3.3kV-27kV Air Insulated Switchgear


Leading the future of electrification

3.3kV - 27kV Air Insulated Switchgear


Leading the future of electrification

GE
GE is a diversified organization covering a myriad of market segments, including infrastructure, finance and media. From energy, water, transportation and health to access to money and information, GE serves customers in more than 100 countries and employs more than 300,000 people worldwide. The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston Electric Company created the General Electric Company. GE is the only company listed in the Dow Jones Industrial Index today that was also included in the original index in 1896.

Industrial Solutions
GE Industrial Solutions, a division of GE Energy, is a global leading provider in power distribution, offering a wide range of services and products which include medium and low voltage power distribution equipment and components, motor & control systems and service products that are safe, reliable and offer high performance.

Honour
2010 World's Most Innovative Companies 2011 Worlds Most Admired Companies 2009 Worlds Most Respected Companies 2011 Best Global Brand

2008 Worlds Most Respected Companies

2007 Worlds Best R&D Companies

80

More Than 80 Years of Interrupter Experience


GE pioneered experimental vacuum interrupters in the 1920s. Refined it and introduced the world's first 15kV Vacuum circuit breaker in the 1960s. To date, this interrupter design has been the world leader in vacuum technology and has accumulated over 45 years of reliable field service.

Contents
General Introduction
GE GE Industrial Solutions

Product Description
SecoGear Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02 Solutions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 07 Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 08 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

A
World Class Quality
Manufactured, assembled and tested all in the same sophisticated facility, SecoVac is the product of state of the art manufacturing processes assured by ISO 9001:2008 and ISO 14001 certification. Precision tooled parts, computer aided design and advanced production techniques, as well as the protection of the 'E Coat' (cathodic electrocoating) paint process have resulted in a standard of excellence unmatched in the industry.

Universal Applications
SecoGear is designed, assembled and tested to meet or exceed applicable IEC, GB and DL standards. It is suitable for applications in all major industries including T&D, Oil & Gas, Automotive, Processing plants, Iron and Steel mills, Mining, Commercial buildings, etc. It provides protection for all types of applications: coble, overhead lines, motors, capacitors, transformers, busbar sections, etc.

Product Introduction
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 15 Control and Operation . . . . . . . . . . . . . . . . . . . . . . . . 17 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . 18 Operation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 19 Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 IEC Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Configurations
Typical Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Incoming/Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Busbar Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Riser with VT & CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 VT Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Incoming with Measuring (VT) . . . . . . . . . . . . . . . . . 28 Incoming with ES & VT . . . . . . . . . . . . . . . . . . . . . . . . 29 Incoming with ES & Fix VT. . . . . . . . . . . . . . . . . . . . . 30 Riser with ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 CPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Measurement, Protection and Control

eco

Environment Consciousness
Selecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. With commitment to environment protection, the solid insulation of epoxy resin is used for SecoVac series MV embedded pole vacuum circuit breaker instead of SF6 gas.

Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Switchgear Compartment
Vacuum Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . 45 Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Voltage Transformer Truck. . . . . . . . . . . . . . . . . . . . 50 Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Operation Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Installation Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

MV Switchgear with better reliability and safety.


For over 80 years, General Electric has provided medium voltage equipment combining advanced technology with engineering excellence. The SecoGear range provides the highest safety and reliability standards with a cost effective solution in the public distribution, industry and building sectors.

Product Description

SecoGear Series 3.3/7.2/12/13.8/15/17.5/24/27kV Switchgear


Indoor, metal-enclosed switchgear designed for the MV
D B

section of HV/MV and MV/MV substation


Air insulated switchgear with a compact design Safe and Reliable switchgear for universal indoor applications Designed with full metallic segregation of its internal

compartments
Equipped with the latest design embedded pole SecoVac

vacuum circuit breaker


Cable compartments with ample space for ease of power
C

cable connection
Fully arc-proof unit up to 40kA for 1 second AFLR, 24/27kV

31.5kA/1s

Unit compartment
A B C D

Tested in accordance with the IEC and GB international

standards
Tested to UBC zone 4 and GB intensity 9 for Seismic Front panel features easy operation and low maintenance Complete interlocking system to prevent incorrect operation

Circuit breaker compartment Busbar compartment Cable compartment Low voltage compartment

and to improve safety Innovative in its design, GE' s SecoGear is compact Air insulated switchgear and leads the industry in safety, reliability, performance and sustainability. Fully IEC certified at the KEMA and IPH test labs to IEC 62771-100 and 62771-200. SecoGear Switchgear is suited to provide control and protection for cables, transformers, capacitors and motors used across many industries. SecoGear excels anywhere that medium voltage power has to be switched, controlled and protected.

02

03

Product Description

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Shock wave
10.000 Zone4 [SRS] Minimum (1.0,3.63974E-001) Maximum (2.454353,2.5735E+000)

Built to highest quality standards


SecoGear is designed and fully third-

Circuit breaker making and breaking capacity


The SecoVac vacuum circuit breaker is subjected to the rated current and shortcircuit current breaking tests. Furthermore, it is also subjected to the opening and closing of capacitive and inductive loads, capacitor banks and/or cable lines.

Mechanical operations
1.0000

The mechanical endurance tests on all of the apparatus. General experience in the electro-technical sector shows that mechanical faults are one of the most common causes of a fault in an installation. The circuit breaker is tested by carrying out a high number of operations - higher than those which are normally carried out by installations in the field. Furthermore, the switchgear components are part of a quality control program and samples are regularly taken from the production lines and subjected to total mechanical life tests to verify that the quality is identical to that of the components subjected to the type tests.
0.1000 1.0000 10.000 Hz 100.00

Product Description

200 standards. It is fully isolated by earthed metal partitions for all the major compartments. It is equipped with GE' s very latest series of IEC vacuum circuit breakers type SecoVac, which are fully third party type tested in accordance with IEC 62771-100. Using GEs state of the art technology, and manufactured in accordance with the highest quality standards; our engineers have integrated core technologies. These technologies such as circuit breaker and mechanism design, vacuum arc control technology, insulation technology and electrical field control and analysis combine to build a highly reliable and compact system. SecoGear benefits from GE' s best practices incorporated in our current medium voltage. The typical rated voltage of SecoGear is 3.3/7.2/12/13.8/15/17.5/24/27kV and rated current ranges for SecoGear up to 17.5 is from 630A to 4000A(4000A is force cooled), for SecoGear 24/27kV the rated current is up to 2500A. All SecoGear with a switching device is equipped with SecoVac vacuum circuit breaker with corresponding specifications.

IP degree
The IP protection degree is the resistance offered by SecoGear against penetration of solid objects and liquids. This degree of resistance is indicated by the prefix IP followed by two characters (IP 4X is for the enclosure and IP 2X for the partitions.). The first number identifies the degree of protection against the entrance of solid objects, the second one is related to liquids.

Seismic rating
Up to Uniform Building Code (UBC) 1997 Zone 4

Fully type tested to latest IEC standards


The switchgear is type tested to the latest IEC 62271-200 and has the third party certification to prove internal arc containment classification of AFLR from 31.5kA for 1 second and up to 40kA for 1 second, 24/27kV 31.5kA/1s. This means protection against harm to personnel in the unlikely event of an internal arc in the cable compartment, vacuum circuit breaker compartment and the bus bar compartment in any direction: front, rear and sides of the switchgear. The earth switch of the SecoGear switchgear can be closed under shortcircuit up to 31.5kA. The earth switch is interlocked to avoid being operated on circuits which are still live. However, should the switch be accidentally closed then safety of the operating personnel is assured by arc fault containment.

Earthing switch making capacity

High ambient temperatures


The service conditions for the electrical apparatus in marine installations are generally more severe than those in normal land applications. Temperatures are a main factor and for this reason the shipping register regulations require the switchgear to be able to operate at higher ambient temperatures (40 C or higher).

