DSEGenset

DSE7520
AUTO MAINS FAILURE & INSTRUMENTATION CONTROL MODULE
DSE130 DSE157
MODEM PC PC 9 232 485 3 3

DSE EXPANSION

RS232 AND RS485

P810

CONFIGURABLE INPUTS

DC OUTPUTS

ANALOGUE SENDERS

EMERGENCY STOP

DC POWER SUPPLY 8-35V

DSE7520
7
OTHER

MAINS (UTILITY) SENSING

N/C VOLT FREE OUTPUT

N/O VOLT FREE OUTPUT

GENERATOR SENSING

VOLTS

CURRENT

CURRENT

VOLTS

1ph 2ph 3ph N

1ph

1ph 2ph 3ph E N

+
DEUTZ ISUZU PERKINS CATERPILLAR MTU VOLVO CUMMINS SCANIA

CHARGE ALTERNATOR

FUEL & CRANK OUTPUTS

ELECTRONIC ENGINES & MAGNETIC PICK-UP

D+ W/L

1ph 2ph 3ph N

ISSUE 6

DSE Model 7520 AMF Controller Operators Manual

4.2
4.2.1

TYPICAL WIRING DIAGRAMS


3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION

NOTE:- Earthing the neutral conductor before the neutral CT allows the module to read earth faults after the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor after the neutral CT allows the module to read earth faults before the CT only (Restricted to generator / upstream of the CT)

NOTE:- The MAINS CT is only required on for true peak lop systems where the mains is held at a constant level and the generator provides variable power to the load.

057-090

7520 OPERATING MANUAL ISSUE 10.1 06/11/08 AM

25

DSE Model 7520 AMF Controller Operators Manual

4.3

ALTERNATIVE TOPOLOGIES

The 7000 controller is factory configured to connect to a 3 phase, 4 wire Star connected alternator. This section details connections for alternative AC topologies. Ensure to configure the 7000 series controller to suit the required topology. NOTE:- Further details of module configuration are contained within the DSE7000 Series configuration software manual (DSE part number 057-078)

4.3.1

3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION

26

057-090

7520 OPERATING MANUAL ISSUE 10.1 06/11/08 AM

DSE Model 7520 AMF Controller Operators Manual

4.3.2

SINGLE PHASE WITH RESTRICTED EARTH FAULT

NOTE:- Earthing the neutral conductor before the neutral CT allows the module to read earth faults after the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor after the neutral CT allows the module to read earth faults before the CT only (Restricted to generator / upstream of the CT)

4.3.3

SINGLE PHASE WITHOUT EARTH FAULT

057-090

7520 OPERATING MANUAL ISSUE 10.1 06/11/08 AM

27

DSE Model 7520 AMF Controller Operators Manual

4.3.4

2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT

NOTE:- Earthing the neutral conductor before the neutral CT allows the module to read earth faults after the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor after the neutral CT allows the module to read earth faults before the CT only (Restricted to generator / upstream of the CT)

4.3.5

2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT

28

057-090

7520 OPERATING MANUAL ISSUE 10.1 06/11/08 AM

DSE Model 7520 AMF Controller Operators Manual

4.3.6

2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT

NOTE:- Earthing the neutral conductor before the neutral CT allows the module to read earth faults after the CT only (Restricted to load / downstream of the CT) Earthing the neutral conductor after the neutral CT allows the module to read earth faults before the CT only (Restricted to generator / upstream of the CT)

4.3.7

2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING

057-090

7520 OPERATING MANUAL ISSUE 10.1 06/11/08 AM

29

DSE Model 7520 AMF Controller Operators Manual

4.3.8

3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING

30

057-090

7520 OPERATING MANUAL ISSUE 10.1 06/11/08 AM