Beruflich Dokumente
Kultur Dokumente
LSIS PLC/Drive
www.lsis.biz
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 Diagnosis
Configuration
RS-485 (Modbus communication) Baud rate: 9600, Data bit: 8, Stop bit: 1, Parity bit: None
Note that baud rate and stop/parity bit are selectable in I/O group. * I/O group: I61 baud rate, I65: parity/stop bit setting.
Wiring Diagram
+ S+ SS+ S-
iG5A Station: 1
iG5A Station: 2
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 Diagnosis Set up each drive communication-concerning parameter as follows. For iG5A (station: 1) * DRV-03 [Drive mode]: 3 [RS-485] * DRV-04 [Freq. mode]: 7 [RS-485] * I/O 59 [Communication protocol]: 0 [Modbus RTU] * I/O 60 [VFD station number]: 1 * I/O 61 [communication speed]: 3 (9600bps) For iG5A (station: 2) * DRV-03 [Drive mode]: 3 [RS-485] * DRV-04 [Freq. mode]: 7 [RS-485] * I/O 59 [communication protocol]: 0 [Modbus RTU] * I/O 60 [VFD station number]: 1 * I/O 61 [communication speed]: 3 (9600bps)
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - XGB Setup XG5000 Diagnosis Double click
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - P2P XG5000 Diagnosis Double click
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - P2P XG5000 Diagnosis Double click
Slave address
Click
Conditional flag: M0000 This request frame is sent from XGB at M0 bit rising edge. Data type/Data size This request frame is to write 4 word data to iG5A.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - P2P XG5000 Diagnosis
Modbus corresponding addresses of iG5A are acquired by the following formula. [Modbus address] = [iG5A address] 1 Modbus word output area is from 0x40000. Therefore, [0x0005] is to be [0x40004]. Here D0000 is assigned to 0x40004, which means D0 data value is sent to ref. Freq. area. In the previous slide, 4 words are to be sent. Therefore, D0 for Reference Frequency D1 for Run command (D1.0 bit is on iG5A stop; D1.1 bit is on iG5A forward run, etc). D2 for ACC time D3 for DEC time
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - P2P XG5000 Diagnosis Slave address Click
Conditional flag: M0001 This request frame is sent from XGB at M1 bit rising edge. Data type/Data size This request frame is to read 8 word data from iG5A. Note that data size should be less than or equal to 8. If not, iG5A does not respond properly.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - P2P XG5000 Diagnosis
Modbus word input area is from 0x30000. Therefore, [0x0007] to be [0x30006]. Here D0020 is assigned to 0x30006, which means ACC time is sent to D20. In the previous slide, 8 words to be sent from drive to XGB. Therefore, D20 for ACC time; D21 for DEC time, D22 for Output Current; D23 for Reference Frequency; D24 for Output voltage; D25 for DC Link voltage; D26 for Output power; D27 for drive status (D27.0 bit is on iG5A stop; D27.1 bit is on iG5A forward run, etc).
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - P2P XG5000 Diagnosis Slave address Click
Conditional flag: M0002 This request frame is sent from XGB during M2 bit rising edge. Data type/Data size This request frame is to write 4 word data to iG5A. Data assignment method: the same as iG5A (station 1) D100 for Reference Frequency D101 for Run command (D1.0 bit is on iG5A stop; D1.1 bit is on iG5A forward run, etc). D102 for ACC time D103 for DEC time
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - P2P XG5000 Diagnosis Slave address Click
Conditional flag: M0003 This request frame is sent from XGB during M3 bit rising edge. Data type/Data size This request frame is to read 8 word data from drive to XGB. Data assignment method: the same as iG5A (station 1) D120 for ACC time; D121 for DEC time, D122 for Output Current; D123 for Reference Frequency; D124 for Output voltage; D125 for DC Link voltage; D126 for Output power; D27 for drive status (D27.0 bit is on iG5A stop; D27.1 bit is on iG5A forward run, etc).
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD - Down & Link XG5000 Diagnosis
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Programming Diagnosis
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Programming Diagnosis
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Programming Diagnosis
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Programming Diagnosis
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Programming Diagnosis
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Monitoring Diagnosis
iG5A (#1) Control: Set Ref. Freq. and make it run forward
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Monitoring Diagnosis
iG5A reference frequency is set as 12.34Hz. Its status is FWD Run. ACC and DEC time is set as 1.0 and 2.0 sec, respectively. Now lets monitor iG5A.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Monitoring Diagnosis
iG5A is running as we set in the previous slide. D27.1 bit means its operation status is FWD Run.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Monitoring Diagnosis
iG5A (#2) Control: Ref. Freq., Operation command and ACC/DEC time
Station 2 reference frequency: 43.21Hz Station 2 operation command: Reverse running Station 2 ACC time: 3.0 sec Station 2 DEC time: 4.0 sec
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Monitoring Diagnosis
iG5A is running as we set in the previous slide. D27.1 bit means its operation status is REV Run.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Monitoring Diagnosis
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 - Monitoring Diagnosis
When station 1 is turned off or disconnected from network, its error flags are increased. After the problem is recovered, error-concerned flags are not increased but hold their values. Note that L relay is latched.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 Diagnosis Right-mouse click
Select [Channel 2] and click [Start] then you will see its communication frame. Even though XGB has no RTC, but it shows time stamp when the transmission/reception frame pass through the comm. port. This is important because in 1:N comm. In RS-485 (half-duplex) system, transmission and reception frame should be interlocked. And a user could know the best possible conditional flag to send each frame by this time stamp.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD 3 XG5000 4 Diagnosis
(1) If there is unknown in Result, the frame is wrong. (2) It shows when each frame passes through the communication port. (3) When the transmission frame is sent to iG5A (station 1) at 0:00:02:770 (2.770sec after monitoring start), the reception frame is delivered to XGB from station 1 after 0.03sec later. (4) It shows one cycle in this system composed of 8 frames. Write request to #1 (M0 bit ) Write response from #1 Read request to #1 (M1 bit ) Read response from #1 Write request to #2 (M2 bit ) Write response from #2 Read request to #2 (M3 bit ) Read response from #2 Note that every transmission frame is sent with 200ms period.
Application Solution
Communication with VFD (Variable Frequency Drive)
Configuration Drive Setup XG-PD XG5000 Diagnosis Right-mouse click
Select [P2P Service] and click [Multiple Reading] then you will see comm. status. Whenever an communication error occurs, its error count will increase.