This describes the monitoring port for the door status sensor. This port is a dry contact point Boolean signal monitoring port and suitable for a bare terminal of a cable (24 AWG - 12 AWG). For the position of the monitoring port for the door status sensor, see Appearance of the EMUA. Figure 1 shows this port. Figure 1 Monitoring port for the door status sensor
Table 1 lists the meanings of the terminals of the monitoring port for the door status sensor. Table 1 Meanings of the terminals of the monitoring port for the door status sensor Silkscreen 12VG Meaning Positive input terminal for door status monitoring signals Negative input terminal for door status monitoring signals
GATE
NOTE: You can set bit 4 of the DIP switch SW_BKE to choose whether to use the monitoring port for the door status sensor. For details, see Internal Structure of the EMUA.
(1) Indicator
(1) Indicator
NOTE: The grounding screw of the EMUA of type B is on the rear panel.
(1) Indicator
Board Layout
Figure 1 shows the board layout inside the EMUA of type A or B. Figure 1 Board layout inside the EMUA of type A or B
Figure 2 shows the board layout inside the EMUA of type C. Figure 2 Board layout inside the EMUA of type C
DIP Switches
Table 1 lists the functions and settings of the DIP switches on the panel of the EMUA. Table 1 Functions and settings of the DIP switches on the panel of the EMUA
Silkscreen SW_ADDR
Setting If a DIP switch bit is set to ON, it represents 0. If a DIP switch bit is set to OFF, it represents 1. The settings of the DIP switch SW_ADDR (1234) are as follows: Outdoor CDMA BTS: 0000 Indoor CDMA BTS or non-doubledensity GSM BTS: 0001 Double-density GSM BTS, WCDMA NodeB or LTE eNodeB: 0010 CAUTION: If an EMUA is delivered along with the BTS/NodeB, the communication protocol is already configured according to the BTS/NodeB type. If an EMUA is delivered independently, the default setting of the DIP switch SW_ADDR (1234) is 0010. This bit is set to ON if a sensor is not used. This bit is set to OFF if a sensor is used.
SW_BKE
This bit is set to ON no matter whether a sensor is used. This bit is set to ON if a sensor is not used. This bit is set to OFF if a sensor is used. This bit is set to ON if a sensor is used. This bit is set to OFF if a sensor is not used. This bit is set to ON if a sensor is used. This bit is set to OFF if a sensor is not used. This bit is set to ON if a sensor is used. This bit is set to OFF if a sensor is not used.
SW_THE
SW_AE
Each bit corresponds to an analog sensor. This bit is set to ON if a sensor is used. This bit is set to OFF if a sensor is not used. Each bit corresponds to an analog sensor. This bit is set to ON if a current-type
SW_AV
Table 1 Functions and settings of the DIP switches on the panel of the EMUA Silkscreen Function SW12A, SW12B, SW24A, SW24B Thirty-two bits for Boolean signal input Setting sensor is used. This bit is set to OFF if a voltage-type sensor is used. Bits 1-8 of the DIP switch SW12A correspond to input signals 1-8. Bits 1-8 of the DIP switch SW12B correspond to input signals 9-16. Bits 1-8 of the DIP switch SW24A correspond to input signals 17-24. Bits 1-8 of the DIP switch SW24B correspond to input signals 25-32. When a bit is set to ON, it represents high-level alarms. When a bit is set to OFF, it represents low-level alarms or is not used.