200/300/400 watts (680/1,025/1,360 BTUs)

Lil Chill LC Series Dual Mode Water Chillers


Ideal for Demanding Laser, Medical, Industrial & Electronics Applications

PROCESS RECIRCULATING WATER CHILLERS W/AIR-COOLED CONDENSERS K-O Concepts Models LC-2, LC-3 & LC-4 FEATURES
Easy to Service and Maintain Order spare parts and assemblies from the Thomas Register Order Online program at www.thomasregister.com. Chillers are designed for easy service and maintenance. Convenient process water fill and drain features on all models. Panel-mounted air filter for ease of service. Options include quick disconnect fittings, particle filter, deionizer cartridge, DI water monitor, and umbilical assembly to protect coolant lines. Free-Standing Cabinet w/Locking Casters All models: 9.9 H x 10.0 W x 20.1 D inches (cabinet dimensions) Height w/Casters: 12.0 inches Extremely Light Weight From 33 lb. /15 kg. Quality Components and Construction K-O Concepts combines quality design, components and construction to provide a user friendly, reliable, cooling instrument. State-of-the-Art Technology K-O Concepts uses the latest in refrigeration technology to supply unparalleled performance and package size for your recirculating chiller requirements. Dual Mode Chiller Operation K-O Concepts chiller modules incorporate a unique dual mode operation. This design allows the system compressor to be unloaded without the use of hot gas bypass. Continuous Run Compressor System compressor is operated in a continuous run mode for optimum reliability and accurate control of the process coolant temperature. Stainless Steel Heat Exchangers All models equipped with grade 316 stainless steel heat exchangers for high purity applications. Brazed plate design offers optimum heat transfer efficiency with minimum size and weight. Process Water Pumps A variety of positive displacement and centrifugal water pump options accommodate a wide range of flow and pressure requirements. Accurate Process Water Temperature Control Standard digital P ID controller accurately maintains the desired process water temperature. Optional Deionized (DI) Water Package Includes nickel brazed heat exchanger, rear panel mounted DI cartridge assembly, and upgraded 316 stainless steel fittings. Easy service to the DI cartridge is accomplished from the rear panel.
Page 2 of 4

PROCESS WATER CHILLER SPECIFICATIONS K-O Concepts Models LC-2, LC-3, LC-4
Cooling Capacities (LC-2 / -3 / -4) Process Coolant Temperature Range Process Coolant Note: Coolant additives available. Process Coolant Tank Capacity Environment Temperature Controller Temperature Stability Note: Temperature Stability Performance Requires a Stable Heat Load. Heat Exchanger Note: All units feature brazed plate design. Heat Dissipation Condenser Fan Refrigerant Process Water Pump Note: Performance shown is @ 60 Hz. 50 Hz performance provided upon request. Input Power Requirements Circuit Breaker Air Filter 200 / 300 / 400 watts (680 / 1,025 / 1,360 BTUs) See Notes below for additional explanation. 5-45C / 41-113F Standard Feature: Demineralized (distilled) water Optional Feature: Deionized (DI) water 26 oz. / 0.8 liters Indoor operation only with unrestricted ambient air required from 5-30C / 41-86F. Standard feature: Digital (PID) controller Digital controller stability w/ thermocouple sensor: 0.5C typical

Dimensions (H x W x D) Weight Electrical Interface Signals Note: All interface signals are contact closures except process water alarm. Process Coolant Connections Process Coolant Fill / Drain Feature Optional Process Coolant Umbilical

Optional 15 micron Particle Filter Optional Deionizer Package Optional Deionized (DI) Water Monitor

Standard Feature: Grade 316 stainless steel, copper brazed Optional Feature: Grade 316 stainless steel, nickel brazed To air (air-cooled) Note: Air intakes from front and exhausts from rear of cabinet. Standard Feature: Rear panel mounted condenser fan assembly for ease of service (all models). R134a / CFC- Free (all models) Standard Feature: Model MD-6 pump is a sealless magnetic drive design and is compatible with deionized D I water. Optional Feature: Other pumps available upon request. Standard Feature: 115 VAC / 60 Hz / 1 (all models). Optional Feature: 220 VAC / 50-60 Hz / 1 (all models). DPST circuit breaker is located on the back panel. Standard Feature: Front panel mounted air filter assembly for ease of service. Assures long term peak performance of condenser coil (all models). All Models: 9.9 x 10.0 x 20.1 inches (cabinet dimensions) Height w/Casters: 12.0 inches From 33 lb. / 15 kg. (dry weight) Signals (N.O. in failed condition): Process water flow, process water level, and compressor over temperature warning. Process water alarm is a solid state relay output (5VDC). Signals reported via (DA 15P) connector on back panel. Standard: 3/8 inch FPT Optional: Quick disconnect fittings Coolant F ill access via plug located on top panel. Coolant D rain access via port located on underside of unit. 8 ft. L x 1-1/4 inch umbilical w/2ea. 1/2 inch OD process coolant lines offered on all models. The umbilical is mounted to a bracket located on the rear of the chiller unit. Easy service particle filter cartridge located on back panel. Service with module installed into cabinet. Materials upgraded for deionized (DI) water compatibility. Includes easy service deionizer cartridge located on back panel. Provides contact closure signal to interface connector when DI cartridge requires maintenance.

Notes: Data shown is with 30C / 86F (unrestricted) ambient air. Cooling capacity ratings are with process coolant @ 20C / 68F. See Thermal Performance chart for cooling capacities at other process temperatures. Specifications are subject to change without notice.

Page 3 of 4

PROCESS WATER CHILLER PERFORMANCE DATA K-O Concepts Models LC-2, LC-3, LC-4
THERMAL PERFORMANCE PROCESS WATER PUMP PERFORMANCE

Cooling Capacity % of Rating vs. Process Temperature


125 100 75 50 25 0 5 (41) 10 (50) 15 (59) 20 (68) 25 (77) 30 (86)

% of Rated Capacity

Process Temperature, C (F) 60 Hz 50 Hz

FEATURES & DIMENSIONS (All Models)


TOP VIEW
OPTIONAL UMBILICAL SIGNAL INTERFACE CONNECTOR (DEM-15S) PROCESS COOLANT FILL (REMOVABLE PLUG) SWITCH (DPST BREAKER) AC POWER OPTIONAL SENSOR OUTPUT (THERMOCOUPLE/RTD) FAN POWER CORD WITH DISCONNECT

BACK VIEW
PROCESS COOLANT SUPPLY/RETURN 2X FITTING (3/8 FPT)

AIR EXHAUST (CONDENSER FAN)

4X LOCKING CASTERS

LEFT SIDE
22.1 20.1 18.7

DIGITAL (PID) TEMPERATURE CONTROLLER (STANDARD FEATURE)

FRONT VIEW
CONTROL SWITCHES

9.9 12.0

AIR INTAKE (AIR FILTER)

PROCESS COOLANT DRAIN

10.00

K-O Concepts, Incorporated 21 North Texas Ave., Suite A Orlando, Florida 32805 Phone: 407/296-7788 Fax: 407/296-4696 E-Mail: Sales@K-OConcepts Web: www.K-OConcepts.com

Chillers & Cooling Modules Catalog & Custom


70252200 Rev A Page 4 of 4 09-01