04

05

Product Description

party type tested to the latest IEC 62271-

the operating parts ensure the reliability

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Solutions
Rack in/out draw out mechanism
SecoGear has a draw out mechanism that is designed to avoid misalignment during racking, therefore overheating of the primary disconnect is totally prevented. The

Minimal costs during service due to:


Robust maintenance-free design with minimum number of parts SecoVac vacuum circuit breaker has a long life of 10,000 operations without the need for active

draw out mechanism is bolted to the enclosure frame with a double bended support.

SecoGear offers you:


Flexible and adapted solution The experience of GE a global electrical

maintenance
An advanced vacuum interrupter contact design prevents hot spots, creates less heat and minimizes

GE's Multilin protection, monitoring and control relays


SecoGear provides the most efficient

Product Description

Low end of life disposal costs due to:

Dedicated engineering

range of applications
With the use of GE Multilin devices,

- Vacuum switching technology - Air insulation - Recycling or re-use of all materials possible - No special decommissioning procedures necessary

Smart distribution
Intuitive industrial and utility protective relays for feeders, motors and transformers

SecoGear can be easily integrated into a monitoring and control system

User interface friendly


Cable connection and user interfaces for operation on the same side of the unit Up to 6 cables per phase with standard compression lug for ease of cable connection Secondary cable entry points on both sides of the low voltage compartment top plate Secondary cable wiring runs over the length of the switchgear to help with inter-unit wiring Secondary cable terminals positioned at a good reachable height within the low voltage compartment Clear and simple, straightforward operation, panels combined with an active LED mimic diagram

Remote control solution


By special order request For remote control from a central

Key benefits of Multilin Protection Relays


Easy to use and cost effective Effortless draw-out construction Environmental monitoring system to

Low lifetime cost Low initial costs due to:


Compact footprint Cable access from front or rear Cable entry from either top or bottom Easy-access cable compartment for ease of cable connection Integrated arc chamber Back to wall configuration with front cable access

control room for intelligent switchgear systems


The following functions of SecoGear

alarm on destructive operating conditions


Easy to use interface and set up in one step Accelerated Life Cycle tested to ensure

are provided: - Motorized draw out mechanism for remote connect and test position - Remote opening and closing the switchgear device - Motorized line side earth switch

reliability under abnormal conditions


Advanced diagnostics to increase

reliability
Flexible communications with multiple

ports & protocols to allow seamless integration


Easy access to information via multiple

communication network options


Powerful Security Audit Trail
07

06

Product Description

electrode erosion to yield longer life

manufacturer

means to control and protect a wide

Solutions

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Applications

Utilities and power plants


Power generation stations Transformer stations Switching stations Main and auxiliary switchgear

Applications

Product Description

Industry
Oil and Gas Mining Marine Pulp and Paper Cement Textiles Chemicals Automotive Petrochemical Data Center Metallurgy

Transport
Airports Ports Railways Underground transport

Services
Supermarkets Shopping malls Hospitals Large infrastructure and civil works

08

09

Product Description

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Safety
Internal Arc Containment
When developing modern medium voltage switchgear, personnel safety must take priority. This is why the SecoGear switchgear has been designed and tested to withstand an internal arc due to a short-circuit current of the same current level as the maximum shorttime withstand level. The tests show that the metal housing of SecoGear switchgear provides an enhanced degree of protection for personnel near the switchgear in the case of an internal arcing fault. SecoGear up to 17.5kV passes the 40kA/1s

P13
Interlock
IAC test. SecoGear up to 27kV passes the 31.5kA/1s.
All high voltage primary compartment

GE safety interlock systems guarantee the highest level of personnel safety preventing operator errors from occurring. SecoGear is designed with a number of interlocking systems to prevent misoperation:
The circuit breaker can only be moved

The earthing switch can be opened

only when the cable compartment door is closed


The secondary plug can be inserted or

are provided with pressure relief flaps located on the topside of the switchgear
Any overpressure inside the

removed only when the circuit breaker is in the test position


The circuit breaker can only be closed

P13

Product Description

arcing will be released through the pressure relief flaps

versa when circuit breaker is opened


The earthing switch cannot be closed

located in the test or connect position


When the circuit breaker is removed

when the circuit breaker is in the connect position and in the traveling position between test and connect
SCALE 1,000

from connect position, the metal shutters will close automatically preventing access to live connections

The cable compartment door can be

Arc release channel

opened only when the earthing switch is closed


Description of the interlock system Key-lock for VCB rack in
A B C C

Arc Release System


Arc Release System is a perfect solution for E-house, marine and other limited places, which do not allow hot particles and gases into the room. And it also guarantees personnel safety. Each panel is fitted with two metal mesh boards on the top of it. The pressure generated by arc fault makes it open, allowing the gas and particles into the tunnel and evacuate to the outside of the room. Switchgear with standard arc release system can be used where the room height is greater than 3000mm. At the location of the exhaust exits from the switchroom, personal access should be limited.

Arc skirt (optional)


The switchgear units have been tested according to IEC 62271-200:2003 for the following Internal Arc Classification. The SecoGear have pass type test IAC AFLR 40kA/1s for 17.5kV, 31.5kA/1s for 27kV with skirt as below, the minimum height of room is 4m.

Key Condition Key will be free when the truck in the disconnect position Key will be trapped when the truck in the rack-in position Key will be free when the earthing switch is open Key will be trapped when the earthing switch in closed position Key will be free when the earthing switch closed Key will be trapped when the earthing switch in open position

Functional truck racking-in lock Key-lock for Earthing switch Earthing switch closing lock Earthing switch opening lock
SCALE 1,000

Arc release channel

SCALE

1,000

Interlock
1152 650 650 1000 1200 800 900 C View 1152 2720 546 3100 800 500 800 2180

2200

B C
1500
SCALE 1,000

Arc Release System

Arc skirt (optional)

Interlock

10

11

Product Description

compartment caused by internal

from test to connect position and vice

when the circuit breaker is positively

Safety

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Environment
Increasing global legislation concerning the use of green house gases such as SF6 gas and their related disposal costs, makes vacuum technology with its reliability, low maintenance, and low environmental impact the choice for now and the future. As the world strives to reduce the amount of SF6 gas used in all applications there is a responsibility on the users of electrical switchgear to find, where appropriate, alternatives to SF6 gas as an insulation and switching medium. Air and solid

Environmentally friendly
From the very beginning GE made a fundamental choice not to use SF6 as a switching and insulation medium for primary medium voltage equipment. SF6 is on the list of greenhouse gasses in the Kyoto protocol and is the most potent of the six main greenhouse gasses, with a Global Warming Potential (GWP) of 23,000. Many other medium voltage switchgear systems use SF6 gas as the insulating medium. Leakage of SF6 gas from switchgear contributes significantly to the threat of the greenhouse effect and associated climate change. They also require additional safety measures and special handling requirements at the end of life.

Energy efficient assembly


SecoGear is produced in an energy efficient environment. Standard processes and materials are used in the design and require no special handling or manufacturing processes, thus reducing the amount of energy required to manufacture and assemble the switchgear.

Product Description

technologies are a reliable, safe and economic alternative for use in electrical systems below 36kV and therefore should be used instead of SF6 gas insulated systems. Modern medium voltage switchgear employing vacuum technology together with air and epoxy resin insulation provides:
Minimum number of parts and components No special requirements for the end-of-life disposal of the

Efficient use of materials


Besides the energy sources, special focus is placed on the efficient use of material during assembly. For example by using advanced nesting tools the hot dipped galvanized steel plates are cut with the least amount of waste, and similar principles are followed in the design and manufacture of other product components

switchgear
Environmentally-friendly materials used in the design No use of SF6-gas for switching and insulation No risk of damaging leaks of SF6 gas or of toxic byproducts Energy-efficient production and assembly, with

Minimum service checks on site


SecoGear is designed for a lifetime of at least 20 years; therefore the energy usage for maintenance activities during this long period is minimal. Due to the green insulation and switching technology, there is also no leakage of the harmful SF6 gas during its lifetime and no need for performing extra maintenance activities on SF6 gas pressure checks.

environmentally friendly energy sources


Minimal number of transition points in the primary design

Re-use or recycling of materials


All materials of SecoGear and SecoVac can be reused, all materials are not any impact on the environment, it fully reflects the GE corporate social responsibility to design and produce products.

enables low energy loss during operation


Only re-usable and/or recyclable materials used

Environmentally friendly design


GE's production plants act entirely in accordance with the rules and procedures of the ISO 14001 environmental certificate during development and production processes. Material selection and the number of parts that are used to manufacture the SecoGear are critical to determining how environmentally friendly the manufacturing process is. GE selects
12

its materials to ensure that they have the lowest possible impact on the environment. It is essential that they are equally safe for people not just during use, but at the end of service life too. Within SecoGear and the SecoVac vacuum circuit breaker, a combination of solid (cast-resin) and air is used as insulation. The castresin technology, in combination with electrical field calculations, provides a very

compact, environmentally friendly design for the circuit breaker and the switchgear. Because the switching medium - vacuum is used, SecoGear can be completely recycled at the end of its life without any issues relating to safety procedures, special handling or safe disposal.

