GE is a diversified organization covering a myriad of market segments, including infrastructure, finance and media. From energy, water, transportation and health to access to money and information, GE serves customers in more than 100 countries and employs more than 300,000 people worldwide. The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the original index in 1896.
Industrial Solutions
GE Industrial Solutions, a division of GE Energy, is a global leading provider in power distribution, offering a wide range of services and products which include medium and low voltage power distribution equipment and components, motor & control systems and service products that are safe, reliable and offer high performance.
Honour
2010 World's Most Innovative Companies 2011 Worlds Most Admired Companies 2009 Worlds Most Respected Companies 2011 Best Global Brand
80
Contents
General Introduction
GE GE Industrial Solutions
Product Description
SecoGear Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02 Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 07 Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
A
World Class Quality
Manufactured, assembled and tested all in the same sophisticated facility, SecoVac is the product of state of the art manufacturing processes assured by ISO 9001:2008 and ISO 14001 certification. Precision tooled parts, computer aided design and advanced production techniques, as well as the protection of the 'E Coat' (cathodic electrocoating) paint process have resulted in a standard of excellence unmatched in the industry.
Universal Applications
SecoGear is designed, assembled and tested to meet or exceed applicable IEC, GB and DL standards. It is suitable for applications in all major industries including T&D, Oil & Gas, Automotive, Processing plants, Iron and Steel mills, Mining, Commercial buildings, etc. It provides protection for all types of applications: coble, overhead lines, motors, capacitors, transformers, busbar sections, etc.
Product Introduction
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 15 Control and Operation . . . . . . . . . . . . . . . . . . . . . . . . 17 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . 18 Operation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 19 Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 IEC Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Configurations
Typical Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Incoming/Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Busbar Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Riser with VT & CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 VT Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Incoming with Measuring (VT) . . . . . . . . . . . . . . . . . 28 Incoming with ES & VT . . . . . . . . . . . . . . . . . . . . . . . . 29 Incoming with ES & Fix VT. . . . . . . . . . . . . . . . . . . . . 30 Riser with ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 CPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
eco
Environment Consciousness
Selecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used for SecoVac series MV embedded pole vacuum circuit breaker instead of SF6 gas.
Switchgear Compartment
Vacuum Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . 45 Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Voltage Transformer Truck. . . . . . . . . . . . . . . . . . . . 50 Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Operation Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Installation Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Product Description
compartments
Equipped with the latest design embedded pole SecoVac
cable connection
Fully arc-proof unit up to 40kA for 1 second AFLR, 24/27kV
31.5kA/1s
Unit compartment
A B C D
standards
Tested to UBC zone 4 and GB intensity 9 for Seismic Front panel features easy operation and low maintenance Complete interlocking system to prevent incorrect operation
Circuit breaker compartment Busbar compartment Cable compartment Low voltage compartment
and to improve safety Innovative in its design, GE' s SecoGear is compact Air insulated switchgear and leads the industry in safety, reliability, performance and sustainability. Fully IEC certified at the KEMA and IPH test labs to IEC 62771-100 and 62771-200. SecoGear Switchgear is suited to provide control and protection for cables, transformers, capacitors and motors used across many industries. SecoGear excels anywhere that medium voltage power has to be switched, controlled and protected.
02
03
Product Description
Shock wave
10.000 Zone4 [SRS] Minimum (1.0,3.63974E-001) Maximum (2.454353,2.5735E+000)
Mechanical operations
1.0000
The mechanical endurance tests on all of the apparatus. General experience in the electro-technical sector shows that mechanical faults are one of the most common causes of a fault in an installation. The circuit breaker is tested by carrying out a high number of operations - higher than those which are normally carried out by installations in the field. Furthermore, the switchgear components are part of a quality control program and samples are regularly taken from the production lines and subjected to total mechanical life tests to verify that the quality is identical to that of the components subjected to the type tests.
0.1000 1.0000 10.000 Hz 100.00
Product Description
200 standards. It is fully isolated by earthed metal partitions for all the major compartments. It is equipped with GE' s very latest series of IEC vacuum circuit breakers type SecoVac, which are fully third party type tested in accordance with IEC 62771-100. Using GEs state of the art technology, and manufactured in accordance with the highest quality standards; our engineers have integrated core technologies. These technologies such as circuit breaker and mechanism design, vacuum arc control technology, insulation technology and electrical field control and analysis combine to build a highly reliable and compact system. SecoGear benefits from GE' s best practices incorporated in our current medium voltage. The typical rated voltage of SecoGear is 3.3/7.2/12/13.8/15/17.5/24/27kV and rated current ranges for SecoGear up to 17.5 is from 630A to 4000A(4000A is force cooled), for SecoGear 24/27kV the rated current is up to 2500A. All SecoGear with a switching device is equipped with SecoVac vacuum circuit breaker with corresponding specifications.
IP degree
The IP protection degree is the resistance offered by SecoGear against penetration of solid objects and liquids. This degree of resistance is indicated by the prefix IP followed by two characters (IP 4X is for the enclosure and IP 2X for the partitions.). The first number identifies the degree of protection against the entrance of solid objects, the second one is related to liquids.
