Almost all power system analyses are performed in perunits x ( engr. unit )
x per unit ( pu ) =
engineering ( actual )
x% = 100
I Lbase =
S3 base 3 VLLbase
S1 base
Z base
S3 base
Z old pu Z
new pu
new Z pu
(V )
( V )
S
old pu
=Z
old pu
S S
V V
new pu
=Z
old pu
The per-unit impedance, voltages, and currents of transformers are the same regardless of whether they are referred to the primary or the secondary side.
Different voltage levels disappear across the entire system. The system reduces to a system of simple impedances
The circuit laws are valid in per-unit systems, and the power and voltages equations are simplified since the factors of 3 and 3 are eliminated in the per-unit system
Power Systems I
Generador Transformador 100 MVA 100 MVA 22 kV 22:110 kV X=90% X=10% Lnea de transmisin Z = j60.5 ohms
Transformador 100 MVA Generador 120:24 kV 80 MVA X=12.6% 22 kV X=1.48 pu Lnea de transmisin X = 60.5 ohms
2. 3. 4.
5.
Seleccionar una base general de potencia, p. ej. 100 MVA Definir voltajes base por zonas (definidas por los transformadores) Convertir todas las impedancias a p.u. Si las bases de los equipos no son las del sistema Convertir las impedancias a Evaluar el nuevo valor de la impedancia en p.u. Dibujar el diagrama de impedancias en p.u.
1
Identificar los circuitos existentes de acuerdo a los diferentes niveles de voltaje. Guiarse utilizando los transformadores
Definicin de Bases
Seleccin de la primera base de voltaje.
Para este ejemplo se selecciona una base de 110 kV en alta tensin.
Lnea de transmisin Z = j0.8403 pu @ 120 kV y 50 MVA
Definicin de Bases
Seleccin de bases en los tres circuitos de acuerdo a la relacin de transformacin
Sbase = 100 MVA Vbase = 110 kV
22:110 kV
120:24 kV
La potencia base es igual en todo el sistema Los voltajes base cambian de acuerdo a la relacin de transformacin nominal
Clculo de las impedancias de los elementos en p.u. de la base nueva Lado del generador 1
Generador : (0.9 pu placa Z base generador ) = Z generador X g1 = Z base sistema Z base sistema (22kV ) 2 0 . 9 pu placa 100 MVA = 0.9 pu X g1 = sistema 2 (22kV ) 100 MVA Transformador : (0.1pu placa Z basetransf ) = Z transf X t1 = Z base sistema Z base sistema (22kV ) 2 0 . 1 pu placa 100MVA = 0.1 pu X t1 = sistema 2 (22kV ) 100 MVA
Estos clculos no son estrictamente necesarios porque: la base del generador corresponde a la base del sistema la base del transformador corresponde a la base del sistema
5
Clculo de las impedancias de los elementos en p.u. de la base nueva Lneas y carga
Lnea superior :
Z L = jX L =
( j 0.8403
pu placa
Z base linea )
Z base sistema
(120kV ) 2 j 0.8403 pu placa 50MVA = j 242 = j 2 pu = sistema 2 (110kV ) 2 (110kV ) 100 MVA 100MVA
Lneas inferiores : Z linea j 60.5 Z L = jX L = = = j 0.5 pu sistema Z base sistema (110kV ) 2 100 MVA
Carga : Z carga Z base sistema (110kV ) 2 10 MVA 0 = = 100 pu sistema (110kV ) 2 100 MVA
Z L = jX L =
Clculo de las impedancias de los elementos en p.u. de la base nueva Lado del generador 2
Sbase = 100 MVA Vbase = 22 kV
Generador : X g2 =
(1.48
pu placa
Z base generador )
2
Z base sistema
X g2
Transformador : Xt2 =
(0.126
pu placa
Z base transf )
2
Z base sistema
(24kV ) 0.126 pu placa 100MVA = 0.15 pu Xt2 = sistema (22kV ) 2 100 MVA
7
Anlisis de Nodos
Lo anterior nos da el siguiente diagrama de impedancias en por unidad de una base comn:
z13=j2 p.u. zg1=j0.9 zt1=j0.1 zt2=j0.15
zg2=j1.85 5
+ V3= -j1 p.u. -
1
z12=j0.5 p.u.
3 2
z23=j0.5 p.u.
4
+ V1= 1 p.u. -
z2=10 p.u.
Los voltajes de las fuentes son supuestos y pueden variar, pero el diagrama de impedancias se conserva
zgt1=j 1 1
z12=j0.5 p.u.
+ V1= 1 p.u. -
zgt2=j2 3
z2=10 p.u.
z13=j2 1 I1= -j1 pu z1=j1 z=10 z3=j2 I3= -0.5 pu 8 z12=j0.5 2 z23=j0.5 3
G T1 L1 T2 T3 L2 T4
Ld