Regional Headquarters Authorized Distributor: OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands Tel:(31)2356-81-300/Fax:(31)2356-81-388 OMRON ELECTRONICS LLC 1 East Commerce Drive, Schaumburg, IL 60173 U.S.A. Tel:(1)847-843-7900/Fax:(1)847-843-8568 OMRON IDM Controls 9510 North Houston, Tx. 77088 U.S.A. Tel: (1)800-395-4106/Fax: (1)713-849-4666 OMRON ASIA PACIFIC PTE. LTD. 83 Clemenceau Avenue, #11-01, UE Square, Singapore 239920 Note: Specifications subject to change without notice. Tel:(65)6835-3011/Fax: (65)6835-2711

Cat.No.I905-E1-05 Printed in Japan 0204-1M

Downloaded from www.Manualslib.com manuals search engine

Contents
Features Applications Nomenclature Using Digital Operator
The frequency adjuster on the front panel makes it possible to easily adjust the speed of the motor. The Inverter can be operated immediately after the power is turned ON.

2 4 6 8 11 14 22 27 28 29 34 47

List of Parameters Function of Each Parameter Specifications Dimensions Standard Connections Protective and Diagnostic Functions Options Inverter Models

There has been a great demand for inverters that provide easier motor speed control. OMRON's simple, compact 3G3JV Series meets the demand. The 3G3JV Inverters provide versatile functions and ensure powerful performance. The front panel of the 3G3JV Inverter has a frequency adjuster that makes it possible to start the motor and easily control the motor speed. The 3G3JV Inverters are easy to mount and operate and support a wide range of applications for efficient motor control.

The 3G3JV Inverter performs versatile speed control, such as multi-step speed control up to a maximum of nine steps, acceleration and deceleration (UP/DOWN) control, and jog operations. Furthermore, the 3G3JV Inverter provides a variety of useful functions, including slip compensation, overtorque detection, and speed search functions.

This catalog provides information for the selection of models, but does not provide operational precautions. For information on the operation of the 3G3JV Inverters and operational precautions, be sure to read the operation manual.

The cooling fan can be easily mounted or dismounted. The cooling fan can also be turned on only when the 3G3JV Inverter is in operation, prolonging the life of the fan.

The 3G3JV Inverter incorporates main circuit terminals arranged in two rows on the top and bottom of the housing, making it possible to mount the 3G3JV Inverter like a contactor. The optional DIN Track Mounting Bracket makes it possible to easily mount a 3G3JV Inverter to a DIN track.

The 3G3JV Inverters are compact and space-saving to mount easily into a panel.

The 3G3JV Inverter supports a variety of I/O, such as analog inputs between 0 and 10V, 4 to 20 mA, or 0 to 20 mA, multifunction I/O, and analog monitor outputs. Multi-function inputs can set to either PNP or NPN, providing flexibility in input signals.

Actual Size
Three-phase 100 W at 200 V 68 x 128 x 78.5 mm (W x H x D)

Standard models meet CE and UL/cUL standards.

Downloaded from www.Manualslib.com manuals search engine

Conventional Systems
Relay contact welding occurs, which may put the system and operators in danger. Furthermore, the life of the system is comparatively short. The system employs a gearbox for speed control, the designing and Breaker adjustment of which require time and labor. To ensure the safety of the system, the system needs peripheral safety Open-phase detection devices, the wiring of which requires time and labor. The motor always rotates at top speed, consuming a high amount of power. A strong shock is produced when the motor is driven, which may cause loads to shift, deteriorate the quality of products, or put the system and operators in danger. Contactor
Three-phase inductive motor

3G3JV Inverter Solutions


A 3G3JV Inverter has no mechanical relay contacts and thus allows a safe, long-life system operation. A 3G3JV Inverter performs versatile speed control, such as multi-step speed control for up to nine steps, acceleration and deceleration (UP/DOWN) control, and jog operations. A 3G3JV Inverter provides a variety of protective functions, such as a highspeed current limit, ground fault protection, and undervoltage protection. A 3G3JV Inverter drives the motor at flexible speeds within the rated speed range of the motor, thus reducing motor power consumption. A 3G3JV Inverter provides soft-start and soft-stop functions, preventing loads from shifting and deterioration of product quality, while ensuring the safety of the system.

A 3G3JV Inverter provides soft-start and soft-stop functions to prevent loads from shifting. Furthermore, a 3G3JV Inverter performs flexible speed control of the conveyor up to nine steps.

A 3G3JV Inverter performs flexible speed control of a compact agitator or separator.

Breaker

3G3JV Inverter

Gear box

Starter

Current leakage detection

Three-phase inductive motor

Conventional Systems
A strong shock results at the moment the motor is driven, which may cause load shifting, deteriorates the quality of products, or puts the system and operators in danger. The capacity of the motor is small. Therefore, the rotation speed of the motor will drop if a speed reducer is used for the maintenance of the torque. The rotation of the motor fluctuates. Failures in the motor are not detected by the host controller. The types of available motors are limited.

3G3JV Inverter Solutions


A 3G3JV Inverter provides soft-start and soft-stop functions, preventing loads from shifting and deterioration of product quality while ensuring the safety of the system. The 3G3JV Inverters are available up to a maximum motor capacity of 3.7 kW and ensure smooth rotation speed and torque in the motor. A three-phase motor has less speed fluctuation compared with a singlephase motor, ensuring the safe operation of the system. A 3G3JV Inverter can report errors in contact outputs or data to a host controller, such as a Programmable Controller. A wide range of motors is available.

A 3G3JV Inverter provides optimum control of fan speed according to the room temperature. The 3G3JV Inverter has no mechanical relay contacts, ensuring the safety and reliability of the system compared with the ON/OFF control of contactors. Optimum control of fan speed also saves energy.

A 3G3JV Inverter provides multi-step speed control to open and close an electric shutter safely and efficiently. The shutter opens quickly at a high speed, but closes at a medium-range speed while the system checks the safety of the operation and decelerates to low speed before it is fully closed to prevent people from being caught by the shutter.

Breaker

Breaker

3G3JV Inverter

Three-phase inductive motor Gear box Speed controller

Downloaded from www.Manualslib.com manuals search engine

Nomenclature
Panel
Top protection cover: Remove this cover when wiring the upper terminal block.

Upper terminal block: A terminal block on the input side of the main circuit.

Digital Operator: Used to set parameters, perform various monitoring, and start and stop the Inverter.

ALARM indicator: RUN indicator: Displays the operating status of the Inverter. Alarm (Red): Lights when an error occurs. Flashes when a warning occurs. RUN (Green): Flashes when no RUN command is input during normal status. Lights when a RUN command is input during normal status. Optional cover: Remove this cover when setting the input method selector. Front cover: Remove this cover when wiring the upper or lower terminal block.

Front cover mounting screw:

A screw for fixing the front cover. Lower terminal blocks: A terminal block on the output side of the main circuit and a terminal block for the control circuit. Bottom protection cover: Remove this cover when wiring the lower terminal blocks.

6
Downloaded from www.Manualslib.com manuals search engine

Nomenclature
Digital Operator

Data display

Indicators (Setting/Monitor item indicators)

Keys

FREQ adjuster

Appearance

Name Data display Frequency adjuster

Function Displays relevant data items, such as frequency reference, output frequency, and parameter set values. Sets the frequency reference within a range between 0 Hz and the maximum frequency.

Frequency reference indicator Output frequency indicator Output current indicator Multi-function monitor indicator Forward/Reverse selection indicator Local/Remote selection indicator Parameter setting indicator Mode Key

The frequency reference can be monitored or set while this indicator is lit. The output frequency of the Inverter can be monitored while this indicator is lit. The output current of the Inverter can be monitored while this indicator is lit. The values set in U01 through U10 are monitored while this indicator is lit. The direction of rotation can be selected while this indicator is lit when operating the Inverter with the RUN Key. The operation of the Inverter through the Digital Operator or according to the set parameters is selectable while this indicator is lit. (See note 1.) The parameters in n01 through n79 can be set or monitored while this indicator is lit. (See note 2.) Switches the setting and monitor item indicators in sequence. Parameter being set will be canceled if this key is pressed before entering the setting. Increases multi-function monitor numbers, parameter numbers, and parameter set values. Decreases multi-function monitor numbers, parameter numbers, and parameter set values. Enters multi-function monitor numbers, parameter numbers, and internal data values after they are set or changed. Starts the Inverter running when the 3G3JV is in operation with the Digital Operator. Stops the Inverter unless parameter n06 is set to disable the STOP Key. Used to reset the Inverter when an error occurs. (See note 3.)

Increment Key Decrement Key Enter Key RUN Key STOP/RESET Key

Note: 1. The status of the local/remote selection indicator can be only monitored while the Inverter is in operation. Any RUN command input is ignored while this indicator is lit. 2. While the Inverter is in operation, the parameters can be only monitored and only some parameters can be changed. Any RUN command input is ignored while the parameter setting indicator is lit. 3. For safety reasons, the reset function cannot be used while an operation instruction (forward/reverse) is being input. Turn the operation instruction OFF before using this function.

7
Downloaded from www.Manualslib.com manuals search engine

Using Digital Operator


Selecting Indicators
Power ON

represents a lit indicator. Frequency reference Output frequency Output current

Parameter settings
Parameter n01

Local/Remote selection
Remote mode

Direction of rotation
Forward

Multi-function monitor
Frequency reference

Parameter n02

Local mode

Reverse

Output frequency

Other parameters

Other monitor items

Note: If the power is turned OFF with the FOUT or IOUT indicator lit, the same indicator will light when the power is turned ON again. In other cases, the FREF indicator will light when the power is turned ON.