Seismic rating
Up to Uniform Building Code (UBC) 1997 Zone 4
04
05
Product Description
Solutions
Rack in/out draw out mechanism
SecoGear has a draw out mechanism that is designed to avoid misalignment during racking, therefore overheating of the primary disconnect is totally prevented. The
draw out mechanism is bolted to the enclosure frame with a double bended support.
maintenance
An advanced vacuum interrupter contact design prevents hot spots, creates less heat and minimizes
Product Description
Dedicated engineering
range of applications
With the use of GE Multilin devices,
- Vacuum switching technology - Air insulation - Recycling or re-use of all materials possible - No special decommissioning procedures necessary
Smart distribution
Intuitive industrial and utility protective relays for feeders, motors and transformers
are provided: - Motorized draw out mechanism for remote connect and test position - Remote opening and closing the switchgear device - Motorized line side earth switch
reliability
Flexible communications with multiple
06
Product Description
manufacturer
Solutions
Applications
Applications
Product Description
Industry
Oil and Gas Mining Marine Pulp and Paper Cement Textiles Chemicals Automotive Petrochemical Data Center Metallurgy
Transport
Airports Ports Railways Underground transport
Services
Supermarkets Shopping malls Hospitals Large infrastructure and civil works
08
09
Product Description
Safety
Internal Arc Containment
When developing modern medium voltage switchgear, personnel safety must take priority. This is why the SecoGear switchgear has been designed and tested to withstand an internal arc due to a short-circuit current of the same current level as the maximum shorttime withstand level. The tests show that the metal housing of SecoGear switchgear provides an enhanced degree of protection for personnel near the switchgear in the case of an internal arcing fault. SecoGear up to 17.5kV passes the 40kA/1s
P13
Interlock
IAC test. SecoGear up to 27kV passes the 31.5kA/1s.
All high voltage primary compartment
GE safety interlock systems guarantee the highest level of personnel safety preventing operator errors from occurring. SecoGear is designed with a number of interlocking systems to prevent misoperation:
The circuit breaker can only be moved
are provided with pressure relief flaps located on the topside of the switchgear
Any overpressure inside the
P13
Product Description
when the circuit breaker is in the connect position and in the traveling position between test and connect
SCALE 1,000
from connect position, the metal shutters will close automatically preventing access to live connections
Key Condition Key will be free when the truck in the disconnect position Key will be trapped when the truck in the rack-in position Key will be free when the earthing switch is open Key will be trapped when the earthing switch in closed position Key will be free when the earthing switch closed Key will be trapped when the earthing switch in open position
Functional truck racking-in lock Key-lock for Earthing switch Earthing switch closing lock Earthing switch opening lock
SCALE 1,000
SCALE
1,000
Interlock
1152 650 650 1000 1200 800 900 C View 1152 2720 546 3100 800 500 800 2180
2200
B C
1500
SCALE 1,000
Interlock
10
11
Product Description
Safety
Environment
Increasing global legislation concerning the use of green house gases such as SF6 gas and their related disposal costs, makes vacuum technology with its reliability, low maintenance, and low environmental impact the choice for now and the future. As the world strives to reduce the amount of SF6 gas used in all applications there is a responsibility on the users of electrical switchgear to find, where appropriate, alternatives to SF6 gas as an insulation and switching medium. Air and solid
Environmentally friendly
From the very beginning GE made a fundamental choice not to use SF6 as a switching and insulation medium for primary medium voltage equipment. SF6 is on the list of greenhouse gasses in the Kyoto protocol and is the most potent of the six main greenhouse gasses, with a Global Warming Potential (GWP) of 23,000. Many other medium voltage switchgear systems use SF6 gas as the insulating medium. Leakage of SF6 gas from switchgear contributes significantly to the threat of the greenhouse effect and associated climate change. They also require additional safety measures and special handling requirements at the end of life.
Product Description
technologies are a reliable, safe and economic alternative for use in electrical systems below 36kV and therefore should be used instead of SF6 gas insulated systems. Modern medium voltage switchgear employing vacuum technology together with air and epoxy resin insulation provides:
Minimum number of parts and components No special requirements for the end-of-life disposal of the
switchgear
Environmentally-friendly materials used in the design No use of SF6-gas for switching and insulation No risk of damaging leaks of SF6 gas or of toxic byproducts Energy-efficient production and assembly, with
its materials to ensure that they have the lowest possible impact on the environment. It is essential that they are equally safe for people not just during use, but at the end of service life too. Within SecoGear and the SecoVac vacuum circuit breaker, a combination of solid (cast-resin) and air is used as insulation. The castresin technology, in combination with electrical field calculations, provides a very
compact, environmentally friendly design for the circuit breaker and the switchgear. Because the switching medium - vacuum is used, SecoGear can be completely recycled at the end of its life without any issues relating to safety procedures, special handling or safe disposal.