Minimal energy loss during operation


The number of electrical contact or changeover points within the SecoGear system has been kept to an absolute minimum. This reduces the potential number of "hot spots" and prevents additional energy loss associated with contact surfaces.

13

Product Description

insulation switchgear systems incorporating vacuum switching

Environment

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Product Introduction
1

Low voltage compartment

The compartment is isolated with earthed metal partitions and has ample space for control and protection devices. A fully isolated metal wire way is mounted at the top of each switchgear panel; this connects together to form a continuous low voltage wire way that runs along the entire length of the switchgear.
1

Product Introduction
Product Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 15 Control and Operation . . . . . . . . . . . . . . . . . . . . . . . . 17 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . 18 Operation Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 2 2

Busbar compartment

Busbars are totally enclosed in their own earthed metal compartment which vents into the arc the busbars for up to 27kV SecoGear are type tested for ratings up to 4000A, 40kA for 3 seconds. for 24/27kV SecoGear, the busbars are type tested for rating up to 2500A, 31.5kA for 3 seconds. Epoxy moldings separate switchgear sections. chamber. Fully insulated along their entire length,
4

Product Introduction

IEC Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

6 3 5

Vacuum circuit breaker compartment

Fully isolated by earthed metal partitions, with its own pressure relief channel into the arc chamber. The compartment provides all the safety
8 7 9

interlocking mechanisms required for safe and reliable operation of the vacuum circuit breaker. Manual operation buttons allow for full operation of the vacuum circuit breaker from the front of the switchgear with the door fully closed. The circuit breaker is mechanically interlocked with the compartment door so that the door cannot be opened until the circuit breaker is switched off and racked out into the Test position.

14

15

Product Introduction

Storage Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Automatic shutters

Control and Operation


1 Low voltage control and protection compartment Panel with all controls and indicators clearly visible and easy to operate Protection relay GE has a range of Multilin relay options that can be fitted as standard. However, customer specific protection relays from any manufacturer can be fitted to the compartment door Mimic diagram Easy to understand mimic diagram of each circuit Circuit breaker position indicator Breaker position indication shows the breaker in the connected/service or disconnected/test position Electrical operation with circuit breaker status indicator Breaker open/closed status indicator. Breaker open/closed command switch. Optional LED indication of spring charge mechanism charged status Voltage detection system Each circuit breaker panel can be equipped with an optional standard three phase voltage detection system for voltage detection to IEC 61243-5 Viewing windows The circuit breaker compartment door viewing window provides visual indication of the position of the circuit breaker indicating: - The status of the breaker - The status of the spring charged mechanism Circuit breaker racking operate hole Circuit breaker racking in/out operate hole Earthing switch operate hole Earthing switch open/close 1 2 4 6 5

When the circuit breaker is in Test or Disconnect position, the shutters automatically close to isolate the fixed contact from any live parts. Shutters can be individually and automatically operated for bus side and feeder side connection in close position. 2

Earth switch

Cable compartment
3

The earthing switch can be operated from the front of the switchgear. It is mechanically interlocked with the circuit breaker truck so that the earthing switch can only be operated when the circuit breaker is open in Test/Disconnect position as well. The switch is also mechanically interlocked with the cable compartment for additional safety.

Cable supports are provided to secure cables. Cable clamps are applied for fix the cables. And the metal floor cover is removable.

Product Introduction

Earth bar is made of copper and


6

Current transformers

installed in the bottom of cable compartment. The earth bar system has been fault tested and runs vertically and horizontally with each panel section and is connected to the earth switch. 7
10

Current transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes.

Surge arrester

Surge arrester is used to protect electric equipment against


7

Voltage transformers

transient operating or lightning over-voltage. It is connected between primary conductor and ground for protecting protective load from damage effect. When the operating or lightning over-voltage occurs, surge arrester immediately limits over-voltage amplitude and protects the insulation of device. 9 8

Voltage transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes.

16

17

Product Introduction

Earth bar

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Technical Characteristics
Rated voltage Rated power frequency (1min) Rated lightning impulse (1.2/50s) Rated frequency Rated current (main busbar) Rated short time withstand (3sec) Rated peak withstand current 1 IP level for weather protection kV kV kV Hz A kA kA Enclosure Between compartment 7.2 20 60 12 28 75 15 36 95 17.5 38 95 24 50 125 27 65 125

Operating Conditions
Normal operating conditions
The switchgear is fundamentally designed for the normal service conditions for indoor switchgear to IEC Publication 62271-1. The following limit values, among others, apply.
Ambient temperature

Note on any special climatic operating conditions


When the switchgear is operated in areas with high humidity and/or major rapid temperature fluctuations, there is a risk of condensation. Preventive action (e.g. fitting the electric heater) must be taken in consultation with the manufacturer to avoid the condensation and any resulting corrosion or other adverse effects. The control of the heaters depends on the relevant project.

50/60 630/1250/1600/2000/2500/3150/4000* 25/31.5/40 65/82/104 IP4X IP2X

50/60 1250/1600/2000/2500 20/31.5 65/82 IP4X IP2X

*4000A switchgear with force cooling

- Maximum +40C - 24h-Medium +35C - Minimum -15C


Humidity

Special operating conditions


SecoGear is suitable for operation in the climate of indoor type according to IEC standard. Special operating conditions must be discussed with GE in advance. For example: At site altitudes above 1000 m, the effects of the reduction in density of the air on the dielectric properties must be taken into account. Increased ambient temperatures must be compensated for in the design of the busbar and the branch conductors as well as the withdrawable parts; otherwise the current carrying capacity will be reduced. Fitting additional ventilation facilities can assist heat dissipation in the switchgear panel.

Protection
IP4X for the enclosure IP2X between each compartment

Construction
Internal arc withstand (classification IAC): AFLR 3 compartments (classification LSC2B according to IEC 62271-200) All the metal surfaces in the panels are corrosion proof Panels are produced using hot dipped galvanized steel sheet

- Highest average value measured over 24 hours - Relative humidity 95% - Highest average value measured over 1 month - Relative humidity 90%
The maximum site altitude is 1000 m

Product Introduction

Connections
Front and/or rear access Cable entry from bottom or top

Busbar fully insulated for 7.2kV, 12kV, 13.8kV, 15kV, 17.5kV, 24kV, 27kV

above sea level


Seismic Rating up to Uniform Building

Code (UBC) 1997 Zone 4

High altitude application


The insulating capacity of the switchgear with rated values of short-time powerfrequency withstand voltage and impulse withstand voltage according to IEC 62271-1.

18

19

Product Introduction

IP42 optional

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Storage Conditions
In order to retain all of the functional units qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between 15C and + 40C. For storage: -30C.

IEC Standards
SecoGear complies with the standards metal enclosed switchgear and has been type tested in accordance with the IEC publications as given below. and specifications for factory assembled

Product Introduction

IEC 62271-100: 2008 High-voltage alternating current circuit breakers. IEC 62271-200: 2003 AC Metal enclosed switchgear and control gear for rated voltages IEC 62271-1: 2007 IEC 60529:1989 above 1kV and up to 52kV. The common specification for high voltage switchgear and control gear Standards. Degrees of protection as provided by enclosures (IP Code). IEC 62271-102: 2001 High-voltage alternating current disconnector and Earth Switches.

