Distribution cutouts

Type ICX Outdoor open type cutout

Product features 7.8 kV, 15 kV, 15/27 kV, 27 kV, or 38 kV on 100 A 7.8 kV, 15 kV, and 15/27 kV only on 200 A 110, 125, 150, 170, or 180 kV BIL 180 kV BIL available as V silicone only 100 A, 200 A continuous current fused and up to 16 kA interrupting current on 15 kV, 100 A only 300 A disconnect blade Porcelain, polymer concrete, or silicone insulators available Seacoast design Cutout/arrester combo Kick-out spring available for the 100 A tube only Description The ICX cutout is used on overhead distribution systems to provide overcurrent protection and visible indication of fuse operation. The ICX provides a visible break sectionalizing point for maintenance personnel and is equipped with hooks for use with a portable loadbreak tool. This allows the ICX to be used as a loadbreak switch to open the circuit with load current flowing. Porcelain, polymer concrete, or silicone insulators, seacoast design, cutout/arrester combination, and kickout spring options are available on certain models. Ratings The ICX is offered in several frame sizes to properly match each system BIL. Each fuse support has universal contacts that accommodate a 100 A fuseholder, a 200 A fuseholder, or a 300 A disconnect blade. Design features The ICX 100 A fuse is provided with a moisture-proof tube as a standard offering. Cutouts perform by expelling gases during interruption from the bottom of the fuse tube. For the highest interrupting rating, a link extender rod is attached to the fuse tube cap, improving the efficiency of gas expulsion and arc interruption. Fuse tubes are clearly labeled to indicate interrupting capability. Interchangeability The ICX cutout is designed to be electrically and mechanically interchangeable with the S&C type XS, A.B. Chance type C, and Cooper type L cutouts. Testing has confirmed the performance of the ICX fuseholder and fuse support with S&C and Chance. Standards and design testing The ICX cutout meets or exceeds all applicable requirements of IEEE C37.41 and C37.42 standards. Refer to Ordering Instructions section for styles that meet CSA 0310-09 standards. Warranty A ten-year warranty is offered on silicone and polymer concrete ICX cutouts and a five-year warranty is offered on porcelain ICX cutouts, provided ABB parts are used exclusively.

Options and construction details

Silicone rubber Silicone rubber has been used for more than thirty years as an outdoor insulation material and is the fastest growing choice for polymeric material for medium and high voltage outdoor insulation. Silicone is used for its superior performance, durability, and insulation properties. It has the unique ability to maintain its hydrophobicity and offers greater stability against heat and ultraviolet radiation compared to other polymers. In addition, silicone cutouts are 30% - 50% lighter than porcelain units. Silicone insulators are available in all ratings up to 180 kV BIL. Polymer concrete ABB has been using polymer concrete for more than twenty years. Available in 110 and 125 kV BIL ratings, polymer concrete provides a safe, shatter-proof design with molded-in rods to prevent moisture penetration. Because it resists damage from freeze/thaw cycles, the material is an excellent alternative to porcelain in colder climates. Polymer concrete is a fieldproven material that provides excellent electrical properties and dielectric strengths, as well as superior mechanical durability. Kick-out spring All ICX 100 A fuse tubes are available with an optional kick-out spring. The spring assists the drop-out operation by increasing the kick-out force on the tube. Arrester combinations ABB offers a combination ICX cutout with an arrester option. This combination unit is pre-assembled at the factory and provides overall savings by reducing installation time and accumulated costs that result from independently purchased parts. ICX combination units are available with various mounting brackets to fulfill industry requirements. The combo units are equipped with normal duty, heavy duty, or riser pole polymer metal oxide arresters.

Fuse tube construction The ICX cutouts utilize two different types of fuse tubes: a moisture-proof fuse tube or a horn fiber fuse tube. The moisture proof fuse tube is standard on all 100 A designs and is notated by the letter M in the 8th digit of the style number (refer to Ordering Instructions on pages 4-5). The moisture-proof tube reduces swelling of the liner that can create problems with interruption. The 200 A design utilizes a horn fiber fuse tube and is notated by the letter A in the 8th digit of the style number (refer to Ordering Instructions on pages 4-5). This fuse tube is composed of a horn fiber liner surrounded by a glass filament wound outer shell. Both designs have a durable tube that withstands the rigors of high fault current interruptions. In addition, the tube is applied with paint to provide protection against the effects of ultraviolet rays. Voltage levels Single voltage rated cutouts can be applied on any single or three-phase system where the line-to-line voltage does not exceed the cutout rating. Dual voltage rated cutouts are suitable on single-phase circuits where maximum line-to-ground voltage does not exceed the value shown to the left of the slash (for example, does not exceed 15 kV in 15/27 kV). ICX cutouts may be used on three-phase circuits that are solidly grounded and where the maximum line-to-line voltage does not exceed the value shown to the right of the slash (for example, does not exceed 27 kV in 15/27 kV).

