2010 CBC STANDARD SUSPENDED CEILING DETAILS

Issue Date : XX/XX/XX Revision : Date :

8/22/2012 5:07:01 PM

DRAWING INDEX
CLX DRAWING INDEX, NARRATIVE AND FLOWCHART CLX.00 DRAWING INDEX CLX.01 DRAWING INDEX (CONTINUED) CLX.02 NARRATIVE 6 PAGE 1 OF 4 CLX.03 NARRATIVE 6 PAGE 2 OF 4 CLX.04 NARRATIVE 6 PAGE 3 OF 4 CLX.05 FLOWCHART 6 OVERVIEW OF OPD USE CLX.06 FLOWCHART 6 CEILING GRID CLX.07 FLOWCHART 6 COMPRESSION STRUT AND OBSTRUCTIONS CLX.08 FLOWCHART CONNECTIONS TO STRUCTURE CL0 GENERAL NOTES CL0.00 CL0.01 CL0.02 CL0.03 CL1 GENERAL NOTES GENERAL NOTES GENERAL NOTES GENERAL NOTES

REVISIONS

CL1.1 CL1.2 CL1.3 CL1.4a CL1.4b CL1.5

POWDER ACTUATED FASTENER VALUES / LT WT CONCRETE POWDER ACTUATED FASTENER DETAIL / LT WT CONCRETE POWDER ACTUATED FASTENER / STEEL EXPANSION/ ANCHOR CAPACITY EXPANSION ANCHOR INSTALLATION CRITERIA METAL STUD PROFILE

CL2 SUSPENDED ACOUSTICAL CEILING DETAILS

Agency Stamp: Code : 2010 CBC Section Title : . 2010 CBC Sheet Title : Issue Date : XX/XX/XX Revision : Date :
OPD No:

ra f

CL2.1 ISOMETRIC DETAIL CL2.2 TYPICAL CEILING PLAN CL2.3 CORRIDOR CEILING PLAN CL2.4 CORRIDOR INTERSECTION SLIP JOINT CL2.5 TYPICAL CEILING SECTION CL2.6 CEILING PERIMETER CL2.7 CUBICLE CURTAIN/ I.V. TRACK CL2.8 LIGHT FIXTURE/ AIR TERMINAL SUPPORT DETAIL

t_

823 -2 01 2
CLX.00

SUSPENDED CEILING FRAMING COMPONENTS

DRAWING INDEX

8/22/2012 5:07:01 PM

DRAWING INDEX
CL3 COMPRESSION STRUT DETAILS CL3.1 CL3.2 CL3.3 CL3.4 CL4 CHANNEL TYPE COMPRESSION STRUT TUBE TYPE COMPRESSION STRUT CHANNEL TYPE COMPRESSION STRUT OFFSET WITH KICKER TUBE TYPE COMPRESSION STRUT OFFSET WITH KICKER HANGER AND SPLAY WIRE CONNECTION DETAILS TYPICAL WIRE TURNS CONNECTION MATRIX CONNECTION CONCRETE FILED METAL DECK CONNECTION METAL DECK AND NON6 STRUCTURAL FILL ASSEMBLY CONNECTION CONCRETE SLAB, BEAM, OR JOIST CONNECTION STRUCTURAL STEEL CONNECTION SAWN TIMBER CONNECTION CONNECTION TO METAL STUD WALL FRAMING CONNECTION CONNECTION TO METAL STUD WALL FRAMING CONNECTION CONNECTION TO METAL STUD WALL FRAMING

REVISIONS

CL4.1 CL4.2 CL4.3 CL4.4 CL4.5 CL4.6 CL4.7 CL4.8 CL4.9 CL4.10 CL5 CL5.1 CL5.2 CL5.3 CL5.4 CL5.5 CL5.6 CL5.7

COMPRESSION STRUT CONNECTION DETAILS

CONNECTION MATRIX CONNECTION CONCRETE FILLED METAL DECK CONNECTION METAL DECK AND NON6 STRUCTURAL ASSEMBLY CONNECTION CONCRETE SLAB, BEAM, OR JOIST CONNECTION STRUCTURAL STEEL CONNECTION SAWN TIMBER WITH GYPSUM BOARD CONNECTION SAWN TIMBER WITHOUT GYPSUM BOARD

CL6 SPECIAL DETAILS CL6.1 CL6.2 CL6.3 CL6.4 CL6.5 CL6.6 CL6.7

Agency Stamp: Code : 2010 CBC Section Title : . Sheet Title : Issue Date : XX/XX/XX Revision : Date :
OPD No:

ra f

OBSTRUCTION: COUNTER SLOPING WIRES AND TRAPEZE CONDITION OBSTRUCTION: BRIDGE AT LARGE OFFSET CONDITION OBSTRUCTION: COUNTER SLOPING COMPRESSION STRUTS OBSTRUCTION: PERIMETER CONDITION OBSTRUCTION: RECESSED LIGHT AT PERIMETER OBSTRUCTION: STUD BRACE TO OVERHEAD OBSTRUCTION: STUD BRACE TO WALL

t_

823 -2 01 2
CLX.01

DRAWING INDEX (CONTINUED)

NARRATIVE 2010 California Building Code (2010 CBC) Standard Ceiling Details document contains OSHPD Pre6Approved Details (OPD), which may be incorporated into construction documents. These details have been reviewed for compliance with the 2010 CBC and, when used as shown, without modifications, are deemed to comply with code. They are intended to cover common conditions that occur on many projects. It is anticipated that use of these details will facilitate the design, review, and construction process. The Narrative and supporting Flowchart, which follows the Narrative, are provided to assist in selecting applicable details from the OPD for incorporation into the construction documents. It is to be used only as a guide and does not provide complete step6by6 step instructions for use of the OPD. Narrative comment numbers correspond to the numbered items on the Flowchart. The following steps apply to use of OPD: 1. Define Project Parameters A. Short Period Spectral Response Acceleration (Sds) for project site. i. The (Sds) identified for use with the OPD shall not be lower than the Sds documented in the project General Notes and/or Specifications.

i. The Registered Design Professional (RDP) in responsible charge shall identify the floor and/or roof framing materials which apply to the use of the OPD under consideration (e.g. wood, concrete, metal deck). C. Project specific geometry and other conditions.

i. The RDP in responsible charge shall identify the geometry which applies to the use of the OPD under consideratio (e.g. floor6to6floor height, wall thickness). ii. The RDP in responsible charge shall identify other unique conditions which apply to the use of the OPD under consideration (e.g. mechanical duct conflicts and other obstructions). 2. Verify Applicability of OPD Refer to PIN 51.

Agency Stamp: Code : Section Title : DRAWING INDEX, . NARRATIVE AND FLOWCHART Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

NARRATIVE
8/22/2012 5:07:02 PM

B. The details must be directly applicable to the project conditions. For example, OPD for attachment of a ceiling below a steel deck with concrete fill are not applicable to wood frame construction.

ra f

A. The RDP in responsible charge shall verify the applicability of the OPD for their specific project conditions. For example, when designing a fire6rated corridor, use of ceiling details OPD are acceptable provided the OPD are compatible with the construction requirements for the fire rated assembly.

t_

OPD allow design professionals to incorporate pre6approved details into their construction documents. Projects that utilize OPD shall satisfy the following conditions.

823 -2 01 2

B. Type of construction.

CLX.02

A. Substitutions of items shown in the OPD are not permitted, unless specifically allowed by the OPD. For example, a power6actuated fastener (PAF) may not be substituted in a connection detail that specifies an expansion anchor, unless the OPD specifically permits it. Use of post6installed anchors from different manufacturers is permitted, provided the substituted anchors meet the installation criteria and Allowable Strengths as specified in the OPD. B. Changes to the OPD to accommodate project conditions are not permitted. In such cases, project specific details are required. 3. 1. Select Appropriate Details from OPD Review OPD General Notes before the start of OPD selection process. A. The GENERAL NOTES section of the OPD document provides detailed specification of the materials and the workmanship associated with the details. The Design Professional of Record (DPOR) shall confirm the applicability of the OPD details and the specifications noted in this section. (CL0.00, CL0.01, CL0.02, CL0.03, CL0.04). Refer to CL2.1 to confirm general configuration requirements. B. Typical geometric conditions shall be verified from CL2.2. Refer to Section 10 of the GENERAL NOTES for system component requirements. C. Ceiling boundary condition shall be provided in conformance with the requirements detailed on CL2.5 and CL2.6. Refer to Section 11 of the GENERAL NOTES for system installation requirements. D. Detailing requirements needed to comply with the requirements for both slip and fixed conditions in corridor ceilings are shown on CL2.3, CL2.4, and CL2.5. Refer to Section 12 of the GENERAL NOTES. E. CL2.7 and CL2.8 show the necessary detailing requirements for the support of Curtain Tracks, Air Terminals, and Light Fixtures suspended directly from the ceiling system. Refer to Section 15 of the GENERAL NOTES. F. Hanger and Splay Wire specifications are shown in Section 9 of the GENERAL NOTES. CL4.1 graphically illustrates the requirements of the specifications at the terminal ends of the wire. G. Compression Strut requirements are detailed in Section 3. Channel and Electrical Metallic Tubing (EMT) are the two types of Compression Struts that are included within the scope of this OPD. Refer to Section 13 of the GENERAL NOTES for system installation requirements. 1. Channel Type Compression Strut details are shown on CL3.1. The offset condition is shown on CL3.3. 2. Electrical Metallic Tubing (EMT) Compression Strut details are shown on CL3.2. The offset condition is shown on CL3.4. H. Requirements for detailing at obstructions between the ceiling and the support structure are illustrated in Section 6. Different obstruction types require special detailing of Hanger Wires, Splay Wires, and Compression Struts. Refer tO Section 14 of the GENERAL NOTES for system installation requirements.

Agency Stamp: Code : Section Title : DRAWING INDEX, . NARRATIVE AND FLOWCHART Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

NARRATIVE
8/22/2012 5:07:02 PM

ra f

t_

823 -2 01 2

CLX.03

1. Requirements for detailing at obstructions at Hanger and Spay Wires are shown on CL6.1. CL6.2, CL6.4, CL6.6, CL6.7. 2. Requirements for detailing at obstructions at Compression Struts are shown on CL6.2. CL6.3, CL6.5. I. Connection detail requirements for the connection of Hanger and Splay Wire to support structure are illustrated in Section 4. Detail requirements for attachment to various structural materials and systems are included within this Section of the OPD. Refer to Section 14 of the GENERAL NOTES for system installation requirements. Refer to Section 1 of the OPD document (SUSPENDED CEILING FRAMING COMPONENTS) for fastener design capacities and component properties. J. Connection detail requirements for the connection of Compression Strut to support structure are illustrated in Section 5. Detail requirements for attachment to various structural materials and systems are included within this Section of the OPD. Refer to Section 14 of the GENERAL NOTES for system installation requirements. Refer to Section 1 of the OPD document (SUSPENDED CEILING FRAMING COMPONENTS) for fastener design capacities and component properties.

4. 5.