Configurations
Typical Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Incoming/Feeder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Busbar Tie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Riser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Riser with VT & CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 VT Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Incoming with Measuring (VT) . . . . . . . . . . . . . . . . . 28 Incoming with ES & VT . . . . . . . . . . . . . . . . . . . . . . . . 29 Incoming with ES & Fix VT. . . . . . . . . . . . . . . . . . . . . 30 Riser with ES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 CPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

20

21

Configurations

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Typical Panels
The SecoGear series comprises 10 basic configuration applications. The table below can be used to link requirements to functional units and gives basic information on the general composition of each unit.

Incoming/Feeder

P26
Riser Riser with VT & CT

Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)

630 1250 1600

7.2 20 60 650 2200 1900 1400

12

15 28 75 36 95 1000 2200 1900 1400 650 2200 1900 1400 1000 2200 1900 1400

17.5 38 95 650 2200 1900 1400

24 50 125 1000 2200 1900 1400 650 2400 1800 1000 2400 1800 65 125 27

3.3kV-17.5kV
Incoming/Feeder Incoming with measuring (VT) Busbar Tie

1000 2200 1900 1400

650 2200 1900 1400

Rated current (A)

2000 2500 3150 4000* 25

Configurations

Breaking capacity (kA)

31.5 40 25

650 2400 1800

Short time withstand current (kA/3s) VT Panel Incoming with measuring (VT) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling Top Access Bottom Access

31.5 40

1000 2400 1800

615

615

615

615

1100

1100

24kV-27kV
Incoming with ES & VT (24kV) Incoming with ES & VT (27kV) Riser with ES CPT

17

22

23

Configurations

22

04

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Busbar Tie

Riser
630 1250 1600 650 2200 1400 20 60 1000 2200 1400 650 2200 1400 7.2 28 75 1000 2200 1400 650 2200 1400 1000 2200 1400 12 36 95 650 2200 1400 15 38 95 1000 2200 1400 650 2400 1800 1000 2400 1800 17.5 50 125 650 2400 1800 1000 2400 1800 Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling Short time withstand current (kA/3s) Breaking capacity (kA) 24 65 125 Rated current (A) 27

P28

Rated Voltage (kV)

P29

Rated Voltage (kV)

630 1250 1600 2000 2500 3150 4000* 25 31.5 40 25 31.5 40

7.2 20 60 650 2200 1400

12

15 28 75 36 95 1000 2200 1400 650 2200 1400 1000 2200 1400

17.5 38 95 650 2200 1400

24 50 125 1000 2200 1400 650 2400 1800 1000 2400 1800 65 125 27

Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)

Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)

1000 2200 1400

650 2200 1400

Rated current (A)

2000 2500 3150 4000* 25

Configurations

Breaking capacity (kA)

31.5 40 25

650 2400 1800

Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling

31.5 40

1000 2400 1800

615

615

615

615

1100

1100

615

615

615

615

1100

1100

01

C
SCALE 1,000

C
SCALE 1,000

24

25

Configurations

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

P30 Riser with VT & CT


Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV) 630 1250 1600 Rated current (A) 2000 2500 3150 4000 25 Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) 31.5 40 7.2 20 60 800 2200 1400 615 12 28 75 800 2200 1400 615 800 2200 1400 615 36 95 15 17.5 38 95 800 2200 1400 615 800 2400 1800 1100 800 2400 1800 1100 24 50 125 27 65 125

VT Panel
Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV) Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) 25 31.5 40 7.2 20 60 800 2200 1400 615 12 28 75 800 2200 1400 615 800 2200 1400 615 36 95 15 17.5 38 95 800 2200 1400 615 800 2400 1800 1100 800 2400 1800 1100 24 50 125 27 65 125

Configurations

JSZV17-15R

15

JSZV17-15R

15

01

26

76

95.5

76

95.5

27

Configurations

SecoGear 3.3kV-27kV Air Insulated Switchgear

Incoming with Measuring (VT)

P29
7.2 12 20 60 28 75 1000 2200 1400 650 2200 1400 1000 2200 1400 650 2200 1400 1000 2200 1400 36 95 650 2200 1400 15 38 95 1000 2200 1400 650 2400 1800 1000 2400 1800 17.5 50 125 650 2400 1800 1000 2400 1800 24 65 125 27

SecoGear 3.3kV-27kV Air Insulated Switchgear

Incoming with ES & VT (24kV)


Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV) 630 1250 Rated current (A) 1600 2000 2500 Breaking capacity (kA) Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling 25 31.5 25 31.5 800 2400 1800 1100 50 125 24

P32

Rated Voltage (kV)

630 1250 1600

Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)

650 2200 1400

Rated current (A)

2000 2500 3150 4000* 25

Configurations

Breaking capacity (kA)

31.5 40 25

1000 2400 1800

Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling

31.5 40

615

615

615

615

1100

1100

10

SCALE

1,000

28

29

Configurations

P30

SecoGear 3.3kV-27kV Air Insulated Switchgear

Incoming with ES & VT (27kV)


Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV) 630 1250 Rated current (A) 1600 2000 2500 Breaking capacity (kA) 25 31.5 25 31.5 650 2400 1800 1100 65 125 1000 2400 1800 27

P31

SecoGear 3.3kV-27kV Air Insulated Switchgear

Riser with ES
Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV) 630 1250 Rated current (A) 1600 2000 2500 Breaking capacity (kA) Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling 25 31.5 25 31.5 650 2400 1800 1100 65 125 27

Configurations

Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling

1000 2400 1800

30

31

Configurations

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

CPT

Configurations scheme
17.5kV
630 1250 1600 650 2400 1800 1100 65 125 1000 2400 1800 Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm) Scheme Number 630~4000 1 2 630~4000 1 2 630~4000 1 3 630~4000 1 3 630~4000 1 2 2 2 630~4000 1 3 3 3 Primary Scheme Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm) Scheme Number 630~4000 1 3 630~4000 1 3 630~4000 1 3 630~4000 1 3 630~4000 1 3 630~4000 1 3 27 Primary Scheme

P32

Rated Voltage (kV) Rated Insulation Level Power frequency withstand voltage (kV) Lightning impulse withstand voltage (kV)

Scheme Number

P33

01

02

03

04

05

06

Rated current (A)

2000 2500 3150 4000* 25

1 I/F 650/1000 07 I/F 650/1000 08

Configurations

Breaking capacity (kA)

31.5 40 25

I/F 650/1000 10

I/F 650/1000 11

09

12

Short time withstand current (kA/3s) Dimensions (mm) Width (W) Height (H) Depth (D) Estimated Weight (kg) *4000A switchgear with force cooling

31.5 40

B 650/1000 13

B 650/1000 14

B 650/1000 15

B 650/1000 16

I/F 650/1000 17

I/F 650/1000 18

Primary Scheme

Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm)

630~4000 1 2 3 3

630~4000 1 3 3 3 1 I/F 650/1000

630~4000

630~4000

630~4000

630~4000

2 3

2 3 3 VT 650/1000

3 3

3 3 3 VT 650/1000

I/F 650/1000

VT 650/1000

VT 650/1000

32

33

Configurations

1 3 I/F 650/1000

1 3 I/F 650/1000

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Configurations scheme
17.5kV

Scheme Number

P34

19

20

21

22

23

24

Primary Scheme

Configurations

Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm) Scheme Number

630~4000

630~4000

630~4000 2 2 2

630~4000 2 2 2

630~4000 3 3 3

630~4000 3 3 3

R 650/1000 25

R 650/1000

M 650/1000

M 650/1000

M 650/1000

M 650/1000

Primary Scheme

Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm)

630~1250 2 3 3

M 800

27kV
Scheme Number 26 27 28 29

Measurement, Protection and Control


Multilin 3 Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Multilin 650 Family . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Primary Scheme

Rated Curent (A) Vacuum Circuit Breaker Current Transformer Voltage Transformer Main Apparatus High Voltage Fuse Earthing Switch Arrester Application Switchgear Width (mm)
34

1250~2500 1 3 3 3 1 1/F 800/1000

1250~2500 1 3 3 3 1 1/F 800/1000

1250~2500

1250~2500

2 3 1 R 800 M 1000
35

Monitoring and Protection

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Measurement, Protection and Control


For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/3Series.htm

Features
Protection & control (for Multilin 350 Feeder Protection System)
Phase, neutral and ground TOC and IOC Undervoltage, overvoltage, frequency Neutral/ground directional Negative sequence overcurrent ANSI, IAC, IEC, flex curves

Easy-to-use
Drawout construction The Multilin 3 Series offers a complete drawout feature eliminating the need for rewiring after testing has been concluded. The withdrawable feature also eradicates the need to disconnect communication cables, e.g. fiber, copper, RJ45, etc and helps retain communication status even after a relay has been withdrawn from its case.

