu Ics % (1)

kA

20 30

690 V

Icu Ics % (1)

kA

6 60

Associated fuses (if required) for use with circuit-breaker only or circuit-breaker combined with a thermal overload relay if lsc > breaking capacity

230/240 V

aM gG

A A A A A A A A A A

160 250 160 200 160 200 125 160 100 125

400/415 V

aM gG

440 V

aM gG

500 V

aM gG

690 V

aM gG

Use of circuit-breakers without fuses

Minimum cable length (in metres) limiting the maximum short-circuit current to 35 kA maximum, so enabling breakers GK3 EF to be used without fuses mm 2 50 kA 45 kA 40 kA 37 kA m m m m y 25 5 5 5 5 35 6 5 5 5 50 8 7 5 5 70 10 8 5 5 95 13 10 8 5 120 15 12 9 5

Cable c.s.a. Isc (rms) 3-phase, incoming (Ue = 400 V)

(1) As % of Icu

References : pages 3/50 and 3/51

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/15

Characteristics

TeSys protection components


Thermal-magnetic and magnetic motor circuit-breakers GV2
Auxiliary contacts

Type of contacts Rated insulation voltage (Ui) (associated insulation coordination) Conventional thermal current (Ith) Conforming to IEC 60947-1 V

Instantaneous auxiliary GV AN, GV AD 690 600 6 5 100 000 AC-15/100 000 C.O.

Conforming to CSA C22-2 n 14 V and UL 508 Conforming to IEC 60947-5-1 A Conforming to CSA C22-2 n 14 A and UL 508 C.O.

Fault signalling Instantaneous GV AD, GV AM11 (1) auxiliary GV AE 690 250 (690 in relation to main circuit) 300 300 2.5 1 1000 AC-14/1000 C.O. 48 48 2.5 1 100 000 AC-15/100 000 C.O. 48 60 110 230 127 240 120 120 1.27 2.4 0.5

Mechanical durability (C.O. : Closing - Opening) Operational power and current conforming to IEC 60947-5-1 a.c. operation Rated operational voltage (Ue) Operational power, normal conditions Occasional breaking and making capacities, abnormal conditions Rated operational current (Ie) Operational power and current conforming to IEC 60947-5-1 d.c. operation Rated operational voltage (Ue) Operational power, normal conditions Occasional breaking and making capacities, abnormal conditions Rated operational current (Ie) Low level switching reliability of contact Minimum operational conditions d.c. operation Short-circuit protection Cabling, screw clamp terminals Number of conductors Solid cable Flexible cable without cable end Flexible cable with cable end Tightening torque

V VA kVA A

48

110 230 380 440 500 690 24 127 240 415 300 500 720 850 650 500 400 36 3 6 7 4.5 13 3.3 15 2.2 13 1.5 12 1 9 0.6

110 230 24 127 240 72 72 48

0.22 0.3 1.5 1

0.45 0.45 0.48 0.6 0.5 0.3 2

1.25 1

DC-13/100 000 C.O. V W W A 24 110 240 (2) 140 240 180 140 120 240 360 240 210 180 6 5 3 1.3 0.5 48 60

DC-13/1000 C.O. 24 24 48 15 60 9 50

DC-13/100 000 C.O. 24 24 48 15 60 9 50

100 50 1 0.3

100 50 1 0.3

0.15

0.15

V mA

mm2 mm2 mm2 N.m

GV A: number of failures for n million operating cycles (17 V-5 mA): = 10-6 17 5 By GB2 CBpp circuit-breaker (rating according to operational GB2 CB06 or current for Ue y 415 V) or by gG fuse 10 A max gG fuse, 10 A max 1 2 12.5 12.5 0.752.5 0.752.5 0.751.5 0.751.5 1.4 max 1.4 max GV AN only 0.752.5
0

Cabling, spring terminals Flexible cable without cable end mm2 Operation of instantaneous auxiliary contacts
Power pole

0.752.5
1

0.751.5 Operation of fault signalling contacts

F F F O F O F F F O F O
Contact open Contact closed

GV AM11 Change of state following tripping on short-circuit. GV AD10pp and GV AD01pp Change of state following tripping on short-circuit. overload or undervoltage.

(1) For application example of fault signalling contact and short-circuit signalling contact, see page 3/68. (2) Add an RC circuit type LA4 D to the load terminals, see page 24511/5.

References : page 3/53

Dimensions, schemes : pages 3/62 to 3/73

3/16

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers GV3 ME
Auxiliary contacts

Type of contacts Rated insulation voltage (Ui) Conforming to IEC 60947-1 V

Instantaneous auxiliary contacts GV3 A01A07 690 600 (B600) 6 5 (B600) 100 000 48 110 220 380 127 240 415 AC-11/100 000 C.O. 350 500 4 6 24 12 4.5 48 800 20 3.5 60 850 20 2.2 110 440 500 690

Fault signalling contacts GV3 A08 and A09 690 600 (B600) 6 5 (B600) 1000 48 110 220 380 127 240 415 AC-11/1000 C.O. 240 460 2.4 5 24 8 3.6 48 800 12 3.5 60 850 15 2.2 110 440 500 690

Conventional rated thermal current (Ith)

Conforming to CSA C22-2 n 14, V UL 508 Conforming to IEC 60947-5-1 A Conforming to CSA C22-2 n 14, A UL 508 C.O. Rated operational voltage (Ue) Operational power V

Mechanical durability (C.O.: Closing - Opening) Operational power and current conforming to IEC 60947-5-1 a.c. operation

VA Occasional breaking and making kVA capacities A Operational current (Ie) Operational power and current conforming to IEC 60947-5-1 d.c. operation Rated operational voltage (Ue) Operational power V

700 15 1.5 220

700 15 1.5

400 10 0.6

450 12 1 220

450 12 1

200 8 0.3

DC-11/100 000 C.O. W 180 240 240 360 6 5 180 240 3 140 210 1.3 120 180 0.5

DC-11/1000 C.O. 120 120 180 180 5 2.5 90 135 1.5 70 105 0.7 60 90 0.3

Occasional breaking and making capacities Operational current (Ie) Short-circuit protection Cabling Number of conductors Solid cable

W A

By GB2 CB08 circuit-breaker or gG fuse, 6A max 1 mm 2 12.5 0.752.5 0.752.5 2 12.5 0.752.5 0.751.5 GV3 A08 and A09 change state following tripping on short-circuit or overload

Flexible cable without cable end mm 2 Flexible cable with cable end Contact operation mm 2

0
Power pole

GV3 A01, A07 O F GV3 A02 F F O F F F F F F F


Contact open Contact closed

GV3 A03

GV3 A05

GV3 A06

References : page 3/55

Dimensions, schemes : pages 3/62 to 3/73

3/17

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7
Auxiliary contacts

Auxiliary contact characteristics


Type of contacts Rated insulation voltage (Ui) (associated insulation coordination) Conventional thermal current (Ith) Mechanical durability (C.O.: Closing - Opening) Operational current conforming to IEC 60947-5-1 a.c. operation Conforming to IEC 60947-1 V GV7 AE11 690 GV7 AB11 690

Conforming to IEC 60947-5-1

A C.O.

6 50 000 AC-12 or AC-15. 50 000 C.O. 24 48 110 230/ 380/ 440 240 415 6 6 6 6 6 6 6 6 5 4 3 3

6 50 000 AC-12 or AC-15. 50 000 C.O. 24 48 110 230/ 380/ 440 240 415 5 5 5 5 5 5 5 5 4 3 2.5 2.5

Rated operational voltage (Ue) Rated operational current (Ie)

V AC-12 AC-15 A A

690 6 0.1

690 5 0.1

Operational current conforming to IEC 60947-5-1 d.c. operation

Rated operational voltage (Ue) Rated operational current (Ie)

V DC-12 DC-14 A A V mA

DC-12 or DC-14. 50 000 C.O. 24 48 110 2.5 1 17 5 2.5 0.2 0.8 0.5

250 0.3

DC-12 or DC-14. 50 000 C.O. 24 48 110 2 2 0.1 0.5 0.25

250

0.03 0.5 12 5

Minimum operational conditions d.c. operation Short-circuit protection Cabling Solid cable

mm2

By GB2 CBpp circuit-breaker (rating according to operational current for Ue y 415 V) or gG fuse, 10 A max. 1 x 1.5 conductor 1 x 1.5 conductor 1 x 1.5 conductor 1 x 1.5 conductor 1 x 1.5 conductor 1 x 1.5 conductor

Flexible cable without cable end mm2 Flexible cable with cable end mm2

References : page 3/57

Dimensions, schemes : pages 3/62 to 3/73

3/18

Characteristics

TeSys protection components


Magnetic motor circuit-breakers GK3

Characteristics of Start-Stop and fault signalling contacts


Rated insulation Conforming to IEC 60947-1 voltage (Ui) Rated operational Conforming to IEC 60947-1 voltage (Ue) Conventional thermal Conforming to IEC 60947-5-1 current (Ith) Operational power and current conforming to IEC 60947-5-1 Rated operational voltage (Ue) a.c. operation (C.O.: Closing - Opening) Operational power Occasional breaking and making capacities Rated operational current (Ie) Operational power and current conforming to IEC 60947-5-1 Rated operational voltage (Ue) d.c. operation (C.O.: Closing - Opening) Operational power Occasional breaking and making capacities Rated operational current (Ie) Short-circuit protection Cabling Conforming to IEC 60947-5-1 Solid cable mm 2 V V A 500 500 6 AC-15. 20 000 C.O. 48 110/127 360 4000 6 500 12 000 4.5

V VA VA A

220/240 800 20 000 3.5

380/415 850 20 000 2.2

440 700 15 000 1.5

500 700 15 000 1.5

V W W A

DC-13. 1000 C.O. 24 48 180 240 6 240 280 5

60 180 240 3

110 140 210 1.3

220 120 180 0.5

By GB2 CB08 circuit-breaker or gG fuse, 6A max 1 x 14 conductor 1 x 2.5 conductor 1 x 12.5 conductor or 2 x 12.5 conductors 0.8

Flexible cable without cable end mm 2 Flexible cable with cable end Tightening torque mm 2 N.m

References : page 3/55

Dimensions, schemes : pages 3/62 to 3/73

3/19

Characteristics

TeSys protection components


Thermal-magnetic motor circuit-breakers
Electric trips

Characteristics of electric trips


Type of circuit-breaker Type of trip Rated insulation voltage (Ui) Conforming to IEC 60947-1 V GV2 ME, GV2 P GV AU GV AX (1) GV AS 690 500 690 600 600 0.7 1.1 Un 0.75 0.2 Un 14 10.5 5 1.6 GV3 ME GV3 B 690 GV3 D 690 GV7 R GV7 AU 690 GV7 AS 690 600 0.7 1.1 Un 0.2 0.75 Ue

Operational voltage Drop-out voltage Inrush consumption

Conforming to CSA C22-2 n 14, V UL 508 V Conforming to IEC 60947-1 V a c VA W VA W

600 (B600) 600 (B600) 600 0.81.1 Un 0.70.35 Un 12 7 7 2.5 0.85 1.1 Un 0.35 0.7 Ue < 10 <5 <5 <5

0.851.1 Un 0.70.35 Un 12 8 3.5 1.1

Sealed consumption

a c

3
Operating time On-load factor Cabling Number of conductors Solid cable

Conforming to IEC 60947-1 ms

From the moment the voltage reaches its operational value until opening of the circuit-breaker. 1015 10 15 < 50 100 % 1 or 2 100 % 1 or 2 12.5 0.752.5 0.752.5 1.2 100 % 1 1.5 1.5 1 1.2

mm2

12.5 0.752.5 0.751.5 1.4 max 100 000

Flexible cable without cable end mm2 Flexible cable with cable end Tightening torque Mechanical durability (C.O.: Closing - Opening) mm2 N.m C.O.

50 % of the mechanical durability of the circuit-breaker (1) Wiring scheme of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME only, see page 3/68.