Implementation and Use of OPD During Plan Review Refer to PIN 51. Implementation and Use of OPD During Construction Process Refer to PIN 51.

A.During construction, OPD are treated as any other detail in the approved documents.

B.Pre6approved details submitted after the construction documents have been approved and a building permit has been issued shall be used and/or processed in accordance with Code Application Notice 26107.4 Amended Construction Documents. Pre6approved details may be applied as alternates to the approved details shown on the permitted construction documents only on a one for one basis and with written consent of the registered design professional and the registered design professional in responsible charge and in concurrence with OSHPD field staff. Pre6approved details will not be subject to additional plan review provided they are incorporated without any modification. Pre6approved details are subject to field confirmation during which the applicability of pre6approved details for specific project conditions shall be evaluated. C. Changing the scope of a project (adding additional ceilings, for example) does constitute a material alteration to the project, even if OPD can be used for all conditions. In such a case, an Amended Construction Document must be submitted to OSHPD field staff for review.

Agency Stamp: Code : Section Title : DRAWING INDEX, . NARRATIVE AND FLOWCHART Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

NARRATIVE
8/22/2012 5:07:02 PM

ra f

t_

823 -2 01 2

CLX.04

Agency Stamp: Code : Section Title : DRAWING INDEX, . NARRATIVE AND FLOWCHART Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

FLOWCHART
8/22/2012 5:07:02 PM

ra f

t_

823 -2 01 2
CLX.05

Agency Stamp: Code : Section Title : DRAWING INDEX, . NARRATIVE AND FLOWCHART Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

FLOWCHART
8/22/2012 5:07:03 PM

ra f

t_

823 -2 01 2
CLX.06

Agency Stamp: Code : Section Title : DRAWING INDEX, . NARRATIVE AND FLOWCHART Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

FLOWCHART
8/22/2012 5:07:03 PM

ra f

t_

823 -2 01 2
CLX.07

Agency Stamp: Code : Section Title : DRAWING INDEX, . NARRATIVE AND FLOWCHART Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

FLOWCHART
8/22/2012 5:07:03 PM

ra f

t_

823 -2 01 2
CLX.08

1. CONSTRUCTION, WORKMANSHIP AND MATERIAL SHALL CONFORM TO THE 2010 CALIFORNIA BUILDING CODE, TITLE 24, PART 2 (CODE), WITH OSHPD AMENDMENTS, ASCE 7605. 2. THE CONTRACTOR SHALL NOTIFY OSHPD AND THE DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHERE A CONFLICT OR DISCREPANCY OCCURS BETWEEN THE CONSTRUCTION DRAWINGS AND ANY OTHER PORTION OF THE CONTRACT DOCUMENTS, FIELD CONDITIONS, OR WHERE ANY CONDITIONS ARISE NOT COVERED BY THESE DOCUMENTS WHEREIN WORK WILL NOT COMPLY WITH CODE REQUIREMENTS. 3. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE HOSPITAL BUILDING IN ACCORDANCE WITH THE CALIFORNIA BUILDING STANDARD CODE, TITLE 24, CALIFORNIA CODE OF REGULATIONS. SHOULD ANY CONDITION DEVELOP NOT COVERED BY THE APPROVED PLANS AND SPECIFICATIONS WHEREIN THE WORK WILL NOT COMPLY WITH TITLE 24, CALIFORNIA CODE OF REGULATIONS, A CHANGE ORDER DETAILING AND SPECIFYING THE REQUIRED WORK SHALL BE SUBMITTED TO AND APPROVED BY OSHPD BEFORE PROCEEDING WITH THE WORK. 4. GALVANIZED METAL STUDS, TRACK AND SHEET STEEL SHALL CONFORM TO ASTM A653 MATERIAL (OR OTHER EQUIVALENT ASTM LISTED MATERIALS INTHE 2001 EDITION OF THE AISI6NAS, SECTION A2.1) WITH A MINIMUM YIELD STRENGTH OF 33 KSI FOR 18 GAGE AND LIGHTER, AND MINIMUM YIELD STRENGTH OF 50 KSI FOR 16 GAGE AND HEAVIER. 5. METAL STUDS AND TRACKS SHALL BE OF SIZE, THICKNESS AND SECTION PROPERTIES SHOWN ON TABLES I61 AND I62 OF THE 2008 EDITION OF THE AISI MANUAL, COLD6FORMED STEEL DESIGN. THE DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR OBTAINING OSHPD APPROVAL FOR ANY SUBSTITUTIONS. 6. THESE DOCUMENTS REFER TO FASTENER TYPE AND SIZE BUT DO NOT SPECIFY OR ENDORSE A SPECIFIC MANUFACTURER,THE DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL SELECT A MANUFACTURER AND FASTENERS THAT MATCH OR EXCEED THE CAPACITIES/ DESIGN VALUES LISTED HEREIN. THE FOLLOWING REQUIREMENTS SHALL ALSO BE MET: a. SCREW FASTENER SHALL SATISFY AC1186 ACCEPTANCE CRITERIA FOR SELF DRILLING SCREW FASTENERS. PENETRATION OF SCREWS THROUGH JOINED MATERIAL SHALL NOT BE LESS THAN 3 EXPOSED THREADS. LISTING OF CURRENT ICC6ES EVALUATION REPORTS ( OR REPORTS FROM OTHER OSHPD6APPROVED TESTING AGENCIES) SHALL BE REQUIRED FOR FASTENERS USED. SAID REPORTS SHALL BE FIELD REVIEWED BY THE INSPECTOR OF RECORD (IOR) AND OSHPD FIELD STAFF TO VERIFY CONFORMANCE WITH THE ABOVE6NOTED ACCEPTANCE CRITERIA, PRIOR TO INSTALLATION OF FASTENERS. b. WELDING SHALL BE IN ACCORDANCE WITH AWS D1.3 USING E60XX SERIES ELECTRODES. ALL FIELD WELDING SHALL HAVE SPECIAL INSPECTION IN ACCORDANCE WITH CBC 1704A.3.1. c. POST6 INSTALLED ANCHORS SHALL HAVE SPECIAL INSPECTION IN ACCORDANCE WITH CBC 1916A.8, AND CAN 261916A.8. FOR QUALIFICATION, DESIGN AND USE OF POST6 INSTALLED ANCHORS IN CONCRETE SEE CBC 1912A.1 AND CAN 261912A.1. LISTING OF CURRENT ICC6ES EVALUATION REPORTS (OR REPORTS FROM OTHER OSHPD6APPROVED TESTING AGENCIES) SHALL BE REQUIRED FOR FASTENER USED. SAID REPORTS SHALL BE FIELD6 REVIEWED BY THE INSPECTOR OF RECORD (IOR) AND OSHPD FIELD STAFF TO VERIFY CONFORMANCE WITH THE ABOVE6 NOTED ACCEPTANCE CRITERIA, PRIOR TO INSTALLATION OF FASTENERS.

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC GENERAL NOTES

ra f
Issue Date : XX/XX/XX Revision : Date :

t_

823 -2 01 2

OPD No:

GENERAL NOTES
8/22/2012 5:06:50 PM

CL0.00

d. POWER6 ACTUATED FASTENER SHALL SATISFY THE CURRENT AC706 ACCEPTANCE CRITERIA FOR FASTENER DRIVEN INTO CONCRETE, STEEL AND MASONRY ELEMENTS. LISTING OF CURRENT ICC6ES EVALUATION REPORTS ( OR REPORTS FROM OTHER OSHPD6APPROVED TESTING AGENCIES) SHALL BE REQUIRED FOR FASTENERS USED. SAID REPORTS SHALL BE FIELD6REVIEWED BY THE INSPECTOR OF RECORD (IOR) AND OSHPD FIELD STAFF TO VERIFY CONFORMANCE WITH THE ABOVE6NOTED ACCEPTANCE CRITERIA, PRIOR TO INSTALLATION OF FASTENERS. 7. DESIGN CRITERIA a. BUILDING CODE: 2010 CALIFORNIA STATE BUILDING CODE (CBC), ASCE 7605, 2001 AISI/ NORTH AMERICAN SPECIFICATION (NASPEC) FOR COLD6FORMED MEMBERS, AISI 2007, ASTM E580, ASTM C 635, ASTM C 636. THE REQUIREMENTS IN THIS OPD APPLY TO CEILING SYSTEMS WHOSE TOTAL WEIGHT, INCLUDING CEILING MOUNTED AIR TERMINALS, SERVICES AND LIGHT FIXTURES, DOES NOT EXCEED FOUR (4) psf. HEAVY SYSTEMS, AND THOSE SUPPORTING LATERAL LOADS FROM PARTITIONS, WILL REQUIRE SPECIAL DESIGN DETAILS. b. FASTENER CAPACITIES TABLES WERE DEVELOPED BASED ON ICC REPORTS BY SEVERAL MANUFACTURERS. c. THE DESIGN ASSUMES THAT BUILDING ELEMENTS AND SUPPORTS, TO WHICH THE COMPONENTS ADDRESSED IN THIS DOCUMENT ARE ANCHORED, HAVE SUFFICIENT CAPACITY TO CARRY THE LOADS IMPOSED BY THE COMPONENTS IN COMBINATION WITH ALL OTHER LOADS. EVALUATION OF THE CAPACITY OF THESE SUPPORTING BUILDING ELEMENTS IS BEYOND THE SCOPE OF THE DESIGN. 8. THE DESIGN PROFESSIONAL OF RECORD SHALL VERIFY UNDERWRITER LABORATORY RATING FOR ALL CEILING ASSEMBLIES.

a. ULTIMATE STRESS FOR #10 AND #12 WIRE, OF 60,000 PSI SHALL BE USED.

b. DESIGN STRESS SHALL BE AND THE ULTIMATE STRESS DIVIDED BY 2.5 (24,000 PSI) FOR #10 AND #12 WIRE c. #10 WIRE (0.135" DIAMETER) SHALL HAVE AN ALLOWANCE LOAD OF 343 LBS.

d. #12 WIRE (0.106" DIAMETER) SHALL HAVE AN ALLOWANCE LOAD OF 209 LBS.

e. 4 TWISTS WITHIN 3" MAY BE USED TO DEVELOP THE MAXIMUM ALLOWABLE LOAD.

f. 3 TWISTS WITHIN 3" MAY BE USED TO DEVELOP THE MAXIMUM 50% OF ALLOWABLE LOAD.