Multilin 3 Series
Intuitive industrial and utility protective relay systems for feeders, motors and transformers

Cable Thermal Model protection Breaker failure Cold load pick-up Four-shot auto reclose 8 digital inputs, 7 contact outputs Two setting groups

Overview
The Multilin 3 Series of protection relays are a highly functional, economical protection relays for feeders, motors and transformers. By providing an economical system for protection, control, monitoring and metering, and both local and remote user interfaces in one assembly, the Multilin 3 Series relays effectively eliminate the need for expensive discrete components. The Multilin 3 Series provides detailed diagnostic information allowing users to troubleshoot and minimize downtime. Detailed diagnostics is provided via the 256 1ms time stamped event recorder and the 192 cycle Oscillography report sampled at 32 samples per cycle. The robust Multilin 3 Series streamlines user work flow processes and simplifies engineering tasks such as configuration, wiring, testing, commissioning, and maintenance. This cost-effective relay also offers enhanced features such as diagnostics, preventative maintenance, device health reports and advance security features.

Metering & monitoring


Event Recorder: 256 events with 1ms

time stamping
Oscillography with 32 samples per

cycle and digital states

Key benefits

IRIG-B clock synchronization Application flexibility with the use of programmable logic Relay & Asset Health Diagnostics Security audit trail

Monitoring and Protection

feeders, motors and transformers


Effortless draw-out construction eliminates requirements for

elements
Large backlit display with 40 characters for easy viewing of

Advanced communications
Easy integration into new or existing infrastructure With several Ethernet and serial port options, and a variety of communication protocols, the Multilin 3 Series provides advanced and flexible communication selections enabling seamless integration into new or existing applications. The Multilin 3 Series supports various industry standard protocols such as, IEC 61850 & IEC 61850 GOOSE, Modbus RTU, Modbus TCP/IP, DNP3.0, IEC 60870-5-104 and IEC 60870-5-103.

User interface and programming


4x20 character LCD display Control panel with 12 LED indicators Front USB and rear serial, Ethernet and

test switches and reduces downtime


Environmental monitoring system to alarm on destructive

relay information and settings


Flexible communications with multiple ports & protocols to

operating conditions to enable preventative maintenance


Easy-to-use interface and set up in one simple step Accelerated Life Cycle Tested to ensure reliability of relay

allow seamless integration into new and existing infrastructure


Easy access to information via multiple communication

Fiber ports
Multiple protocols - IEC 61850 & 61850

network options including USB, Serial, Fiber & Copper Ethernet


Reduced wiring with support for remote I/O Reduce setup and configuration time with the Simplified Motor

operation under abnormal conditions


Advanced power system diagnostics to increase reliability

GOOSE, ModBus RTU, ModBus TCP/IP, DNP 3.0, IEC 60870-5-104, IEC 60870-5-103 EnerVista software
An industry-leading suite of software

through fault and disturbance recording capabilities


Arc Flash mitigation via zone inter-tripping, flex curves and

Setup screen
Powerful Security Audit Trail tool to increase security and

multiple setting groups

minimize system risks by tracking setting changes

tools that simplifies every aspect of working with Multilin devices

Applications
Advanced protection, monitoring & control relays for feeders Distribution utility down stream breaker protection Medium voltage utility feeders with advanced control features

Document and software archiving

toolset to ensure reference material and device utilities are up-to-date

(Multilin 350), motors (Multilin 339) and transformers (Multilin 345)


Industrial feeders with enhanced breaker monitoring and

including, cold load pickup, auto reclose and multiple setting groups

diagnostics

36

37

Monitoring and Protection

Easy-to-use and cost effective protection and control for

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Enhanced diagnostics
Preventative maintenance The Multilin 3 Series allows users to track relay exposure to extreme environmental conditions by monitoring and alarming at high temperatures. This data allows user to proactively schedule regular maintenance work and upgrade activities. All relays utilize EnerVista setup
TM

EnerVistaTM Launchpad
EnerVista Launchpad is a complete set of powerful device setup and configuration tools that is included at no extra charge with the SR Relays.
Set up the Multilin 3 Series Relays - and any

Security
Security audit trail The Multilin 3 Series monitors security and reliability of asset protection. The Multilin 3 Series protection devices offer complete traceability of any relay setting and command changes, allowing the user to quickly identify changes made to the relay.

Measurement, Protection and Control


For more information visit our website: http://www.gedigitalenergy.com/multilin/catalog/F650.htm

other Multilin device - in minutes. Retrieve and view oscillography and event data at the click of a button
Build an instant archive on any of the

software for communication, monitoring and metering. Actual values, setpoints, status, trending, and waveform capture information may all be viewed via the software, and can be used for troubleshooting.

Multilin 650 Family


Advanced protection, control and monitoring system

latest Multilin manuals, service advisories, application notes, specifications or firmware for your SR Relay
Automatic document and software version

updates via the internet and detailed e-mail notification of new releases

User Interface
SETPOINT GROUP 1, 2:
These indicators are continuously on if corresponding group provides settings for protection elements. TRIP: Indicator turns on when relay detects a trip condition. Operates the trip relay to open the breaker. ALARM: While relay detects an alarm condition, indicator flashes. PICKUP: Indicator lights steady when any protection feature pickup threshold exceeded.

Key benefits
plus programmable logic
Flexible and cost effective control for complex systems -

Monitoring and Protection

through standard RS232 & RS485 Ethernet Ports


Optimal integration flexibility via open standard protocols -

DISPLAY: LEDs:

4 line text for easy viewing of key data.

Use IEC compatible programmable logic to customize the functionality of your protection & control system to address unique, site specific applications
Human machine interface (HMI) - Standard backlit LCD display

Modbus RTU, DNP 3.0 Level 2, IEC 60870-5-104, IEC 61850, IEC 870-5-103
Minimize communication down time - Reliable redundant

10 LED indicators for quick diagnostics.

KEYPAD:

Ethernet Communication ports with 10/100BaseTX, 100BaseFX with ST connectors and optional double 100BaseFX, with ST connectors
Complete asset monitoring - Full metering including demand

Ten button keypad for access to device interrogation and change of settings.

with 4 x 20, optional 16 x 40 (240 x 128 pixels) graphical LCD, programmable buttons and directional keys for selecting setting menus and submenus
Minimize replacement time - Modular with card draw-out

FRONT PORT:

Electrically isolated front USB communication port.