Example of Frequency Reference Settings


Flashing

Key sequence

Indicator

Display example

Explanation Power ON Note If the FREF indicator has not been lit, press the Mode Key repeatedly until the FREF indicator is lit. Use the Increment or Decrement Key to set the frequency reference. The data display will flash while the frequency reference is set. (see note 1) Press the Enter Key so that the set value will be entered and the data display will be lit. (see note 1)

Note: The Enter Key need not be pressed when performing the setting for n08. The frequency reference will change when the set value is changed with the Increment or Decrement Key while the data display is continuously lit.

8
Downloaded from www.Manualslib.com manuals search engine

Using Digital Operator


Example of Multi-function Display
Frequency reference DC bus voltage Monitor data

Complete

Key sequence

Indicator

Display Power ON

Explanation

Press the Mode Key repeatedly until the MNTR indicator is lit. U01 will be displayed. Use the Increment or Decrement Key to select the monitor item to be displayed. Press the Enter Key so that the data of the selected monitor item will be displayed. The monitor number display will appear again by pressing the Mode Key.

Status Monitor
Item U01 U02 U03 U04 U05 U06 Display Frequency reference Output frequency Output current Output voltage DC bus voltage Input p terminal status Display unit Hz Hz A V V --Function Monitors the frequency reference. (Same as FREF) Monitors the output frequency. (Same as FOUT) Monitors the output current. (Same as IOUT) Monitors the internal output voltage reference value of the Inverter. Monitors the DC voltage of the internal main circuit of the Inverter. Shows the ON/OFF status of inputs. : Input ON : No input

U07

Output p terminal status

---

Not used Shows the ON/OFF status of outputs.

Terminal S1: Forward/Stop Terminal S2: Multi-function input 1 (S2) Terminal S3: Multi-function input 2 (S3) Terminal S4: Multi-function input 3 (S4) Terminal S5: Multi-function input 4 (S5)

: Closed Not used U09 Error log g (most ( recent one) ) --Displays the latest error.

: Open

Terminal MA: Multi-function contact output

U10

Software No.

---

Error OMRON use only.

9
Downloaded from www.Manualslib.com manuals search engine

Using Digital Operator


Example of Parameter Settings
The following example shows how to set 2 to enable the frequency reference control terminal for 0- to 10-V input in parameter n03 (Frequency Reference Selection).

Cancels set data.

Enable the frequency reference control terminal for 0- to 10-V input. Complete

In approximately 1 s.

Key sequence

Indicator

Display example Power ON

Explanation

Press the Mode Key repeatedly until the PRGM indicator is lit. Use the Increment or Decrement Key to set the parameter number. Press the Enter Key. The data of the selected parameter number will be displayed. Use the Increment or Decrement Key to set the data. At that time the display will flash. Press the Enter Key so that the set value will be entered and the data display will be lit. (see note 1) The parameter number will be displayed.

In approximately 1 s.

Note: 1. To cancel the set value, press the Mode Key instead. The parameter number will be displayed. 2. There are parameters that cannot be changed while the Inverter is in operation. Refer to the list of parameters. When attempting to change such parameters, the data display will not change by pressing the Increment or Decrement Key.

10
Downloaded from www.Manualslib.com manuals search engine

List of Parameters
List of Parameters
Parameter No. n01 Name Description Setting range 0, 1, 6, 8, 9 Unit of setting (see note 2) 1 Default setting 1 Changes during operation No Reference page 14

Parameter write-prohibit selection/ parameter initialization

Used to prohibit parameters to be written, sets parameters, or change the monitor range of parameters. Used to initialize parameters to default values.

n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15

Operation mode selection Frequency reference selection Interruption mode selection Reverse rotation-prohibit selection STOP/RESET Key function selection Frequency selection in local mode Key sequential frequency setting Maximum frequency (FMAX) Maximum voltage (VMAX) Maximum voltage frequency (FA) Middle output frequency (FB) Middle output frequency voltage (VC) Minimum output frequency (FMIN) Minimum output frequency voltage (VMIN) Acceleration time 1 Deceleration time 1 Acceleration time 2 Deceleration time 2 S-shape acceleration/deceleration characteristic Frequency reference 1 Frequency reference 2 Frequency reference 3 Frequency reference 4 Frequency reference 5 Frequency reference 6 Frequency reference 7 Frequency reference 8 Inching frequency command

Used to select the input method for the RUN and STOP commands in remote mode. Used to set the input method for the frequency reference in remote mode. Used to set the stopping method for use when the STOP command is input. Used to select the operation with the reverse command input. Used to select the stop method in remote mode with n02 for operation mode selection set to 1. Used to set the input method for the frequency reference in local mode. Used to enable the Enter Key for setting the frequency reference with the Increment and Decrement Keys. Used to set the V/f pattern as the basic characteristic of the Inverter with output voltage per frequency set. Note Set the parameters so that the following condition will be satisfied. n14 14 x n12 12 < n11 11 x n09 09 Note The value set in n13 will be ignored g if parameters p n14 14 and d n12 12 are the th same in i value. l

0, 1 0 to 4 0, 1 0, 1 0, 1 0, 1 0, 1 50.0 to 400 1 to 255 (see note 1) 0.2 to 400 0.1 to 399 1 to 255 (see note 1) 0.1 to 10.0 1 to 50 (see note 1)

1 1 1 1 1 1 1 0.1 Hz 1V 0.1 Hz 0.1 Hz 1V 0.1 Hz 1V

0 0 0 0 0 0 0 60.0 200 (see note 1) 60.0 1.5 12 (see note 1) 1.5 12 (see note 1) 10.0 10.0 10.0 10.0

No No No No No No No No No No No No No No

14 14 14 14 14 14 14 14 14 14 14 14 14 14

n16 n17 n18 n19 n20 n21 n22 n23 n24 n25 n26 n27 n28 n29

Acceleration time: The time required to go from 0% to 100% of the maximum frequency. Deceleration time: The time required to go from 100% to 0% of the maximum frequency. Note The actual acceleration or deceleration time is obob tained from the following formula. Acceleration/Deceleration time = (Acceleration/Deceleration time set value) (Frequency reference value) (Max. frequency) Used to set S-shape acceleration/deceleration characteristics. U Used to set internal frequency q y references. Note Frequency reference 1 is enabled in remote mode with n03 for frequency reference selection set to 1. 1 Note These frequency references are selected with mulmul ti-step speed references (multi-function input). See the reference pages for the relationship between multi-step speed references and frequency references ences.

0.0 to 999

0.1 s

Yes Yes Yes Yes No No No No No No No No No No

15 15 15 15 15 15 15 15 15 15 15 15 15 15

0 to 3 0 0 to max. 0.0 f frequency

1 0.1 Hz 0

0 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6.0

Used to set the inching frequency command.

Note: 1. With 400-class Inverters, the default settings and maximum values setting ranges for n10, n13, and n15 are double those given in the table. 2. Values longer than 3 digits are rounded up to the next unit multiple.

11
Downloaded from www.Manualslib.com manuals search engine

List of Parameters
Parameter No. n30 n31 n32 Name Description Setting range 0 to 110 0 to 110 0.0 to 120% of rated output current 0 to 2 1 to 60 0, 1 Unit of setting (see note) 1% 1% 0.1 A Default setting 100 0 Varies with the capacity. 0 8 0 Changes during operation No No No Reference page 16 16 16 Frequency reference upper limit Frequency reference lower limit Rated motor current Used to set the upper and lower frequency reference limits in percentage based on the maximum frequency as 100% 100%. Used to set the rated motor current for motor overload detection (OL1) based on the rated motor current. Note Motor overload detection (OL1) is disabled by setting the parameter to 0.0. Used to set the motor overload detection (OL1) for the electronic thermal characteristics of the motor. Used to set the electric thermal characteristics of the motor to be connected in 1-minute increments. Used to operate the Cooling Fan of the Inverter while the Inverter is turned on or only while the Inverter is in operation. Used to select the functions of multi-function input terminals S2 through S5.

n33 n34 n35

Motor protection characteristics Motor protective time setting Cooling fan operation function Multi-function input 1 (Input terminal S2) Multi-function input 2 (Input terminal S3) Multi-function input 3 (Input terminal S4) Multi-function input 4 (Input terminal S5) Multi-function output (MA/MB and MC output terminals) Frequency reference gain Frequency reference bias Analog frequency reference filter time Analog monitor output Analog monitor output gain Carrier frequency selection Momentary power interruption compensation Fault retry

1 1 min 1

No No No

16 16 16

n36 n37 n38 n39 n40

2 to 22 0 to 22 2 to 22 2 to 34

1 1 1 1 1

2 5 3 6 1

No No No No No

16 16 16 16 17

Used to select the functions of multi-function output terminals. Used to the input characteristics of analog frequency references.

0 to 7, 10 to 17 0 to 255 99 to 99

n41 n42 n43 n44 n45 n46

1% 1% 0.01 s 1 0.01 1

100 0 0.10 0 1.00 Varies with the capacity. 0

Yes Yes No No Yes No

17 17 17 17 17 18

Used to set the digital filter with a first-order lag for analog frequency references to be input. Used to set the output frequency or current as a monitored item. Used to set the output characteristics of analog monitor output. Used to set the carrier frequency.