13
Product Description
Environment
Product Introduction
1
The compartment is isolated with earthed metal partitions and has ample space for control and protection devices. A fully isolated metal wire way is mounted at the top of each switchgear panel; this connects together to form a continuous low voltage wire way that runs along the entire length of the switchgear.
1
Product Introduction
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 15 Control and Operation . . . . . . . . . . . . . . . . . . . . . . . . 17 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . 18 Operation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 2 2
Busbar compartment
Busbars are totally enclosed in their own earthed metal compartment which vents into the arc the busbars for up to 27kV SecoGear are type tested for ratings up to 4000A, 40kA for 3 seconds. for 24/27kV SecoGear, the busbars are type tested for rating up to 2500A, 31.5kA for 3 seconds. Epoxy moldings separate switchgear sections. chamber. Fully insulated along their entire length,
4
Product Introduction
IEC Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6 3 5
Fully isolated by earthed metal partitions, with its own pressure relief channel into the arc chamber. The compartment provides all the safety
8 7 9
interlocking mechanisms required for safe and reliable operation of the vacuum circuit breaker. Manual operation buttons allow for full operation of the vacuum circuit breaker from the front of the switchgear with the door fully closed. The circuit breaker is mechanically interlocked with the compartment door so that the door cannot be opened until the circuit breaker is switched off and racked out into the Test position.
14
15
Product Introduction
Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Automatic shutters
When the circuit breaker is in Test or Disconnect position, the shutters automatically close to isolate the fixed contact from any live parts. Shutters can be individually and automatically operated for bus side and feeder side connection in close position. 2
Earth switch
Cable compartment
3
The earthing switch can be operated from the front of the switchgear. It is mechanically interlocked with the circuit breaker truck so that the earthing switch can only be operated when the circuit breaker is open in Test/Disconnect position as well. The switch is also mechanically interlocked with the cable compartment for additional safety.
Cable supports are provided to secure cables. Cable clamps are applied for fix the cables. And the metal floor cover is removable.
Product Introduction
Current transformers
installed in the bottom of cable compartment. The earth bar system has been fault tested and runs vertically and horizontally with each panel section and is connected to the earth switch. 7
10
Current transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes.
Surge arrester
Voltage transformers
transient operating or lightning over-voltage. It is connected between primary conductor and ground for protecting protective load from damage effect. When the operating or lightning over-voltage occurs, surge arrester immediately limits over-voltage amplitude and protects the insulation of device. 9 8
Voltage transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes.
16
17
Product Introduction
Earth bar
Technical Characteristics
Rated voltage Rated power frequency (1min) Rated lightning impulse (1.2/50s) Rated frequency Rated current (main busbar) Rated short time withstand (3sec) Rated peak withstand current 1 IP level for weather protection kV kV kV Hz A kA kA Enclosure Between compartment 7.2 20 60 12 28 75 15 36 95 17.5 38 95 24 50 125 27 65 125
Operating Conditions
Normal operating conditions
The switchgear is fundamentally designed for the normal service conditions for indoor switchgear to IEC Publication 62271-1. The following limit values, among others, apply.
Ambient temperature
Protection
IP4X for the enclosure IP2X between each compartment
Construction
Internal arc withstand (classification IAC): AFLR 3 compartments (classification LSC2B according to IEC 62271-200) All the metal surfaces in the panels are corrosion proof Panels are produced using hot dipped galvanized steel sheet
- Highest average value measured over 24 hours - Relative humidity 95% - Highest average value measured over 1 month - Relative humidity 90%
The maximum site altitude is 1000 m
Product Introduction
Connections
Front and/or rear access Cable entry from bottom or top
Busbar fully insulated for 7.2kV, 12kV, 13.8kV, 15kV, 17.5kV, 24kV, 27kV
18
19
Product Introduction
IP42 optional
Storage Conditions
In order to retain all of the functional units qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between 15C and + 40C. For storage: -30C.
IEC Standards
SecoGear complies with the standards metal enclosed switchgear and has been type tested in accordance with the IEC publications as given below. and specifications for factory assembled
Product Introduction
IEC 62271-100: 2008 High-voltage alternating current circuit breakers. IEC 62271-200: 2003 AC Metal enclosed switchgear and control gear for rated voltages IEC 62271-1: 2007 IEC 60529:1989 above 1kV and up to 52kV. The common specification for high voltage switchgear and control gear Standards. Degrees of protection as provided by enclosures (IP Code). IEC 62271-102: 2001 High-voltage alternating current disconnector and Earth Switches.
Configurations
Typical Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Incoming/Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Busbar Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Riser with VT & CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 VT Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Incoming with Measuring (VT) . . . . . . . . . . . . . . . . . 28 Incoming with ES & VT . . . . . . . . . . . . . . . . . . . . . . . . 29 Incoming with ES & Fix VT. . . . . . . . . . . . . . . . . . . . . 30 Riser with ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 CPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
20
21
Configurations
Typical Panels
The SecoGear series comprises 10 basic configuration applications. The table below can be used to link requirements to functional units and gives basic information on the general composition of each unit.