Protection Features
BUS BUS VT 52 79 TRIP 3 CLOSE 1 MONITORING 50P 2 50N 2 CLP 1 50G 2 50G/ 51G 51G 1 51P 1 51N 1 50BF 79 50_2 1 49 1 METERING 27P 1 59P 1 27X 1 59X 1 59_2 1 59N 1 81U 2 81O 2

ANSI Device Numbers & Functions


Device Number 27P 27X 49 50P 50N 50G 50BF 50_2 51P 51G 51N 59P 59X 59N 59_2 67G 67N 79 81U 81O CLP

& energy
Follow technology evolution - Flash memory for product field

Function
Phase Undervoltage Auxiliary Undervoltage Thermal Model Phase Instantaneous Overcurrent Neutral Instantaneous Overcurrent Ground/Sensitive Ground Instantaneous Overcurrent Breaker Failure Negative Sequence Overcurrent Phase Timed Overcurrent Ground Timed Overcurrent Neutral Timed Overcurrent Phase Overvoltage Auxiliary Overvoltage Neutral Overvoltage Negative Sequence Overvoltage Ground Directional Overcurrent Neutral Directional Overcurrent Autoreclose Underfrequency Overfrequency Cold Load Pickup

construction
Reduce troubleshooting time and maintenance costs - IRIG-B

upgrade

time synchronization, event reports, waveform capture, data logger

Applications
F650: Management and primary protection of distribution G650: Distributed generation management device G650: Reliable Distributed Generation interconnection

TRANSIENT RECORDER EVENT RECORDER

feeders and bus couplers


F650: Backup protection of busses, transformers and power

protection system
W650: Wind turbine protection, control and monitoring W650: Distributed generation grid interconnection device
39

350 RELAY
LOAD

lines
G650: Packaged generator mains failure detection

Latched Lockout available as a standard feature

38

Monitoring and Protection

Unique built-in control features - Comprehensive protection

Cost Effective Access information - Via multiple protocols,

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Features
Protection and control
Up to 32 Programmable digital inputs Up to 16 digital outputs Trip Circuit Supervision Redundant power supply option Configurable PLC logic according to IEC 61131-3 Fully configurable graphic display HMI interface Alarms panel

These records are stored in non volatile User interface


Large graphic (16 x 40) or regular (4 x 20) character display Easy-to-use control via Shuttle key Front USB port or standard RS232 Rear wire 10/100BaseTX Ethernet for LAN connection Rear wire CAN bus port (OPEN CAN protocol - W650) Optional fibre optic 100BaseFX Ethernet, single or redundant Optional rear RS485 port 1 ready LED and 15 programmable LED indicators

Communications
Multilin 650 units incorporate up to three ports that operate independently. Redundant ports are available for high reliability applications: Available protocols for rear port 1 and 2 are ModBus RTU, IEC 103 and serial DNP 3.0. The third port is located in a removable communications card. This plug-andplay card can be easily changed in the future as new standards arrive to the market, thus providing a migration path to the customer. The protocol available for the third port is DNP 3.0 over TCP/IP, UDP/IP, ModBus TCP/IP and IEC 60870-5-104.

memory. Therefore, there is no need for internal battery monitoring or maintenance. Trip circuit monitoring Multilin 650 units offer as an option two complete supervision circuits for breaker trip and closing coils and circuits. These supervision inputs monitor both the battery voltage level and the continuity of the trip and/or closing circuits, applying current through those circuits and checking that it flows properly. In order to apply this feature it is necessary to choose I/O board 1 option 2.

Monitoring and metering


Energy metering Demand metering Trip circuit monitoring Oscillography Data logger Sequence of event Self diagnostic

EnerVistaTM Integrator providing easy integration of data in the

650 relay into new or existing monitoring and control systems

Overview
The Multilin 650 family has been designed as a comprehensive protection, control, metering and monitoring package. The microprocessor based architecture is a complete solution for different applications that complies with the most relevant international standards. All the elements required for each application have been integrated into a single package for a cost-effective, reliable and simple utilization. The low number of components, thanks to the use of stateof-the-art but mature technology, deliver a very high reliability. Hardware inputs and outputs have been designed in a modular way that allow easy migration from simple to more complex applications. The control functions include a fullscheme virtual PLC with an optional graphical display. The combination of both elements provide total control for a bay. This means real-time monitoring of breakers and selector switches, open and close commands supervised by the programmable interlockings and metering
40

Metering
screens. The metering capability allows 0.5% accuracy for current and 1% from 10V to 208V for voltage in metering range. Monitoring functions include a 479 event recorder, and a programmable oscillography recorder. The Multilin 650s communications capability and option make the product very unique. These units include a maximum of three independent communication ports: COM1, COM2 and COM3, with many physical choices through the use of two removable plugand-play boards. The brain of the Multilin 650 units includes a powerful built-in virtual PLC. This PLC can be programmed according to the IEC 61131-3 language by functional block diagrams. 650 units come with 8 to 32 digital inputs and with 8 to 16 outputs depending on options. All digital inputs may be filtered with a separate debounce time to tailor customer requirements. Recording functions The recording functions within the Multilin 650 include:
Event recorder capable of storing 479

The Multilin 650 provides the following metering values.


Current: Ia, Ib, Ic, In, Ig, Isg Phase-to-phase and phase-to-ground

User Interface

Graphic 16 x 40 or text 4 x 20 LCD display Fluorescent backlight to improve visibility Multicolor programmable LEDs with label panel Local/Remote/Off pushbutton with LEDs Key control for easy navigation Ergonomic programmable keys

Monitoring and Protection

Vbn, Vcn, Vab, Vbc, Vca, Vx


Active power (per phase and total) : Wa,

Wb, Wc, W
Reactive power (per phase and total) :

VARa, VARb, VARc, VAR


Power factor (per phase and total) Frequency These signals are available for local

Electrically isolated front USB communication port


ANSI Device Numbers & Functions
Device Number

display and accessible remotely using communications

Function
Synchrocheck Bus/Line Undervoltage Sensitive Directional Power Forward Power Wattmetric zero-sequence directional Negative Sequence Time Overcurrent Negative Sequence Voltage Blocked Rotor Thermal Image - overload protection Breaker Failure Phase Instantaneous Overcurrent (High/Low) Neutral Instantaneous Overcurrent Ground Instantaneous Overcurrent Sensitive Ground Instantaneous Overcurrent Isolated Ground Instantaneous Overcurrent Neutral Time Overcurrent Ground Time Overcurrent Sensitive Ground Time Overcurrent Voltage Restraint Phase Time Overcurrent Bus/Line Overvoltage Neutral Overvoltage - High/Low Phase Directional Overcurrent Neutral Directional Overcurrent Ground Directional Overcurrent Sensitive Ground Directional Overcurrent Autorecloser Under/Over Frequency Broken Conductor Detection Load Encroachment Frequency Rate of Change VT Fuse Failure Detection

Functional Block Diagram

52 79
1

CLOSE Monitoring
49
3

TRIP
BROKEN CONDUCTOR

27X
3

59X

50BF
1

50PH 50PL
3 3

46
3

48
3

32FP
3

32
3

32N
3

51PH/V 51PL/V 67P


R R

50N
3

51N
3

67N
3

25
1

time-tagged events (1 true millisecond accurate tagging)


Up to 20 separate oscillography records

1 1

50G
3

51G
3

67G
3

50SG 51SG
3 3

50IG
3

67SG
3

METERING

3V_0

can be stored in memory. The capacity of each record will depend on the type of oscillo selected (1 Mbyte/Max. No. Osc)

47
3

27
3

59
3

VTFF
1

81U
3

81O
3

81R
3

59NH
3

25 27/27X 32 32FP 32N 46 47 48 49 50 BF 50PH/PL 50N 50G 50SG 50IG 51N 51G 51SG 51PH/V 51PL/V 59/59X 59NH/NL 67P 67N 67G 67SG 79 81 U/O N/A 81R VTFF

F650 Digital Bay Controller

59NL
3
EN F650 BLOCK F.CDR

41

Monitoring and Protection

voltage values for bus and line: Van,

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Device setup & document management toolset


The EnerVistaTM launchpad software is a powerful toolset used for the complete support and management of Multilin products. Support application including product software, manuals, and setting files management is used to ensure your important files are kept up-to-date and easily accessible. Site Management will allow you to properly maintain your asset and devices by providing real-time diagnostic data and reports.

Logic, IEC 61850 system configuration and Real-Time monitoring


Viewpoint Engineer is the most advanced tool for protection & control engineers and commissioning staff available. Use the full-featured Graphical Logic Designer to build and annotate complex Flexlogic and then observe it in real-time with the Graphical Logic Monitor. Use the System Designer option to design and annotate IEC 61850 communication schemes, including ICD file import and SCD file export for non-GE IEDs.

Security auditing, device and asset health reporting and fault data retrieval
Viewpoint Maintenance provides security auditing, device and asset health reporting as well as easily accessible fault data. With a comprehensive security audit report, changes to the device settings, including the MAC address, are recorded enabling compliance with NERC / Critical Infrastructure Protection Standards. Device and Asset status reports detail current and historical health for both the intelligent protection device and the asset being protected.