0.00 to 2.00 0, 1 0.00 to 2.00 1 to 4, 7 to 9 0 to 2

n47

Used to specify the processing that is performed when a momentary power interruption occurs. Used to set the number of times the Inverter is reset and restarted automatically in the case the Inverter has an overvoltage fault, overcurrent fault, or ground fault. Used to set the frequency q yj jump p function. Note These values must satisfy the following condition: n49 y n50

No

18

n48

0 to 10

No

18

n49 n50 n51 n52 n53 n54 n55

Jump frequency 1 Jump frequency 2 Jump width DC control current Interruption DC control time Startup DC control time Stall prevention during deceleration Stall prevention level during acceleration Stall prevention level during operation Frequency detection level

0.0 to 400 0.0 to 400 0.0 to 400 0 to 100 0.0 to 25.5 0.0 to 25.5

0.1 Hz 0.1 Hz 0.1 Hz 1% 0.1 s 0.1 s 1

0.0 0.0 0.0 50 0.5 0.0 0

No No No No No No No

18 18 18 18 18 18 18

Used to impose DC U p C on the induction motor for braking g t l control.

Used to select a function to change the deceleration time of the motor automatically so that there will be no overvoltage imposed on the motor during deceleration. Used to select a function to stop the acceleration of the motor automatically for stall prevention during acceleration. Used to select a function to reduce the output frequency of the Inverter automatically for stall prevention during operation. Used to set the frequency to be detected.

0, 1

n56

30 to 200

1%

170

No

19

n57

30 to 200

1%

160

No

19

n58

0.0 to 400

0.1 Hz

0.0

No

19

Note: Values longer than 3 digits are rounded up to the next unit multiple.

12
Downloaded from www.Manualslib.com manuals search engine

List of Parameters
Parameter No. n59 Name Description Setting range 0 to 4 1 Unit of setting (see note) Default setting 0 Changes during operation No Reference page 19

Overtorque detection function selection Overtorque detection level Overtorque detection time UP/DOWN command frequency memory Torque compensation gain Motor rated slip

Used to enable or disable overtorque detection and select the processing method after overtorque detection. Used to set overtorque detection level. Used to set the detection time of overtorque. Used to store the adjusted frequency reference with the UP/DOWN function. Used to set the gain of the torque compensation function. Used to set the rated slip value of the motor in use.

n60 n61 n62

30 to 200 0.1 to 10.0 0, 1

1% 0.1 s 1

160 0.1 0

No No No

19 19 20

n63 n64

0.0 to 2.5 0.0 to 20.0

0.1 0.1 Hz

1.0 Varies with the capacity. Varies with the capacity. 0.0 2.0 --0

Yes Yes

21 21

n65

Motor no-load current Slip compensation gain Slip compensation time constant OMRONs control reference use Low-speed carrier frequency reduction selection O OMRONs O control reference f use Error log

Used to set the no-load current of the motor in use based on the rated motor current as 100%. Used to set the gain of the slip compensation function. Used for the response speed of the slip compensation function. Do not change the set value. Used to select a function to reduce the carrier frequency when Inverter is at low speed. Do not change g the set value. Used to display the latest error recorded.

0 to 99

1%

No

21

n66 n67 n68 to n74 n75

0.0 to 2.5 0.0 to 25.5 --0.1

0.1 0.1 s --1

Yes No --No

21 21 -----

n76 n77 n78

-----

-----

-----

-----

-----

Display Note Note n79 Software number will be displayed if no error has been recorded. This parameter is monitored only. -----------

Used to display the software number of the Inverter for OMRONs control reference use. Note This parameter is monitored only.

Note: Values longer than 3 digits are rounded up to the next unit multiple.

13
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


Note: The shaded values indicate default settings.

Parameter Write-prohibit Selection/Parameter Initialization (n01)


This parameter makes it possible to write-prohibit parameters, change the parameter set or displayed range, or initialize all parameters to default values.
Value 0 1 6 8 9 Description Only n01 can be displayed and set. The n02 through n79 parameters can be displayed only. The n01 through n79 parameters can be displayed and set. Only the error log memory is cleared. Enables the initialization of all parameters in 2-wire sequence so that the parameters will return to default values. Enables the initialization of all parameters in 3-wire sequence.

Reverse Rotation-prohibit Selection (n05)


Select the operation to be performed when the reverse rotation command is input.
Value 0 1 Description Reverse rotation possible (command accepted) Reverse rotation prohibited (command not accepted)

STOP/RESET Key Function Selection (n06)


When parameter n02 is set to 1, set whether or not to use the STOP/RESET Key of the Digital Operator to stop the Inverter in remote mode. The STOP/RESET Key is always enabled in local mode regardless of the setting in n02.
Value 0 1 Description The STOP/RESET Key of the Digital Operator is enabled. The STOP/RESET Key of the Digital Operator is disabled.

Operation Mode Selection (n02)


Select the method of operation mode input to start or stop the Inverter in remote mode.
Value 0 1 Description The RUN and STOP/RESET Keys of the Digital Operator are enabled. Multi-function input in 2- or 3-wire sequence through the control circuit terminals is enabled.

Frequency Reference Selection (n07) (Local Mode)


Select the input method of frequency references in local mode.
Value 0 1 Description The FREQ adjuster of the Digital Operator is enabled. Key sequences on the Digital Operator are enabled.

Note: In local mode, RUN commands can be entered using the Digital Operator only.

Frequency Reference Selection (n03) (Remote Mode)


Select the method for inputting the frequency reference to the Inverter in remote mode.
Value 0 1 2 3 4 Description The FREQ adjuster of the Digital Operator is enabled. Frequency reference 1 (n21) is enabled. The frequency reference control terminal (for 0- to 10-V input) is enabled. The frequency reference control terminal (for 4- to 20-mA current input) is enabled. The frequency reference control terminal (for 0- to 20-mA current input) is enabled.

Key Sequential Frequency Setting (n08)


Select whether to enable the Enter Key when setting the frequency reference with the Increment and Decrement Keys on the Digital Operator.
Value 0 1 Description The Enter Key is enabled. (The setting is made valid by pressing the Enter Key.) The Enter Key is disabled. (The setting is directly treated as a frequency reference without the Enter Key being pressed.)

V/f Pattern Settings (n09 to n15)


Set the V/f pattern as the basic characteristic of the Inverter with output voltage per frequency set.
Value n09 n10 n11 n12 n13 n14 n15 Name Maximum Frequency (FMAX) Maximum Voltage (VMAX) Maximum Voltage Frequency (FA) Middle Output Frequency (FB) Middle Output Frequency Voltage (VC) Minimum Output Frequency (FMIN) Minimum Output Frequency Voltage (VMIN) Setting range 50.0 to 400 1 to 255 0.2 to 400 0.1 to 399 1 to 255 0.1 to 10.0 1 to 50 Unit of setting 0.1 Hz 1V 0.1 Hz 0.1 Hz 1V 0.1 Hz 1V Default settings 60.0 200 60.0 1.5 12 1.5 12

Interruption Mode Selection (n04)


Select the stopping method to be used when the STOP command is input.
Value 0 1 Description Frequency deceleration stop (Decelerates to stop in preset time.) Free running (Output shut OFF by STOP command.)

14
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


Note: For n09, n11, and n12, the unit of setting is as follows: Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz increments if the frequency is 100 Hz or greater.
Output voltage (V)
n10

Setting the Frequency References 1 to 8 and the Inching Frequency Command (n21 to n28 and n29)
Set internal frequency references.
Value Name Setting range 0 0 to max. 0.0 f frequency Unit of setting 0 Hz 0.1 ( (see note t 1) Default settings 6.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 6.0

n21 n22 n23 n24

Frequency reference 1 Frequency reference 2 Frequency reference 3 Frequency reference 4 Frequency reference 5 Frequency reference 6 Frequency reference 7 Frequency reference 8 Inching frequency command

n13

n25 n26 n27

n15

Frequency (Hz) Note: 1. Set the parameters so that the following condition will be satisfied. n14 x n12 < n11 x n09 2. The value set in n13 will be ignored if parameters n14 and n12 are the same in value.

n28 n29

Note:

Acceleration/Deceleration Time Settings (n16 to n19)


The acceleration time is the time required to go from 0% to 100% of the maximum frequency and the deceleration time is the time required to go from 100% to 0% of the maximum frequency. The actual acceleration or deceleration time is obtained from the following formula. Acceleration/Deceleration time = (Acceleration/Deceleration time set value) (Frequency reference value) (Max. frequency)
Value Name Setting range 0.0 0 0 to 999 Unit of setting 0.1 s 0 Default settings 10.0 10.0 10.0 10.0

1. Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz increments if the frequency is 100 Hz or over. 2. Frequency reference 1 is enabled with n03 for frequency reference selection set to 1. (Remote mode) 3. Frequency references 1 to 8 are enabled by setting multistep speed references 1, 2, and 3 in n36 to n39 for multi-function input. Refer to the following table for the relationship between multi-step speed references 1 to 3 and frequency references 1 to 8.
Multi-step speed reference 1 OFF ON OFF ON OFF ON OFF ON Multi-step speed reference 2 OFF OFF ON ON OFF OFF ON ON Multi-step speed reference 3 OFF OFF OFF OFF ON ON ON ON

Frequency reference Frequency reference 1 Frequency reference 2 Frequency reference 3 Frequency reference 4 Frequency reference 5 Frequency reference 6 Frequency reference 7 Frequency reference 8

n16 n17 n18 n19

Acceleration time 1 Deceleration Time 1 Acceleration time 2 Deceleration Time 2

S-shape Acceleration/Deceleration Characteristic (n20)


Any one of three S-shape acceleration/deceleration times (0.2, 0.5, and 1.0 s) is selectable.
Value 0 1 2 3 Description No S-shape acceleration/deceleration characteristic (Trapezoidal acceleration/deceleration) S-shape acceleration/deceleration characteristic time is 0.2 s S-shape acceleration/deceleration characteristic time is 0.5 s S-shape acceleration/deceleration characteristic time is 1.0 s

Note:

1. ON and OFF represent input ON and input OFF, respectively. 2. Inching frequency commands take precedence over multistep speed references.