References : pages 3/53 to 3/57

Dimensions : pages 3/62 to 3/67

Schemes : pages 3/68 and 3/69

3/20

Characteristics

TeSys protection components


Thermal-magnetic and magnetic motor circuit-breakers GV2
Accessories

Characteristics of 3-pole busbars GV2 Gppp


Rated insulation voltage (Ui) Conventional thermal current (Ith) Permissible peak current ( I peak) Permissible thermal limit (I2 t) Degree of protection Conforming to IEC 60947-1 Conforming to IEC 60439-1 V A kA kA2 s Conforming to IEC 60529 690 63 11 104 IP 20

Characteristics of terminal blocks GV2 G05 and GV1 G09


Rated insulation voltage (Ui) Conventional thermal current (Ith) Degree of protection Cabling Conforming to IEC 60947-1 Conforming to IEC 60439-1 Conforming to IEC 60529 Solid cable mm 2 V A 690 63 IP 20 1 x 1.5 to 25 conductor or 2 x 1.5 to 10 conductors 1 x 1.5 to 25 conductor or 2 x 2.5 to 10 conductors 1 x 1.5 to 16 conductor or 2 x 1.5 to 4 conductors 2.2 1.7

Flexible cable without cable end mm 2 Flexible cable with cable end Tightening torque Connector Screw clamp mm 2 N.m N.m

Characteristics of current limiters (GV2 ME and GV2 P)


Type Rated insulation voltage (Ui) Conventional thermal current (Ith) Operating threshold Cabling Solid cable mm 2 Conforming to IEC 60947-1 Conforming to IEC 60947-1 rms current V A A GV1 L3 690 63 1500 (non adjustable threshold) 1 conductor 1.525 1.525 1.516 2.2 2 conductors 1.510 2.510 1.5 4 LA9 LB920 690 63 1000 (non adjustable threshold) 1 conductor 1.525 1.525 1.516 2 conductors 1.510 1.510 1.5 4

Flexible cable without cable end mm 2 Flexible cable with cable end Tightening torque mm 2 N.m

References : pages 3/53 and 3/59

Dimensions, schemes : pages 3/62 to 3/73

3/21

Curves

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

Thermal-magnetic tripping curves for GV2 ME and GV2 P


Average operating time at 20 C related to multiples of the setting current:
Time (s)

10 000

1000

100

1
10

2 3

0,1

0,01

0,001

1,5

10

100
x the setting current (Ir)

1 3 poles from cold state 2 2 poles from cold state 3 3 poles from hot state

References : pages 3/45 and 3/46

Dimensions : pages 3/62 to 3/64

Schemes : page 3/68

3/22

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

Current limitation on short-circuit for GV2 ME and GV2 P (3-phase 400/415 V)


Dynamic stress I peak = f (prospective Isc) at 1.05 Ue = 435 V
Limited peak current (kA)

100

1
=0 .25

0. 3

2 3 4 5 6

10

0.7

0.

7 8

0.

0.

9
= co s 0.9 5

10

11

0,1 0,1

10

15 (12)

100 Prospective Isc (kA)

1 2 3 4 5 6 7 8 9 10 11 12

Maximum peak current 24-32 A 20-25 A 17-23 A 13-18 A 9-14 A 6-10 A 4-6.3 A 2.5-4 A 1.6-2.5 A 1-1.6 A Limit of rated ultimate breaking capacity on short-circuit of GV2 ME (14, 18, 23 and 25 A ratings)

References : pages 3/45 and 3/46

Dimensions : pages 3/62 to 3/64

Schemes : page 3/68

3/23

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME

Thermal limit on short-circuit for GV2 ME


Thermal limit in kA2s in the magnetic operating zone Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100 1

2 3 4 5 6 7

10

9
1

10

0,1

0,01 0,1

10

100 Prospective Isc (kA)

1 24-32 A 2 20-25 A 3 17-23 A 4 13-18 A 5 9-14 A 6 6-10 A 7 4-6.3 A 8 2.5-4 A 9 1.6-2.5 A 10 1-1.6 A

References : pages 3/45 and 3/46

Dimensions : pages 3/62 to 3/64

Schemes : page 3/68

3/24

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 P

Thermal limit on short-circuit for GV2 P


Thermal limit in kA2s in the magnetic operating zone Sum of I 2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100

1 2 3 4 5 6
10

3
7

0,1

0,01 0,1

10

100 Prospective Isc (kA)

1 1 2 3 4 5 6 7 8 9

24 -32 A 20-25 A 17-23 A 13-18 A 9-14 A 6-10 A 4-6.3 A 2.5-4 A 1.6-2.5 A 1-1.6 A

References : pages 3/45 and 3/46

Dimensions : pages 3/62 to 3/64

Schemes : page 3/68

3/25

Curves

TeSys protection components


Thermal-magnetic motor circuit-breakers GV3 ME

Thermal-magnetic tripping curves


Average operating time at 20 C related to multiples of the setting current:
Time (s)

10 000

1000

100

1
10

2 4

0,1

0,01

0,001

10

100
x the setting current (Ir)

1 2 3 4

3 poles from 3 poles from 3 poles from 3 poles from

cold state, 1.616 A rating hot state, 1.616 A rating cold state, 2580 A rating hot state, 2580 A rating

References : page 3/47

Dimensions : page 3/65

Schemes : page 3/69

3/26

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV3 ME

Current limitation on short-circuit (3-phase 400/415 V)


Dynamic stress I peak = f (prospective Isc) at 1.05 Ue = 435 V
Limited peak current (kA)

100

1
=0 .25

2
0. 3 =

3 4

0.

10

5 6 7

0. 8

0.7

8
9 = 0.

10

11

0,1 0,1

10

15

100 Prospective Isc (kA)

1 2 3 4 5 6 7 8 9 10 11

Maximum peak current 56-80 A 40-63 A 25-40 A 16-25 A 10-16 A 6-10 A 4-6 A 2.5-4 A 1.6-2.5 A 1-1.6 A

References : page 3/47

Dimensions : page 3/65

Schemes : page 3/69

3/27

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV3 ME

Thermal limit on short-circuit


Thermal limit in kA2s in the magnetic operating zone Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100

3
10

1 2 3 4 5

0,1 0,1

10

15

100 Prospective Isc (kA)

1 2 3 4 5 6 7 8 9

56 -80 A 40-63 A 25-40 A 16-25 A 10-16 A 6-10 A 4-6 A 2.5-4 A 1.6-2.5 A

References : page 3/47

Dimensions : page 3/65

Schemes : page 3/69

3/28

Curves

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

Thermal-magnetic tripping curves for GV7 R


Average operating time at 20 C related to multiples of the setting current:
Time (s)

10 000 5000

2000 1000 500

200 100 50

20 10 5

1
2 1 0,5

3
0,2 0,1 0,05

0,02 0,01 0,005

0,002 0,001 1 1,12 2 3 4 5 7 10 20 30 40 50 70 100


x the setting current (Ir)

1 Cold state curve 2 Cold state curve 3 1214 Ir In the event of total phase failure, tripping occurs after 4 s 20 %

References : page 3/48

Dimensions : pages 3/65 and 3/67

Schemes : page 3/69

3/29

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

Current limitation on short-circuit (3-phase 400/415 V)


Dynamic stress I peak = f (prospective Isc)
For GV7 RE only
Limited peak current (kA)

1 GV7 RE220 2 GV7 RE150 3 GV7 RE100

100 80 70 60 50 40 30

20

1 2
10 8 7 6 5 4 2 3 4 5 6 10 20 30 40 50 60 70 100 Prospective Isc (kA)

For GV7 RS only


Limited peak current (kA)

1 GV7 RS220 2 GV7 RS150 3 GV7 RS100

100 80 70 60 50 40 30

20

1 2
10 8 7 6 5 4 2 3 4 5 6 10 20 30 40 50 60 70 100 Prospective Isc (kA)

References : page 3/48

Dimensions : pages 3/65 and 3/67

Schemes : page 3/69

3/30

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

Thermal limit (3-phase 400/415 V)


Thermal limit Sum of I 2dt = f (prospective Isc)
For GV7 RE only
Sum of I2dt (A 2s)

107

1 GV7 RE220 2 GV7 RE150 3 GV7 RE100

5x10

3x106 2x106

106

3
1 2 3

5x10 3x10

2x105

10

5x10

3x104 2x10
4

10

20

30

40

50 60 70 100 Prospective Isc (kA)

For GV7 RS only


Sum of I2dt (A 2s)

107

1 GV7 RS220 2 GV7 RS150 3 GV7 RS100

5x10

3x106 2x106

106

1
5x10 3x10
5

2 3

2x105

105

5x104 3x104 2x104 2 3 4 5 6 10 20 30 40 50 60 70 100


Prospective Isc (kA)

References : page 3/48

Dimensions : pages 3/65 and 3/67

Schemes : page 3/69

3/31

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

Current limitation on short-circuit (3-phase 690 V)


Dynamic stress I peak = f (prospective Isc)
For GV7 RE only
Limited peak current (kA)

50 40

1 GV7 RE220 2 GV7 RE150 and GV7 RE100

30

20

1 2
10

8 7 6 5 4 2 3 4 5 6 9 10 20 Prospective Isc (kA)

For GV7 RS only


Limited peak current (kA)

50 40

1 GV7 RS220 2 GV7 RS150 and GV7 RS100

30

20

1 2
10

8 7 6 5 4 2 3 4 5 6 10 20 Prospective Isc (kA)

References : page 3/48

Dimensions : pages 3/65 and 3/67

Schemes : page 3/69

3/32

Curves (continued)

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

Thermal limit on short-circuit (3-phase 690 V)


Thermal stress limit Sum of I 2dt = f (prospective Isc)
For GV7 RE only
Sum of I2dt (A 2s)

3x106

1 GV7 RE220 2 GV7 RE150 and GV7 RE100

2x10

106

3
1 2

5x10

3x105

2x105

105 2 3 4 5 6 8 10 20 Prospective Isc (kA)

For GV7 RS only


Sum of I2dt (A 2s)

3x106

1 GV7 RS220 2 GV7 RS150 and GV7 RS100

2x106

106

5x105

1 2

3x105

2x105

105 2 3 4 5 6 10 20 Prospective Isc (kA)

References : page 3/48

Dimensions : pages 3/65 and 3/67

Schemes : page 3/69

3/33

Curves

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 RT

Thermal-magnetic tripping curves for GV2 RT


Time (s)

10 000

1000

100

3
10

2 1

0,1

0,01

0,001 1 10 100
k x Ir

1 3 poles from cold state 2 2 poles from cold state 3 3 poles from hot state

References : page 3/49

Dimensions : page 3/64

Schemes : page 3/68

3/34

Curves

TeSys protection components


Magnetic motor circuit-breakers GV2 L and GV2 LE

Tripping curves for GV2 L or GV2 LE combined with thermal overload relay LRD or LR2 K
Average operating time at 20 C related to multiples of the setting current
Time (s)

10 000

1000

100

3
1 2 3

10

0,1

0,01

0,001 1 10 100
x the setting current (Ir)

1 3 poles from cold state 2 2 poles from cold state 3 3 poles from hot state

References : page 3/50

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/35

Curves (continued)

TeSys protection components


Magnetic motor circuit-breakers GV2 L and GV2 LE

Current limitation on short-circuit for GV2 L and GV2 LE only (3-phase 400/415 V)
Dynamic stress I peak = f (prospective Isc) at 1.05 Ue = 435 V
Limited peak current (kA)

100

1
= 0.2 5

3
0. 5 =

0.

2 3 4 5 6

10

0.

7 8 9

0.9

0.

10

0,1 0,1

co

=0
1

.95

10

15

100
Prospective Isc (kA)

11

1 Maximum peak current 2 32 A 3 25 A 4 18 A 5 14 A 6 10 A 7 6.3 A 8 4A 9 2.5 A 10 1.6 A 11 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).

References : page 3/50

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/36

Curves (continued)

TeSys protection components


Magnetic motor circuit-breakers GV2 L and GV2 LE

Current limitation on short-circuit for GV2 L and GV2 LE + thermal overload relay LRD or LR2 K (3-phase 400/415 V)
Dynamic stress I peak = f (prospective Isc) at 1.05 Ue = 435 V
Limited peak current (kA)

100

1
.25 =0

0. 3

2 3

4 5

10

0.

0.7

0.

6 7

0.

8
0.9 co s = 5

10

0,1 0,1

10

15

100
Prospective Isc (kA)

11

1 2 3 4 5 6 7 8 9 10 11

Maximum peak current 32 A 25 A 18 A 14 A 10 A 6.3 A 4A 2.5 A 1.6 A Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).