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC GENERAL NOTES Issue Date : XX/XX/XX Revision : Date :
OPD No:

GENERAL NOTES
8/22/2012 5:06:50 PM

c. MAIN RUNNERS, CROSS RUNNERS, SPLICES, EXPANSION DEVICES, INTERSECTION CONNECTORS SHALL BE DESIGNED TO CARRY A MEAN ULTIMATE TEST LOAD OF NOT LESS THAN 180 lbs. IN COMPRESSION & TENSION.

ra f
.

b. SUSPENSION WIRES SHALL BE #12 GAGE (0.106" DIAMETER), SOFT ANNEALED, AND GALVANIZED STEEL WIRES WITH CLASS 1 COATING. THEY MAYBE USED FOR UP TO AND INCLUDING 4'60"x 4'60" GRID SPACING ALONG AND ATTACHED TO MAIN RUNNERS. SPLICES ARE NOT PERMITTED IN ANY HANGER WIRE.

t_

10. SUSPENSION SYSTEM COMPONENTS a. THE CEILING GRID SYSTEM MUST BE RATED HEAVY DUTY AS DEFINED BY ASTM C635.

823 -2 01 2

9. "CEILING WIRE" SHALL CONFORM WITH GALVANIZED SOFT ANNEALED MILD STEEL WIRE AS DEFINED IN ASTM A641 (CLASS 1 COATING):

CL0.01

11. SUSPENSION SYSTEM INSTALLATION: a. PROVIDE #12 GAGE HANGER WIRES AT THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8 INCHES OF THE SUPPORT OR WITHIN ONE6FOURTH (1/4) OF THE LENGTH OF THE END TEE, WHICHEVER IS LEAST, FOR THE PERIMETER OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTH OF THE END TEE IS EIGHT (8) INCHES OR LESS. b. CEILING GRID MEMBERS SHALL BE ATTACHED TO TWO (2) ADJACENT WALLS. c. CEILING GRID MEMBERS SHALL BE AT LEAST 3/4" INCH CLEAR OF OTHER WALLS. IF WALLS RUN DIAGONALLY TO CEILING GRID SYSTEM RUNNERS, ONE END OF MAIN AND CROSS RUNNERS SHOULD BE FREE, AND A MINIMUM OF 3/4 INCH CLEAR OF WALL. d. THE WIDTH OF THE PERIMETER SUPPORTING CLOSURE ANGLE SHALL BE NOT LESS THAN 2 INCHES. e. AT THE PERIMETER OF THE CEILING AREA WHERE MAIN OR CROSS RUNNERS ARE NOT CONNECTED TO THE ADJACENT WALL, PROVIDE INTERCONNECTION BETWEEN THE RUNNERS AT THE FREE END TO PREVENT LATERAL SPREADING. A METAL STRUT OR A #16 GAGE WIRE WITH A POSITIVE MECHANICAL CONNECTION TO THE RUNNER MAY BE USED. WHERE THE PERPENDICULAR DISTANCE FROM THE WALL TO THE FIRST PARALLEL RUNNER IS 8 INCHES OR LESS, THIS INTERLOCK IS NOT REQUIRED. 12. EXPANSION JOINTS, SEISMIC SEPARATIONS, AND PENETRATIONS: a. EXPANSION JOINTS SHALL BE PROVIDED IN THE CEILING AT INTERSECTIONS OF CORRIDORS AND AT JUNCTIONS OF CORRIDORS WITH LOBBIES OR OTHER SIMILAR AREAS. b. FOR CEILING AREAS EXCEEDING 2500 SQUARE FEET, A SEISMIC SEPARATION JOINT SHALL BE PROVIDED TO DIVIDE THE CEILING INTO AREAS NOT EXCEEDING 2500 SQ. FT. c. PENETRATIONS THROUGH THE CEILING FOR SPRINKLER HEADS AND OTHER SIMILAR DEVICES THAT ARE NOT INTEGRALLY TIED TO THE CEILING SYSTEM IN THE LATERAL DIRECTION SHALL HAVE A TWO (2) INCH OVERSIZED RING, SLEEVE OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE MOVEMENT OF ONE (1) INCH IN ALL HORIZONTAL DIRECTIONS. A FLEXIBLE SPRINKLER HOSE FITTING THAT CAN ACCOMMODATE 1 INCH OF CEILING MOVEMENT SHALL BE PERMITTED TO BE USED IN LIEU OF THE OVERSIZED RING, SLEEVE OR ADAPTER. 13. LATERAL FORCE BRACING:

LATERAL FORCE BRACING IS REQUIRED PER THIS SECTION FOR ALL CEILING AREAS. EXCEPTION: LATERAL FORCE BRACING MAY BE OMITTED FOR SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH A CEILING AREA OF 144 SQ. FT. OR LESS, AND FIRE RATED SUSPENDED ACOUSTICAL CEILING SYSTEMS WITH A CEILING AREA OF 144 SQ. FT. OR LESS, WHEN PERIMETER SUPPORT IN ACCORDANCE WITH ASTM E580 ARE PROVIDED AND PERIMETER WALLS ARE DESIGNED TO CARRY THE CEILING LATERAL FORCES. a. PROVIDE LATERAL6FORCE BRACING ASSEMBLIES CONSISTING OF A COMPRESSION STRUT AND FOUR (4) #12 GAGE SPLAYED BRACING WIRES ORIENTED 90 DEGREES FROM EACH OTHER. b. LATERAL6FORCE BRACING ASSEMBLIES SHALL BE SPACED AT A MAXIMUM OF 12 FEET BY 12 FEET ON CENTER WITH THE FIRST ASSEMBLY WITHIN 6 FEET SPACING FROM EACH WALL AND AT THE EDGES OF ANY CHANGE IN ELEVATION OF THE CEILING. THE LAST ASSEMBLY MUST BE WITHIN MAXIMUM DISTANCE FROM EACH WALL. c. THE SLOPE OF BRACING WIRES MAY BE FROM 0 TO 45 DEGREES BUT MAY NOT EXCEED 45 DEGREES FROM THE PLANE OF THE CEILING AND WIRES SHALL BE TAUT. d. COMPRESSION STRUTS SHALL BE ADEQUATE TO RESIST THE VERTICAL COMPONENT INDUCED BY THE BRACING WIRES, AND SHALL NOT BE MORE THAN 1(HORIZONTAL) IN 6 (VERTICAL) OUT OF PLUMB.

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC GENERAL NOTES

ra f

t_

823 -2 01 2

Issue Date : XX/XX/XX Revision : Date :

OPD No:

GENERAL NOTES
8/22/2012 5:06:50 PM

CL0.02

14. ATTACHMENT OF HANGER AND BRACING WIRES: a. FASTEN #12 HANGER WIRES WITH NOT LESS THAN THREE (3) TIGHT TURN IN 3 INCHES. HANGERWIRE LOOPS SHALL BE TIGHTLY WRAPPED AND SHARPLY BENT TO PREVENT ANY VERTICAL MOVEMENT OR ROTATION OF THE MEMBER WITHIN THE LOOPS. b. FASTEN #12 BRACING WIRES WITH THREE (3) TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 3" INCHES. c. HANGER OR BRACING WIRE ANCHORED TO THE STRUCTURE SHOULD BE INSTALLED IN SUCH A MANNER THAT THE DIRECTION OF THE ANCHOR ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTION OF THE WIRE. d. SEPARATE ALL CEILING HANGER AND BRACING WIRES AT LEAST SIX (6) INCHES FROM ALL UNBRACED DUCTS, PIPES CONDUITS, ETC. e. HANGER WIRES SHALL NOT BE ATTACHED TO OR BEND AROUND INTERFERING MATERIAL OR EQUIPMENT. PROVIDE TRAPEZE OR OTHER SUPPLEMETARY SUPPORT MEMBERS AT OBSTRUCTIONS TO TYPICAL HANGER SPACING. PROVIDE ADDITIONAL HANGERS, STRUTS OR BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS, OR DISCONTINUOUS AREAS. f. HANGER WIRES THAT ARE MORE THAN 1 (HORIZONTAL) IN 6 (VERTICAL)OUT OF PLUMB SHALL HAVE COUNTER SLOPING WIRES. PERIMETER HANGER WIRES AT RUNNERS THAT ARE POSITIVELY ATTACHED TO THE PERIMETER CLOSURE ANGLE, COUNTER6SLOPING IS OPTIONAL. g. WHEN DRILLED6IN CONCRETE ANCHORS OR SHOT6IN ANCHORS ARE USED IN REIFORCED CONCRETE FOR HANGER WIRES 1 OUT OF 10 WIRE/ ANCHOR ASSEMBLIES MUST BE FIELD TESTED FOR 200 lbs. IN TENSION. WHEN DRILLED6IN CONCRETE ANCHORS ARE USED FOR BRACING WIRES, 1 OUT OF 2 WIRE/ ANCHOR ASSEMBLIES MUST BE FIELD TESTED FOR 440 lbs. IN TENSION IN THE DIRECTION OF THE WIRE. SHOT6IN ANCHORS IN CONCRETE ARE NOT PERMITTED FOR BRACING WIRES.

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC GENERAL NOTES

ra f

a. CEILING PANELS SHALL NOT SUPPORT ANY LIGHT FIXTURES, AIR TERMINALS OR DEVICES. b. ATTACH ALL LIGHT FIXTURES, CEILING MOUNTED AIR TERMINALS AND ALL OTHER DEVICES TO THE CEILING GRID RUNNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURE. SCREWS OR APPROVED FASTENERS ARE REQUIRED. MINIMUM OF TWO ATTACHNMENTS ARE REQUIRED AT EACH LIGHT FIXTURE. c. RECESSED OR DROP6IN LIGHT FIXTURE, GRILLES, MECHANICAL TERMINALS, AND FLEXIBLE SPRINKLER HOSE FITTINGS OR OTHER SERVICES BE SUPPORTED DIRECTLY ON RUNNERS CLASSIFIED AS ASTM HEAVY DUTY, BUT THEY MUST ALSO HAVE A MINIMUM OF TWO (2) #12 GAGE SLACK SAFETY WIRES ATTACHED TO THE FIXTURE AT DIAGONAL CORNERS AND ANCHORED TO THE STRUCTURE ABOVE. d. ALL FLUSH OR RECESSED LIGHT FIXTURES, MECHANICAL TERMINALS, AND FLEXIBLE SPRINKLER HOSE FITTINGS OR OTHER SERVICES WEIGHING 56 lbs. OR MORE MUST BE INDEPENDENTLY SUPPORTED BY NOT LESS THAN FOUR (4) TAUT #12 GAGE WIRES ATTACHED TO THE HOUSING AND TO THE STRUCTURE ABOVE. THE FOUR (4) TAUT #12 GAGE WIRES, INCLUDING THEIR ATTACHMENT TO THE STRUCTURE ABOVE, MUST BE CAPABLE OF SUPPORTING FOUR (4) TIMES THE WEIGHT OF THE UNIT. e. ALL 4 ft.x 4 ft. LIGHT FIXTURES MUST HAVE SLACK SAFETY WIRES AT EACH CORNER. f. SURFACE6MOUNTED FIXTURES SHALL BE ATTACHED TO THE MAIN RUNNER WITH AT LEAST TWO POSITIVE CLAMPING DEVICES MADE OF MATERIAL WITH A MINIMUM #14 GAGE. ROTATIONAL SPRING CATCHES DO NOT COMPLY. A #12 GAGE SUSPENSION WIRE SHALL BE ATTACHED TO EACH CLAMPING DEVICE TO THE STRUCTURE ABOVE. PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT FIXTURES ARE 8 ft. OR LONGER. MAXIMUM SPACING BETWEEN SUPPORTS SHALL NOT EXCEED 8 FEET.

t_

823 -2 01 2

15. CEILING FIXTURES, TERMINALS, AND DEVICES:

Issue Date : XX/XX/XX Revision : Date :