Incoming/Feeder
P26
Riser Riser with VT & CT
Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)
12
15 28 75 36 95 1000 2200 1900 1400 650 2200 1900 1400 1000 2200 1900 1400
24 50 125 1000 2200 1900 1400 650 2400 1800 1000 2400 1800 65 125 27
3.3kV-17.5kV
Incoming/Feeder Incoming with measuring (VT) Busbar Tie
Configurations
31.5 40 25
Short time withstand current (kA/3s) VT Panel Incoming with measuring (VT) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling Top Access Bottom Access
31.5 40
615
615
615
615
1100
1100
24kV-27kV
Incoming with ES & VT (24kV) Incoming with ES & VT (27kV) Riser with ES CPT
17
22
23
Configurations
22
04
Busbar Tie
Riser
630 1250 1600 650 2200 1400 20 60 1000 2200 1400 650 2200 1400 7.2 28 75 1000 2200 1400 650 2200 1400 1000 2200 1400 12 36 95 650 2200 1400 15 38 95 1000 2200 1400 650 2400 1800 1000 2400 1800 17.5 50 125 650 2400 1800 1000 2400 1800 Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling Short time withstand current (kA/3s) Breaking capacity (kA) 24 65 125 Rated current (A) 27
P28
P29
12
24 50 125 1000 2200 1400 650 2400 1800 1000 2400 1800 65 125 27
Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)
Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)
Configurations
31.5 40 25
Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling
31.5 40
615
615
615
615
1100
1100
615
615
615
615
1100
1100
01
C
SCALE 1,000
C
SCALE 1,000
24
25
Configurations
VT Panel
Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV) Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) 25 31.5 40 7.2 20 60 800 2200 1400 615 12 28 75 800 2200 1400 615 800 2200 1400 615 36 95 15 17.5 38 95 800 2200 1400 615 800 2400 1800 1100 800 2400 1800 1100 24 50 125 27 65 125
Configurations
JSZV17-15R
15
JSZV17-15R
15
01
26
76
95.5
76
95.5
27
Configurations
P29
7.2 12 20 60 28 75 1000 2200 1400 650 2200 1400 1000 2200 1400 650 2200 1400 1000 2200 1400 36 95 650 2200 1400 15 38 95 1000 2200 1400 650 2400 1800 1000 2400 1800 17.5 50 125 650 2400 1800 1000 2400 1800 24 65 125 27
P32
Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)
Configurations
31.5 40 25
Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling
31.5 40
615
615
615
615
1100
1100
10
SCALE
1,000
28
29
Configurations
P30
P31
Riser with ES
Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV) 630 1250 Rated current (A) 1600 2000 2500 Breaking capacity (kA) Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling 25 31.5 25 31.5 650 2400 1800 1100 65 125 27
Configurations
Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling
30
31
Configurations
CPT
Configurations scheme
17.5kV
630 1250 1600 650 2400 1800 1100 65 125 1000 2400 1800 Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm) Scheme Number 630~4000 1 2 630~4000 1 2 630~4000 1 3 630~4000 1 3 630~4000 1 2 2 2 630~4000 1 3 3 3 Primary Scheme Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm) Scheme Number 630~4000 1 3 630~4000 1 3 630~4000 1 3 630~4000 1 3 630~4000 1 3 630~4000 1 3 27 Primary Scheme
P32
Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)
Scheme Number
P33
01
02
03
04
05
06
Configurations
31.5 40 25
I/F 650/1000 10
I/F 650/1000 11
09
12
Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling
31.5 40
B 650/1000 13
B 650/1000 14
B 650/1000 15
B 650/1000 16
I/F 650/1000 17
I/F 650/1000 18
Primary Scheme
Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm)
630~4000 1 2 3 3
630~4000
630~4000
630~4000
630~4000
2 3
2 3 3 VT 650/1000
3 3
3 3 3 VT 650/1000
I/F 650/1000
VT 650/1000
VT 650/1000
32
33
Configurations
1 3 I/F 650/1000
1 3 I/F 650/1000
Configurations scheme
17.5kV
Scheme Number
P34
19
20
21
22
23
24
Primary Scheme
Configurations
Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm) Scheme Number
630~4000
630~4000
630~4000 2 2 2
630~4000 2 2 2
630~4000 3 3 3
630~4000 3 3 3
R 650/1000 25
R 650/1000
M 650/1000
M 650/1000
M 650/1000
M 650/1000
Primary Scheme
Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm)
630~1250 2 3 3
M 800
27kV
Scheme Number 26 27 28 29
Primary Scheme
Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm)
34
1250~2500
1250~2500
2 3 1 R 800 M 1000
35
Features
Protection & control (for Multilin 350 Feeder Protection System)
Phase, neutral and ground TOC and IOC Undervoltage, overvoltage, frequency Neutral/ground directional Negative sequence overcurrent ANSI, IAC, IEC, flex curves
Easy-to-use
Drawout construction The Multilin 3 Series offers a complete drawout feature eliminating the need for rewiring after testing has been concluded. The withdrawable feature also eradicates the need to disconnect communication cables, e.g. fiber, copper, RJ45, etc and helps retain communication status even after a relay has been withdrawn from its case.