Note: When the S-shape acceleration/deceleration characteristic time is set, the acceleration and deceleration times will be lengthened according to the S-shape at the beginning and end of acceleration/deceleration.

15
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


Frequency Reference Upper and Lower Limit Settings (n30 and n31)
Set the upper and lower frequency reference limits in percentage based on the maximum frequency as 100%.
Value n30 n31 Name Frequency Reference Upper Limit Frequency Reference Lower Limit Setting range 0 to 110 0 to 110 Unit of setting 1% 1% Default settings 100 1 0

Cooling Fan Operation Function Selection (n35)


This parameter is used to operate the cooling fan of the Inverter while the Inverter is turned on or only while the Inverter is in operation.
Value 0 Description The fan rotates only while the RUN command is input and for 1 minute after the Inverter stops operating. The fan rotates while the Inverter is turned ON.

Note:

Note: If n31 is set to a value less than the minimum output frequency (FMIN) (n14), the Inverter will have no output when a frequency reference less than the minimum output frequency input is ON.

1. This parameter is available only if the Inverter incorporates a cooling fan. 2. If the operation frequency of the Inverter is low, the life of the fan can be prolonged by setting the parameter to 0.

Multi-function Input Selection (n36 to n39)


Select the functions of multi-function input terminals S2 to S5.
Value n36 n37 n38 n39 Name Multi-function Input 1 (S2) Multi-function Input 2 (S3) Multi-function Input 3 (S4) Multi-function Input 4 (S5) Function Forward/Reverse rotation command Setting range 2 to 8, 10 to 22 0, 2 to 8, 10 to 22 2 to 8, 10 to 22 2 to 8, 10 to 22, 34 Unit of setting 1 1 1 1 Default settings 2 5 3 6

Rated Motor Current Setting (n32)


Set the rated motor current as the reference value for motor overload detection (OL1).
Note: 1. Setting 0.0 disables the motor overload detection (OL1) function. 2. The rated motor current value is factory-set for each Inverter according to the maximum applicable motor capacity.
Name Rated Motor Current Setting range 0.0% to 120% (A) of rated output current of Inverter Unit of setting 0.1 A Default settings Varies with the capacity.

Value n32

Value 0

Description 3-wire sequence (to be set in n37 only) This setting overrides the n36 setting. S1: RUN input (RUN when ON) STOP input (STOP when OFF) Forward/Reverse rotation command (ON: Reverse)

Motor Protection Characteristic Selection (n33)


Set the motor overload detection (OL1) for the electronic thermal characteristics of the motor.
Value 0 1 2 Description Protection characteristics for general-purpose induction motors Protection characteristics for Inverter-dedicated motors No protection 2 3 4 5

S2: S3:

Reverse/Stop External fault (NO) External fault (NC) Fault reset

Reverse rotation command (2-wire sequence) (ON: Reverse) ON: External fault OFF: External fault ON: Fault reset Note Disabled while RUN command is input Signals to select frequency references 1 to 8.

Note: When connecting multiple motors to one Inverter, set 2 (equivalent to n32 = 0.0). In addition, take overload prevention measures by mounting a thermal relay in each motor, for example.

Motor Protective Time Setting (n34)


7

Multi-step speed reference 1 Multi-step speed reference 2 Multi-step speed reference 3 Inching frequency command Acceleration/Deceleration time selection External base block command (NO) External base block command (NC) Search command (Searching starts from maximum frequency)

Set the electronic thermal characteristics of the motor to be connected in 1-minute increments.
Value n34 Name Motor Protective Time Setting Setting range 1 to 60 Unit of setting 1 min Default settings 8

8 10 11

ON: Inching frequency command ON: Acceleration/deceleration time 2

Note:

1. The default setting does not need any changes in normal operation. 2. To set the parameter according to the characteristics of the motor, confirm the thermal time constant with the motor manufacturer and set the parameter with some margin. In other words, set the value a little shorter than the thermal time constant. 3. To detect motor overloading more quickly, reduce the set value, provided that it does not cause any application problems.

12 13 14

ON: Output shut OFF (while motor coasting to a stop and bb flashing) OFF: Output shut OFF (with motor free running and bb flashing) ON: Speed search (Searching starts from n09)

16
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


Value 15 Function Search command (Searching starts from preset frequency) Acceleration/Deceleration-prohibit command Local or remote selection Emergency stop fault (NO) Emergency stop alarm (NO) Emergency stop fault (NC) Emergency stop alarm (NC) Up or down command Description ON: Speed search (Searching starts from the frequency specified by n03.) 15 16 UV in progress Rotating in reverse direction Speed search in progress ON: Undervoltage being monitored (main circuit undervoltage UV or UV1 detected) ON: Rotating in reverse direction

16

ON: Acceleration/Deceleration is on hold

17

ON: Speed search in progress

17 19

ON: Local mode (operated with the Digital Operator) The Inverter stops according to the setting in n04 for interruption mode selection when the emergency stop input turns ON. Note NO Emergenc NO: Emergency stop with ith the concon tact closed. NC: Emergency stop with the contact opened. Note Fault: Fault output is ON and reset with RESET input. Alarm output is ON (no reset required). STP is displayed (lit with fault input ON and flashes with alarm input ON)

Note: Use operation in progress or frequency detection 1/2 for the timing of the external brake.

Gain and Bias Settings (n41 and n42)


Set the input characteristics of analog frequency references in n41 (for the frequency reference gain) and n42 (for the frequency reference bias). Set the frequency of maximum analog input (10 V or 20 mA) in n41 as percentage based on the maximum frequency as 100%. Set the frequency of minimum analog input (0 V, 0 mA, or 4 mA) in n42 as percentage based on the maximum frequency as 100%.
Value n41 n42 Name Frequency Reference Gain Frequency Reference Bias Setting range 0 to 255 99 to 99 Unit of setting 1% 1% Default settings 100 0

20

21

22

Note

34

Up or down command (set in n39 only) This setting overrides the n38 setting. S4: Up command S5: Down command

Multi-function Output Selection (n40)


Select the functions of multi-function output terminals.
Value Name Setting range 0 to 7, 10 to 17 1 Unit of setting Default settings 1

Analog Frequency Reference Filter Time Setting (n43)


The digital filter with a first-order lag can be set for analog frequency references to be input.
Value Name Analog Frequency Reference Filter Time Setting range 0.00 to 2.00 Unit of setting 0.01 s Default settings 0.10

n40

Multi-function Output (MA/ MB and MC) Function Fault output Operation in progress Frequency detection Idling Frequency detection 1 Frequency detection 2 Overtorque being monitored (NO-contact output) Overtorque being monitored (NC-contact output) (Not used) ( ) Alarm output Base block in progress RUN mode Inverter ready Fault retry Function

Value 0 1 2 3 4 5 6

Description ON: Fault output ON: Operation in progress ON: Frequency detection ON: Idling ON: Output frequency y frequency detection level (n58) ON: Output frequency x frequency detection level (n58) Output if any of the following parameter conditions is satisfied. Overtorque detection function selection (n59) Overtorque detection level (n60) Overtorque detection time (n61) Note NO contact: ON with overtorque being detected; NC contact: OFF with overtorque being detected 0 1 n43

Analog Monitor Output Setting (n44)


Set a monitored item for analog monitor output.
Value Description Output frequency (Reference: 10 V at max. frequency) Output current (Reference: 10 V with rated output current)

Note: The values in parentheses are applicable when n45 is set to 1.00.

Analog Monitor Output Gain Setting (n45)


Set the output characteristics of analog monitor output.
Value n45 Name Analog Monitor Output Gain Setting range 0.00 to 2.00 Unit of setting 0.01 Default settings 1.00

8 9 10 11 12 13 14 Value

--ON: Alarm being detected (Nonfatal error) ON: Base block in progress ON: Local mode ON: Inverter ready to operate ON: Fault retry Description

17
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


Carrier Frequency Selection (n46)
Set the carrier frequency.
Value 1 2 3 4 7 8 9 2.5 kHz 5.0 kHz 7.5 kHz 10.0 kHz 2.5 kHz (12): 12 times as high as output frequency (between 1.0 and 2.5 kHz) 2.5 kHz (24): 24 times as high as output frequency (between 1.0 and 2.5 kHz) 2.5 kHz (36): 36 times as high as output frequency (between 1.0 and 2.5 kHz) Description

Output frequency n51

n50

n49

Reference frequency

DC Control Functions (n52 to n54)


Used to impose DC on the induction motor for braking control.

Note: Normally, the factory setting need not be changed.


Value Name

Momentary Power Interruption Compensation (n47)


The parameter specifies the processing that will be performed when a momentary power interruption occurs.
Value 0 1 2 Disabled. The Inverter will continue operating if power is restored within 0.5 s. The Inverter will restart when power is restored. Description

Setting range 0 to 100 0.0 to 25.5 0.0 to 25.5

Unit of setting 1% 0.1 s 0.1 s

Default settings 50 0.5 0.0

n52 n53 n54

DC Control Current Interruption DC Control Time Startup DC Control Time

DC Control Current: Set this value in percentage based on the rated output current of the Inverter as 100%.
Output frequency

Fault Retry (n48)


Set the number of times the Inverter is to be automatically reset and restarted when the Inverter has an overvoltage fault, overcurrent fault, or ground fault.
Value Name Setting range 0 to 10 1 Unit of setting Default settings 0

FMIN (n14) Time n54 n53

n48

Fault Retry

Frequency Jump Function (n49 to n51)


Set the frequency jump function.
Value n49 Name Jump Frequency 1 Setting range 0.0 to 400 Unit of setting 0.1 Hz (see note 1) 0.1 Hz (see note 1) 0.1 Hz Default settings 0.0

Stall Prevention during Deceleration (n55)


Select a function to change the deceleration time of the motor automatically so that there will be no overvoltage imposed on the motor during deceleration.
Value 0 0.0 1 Description Stall prevention during deceleration No stall prevention during deceleration

n50

Jump Frequency 2

0.0 to 400

n51

Jump Width

0.0 to 25.5

0.0

Output frequency

Note:

1. Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1 Hz-increments if the frequency is 100 Hz or greater. 2. Make settings so that n49 y n50.