OPD No:

GENERAL NOTES
8/22/2012 5:06:50 PM

CL0.03

g. SUPPORT PENDANT6MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE ABOVE WITH THE HANGER WIRES OR CABLES PASSING THROUGH EACH PENDANT HANGER AND CAPABLE OF SUPPORTING TWO (2) TIMES THE WEIGHT OF THE FIXTURE. A BRACING ASSEMBLY (EITHER SPLAY WIRES ATTACHED TO THE PENDANT HOUSING OR THE PENDANT HOUSING ATTACHED TO THE CEILING GRID MEMBERS) IS REQUIRED IF THE PENDANT HANGER PENETRATES THE FEILD OF THE CEILING TILE. SPECIAL DETAILS ARE REQUIRED TO ATTACH THE PENDANT HANGER TO THE BRACING ASSEMBLY TO TRANSMIT HORIZONTAL FORCE. IF THE PENDANT MOUNTED LIGHT FIXTURE IS DIRECTLY ATTACHED TO THE CEILING GRID MEMBER, THEN THE BRACING ASSEMBLY IS NOT REQUIRED ABOVE THE CEILING. 16. ADDITIONAL REQUIREMENTS: a. FIRE RATED CEILINGS: PROVIDE A DETAIL AND DESIGN NUMBER FOR RATED CEILING ASSEMBLIES FROM AN AUTHORIZED TESTING AGENCY. THE COMPONENTS AND INSTALLATION DETAILS MUST CONFORM IN EVERY RESPECT WITH THE LISTED DETAIL AND NUMBER. DETAILS SHALL CLEARLY DEPICTS ALL COMPONENTS, INCLUDING INSULATION MATERIALS, FRAMING AND ATTACHMENT OF THE DESIGN SO THAT THE ASSEMBLY CAN BE CONSTRUCTED AND INSPECTED ACCORDINGLY. POP RIVETS, SCREWS, OR OTHER ATTACHMENTS ARE NOT ACCEPTABLE UNLESS SPECIFICALLY DETAILED ON THE DRAWINGS AND APPROVED BY U.L. b. METAL AND OTHER PANELS: METAL PANELS AND PANELS WEIGHING MORE THAN 1/2 psf, OTHER THAN MINERAL FIBER ACOUSTICAL TILE, ARE TO BE POSITIVELY ATTACHED TO THE CEILING SUSPENSION RUNNERS. c. ESSENTIAL SERVICES BUILDINGS: EXIT WAYS SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 13.5.6.2.2(1) OF ASCE 7605 AS AMENDED BY 2010 CBC SECTION 1615A.1.16. SPLICES OR INTERSECTION OF SUCH RUNNERS SHALL BE ATTACHED WITH THROUGH CONNECTORS SUCH AS POP RIVETS, SCREWSS, PINS, PLATES WITH END TABS OR OTHER APPROVED CONNECTORS.

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC GENERAL NOTES

ra f
Issue Date : XX/XX/XX Revision : Date :

t_

823 -2 01 2
OPD No:

GENERAL NOTES
8/22/2012 5:06:50 PM

CL0.04

POWER ACTUATED FASTENER ALLOWABLE DESIGN VALUES (SERVICE LEVEL) . 1. POWER ACTUATED FASTENER DESIGN VALUES FOR SHEAR AND TENSION ARE GENERATED USING ICC REPORT FOR TWO PRODUCTS. S1 6 HILTI LOW6VELOCITY POWER6DRIVEN FASTENER6FASTENER X6U (ICC62269) W/ SHANK DIAMETER 0.157 6 ITW RAMSET POWER6DRIVEN FASTENERS6 PART NO. 1500 (ICC ESR6 1799) WITH SHANK DIAMETER 0.145 2. DESIGN VALUES LISTED BELOW ARE 75% OF THE LESSER VALUE BETWEEN THE TWO REPORTED IN ICC.M

TABLE 1 POWER ACTUATED FASTENER INSTALLED INTO SAND6LIGHTWEIGHT CONCRETE THROUGH METAL DECK f'c=3000 psi NOMINAL SHANK DIAMETER (in.) 0.138 0.145 MIN. EMBED (in.) 7/8" 1 1/8" 6 1 1/8" 7/8" 0.157 1 1/8" MIN. SPACING (in.) 4 4 6 4 4 4 MIN. EDGE DISTANCE (in.) 3.2 3.2 6 3.2 3.2 3.2 TENSION (lbs.) 75 75 6 75 6 SHEAR* (lbs.) 100 100 6 100 100 6

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC SUSPENDED CEILING FRAMING COMPONENTS

ra f

* POWER ACTUATED FASTENER SHEAR CAPACITY IS LIMITED TO 90 LBS WHERE PERMANENT GRAVITY TENSION LOADS ARE PRESENT (OSHPD CAN 261912A.1) ** VALUES ARE FOR SINGLE FASTENER, WHICH MEET REQUIREMENTS PER NOTES BELOW

t_

823 -2 01 2
100

Issue Date : XX/XX/XX Revision : Date :

OPD No:

POWER ACTUATED FASTENER (PAF)6 CAPACITY AND INSTALLATION CRITERIA


8/22/2012 5:06:51 PM

CL1.1

NOTE: 1. MINIMUM CONCRETE STRENGTH fc= 2000 psi UNLESS OTHERWISE NOTED. 2. FASTENERS INSTALL THROUGH LOW FLUTES OF THE METAL DECK PER SKETCH BELOW. 3. MINIMUM EDGE DISTANCE OF 161/8" FROM THE EDGE OF METAL DECK WEB AND 4" FROM THE EDGE OF THE DECK. 4. STEEL DECK TO BE A MINIMUM OF 20 GA. 5. CONCRETE FILL DEPTH ABOVE THE TOP OF METAL DECK MUST BE A MINIMUM OF 361/4" @ LIGHT WEIGHT. COMPOSITE METAL DECK. 6. POWER ACTUATED FASTENERS SHALL NOT BE USED TO RESIST SEISMIC TENSILE FORCES. THEY ARE PERMITTED FOR ATTACHMENT OF VERTICAL SUSPENSION WIRES THAT ARE NOT PART OF THE SEISMIC BRACING. 7. POWER ACTUATED FASTENERS SHALL NOT BE USED IN PRE6STRESSED CONCRETE UNLESS NON6DESTRUCTIVE TESTING METHODS ARE USED TO LOCATE STRAND AND REINFORCE PRIOR TO THE PDF INSTALLATION. 8. PAF INSTALLATION SHALL NOT NICK OR DAMAGE EXISTING CONCRETE REINFORCE. 9. PAF SHALL BE INSTALLED PER CURRENT ICC6ES EVALUATION REPORTS OR REPORT FROM OTHER OSHPD. APPROVED TESTING AGENCY AND PER CAN 261916A.8. 10. TESTING OF PAF'S SHALL BE PER CBC SECTION 1916A.8 AND CAN 261916A.8. MINIMUM CONCRETE SUBSTRAIGHT THICKNESS IS THREE TIMES THE PAF'S PENETRATION INTO THE CONCRETE SUBSTRAIGHT. STEEL DECK CONCRETE STRENGTH SEE TABLE 1, 2, & 3 IN DETAIL CL1.2A

DIRECTION OF DEMAND LOAD

t_

823 -2 01 2
1 1/8" 4 1/2" 7 1/2" FASTENER
N.T.S.

6 1/4"

3"

3 1/4"

4 7/16"

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC SUSPENDED CEILING FRAMING COMPONENTS

ra f

SECTION 6 COMPOSITE DECK

Issue Date : XX/XX/XX Revision : Date :

OPD No:

POWER ACTUATED FASTENER (PAF)6 CAPACITY AND INSTALLATION CRITERIA


8/22/2012 5:06:51 PM

CL1.2

POWER ACTUATED FASTENER ALLOWABLE DESIGN VALUES (SERVICE LEVEL INSTALLED IN STEEL) . 1. POWER ACTUATED FASTENER DESIGN VALUES FOR SHEAR AND TENSION ARE GENERATED USING ICC REPORT FOR THREE PRODUCTS. 6 HILTI LOW6VELOCITY POWER6DRIVEN FASTENER6 FASTENER X6U (ICC62269) W/ SHANK DIAMETER 0.157 6 ITW RAMSET POWER6DRIVEN FASTENERS6 PART NO. 1500K AND 1600K (ICC ESR6 1799) WITH SHANK DIAMETER 0.145 6 SIMPSON POWER6DRIVEN FASTENERS6 FASTENER PDPT (ICCESR62138) WITH SHANK DIAMETER 0.145 2. DESIGN VALUES LISTED BELOW ARE 75% OF THE LESSER VALUE AMONG THE THREE REPORTED IN ICC.

NOMINAL SHANK DIAMETER (in.) 0.145 222

3/16 TENSION(lbs)

823 -2 01 2
1/4 3/8 SHEAR(lbs) TENSION(lbs) 494 510 SHEAR(lbs) 540 255

STEEL THICKNESS (in)

1/2 TENSION(lbs) 120 SHEAR(lbs) 210

SHEAR(lbs) TENSION(lbs) 477

NOTE:

1. MINIMUM SPACING BETWEEN PINS =161/2" O.C. 2. MINIMUM EDGE DISTANCE = 1/2"

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC SUSPENDED CEILING FRAMING COMPONENTS

ra f

t_
Issue Date : XX/XX/XX Revision : Date :

OPD No:

POWER ACTUATED FASTENER (PAF)6 CAPACITIES (INSTALLED IN STEEL) & INSTALLATION CRITERIA
8/22/2012 5:06:51 PM

CL1.3

EXPANSION ANCHOR DESIGN VALUES NOTE: 1. DESIGN VALUES/ ASD VALUE TABLE 1 EXPANSION ANCHORS INSTALLED INTO THE UNDERSIDE OF STRUCTURAL SAND6LIGHTWEIGHT CONCRETE (f'c MIN= 3000 PSI) OVER METAL DECK ANCHOR DIA. (in) 3/8 1/2 1/2 5/8 5/8 EMBED (in.) 2 2 3 1/4 3 1/8 4 SHEAR (lb.) 708 998 1082 1523 2008 TENSION (lb.) (WITH INSPECTION) 532 532 954 728 1691

ANCHOR DIA. (in) 3/8 1/2

EMBED (in.) 2 2

TABLE 3 EXPANSION ANCHORS INSTALLED IN NORMAL WEIGHT CRACKED CONCRETE (f'c MIN= 3000 PSI) ANCHOR DIA. (in) 3/8 1/2 1/2 5/8 5/8 EMBED (in.) 2 2 SHEAR (lb.) 749 TENSION (lb.) (WITH INSPECTION) 827 875 1790 1710 2476

t_

ra f

* VALUES ARE FOR SINGLE ANCHORS, WHICH COMPLY WITH MIN. REQUIREMENTS PER NOTES ON CL1.3B

Agency Stamp: Code : Section Title : 2010 CBC

823 -2 01 2
SHEAR (lb.) 566 566 525 525 2129 2129 3509 3509 3 1/4 3 1/8 4

TABLE 2 EXPANSION ANCHORS INSTALLED INTO THE UNDERSIDE OF STRUCTURAL SAND6LIGHTWEIGHT CONCRETE (f'c MIN= 3000 PSI) OVER METAL DECK TENSION (lb.) (WITH INSPECTION)

. SUSPENDED CEILING FRAMING COMPONENTS


Sheet Title :

Issue Date : XX/XX/XX Revision : Date :

OPD No:

EXPANSION ANCHOR CAPACITY


8/22/2012 5:06:51 PM

CL1.4a

TABLE 4 NOMINAL ANCHOR DIAMETER (in.) 3/8" DIA. EFFECTIVE MIN. EMBEDMENT (in.) MIN. MEMBER THICKNESS NWC SLAB OR BEAM ONLY (in.) MINIMUM ANCHOR SPACING (3 x EMBED) (in.) MINIMUM EDGE DISTANCE (in.) 2 4 6 3/4 4 3/8 2 4 6 3/4 6 1/2" DIA. 3 1/2 6 9 3/4 7 1/2 3 1/8 5 9 3/8 6 1/2 5/8" DIA. 4 6 12 8 3/4

1.2

MIN. 3000 PSI NORMAL OR SAND LT.WT. CONCRETE

1" MIN.