References : page 3/50

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/37

Curves (continued)

TeSys protection components


Magnetic motor circuit-breakers GV2 L and GV2 LE

Thermal limit on short-circuit for GV2 LE only


Thermal limit in kA2s in the magnetic operating zone Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100

2 3 4 5 6

10

8
1

0,1

0,01 0,1

10

100
Prospective Isc (kA)

1 2 3 4 5 6 7 8 9

32 A 25 A 18 A 14 A 10 A 6.3 A 4A 2.5 A 1.6 A

References : page 3/50

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/38

Curves (continued)

TeSys protection components


Magnetic motor circuit-breakers GV2 L and GV2 LE

Thermal limit on short-circuit for GV2 L only


Thermal limit in kA2s in the magnetic operating zone Sum of I 2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100

1 2 3 4 5 6
10

3
7 8

0,1

0,01 0,1

10

100 Prospective Isc (kA)

1 2 3 4 5 6 7 8

25 A and 32 A 18 A 14 A 10 A 6.3 A 4A 2.5 A 1.6 A

References : page 3/50

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/39

Curves (continued)

TeSys protection components


Magnetic motor circuit-breakers GV2 L and GV2 LE

Thermal limit on short-circuit for GV2 L and GV2 LE + thermal overload relay LRD or LR2 K
Thermal limit in kA2s in the magnetic operating zone Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100

2 1 3 4 5 6

10

0,1

10

0,01 0,1

10

15

100 Prospective Isc (kA)

1 32 A (GV2 LE32) 2 25 A and 32 A (GV2 L32) 3 18 A 4 14 A 5 10 A 6 6.3 A 7 4A 8 2.5 A 9 1.6 A 10 Limit of rated ultimate breaking capacity on short-circuit of GV2 LE (14, 18, 23 and 25 A ratings).

References : page 3/50

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/40

Curves

TeSys protection components


Magnetic motor circuit-breakers GK3

Tripping curves for GK3 combined with thermal overload relay LRD 33
Average operating time at 20 C without prior current flow
Time (s)

10 000

1000

100

A 1 2 3
10

0,1

0,01

0,001 1 10 100
x the setting current (Ir)

1 3 poles from cold state 2 2 poles from cold state 3 3 poles from hot state A Thermal overload relay protection zone B GK3 protection zone

References : page 3/51

Dimensions : page 3/72

Schemes : page 2457/5

3/41

Curves (continued)

TeSys protection components


Magnetic motor circuit-breakers GK3

Current limitation on short-circuit for GK3 only


Dynamic stress I peak = f (prospective Isc) at 1.05 Ue = 435 V
Limited peak current (kA)

(3-phase 400/415 V)

100

3
10

2 3 4

0,1 0,1

10

100
Prospective Isc (kA)

1 2 3 4

Maximum peak current 80 A 65 A 40 A

References : page 3/51

Dimensions : page 3/72

Schemes : page 3/73

3/42

Curves (continued)

TeSys protection components


Magnetic motor circuit-breakers GK3

Thermal limit on short-circuit for GK3 only


Thermal limit in A2s Sum of I 2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (A 2s)

1000

1 2 3
100

10

1 0,1

10

100
Prospective Isc (kA)

1 80 A 2 65 A 3 40 A

References : page 3/51

Dimensions : page 3/72

Schemes : page 3/73

3/43

Presentation

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2, GV3 and GV7

1 O 2 4 I 1 2 4

GV2 ME, GV2 P, GV3 ME and GV7 R motor circuit-breakers are 3-pole thermalmagnetic circuit-breakers specifically designed for the control and protection of motors , conforming to standards IEC 60947-2 and IEC 60947-4-1

Connection
These circuit-breakers are designed for connection by screw clamp terminals. Circuit-breaker GV2 ME can be supplied with spring terminal connections. These ensure secure, permanent and durable clamping that is resistant to harsh environments, vibration and impact and is even more effective when conductors without cable ends are used. Each connection can take two independent conductors.

GV2 ME

GV3 ME

1 3 O 2 3 1

Operation
Control is manual and local when the motor circuit-breaker is used on its own. Control is automatic and remote when it is associated with a contactor. GV2 ME and GV3 ME Pushbutton control. Energisation is controlled manually by operating the Start button I 1. De-energisation is controlled manually by operating the Stop button O 2, or automatically by the thermal-magnetic protection elements or by a voltage trip attachment. GV2 P Control by rotary knob. GV7 R Control by rocker lever. Energisation is controlled manually by moving the knob or rocker lever to position I 1. De-energisation is controlled manually by moving the knob or rocker lever to position O 2. De-energisation due to a fault automatically places the knob or rocker lever in the Trip position 3. Re-energisation is possible only after having returned the knob or rocker switch to position O.

3
GV2 P

2 4

GV7 R

533886

533887

Protection of motors and personnel


GV2 ME with screw clamp connections

GV2 ME with spring terminal connections


533889

Motor protection is provided by the thermal-magnetic protection elements incorporated in the motor circuit-breaker. The magnetic elements (short-circuit protection) have a non-adjustable tripping threshold, which is equal to about 13 times the maximum setting current of the thermal trips. The thermal elements (overload protection) include automatic compensation for ambient temperature variations. The rated operational current of the motor is displayed by means of a graduated knob 4. Personnel protection is also provided. All live parts are protected against direct finger contact. The addition of an undervoltage trip allows the circuit-breaker to be de-energised in the event of an undervoltage condition. The user is therefore protected against sudden starting of the machine when normal voltage is restored, since the Start button I has to be pressed to restart the motor.

533888

GV2 P

GV3 ME
533890

With the addition of a shunt trip, de-energisation of the unit can be remotely controlled. The operators on both open-mounted and enclosed motor circuit-breakers can be locked in the Stop position O by up to 3 padlocks. Because they are suitable for isolation, these circuit-breakers, in the open position, provide an adequate isolation distance and indicate the actual position of the moving contacts by the position of the operators.

Special features
GV7 R

These motor circuit-breakers are easily installed in any configuration thanks to their universal fixing arrangement: screw fixing or clip-on mounting on symmetrical, asymmetrical or combination rails.
Dimensions : pages 3/62 to 3/67 Schemes : pages 3/68 and 3/69

Characteristics : pages 3/6 to 3/21

3/44

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

533895

Thermal magnetic circuit-breakers GV2 ME and GV2 P with screw clamp terminals
GV2 ME: pushbutton control, GV2 P: control by rotary knob
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 500 V 690 V P Icu Ics (1) P Icu Ics (1) P Icu kW kA % kW kA % kW kA GV2 ME 0.06 g 0.09 g 0.12 g g g g g g g g g g g g g g g g g g g g 50 g 50 50 40 50 40 50 50 50 g g g g g g g g g 100 g 100 100 100 100 75 75 75 75 75 75 75 75 75 75 Setting range of thermal trips (2) A 0.10.16 0.160.25 0.250.40 0.400.63 0.400.63 0.631 11.6 11.6 11.6 1.62.5 1.62.5 2.54 2.54 2.54 2.54 46.3 46.3 610 610 610 610 914 914 914 914 1318 1318 1723 1723 2025 2025 2432 2432 Magnetic tripping current Id 20 % A 1.5 or g g g g 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 2.4 or 5 or 0.37 g 8 or 0.18 g 0.25 g 0.37 g 0.55 g 0.75 0.75 1.1 1.1 1.5 1.5 2.2 2.2 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 g g g g g g g g g g g g 15 g 15 50 15 50 15 50 10 35 8 or 0.55 g 13 or 0.37 g 0.55 g 0.75 g 1.1 1.1 1.5 1.5 2.2 2.2 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 g g g g g g 50 g 10 50 10 50 6 42 6 10 4 10 4 10 4 10 22.5 or 0.75 g 1.1 1.5 1.5 2.2 2.2 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 22 22 g 3 8 3 8 3 8 3 6 3 6 3 6 3 6 3 6 3 4 3 4 3 4 22.5 or GV2 P 22.5 or 33.5 33.5 51 51 51 51 78 78 138 138 138 138 170 170 170 170 223 223 327 327 327 327 416 416 Reference Weight

Ics (1) %

GV2 ME01 GV2 P01 GV2 ME02 GV2 P02 GV2 ME03 GV2 P03 GV2 ME04 GV2 P04 GV2 ME04 GV2 P04 GV2 ME05 GV2 P05 GV2 ME06 GV2 P06 GV2 ME06 GV2 P06 GV2 ME06 GV2 P06 GV2 ME07 GV2 P07 GV2 ME08 GV2 P08 GV2 ME08 GV2 P08 GV2 ME10 GV2 P10 GV2 ME14 GV2 P14 GV2 ME14 GV2 P14 GV2 ME16 GV2 P16 GV2 ME16 GV2 P16 GV2 ME20 GV2 P20 GV2 ME21 GV2 P21 GV2 ME22 (3) GV2 P22 GV2 ME32 GV2 P32

kg 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350 0.260 0.350

533896

Thermal magnetic circuit-breakers GV2 ME with lugs


To order termal magnetic circuit-breakers with connection by lugs, add the digit 6 to the end of reference selected above. Example: GV2 ME08 becomes GV2 ME086.

Thermal magnetic circuit-breakers GV2 ME with built-in auxiliary contact block


With instantaneous auxiliary contact block (composition, see page 3/53): b GV AE1, add suffix AE1TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE1TQ. b GV AE11, add suffix AE11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AE11TQ . b GV AN11, add suffix AN11TQ to the motor circuit-breaker reference selected above. Example: GV2 ME01AN11TQ. These circuit-breakers with built-in contact block are sold in lots of 20 units in a single pack.
(1) As % of Icu. (2) For use of GV2 ME in an enclosure, see page 2/10. (3) Maximum rating which can be mounted in enclosures GV2 MC or MP, please consult your Regional Sales Office. g > 100 kA.

Characteristics : pages 3/6 to 3/9

Dimensions : pages 3/62 to 3/64

Schemes : page 3/68

3/45

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME

533897

Thermal magnetic circuit-breakers GV2 ME with spring terminal connections


Pushbutton control
Standard power ratings of 3-phase motors 50-60 Hz in category AC-3 400/415 V 500 V P Icu Ics (2) P Icu Ics (2) kW kA % kW kA % Setting range of thermal trips A 0.10.16 Magnetic tripping current Id 20 % A 1.5 Reference

(1)
Weight

GV2 ME013

kg 0.280

GV2 MEpp3

0.06

0.160.25

2.4

GV2 ME023

0.280

0.09

0.250.40

GV2 ME033

0.280

0.12 0.18 0.25 0.37 0.37 0.55 0.75

g g g g g g g

g g g g g g g

0.400.63

GV2 ME043

0.280

0.37

0.631

13

GV2 ME053

0.280

0.37 0.55 0.75 1.1

g g g g

g g g g

11.6

22.5

GV2 ME063

0.280

1.62.5

33.5

GV2 ME073

0.280

1.1 1.5 2.2

g g g

g g g

1.5 2.2 3

g g 50

g g 100

2.54

51

GV2 ME083

0.280

46.3

78

GV2 ME103

0.280

3 4 5.5

g g 15

g g 50

4 5.5 7.5

10 10 6

100 100 75

610

138

GV2 ME143

0.280

914

170

GV2 ME163

0.280

7.5

15

50

75

1318

223

GV2 ME203

0.280

9 11 11

15 15 15

40 40 40

11

75

1723

327

GV2 ME213

0.260

15

75

2025

327

GV2 ME223

0.260

Contact blocks
Description Instantaneous auxiliary contacts Mounting Front Maximum number 1 Type of contacts N/O + N/C Sold in lots of 10 Unit reference GV AE113 Weight kg 0.030

N/O + N/O

10

GV AE203

0.030

LH side

N/O + N/C

GV AN113

0.060

N/O + N/O

GV AN203

0,060

Accessory
Description LA9 D99 Cable end reducer Application For connection of conductors from 1 to 1.5 mm2 Sold in lots of 20 Unit reference LA9 D99 Weight kg

(1) For connection of conductors from 1 to 1.5 mm 2, the use of an LA9 D99 cable end reducer is recommended. (2) As % of Icu. g > 100 kA.

Characteristics : pages 3/6 to 3/19

Dimensions : pages 3/62 to 3/64

Schemes : page 3/68

3/46

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV3 ME

533899

Thermal magnetic circuit-breakers GV3 ME with screw clamp terminals


Pushbutton control
Standard power ratings of 3-phase 50/60 Hz in category AC-3 400/415 V 500 V P Icu Ics (1) P Icu kW kA % kW kA 0.37 100 100 0.37 100 0.55 100 100 0.55 100 0.75 100 0.75 100 100 1.1 100 motors 660/690 V P Icu kW kA 0.75 100 1.1 100 1.5 100 Setting range of thermal trips A 11.6 Reference Weight

Ics (1) % 100 100 100 100

Ics (1) % 100 100 100

GV3 ME06

kg 0.600

1.62.5

GV3 ME07

0.600

GV3 ME20

1.1 1.5 2.2

100 100 100

100 100 100

1.5 2.2 3

100 100 100

100 100 100

2.2 3 4

4 4 4

100 100 100

2.54

GV3 ME08

0.600

46

GV3 ME10

0.600

3 4 7.5

100 100 100

100 100 50

4 5.5 9

8 8 8

100 100 100

5.5 7.5 9 11 15 18.5 22 30 37 45 55

4 4 4 4 4 4 4 4 4 4 2

100 100 100 100 100 100 75 75 75 75 100

610

GV3 ME14

0.600

1016

GV3 ME20

0.600

9 11 15 18.5 22 30 37

100 100 35 35 35 35 15

50 50 50 50 50 50 50

11 15 18.5 22 30 37 45

8 8 8 8 8 8 4

100 100 75 75 75 75 100

1625

GV3 ME25

0.600

2540

GV3 ME40 (2)

0.700

4063

GV3 ME63 (2)

0.700

5680

GV3 ME80 (2)

0.700

(1) As % of Icu. (2) Recommended for use in association with a contactor.