Multilin 3 Series
Intuitive industrial and utility protective relay systems for feeders, motors and transformers
Cable Thermal Model protection Breaker failure Cold load pick-up Four-shot auto reclose 8 digital inputs, 7 contact outputs Two setting groups
Overview
The Multilin 3 Series of protection relays are a highly functional, economical protection relays for feeders, motors and transformers. By providing an economical system for protection, control, monitoring and metering, and both local and remote user interfaces in one assembly, the Multilin 3 Series relays effectively eliminate the need for expensive discrete components. The Multilin 3 Series provides detailed diagnostic information allowing users to troubleshoot and minimize downtime. Detailed diagnostics is provided via the 256 1ms time stamped event recorder and the 192 cycle Oscillography report sampled at 32 samples per cycle. The robust Multilin 3 Series streamlines user work flow processes and simplifies engineering tasks such as configuration, wiring, testing, commissioning, and maintenance. This cost-effective relay also offers enhanced features such as diagnostics, preventative maintenance, device health reports and advance security features.
time stamping
Oscillography with 32 samples per
Key benefits
IRIG-B clock synchronization Application flexibility with the use of programmable logic Relay & Asset Health Diagnostics Security audit trail
elements
Large backlit display with 40 characters for easy viewing of
Advanced communications
Easy integration into new or existing infrastructure With several Ethernet and serial port options, and a variety of communication protocols, the Multilin 3 Series provides advanced and flexible communication selections enabling seamless integration into new or existing applications. The Multilin 3 Series supports various industry standard protocols such as, IEC 61850 & IEC 61850 GOOSE, Modbus RTU, Modbus TCP/IP, DNP3.0, IEC 60870-5-104 and IEC 60870-5-103.
Fiber ports
Multiple protocols - IEC 61850 & 61850
GOOSE, ModBus RTU, ModBus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 60870-5-103 EnerVista software
An industry-leading suite of software
Setup screen
Powerful Security Audit Trail tool to increase security and
Applications
Advanced protection, monitoring & control relays for feeders Distribution utility down stream breaker protection Medium voltage utility feeders with advanced control features
including, cold load pickup, auto reclose and multiple setting groups
diagnostics
36
37
Enhanced diagnostics
Preventative maintenance The Multilin 3 Series allows users to track relay exposure to extreme environmental conditions by monitoring and alarming at high temperatures. This data allows user to proactively schedule regular maintenance work and upgrade activities. All relays utilize EnerVista setup
TM
EnerVistaTM Launchpad
EnerVista Launchpad is a complete set of powerful device setup and configuration tools that is included at no extra charge with the SR Relays.
Set up the Multilin 3 Series Relays - and any
Security
Security audit trail The Multilin 3 Series monitors security and reliability of asset protection. The Multilin 3 Series protection devices offer complete traceability of any relay setting and command changes, allowing the user to quickly identify changes made to the relay.
other Multilin device - in minutes. Retrieve and view oscillography and event data at the click of a button
Build an instant archive on any of the
software for communication, monitoring and metering. Actual values, setpoints, status, trending, and waveform capture information may all be viewed via the software, and can be used for troubleshooting.
latest Multilin manuals, service advisories, application notes, specifications or firmware for your SR Relay
Automatic document and software version
updates via the internet and detailed e-mail notification of new releases
User Interface
SETPOINT GROUP 1, 2:
These indicators are continuously on if corresponding group provides settings for protection elements. TRIP: Indicator turns on when relay detects a trip condition. Operates the trip relay to open the breaker. ALARM: While relay detects an alarm condition, indicator flashes. PICKUP: Indicator lights steady when any protection feature pickup threshold exceeded.
Key benefits
plus programmable logic
Flexible and cost effective control for complex systems -
DISPLAY: LEDs:
Use IEC compatible programmable logic to customize the functionality of your protection & control system to address unique, site specific applications
Human machine interface (HMI) - Standard backlit LCD display
Modbus RTU, DNP 3.0 Level 2, IEC 60870-5-104, IEC 61850, IEC 870-5-103
Minimize communication down time - Reliable redundant
KEYPAD:
Ethernet Communication ports with 10/100BaseTX, 100BaseFX with ST connectors and optional double 100BaseFX, with ST connectors
Complete asset monitoring - Full metering including demand
Ten button keypad for access to device interrogation and change of settings.