T + V T allow, ASD v allow, ASD


3" ANCHOR IN MAX. RIDGE 3 1/4" MIN

MIN. 20 GA. STEEL W6DECK

1" MAX. OFFSET, TYP. NOTE:

Agency Stamp: Code : Section Title : Sheet Title : 2010 CBC SUSPENDED CEILING FRAMING COMPONENTS

1. MINIMUM CONCRETE STRENGTH fc= 3000 psi. 2. EXPANSION ANCHORS INSTALLED THROUGH UPPER OR LOWER FLUTES OF METAL DECK SHALL MEET REQUIREMENTS OF SKETCH ABOVE. 3. STEEL DECK TO BE MINIMUM 20 GA. W6DECK. 4. CONCRETE FILL DEPTH ABOVE THE TOP OF METAL DECK MUST BE A MINIMUM OF 361/4". 5. EXPANSION ANCHOR SHALL NOT BE USED IN PRE6STRESSED CONCRETE UNLESS NON6DESTRUCTIVE TESTING METHODS ARE USED TO LOCATE STRAND & REINFORCED PRIOR TO ANCHOR INSTALLATION. 6. EXPANSION ANCHOR INSTALLATION SHALL NOT NICK OR DAMAGE EXISTING REINFORCE. 7. EXPANSION ANCHOR SHALL BE INSTALLED PER CURRENT ICC6ES EVALUATION REPORT FROM OTHER OSHPD APPROVED TESTING AGENCY AND PER CAN 261912A.1. 8. TESTING OF EXPANSION ANCHORS SHALL BE PER CBC SECTION 1916A.8 AND PER CAN 261916A.8. 9. EXPANSION ANCHORS SHALL BE INSTALLED TO COMPLY WITH THE MIN. SLAB THICKNESS REQUIREMENTS ESTABLISHED BY THE MANUFACTURER'S TECHNICAL GUIDE FOR THE SPECIFIED ANCHOR, PROVIDED SUFFICIENT TEST DATA IS PROVIDED TO SUPPORT SAID INSTALLATION. IF SUFFICIENT TEST DATA IS NOT PROVIDED THAN DESIGN VALUES LISTED IN TABLE ABOVE ARE NOT VALID REQUIRING DESIGN VALUES TO BE DESIGNED BY SEOR AND REVIEWED BY OSHPD.

ra f

t_

823 -2 01 2
UPPER FLUTE (VALLEY) 4 1/2" MIN. 12" TYP.

LOWER FLUTE (RIDGE)

Issue Date : XX/XX/XX Revision : Date :

OPD No:

EXPANSION ANCHOR INSTALLATION CRITERIA


8/22/2012 5:06:52 PM

CL1.4b

163/8" OR 165/8" 163/8" OR 1 5/8" 163/8" OR 165/8" . 3/8" MIN. 3 3/4" . MIN. 3/8" 4" . 3/8" MIN. 6"

STRUCTURAL STUD ('S'6SECTIONS) . 365/8" 161/4" OR 261/2"


*

4" 161/4" OR 261/2"


*

6" 161/4" OR 261/2"


*

STRUCTURAL TRACK ('T'6SECTIONS) 6 DEEP LEG TRACK (WHERE OCCURS AS NOTED IN DETAILS)
*

18 27 33 43 54 68 97

118

NOTE:

Agency Stamp: Code : Section Title : SUSPENDED CEILING FRAMING COMPONENTS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

METAL STUD PROFILES


8/22/2012 5:06:52 PM

1. SEE WALL STUD FRAMING SECTIONS FOR THICKNESS OF STUDS & TRACKS. 2. Fy = 50KSI FOR 54 MIL (16GA) & THICKER SECTIONS, AND Fy = 33KSI FOR SECTIONS UP TO & INCLUDING 43 MI (18GA). 3. SIZE AND THICKNESS ARE CONSIDERED MINIMUMS. 4. STRUCTURAL STUDS MAY BE PUNCHED UNLESS NOTED OTHERWISE. STRUCTURAL TRACK SHALL BE UNPUNCHED UNLESS NOTED OTHERWISE.

ra f

t_

823 -2 01 2
25 22 20 18 16 14 12 10

DESIGNATION THICKNESS (MILS)

REFERENCE ONLY GAUGE NO.

CL1.5

12 GA. VERT. HANGER WIRE @ 4'60" O.C. EA. WAY WITH MINIMUM SEE CL4.1

12 GA. SPLAYED BRACE WIRES IN FOUR DIRECTIONS 90 APART @ 12'60" x 12'60" O.C. EA. WAY. SEE CL4.1

RIGID VERT. COMPRESSION STRUT, SEE DET. CL2.21 COMPRESSION STRUT SHALL NOT REPLACE HANGR WIRES 45 OR CL2.22

FOR CONDITIONS AT CORRIDORS REFER TO DETAIL

CL2.3

NOTES:

Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

ISOMETRIC DETAIL
8/22/2012 5:06:53 PM

ra f

t_

1. SEE SUSPENDED CEILING NOTES ON CL2.4

823 -2 01 2

CEILING PANELS, TYP.

CL2.1

6'60" MAX. 6'60"MAX.

12'60" MAX.

CL2.7

FIXED JOINT

CL2.7 12'60" MAX. 144SF CROSS RUNNERS TYP. MAIN RUNNERS BRACING WIRE LOCATION6TYP.

CL2.7

EXPANSION JOINT

NOTE:

Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

TYPICAL CEILING PLAN


8/22/2012 5:06:53 PM

ra f

BRACING WIRES AND COMP. STRUT SHALL OCCUR AT EVERY 144 SQ. FT. MAX. IN ROOMS OVER 144 SQ. FT.

t_

823 -2 01 2
CL2.7 7/8 x 2" x 16GA CONT. ANGLE @ PERIMETER.

STRUTS 8" MAX. FROM WALL TYP. ALONG EXPANSION JOINTS.

CL2.2

EXPANSION JOINT

FIXED JOINT

FIXED JOINT

CL2.5 SLIP JOINT

CL2.5

823 -2 01 2
O.H. CL2.6 CL2.6 EXPANSION JOINT

EXPANSION JOINT

FIXED JOINT

Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

SUSPENDED ACOUSTICAL CEILING6 CORRIDOR CEILING PLAN


8/22/2012 5:06:53 PM

ra f

LOCATION OF EXPANSION/SLIP JOINTS IN CORRIDORS

t_

CL2.3

4'60" OR LESS

8" MAX.

8" MAX.

TYP. HANGER WIRES @ 4'60"

TYPICAL SPLICE @ CROSS RUNNERS

823 -2 01 2
POP RIVET CONT. RUNNERS (SPLICE ALL JOINTS)

POP RIVET

Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

SUSPENDED ACOUSTICAL CEILING6 CORRIDOR INTERSECTION SLIP JOINT


8/22/2012 5:06:53 PM

ra f

t_

RUNNER SPLICE

SLIP JOINT

CL2.4

8" MAX. TYP. HANGER WIRE @ 4'60" O.C. W/ (1) PAIR OF BRACING WIRES PARALLEL TO WALL @ 12'60" O.C. & 4'60" MAX. FROM EACH END

TYP. HANGER WIRE @ 4'60" O.C.

TYPICAL SPLICE @ CROSS RUNNERS

3/4"CLR.

POP RIVET TYP. WALL ANGLE PER CL2.2

FIXED JOINT

RUNNER SPLICE

Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

TYPICAL CEILING SECTION


8/22/2012 5:06:53 PM

ra f

t_

823 -2 01 2
POP RIVET TYP. WALL ANGLE

ADDITIONAL BRACING WIRES REQUIRED PER FOR CORRIDOR

CL2.1

WIDTHS < 12'60"

EXPANSION JOINT

CL2.5

8" MAX. (SEE NOTE 1 BELOW) HANGER WIRE MAIN OR CROSS

8" MAX. (SEE NOTE 1 BELOW)

3/4" CLR.

ACOUSTIC PANEL

POP RIVET @ FIXED SIDE ONLY

ALTERNATE STRUT SPACER LOCATION W/O NAIL CONT. SLOTTED ANGLE STRUT SPACER W/ HORIZ. 6d RINGSHANK NAIL (SEE NOTE 2 BELOW) (OMIT STRUT WHERE RUNNER IS WITHIN 12" OF WALL)

FIXED JOINT
1.

PROVIDE #12 GAGE HANGER WIRES AT THE ENDS OF ALL MAIN AND CROSS RUNNERS WITHIN EIGHT (8) INCHES OF THE SUPPORT OR WITHIN ONE6FOURTH (1/4) OF THE LENGTH OF THE END TEE, WHICHEVER IS LEAST, FOR THE PERIMETER OF THE CEILING AREA. PERIMETER WIRES ARE NOT REQUIRED WHEN THE LENGTH OF THE END TEE IS EIGHT (8) INCHES OR LESS.

2. NAILS AT ENDS OF HORIZONTAL STRUTS ARE TO BE PLACED WITH NAIL HEAD TOWARD CENTER LINE OF SPAN OF STRUT.

ra f

t_

3. SPACER MAY ALSO BE CHANNELS WITH "DIAMOND POINTS" OF SPRING STEEL WHICH SNAP TIGHT TO PREVENT MOVEMENT OF STRUT.

823 -2 01 2
RUNNER

EXPANSION JOINT

CHANNEL. (HORIZ. STRUT)

Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

CEILING PERIMETER
8/22/2012 5:06:54 PM

CL2.6

LOCATE HANGER WIRE AT EACH TRACK CONNECTIONS SPLICE @ CROSS RUNNERS T6BAR ACOUSTICAL CEILING PANEL

Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

SUSPENDED ACOUSTICAL CEILING6 CUBICLE CURTAIN I.V. TRACK


8/22/2012 5:06:54 PM

ra f

t_

823 -2 01 2
24" MAX. CUBICLE CURTAIN OR I.V. TRACK

26#8 S.M.S. @ 48" O.C. AND 12" MAX. FROM EACH END OF TRACK ATTACHED TO CEILING GRID MEMBERS ONLY.