Characteristics : pages 3/6 to 3/10

Dimensions : page 3/65

Schemes : page 3/69

3/47

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

533900

Thermal magnetic circuit-breakers GV7 R with screw clamp terminals


Control by rocker lever
Standard power ratings of 3-phase 50/60 Hz in category AC-3 400/415 V 500 V P Icu Ics (1) P Icu kW kA % kW kA 7.5 36 100 9 18 9 36 100 11 18 GV7 RE 7.5 9 9 11 70 70 36 36 70 70 36 100 100 100 100 100 100 100 9 11 11 15 11 15 18.5 22 18.5 50 50 18 18 50 50 18 18 50 motors 660/690 V P Icu kW kA 11 8 15 8 11 15 15 18.5 15 18.5 22 10 10 8 8 10 10 8 Setting range of thermal trips A 1220 Reference Weight

Ics (1) % 100 100 100 100 100 100 100 100 100 100 100

Ics (1) % 100 100 100 100 100 100 100 100 100

GV7 RE20

kg 2.010

1220

GV7 RS20

2.010

1525

GV7 RE25

2.010

533901

9 11 18.5

1525

GV7 RS25

2.010

2540

GV7 RE40

2.010

18.5

70

100

22

10

100

2540

GV7 RS40

2.010

22

36

100

30

18

100

30

100

3050

GV7 RE50

2.015

22 GV7 RS 37

70

100

30

50

100

30

10

100

3050

GV7 RS50

2.015

36

100

45 55 45 55

18 18 50 50 18

100 100 100 100 100

55

100

4880

GV7 RE80

2.040

37

70

100

55

10

100

4880

GV7 RS80

2.040

45

36

100

75

100

60100

GV7 RE100

2.040

45

70

100

50

100

75

10

100

60100

GV7 RS100

2.040

55 75 55 75 90 110 90 110

35 35 70 70 35 35 70 70

100 100 100 100 100 100 100 100

75 90 75 90 110 132 160 110 132 160

30 30 50 50 30 30 30 50 50 50

100 100 100 100 100 100 100 100 100 100

90 110 90 110 160 200 160 200

8 8 10 10 8 8 10 10

100 100 100 100 100 100 100 100

90150

GV7 RE150

2.020

90150

GV7 RS150

2.020

132220

GV7 RE220

2.350

132220

GV7 RS220

2.350

(1) As % of Icu.

Characteristics : pages 3/6 to 3/11

Dimensions : page 3/65

Schemes : page 3/69

3/48

References

TeSys protection components


Thermal-magnetic circuit-breakers GV2 RT

533902

For motors with high current peak on starting


Control by rocker lever
Standard power ratings of 3-phase motors 50-60 Hz in category AC-3 220/ 400/ 440 V 500 V 690 V 230 V 415 V kW kW kW kW kW 0.06 0.09 0.09 0.12 0.12 0.18 0.37 0.18 0.09 0.25 0.25 0.37 0.55 0.12 0.37 0.37 0.18 0.37 0.37 0.37 0.75 0.25 0.55 0.55 0.55 1.1 0.75 0.37 0.75 0.75 1.1 1.5 1.1 0.55 1.1 1.5 1.5 2.2 0.75 1.5 2.2 3 1.1 2.2 2.2 3 4 3 1.5 3 4 4 5.5 2.2 4 5.5 7.5 2.2 5.5 5.5 7.5 9 3 7.5 11 4 7.5 7.5 9 15 9 5.5 9 11 11 18.5 11 Setting range of thermal trips A 0.250.40 0.400.63 0.631 11.6 Magnetic tripping current Id 20 % A 8 13 22 33 Reference Weight

GV2 RT03 GV2 RT04 GV2 RT05 GV2 RT06

kg 0.350 0.350 0.350 0.350

GV2 RT

1.62.5 2.54 46.3 610 914 1318 1723

51 78 138 200 280 400 400

GV2 RT07 GV2 RT08 GV2 RT10 GV2 RT14 GV2 RT16 GV2 RT20 GV2 RT21

0.350 0.350 0.350 0.350 0.350 0.350 0.350

For primaries of 3-phase transformers


Control by rocker lever
Standard power ratings 230/240 V 400/415 V 440 V kW kW kW 0.4 0.63 1 1.6 2 2.5 4 5 6.3 0.63 1 1.6 2 2.5 0.63 1 1.6 2 2.5 4 5 6.3 10 500 V kW 0.63 1 1.6 2 2.5 4 690 V kW 1 1.6 2 2.5 4 5 6.3 10 12.5 10 Setting range of thermal trips A 0.250.40 0.400.63 0.631 11.6 1.62.5 2.54 46.3 Magnetic tripping current Id 20 % A 8 13 22 33 51 78 138 Reference Weight

GV2 RT03 GV2 RT04 GV2 RT05 GV2 RT06 GV2 RT07 GV2 RT08 GV2 RT10

kg 0.350 0.350 0.350 0.350 0.350 0.350 0.350

4 5 6.3 10

5 6.3 10 12.5

610 914 1318

200 280 400

GV2 RT14 GV2 RT16 GV2 RT20

0.350 0.350 0.350

Accessory (1)
Description Padlockable external operator (IP 54) black handle, blue legend plate Reference GV2 AP03 Weight kg 0.280

(1) Other accessories such as mounting, cabling and marking accessories are identical to those used for GV2 ME motor circuitbreakers, see page 3/59.

Characteristics : pages 3/6 to 3/21

Dimensions : page 3/64

Schemes : page 3/68

3/49

References

TeSys protection components


Magnetic motor circuit-breakers GV2 LE and GV2 L

Magnetic circuit-breakers GV2 LE and GV2 L with screw clamp terminals


534101

GV2 LE: control by rocker lever, GV2 L: control by rotary knob


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 500 V P Icu Ics (1) P Icu kW kA 0.06 g 0.09 g 0.12 g GV2 LE 0.18 g g g g g g g g g g g g g g g g g g g g g g g 100 g 100 100 100 75 75 75 75 75 75 75 75 75 75 g g g 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 75 100 0.63 1 1 1 1 1.6 1.6 2.5 2.5 2.5 4 4 4 6.3 6.3 10 10 10 10 10 14 14 14 14 18 18 25 25 25 25 32 32 8 or 13 or 13 or 0.75 g 1.1 1.5 1.5 3 3 4 4 5.5 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 22 22 g 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 13 or 0.37 g 0.55 g 0.37 g 0.55 g 0.75 g 1.1 1.1 1.5 1.5 2.2 3 3 4 4 5.5 7.5 7.5 9 9 11 11 15 15 18.5 18.5 g g g g g 50 g 10 10 10 6 10 6 10 4 10 4 10 4 10 13 or 22.5 or 22.5 or GV2 L 0.75 g 0.75 g 1.1 g 1.5 1.5 2.2 2.2 3 3 4 g g g g g g g 33.5 33.5 33.5 or 51 51 51 or 78 78 138 138 138 or 5.5 15 50 5.5 50 50 7.5 15 50 7.5 50 50 9 15 40 9 50 50 11 15 40 11 50 50 15 10 50 15 35 50 (1) As % of Icu. g > 100 kA. 138 138 170 170 170 170 223 223 327 327 327 327 416 416 g g g kW kA Magnetic protection rating 690 V Ics (1) P Icu kW kA Ics (1) A 0.4 0.4 0.63 A 5 5 or 0.37 g g 8 or Tripping current Id 20 % Use in Reference association with thermal overload relay LR2 K0302 LR2 K0304 LRD 03 LR2 K0304 LRD 04 LR2 K0305 LRD 04 LR2 K0305 LRD 05 LR2 K0306 LRD 05 LR2 K0306 LRD 06 LR2 K0306 LRD 05 LR2 K0307 LRD 06 LR2 K0307 LRD 06 LR2 K0308 LRD 07 LR2 K0308 LRD 08 LR2 K0310 LRD 08 LR2 K0312 LRD 08 LR2 K0312 LRD 10 LR2 K0314 LRD 12 LR2 K0316 LRD 14 LRD 14 LRD 14 LRD 16 LRD 16 LR2 K0321 LRD 16 LRD 21 LRD 21 LRD 22 LRD 22 LRD 22 LRD 22 LRD 32 LRD 32 GV2 LE03 GV2 LE03 GV2 L03 GV2 LE04 GV2 L04 GV2 LE04 GV2 L04 GV2 LE05 GV2 L05 GV2 LE05 GV2 L05 GV2 LE05 GV2 L05 GV2 LE05 GV2 L05 GV2 LE06 GV2 L06 GV2 LE06 GV2 L06 GV2 LE07 GV2 L07 GV2 LE07 GV2 L07 GV2 LE08 GV2 L08 GV2 LE08 GV2 L08 GV2 LE10 GV2 L10 GV2 LE14 GV2 L14 GV2 LE14 GV2 L14 GV2 LE14 GV2 L14 GV2 LE16 GV2 L16 GV2 LE16 GV2 L16 GV2 LE20 GV2 L20 GV2 LE22 GV2 L22 GV2 LE22 GV2 L22 GV2 LE32 GV2 L32 Weight

3
534102

0.55 g

0.25 g

kg 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330 0.330

Characteristics : pages 3/12 and 3/13

Dimensions : pages 3/70 to 3/72

Schemes : page 3/73

3/50

References

TeSys protection components


Magnetic motor circuit-breakers GK3

534103

Magnetic circuit-breakers GK3 with screw clamp connections


Control by rotary knob
Standard power ratings of 3-phase motors 50-60 Hz in category AC-3 400/415 V 500 V P Icu Ics (1) P Icu kW kA kW kA 15 50 30 18.5 20 Associated Contactor minimum size Ics (1) Reference LC1 D32 equipment Thermal overload relay Reference LRD 32 Circuit-breaker Short-circuit protection Rating (1) A 40 Reference GK3 EF40 Weight kg 0.710

690 Ics (1) P kW 30

V Icu kA

GK3 EF

22

60

LC1 D40

LRD 3353

40

GK3 EF40

0.710

18.5 50

30

22

20

30

30

60

LC1 D40

LRD 3355

40

GK3 EF40

0.710

22

35

25

30

15

30

LC1 D50

LRD 3357

65

GK3 EF65

0.790

37

50

LC1 D65

LRD 3357

65

GK3 EF65

0.790

30

35

25

37

15

30

LC1 D65

LRD 3359

65

GK3 EF65

0.790

30

35

25

37

15

30

LC1 D65

LRD 3361

65

GK3 EF65

0.790

45

50

LC1 D80

LRD 3359

65

GK3 EF65

0.790

37

35

25

45

15

30

LC1 D80

LRD 3361

80

GK3 EF80

0.795

37

35

25

55

15

30

LC1 D80

LRD 3363

80

GK3 EF80

0.795

(1) Associated current limiter or fuses, where required. See characteristics page 3/15.