with 4 x 20, optional 16 x 40 (240 x 128 pixels) graphical LCD, programmable buttons and directional keys for selecting setting menus and submenus
Minimize replacement time - Modular with card draw-out
FRONT PORT:
Protection Features
BUS BUS VT 52 79 TRIP 3 CLOSE 1 MONITORING 50P 2 50N 2 CLP 1 50G 2 50G/ 51G 51G 1 51P 1 51N 1 50BF 79 50_2 1 49 1 METERING 27P 1 59P 1 27X 1 59X 1 59_2 1 59N 1 81U 2 81O 2
& energy
Follow technology evolution - Flash memory for product field
Function
Phase Undervoltage Auxiliary Undervoltage Thermal Model Phase Instantaneous Overcurrent Neutral Instantaneous Overcurrent Ground/Sensitive Ground Instantaneous Overcurrent Breaker Failure Negative Sequence Overcurrent Phase Timed Overcurrent Ground Timed Overcurrent Neutral Timed Overcurrent Phase Overvoltage Auxiliary Overvoltage Neutral Overvoltage Negative Sequence Overvoltage Ground Directional Overcurrent Neutral Directional Overcurrent Autoreclose Underfrequency Overfrequency Cold Load Pickup
construction
Reduce troubleshooting time and maintenance costs - IRIG-B
upgrade
Applications
F650: Management and primary protection of distribution G650: Distributed generation management device G650: Reliable Distributed Generation interconnection
protection system
W650: Wind turbine protection, control and monitoring W650: Distributed generation grid interconnection device
39
350 RELAY
LOAD
lines
G650: Packaged generator mains failure detection
38
Features
Protection and control
Up to 32 Programmable digital inputs Up to 16 digital outputs Trip Circuit Supervision Redundant power supply option Configurable PLC logic according to IEC 61131-3 Fully configurable graphic display HMI interface Alarms panel
Communications
Multilin 650 units incorporate up to three ports that operate independently. Redundant ports are available for high reliability applications: Available protocols for rear port 1 and 2 are ModBus RTU, IEC 103 and serial DNP 3.0. The third port is located in a removable communications card. This plug-andplay card can be easily changed in the future as new standards arrive to the market, thus providing a migration path to the customer. The protocol available for the third port is DNP 3.0 over TCP/IP, UDP/IP, ModBus TCP/IP and IEC 60870-5-104.
memory. Therefore, there is no need for internal battery monitoring or maintenance. Trip circuit monitoring Multilin 650 units offer as an option two complete supervision circuits for breaker trip and closing coils and circuits. These supervision inputs monitor both the battery voltage level and the continuity of the trip and/or closing circuits, applying current through those circuits and checking that it flows properly. In order to apply this feature it is necessary to choose I/O board 1 option 2.
Overview
The Multilin 650 family has been designed as a comprehensive protection, control, metering and monitoring package. The microprocessor based architecture is a complete solution for different applications that complies with the most relevant international standards. All the elements required for each application have been integrated into a single package for a cost-effective, reliable and simple utilization. The low number of components, thanks to the use of stateof-the-art but mature technology, deliver a very high reliability. Hardware inputs and outputs have been designed in a modular way that allow easy migration from simple to more complex applications. The control functions include a fullscheme virtual PLC with an optional graphical display. The combination of both elements provide total control for a bay. This means real-time monitoring of breakers and selector switches, open and close commands supervised by the programmable interlockings and metering
40
Metering
screens. The metering capability allows 0.5% accuracy for current and 1% from 10V to 208V for voltage in metering range. Monitoring functions include a 479 event recorder, and a programmable oscillography recorder. The Multilin 650s communications capability and option make the product very unique. These units include a maximum of three independent communication ports: COM1, COM2 and COM3, with many physical choices through the use of two removable plugand-play boards. The brain of the Multilin 650 units includes a powerful built-in virtual PLC. This PLC can be programmed according to the IEC 61131-3 language by functional block diagrams. 650 units come with 8 to 32 digital inputs and with 8 to 16 outputs depending on options. All digital inputs may be filtered with a separate debounce time to tailor customer requirements. Recording functions The recording functions within the Multilin 650 include:
Event recorder capable of storing 479
User Interface
Graphic 16 x 40 or text 4 x 20 LCD display Fluorescent backlight to improve visibility Multicolor programmable LEDs with label panel Local/Remote/Off pushbutton with LEDs Key control for easy navigation Ergonomic programmable keys
Wb, Wc, W
Reactive power (per phase and total) :
Function
Synchrocheck Bus/Line Undervoltage Sensitive Directional Power Forward Power Wattmetric zero-sequence directional Negative Sequence Time Overcurrent Negative Sequence Voltage Blocked Rotor Thermal Image - overload protection Breaker Failure Phase Instantaneous Overcurrent (High/Low) Neutral Instantaneous Overcurrent Ground Instantaneous Overcurrent Sensitive Ground Instantaneous Overcurrent Isolated Ground Instantaneous Overcurrent Neutral Time Overcurrent Ground Time Overcurrent Sensitive Ground Time Overcurrent Voltage Restraint Phase Time Overcurrent Bus/Line Overvoltage Neutral Overvoltage - High/Low Phase Directional Overcurrent Neutral Directional Overcurrent Ground Directional Overcurrent Sensitive Ground Directional Overcurrent Autorecloser Under/Over Frequency Broken Conductor Detection Load Encroachment Frequency Rate of Change VT Fuse Failure Detection
52 79
1
CLOSE Monitoring
49
3
TRIP
BROKEN CONDUCTOR
27X
3
59X
50BF
1
50PH 50PL
3 3
46
3
48
3
32FP
3
32
3
32N
3
50N
3
51N
3
67N
3
25
1
1 1
50G
3
51G
3
67G
3
50SG 51SG
3 3
50IG
3
67SG
3
METERING
3V_0
can be stored in memory. The capacity of each record will depend on the type of oscillo selected (1 Mbyte/Max. No. Osc)
47
3
27
3
59
3
VTFF
1
81U
3
81O
3
81R
3
59NH
3
25 27/27X 32 32FP 32N 46 47 48 49 50 BF 50PH/PL 50N 50G 50SG 50IG 51N 51G 51SG 51PH/V 51PL/V 59/59X 59NH/NL 67P 67N 67G 67SG 79 81 U/O N/A 81R VTFF
59NL
3
EN F650 BLOCK F.CDR
41
Security auditing, device and asset health reporting and fault data retrieval
Viewpoint Maintenance provides security auditing, device and asset health reporting as well as easily accessible fault data. With a comprehensive security audit report, changes to the device settings, including the MAC address, are recorded enabling compliance with NERC / Critical Infrastructure Protection Standards. Device and Asset status reports detail current and historical health for both the intelligent protection device and the asset being protected.