Deceleration time is controlled to prevent overvoltage.

Time Deceleration time (Set value)

18
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


Stall Prevention Level during Acceleration (n56)
Set the operation level of a function to stop the acceleration of the motor automatically for stall prevention during acceleration. Set this value in percentage based on the rated output current of the Inverter as 100%.
Value n56 Name Stall Prevention Level during Acceleration Setting range 30 to 200 Unit of setting 1% Default settings 170 2

Overtorque Detection Function Selection (n59 to n61)


Set n59 to enable or disable overtorque detection and select the processing to be performed after overtorque detection.
Value 0 1 Description Inverter does not monitor overtorque. Inverter monitors overtorque only when speed is matched. It continues operation (issues warning) even after overtorque is detected. Inverter monitors overtorque only when speed is matched. It discontinues operation (through protective function) when overtorque is detected. Inverter always monitors overtorque during operation. It continues operation (issues warning) even after overtorque is detected. Inverter always monitors overtorque during operation. It discontinues operation (through protective function) when overtorque is detected.

Stall Prevention during Acceleration Output current n56


3

Time Output frequency The output frequency is controlled so that the Inverter will not stall. Time

Set the overtorque detection level in n60 and the overtorque detection time in n61.
Value Name Setting range 30 to 200 0.1 to 10.0 Unit of setting 1% 0.1 s Default settings 160 0.1

Stall Prevention Level during Operation (n57)


Select the operation level of a function to reduce the output frequency of the Inverter automatically for stall prevention during operation. Set this value in percentage based on the rated output current of the Inverter as 100%.
Value n57 Name Stall Prevention Level during Operation Setting range 30 to 200 Unit of setting 1% Default settings 160

n60 n61

Overtorque Detection Level Overtorque Detection Time

Note:

1. In n60, set the overtorque detection level in percentage based on the rated output current of the Inverter as 100%. 2. In n61, set the overtorque detection time in 0.1-s increments. See note. n60

Overtorque Detection Output current

Stall Prevention during Operation Time Output current n57 Overtorque detection (NO) Time Output frequency The output frequency is controlled so that the Inverter will not stall. Time n61 Time Note: Overtorque detection will be canceled if the output current decreases from the detection level by approximately 5% of the Inverter rated current.

Frequency Detection Level (n58)


Set the frequency to be detected. Note: When frequency detection 1 and 2 are to be output, n40 (multi-function output) must be set.
Value n58 Name Frequency Detection Level Setting range 0.0 to 400 Unit of setting 0.1 Hz Default settings 0.0

19
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


UP/DOWN Command Frequency Memory Selection (n62)
Select whether to store the frequency reference adjusted with the UP/DOWN function.
Value 0 1 Description The frequency on hold is not retained. The frequency on hold for 5 s or more is retained.

Use n62 (UP/DOWN command frequency memory) to set whether the frequency reference on hold is stored or not when an UP or DOWN command is sent to the multi-function input terminals. If n62 is set to 1, the output frequency held by the UP/DOWN function for 5 s or more will be stored in the memory. This value will be stored in memory even if power is interrupted. When a RESET command is input, operation will start with this value as the frequency. If n62 is set to 0, the frequency will be cleared. If parameter initialization is performed (i.e.: n01 is set to 8 or 9), the stored frequency will be initialized. Note: If the UP/DOWN function is used in remote mode, frequency references can only be given with UP/DOWN commands and inching commands. Multi-step speed references will be invalid.

The UP/DOWN function uses UP and DOWN commands to change frequency references. When using the UP/DOWN function, set multi-function input 4 (n39) to 34 (UP or DOWN command). The terminals for multifunction input 3 (S4) and multi-function input 4 (S5) will be set to function in the following way: Multiple-function input 3 (S4): UP command Multiple-function input 4 (S5): DOWN command
Operation of UP/DOWN Function RUN command (Forward rotation) UP command (S4)

Time

Time DOWN command (S5) Time Output frequency Upper limit

Lower limit Time Status Frequency detection Status U: UP (acceleration) D: DOWN (deceleration) H: Hold U1: Frequency acceleration restricted by upper limit. D1: Frequency deceleration restricted by lower limit.

Time

20
Downloaded from www.Manualslib.com manuals search engine

Function of Each Parameter


Torque Compensation Gain (n63)
Set the gain of the torque compensation function. Note: Normally, the factory setting need not be changed.
Value n63 Name Torque Compensation Gain Setting range 0.0 to 2.5 Unit of setting 0.1 Default settings 1.0

Slip Compensation Functions (n64 to n67)


In n64, set the rated slip value of the motor in use. In n65, set the no-load current of the motor in use based on the rated motor current as 100%. In n66, set the gain of the slip compensation function. In n67, set the response speed of the slip compensation function.
Value n64 n65 n66 n67 Name Motor Rated Slip Motor No-load Current Slip Compensation Gain Slip Compensation Time Constant Setting range 0.0 to 20.0 0 to 99 0.0 to 2.5 0.0 to 25.5 Unit of setting 0.1 Hz 1% 0.1 0.1 s Default settings Varies ith th with the capacity. 0.0 2.0

Note: If 0.0 is set for n66, the slip compensation function will be disabled.

21
Downloaded from www.Manualslib.com manuals search engine

Specifications
Specifications
3p 3-phase 200 V AC 200-V models Model 3G3JVPower supply l Rated voltage and frequency Allowable voltage fluctuation Allowable frequency fluctuation Input power supply capacity (kVA) (see note 1) Heat radiation (W) (see note 2) Weight (kg) Cooling method S g p Single-phase 200 V AC 200-V models Model 3G3JVPower supply l Rated voltage and frequency Allowable voltage fluctuation Allowable frequency fluctuation Input power supply capacity (kVA) (see note 1) Heat radiation (W) (see note 2) Weight (kg) Cooling method A2001 15% to 10% 5% 0.4 13.0 0.5 0.9 18.0 0.5 1.6 28.1 0.8 2.7 45.1 0.9 Cooling fan AB002 AB004 AB007 AB015 ----4.3 72.8 1.3 5.9 94.8 1.5 9.3 149.1 2.1 A2002 A2004 A2007 A2015 A2022 A2037 3-phase 200 to 230 V AC at 50/60 Hz

Natural cooling AB001 15% to 10% 5% 0.5 14.1 0.5 0.9 20.0 0.5 1.6 31.9 0.9

Single-phase 200 to 240 V AC at 50/60 Hz

2.7 51.4 1.5

4.3 82.8 1.5 Cooling fan

-------

-------

Natural cooling

Note: 1. The power supply capacity, is the capacity when the Inverter is operating at its rated output. The value will vary with the impedance at the input power supply side. (Because the power factor of the input power supply changes, the power factor will improve if an AC reactor is inserted.) The ratio with the rated current of the motor used and the rated output current of the Inverter will vary. 2. The heat radiation is the power consumed in the Inverter when it is operating at its rated output.
Max. applicable motor capacity (kW) Output O p ifi ti specifications Rated output capacity (kW) Rated output current (A) Rated output voltage (V) Max. output frequency C Control characteristics h t i ti Harmonic-current countermeasures Control method Carrier frequency Frequency control range Frequency precision (temperature characteristics) Frequency setting resolution Output frequency resolution Overload capacity External frequency set signal Acceleration/deceleration time Braking torque Voltage/frequency characteristics Protective f functions ti Motor protection Instantaneous overcurrent protection Overload protection Overvoltage protection Undervoltage protection Momentary power interruption compensation (selection) Cooling fin overheating Grounding protection Charge indicator (RUN indicator) 0.1 0.3 0.8 0.2 0.6 1.6 0.4 1.1 3.0 0.75 1.9 5.0 1.5 3.0 8.0 2.2 4.2 11.0 3.7 6.7 17.5

3-phase 200 to 230 V AC (according to the input voltage) 400 Hz parameter setting DC reactor (option) connection possible Sine wave PWM (V/f control) 2.5 to 10.0 kHz (in vector control) 0.1 to 400 Hz Digital commands: 0.01% (10C to 50C) Analog commands: 0.5% (25C 10C) Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over) Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000) 0.01 Hz (calculated resolution) 150% of rated output current for 1 min Selectable with FREQ adjuster: 0 to 10 V DC (20 k), 4 to 20 mA (250 ), and 0 to 20 mA (250 ) 0.0 to 999 s (Independent acceleration and deceleration time settings) Approx. 20% Set a user V/f pattern Protection by electronic thermal Stops at approx. 250% of rated output current Stops in 1 min at approximately 150% of rated output current Stops when main-circuit DC voltage is approximately 410 V Stops when main-circuit DC voltage is approximately 200 V (160 V for single-phase 200-V AC model) Stops for 15 ms or more. By setting the Inverter to momentary power interruption mode, operation can be continued if power is restored within approximately 0.5 s. Detects at 110C 10C Protection at rated output current level Lit when the main circuit DC voltage is approximately 50 V or less.