2 Type ICX outdoor cutout | Product bulletin

Dimensions

A B

2.25 [57]

.312 NEMA "A" BRKT .375 NEMA "B" BRKT 3.0-4.0 [76-102]

7.75 [197] C 4.12-5.12 [105-130] 1.56 [40]

FR 17-20 DEG 1.00 [25]

Note: Metric dimensions are displayed in [mm].

Unit dimensions (in) kV Class 7.8 or 15 15/27 or 27 27 or 38 27 or 38 27 or 38 BIL (kV) 110 125 150 150 170 A 12.79 13.30 13.30 13.30 13.96 B 7.33 7.84 7.84 7.84 8.51 C 6.50 8.17 8.17 8.17 10.42 D 8.55 10.25 10.25 10.25 13.00 E 6.60 6.08 6.08 6.08 5.27 FR 11.41 14.88 14.88 14.88 18.36 Porcelain 9.1 12.8 17.0 26.2

Creep (in) Silicone 14.96 18.90 18.90 23.62 Creep (mm) E 168 154 154 154 134 FR 290 378 378 378 466 Porcelain 231 325 432 665 Silicone 380 480 480 600 Polymer concrete 216 305 Porcelain 6.4 9.0 12.0 16.1 Polymer concrete 8.5 12.0 Porcelain 14.0 20.0 26.5 35.5

Weight (lb) Silicone 9.3 9.5 10.2 10.5 Weight (kg) Silicone 4.2 4.3 4.6 4.8 Polymer concrete 5.4 6.4 Polymer concrete 11.8 14.0 -

Unit dimensions (mm) kV Class 7.8 or 15 15/27 or 27 27 or 38 27 or 38 27 or 38 BIL (kV) 110 125 150 150 170 A 325 338 338 338 356 B 186 199 199 199 216 C 165 208 208 208 265 D 217 260 260 260 330

Bracket dimensions
.312 [8]
.375 [10]

.38 [10]

7.8 [198]

7.8 [198]

7.8 [198] 1.5 [38]

1.6 [40] 2.6 [67]


2.6 [67]

1.6 [40]

5.4 [137]

NEMA A bracket

NEMA B bracket

Extended bracket Product bulletin | Type ICX outdoor cutout 3

Ordering instructions

ICX cutout arrester combination


Digit 2 Digit 4
Cutout cap
S = 100A Solid cap L = 100A Link extender T = 200A Solid cap M = 200A Link extender

Digit 11 Digit 6
Arrester type

Voltage level
1 = 15 kV 2 = 27 kV 3 = 38 kV (use 150 kV BIL insulator)

Cutout insulator material


(Blank) = Porcelain J = Silicone Z = Polymer concrete (only available for 110 and 125 kV BIL cutouts)

Digit 9

C = Polymer normal duty H = Polymer heavy duty R = Polymer riser pole

Cutout terminals
1 = Clamshell 2 = Eyebolt

C
Digit 3
Insulator BIL

Digit 5

Bracket

Digits 7-8
03 = 3 kV 06 = 6 kV 09 = 9 kV 10 = 10 kV

Arrester voltage
15 = 15 kV 18 = 18 kV 21 = 21 kV 24 = 24 kV 27 = 27 kV

Digit 10

1 = 110 kV BIL 2 = 125 kV BIL 5 = 150 kV BIL

U = Standard combo Contact factory for other options

Special options 1 = None


8 = 12" lead B = Arrester bird guard S = Seacoast cutout X = No arrester but in combo box

12 = 12 kV

ICX 15 kV
Digit 4 Digit 2
Terminal connectors
N = No terminal C = Clamshell E = Eyebolt

Digit 6

Special options

Digit 11

Additional options

N = None F = Wildlife guard

Insulator BIL
1 = 110 kV BIL

K = Kick-out spring on fuse tube (100 A only) S = Seacoast design silicone

1
Digit 3
Fuse supports

Digit 5

Bracket
N = No bracket A = NEMA A B = NEMA B L = Extended

Digits 7-10
Fuseholder
AM11 = 100A, 10kAIC, solid cap LM11 = 100A, 16kAIC, link extender KA21 = 200A, 10kAIC, link extender PA21 = 200A, 12kAIC, link extender (rated 7.8 kV) CA31 = 300A, solid blade 0000 = Fuse support only (no tube)

N = Porcelain J = Silicone Z = Polymer concrete S = Seacoast design porcelain

ICX 27 kV
Digit 2
Insulator BIL
2 = 125 kV BIL* 4 = 150 kV BIL 600 mm creep (silicone only) 5 = 150 kV BIL
8 = 180 kV BIL 750 mm creep (silicone only)

Digit 11 Digit 4 Digit 6

Additional options
K = Kick-out spring on fuse tube (100 A only) S = Seacoast design silicone