Easy-to-Use monitoring and data recording


Viewpoint Monitoring provides simplified visualization of real-time data from all GE Multilin using ready-made Plug-andPlay screens. Built-in data logger, alarm annunciator and time synchronization round out this HMI package. Third-party devices can be incorporated using either generic Modbus RTU or Modbus TCP/IP or IEC 61850 and optional OPC/DDE server connectivity can link to existing facility DCS or SCADA systems.

OPC connectivity to automation and historian applications


Seamless integration of GE Multilin and SCADA systems and other data consumer applications (data historians, data visualization tools) using standard open OPC/DDE connectivity. generic Modbus devices into existing DCS,

Monitoring and Protection

42

43

Monitoring and Protection

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Vacuum Circuit Breaker


SecoVac VB2 Plus embedded pole vacuum circuit breaker 7.2kV, 12kV and 17.5kV
Safety, more reliability and High performance in a compact package

SecoVac VB2 Plus of Modular design

Features and benefits


Industry leading vacuum and solid insulation technology
Fixed and withdrawable versions available Environmentally friendly design - no SF6 gas Conformance to the latest IEC standards - IEC 62271-100

Applications
Serving global 50 Hz and 60 Hz Segments of the electrical industry: industrial, commercial,

utility, mining, marine and off-shore


Protecting transformers, capacitor banks, motors, busbar

and IEC 62271-1


Numerous safety features for maximum personnel

sections and cables


Suitable for special environment conditions: shock, vibration

protection
User friendly operation with easy access and minimal

and high ambient temperature

inspection
Compact and cost effective Flexible with a full line of accessories and OEM Solution

Spare Parts

Switchgear Compartment
Vacuum Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . 45 Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Voltage Transformer Truck. . . . . . . . . . . . . . . . . . . . 50 Earthing Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Operation Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

44

45

Spare Parts

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Circuit Breaker Characteristics


Rated Voltage Rated power frequency withstand (1min) Rated lightning frequency impulse withstand voltage (1.2/50s) Rated Frequency Rated Current Rated short-circuit breaking current Percentage of DC component Rated short-circuit closing current Rated short time withstand current Rated peak value withstand current Rated duration time for short-circuit Opening Time Closing Time Rated auxiliary control voltage Operation sequence Mechanical life operations Electrical Endurance class Single capacitor bank Switching current Rating for Earthing Switch short time withstand current * Force cooling. kV kV kVp Hz A kA kAp kA kAp s ms ms V Quantity A 7.2 20 60 12 28 75 50/60 630/1250/1600/2000/2500/3150/4000* 25/31.5/40 Up to 50% 65/82/104 25/31.5/40 65/82/104 3 20~50 30~70 36/48/60/110/220 V DC 110/220 V AC O-0.3s-CO-180s-CO/ O-0.3s-CO-15s-CO 10,000 (M 2) E2 400 31.5kA 1s O-0.3s-CO-15s-CO 10,000 (M 2) E2 (list 1) 400 31.5kA 1s 15 36 95 17.5 38 95 24 50 125 50/60 1250, 2500 31.5 52% 82 31.5 82 3 20~50 30~70 27 65 125

Internal wiring diagram (AC) 17.5kV


Spring Charge Motor
26 24 25

Closing Circuit
10

Breaker Interlock Circuit


52

Opening Circuit
30 6 3 5 7 9 23 27 28 29 8

Truck Interlock Circuit


1

V2

V4

V3

V1

K0 (13) (14)

CC TC S2 S4 BC (73) (74) S5 (11) (12) S5 91 92 31 32 41 42 71 72 61 62 63 64 23 24 33 34 83 84 93 94


V5 A~ C+ BY4 1
ZC 2

M
(51) (52) (53) S5 (5) (3)

D~

(54) S5 K0 (2)

S5

(21) (22) S3

(13) (14) S3

(21) (22) S1

43 44

S8

43 44

S9

36

34

35

20

53

54

31

32

16 13 15 17 19 33 37 38

39 18

40

11

47

57

55

13 14 S9

33 34 S9

23 24 S9

53 54 S9

Main circuit resistance of SecoVac


Item Rated Current Resistance Unit A 45 Value 1250~1600 2000~4000 25
21 22 43 S5 44 S5

13 14 S8

33 34 S8

23 24 S8

53 54 S8

13 14 S5

81 82 S5

21 22 51 50

12

14

48

49 58

56

Coil Characteristics
S9: Limit switch (working position) Rated voltage Rated current Rated voltage Rated current Rated voltage Rated current (V) (A) (V) (A) (V) (A) DC36 DC110 11.5 2.9 2.9 DC48 DC220 AC220 8.4 1.5 1.5 DC60 11.5 S8: Limit switch (testing position) S5: Auxiliary switch S1~S3: Energy storing travel switch Note: 1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state. 2. The polarity in dashed frame should be connected to common DC voltage terminal. 3. Rectifier will be removed if DC is applied. Energy staring period under rated operation voltage (s) <10s <10s <10s <10s <10s Input power (W) 150 150 150 150 150 CC: Closing coil TC: Trip coil V1~V4: Rectitier KO: Anti-pumping relay (optional) BC: Electromagnet for locking (optional) ZC: Electomagnet for locking truck (optional)

S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor

Spare Parts

AC110

Motor Characteristics
Rated voltage (V) DC125 DC110 DC220 AC110 AC220 Normal operation voltage scope 85%~110% 85%~110% 85%~110% 85%~110% 85%~110%

46

47

Spare Parts

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Internal wiring diagram (AC) 27kV


Spring Charge Motor
26 24 25

Component
Breaker Interlock Circuit
52

Closing Circuit
10

Opening Circuit
30 6 3 5 7 9 23 27 28 29 8

Truck Interlock Circuit


1

V2

V4

V3

V1

K0 (13) (14)

CC TC S2 S4 BC (73) (74) S5 (11) (12) S5 91 92 31 32 41 42 71 72 61 62 63 64 23 24 33 34 83 84 93 94


V5 A~ C+ BY4 1
ZC 2

M
(51) (52) (53) S5 (5) (3)

D~

(54) S5 K0 (2)

S5

(21) (22) S3

(13) (14) S3

(21) (22) S1

43 44

S8

43 44

S9

Current Transformer
31 32 16 13 15 17 19 33 37 38 39 18 40

Ground Fault Sensing CT


It is of the type insulated in resin and is used to supply measurement and protection devices. These CTs can be furnished in either a solid or split core design. They can be used either for measuring phase currents or for detecting the earth fault current. They conform to the IEC 60044-1 Standards. CT type: LMZC

Voltage Transformer
Voltage transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture. It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes. 17.5kV VT type: JDZ17-15A 27kV VT type: JDZ11-25 JDZX11-25E Fuse type: JDZX15-25R

36

34

35

20

53

54

Current transformers are cast in resin, and totally enclosed. This provides superior protection against pollutants and moisture.

11

47

57

55

It can be equipped with one or more independent magnetic cores with equal or different characteristics for measuring, metering and protection purposes. Current 1250A the CT type is LZZB-17

13 14 S9

33 34 S9

23 24 S9

53 54 S9

13 14 S8

33 34 S8

23 24 S8

53 54 S8

150A1 or A4 Current > 1250A the CT type is LMZB1-17

21 22

43 S5 44 S5

13 14 S5

81 82 S5

Recommended CT
21 22 51 50 12 14 48 49 58 56

Primary Current

Type

Ratio
500/5A 500/1A

Accuracy Class
0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s 0.5 or 0.5s 0.2 or 0.2s 0.5 or 0.5s 0.2 or0.2s

Protection Class
5P or 10P 5P or 10P 5P or 10P

JDZX11-15C Fuse type: XRNP 17.5/1A

S9: Limit switch (working position) S8: Limit switch (testing position) S5: Auxiliary switch

CC: Closing coil TC: Trip coil V1~V4: Rectitier

KO: Anti-pumping relay (optional) BC: Electromagnet for locking (optional) ZC: Electomagnet for locking truck (optional)
50A 25kA/3s LZZB-17 500

S4: Electromagnet for locking's auxiliary switch M: Spring Charge Motor S1~S3: Energy storing travel switch

500-250/5A 500-250/1A 1000/5A 1000/1A 1000A 25kA/3s LZZB-17 1000 1000-500/5A 1000-500/1A 3000/5A 3000/1A 3000A 25kA/3s LZZB-17 3000 3000-1500/5A 3000-1500/1A

Spare Parts

Note: 1. This wiring diagram describes that a breaker is open, racked to test position with spring in discharge state. 2. The polarity in dashed frame should be connected to common DC voltage terminal. 3. Rectifier will be removed if DC is applied.