Characteristics : pages 3/14 and 3/15

Dimensions : page 3/72

Schemes : page 3/73

3/51

GV2 AK00

GV1 L3

3
GV2 ME

GV AX

GV AD GV AM11

GV AU

GV2 P

GV AM11

GV AS

GV2 L

GV AE11, AE20

GV AN GV AN GV AE1 GV2 LE GV AE1

3/52

References

TeSys protection components


Thermal-magnetic and magnetic motor circuitbreakers GV2 with screw clamp connections
Accessories

Contact blocks
Description Instantaneous auxiliary contacts Mounting Front (1) Maximum number 1 Type of contacts N/O or N/C (2) N/O + N/C N/O + N/O N/O + N/C N/O + N/O N/O (fault) + N/O + N/C N/C (fault) + N/O + N/C C/O common point Sold in lots of 10 10 10 1 1 1 1 1 1 1 Unit reference GV AE1 GV AE11 GV AE20 GV AN11 GV AN20 GV AD1010 GV AD1001 GV AD0110 GV AD0101 GV AM11 Weight kg 0.015 0.020 0.020 0.050 0.050 0.055 0.055 0.055 0.055 0.045

Side (LH) Fault signalling contact + instantaneous auxiliary contact Side (3) (LH)

2 1

Short-circuit signalling contact

Side (LH)

Electric trips
Mounting Voltage Reference Weight kg 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105 0.105

Undervoltage or shunt trips (4)


Side (1 block on RH side of circuit-breaker) 24 V 48 V 100 V 100110 V 110115 V 120127 V 127 V 200 V 200220 V 220240 V 380400 V 415440 V 415 V 440 V 480 V 500 V 600 V 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 60 Hz 60 Hz 50 Hz 60 Hz GV Ap025 GV Ap026 GV Ap055 GV Ap056 GV Ap107 GV Ap107 GV Ap115 GV Ap116 GV Ap125 GV Ap115 GV Ap207 GV Ap207 GV Ap225 GV Ap226 GV Ap385 GV Ap386 GV Ap415 GV Ap416 GV Ap385 GV A p415 GV Ap505 GV Ap505

Undervoltage trip, INRS (can only be mounted on GV2 ME) Safety device for dangerous machines conforming to INRS and VDE 0113
Side (1 block on RH side of circuit-breaker GV2 ME) 110115 V 127 V 220240 V 380400 V 415440 V 440 V 50 60 60 50 60 50 60 50 60 Hz Hz Hz Hz Hz Hz Hz Hz Hz GV AX115 GV AX116 GV AX115 GV AX225 GV AX226 GV AX385 GV AX386 GV AX415 GV AX385 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110 0.110

Add-on contact blocks


Description Visible isolation block (5) Limiters Mounting Front (1) At top (GV2 ME and GV2 P) Independent Maximum number 1 1 1 Reference GV2 AK00 GV1 L3 LA9 LB920 Weight kg 0.150 0.130 0.320

LA9 LB920

(1) Mounting of a GV AE contact block or a GV2 AK00 visible isolation block on GV2 P and GV2 L (2) Choice of N/C or N/O contact operation, depending on which way round the reversible block is mounted. (3) The GV AD is always mounted next to the circuit-breaker. (4) To order an undervoltage trip: replace the dot (p) in the reference with a U, example: GV AU025. To order a shunt trip: replace the dot (p) in the reference with an S, example: GV AS025. (5) Visible isolation of the 3 poles upstream of circuit-breaker GV2 P and GV2 L.

Characteristics : pages 3/16, 3/20 and 3/21

Dimensions, schemes : pages 3/62 to 3/73

3/53

3
GV3 A01...A07

GV3 A08 GV3 A09

3/54

References

TeSys protection components


Motor circuit-breakers, thermal-magnetic GV3 ME and magnetic GK3 with screw clamp connections
Accessories

For thermal-magnetic motor circuit-breakers GV3 ME


Contact blocks
Description Instantaneous auxiliary contact blocks (1 per circuit-breaker) Type of standard early break contacts N/C + N/O N/O + N/O N/C + N/O + N/O N/O + N/O + N/O N/O + N/O + 2 volt-free terminals N/C + N/O + 2 volt-free terminals N/C N/O Reference GV3 GV3 GV3 GV3 GV3 GV3 A01 A02 A03 A05 A06 A07 Weight kg 0.060 0.060 0.070 0.070 0.070 0.070 0.030 0.030

Fault signalling contacts (1)

GV3 A08 GV3 A09

Electric trips
Description Udervoltage trips (1) Voltages 50 Hz 110, 120, 127 V 220, 240 V 380, 415 V 110, 120, 127 V 220, 240 V 380, 415 V Reference 60 Hz 120, 127 V 277 V 440 V, 480 V 120, 127 V 277 V 440 V, 480 V GV3 B11 GV3 B22 GV3 B38 GV3 D11 GV3 D22 GV3 D38 Weight kg 0.070 0.070 0.070 0.070 0.070 0.070

Shunt trips (1)

Accessory
Description Padlocking device, for locking the start button (on open-mounted product) Sold in lots of 5 Unit reference GV1 V02 Weight kg 0.010

For magnetic circuit-breakers GK3


Contact blocks
Description Auxiliary contact blocks for On-Off signalling and control circuit test function (1 or 2 blocks per device) mounted on RH side of GK3 EF Instantaneous fault signalling contact blocks (1 or 2 blocks per device) mounted on LH side of GK3 EF Composition N/O N/O + N/O N/C + N/O N/O N/O + N/O N/C + N/O Reference GK2 AX10 GK2 AX20 GK2 AX50 GK2 AX12 GK2 AX22 GK2 AX52 Weight kg 0.025 0.031 0.031 0.025 0.031 0.031

Accessories
Description Padlocking device for padlocking the operator, using up to 3 padlocks (padlocks not supplied) Reference GK3 AV01 Weight kg 0.020

External operator for mounting on the enclosure door. GK3 AP03 Red 40 pushbutton on yellow plate. Can be locked in position "O" by means of up to 3 padlocks, with door locked in position "I" and door locked in position "O" when padlocked.

0.300

(1) 1 voltage trip OR 1 fault signalling contact to be fitted inside the motor circuit-breaker.

Other versions

24 to 690 V, 50 or 60 Hz voltage trips for circuit-breakers GV3 ME. Please consult your Regional Sales Office.

Characteristics : pages 3/16 and 3/20

Dimensions, schemes : pages 3/62 to 3/73

3/55

3 2 1

GV7 AE11, AB11

GV7 RE, RS

GV7 AU, AS

3/56

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R with screw clamp connections
Accessories

Add-on auxiliary contacts


They allow remote indication of the circuit-breaker contact states. They can be used for signalling, electrical locking, relaying, etc. Two versions are available: standard and low level. They include a terminal block and the auxiliary circuits leave the circuit-breaker through a hole provided for this purpose. They perform the following functions, depending on where they are located in the circuit-breaker:
Location 1 and/or 4 2 Function C/O contact Trip indication Application Indicates the position of the circuit-breaker poles Indicates that the circuit-breaker has tripped due to an overload, a short-circuit, a differential fault or the operation of a voltage trip (undervoltage or shunt trip) or of the push to trip test button. It resets when the circuit-breaker is reset. Indicates that the circuit-breaker has tripped due to an overload, a short-circuit or a differential fault. It resets when the circuit-breaker is reset. Reference GV7 AE11 GV7 AB11 Weight kg 0.015 0.015

Electrical fault indication

Type Standard Low level

Fault discrimination devices


They make it possible to: b either differentiate a thermal fault from a magnetic fault, b or open the contactor only in the event of a thermal fault.
Voltage a 24...48 and c 2472 V z 110240 V Reference GV7 AD111 (1) GV7 AD112 (1) Weight kg 0.100 0.100

Electric trips
These allow the circuit-breaker to be tripped via an electrical control signal. b Undervoltage trip GV7 AU v Trips the circuit-breaker when the control voltage drops below the tripping threshold, which is between 0.35 and 0.7 times the rated voltage. v Circuit-breaker closing is only possible if the voltage exceeds 0.85 times the rated voltage. Circuit-breaker tripping by a GV7 AU trip meets the requirements of IEC 60947-2. b Shunt trip GV7 AS Trips the circuit-breaker when the control voltage rises above 0.7 times the rated voltage. b Operation (GV7 AU or GV7 AS) v When the circuit-breaker has been tripped by a GV7 AU or AS, it must be reset either locally or by remote control. (For remote control, please consult your Regional Sales Office). v Tripping has priority over manual closing: if a tripping instruction is present, manual action does not result in closing, even temporarily, of the contacts. v Durability: 50 % of the mechanical durability of the circuit-breaker.
Type Undervoltage trip Voltage 48 V, 50/60 Hz 110130 V, 50/60 Hz 200240 V, 50/60 Hz 380440 V, 50/60 Hz 525 V, 50 Hz 48 V, 50/60 Hz 110130 V, 50/60 Hz 200240 V, 50/60 Hz 380440 V, 50/60 Hz 525 V, 50 Hz Reference GV7 GV7 GV7 GV7 GV7 GV7 GV7 GV7 GV7 GV7 AU055 AU107 AU207 AU387 AU525 AS055 AS107 AS207 AS387 AS525 (1) (1) (1) (1) (1) (1) (1) (1) (1) (1) Weight kg 0.105 0.110 0.110 0.105 0.100 0.105 0.110 0.110 0.105 0.100

Shunt trip

(1) For mounting of a GV7 AD or a GV7 AU or AS.

Characteristics : pages 3/16, 3/20 and 3/21

Dimensions : pages 3/65 to 3/67

Schemes : page 3/69

3/57

TRIP

T RESE

3/58

References

TeSys protection components


Thermal-magnetic and magnetic motor circuit-breakers GV2 with screw clamp connections
Accessories

Accessories
Description Adapter plates Application For mounting a GV2 ME or GV2 LE by screw fixing For mounting a GV2 ME or GV2 P and contactor LC1 D09D38 with front faces aligned 7.5 mm Between GV2 and contactor LC1 K or LP1 K Between GV2 and contactor LC1 D09D38 Between GV2 mounted on LAD 311 and contactor LC1 D09D38 With 3-pole connection for mounting a GV2 and a contactor LC1 D09D25 Application 2 tap-offs Sold in lots of 10 1 Unit reference GV2 AF02 LAD 311 Weight kg 0.021 0.040

Height compensation plate Combination blocks

10 10 10 10

GV1 F03 GV2 AF01 GV2 AF3 GV2 AF4

0.003 0.020 0.016 0.016

Motor starter adapter plate

GK2 AF01

0.120

Description Sets of 3-pole busbars 63 A

3 tap-offs 4 tap-offs

5 tap-offs Description Protective end cover Terminal block for supply to one or more GV2 G busbar sets Cover for terminal block Flexible 3-pole connection for connecting a GV2 to a contactor LC1-D09D25 Application For unused busbar outlets Connection from the top Can be fitted with current limiter GV1 L3 (GV2 ME and GV2 P) For mounting in modular panels Centre distance between mounting rails: 100120 mm

Pitch mm 45 54 72 45 54 45 54 72 54 Sold in lots of 5 1 1

Reference GV2 GV2 GV2 GV2 GV2 GV2 GV2 GV2 GV2 G245 G254 G272 G345 G354 G445 G454 G472 G554

Weight kg 0.036 0.038 0.042 0.058 0.060 0.077 0.085 0.094 0.100 Weight kg 0.005 0.040 0.115

Unit reference GV1 G10 GV1 G09 GV2 G05

10 10

LA9 E07 GV1 G02

0.005 0.013

Set of connections upstream/downstream Clip-in marker holders (supplied with each circuit-breaker)

For connecting GV2 ME to a printed circuit board

10

GV2 GA01

0.045

For GV2 P, GV2 L, GV2 LE and GV2 RT (8 x 22 mm)

100

LA9 D92

0.001

Padlockable external operators


Description For GV2 P and GV2 L (150 to 290 mm) Padlocking in On and Off position Black handle, blue legend plate, IP 54 Padlocking in Off position Red handle, yellow legend plate, IP 54 Padlocking in On and Off position Black handle, blue legend plate, IP 54 Reference GV2 AP01 GV2 AP02 Weight kg 0.200 0.200

For GV2 LE

GV2 AP03

0.280

Padlocking device
Description For all GV2 devices For use with up to 4 padlocks (not supplied), 6 mm shank max. Reference GV2 V03 Weight kg 0.092

Dimensions : pages 3/62 to 3/72

3/59

ON

ON

OFF

GV7 AP04
O

OFF

ON

GV7 AP01, AP02

GV7 RE, RS GV7 AP03

ON

OFF

ON

OFF

ON

OFF

OFF

GV7 AP05

GV7 AC04

GV7 AC01

GV7 V01

GV7 RE, RS

GV7 AC04

GV7 AC03

GV7 AC01

3/60

References

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R with screw clamp connections
Accessories

Cabling accessories
Description Application For contactor Sold in lots of 3 3 1 Unit reference GV7 AC021 GV7 AC022 GV7 AC03 Weight kg 0.300 0.350 0.180

Clip-on connectors for GV7 R

Up to 150 A, 1.595 mm2 Up to 220 A, 1.5185 mm2

Spreader 3-pole (1) Terminal shields IP 405 (1) Phase barriers Insulating screens Kit for combination with contactor (2)

To increase the pitch to 45 mm

Supplied with sealing accessory Safety accessories used when fitting of shields is impossible Ensure insulation between the connections and the backplate Allowing link between the circuit-breaker and the contactor. The cover provides protection against direct finger contact.