22
Downloaded from www.Manualslib.com manuals search engine

Specifications
Environment Location Ambient temperature Ambient humidity Ambient temperature Altitude Insulation resistance Vibration resistance Degree of protection Indoors (with no corrosive gas, oil spray, or metallic dust) Operating: 10C to 50C Operating: 95% max. (with no condensation) 20C to 60C 1,000 m max. 5 M min. (Do not carry out any insulation resistance or withstand voltage tests) 9.8 m/s2 max. between 10 to 20 Hz 2.0 m/s2 max. between 20 and 50 Hz Panel-mounting models: Conforms to IP20

23
Downloaded from www.Manualslib.com manuals search engine

Specifications
3-phase 3 p 400 V AC 400-V models Model 3G3JVPower supply l Rated voltage and frequency Allowable voltage fluctuation Allowable frequency fluctuation Input power supply capacity (kVA) (see note 1) Heat radiation (W) (see note 2) Weight (kg) Cooling method A4002 15% to 10% 5% 1.3 23.1 1.0 Natural cooling 1.9 30.1 1.1 3.6 54.9 1.5 5.1 75.7 1.5 Cooling fan 5.9 83.0 1.5 9.1 117.9 2.1 A4004 A4007 A4015 A4022 A4037 3-phase 380 to 460 V AC at 50/60 Hz

Note: 1. The power supply capacity, is the capacity when the Inverter is operating at its rated output. The value will vary with the impedance at the input power supply side. (Because the power factor of the input power supply changes, the power factor will improve if an AC reactor is inserted.) The ratio with the rated current of the motor used and the rated output current of the Inverter will vary. 2. The heat radiation is the power consumed in the Inverter when it is operating at its rated output.
Max. applicable motor capacity (kW) O p Output specifications ifi ti Rated output capacity (kW) Rated output current (A) Rated output voltage (V) Max. output frequency Control C h t i ti characteristics Harmonic-current countermeasures Control method Carrier frequency Frequency control range Frequency precision (temperature characteristics) Frequency setting resolution Output frequency resolution Overload capacity External frequency set signal Acceleration/deceleration time Braking torque Voltage/frequency characteristics Protective f functions ti Motor protection Instantaneous overcurrent protection Overload protection Overvoltage protection Undervoltage protection Momentary power interruption compensation (selection) Cooling fin overheating Grounding protection Charge indicator (RUN indicator) Environment Location Ambient temperature Ambient humidity Ambient temperature Altitude Insulation resistance Vibration resistance Degree of protection 0.2 0.9 1.2 0.4 1.4 1.8 0.75 2.6 3.4 1.5 3.7 4.8 2.2 4.2 5.5 3.7 6.6 8.6

3-phase 380 to 460 V AC (according to the input voltage) 400 Hz parameter setting DC reactor (option) connection possible Sine wave PWM (V/f control) 2.5 to 10.0 kHz (in vector control) 0.1 to 400 Hz Digital commands: 0.01% (10C to 50C) Analog commands: 0.5% (25C 10C) Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over) Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000) 0.01 Hz (calculated resolution) 150% of rated output current for 1 min Selectable with FREQ adjuster: 0 to 10 V DC (20 k), 4 to 20 mA (250 ), and 0 to 20 mA (250 ) 0.0 to 999 s (Independent acceleration and deceleration time settings) Approx. 20% Set a user V/f pattern Protection by electronic thermal Stops at approx. 250% of rated output current Stops in 1 min at approximately 150% of rated output current Stops when main-circuit DC voltage is approximately 820 V Stops when main-circuit DC voltage is approximately 400 V Stops for 15 ms or more. By setting the Inverter to momentary power interruption mode, operation can be continued if power is restored within approximately 0.5 s. Detects at 110C 10C Protection at rated output current level Lit when the main circuit DC voltage is approximately 50 V or less. Indoors (with no corrosive gas, oil spray, or metallic dust) Operating: 10C to 50C Operating: 95% max. (with no condensation) 20C to 60C 1,000 m max. 5 M min. (Do not carry out any insulation resistance or withstand voltage tests) 9.8 m/s2 max. between 10 to 20 Hz 2.0 m/s2 max. between 20 and 50 Hz Panel-mounting models: Conforms to IP20

24
Downloaded from www.Manualslib.com manuals search engine

Specifications
Terminal Block
Position of Terminal Block
Ground terminal Main circuit input terminals

Control circuit terminals Main circuit output terminals Ground terminal

Arrangement of Control Circuit Terminals

Note: This illustration shows the terminal block with the front cover removed.

Main Circuit Terminals


Symbol R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 +1 +2 Connection terminals +1 and +2: DC reactor connection terminals +1 and : DC power supply input terminals Ground terminal Be sure to ground the terminal under the following conditions. 3G3JV-A2j: Ground at a resistance of 100 or less. 3G3JV-ABj: Ground at a resistance of 100 or less. 3G3JV-A4j: Ground at a resistance of 10 or less. Connect to a neutral point on the power supply to conform to EC Directives. Note Be sure to connect the ground terminal directly to the motor frame ground. Motor output terminals Name Power supply input terminals Description 3G3JV-A2j: 3-phase 200 to 230 V AC 3G3JV ABj: Single-phase 3G3JV-AB Si l h 200 to t 240 V AC 3G3JV-A4j: 3-phase 380 to 460 V AC Note Connect single-phase input to terminals R/L1 and S/L2. 3-phase power supply output for driving motors. 3G3JV-A2 3-phase 3G3JV A2j: 3 phase 200 to 230 V AC 3G3JV-ABj: 3-phase 200 to 240 V AC 3G3JV-A4j: 3-phase 380 to 460 V AC Note The maximum output voltage corresponds to the input power supply voltage for the Inverter. Connect the DC reactor for suppressing harmonics to terminals +1 and +2. When driving the Inverter with DC power, input the DC power to terminals +1 and . (Terminal +1 is a positive terminal.)

25
Downloaded from www.Manualslib.com manuals search engine

Specifications
Control Circuit Terminals
Symbol Input p S1 S2 S3 S4 S5 SC FS FR FC Output MA MB MC AM AC Name Forward/Stop Multi-function input 1 (S2) Multi-function input 2 (S3) Multi-function input 3 (S4) Multi-function input 4 (S5) Sequence input common Frequency reference power supply Frequency reference input Frequency reference common Multi-function contact output (Normally open) Multi-function contact output (Normally closed) Multi-function contact output common Analog monitor output Analog monitor output common Function Forward at ON. Stops at OFF. Set by parameter n36 (Reverse/Stop) Set by parameter n37 (Fault reset) Set by parameter n38 (External fault: Normally open) Set by parameter n39 (Multistep reference 1) Common for S1 through S5 DC power supply for frequency reference use Input terminal for frequency reference use Common for frequency reference use Set by parameter n40 (during u g) running) Signal level Photocoupler p 8 mA A at 24 V DC ( (see note 2)

20 mA at 12 V DC 0 to 10 V DC (Input ( pu impedance peda ce = 20 0 k)

Relay output a a C 1 A max. at 30 V DC 1 A max. at 250 V AC C

Common for MA and MB use Set by parameter n44 (Output frequency) Common for AM use 2 mA max. at 0 to 10 V DC

Note: 1. Functions in parentheses are default settings. 2. The input method is set to NPN by default, so use the GND common for wiring. An external power supply is not required. When a power supply is used and a common on the plus side is used for wiring, set SW7 to PNP and use a 24-V DC (10%) power supply.

26
Downloaded from www.Manualslib.com manuals search engine

Dimensions
Dimensions
3G3JV-A2001 to 3G3JV-A2007 (0.1 to 0.75 kW) 3-phase 200-V AC Input 3G3JV-AB001 to 3G3JV-AB004 (0.1 to 0.4 kW) Single-phase 200-V AC Input 3G3JV-A2015 to 3G3JV-A2022 (1.5 to 2.2 kW) 3-phase 200-V AC Input 3G3JV-AB007 to 3G3JV-AB015 (0.75 to 1.5 kW) Single-phase 200-V AC Input 3G3JV-A4002 to 3G3JV-A4022 (0.2 to 2.2 kW) 3-phase 400-V AC Input
Two, 5-dia. holes

Rated voltage

Model 3G3JV3G3JV A2001 A2002 A2004 A2007

Dimensions (mm) D t 3 3 5 5 3 3 5 70 70 102 122 70 70 112

Weight (kg)

Rated voltage

Model 3G3JV3G3JV A2015 A2022 AB007 AB015 A4002 A4004 A4007 A4015 A4022

Dimensions (mm) D 129 154 129 154 81 99 129 154 154

Weight (kg)

3-phase 200 V AC p

Approx. 0.5 Approx. 0.5 Approx. 0.8 Approx. 0.9 Approx. 0.5 Approx. 0.5 Approx. 0.9

3-phase p 200 V AC Single-phase g p 200 V AC 3-phase p 400 V AC

Approx. 1.3 Approx. 1.5 Approx. 1.5 Approx. 1.5 Approx. 1.0 Approx. 1.1 Approx. 1.5 Approx. 1.5 Approx. 1.5

Single-phase 200 V AC g p

AB001 AB002 AB004

3G3JV-A2037 (3.7 kW) 3-phase 200-V AC Input 3G3JV-A4037 (3.7 kW) 3-phase 400-V AC Input

Rated voltage

Model 3G3JV3G3JV A2037 A4037

Dimensions (mm) D 161 161

Weight (kg)

3-phase 200 V AC 3-phase 400 V AC

Approx. 2.1 Approx. 2.1

27
Downloaded from www.Manualslib.com manuals search engine

Standard Connections
Standard Connections
DC reactor (optional) Noise Filter

3-phase 200 V AC Single-phase 200 V AC (see note 1) 3-phase 400 V AC

Forward/Stop
Multi-function input 1 (S2) Multi-function input 2 (S3)

Multi-function contact output NO NC Common

Multi-function input 3 (S4) Multi-function input 4 (S5)

Sequence input common Frequency reference power supply 20 mA at +12 V FREQ adjuster (2 k, 1/4 W min.) Frequency reference input Frequency reference common

Analog monitor output Analog monitor output common

Note: 1. Connect single-phase 200 V AC to terminals R/L1 and S/L2 of the 3G3JV-ABj. 2. The braking resistor cannot be connected because no braking transistor is incorporated.

