HV Diagnostics Sarl is a Swiss based company in the field of high voltage test equipment for cable testing and diagnosis.
Company
AUSTRIA
Products
Universal High Voltage Test System HVA-Series Tan Delta Test System TD-Series Partial Discharge Detection and Location for MV Cables PD-Series
complete cable failure is normally imminent and inevitable. A single water tree which converts to an electrical tree is causing a cable to fail!
conductance in a cable.
VLF Testing
Standards IEEE 400 & IEEE 400:2 Revised 2001 (USA) IEC 60060-3 (Europe & International) CENERLEC HD 620 & 621 (Europe & International) VDE 0276 Part 620 SANS 10198 (South Africa) NEN3620/C1 ( Nederland)
VLF Testing
VLF 0,1Hz Voltage Testing according DIN VDE 0276 (HD 620 S1)
Voltage 5,6 8 U0 2 U0 3 U0 2 U0 3 U0
VLF Testing
Advantage Disadvantage not 50Hz but Sinusoidal Waveform 0.1Hz Stresses both resistivity R and impedance R, L and C Higher breakdown strength than 50Hz Tan Delta measurements possible Partial discharge measurements possible Stress lines similar to 50Hz on cable, terminations & joints. Sinusoidal is symmetrical under any load (electronically generated)
HVA 30
Universal High Voltage Test System
Output Voltage Sinusoidal: 0-33 kV peak, 23kV RMS DC : 0-30 kV (both polarities) Square-Wave: 0-30kV Output Current 15mA Frequency 0,01Hz to 0,1Hz Load 0,5F @ 0,1Hz @ 23kV RMS 12F Maximum Capacitance!
HVA 30
Universal High Voltage Test System
Auto Frequency Selection AC (VLF) Symmetrical and load independent across full range Fast Trip Out and Fault Conditioning Burn Modes Programmable Fully Automatic Test Sequences Less than 20kg
HVA 30
Universal High Voltage Test System
Battery (optional) Build-in 12kV Feedback Protection! PC Software HVA Control Center No thermal limitation for operating time Less maintainance no oil used
HVA 60
Universal High Voltage Test System
Output Voltage Sinusoidal: 0-62 kV peak, 44kV RMS DC : 0-60 kV (both polarities) Square-Wave: 0-60kV Output Current 37mA Frequency 0,01Hz to 0,1Hz Load 1F @ 0,1Hz @ 44kV RMS 5F @ 0,02Hz @ 44kV RMS 15F Maximum Capacitance
HIGH VOLTAGE DIAGNOSTICS SARL
HVA 90
Universal High Voltage Test System
Output Voltage Sinusoidal: 0-90 kV peak, 64kV RMS DC : 0-90 kV (both polarities) Square-Wave: 0-90kV Output Current 40mA Frequency 0,01Hz to 0,1Hz Load 1F @ 0,1Hz @ 64kV RMS 10F @ 0,01Hz @ 64kV RMS 11F Maximum Capacitance
HIGH VOLTAGE DIAGNOSTICS SARL
HVA Series
The load independent, symmetrical output waveform avoids the potentially destructive space charge effects caused by DC polarization that occurs in aged extruded cables such as XLPE / PE / EPR. The instrument automatically calculates the optimum frequency to energize larger loads (longer cables). The instrument is easily programmable allowing the operator to setup or select test sequences in either automatic or manual mode.
HVA Series
I Capacitive IC ITOTAL
IR
V (applied)
The HVA measures the real time output wave and digitize the information (Digital Signal Processor). Therefore it is possible to measure not only the RMS leakage current but also the Capacitive current (capacitance is displayed) AND the resistive current (Megohm reading).
HVA Series
Example: HVA60 Output Load 1.0 F @ 0.1 Hz @ 44kV RMS (Approx 3 km of cable) 2.0 F @ 0.05 Hz @ 44kV RMS (Approx 6 km of cable) 5.0 F @ 0.02 Hz @ 44kV RMS (Approx 15 km of cable) Maximum Capacitance 10F
Based on a typical cable: 330nF/km
3,030085 km
HVA Series
Applications
Cables: XLPE, PE, EPR, PILC etc. such as IEEE 400.2, VDE 0276, CENELEC HD 620 S1, the present draft of IEC 60060-3, etc. Capacitors Switchgear Transformers Rotating Machines (IEEE 433) Insulators Bushings
DIAGNOSTICS
TAN DELTA Test System
Easy method to diagnose the condition of the cable isolation Non destructive method A method to diagnose Water Trees Preventive maintenance scheduling of repair and replacement
Preventive maintenance
DIAGNOSTICS
TAN DELTA Test System
A cable is a large capacitor. IC is very large IR is very small
TD = Tan Delta ( ) = True Power Capacitive Reactive Power = U2/R U2 C = 1 XLPE = 1.2 x 10-3 CR PILC = 50 X 10-3
DIAGNOSTICS
TAN DELTA Test System
Conventional System:
DIAGNOSTICS
TAN DELTA Test System
DIAGNOSTICS
TAN DELTA Test System
TD30/TD60
TAN DELTA Test System
Input Voltage TD30 1 23 kV RMS TD60 1-44kV RMS 2 CType Batteries (10hours) Tan Delta Resolution: 1 x 10-5 Accuracy: 1 x 10-4 (load > 15nF) Frequency 0,1Hz Load Standard 15nF to 5F (minimum 1A RMS)
TD30/TD60
TAN DELTA Test System
3kg only! (TD60 5kg) Comprehensive Computer software TD Control Center BluetoothTM Dongle Visual indication of TD Levels No complicated wiring, easy set-up!
TD30/TD60
TAN DELTA Test System
HVA TD Systems fits directly into the HVA Series of Generators TD Measurement and Pressure Testing at the same time No need for separate fibre optics for data transmission Ultra small size and light weight TD system (3kg for TD30 and 5kg for TD60) Standard Bluetooth built in for easy setup on computers running Microsoft Windows Complete PC based Reporting and Storage Software included
TD30/TD60
TD Control Center
TD30/TD60
TD Control Center
SMART VLF
with Tan Delta
Diagnose your existing network quick and easy Make a fingerprint of your new installations or maintenance work as a future reference
DSO graph
PD30/60/90
TDR signature PD Amplitude & Location
LOC graph
Coupling Capacitor
PD discharge meter