GV7 AC01

0.125

LC1 F115F185

2 2 1

GV7 AC04 GV7 AC05 GV7 AC06 GV7 AC07 GV7 AC08

0.075 0.075 0.550 0.550 0.550

LC1 F225 and F265 1 LC1 D115 and D150 1

Direct rotary handle


Replaces the circuit-breaker front cover; secured by screws. It includes a device for locking the circuit-breaker in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). A conversion accessory allows the direct rotary handle to be mounted on the enclosure door. In this case, the door cannot be opened if the circuit-breaker is in the ON position. Circuit-breaker closing is inhibited if the enclosure door is open.
Description Direct rotary handle Type Black handle, black legend plate Red handle, yellow legend plate Adapter plate (3) Four mounting direct rotary handle on enclosure door Degree of protection IP 40 IP 40 IP 43 Reference GV7 AP03 GV7 AP04 GV7 AP05 Weight kg 0.205 0.205 0.100

Extended rotary handle


Allows a circuit-breaker installed in the back of an enclosure to be operated from the front of the enclosure. It comprises: b a unit which replaces the circuit-breaker front cover; secured by screws, b an assembly (handle and front plate) to be fitted on the enclosure door, b an extension shaft which must be adjusted (distance between the mounting surface and the door: 185 mm minimum, 600 mm maximum). It includes a device for locking the circuit-breaker in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). This prevents the enclosure door from being opened.
Description Extended rotary handle Type Black handle, black legend plate Red handle, yellow legend plate Degree of protection IP 55 IP 55 Reference GV7 AP01 GV7 AP02 Weight kg 0.775 0.775

Locking device
Allows circuit-breakers not fitted with a rotary handle to be locked in the "O" (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied).
Description Locking device Application For circuit-breaker not fitted with a rotary handle Reference GV7 V01 Weight kg 0.100

(1) Terminal shields cannot be used together with spreaders. (2) The kit comprises links, a protective shield and a depth adjustable metal bracket for the breaker. (3) This conversion accessory makes it impossible to open the door if the device is closed and prevents the device from being closed if the door is open.

Dimensions : pages 3/65 to 3/67

Schemes : page 3/69

3/61

Dimensions, mounting

TeSys protection components


3

Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

GV2 ME

GV AX

GV AD, AM, AN, AU, AS, AX


Block GV AD, AM, AN Block GV AU, AS, AX

GV AE

X1

11

67,2

15
10

15,7

X1

46

44,5

45

16

9,3

9,3 81(1)

18

b GV2 MEpp 89 GV2 MEpp3 101 (1) Maximum X1 Electrical clearance = 40 mm for Ue y 690 V

GV2 P

GV AD, AM, AN, AU, AS


Block GV AD, AM, AN Block GV AU, AS

GV2 AK00
14 98 32

X1

89

45
44,5

15

X2

26

50 82

61

9,3

9,3 81(1)

18 44,5

(1) Maximum X1 Electrical clearance = 40 mm for Ue y 415 V, or 80 mm for Ue = 440 V, or 120 mm for Ue = 500 and 690 V X2 = 40 mm

Mounting of GV2 ME
On 35 mm 5 rail On panel with adapter plate GV2 AF02 AM1 PA On pre-slotted mounting plate On mounting rails DZ5 MB201

4,2

AF1 EA4

15

35

50/60

50/60

c
c = 78.5 on AM1 DP200 (35 x 7.5) c = 86 on AM1 DE200, ED200 (35 x 15)

80

35 35 GV2 AF02 DZ5 ME8 DZ5 MB201

Mounting of GV2 P
On rail AM1 DE200, ED200 (35 x 15) On panel On pre-slotted mounting plate AM1 PA Adapter plate GK2 AF01

AF1 EA4
35 5

55

44,5

135

84

84

45

44,5

45

106

13,5

13,5

24

9,5

35

54

Characteristics : pages 3/6 to 3/21

References : pages 3/44 to 3/46

Schemes : page 3/68

3/62

105 5

50 60

Dimensions, mounting (continued)

TeSys protection components


3

Thermal-magnetic motor circuit-breakers GV2 ME and GV2 P

GV2 AF01
Combination GV2 ME + k contactor

GV2 AF3
Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor

152

79

45 c1 c 45 c1 c d1 d
GV2 P + b c1 c d1 d LC1 D09D18 177.4 88.6 94.1 91 96.8

45

GV2 ME + b c1 c

LC1 D09D18 176.4 88.65 94.15

LC1 D25 & D32 186.8 94.95 100.45

LC1 D25 & D32 187.8 94.95 100.45 91 96.8

GV2 AF4 + LAD 31


Combination GV2 ME + TeSys d contactor Combination GV2 P + TeSys d contactor

GV2 ME + GV1 L3 (current limiter)

40

X1

77

X1

44,5

c1 c d1 d
GV2-ME + b c1 c d1 d LC2 D09D18 188.6 92.7 98.2 98.3 103.8

45

c1 c

45

X1 = 10 mm for Ue = 230 V or 30 mm for 230 V < Ue y 690 V

7.5 mm height compensation plate GV1 F03


39 13 35
Door cut-out

LC2 D25 and D32 199 99 104.5 98.3 103.8

GV2 P + b c1 c

LC2 D09D18 169.1 116.8 122.3

LC2 D25 & D32 199.5 116.8 122.3

Mounting of external operator GV2 AP01 or GV2 AP02 for GV2 P

=
65

45

89

=
1,5...5 53 135284 5,2 = =

= 54

Characteristics : pages 3/6 to 3/21

References : pages 3/44 to 3/46

Schemes : page 3/68

3/63

54

129

Dimensions, mounting (continued)

TeSys protection components


3

Thermal-magnetic motor circuit-breakers GV2 ME, GV2 P, GV2 RT

Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05
a 3 l p
GV2 G445 (4 x 45 mm) GV2 G454 (4 x 54 mm) GV2 G472 (4 x 72 mm) l 179 206 260 a 5 224 260 332 p 45 54 72

18

63

45

Number of tap-offs GV2 G445 GV2 G454 GV2 G472

6 269 314 404

7 314 368 476

8 359 422 548

Sets of busbars GV2 G ppp with terminal block GV1 G09

Sets of busbars GV2 G245, GV2 G254, GV2 G272


l
GV2 G245 (2 x 45 mm) GV2 G254 (2 x 54 mm) GV2 G272 (2 x 72 mm) l 89 98 116

Sets of busbars GV2 G554


260

30

GV1 G09

Sets of busbars GV2 G345 and GV2 G354


l
GV2 G345 (3 x 45 mm) GV2 G354 (3 x 54 mm) l 134 152

Dimensions of GV2 RT
X1 12,5 66

Mounting of external operator GV2 AP03


12,3 =

89

X1

7,5

16

44

44,5 53

45

65

1,5...5 133282 6 = =

X1 Electrical clearance = 40 mm for Ue < 690 V

Mounting of GV2 RT
On 35 mm 7 rail On panel with adapter plate GV2 AF02 On pre-slotted mounting plate AM1 PA On mounting rails DZ5 MB

4,2 44,5

13

AF1 EA4

15

35

50/60

50/60

44,5

c
c = 80 on AM1 DP200 (35 x 7.5) c = 88 on AM1 DE200, ED200 (35 x 15)

84,5

35

35 GV2 AF02

DZ5 ME8 DZ5 MB201

Characteristics : pages 3/6 to 3/21

References : pages 3/49 and 3/59

Schemes : page 3/68

3/64

50 60

Dimensions, mounting

TeSys protection components


3

Thermal-magnetic motor circuit-breakers GV3 ME and GV7 R

Motor circuit-breakers GV3 ME


4,5 X1 17,3

Mounting on rail AM1 DE200 or AM1 ED201

(1)

100110

113
X1 Electrical clearance (ISC max) 40 mm for Ue < 500 V, 50 mm for Ue < 690 V (1) Block GV3 A01A07

X1

22

77,5

5,5

120

70,4

122,5

Mounting
On panel On pre-slotted mounting plate AM1 PA

3
100110

= 113 20 20 61,2 21,2 113 20 AF1 EA4

Motor circuit-breakers GV7 R

100110

Motor circuit-breakers with terminal shields or phase barriers GV7 R + GV7 AC01 or AC04
35 = = = =

= 321 = 357

161

125

161 =

81 86 111 (1)
(1) 126 for GV7 Rp220 (2) Phase barriers: GV7 AC04

= 105

(2)
81
(3) Terminal shields: GV7 AC01

(3)

Combination of GV7 R and LC1 F with kit GV7 AC0p


c a
a b c GV7 R + LC1 F115 or 119 334 181 F150 + GV7 AC06 GV7 R + LC1 F185 + 119 338 188 GV7 AC06 GV7 R + LC1 F225 + 131 358 188 GV7 AC07 GV7 R + LC1 F265 + 131 364 215 GV7 AC07 Minimum distance between 2 circuit-breakers mounted side-by-side = 0

Minimum electrical clearance


x2

x1

x1

x2

Painted or insulated metal plate, insulation or insulated bar Bare U y 440 V metal 440 V < U < 600 V plate U u 600 V Characteristics : pages 3/6 to 3/21 References : pages 3/47 to 3/48 Schemes : page 3/69

x1 0

x2 30

5 10 20

35 35 35

3/65

Mounting

TeSys protection components


Thermal-magnetic motor circuit-breakers GV7 R

Panel mounting

Mounting on 2 mounting rails DZ5 MB201


DZ5 ME5 = 125

135

35

35

35

15

35

Flush-mounting

3
47

1 circuit-breaker GV7 R

125

n circuit-breakers GV7 R side-by-side

76

108

=
G 85 85 85 85 85 H 120 120 120 120 120

29

88

== 29

83

= 108

Combination of GV7 R and LC1 F with kit GV7 AC0p


G

GV7 GV7 GV7 GV7 GV7

R+ R+ R+ R+ R+

LC1 LC1 LC1 LC1 LC1

F115 F150 F165 F225 F265

+ GV7 AC06 + GV7 AC06 + GV7 AC06 + GV7 AC07 + GV7 AC07

E 44 46 48 57 60

Characteristics : pages 3/6 to 3/21

References : page 3/48

Schemes : page 3/69

3/66

108

Dimensions, mounting (continued)

TeSys protection components


3

Thermal-magnetic motor circuit-breakers GV7

Spreaders GV7 AC03


114 45 45

Cabling
Smooth terminals Connectors

Z
10,5 a Z 19 Z

30

41

X
70 70

GV7 Rp40Rp150 GV7 Rp220

a 19.5 21.5

Direct rotary handle GV7 AP03, GV7 AP04


Flush-mounting

3
47

I
45 73 76 89

121 155

55 91

36

28

=
97

Direct rotary handle GV7 AP03 or GV7 AP04 with conversion accessory GV7 AP05
Front face cut-out Enclosure viewed from top

9,25 h

120

59

41

100

Door cut-outs require a minimum distance between the centre of the circuit-breaker and the door hinge point u 100 + (h x 5).

125 2

69 120

51

= 100

e = 1 to 3 max

Extended rotary handle GV7 AP01, GV7 AP02


9,25 60 I

60 l = 75
l: 185 min, 600 max The shaft of the extended rotary handle GV7 AP01 or GV7 AP022 must be cut to length: l 126 mm.