CL2.7

NOTES:
1. ATTACH ALL LIGHT FIXTURES TO THE CEILING GRID RUNNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. 2. SUPPORT SURFACE MOUNTED LIGHT FIXTURES BY AT LEAST TWO POSITIVE DEVICES WHICH SURROUND THE CEILING RUNNER AND WHICH ARE EACH SUPPORTED FROM THE STRUCTRE ABOVE BY A 12 GA. WIRE SPRING CLIPS OR CLAMPS THAT CONNECT ONLY TO THE RUNNER ARE NOT ACCEPTABLE. 3. SUPPORT PENDANT MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE ABOVE WITH HANGERS WIRES OR CABLES CAPABLE OF SUPPORTING 2 TIMES THE WEIGHT OF THE FIXTURE.

AIR TEMINAL OR LIGHT FIXTURE (56# MAX.)

ra f
Agency Stamp: Code : Section Title : SUSPENDED ACOUSTICAL CEILING DETAILS . Sheet Title : 2010 CBC

t_
HEAVY DUTY SYSTEM

823 -2 01 2

12GA WIRE HANGERS HEAVY DUTY SYSTEM: PLACE ON DIAGONAL CORNERS (2) EXCEPT 4'x 4' FIXTURES SHALL HAVE HANGERS AT EACH CORNER (4). DEVICES THAT WEIGHT LESS THAN 56 LBS REQUIRE A MINIMUM OF 2 SLACK WIRES LOCATED AT DIAGONAL CORNERS.

26#8 S.M.S. EA. SIDE OR PROVIDE

Issue Date : XX/XX/XX Revision : Date :

OPD No:

SUSPENDED ACOUSTICAL CEILING6 LIGHT FIXTURES/ AIR TERMINAL SUPPORT DETAIL


8/22/2012 5:06:54 PM

CL2.8

FOR CONNECTION TO STRUCTURE SEE CL5.1

STRUCTURE

L < 6'60" < 8'60"

CHANNEL 250T125633 (20 GA) 400S137633 (20 GA)

CHANNEL PER SCHEDULE

823 -2 01 2
6" MAX. 2" MAX.

HANGER WIRE SPLAY WIRES SEE CL4.1

0 TO 45 MAX.

3/4" MIN. EDGE DISTANCE,TYP. .

ra f

(2) 1/4"DIA. MACHINE BOLT

t_

MAIN RUNNER CROSS RUNNER

Agency Stamp: Code : Section Title : COMPRESSION STRUT DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

SUSPENDED ACOUSTICAL CEILING6 CHANNEL TYPE COMPRESSION STRUT


8/22/2012 5:06:54 PM

CL3.1

ELECTRICAL CONDUIT TUBE SCHEDULE


L 4'60" 5'66" 7'60" DIA. 3/4" 1" 161/4" "t" 0.046" 0.054" 0.061"

STRUCTURE FOR CONNECTION TO STRUCTURE SEE

CL5.1
HANGER WIRE WITHIN

ELECTRICAL CONDUIT TUBE PER SCHEDULE HANGER WIRE

(3) #10 S.M.S. @ 2" O.C.

823 -2 01 2
6"MAX. SPLAY WIRES SEE

CL4.1

(3) #10S.M.S. @ 2" O.C.

12"MAX.

6"MIN. OVERALL

TIGHT TO RUNNER

FLATTEN END

2"MAX.

ra f

LOWER SECTION ONE SIZE LARGER THAN MAIN SECTION

t_
(1) 3/8"DIA. MACHINE BOLT SLOT END

OPTION 1

OPTION 3

OPTION 2

DOUBLE NUTS

Agency Stamp: Code : Section Title : COMPRESSION STRUT DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

SUSPENDED ACOUSTICAL CEILING6 TUBE TYPE COMPRESSION STRUT


8/22/2012 5:06:55 PM

CL3.2

1/2" DIA. WEDGE ANCHOR W/ 3 1/4" EMBED 2" X 2" X 1/4" THK X 4" LONG ANGLE CHANNEL PER SCHEDULE L (2) 1/4" DIA. MACHINE BOLT OR (3)6#10 S.M.S. @ EACH END OF KICKER < 6'60" < 8'60"

CONCRETE STRUCTURE

CHANNEL 4"x 165/8"x 16GA STUD 6"x165/8"x 16GA STUD

823 -2 01 2
CHANNEL KICKER TO MATCH VERT. 6" MAX. 2" MAX. 1 2'60" MAX.

HANGER WIRE SPLAY WIRES SEE

CL4.1

t_

ra f

(2) 1/4" DIA. MACHINE BOLT OR (2) #12 S.M.S.

MAIN RUNNER CROSS RUNNER

Agency Stamp: Code : Section Title : COMPRESSION STRUT DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

SUSPENDED ACOUSTICAL CEILING6 CHANNEL TYPE COMPRESSION STRUT OFFSET WITH KICKER
8/22/2012 5:06:55 PM

CL3.3

ELECTRICAL CONDUIT TUBE SCHEDULE


L 5'66" 7'60" DIA. 2.5" 3" "t" 0.072" 0.072"

1/2" DIA. WEDGE ANCHOR W/ 3 1/4" EMBED 2" X 2" X 1/4" THK X 4" LONG ANGLE.

CONCRETE STRUCTURE ELECTRICAL CONDUIT TUBE PER SCHEDULE

#14 S.M.S.

ELECT. CONDUIT TUBE SEE SCHED. 12" MAX.

823 -2 01 2
SPLAY WIRES SEE 6 MIN. OVERALL

HANGER WIRE

CL4.1

4" MAX. 2" MAX.

SLOT END

ra f

(1) 3/8" DIA. MACHINE BOLT (TYP. @ TOP AND BOTTOM) LOWER SECTION ONE SIZE LARGER THAN MAIN SECTION

t_

DOUBLE NUTS 26# 14 S.M.S. @ EA. END OF KICKER

1'60" MAX.

Agency Stamp: Code : Section Title : COMPRESSION STRUT DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

SUSPENDED ACOUSTICAL CEILING6TUBE TYPE COMPRESSION STRUT OFFSET WITH KICKER


8/22/2012 5:06:55 PM

CL3.4

FOR CONNECTION TO STRUCTURE SEE CONNECTION MATRIX ON

CL4.2
3" MAX. 3 TURNS TYPICAL @ EACH END

HANGER WIRE

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

HANGER & SPLAY WIRE CONNECTION6 TYPICAL WIRE TURNS


8/22/2012 5:06:55 PM

ra f

t_
SPLAY WIRE

823 -2 01 2
CL4.2
0 TO 45.0 MAX. 3"
.

FOR CONNECTION TO STRUCTURE SEE CONNECTION MATRIX ON

3 TURNS TYPICAL @ EACH END

CL4.1

STRUCTURAL CONDITION OF FLOOR/ ROOF ABOVE SUSPENDED CEILING


CONCRETE FILLED METAL DECK METAL DECK WITH NON STRUCTURAL FILL CONCRETE SLAB, BEAM, OR JOIST STRUCTURAL STEEL SAWN TIMBER

APPLICABLE DETAIL
CL4.3 CL4.4 CL4.5 CL4.6 CL4.7 CL4.8

METAL STUD WALL

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

HANGER & SPLAY WIRE CONNECTION6 CONNECTION MATRIX


8/22/2012 5:06:56 PM

ra f

t_

823 -2 01 2
CL4.2

C L BOLT & FLUTE LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE

C L

POWDER6ACTUATED CEILING CLIP ASSEMBLY (REF. ICC6ES AC70 REPORT NO.)

1" MIN.

1" MIN.

13GA x 3/4" CEILING CLIP

3/8" DIA. SLEEVE ANCHOR OR 3/8" DIA. WEDGE ANCHORS

STEEL DECK

CL4.1
3/8" MAX.

MIN. # 12 GA. ASTM A641 CLASS 1 WIRE

MIN. 3 TIGHT

MIN. 5/8" DRILL6IN EXPANSION ANCHOR W/ 4" MIN. EMBED. (REF. ICC6ES AC193 REPORT NO.)

t_

ra f

SPLAY WIRE

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

CONNECTION TYPE I CONCRETE FILLED METAL DECK


8/22/2012 5:06:56 PM

823 -2 01 2
HANGER
OPTION 2

OPTION 1

OPTION 2

OPTION 3

MIN. 3 TIGHT TURNS IN 3" MIN. # 12 GA ASTM A641 CLASS 1 WIRE

CL4.3

METAL DECK (20 GA MIN.) WITH NON6 STRUCTURAL FILL ASSEMBLY

1" MIN. 161/2" TO 2" 2" WIDEx 16GA STRAP #10 S.M.S. (4 PER CHANNEL) L 161/2"x 161/2"x 16ga OR 162T125616 #10 S.M.S. EACH SIDE

CL4.1 OPTION 2

OPTION

HANGER
METAL DECK (20 GA MIN.) W/ NON6STRUCTURAL FILL ASSEMBLY

66 #10 S.M.S. @ 2" O.C. 6" WIDE x 4" LONG x 12GA STRAP

823 -2 01 2
STRUC'L CONC. FILL POWDER6ACTUATED CEILING WIRE ASSEMBLY (REF. ICC6ES AC70 REPORT NO.) STRUCTURAL CONCRETE MIN. # 12 GA. ASTM A641 CLASS 1 WIRE

POWDER6ACTUATED CEILING WIRE ASSEMBLY (REF. ICC6ES AC70 REPORT NO.)

STEEL DECK

1/4" DIA. HOLE @ 1/2" FROM EDGE

MIN. # 12 GA. ASTM A641 CLASS 1 WIRE

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

CONNECTION TYPE 2 METAL DECK AND NON6STRUCTURAL FILL MATERIAL


8/22/2012 5:06:56 PM

ra f

t_

SPLAY WIRE

CL4.4

5/8" DIA. WEDGE ANCHOR W/ 4" EMBED. LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE SLAB. DO NOT CONNECT SPLAY WIRE TO JOIST OR BEAM.

CL4.1
1/2" (MAX) STEEL ANGLE 2" WIDE x 3" LONG x 1/4" THK.

OPTION 1

OPTION 2

SPLAY WIRE
261/4" MIN. EDGE DISTANCE FACE OF BEAM OR JOIST WHERE OCCUR 3/8" DIA. SLEEVE ANCHOR OR 3/8" DIA. WEDGE ANCHOR

13 ga x 1 1/2" WIDE CEILING CLIP

CL4.1

OPTION 1

823 -2 01 2
LIGHTWEIGHT OR NORMAL WEIGHT CONC. SLAB, BEAM OR JOIST SOFFIT (MIN. 461/2" WIDE) 3/8" MAX.