42
43
Applications
Serving global 50 Hz and 60 Hz Segments of the electrical industry: industrial, commercial,
protection
User friendly operation with easy access and minimal
inspection
Compact and cost effective Flexible with a full line of accessories and OEM Solution
Spare Parts
Switchgear Compartment
Vacuum Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . 45 Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Voltage Transformer Truck. . . . . . . . . . . . . . . . . . . . 50 Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Operation Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
44
45
Spare Parts
Closing Circuit
10
Opening Circuit
30 6 3 5 7 9 23 27 28 29 8
V2
V4
V3
V1
K0 (13) (14)
M
(51) (52) (53) S5 (5) (3)
D~
(54) S5 K0 (2)
S5
(21) (22) S3
(13) (14) S3
(21) (22) S1
43 44
S8
43 44
S9
36
34
35
20
53
54
31
32
16 13 15 17 19 33 37 38
39 18
40
11
47
57
55
13 14 S9
33 34 S9
23 24 S9
53 54 S9
13 14 S8
33 34 S8
23 24 S8
53 54 S8
13 14 S5
81 82 S5
21 22 51 50
12
14
48
49 58
56
Coil Characteristics
S9: Limit switch (working position) Rated voltage Rated current Rated voltage Rated current Rated voltage Rated current (V) (A) (V) (A) (V) (A) DC36 DC110 11.5 2.9 2.9 DC48 DC220 AC220 8.4 1.5 1.5 DC60 11.5 S8: Limit switch (testing position) S5: Auxiliary switch S1~S3: Energy storing travel switch Note: 1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state. 2. The polarity in dashed frame should be connected to common DC voltage terminal. 3. Rectifier will be removed if DC is applied. Energy staring period under rated operation voltage (s) <10s <10s <10s <10s <10s Input power (W) 150 150 150 150 150 CC: Closing coil TC: Trip coil V1~V4: Rectitier KO: Anti-pumping relay (optional) BC: Electromagnet for locking (optional) ZC: Electomagnet for locking truck (optional)
Spare Parts
AC110
Motor Characteristics
Rated voltage (V) DC125 DC110 DC220 AC110 AC220 Normal operation voltage scope 85%~110% 85%~110% 85%~110% 85%~110% 85%~110%
46
47
Spare Parts
Component
Breaker Interlock Circuit
52
Closing Circuit
10
Opening Circuit
30 6 3 5 7 9 23 27 28 29 8
V2
V4
V3
V1
K0 (13) (14)
M
(51) (52) (53) S5 (5) (3)
D~
(54) S5 K0 (2)
S5
(21) (22) S3
(13) (14) S3
(21) (22) S1
43 44
S8
43 44
S9
Current Transformer
31 32 16 13 15 17 19 33 37 38 39 18 40
Voltage Transformer
Voltage transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes. 17.5kV VT type: JDZ17-15A 27kV VT type: JDZ11-25 JDZX11-25E Fuse type: JDZX15-25R
36
34
35
20
53
54
Current transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture.
11
47
57
55
It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes. Current 1250A the CT type is LZZB-17
13 14 S9
33 34 S9
23 24 S9
53 54 S9
13 14 S8
33 34 S8
23 24 S8
53 54 S8
21 22
43 S5 44 S5
13 14 S5
81 82 S5
Recommended CT
21 22 51 50 12 14 48 49 58 56
Primary Current
Type
Ratio
500/5A 500/1A
Accuracy Class
0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s
Protection Class
5P or 10P 5P or 10P 5P or 10P
S9: Limit switch (working position) S8: Limit switch (testing position) S5: Auxiliary switch
KO: Anti-pumping relay (optional) BC: Electromagnet for locking (optional) ZC: Electomagnet for locking truck (optional)
50A 25kA/3s LZZB-17 500
S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor S1~S3: Energy storing travel switch
500-250/5A 500-250/1A 1000/5A 1000/1A 1000A 25kA/3s LZZB-17 1000 1000-500/5A 1000-500/1A 3000/5A 3000/1A 3000A 25kA/3s LZZB-17 3000 3000-1500/5A 3000-1500/1A
Spare Parts
Note: 1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state. 2. The polarity in dashed frame should be connected to common DC voltage terminal. 3. Rectifier will be removed if DC is applied.