5P or 10P 5P or 10P 5P or 10P 5P or 10P 5P or 10P 5P or 10P 5P or 10P 5P or 10P

48

49

Spare Parts

5P or 10P

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Cable Connection
The cable compartment contains current transformers, voltage transformers (fixed), withdrawable, and earthing switch, depending on the individual operating requirements. The cable compartment is constructed for installation of three current transformers. When all the three current transformers are not required, dummies can be installed in their place to maintain the same installation and connection procedures. The fixed voltage transformers (optional) are connected on the primary side with busbar and fitted with HRC fuses. The earthing switch can be operated by manual, with position indicated by mechanical indicator on the driveshaft and the auxiliary switch. Three surge arrestor (optional) can be mounted in the space available.
7.2/12/15/17.5 Rated voltage (kV) Panel width (mm) 650 800 1000 Max. number of parallel cables per Phase 6 6 6 630 35-54 27-62 Max. cross section of cables (mm2) Range of cable clamp (mm) Range of reducer ring (mm)

Voltage Transformer Truck


The withdrawable trucks also allow replacement of the fuses with the switchboard in service. Truck rackingout with the door closed automatically operates closure of a metallic segregation shutter between the live parts of the switchgear and the instrument compartment. The earthing switch can be operated from the front of the switchgear. It is mechanically interlocked with the circuit breaker truck so that the earthing switch can only be operated when the circuit breaker is open in the Test/Disconnect position as well. The switch is also mechanically interlocked with the cable compartment for additional safety.

Earthing Switch

Earthing switch characteristics


Specification Rated voltage Rated Work frequency withstand voltage (1min) in open condition of switch Rated Lighting impulse withstand voltage (peak value) in open condition of switch Rated short-time withstand current (3s) Rated peak value withstand current Rated short circuit making current Centre distance between phases Electric endurance class Mechanical endurance Unit kV kV kVp kA kAp kAp mm Times 7.2/12/15/17.5 20/28/36/38 60/75/95/95 31.5 82 82 170 E1 2000 Data 24 50 125 31.5 82 82 170 E1 2000 27

Operation Tool
Gear door locks key Rack handle for truck Earthing switch handle

Spare Parts

125

50

51

Spare Parts

65

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Installation Guide
In order to obtain an optimum installation sequence and ensure high quality standards, site installation of the switchgear should only be carried out by specially trained personnel, or supervised and monitored by qualified personnel, or by personnel supervised and monitored by responsible persons. On commencement of installation on site, the switch-room must be fundamentally finished, provided with lighting and the electricity supply, lockable, dry and with facilities for ventilation, It is also required that the basic frame and indoor ground of substation should be checked and accepted before the construction, It must be ensure that the ceiling height is sufficient for the opening travel of the pressure relief plates and clearance for exhaust. Tolerances for laying the floor frame are: Evenness tolerance: 1mm within a measuring length of 1m, Straightness tolerance: 1mm per 1m, but not more than 3mm over entire length of frame.

Panel layout for switchgear arrangement

Power Cable Duct

SecoGear P/V

Control Cable Duct 1200 n*650/800/1000 1200

Control Cable Duct

Installation guide

2500

1500

800

SecoGear P/V

Installation Guide
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

52

800

Power Cable Duct

53

Installation guide

1500

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Switch room cable duct arrangement


17.5kV 27kV
600

400

250

800

Power Cable Duct

800 70 800 70 30 1800 150 30 1800 150

Power Cable Duct 70

1400

760

1400

40

150

1360

Basic Frame

Basic Frame 1800 1700

280 210

Control Cable Duct

250 30

800/1000 550 250 800 Power Cable Duct 800 70

1400

760

280 210

1360

Basic Frame

1400

40

150

Power Cable Duct

Basic Frame 1800 Control Cable Duct 750 250 800/1000 800 Power Cable Duct 70 250 30 150 1700

Installation guide

280 210

1360

Basic Frame

Control Cable Duct

54

250 30

55

Installation guide

1400

760

1400

40

SecoGear 3.3kV-27kV Air Insulated Switchgear

SecoGear 3.3kV-27kV Air Insulated Switchgear

Cross section view of switchgear room layout


17.5kV

Detail of switchgear cable access cutout


17.5kV
1400 1330 350 30

2200

800 70

1500 1400 30

614x28
Top Curface of basic frame 3~5mm above ground

Basic Frame 150 280 380 0.0m -0.25m Strap of control cable duct Figured steel plate (t=5mm)

200

70

Control Cable Duct 250*250 800 Power Cable Duct 800*1000 300 760

Width A B C

650 400 470

800 550 620

1000 750 820

650 Power Cable

545 Control Cable

27kV 27kV

1800 1700

2400

800 70

1900 1800 30

4-15x20

Top Curface of basic frame 3~5mm above ground


A

Basic Frame

140

250

130

+5.0m

Installation guide

70

Strap of control cable duct Figured steel plate (t=5mm) 1200


144 358 Power Cable Control Cable 190 130

Control Cable Duct 250*250

800 Power Cable Duct 800*1000

290

800

Width A B C

800 600 595

1000 800 695

56

57

Installation guide

300

54

You may be interested in other MV Seco-family products


For more information, please visit www.geindustrial.com

GE Energy

Greater China
Shanghai
4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech Park Shanghai, China 201203 T : +86 21 3877 7888 F : +86 21 3877 7600

Taiwan
6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480 T : +886 2 2183 7000 F : +886 2 2516 6829

South East Aisa


Malaysia
Level 6, 1 Sentral, Jalan Travers, Kuala Lumpur Sentral Kuala Lumpur, Malaysia 50470 T : +603 2273 9788 F : +603 2273 7988

Philippines
8F Net Cube Building, 30th Street Corner 3rd Avenue, Crescent West Park Global City Taguig 1634 T : +63 2 877 7000 F : +63 2 846 0629

Indonesia
BRI II Tower, 27th floor Jl. Jend. Sudirman No. 44-46 Jakarta 10210 T: +62 21 573 0430 F: +62 21 574 7089

Thailand
25th floor, CRC Tower, All Seasons Place 87/2 Wireless Road, Lumpini Pathumwan, Bangkok 10330 T : +66 2 648 0202 F : +66 2 648 0200

Vietnam
Saigon Centre, Unit 1, Floor 7 Le Loi Boulevard, District 1 HoChiMinh City T : +84 8 3914 6700 F : +84 8 3827 8229

Singapore
240 Tanjong Pagar Road #06-00 GE Tower Singapore 088540 T : +65 6220 7022 F : +65 6326 3015

ANZ

Australia
125-127 Long Street Smithfield, Sydney, NSW 2164 T : +61 2 8788 6911 F : +61 2 8788 7224

New Zealand
Level 1, 8 Tangihua Street Auckland, North Island T : +64 9 353 6706 F : +64 9 353 6707

North Asia
Japan
11F, Akasaka Park Bldg.,5-2-20 Akasaka, Minato-ku Tokyo 107-6111 T : +81 3 3588 5288 F : +81 3 3585 3010

Korea
3rd Floor, GE Tower, 71-3, Cheongdam-dong, Gangnam-gu Seoul, Korea 135-100 T : +82 2 6201 4501 F : +82 2 6201 4344

For more information, please visit www.geindustrial.com


Printing Code: IN201202B29EN Copyright GE Industrial Solutions 2012

Das könnte Ihnen auch gefallen