Installation, Inspection and Maintenance of Electrical Installations in Potentially Explosive Atmospheres in accordance with IEC 60079-14 and IEC 60979-18

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 1

Europe

Installation IEC 60079-14


General requirements Requirements for non-hazardous apply Electrical apparatus only to be used within their electrical ratings for power Hazardous areas divided in to Zones Documentation Area classification documents Instructions for erection and connection Documents for apparatus with special conditions marked with an X
CEAG Sicherheitstechnik GmbH
Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 2

Europe

Installation IEC 60079-14


Assurance of Conformity of Apparatus Certification Selection of Apparatus Specific information Selection according to Zones Selection according to Temperature Class Selection according to Apparatus Class External influences
CEAG Sicherheitstechnik GmbH
Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 3

Europe

Check list - Apparatus


is appropriate to area classification explosion group is correct temperature class is correct documentation is complete no damage no inadmissable modifications bolts, cable entries etc. complete and tight seals and gaskets satisfactory electrical connections are tight lamp ratings, type and position correct flameparths within max. values and clean "d" special conditions of use are complied with "i"

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 4

Europe

Check list - Installation


Cable and wiring as selected Cable and wiring earthed as required Cable and wiring is not damaged Cable entries correctly closed Cable glands correct No inadmissible bunching of cables Fulfilment of all special requirements Proper function of all protective devices Installation corresponds to documentation Potential equalization correct Eletrostatic at safe level Lightning protection according to the rules Emergency switch-off according to the rules Purg time is sufficient ("p")
CEAG Sicherheitstechnik GmbH
Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 5

Europe

Check list - Installation


Electrical circuits "e" and "i" separated Ingress protection sufficient Mechanical protection sufficient Thermal protection sufficient Chemical protection sufficient

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 6

Europe

Inspection and Maintenance IEC 60079-17


Maintenance
to retain or restore to original spec. so to perform its correct function

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 7

Europe

Inspection scrutiny with or without partial dismantling, and if necessary measurement to reach a conclusion on the condition of the apparatus

visual - inspection which identifies, without the use of


access equipment or tools, those defects, such as missing bolts, which will be apparent to the eye

close - aspects covered by a visual inspection and, in


addition, identifies those defects, such as loose bolts, which will be apparent only by the use of access equipment, for example steps, (where necessary), and tools
CEAG Sicherheitstechnik GmbH
Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 8

Europe

Inspection
detailed - aspects covered by a visual inspection and,
in addition, identifies those defects, such as loose terminations, which will only be apparent by opening the enclosure, and/or using, where necessary, tools and test equipment

initial - inspection of all electrical apparatus, systems and


installations before they are brought into service

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 9

Europe

Inspection
periodic - inspection of all electrical apparatus, systems
and installations carried out on routine basis

sample - inspection of a proportion of the electrical


apparatus, systems and installations

continuous supervision - frequent attendance, inspection,


service, care and maintenance of the electrical installation by skilled personnel who have experience in the specific installation and its environment in order to maintain the explosion protection features of the installation in satisfactory condition
CEAG Sicherheitstechnik GmbH
Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 10

Europe

General requirements
documentation area classification apparatus group and temperature class technical information, spares lists, manufacturers instructions etc.

qualification of personnel experienced and trained personnel, with knowledge of types of protection, installation practices, relevant rules and regulations. With evidence of relevant experience and training

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 11

Europe

Continuous supervision
Concept - where an installation is visited on a regular basis
in the normal course of work by skilled personnel who are required to carry out visual and/or close inspections as part of their normal work schedule and detailed inspections as part of any replacement, repair, modification or adjustment

Objective - continuous supervision is to enable the


early detection of arising faults and their subsequent repair.

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 12

Europe

Continuous supervision
Responsibilities Technical persons with executive function Skilled personnel Frequency of inspection Documents Training

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 13

Europe

Maintenance requirements
Remedial measures and alterations
maintain the integrity of the type of protection provided for the apparatus; this may require consultation with the manufacturer. Replacement parts shall be in accordance with the safety documentation. Alterations to apparatus shall not be carried out without appropriate authorization where they adversely affect the safety of the apparatus as stated in the safety documentation.

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 14

Europe

Maintenance requirements
Maintenance of flexible cables
Flexible cables, flexible conduits and their terminations are particularly prone to damage. They shall be inspected at regular intervals and shall be replaced if found to be damaged or defective.

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 15

Europe

Maintenance requirements
Withdrawal from service
If it is necessary, for maintenance purposes, to withdraw apparatus, etc. from service, the exposed conductors shall be a) correctly terminated in an appropriate enclosure, or b) isolated from all sources of power supply and insulated, or c) isolated from all sources of power supply and earthed. If the apparatus is to be permanently withdrawn from service, the associated wiring, which shall be isolated from all sources of power supply, shall be removed, or, alternatively, correctly terminated in an appropriate enclosure.
CEAG Sicherheitstechnik GmbH
Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 16

Europe

Maintenance requirements
Fastenings and tools
Where special bolts and other fastenings or special tools are required, these items shall be available and shall be used.

Environmental conditions
Electrical apparatus in a hazardous area can be adversely affected by the environmental conditions in which it is used. Some of the key elements to consider are corrosion, ambient temperature, ultraviolet radiation, ingress of water, accumulation of dust or sand, mechanical effects and chemical attack.
CEAG Sicherheitstechnik GmbH
Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 17

Europe

CEAG Sicherheitstechnik GmbH


Inst & Maint 250804.ppt/01.08.2002/Eg/ Page 18