Terminal connectors
N = No terminal C = Clamshell E = Eyebolt

Special options
N = None F = Wildlife guard

* Y = 125 kV BIL silicone insulator to meet CSA C310-09

X
Digit 3
Fuse supports

Digit 5

Bracket
N = No bracket B = NEMA B L = Extended

Digits 7-10
Fuseholder
AM12 = 100A, 8kAIC, solid cap MM12 = 100A, 12kAIC, link extender BA22 = 200A, 10kAIC, solid cap (tube rated 15 kV) VA22 = 200A, 12kAIC, link extender WA22 = 200A, 10kAIC, link extender (tube rated 15/27 kV) DA32 = 300A, Solid blade 0000 = Fuse support only (no tube)

N = Porcelain J = Silicone Z = Polymer concrete (125 kV BIL only) S = Seacoast design porcelain

4 Type ICX outdoor cutout | Product bulletin

ICX 38 kV, 150 or 180 kV BIL


Digit 2
Insulator BIL

4 = 150 kV BIL 600mm creep (silicone only) 5 = 150 kV BIL 8 = 180 kV BIL 750mm creep (silicone only)

Digit 4

Terminal connectors
N = No terminal C = Clamshell E = Eyebolt

Digit 6

Special options
N = None F = Wildlife guard

Digit 11

Additional options
K = Kick-out spring on fuse tube S = Seacoast design silicone

X
Digit 3
Fuse supports

Digit 5

Bracket
N = No bracket B = NEMA B L = Extended

Digits 7-10
Fuseholder
TM12 = 100A, 10kAIC, link extender DA32 = 300A, solid blade 0000 = Fuse support only (no tube)

N = Porcelain J = Silicone S = Seacoast design porcelain

ICX 38 kV, 170 kV BIL


Digit 4 Digit 2
Terminal connectors
N = No terminal C = Clamshell E = Eyebolt

Digit 6

Special options
N = None F = Wildlife guard

Digit 11

Additional options
K = Kick-out spring on fuse tube

Insulator BIL

7 = 170 kV BIL

7
Digit 3
Fuse supports

Digit 5

Bracket

Digits 7-10
Fuseholder
RM15 = 100A, 10kAIC, link extender FA34 = 300A, solid blade RM14 = 100A, 12kAIC, link extender (tube rated for 27 kV) SA24 = 200A, 10kAIC, link extender (tube rated for 15/27 kV) 0000 = Fuse support only (no tube)

N = Porcelain S = Seacoast design porcelain

N = No bracket B = NEMA B L = Extended

Product bulletin | Type ICX outdoor cutout 5

Optional parts and accessories

Replacement fuseholders Interrupting Style number 7194C60G01MP 7194C60G02MP 7194C60G03 7194C60G19 7194C60G04 7194C60G05MP 7194C60G06MP 7194C60G07 7194C60G08 7194C60G08 7194C60G11MP 7194C60G12 7194C60G26 7194C60G29 Voltage rating (kV) 15 15 7.8 15 15 27 27 15 27 38 27 38 27 38 BIL (kV) 110 110 110 110 110 125 or 150 125 or 150 125 or 150 125 or 150 150 170 170 125 or 150 170 Current rating (A) 100 100 200 200 300 100 100 200 300 300 100 300 200 100 rating (kAIC) 10 16 12 10 8 12 10 12 12 10 Cap type Solid Link extender Link extender Link extender Solid disconnect blade Solid Link extender Solid Solid disconnect blade Solid disconnect blade Link extender Solid disconnect blade Link extender Link extender Corresponding cutout* AM11 LM11 PA21 KA21 CA31 AM12 MM12 BA22 DA32 DA32 RM14 FA34 VA22 RM15

* Used with ICX cutouts having the following characters in digit positions 7-10 of the ABB cutout style number.

Replacement fuseholder caps Interrupting Style number 3A31186H01 9861A62G05 9861A62G08 3A31187H01 3A31186H01 9861A62G06 9861A62G07 9861A62G11 Voltage rating (kV) 15 15 7.8 15/27 27 27 27 38 BIL (kV) 110 110 110 125 or 150 125 or 150 125 or 150 170 170 Current rating (A) 100 100 200 200 100 100 100 100 rating (kAIC) 10 16 12 10 8 12 12 10 Cap type Solid Link extender Link extender Solid Solid Link extender Link extender Link extender

Brackets Style number 367C723G05 403A101G03 367C802G04 Type NEMA A NEMA B Extended

6 Type ICX outdoor cutout | Product bulletin

Notes

Product bulletin | Type ICX outdoor cutout 7

For more information please contact: ABB Inc. Medium Voltage Distribution Components 3022 NC 43 North Pinetops, NC 27864 USA Phone: +1 252 827 3212 Fax: +1 252 827 4286 www.abb.com/mediumvoltage

Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproductionin whole or in partsis forbidden without ABBs prior written consent. Copyright 2006 ABB. All rights reserved.

1VAG271201-DB Rev. M May 2013