OPTION 2

t_

HANGER

APPROVAL OF THE ENGINEER OF RECORD IS REQUIRED PRIOR TO INSTALLATION OF ANCHORAGE INTO PRESTRESSED CONCRETE.

ra f

NOTE:

POWDER6ACTUATED CEILING CLIP ASSEMBLY ( REFERENCE ICC6ES AC70 REPORT NO.)

MIN. 3 TIGHT TURNS IN 3"

MIN. # 12 GA. ASTM A641 CLASS 1 WIRE

OPTION 3
Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

HANGER & SPLAY WIRE CONNECTION TYPE 36 CONCRETE SLAB, BEAM, JOIST
8/22/2012 5:06:56 PM

CL4.5

260.145" DIA. SHOT PINS PER

FIRE PROOFING

CL1.3
STRUCTURAL STEEL 3/8" MAX.

161/2"x 161/2"x 13ga x 0'63" CLIP

TEST EACH WIRE & CLIP ASSEMBLY FOR 200# TENSION LOAD.

3/8" MAX.

3/8" DIA. 307 BOLT

3/16" MIN. TEST EACH WIRE AND CLIP ASSEMBLY FOR 440# TENSION LOAD IN THE DIRECTION OF THE WIRE.

t_

ra f

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

HANGER & SPLAY WIRE CONNECTION TYPE 46 STRUCTURAL STEEL


8/22/2012 5:06:56 PM

823 -2 01 2
HANGER
1/4" MAX. 3" WIDE x 2"LONG x 12GA CLIP

FIRE PROOFING

STRUCTURAL STEEL

SPLAY WIRE

CL4.6

2 x MIN. GYP. BOARD WHERE OCCURS

161/4" MIN.

1/4" DIA. CLOSED EYE SCREW 4" X 4" BLOCKING FASTEN TO JOIST USING 1 1/2" X 2 1/2" X 18 GA. FRAMING ANGLE W/ 868d X 1 1/2" NAILS EACH SIDE AND EACH END.

HANGER

1/2" DIA. EYE SCREW W/ 3" MIN. PENETRATION AT ANGLE OF WIRE. GYP. BOARD WHERE OCCURS

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

HANGER & SPLAY WIRE CONNECTION TYPE65 SAWN TIMBER


8/22/2012 5:06:57 PM

ra f
SPLAY WIRE

t_

823 -2 01 2
0645 MAX.

CL4.7

METAL STUD (20 ga. MIN.) 1 LAYER OF GYP. BD. 26#10 S.M.S. @ 1" O.C. 1/2" 13 GA.x 2" WIDE CLIP ANGLE BACK TO BACK 161/2" X 3" X 14 GA ANGLE (LLV) SPAN 4 WALL STUDS MIN. FASTEN ANGLE TO WALL STUDS USING 2"X #10 X 16 1/4" SMS PER ANGLE AT EACH STUD.

1/2" 2" 1/2"

SPLAY WIRE

0 TO 45 MAX.

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

CONNECTION TO METAL STUD WALL FRAMING


8/22/2012 5:06:57 PM

ra f

t_

823 -2 01 2
1 6

HANGER

CL4.8

FRAMING GYP. BD.

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

CONNECTION TO METAL STUD WALL FRAMING


8/22/2012 5:06:57 PM

ra f

NOTE: THIS IS APPLIED FOR PERIMETER WIRE ATTACHEMENT OR WHERE OBSTRUCTION PREVENTS ATTACHMENT TO STRUCTURE ABOVE.

t_

A. "DIRECT" (FOR NOTES SEE "THRU GYP")

823 -2 01 2
B. "THRU GYP"

(1) #10 SCREW TO FRAMING 163/4" x 3/4" 12 GA CLIP

CEILING HANGER WIRE AS REQUIRED

CL4.9

16 GA. BACKING STUD. SPAN 3 WALL STUDS MINIMUM. FASTEN BACKING TO WALL STUDS USING 2X #10X161/4" SMS AT EACH STUD. 12 GA.X 1" WIDE SIESMIC BRACKET. FASTEN TO BACKING STUD USING #10 X 161/4" SHEET METAL SCREW.

Agency Stamp: Code : Section Title : HANGER & SPLAY . WIRE CONNECTION DETAILS Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

CONNECTION TO METAL STUD WALL FRAMING


8/22/2012 5:06:57 PM

ra f

t_

823 -2 01 2

12 GA. PERIMETER WIRE WITH 3 TIGHT TURNS IN 3" BOTH ENDS OF WIRE TYPICAL.

CL4.10

STRUCTURAL CONDITION OF FLOOR / ROOF ABOVE SUSPENDED CEILING


CONCRETE FILLED METAL DECK METAL DECK WITH NON STRUCTURAL FILL CONCRETE SLAB, BEAM, OR JOIST STRUCTURAL STEEL SAWN TIMBER WITH GYPSUM BOARD

APPLICABLE DETAIL
CL5.2 CL5.3 CL5.4 CL5.5 CL5.6 CL5.7

SAWN TIMBER WITHOUT GYPSUM BOARD

Agency Stamp: Code : Section Title : COMPRESSION STRUT CONNECTION DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

COMPRESSION STRUT CONNECTION6 CONNECTION MATRIX


8/22/2012 5:06:58 PM

ra f

t_

823 -2 01 2
CL5.1

LIGTHWEIGHT OR NORMAL WEIGHT CONCRETE

1" MIN. #10 S.M.S. 2" 4 1/2" MIN. 5/16" DIM. SLEEVE ANCHOR @ CENTER OF FLUTE FLATTEN END PLACE TIGHT TO CLIP OR STRUCTURE CUT FLANGES AND BEND 161/2"x 161/2"x 13 ga x 0'62" SLOT END OF TUBE WIRE WITHIN CLIP PER

CL4.3

PLACE TIGHT TO CLIP OR STRUCTURE

OPTION 1

OPTION 2

CHANNEL STRUT
1" MIN.

5/16" DIA. SLEEVE ANCHOR @ CENTER OF FLUTE PLACE TIGHT TO CLIP OR STRUCTURE

ra f D
Agency Stamp: Code : Section Title : 2010 CBC

t_
OPTION 3

823 -2 01 2

TUBE STRUT

L 161/2 x 161/2 x 13 ga.x 0'62" #10 S.M.S.x 2" LONG SLOT END OF TUBE

TUBE STRUT

COMPRESSION STRUT CONNECTION DETAILS . Sheet Title :

Issue Date : XX/XX/XX Revision : Date :

OPD No:

COMPRESSION STRUT CONNECTION TYPE 16 CONCRETE FILLED METAL DECK


8/22/2012 5:06:58 PM

CL5.2

METAL DECK (20 GA MIN.) AND LIGHT WEIGHT OR REGULAR CONCRETE

CHANNEL STRUT

Agency Stamp: Code : Section Title : COMPRESSION STRUT CONNECTION DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

CONNECTING TYPE6 2 METAL DECK AND NON6STRUCTURAL FILL ASSEMBLY


8/22/2012 5:06:58 PM

ra f

t_

823 -2 01 2
260.145 DIM. SHOT6PINS CUT FLANGES AND BEND

PLACE TIGHT TO STRUCTURE

CL5.3

FACE OF BEAM OR JOIST WHERE OCCUR, TYPICAL

LIGTHWEIGHT OR NORMAL WEIGHT CONCRETE, TYP.

1" MIN. #10 S.M.S. 2" 5/16" DIM. SLEEVE ANCHOR FLATTEN END PLACE TIGHT TO CLIP OR STRUCTURE CUT FLANGES AND BEND 161/2"x 161/2"x 13 ga x 0'62" SLOT END OF TUBE WIRE WITHIN CLIP PER

CL4.5

PLACE TIGHT TO CLIP OR STRUCTURE

OPTION 1

OPTION 2

CHANNEL STRUT

5/16" DIA. SLEEVE ANCHOR

ra f D
Agency Stamp: Code : Section Title : 2010 CBC

t_
OPTION 3

PLACE TIGHT TO CLIP OR STRUCTURE

823 -2 01 2

TUBE STRUT

L 161/2 x 161/2 x 13 ga.x 0'62" #10 S.M.S.x 2" LONG SLOT END OF TUBE

TUBE STRUT

COMPRESSION STRUT CONNECTION DETAILS . Sheet Title :

Issue Date : XX/XX/XX Revision : Date :

OPD No:

COMPRESSION STRUT CONNECTION TYPE 63 CONCRETE SLAB, BEAM, JOIST SOFFIT


8/22/2012 5:06:58 PM

CL5.4

260.145" DIA. SHOT PINS

FIRE PROOFING FIRE PROOFING 260.145" DIA. SHOT PINS

3/16" MIN. #8 S.M.S.


2"

#10 S.M.S. PLACE TIGHT TO CLIP OR STRUCTURE

161/2 x 161/2x 13 ga x 0'63" ANGLE CUT FLANGES AND BEND

CHANNEL STRUT
FIRE PROOFING

OPTION 1

823 -2 01 2
260.145" DIA. SHOT PINS 161/2"x 161/2"x 13 ga x 3" ANGLE SLOT END OF TUBE

260.145" DIA. SHOT PINS

FIRE PROOFING

PLACE TIGHT TO CLIP OR STRUCTURE

#10 x 2" S.M.S.

ra f

t_

PLACE TIGHT TO CLIP OR STRUCTURE

WIRE WITHIN

Agency Stamp: Code : Section Title : COMPRESSION STRUT CONNECTION DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

COMPRESSION STRUT CONNECTION TYPE64 STRUCTURAL STEEL


8/22/2012 5:06:59 PM

OPTION 2

OPTION 3

CL5.5

FASTEN COMPRESSION STRUT TO 2x 4 IN LIEU OF RAFTER/ JOIST

C L STRUT

1 1/4" MIN.

1 1/4" MIN.

GYP. BOARD

1/4" DIA. LAG SCREW CUT FLANGES AND BEND

2x4 STRUT 1/4" DIA. LAG SCREW CONNECT USING OTHER DETAIL ON THIS SHEET

OPTION

OPTIONAL 2x4 STRUT FOR CHANNEL & TUBE STRUTS

1/4" DIA. LAG SCREW

1 1/4"

823 -2 01 2
1/4" DIA. LAG SCREW 1 1/4" #10 S.M.S. PLACE TIGHT TO CLIP OR STRUCTURE

CHANNEL STRUT

1 1/4" 161/2" X 161/2" 13 GA. BEARING PLATE (MIN.) 1/4" DIA. CLOSED EYE SCREW WIRE WITHIN

OPTIONAL ORIENTATION SLOT END PLACE TIGHT TO CLIP OR STRUCTURE #10 S.M.S.

ra f

L6161/2"x161/2"x 13 ga x 0'62" CLIP

t_
OPTION

OPTION

OPTION

D
Agency Stamp: Code : Section Title : 2010 CBC

TUBE STRUT

COMPRESSION STRUT CONNECTION DETAILS . Sheet Title :

Issue Date : XX/XX/XX Revision : Date :

OPD No:

COMPRESSION STRUT CONNECTION TYPE65 SAWN TIMBER WITH GYPSUM BOARD


8/22/2012 5:06:59 PM

CL5.6

1 1/4" #8 1/4" DIA. LAG SCREWS 1 1/2" MIN. FASTEN COMPRESSION STRUT TO 2x4 IN LIEU OF RAFTER/ JOIST

C L COMPRESSION STRUT

161/4" 2"MIN.