Input Method Selection


Switches SW7 and SW8, both of which are located above the control circuit terminals, are used for input method selection. Remove the front cover and optional cover to use these switches.

Selector

Control circuit terminal block

Sequence Input Method Selection


By using SW7, NPN or PNP input can be selected as shown below.
24 V

(Factory setting)

S1 to 5 24 V DC (10%)

S1 to 5

Frequency Reference Input Method Selection


By using SW8, frequency reference voltage or current input can be selected. Parameter settings are required together with the selection of the frequency reference input method.
Frequency reference input method Voltage input Current input V (OFF) I (ON) SW8 setting Frequency reference selection (parameter n03) Set value 2 Set value 3 or 4

28
Downloaded from www.Manualslib.com manuals search engine

Protective and Diagnostic Functions


Fault Detection (Fatal Error)
The Inverter will detect the following faults if the Inverter or motor burns or the internal circuitry of the Inverter malfunctions. When the Inverter detects a fault, the fault code will be displayed on the Digital Operator, the fault contact output will operate, and the Inverter output will be shut off causing the motor to coast to a stop. The stopping method can be selected for some faults, and the selected stopping method will be used with these faults. If a fault has occurred, refer to the following table to identify and correct the cause of the fault. Use one of the following methods to reset the fault after restarting the Inverter. If the operation command is being input, however, the reset signal will be ignored. Therefore, be sure to reset the fault with the operation command turned off. Turn on the fault reset signal. A multi-function input (n36 to n39) must be set to 5 (Fault Reset). Press the STOP/RESET Key on the Digital Operator. Turn the main circuit power supply off and then on again.

Fault Displays and Processing


Fault display %c Fault name and meaning Overcurrent (OC) The Inverter output current is as high as or higher than 200% of the rated output current. Probable cause and remedy A short-circuit or ground fault has occurred and at the Inverter output. Check and correct the motor power cable. Reduce the V/f set voltage. Reduce the motor capacity to the maximum permissible motor capacity. Rearrange the sequence so that the magnetic contactor will not open or close while the Inverter has current output. Replace the Inverter. Increase the deceleration time. Decrease the voltage so it will be within specifications. Suppress the overshooting as much as possible. The V/f setting is incorrect. The motor capacity is too large for the Inverter. The magnetic contactor on the output side of the Inverter has been opened and closed.

The output circuit of the Inverter is damaged. %U Overvoltage (OV) The main circuit DC voltage has reached the overvoltage detection level (200-V models: 410 V DC min.; 400-V models: 820 V DC min.). uU1 Main circuit undervoltage (UV1) The main circuit DC voltage has reached the undervoltage detection level (200 V DC for the 3G3JV-A2j, 160 V DC for the 3G3JV-ABj, and 400 V DC for the 3G3JV-A4j). The deceleration time is too short. The power supply voltage is too high. There is excessive regenerative energy due to overshooting at the time of acceleration. Power supply to the Inverter has phase loss, power input terminal screws are loose, or the power cable is disconnected. %h Radiation fin overheated (OH) The temperature of the radiation fins of the Inverter has reached 110_C 10_C. Check the above and take necessary countermeasures. Make sure that the power supply voltage is within specifications. Use the momentary power interruption compensation (Set n47 so that the Inverter restarts after power is restored) Improve the power supply. Change the Inverter. Ventilate the Inverter or install a cooling unit. Reduce the load. Decrease the Inverter capacity. Reduce the V/f set voltage. Increase the acceleration/deceleration time. Change the location of the Inverter to meet the installation conditions. Replace the cooling fan. Incorrect power supply voltage Momentary power interruption has occurred.

The internal circuitry of the Inverter is damaged. The ambient temperature is too high. The load is excessive.

The V/f setting is incorrect. The acceleration/deceleration time is too short. The ventilation is obstructed. The cooling fan of the Inverter does not work.

29
Downloaded from www.Manualslib.com manuals search engine

Protective and Diagnostic Functions


Fault display %l1 Fault name and meaning Motor overload (OL1) The electric thermal relay actuated the motor overload protective function. The load is excessive. Reduce the load. Decrease the Inverter capacity. Reduce the V/f set voltage. Check the motor nameplate and set n11 to the rated frequency. Increase the acceleration/deceleration time. Check the motor nameplate and set n32 to the rated current. Disable the motor overload detection function and install an electronic thermal relay for each of the motors. The motor overload detection function is disabled by setting n32 to 0.0 or n33 to 2. Set n34 to 8 (the default value). Reduce the load. Reduce the V/f set voltage. Increase the acceleration/deceleration time. Use an Inverter model with a higher capacity. Check the mechanical system and correct the cause of overtorque. Adjust the n60 and n61 parameters according to the mechanical system. Increase the set values in n60 and n61. Probable cause and remedy

The V/f setting is incorrect. The value in n11 for maximum voltage frequency is low. The acceleration/deceleration time is too short. The value in n32 for rated motor current is incorrect. The Inverter is driving more than one motor.

The motor protective time setting in n34 is short. %l2 Inverter overload (OL2) The electronic thermal relay has actuated the Inverter overload protective function. %l3 Overtorque detection (OL3) There has been a current or torque the same as or greater than the setting in n60 for overtorque detection level and that in n61 for overtorque detection time. A fault has been detected with n59 for overtorque detection function selection set to 2 or 4. gf Ground fault (GF) The ground fault current at the output of the Inverter has exceeded the rated output current of the Inverter. efj External fault j (EFj) An external fault has been input from a multi-function input. A multi-function input 1, 2, 3, or 4 set to 3 or 4 has operated. The EF number indicates the number of the corresponding input (S2 to S5). f00 Digital Operator transmission fault 1 (F00) An initial memory fault has been detected f01 Digital Operator transmission fault 2 (F01) A ROM fault has been detected. f04 Initial memory fault (F04) An error in the built-in EEPROM of the Inverter has been detected. f05 Analog-to-digital converter fault (F05) An analog-to-digital converter fault has been detected. f07 Digital Operator fault (F07) An error in the built-in control circuit of the Digital Operator has been detected. The load is excessive. The V/f setting is incorrect. The acceleration/deceleration time is too short. The Inverter capacity is insufficient. The mechanical system is locked or has a failure. The parameter settings were incorrect.

A ground fault has occurred at the Inverter output. Check the connections between the Inverter and motor and reset the fault after correcting its cause.

An external fault was input from a multi-function input. Remove the cause of the external fault. Check and change the external fault input sequence including the input timing and NO or NC contact. The sequence is incorrect.

The internal circuitry of the Inverter has a fault. Turn the Inverter off and on. Replace the Inverter if the same fault occurs again.

The internal circuitry of the Inverter has a fault. Turn the Inverter off and on. Replace the Inverter if the same fault occurs again. Initialize the Inverter with n01 set to 8 or 9 and turn the Inverter off and on. Replace the Inverter if the same fault occurs again. Turn the Inverter off and on. Replace the Inverter if the same fault occurs again.

The internal circuitry of the Inverter has a fault.

The internal circuitry of the Inverter has a fault.

The internal circuitry of the Digital Operator has a fault. Turn the Digital Operator off and on. Replace the Digital Operator if the same fault occurs again.

30
Downloaded from www.Manualslib.com manuals search engine

Protective and Diagnostic Functions


Fault display ce Fault name and meaning Communications time-over (CE) Normal RS-422A/485 communications were not established within 2 s. The Inverter will detect this error if n68 (RS-422A/485 communications time-over detection selection) is set to 0, 1, or 2. Check and correct the line. Set the termination resistance of only the Inverter located at each end of the network to ON. Do not wire the communications line along with power lines in the same conduit. Use the twisted-pair shielded wire for the communications line, and ground it at the Master. Check and correct the program so that communications will be performed more than once every 2-s period. If the same error is detected as a result of a self-diagnostic test, change the Inverter. Remove the cause of the fault. Check and change the external fault input sequence including the input timing and NO or NC contact. Probable cause and remedy A short-circuit, ground fault, or disconnection has occurred on the communications line. The termination resistance setting is incorrect. Noise influence.

Masters program error.

Communications circuit damage. Emergency stop (STP) An emergency stop alarm is input to a multi-function input. (A multi-function input 1, 2, 3, or 4 set to 19 or 21 has operated.) OFF Power supply error Insufficient power supply voltage Control power supply fault Hardware fault An emergency stop alarm is input to a multi-function input. The sequence is incorrect.

No power supply is provided. Check and correct the power supply wire and voltage. Check and tighten the terminal screws. Replace the Inverter. Terminal screws are loosened. The Inverter is damaged.