48
49
Spare Parts
5P or 10P
Cable Connection
The cable compartment contains current transformers, voltage transformers (fixed), withdrawable, and earthing switch, depending on the individual operating requirements. The cable compartment is constructed for installation of three current transformers. When all the three current transformers are not required, dummies can be installed in their place to maintain the same installation and connection procedures. The fixed voltage transformers (optional) are connected on the primary side with busbar and fitted with HRC fuses. The earthing switch can be operated by manual, with position indicated by mechanical indicator on the driveshaft and the auxiliary switch. Three surge arrestor (optional) can be mounted in the space available.
7.2/12/15/17.5 Rated voltage (kV) Panel width (mm) 650 800 1000 Max. number of parallel cables per Phase 6 6 6 630 35-54 27-62 Max. cross section of cables (mm2) Range of cable clamp (mm) Range of reducer ring (mm)
Earthing Switch
Operation Tool
Gear door locks key Rack handle for truck Earthing switch handle
Spare Parts
125
50
51
Spare Parts
65
Installation Guide
In order to obtain an optimum installation sequence and ensure high quality standards, site installation of the switchgear should only be carried out by specially trained personnel, or supervised and monitored by qualified personnel, or by personnel supervised and monitored by responsible persons. On commencement of installation on site, the switch-room must be fundamentally finished, provided with lighting and the electricity supply, lockable, dry and with facilities for ventilation, It is also required that the basic frame and indoor ground of substation should be checked and accepted before the construction, It must be ensure that the ceiling height is sufficient for the opening travel of the pressure relief plates and clearance for exhaust. Tolerances for laying the floor frame are: Evenness tolerance: 1mm within a measuring length of 1m, Straightness tolerance: 1mm per 1m, but not more than 3mm over entire length of frame.
SecoGear P/V
Installation guide
2500
1500
800
SecoGear P/V
Installation Guide
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
52
800
53
Installation guide
1500
400
250
800
1400
760
1400
40
150
1360
Basic Frame
280 210
250 30
1400
760
280 210
1360
Basic Frame
1400
40
150
Basic Frame 1800 Control Cable Duct 750 250 800/1000 800 Power Cable Duct 70 250 30 150 1700
Installation guide
280 210
1360
Basic Frame
54
250 30
55
Installation guide
1400
760
1400
40
2200
800 70
1500 1400 30
614x28
Top Curface of basic frame 3~5mm above ground
Basic Frame 150 280 380 0.0m -0.25m Strap of control cable duct Figured steel plate (t=5mm)
200
70
Control Cable Duct 250*250 800 Power Cable Duct 800*1000 300 760
Width A B C
27kV 27kV
1800 1700
2400
800 70
1900 1800 30
4-15x20
Basic Frame
140
250
130
+5.0m
Installation guide
70
290
800
Width A B C
56
57
Installation guide
300
54
GE Energy
Greater China
Shanghai
4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech Park Shanghai, China 201203 T : +86 21 3877 7888 F : +86 21 3877 7600
Taiwan
6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480 T : +886 2 2183 7000 F : +886 2 2516 6829
Philippines
8F Net Cube Building, 30th Street Corner 3rd Avenue, Crescent West Park Global City Taguig 1634 T : +63 2 877 7000 F : +63 2 846 0629
Indonesia
BRI II Tower, 27th floor Jl. Jend. Sudirman No. 44-46 Jakarta 10210 T: +62 21 573 0430 F: +62 21 574 7089
Thailand
25th floor, CRC Tower, All Seasons Place 87/2 Wireless Road, Lumpini Pathumwan, Bangkok 10330 T : +66 2 648 0202 F : +66 2 648 0200
Vietnam
Saigon Centre, Unit 1, Floor 7 Le Loi Boulevard, District 1 HoChiMinh City T : +84 8 3914 6700 F : +84 8 3827 8229
Singapore
240 Tanjong Pagar Road #06-00 GE Tower Singapore 088540 T : +65 6220 7022 F : +65 6326 3015
ANZ
Australia
125-127 Long Street Smithfield, Sydney, NSW 2164 T : +61 2 8788 6911 F : +61 2 8788 7224
New Zealand
Level 1, 8 Tangihua Street Auckland, North Island T : +64 9 353 6706 F : +64 9 353 6707
North Asia
Japan
11F, Akasaka Park Bldg.,5-2-20 Akasaka, Minato-ku Tokyo 107-6111 T : +81 3 3588 5288 F : +81 3 3585 3010
Korea
3rd Floor, GE Tower, 71-3, Cheongdam-dong, Gangnam-gu Seoul, Korea 135-100 T : +82 2 6201 4501 F : +82 2 6201 4344