Characteristics : pages 3/6 to 3/21

References : page 3/48

Schemes : page 3/69

75

29

3/67

Schemes

TeSys protection components


Thermal-magnetic motor circuit-breakers GV2 ME, GV2 P and GV2 RT

GV2 MEpp and GV2 RT


1/L1 3/L2 5/L3

GV2 Ppp
1/L1 3/L2 4/T2 5/L3 6/T3

2/T1

4/T2

6/T3

Current limiter
GV1 L3
1/L1 3/L2 5/L3

Front mounting add-on contact blocks Instantaneous auxiliary contacts


GV AE1
or

2/T1

GV AE11

GV AE20

11

13

13

21

13 14
E2 E1

14

12

14

22

Side mounting add-on contact blocks Instantaneous auxiliary contacts and fault signalling contacts
GV AD0110 GV AD0101 GV AD1010 GV AD1001

95

53

95

51

97

97

53

98

96

96

52

98

Instantaneous auxiliary contacts


GV AN11
(61) 31 43 (73)

54

Short-circuit signalling contacts


GV AM11

GV AN20
(63) 33 43 (73)

(62) 32

44 (74)

(64) 34

44 (74)

Voltage trips
GV AUppp GV AS ppp GV AXppp
D1 D2

D1

D2

C2

C1

E1

Use of fault signalling contact and short-circuit signalling contact


GV AM11 GV AD10pp

Connection of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME only
10Agl max

E2

1/L1

05

08 06

3/L2

54

5/L3

D1

Short-circuit signalling

Trip signalling

2/T1

4/T2

Characteristics : pages 3/6 to 3/21

References : pages 3/45 to 3/47

Dimensions : pages 3/62 to 3/64

3/68

6/T3

N/C or N/O Start-Stop contact

D2

52

51

24

23

Schemes

TeSys protection components


Thermal-magnetic motor circuit-breakers GV3 ME and GV7 R

Motor circuit-breakers
GV3 ME
3/L2 1/L1 5/L3

Auxiliary contact blocks


GV3 A01
13 21

GV3 A02
13 23

GV3 A03
13 23 31

GV3 A05
13 23 33

GV3 A06
13 23 33

GV3 A07
23 24 13 31 32

14

24

32

14

24

34

14

24

14

22

14

2/T1

Fault signalling contacts


GV3 A08
95

4/T2

6/T3

Voltage trips
GV3 A09
97

GV3 B
D1

24

GV3 D

34

14

U
D2 C2

Motor circuit-breakers
GV7 R
3/L2 1/L1 5/L3

96

98

Add-on auxiliary contacts according to their location (1)


GV7 AE11, GV7 AB11 Location 1 Location 2 C/O contact Trip indication Location 3 Electrical fault indication
82 84

C1

Location 4 C/O contact

12

92

14

94

11

91

81

2/T1

4/T2

6/T3

A self-adhesive label, supplied with the contact, can be affixed to the front face of the circuitbreaker to allow personalised marking according to the function of the contact or contacts. (1) See pages 3/18 and 3/57. GV7 ASppp
C1

Electric trips
GV7 AUppp
D1

GV7 AD111, AD112

97

50 ms

D4

C2

Recommended application schemes GV7 AD111, AD112


Fault indication Contactor opening on overload

98

97

97

KA1 14

13

50 ms

50 ms

Reset

98

98

23

Reset

KA1 A1 22 A1 B1

24

A2

Associated components KA1: CA2 KN or CAD N

Associated components KA1: CAD N + LA6 DK10 or RHK KM1: LC1 D or LC1 F

Characteristics : pages 3/6 to 3/21

References : pages 3/47 and 3/48

Dimensions : pages 3/65 to 3/67

A2

KA1

Overload fault

KA1

KM1

21

21

24

22

3/69

Dimensions, mounting

TeSys protection components


3

Magnetic motor circuit-breakers GV2 L and GV2 LE

GV2 L

GV AD, AM, AN, AU, AS


Block GV AD, AM, AN Block GV AU, AS

GV2 AK00
14 98

X1

89

45

15

82

X2

26

50

44,5

61

9,3

9,3 81 (1)
(1) Maximum

18 44,5

X1 Electrical clearance = 40 mm for Ue y 415 V, or 80 mm for Ue = 440 V, or 120 mm for Ue = 500 and 690 V. X2 = 40 mm.

Mounting of GV2 L
On rail AM1 DE200, AM1 ED200 (35 x 15) On panel On pre-slotted mounting plate AM1 PA

Adapter plate GK2 AF01

AF1 EA4

35

32 55 5
5,5 45

84

84

44,5

45

106

13,5

13,5

24

9,5

35

54

7.5 mm height compensation plate GV1 F03

13

35

GV2 LE

39

GV AD, AM, AN, AU, AS


Block GV AD, AM, AN Block GV AU, AS

GV AE

X1

15
10

89

45

12,5

X1

7,5

16

44 66

44,5

9,3

9,3 81 (1)

18

X1 Electrical clearance = 40 mm for Ue y 690 V.

(1) Maximum On pre-slotted plate AM1 PA On rails DZ5 MB201

Mounting of GV2 LE
On 35 mm 7 rail On panel with adapter plate GV2 AF02

AF1 EA4

44,5

15

35

44,5

50/60

50/60

c
c = 80 on AM1 DP200 (35 x 7.5) and 88 on AM1 DE200, ED200 (35 x 15) Characteristics : pages 3/6 to 3/21

84,5

4,2 35
35 GV2 AF02 DZ5 ME8 DZ5 MB201

References : page 3/50

Schemes : page 3/73

3/70

50 60

1055

44,5

135

Dimensions, mounting (continued)

TeSys protection components


3

Magnetic motor circuit-breakers GV2 L and GV2 LE

Mounting of external operator GV2 AP01 or GV2 AP02 for GV2 L

65

1,5...5 53 135284 6 5,2 = =

Mounting of external operator GV2 AP03 for GV2 LE


12,3

65

1,5...5 53 133282 6 = =

Door cut-out
4x3,5 43

13

= = 54 =

Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05
a 3 18 l p

63

45

GV2 G445 (4 x 45 mm) GV2 G454 (4 x 54 mm) GV2 G472 (4 x 72 mm)

l 179 206 260 a 5 224 260 332

=
p 45 54 72 Number of tap-offs GV2 G445 GV2 G454 GV2 G472 6 269 314 404

54

7 314 368 476

8 359 422 548

Characteristics : pages 3/12 and 3/13

References : page 3/50

Schemes : page 3/73

3/71

Dimensions, mounting

TeSys protection components


3

Magnetic motor circuit-breakers GV2 L, GV2 LE and GK3

Sets of busbars GV2 Gppp with terminal block GV1 G09


GV1 G09
30

Sets of busbars GV2 G245, GV2 G254, GV2 GR272


l

GV2 G245 (2 x 45 mm) GV2 G254 (2 x 54 mm) GV2 G272 (2 x 72 mm)

l 89 98 116

Set of busbars GV2 G554


260

Sets of busbars GV2 G345 and GV2 G354


l

3
GV2 G345 (3 x 45 mm) GV2 G354 (3 x 54 mm) l 134 152

GK3 EF
X1

GK3 EF + 4 GK2 AX
38 28

105

120

45

80

15

70

4,5

X1

Number of GK2 AX 0 1 2 66 74.8 83.5

3 92.5

4 101

X1 Electrical clearance, 40 mm for Ue y 690 V.

Mounting
On mounting rail AM1 EDpp or AM1 Dpppp On panel

4x4,5

115,5

115,5

20

Mounting of external operator GK3 AP03

Door cut-out
4x3,5 43

65

120

105

1,55 53

= 54

(1)

(1) 150 min, 305 max. with operating shaft, 97 without operating shaft

Characteristics : pages 3/12 to 3/15

References : pages 3/50 and 3/51

Schemes : page 3/73

3/72

54

Schemes

TeSys protection components


Magnetic motor circuit-breakers GV2 L, GV2 LE and GK3

GV2 Lpp
3/L2 1/L1 5/L3

GV2 LEpp
3/L2 4/T2 1/L1 5/L3 6/T3

2/T1

4/T2

6/T3

Front mounting add-on contact blocks Instantaneous auxiliary contacts


GV AE1
OR

GV AE11
21

GV AE20

13

13

13

11

23

2/T1

14

Side mounting add-on contact blocks Instantaneous auxiliary contacts and fault signalling contacts
GV AD0110 GV AD0101 GV AD1010 GV AD1001

95

53

12

14

22

14 51

95

97

24 53

97 98

96

96

52

98

54

54

Instantaneous auxiliary contacts


GV AN11
(61) 31 43 (73)

Short-circuit signalling contacts


GV AM11

GV AN20
(63) 33 43 (73)

(62) 32

44 (74)

(64) 34

44 (74)

Voltage trips
GV AUppp GV ASppp

D1

D2

Motor circuit-breakers GK3 EF


1 3 5

Start-Stop signalling contact blocks


GK2 AX10
13

GK2 AX20
13 23

C2

C1

GK2 AX50
13 21

14

05

08 06

14

14

Fault signalling contact blocks


GK2 AX12
97

GK2 AX22
97 07

24

GK2 AX52
97 05

98

98

Characteristics : pages 3/12 to 3/15

References : pages 3/50 and 3/51

08

Dimensions : pages 3/70 to 3/72

98

06

22

52

51

3/73

Selection guide

Protection components
Thermal-magnetic circuit-breakers for the protection of control circuits, solenoid valves and transformers

Applications

Protection of industrial equipment control circuits and of single-phase loads

Tripping threshold on short-circuit

57 In

1216 In

Operational current

0.5 and 1 A

0.520 A

Maximum operational voltage

415 V

250 V

Number of poles

1 + neutral

Breaking capacity (Icu) conforming to IEC 60947-2

50 kA at 415 V

1.550 kA at 415 V

1.550 kA at 250 V

Device type

GB2 CS

GB2 CB

GB2 CD

Pages

3/81

3/80

3/80

3/74

Protection of transformers

Single-phase y 5000 VA/415 V Primary

3-phase y 10 kVA/415 V Secondary

About 20 In

0.2523 A

415 V

690 V

1 + neutral

1.550 kA at 415 V

1.550 kA at 250 V

15100 kA at 415 V

GB2 DB

GB2 DB

GB2 CD

GV2 RT

3/80

3/80

3/80

3/49

3/75

Presentation, selection

Protection components

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Presentation
GB2 thermal-magnetic circuit-breakers protect and isolate the control circuits of industrial equipment with contactor coils, transformers. They protect and isolate single-phase auxiliary circuits such as solenoid valves, electro-brakes, battery chargers, supplied from the control circuit voltage. GB2 CB, GB2 CD, GB2 DB 12 ratings are available, from 0.5 to 20 A, in single-pole (GB2 CB), single-pole + neutral (GB2 CD) and 2-pole (GB2 DB) versions. They have a magnetic tripping threshold set at between 12 and 16 In to withstand the current peaks generated by many industrial components. GB2 CS 2 ratings are available, 0.5 and 1 A, in single-pole version. The magnetic tripping threshold is set between 5 and 7 In.

Functions, installation Clip-on fixing onto all types of 35 mm 5 rails, on 4 rails and on Telequick mounting plates. Upstream and downstream marking by means of AB1 clip-in markers. Clear indication of I and O positions on the operator. Tamper-proof device which requires no special maintenance (fixed magnetic and thermal tripping thresholds).

Selection for the protection of circuits supplied by transformers


Single-phase transformers. Magnetising peak: 20 In. Operation of magnetic trips: 13 In.
Power VA 40 63 100 160 250 400 630 1000 1600 2000 2500 3000 4000 5000 Primary (1) 220/240 V 380/415 V GB2 DB05 GB2 DB05 GB2 DB05 GB2 DB06 GB2 DB07 GB2 DB07 GB2 DB08 GB2 DB10 GB2 DB14 GB2 DB20 GB2 DB21 GB2 DB22 GB2 DB22 GB2 DB05 GB2 DB05 GB2 DB06 GB2 DB06 GB2 DB07 GB2 DB08 GB2 DB09 GB2 DB14 GB2 DB14 GB2 DB20 GB2 DB20 GB2 DB21 GB2 DB22 Secondary 24 V 48 V GB2 CD07 GB2 CD06 GB2 CD08 GB2 CD10 GB2 CD14 GB2 CD16 GB2 CD22 GB2 CD07 GB2 CD07 GB2 CD09 GB2 CD12 GB2 CD14 GB2 CD21

110 V GB2 CD05 GB2 CD06 GB2 CD06 GB2 CD07 GB2 CD08 GB2 CD09 GB2 CD12 GB2 CD16 GB2 CD22

220 V GB2 CD05 GB2 CD05 GB2 CD05 GB2 CD06 GB2 CD07 GB2 CD07 GB2 CD08 GB2 CD10 GB2 CD14 GB2 CD16 GB2 CD20 GB2 CD21 GB2 CD22

(1) If the breaking capacity of the GB2 is insufficient, use a GV2 RT with 2 poles connected in series, see page 3/49.