2x4 FLAT STRUT

2"

1/4"DIA. LAG SCREW IN CENTER OF JOIST, TYP. CUT FLANGES AND BEND

CONNECT USING OTHER DETAILS ON THIS SHEET

OPTION 1

OPTION 2

CHANNEL STRUT

1/4"DIA. LAG SCREW IN CENTER OF JOIST, TYP.

161/4"

823 -2 01 2
1/4" DIA. LAG SCREW 161/4" #10 S.M.S. PLACE TIGHT TO STRUCTURE

OPTIONAL 2x4 STRUT FOR CHANNEL OR TUBE STRUTS

161/4"

ra f

PLACE TIGHT TO CLIP

t_

SLOT END OF TUBE

#10 S.M.S.

161/2"x 161/2"x 13GA x 0'62" CLIP

161/2" X 161/2" 13 GA. BEARING PLATE (MIN.) 1/4"DIA. CLOSED EYE SCREW WIRE WITHIN

OPTION

OPTION

OPTION

TUBE STRUT

Agency Stamp: Code : Section Title : COMPRESSION STRUT CONNECTION DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

COMPRESSION STRUT CONNECTION TYPE66 SAWN TIMBER WITHOUT GYPSUM BOARD


8/22/2012 5:06:59 PM

CL5.7

CEILING OBSTRUCTION WHERE OCCURS

FOR CONNECTION TO STRUCTURE SEE

CL4.1
12 GA WIRE WITH MIN. OF 3 TIGHT TURNS TOP & BOTTOM LOCATE CHANNEL AS REQUIRED TO MAINTAIN HANGER SPACING CHANNEL PER

CL6.2

4'60' CEILING OBSTRUCTION WHERE OCCURS

4'60'

4'60"

ACOUSTICAL OR GYPSUM BOARD CEILING AS OCCURS

TRAPEZE SUPPORT

823 -2 01 2
NOTE:
6 MAX. SLOPE 1 FROM VERT.

FOR CONNECTION TO STRUCTURE SEE

CL4.1

12 GA WIRE WITH MIN. OF 3 TIGHT TURNS TOP & BOTTOM

ra f

t_
4'60' 4'60' 4'60"

SINGLE HANGER WIRES OK UP TO 1/6 OUT OF PLUMB. COUNTER SLOPING WIRES REQUIRED WHEN GREATER THAN 1/6 OUT OF PLUMB.

ACOUSTICAL OR GYPSUM BOARD CEILING AS OCCURS

COUNTER SLOPING WIRES

Agency Stamp: Code : Section Title : SPECIAL DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

ONSTRUCTION6COUNTER SLOPING WIRES AND TRAPEZE CONDITION


8/22/2012 5:06:59 PM

CL6.1

SEPARATE CONN. TO STRUCTURE BY AT LEAST 4 INCHES. DOUBLE HANGER WIRES MAX. 8'60" OR LONGER SPANS 1/6 OUT PLUMB. CONNECT TO STRUCTURE PER #10 S.M.S TOP & BOTT. TO PREVENT HGR. FROM SLIPPING OFF.

CL4.1
16 GA TRACK BRIDGE BETWEEN ADJACENT STUDS (3 STUDS MIN.) (4) # 10 S.M.S.TYP. 26#10 S.M.S. EACH STUD

OBSTRUCTIONS

823 -2 01 2
PROVIDE COMPRESSION STRUT WHERE OCCURS ACOUSTICAL OR GYPSUM BOARD CEILING AS OCCURS 12'60" MAX.

SADDLE TIE HANGERS TO CHANNEL

PROVIDE COMPR. STRUT & SPLAY WIRE WHERE CLG. STRUT OCCURS

CHANNEL PER SCHEDULE

#10 S.M.S. TOP & BOTT.

t_

#8 S.M.S. @16"O.C. STAGGERED @ EA. END

WALL WHERE OCCURS

SPAN
4 FT. 6 FT. 8 FT. 10 FT. 12 FT.

SECTION

261/2" x 165/8" x 16GA. STUD DBL. 261/2" x 163/8" x 16GA. STUD DBL. 261/2" x 165/8" x 16GA. STUD DBL. 361/2" x 165/8" x 16GA. STUD DBL. 4" x 165/8" x 16GA. STUD

DBL. SECTION

Agency Stamp: Code : Section Title : SPECIAL DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

OBSTRUCTION6BRIDGE AT LARGE OFFSET CONDITION


8/22/2012 5:07:00 PM

ra f

CL6.2

NORTH

EAST

09 22 20 MAIN RUNNER

Agency Stamp: Code : Section Title : SPECIAL DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

OBSTRUCTION6COUNTER SLOPING COMPRESSION STRUTS


8/22/2012 5:07:00 PM

ra f

OPPOSING COMPRESSION POST FOR ACOUSTICAL CEILING

t_

823 -2 01 2
SOUTH

ATTACH TO STRUCTURE. SEE COMPRESSION STRUT CONNECTION FOR MORE DETAIL. WEST

OPPOSING COMPRESSION POSTS MAX LENGTH 20'. BOTH POSTS TO BE SAME ANGLE; MAX ANGLE FROM HORIZONTAL OF 70, MIN ANGLE FROM HORIZONTAL OF 30. SEE COMPRESSION STRUT CONNECTION FOR MORE DETAIL. HANGER WIRE AT EACH COMPRESSION POST 3 TIGHT TURNS.

(2) 12 GA BRACE WIRES ORTHOGONAL TO OPPOSING POSTS ATTACHED TO STRUCTURE. SEE HANGER & SPLAY WIRE CONNECTION TO STRUCTURE FOR MORE DETAIL. 45 MAX, TYP 09 22 20 (2) #8 SCREWS

2" M AX (T YP .)

NOTE: ONE WIRE PER 46WAY INTERSECTION MAY BE FIXED TO STUD EDGE 2" MAX ABOVE MAIN RUNNER (AT OBSTRUCTION)

CL6.3

16 GA.WALL BACKING

FRAMING GYP. BD. (3) #10 SCREW TO FRAMING, TOP & BOTTOM

10 GA. LLH 5"x6"x0'66" LONG 4" MIN. AT LOCATIONS W/O WALL BACKING IN6WALL, INSTALL 6" X 16 GA. TRACK OUTSIDE OF GYP. BD, FASTEN TO WALL STUD USING (3) #10 S.M.S. AT EACH STUD. MEP OBSTRUCTION

EXTENDED CLIP AT OBSTRUCTIONS


WHEN OBSTRUCTIONS OCCURRED BOTH AT THE WALL AND ABOVE THE GRID AT THE PERIMETER HANGER WIRE.

Agency Stamp: Code : Section Title : SPECIAL DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

OBSTRUCTION6PERIMETER CONDITION
8/22/2012 5:07:00 PM

ra f

t_

823 -2 01 2

CEILING HANGER WIRE AS REQUIRED

CL6.4

20 GA ANGLE SCREWED TO (2) STUDS,WITH (2) #10 SMS TO EACH STUD ANGLE 1.5" x 1.5" x 20 GA WITH (2) #8 SMS EACH END LIGHT FIXTURE SUPPORT BRACKET STRONGBACK 250S162643, SPAN TO ADJ VERT L OR COMP POST EA SIDE, 4'60" MAX EACH DIRECTION .

DO NOT ATTACH CLG TO LIGHT FIXTURE

45 MAX.

20 GA CLIP ANGLE WITH (2) #8 SMS EA LEG

t_ ra f
DO NOT ATTACH CLG TO LIGHT FIXTURE Agency Stamp: Code : Section Title : SPECIAL DETAILS . Sheet Title : 2010 CBC 45 MAX.

LOCATIONS WITHOUT CROSS JOISTS

823 -2 01 2
CROSS JOIST .

LOCATIONS WITHOUT CROSS JOISTS

ANGLE 1.5" x 1.5" x 20 GA WITH (2) #8 SMS EACH END

STRONGBACK FROM ADJ LOCATION WHERE OCCURS

Issue Date : XX/XX/XX Revision : Date :

OPD No:

OBSTRUCTION6RECESSED LIGHT AT PERIMETER


8/22/2012 5:07:01 PM

CL6.5

1/2" MAX.

5/8" DIA. WEDGE ANCHOR W/ 4" EMBED

(2) 1/4"620 MACHINE BOLTS KICKER BRACE PER SCHEDULE NOTE: KICKER IS AN ALTERNATE TO SPLAY WIRES. THIS METHOD MAY BE USED IN LIEU OF OPPOSING WIRES. COMPRESSION POST COMPRESSION POST 2 1/2" X 16 GA. STUD 1/2" MAX.

KICKER

823 -2 01 2
0 TO 45 MAX.

OBSTRUCTION

ra f
FRONT VIEW

t_
ATTACH KICKER TO MAIN MAIN RUNNER RUNNER WITH (2)1/4620 MACHINE BOLTS

SIDE VIEW

D
Agency Stamp: Code : Section Title : SPECIAL DETAILS . Sheet Title : 2010 CBC

T BAR CEILING 6 WIRE OBSTRUCTION DETAIL STUD BRACE, LESS SPLAY WIRES, TO DECK.

Issue Date : XX/XX/XX Revision : Date :

OPD No:

OBSTRUCTION6STUD BRACE TO OVERHEAD


8/22/2012 5:07:01 PM

CL6.6

5/8" DIA. WEDGE ANCHOR W/ 4" EMBED

3/4" 1/2" MAX. 2x 1/4"620 MACHINE BOLTS 1/4"620 MACHINE BOLT

1/2" 2" 1/2"

KICKER BRACE PER SCHEDULE BACK TO BACK 161/2" X 3" X 14 GA ANGLE (LLV) SPAN 4 WALL STUDS MIN. FASTEN ANGLE TO WALL STUDS USING 2"X #10 X 16 1/4" SMS PER ANGLE AT EACH STUD.

COMPRESSION POST 2 1/2" X 16 GA. STUD

823 -2 01 2
0 TO 45 MAX. MAINRUNNER SIDE VIEW

OBSTRUCTION

NOTE: KICKER IS AN ALTERNATE TO SPALY WIRES. THIS METHOD MAY BE USED IN LIEU OF OPPOSING WIRES.

KICKER SCHEDULE SPAN < < < 4'60" 8'60" 14'60" MATERIAL 20 GA 20 GA 16 GA

SSMA

250S137633 400S162633 400S162654

Agency Stamp: Code : Section Title : SPECIAL DETAILS . Sheet Title : 2010 CBC Issue Date : XX/XX/XX Revision : Date :
OPD No:

OBSTRUCTION6STUD BRACE TO WALL


8/22/2012 5:07:01 PM

T BAR CEILING 6 WIRE OBSTRUCTION DETAIL STUD BRACE, LESS SPLAY WIRES, TO WALL.

ra f

t_

ATTACH KICKER TO MAIN RUNNER WITH 1/4620 MACHINE BOLT

CL6.7