Characteristics : pages 3/77 to 3/79

References : pages 3/80 and 3/81

Dimensions : page 3/81

Schemes : page 3/81

3/76

Characteristics

Protection components

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breaker type

GB2 CB

GB2 CD

GB2 DB

GB2 CS

Environment
Conforming to standards Product certifications Protective treatment Degree of protection Shock resistance Vibration resistance Ambient air temperature around the device Flame resistance Maximum operating altitude Operating position IEC 60947-1, 947-2, EN 60947-1, 60947-2 CSA, NEMKO, UL NEMKO, UL TC IP 20 22 gn for 20 ms 5 gn (5110 Hz) - 40+ 80 - 20+ 60 960 3000

Conforming Conforming Conforming Storage Operation Conforming

to IEC 60529 to IEC 60068-2-27 to IEC 60068-2-6 C C C m

to IEC 60695-2-1

In relation to normal vertical mounting plane

3
GB2 CB,CD, CS Cabling Solid cable Flexible cable with cable end Tightening torque mm 2 mm 2 N.m Minimum c.s.a. 1 x 0.75 1 x 0.75 1.2 GB2 DB Maximum c.s.a. 1 x 6 or 2 x 4 1 x 4 or 2 x 2.5

Technical characteristics
Utilisation category Rated operational voltage (Ue) Conforming to IEC 60947-2 Conforming to IEC 60947-2 Conforming to CSA C22-2 Nr 14 and UL 1077 Conforming to IEC 60947-2 Conforming to IEC 60947-2 V V Hz kV W C.O. C A 415 (1) 277 50/60 4 2 8000 - 20 - 10 0 A 250 50/60 4 2 8000 + 10 + 20 1 A 415 277 50/60 4 2 8000 + 30 0.95 1216 In + 40 0.90 A 415 (1) 50/60 4 1.9 8000 + 50 0.85 57 In + 60 0.80

Rated operational frequency Rated impulse withstand voltage (U imp) Total power dissipated per pole Mechanical and C.O.: Closing - Opening electrical durability Operational current According to the permissible correction coefficient ambient temperature (a or c) Correction coefficient Tripping threshold Of the magnetic trips

1.2 1.15 1216 In

1.1 1.05 1216 In

(1) One GB2 circuit-breaker on each live conductor.

Tripping curves
Average operating time at 20 C without prior current flow (cold state) GB2 CB, GB2 CD, GB2 DB GB2 CS
120 60 20 10 5 2 1 20 10 5 2 1 500 200 100 50 20 10 5 2 1 1,05 2 3 4 5 6 8 1,5 10 100 x In 120 60 20 10 5 2 1 20 10 5 2 1 500 200 100 50 20 10 5 2 1 1,05 2 3 4 5 6 8 1,5 10 100 x In

Minutes

Seconds

Milliseconds

Presentation, selection : page 3/76

References : pages 3/80 and 3/81

Dimensions : page 3/81

Milliseconds

Seconds

Minutes

Schemes : page 3/81

3/77

Characteristics (continued)

Protection components

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breaker type Rating Breaking capacity conforming to IEC 60947-2 a 50/60 Hz 110 V Icu Ics % (1) Icu Ics % (1) Icu Ics % (1) aM gG aM gG aM gG A kA

GB2 CB05 CB06 CB07 CB08 CB09 CB10 CB12 CB14 CB16 CB20 CB21 CB22 0.5 1 2 3 4 5 6 8 10 12 16 20 50 100 50 25 50 25 g g g g g g 50 50 50 25 50 25 g g g g g g 15 50 15 25 15 25 20 25 16 25 16 25 10 50 3 50 3 50 25 32 20 32 20 32 6 50 3 50 3 50 25 32 20 32 20 32 3 75 2 75 2 75 40 50 32 40 32 40 3 75 1.5 75 1.5 75 40 50 32 40 32 40 3 75 1.5 75 1.5 75 50 63 40 50 40 50 2 75 1.5 75 1.5 75 50 63 40 50 40 50 2 75 1.5 75 1.5 75 63 80 50 63 50 63 2 75 1.5 75 1.5 75 63 80 50 63 50 63 2 75 1.5 75 1.5 75 63 80 50 63 50 63

230/240 V

kA

400/415 V

kA

Associated fuses, if required 110 V if Isc > breaking capacity Icu conforming to IEC 60947-2

A A A A A A

3
Circuit-breaker type Rating Breaking capacity conforming to IEC 60947-2 a 50/60 Hz

230/240 V

400/415 V

A 110 V Icu Ics % (1) Icu Ics % (1) aM gG aM gG kA

GB2 CD05 CD06 CD07 CD08 CD09 CD10 CD12 CD14 CD16 CD20 CD21 CD22 0.5 1 2 3 4 5 6 8 10 12 16 20 50 100 50 25 g g g g 50 50 50 25 g g g g 15 50 15 25 20 25 16 25 10 50 3 50 25 32 20 32 6 50 3 50 25 32 20 32 3 75 2 75 40 50 32 40 3 75 1.5 75 40 50 32 40 3 75 1.5 75 50 63 40 50 2 75 1.5 75 50 63 40 50 2 75 1.5 75 63 80 50 63 2 75 1.5 75 63 80 50 63 2 75 1.5 75 63 80 50 63

230/ 240 V

kA

Associated fuses, if required 110 V if lsc > breaking capacity Icu conforming to IEC 60947-2 230/240 V

A A A A

Circuit-breaker type Rating Breaking capacity conforming to IEC 60947-2 a 50/60 Hz 110 V lcu Ics % (1) lcu Ics % (1) lcu Ics % (1) aM gG aM gG aM gG A kA

GB2 DB05 DB06 DB07 DB08 DB09 DB10 DB12 DB14 DB16 DB20 DB21 DB22 0.5 1 2 3 4 5 6 8 10 12 16 20 50 100 50 25 50 25 g g g g g g 50 50 50 25 50 25 g g g g g g 15 50 15 25 15 25 20 25 16 25 16 25 10 50 3 50 3 50 25 32 20 32 20 32 6 50 3 50 3 50 25 32 20 32 20 32 3 75 2 75 2 75 40 50 32 40 32 40 3 75 1.5 75 1.5 75 40 50 32 40 32 40 3 75 1.5 75 1.5 75 50 63 40 50 40 50 2 75 1.5 75 1.5 75 50 63 40 50 40 50 2 75 1.5 75 1.5 75 63 80 50 63 50 63 2 75 1.5 75 1.5 1.5 63 80 50 63 50 63 2 75 1.5 75 75 75 63 80 50 63 50 63

230/240 V

kA

400/415 V

kA

Associated fuses, if required 110 V if lsc > breaking capacity Icu conforming to IEC 60947-2 230/240 V

A A A A A A

400/415 V

g Fuse not required. Breaking capacity Icu > lsc.

(1) As % of Icu.

Presentation, selection : page 3/76

References : pages 3/80 and 3/81

Dimensions : page 3/81

Schemes : page 3/81

3/78

Characteristics (continued)

Protection components

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breaker type Breaking capacity (lcu) conforming to IEC 60947-2 c Operational current conforming to IEC 60947-5-1 c DC-12 24 V 48 V 24 V 48 V 24 V 48 V kA kA A A A A

GB2 pp05 pp06 pp07 pp08 pp09 pp10 pp12 pp14 pp16 pp20 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1 1 1 1 1 1 1 1 0.5 0.5 0.5 0.5 GB2 CS05 0.5 50 100 50 25 50 25 1.5 1 0.5 0.5 0.5 0.5 48 (3) (3) (3) (3) (3) (3) 48 (3) (3) (3) (3) (3) (3) 48 (3) (3) (3) (3) (3) (3) 110 31 39 52 78 130 200 110 (3) (3) (3) (3) (3) (3) 110 (3) (3) (3) (3) (3) (3) 230 365 460 610 910 1520 2400 230 230 290 390 580 970 1500 230 46 60 80 120 190 310 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 8 8 8 8 10 10 10 12 12 12

pp21 1.5 16 16 16

pp22 1.5 20 20 20

DC-13

Circuit-breaker type Rating Breaking capacity conforming to IEC 60947-2 a 50/60 Hz 110 V lcu lcs % (1) A kA

CS06 1 50 100 50 25 50 25 1.5 1 1 1 1 1 48 6 8 10 15 26 41 48 (3) (3) (3) (3) (3) (3) 48 (3) (3) (3) (3) (3) (3) 110 85 110 145 220 360 580 110 56 70 95 140 230 375 110 13 17 22 34 56 90 230 230 290 380 570 950 1500 230 230 290 380 570 950 1500 230 100 130 170 250 420 680

230/240 V lcu lcs % (1) 400/415 V lcu (2) lcs % (1) Breaking capacity (lcu) conforming to IEC 60947-2 c Operational current conforming to IEC 60947-5-1 c DC-12 24 V 48 V 24 V 48 V 24 V 48 V

kA

kA

kA kA A A A A V m m m m m m V m m m m m m V m m m m m m

DC-13

Maximum permissible line length for star-delta starting (length of cable containing 2 or more conductors)

With contactors LCp D09 D18

Operational voltage C.s.a. 060 mm2 0.75 mm2 1 mm2 1.5 mm2 2.5 mm2 4 mm2

With contactors LCp D25D32

Operational voltage C.s.a. 0.60 mm2 0.75 mm2 1 mm2 1.5 mm2 2.5 mm2 4 mm2

With contactors LCp D40D80

Operational voltage C.s.a. 0.60 mm2 0.75 mm2 1 mm2 1.5 mm2 2.5 mm2 4 mm2

(1) As % of Icu. (2) One GB2 CS circuit-breaker on each live conductor. (3) Use relays.

Presentation, selection : page 3/76

References : pages 3/80 and 3/81

Dimensions : page 3/81

Schemes : page 3/81

3/79

References

Protection components

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

534268

Circuit-breakers with magnetic tripping threshold: 12 to 16 In


Single-pole
Conventional rated thermal current Ith (1) A 0.5 1 2 3 4 5 6 8 10 12 16 20 Magnetic tripping current Id 20 % A 6.6 14 26 40 52 66 83 108 138 165 220 270 Sold in lots of Unit reference Weight

GB2 CBpp

3
534269

6 6 6 6 6 6 6 6 6 6 6 6

GB2 CB05 GB2 CB06 GB2 CB07 GB2 CB08 GB2 CB09 GB2 CB10 GB2 CB12 GB2 CB14 GB2 CB16 GB2 CB20 GB2 CB21 GB2 CB22

kg 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060 0.060

Single-pole + neutral
Conventional rated thermal current Ith (1) A 0.5 1 2 3 4 5 6 8 10 12 16 20 Magnetic tripping current Id 20 % A 6.6 14 26 40 52 66 83 108 138 165 220 270 Sold in lots of Unit reference Weight

GB2 CDpp

6 6 6 6 6 6 6 6 6 6 6 6

GB2 CD05 GB2 CD06 GB2 CD07 GB2 CD08 GB2 CD09 GB2 CD10 GB2 CD12 GB2 CD14 GB2 CD16 GB2 CD20 GB2 CD21 GB2 CD22

kg 0.070 0.070 0.070 0.070 0.070 0.070 0.070 0.070 0.070 0.070 0.070 0.070

534270

2-pole
Conventional rated thermal current Ith (1) A 0.5 1 2 3 4 5 6 8 10 12 16 20 (1) Conforming to IEC 60947-1. Magnetic tripping current Id 20 % A 6.6 14 26 40 50 66 83 108 138 165 220 270 Sold in lots of Unit reference Weight

GB2 DBpp

3 3 3 3 3 3 3 3 3 3 3 3

GB2 DB05 GB2 DB06 GB2 DB07 GB2 DB08 GB2 DB09 GB2 DB10 GB2 DB12 GB2 DB14 GB2 DB16 GB2 DB20 GB2 DB21 GB2 DB22

kg 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115 0.115

Presentation, selection : page 3/76

Characteristics : pages 3/77 to 3/79

Dimensions : page 3/81

Schemes : page 3/81

3/80

References (continued), dimensions, schemes

Protection components
3

Thermal-magnetic circuit-breakers GB2 for the protection of industrial equipment control circuits

Circuit-breakers with magnetic tripping threshold: 5 to 7 In


Single-pole
534271

Conventional rated thermal current Ith (1) A 0.5

Magnetic tripping current Id 20 % A 3.3

Sold in lots of

Unit reference

Weight

GB2 CS05

kg 0.055

GB2 CS06

0.055

GB2 CSpp (1) Conforming to IEC 60947-1.

3
Description Sold in lots of 1 Unit reference GB2 G210 Weight kg 0.100

Accessories for circuit-breakers GB2 CB, DB and CS

Busbar set for supply to 10 GB2 DB or 20 GB2 CB or GB2 CS with 2 connectors

Supply connector

10

GB2 G01

Dimensions
GB2 CBpp, GB2 CDpp, GB2 CSpp GB2 DBpp

74

82 82 75 79 67

15

85 85 78 82 70

30

Marking: up to twelve AB1 R clip-in markers.

Schemes
GB2 CBpp GB2 CDpp
3/L2 (13)

GB2 DBpp
1/L1 3/L2

GB2 CSpp

1/L1

4/T2 (14)

1/L1

2/T1

2/T1

2/T1

Presentation, selection : page 3/76

Characteristics : pages 3/77 and 3/79

4/T2

2/T1

1/L1

74

3/81