Warning Detection (Nonfatal Error)


The warning detection is a type of Inverter protective function that does not operate the fault contact output and returns the Inverter to its original status once the cause of the error has been removed. The Digital Operator flashes and display the detail of the error. If a warning occurs, take appropriate countermeasures according to the table below. Note: Some warnings or some cases stop the operation of the Inverter as described in the table.
Fault display uU (flashing) Warning name and Meaning Main Circuit Undervoltage (UV) The main circuit DC voltage has reached the undervoltage detection level (200 V DC for the 3G3JV-A2j, 160 V DC for the 3G3JV-ABj, and 400 V DC for the 3G3JV-A4j). Main Circuit Overvoltage The main circuit DC voltage has reached the overvoltage detection level (200-V models: 410 V DC min.; 400-V models: 820 V DC min.). Radiation fin overheated (OH) The temperature of the radiation fins of the Inverter has reached 110_C 10_C. Communications standby (CAL) No normal DSR message has been received during RS-422A/4895 communications. The Inverter detects this warning only when RUN command selection (n02) is set to 2 or frequency reference selection (n03) is set to 6. Until the warning is reset, no input other than communications input will be ignored. Overtorque detection (OL3) There has been a current or torque the same as or greater than the setting in n60 for overtorque detection level and that in n61 for overtorque detection time. A fault has been detected with n59 for overtorque detection function selection set to 1 or 3. Probable cause and remedy Power supply to the Inverter has phase loss, power input terminal screws are loose, or the power line is disconnected. Check the above and take necessary countermeasures. Make sure that the power supply voltage is within specifications. Incorrect power supply voltage The power supply voltage is too high. Decrease the voltage so it will be within specifications.

%U (flashing)

%h (flashing)

The ambient temperature is too high. Ventilate the Inverter or install a cooling unit.

cal (flashing)

A short-circuit, ground fault, or disconnection has occurred on the communications line. Check and correct the line. Set the termination resistance of only the Inverter located at each end of the network to ON. Check the start of communications and correct the program. If a CAL or CE error is detected as a result of a self-diagnostic test, change the Inverter. Check the mechanical system and correct the cause of overtorque. Adjust the n60 and n61 parameters according to the mechanical system. Increase the set values in n60 and n61. The termination resistance setting is incorrect. Masters program error. Communications circuit damage. The mechanical system is locked or has a failure. The parameter settings were incorrect.

%l3 (flashing)

31
Downloaded from www.Manualslib.com manuals search engine

Protective and Diagnostic Functions


Fault display ser (flashing) Warning name and Meaning Sequence error (SER) A sequence change has been input while the Inverter is in operation. Local or remote selection is input while the Inverter is in operation. Note The Inverter coasts to a stop. bb (flashing) External base block (bb) The external base block command has been input. Note The Inverter coasts to a stop. The external base block command has been input as multi-function input. Remove the cause of external base block input. Check and change the external fault input sequence including the input timing and NO or NC contact. The sequence is incorrect. A sequence error has occurred. Check and adjust the local or remote selection sequence as multi-function input. Probable cause and remedy

ef (flashing)

Forward- and reverse-rotation input (EF) The forward and reverse commands are input to the control circuit terminals simultaneously for 0.5 s or more. Note The Inverter stops according to the method set in n04. Emergency stop (STP)

A sequence error has occurred. Check and adjust the local or remote selection sequence.

The parameter setting was incorrect. Turn off the forward or reverse command once, check that the n06 parameter setting for STOP/RESET Key function selection, and restart the Inverter.

(flashing)

The Digital Operator stops operating. The STOP/RESET Key on the Digital Operator is pressed while the Inverter is operating according to the forward or reverse command through the control circuit terminals. Note The Inverter stops according to the method set in n04. The emergency stop alarm signal is input as multi-function input. A multi-function input 1, 2, 3, or 4 set to 20 or 22 has been used. Note The Inverter stops according to the method set in n04.

An emergency stop alarm is input to a multi-function input. Remove the cause of the fault. Check and change the external fault input sequence including the input timing and NO or NC contact. The sequence is incorrect.

fRn (flashing)

Cooling fan fault (FAN) The cooling fan has been locked.

The cooling fan wiring has a fault. Turn off the Inverter, dismount the fan, and check and repair the wiring. Check and remove the foreign material or dust on the fan. Replace the fan. Check and correct the line. Set the termination resistance of only the Inverter located at each end of the network to ON. Do not wire the communications line along with power lines in the same conduit. Use the twisted-pair shielded wire for the communications line, and ground it at the Master. Check and correct the program so that communications will be performed more than once every 2-s period. If the same error is detected as a result of a self-diagnostic test, change the Inverter. The cooling fan in not in good condition. The cooling fan is beyond repair.

ce

Communications time-over (CE) Normal RS-422A/485 communications were not established within 2 s. The Inverter will detect this error if n68 (RS-422A/485 communications time-over detection selection) is set to 0, 1, or 2.

A short-circuit, ground fault, or disconnection has occurred on the communications line. The termination resistance setting is incorrect. Noise influence.

Masters program error.

Communications circuit damage.

32
Downloaded from www.Manualslib.com manuals search engine

Protective and Diagnostic Functions


Fault display %p1 (flashing) %p2 (flashing) %p3 (flashing) %p4 (flashing) Warning name and Meaning Operation error (OPj) (Parameter setting ( g error) ) Probable cause and remedy The values in n36 through n39 for multi-function inputs 1 through 4 have been duplicated. Check and correct the values. The V/f pattern settings do not satisfy the following condition. n14 x n12 t n11x n09 Check and correct the set value. The rated motor current set in n32 exceeds 150% of the rated output current of the Inverter. Check and correct the value. The frequency reference upper limit set in n30 and the frequency reference lower limit set in n31 do not satisfy the following condition. n30 y n31 %p5 (flashing) Check and correct the set values. The jump frequencies set n49, n50 do not satisfy the following condition. n49 y n50 Check and correct the set values.

33
Downloaded from www.Manualslib.com manuals search engine

Options
Overview of Options
Power Supply 3G3JV-A2j: 3-phase 200 V AC 3G3JV-ABj: single-phase 200 V AC (connect to R/L1, S/L2) 3G3JV-A4j: 3-phase 400 V AC
Molded case circuit breaker or leakage breaker

Supplied by the customer

Electromagnetic contactor Suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much larger than that of the Inverter. Recommended Option AC Reactor 3G3IV-PUZBABj Recommended Option Input Noise Filter

Supplied by the customer

Eliminates noise in the power line connected to the Inverter and suppresses noise leaking from the Inverter to the power line. There are 2 types available: the EMC-conforming Input Noise Filter and the Simple Input Noise Filter.

Simple Input Noise Filter 3G3EV-PLNFDj R/L1 Dedicated Option DC Reactor 3G3HV-PUZDABj +1 +2 S/L2 T/L3 Dedicated Option
DIN Track Mounting Bracket 3G3IV-PEZZ08122j

Suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter.

An adapter making it possible to easily mount the Inverter to DIN tracks.

Separately Mounted Option

Process Meter K3MA-J U/T1 V/T2 W/T3

Mounted Option Fan Unit 3G3IV-PFANj Replacement for the existing cooling fan of the Inverter.

Recommended Option Output Noise Filter 3G3IV-PLFj Dedicated Option


Adapter Panel 3G3JV-PSI232J (permanent) 3G3JV-PSI232JC (removable) + Digital Operator 3G3IV-PJVOP146 3G3IV-PJVOP140+ 3G3IV-PEZZ08386 (Digital Operator Case) + Digital Operator Connection Cable 3G3IV-PCN126 (1 m) 3G3IV-PCN326 (3 m)
An Adapter Panel is required as an interface to connect a Digital Operator (3G3IV-PJVOP140 or 3G3IV-PJVOP146) to the 3G3JV Inverter. There are two models of Adapter Panel available. The 3G3JV-PSI232J is permanently installed and cannot be removed and the 3G3JV-PSI232JC for copying parameters is installed so that it can be removed.

Connect this Filter to the output side of the Inverter to suppress the noise generated by the Inverter from being transmitted to the output line.

Dedicated Option RS-422/485 Communications Unit 3G3JV-PSI485J 3-phase Inductive Motor


The RS-422/485 Communications Unit (3G3JVPSI485J) functions as an interface for RS-422/485 general-purpose communications. The communications protocol conforms to MODBUS (same protocol as 3G3MV and 3G3RV Inverters). Communications can be used for Inverter control inputs, frequency references, monitoring Inverter operating status, and reading/writing parameter settings.

34
Downloaded from www.Manualslib.com manuals search engine

Options
Mounted Option
Name Model Description Reference page 36

Fan Unit

3G3IV-PFANj

Replacement for the existing cooling fan of the Inverter. Replace the cooling fan if it has reached the end of its service life or a warning of cooling fan failure (FAN) is indicated.

Separately Mounted Option


Name Model Description Reference page 36

Process Meter

K3MA-J

Connected to the multi-function analog output of the Inverter. Displays the rpm or speed of the machine or line in actual units.

Dedicated Options
Name Model Description Reference page 37 38 39

DC Reactor DIN Track Mounting Bracket Adapter Panel

3G3HV-PUZDABj 3G3IV-PEZZ08122j 3G3JV-PSI232J (permanent) 3G3JV-PSI232JC (removable) 3G3IV-PJVOP146 3G3IV-PJVOP140+ 3G3IV-PEZZ08386A (Digital Operator Case)

Suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter. An adapter making it possible to easily mount the Inverter to DIN tracks. An Adapter Panel is required as an interface to connect a Digital Operator (3G3IV-PJVOP140 or 3G3IV-PJVOP146) to the 3G3JV Inverter. There are two models of Adapter Panel available. The 3G3JV-PSI232J is permanently installed and cannot be removed and the 3G3JV-PSI232JC for copying parameters is installed so that it can be removed. The Digital Operator is used to control the Inverter from a distance. There are two models available. The 3G3IV-PJVOP140 is equipped with an adjuster and the 3G3IV-PJVOP146 is not. Always use the 3G3IV-PJVOP140 together with a Digital Operator Case. Without the Case, the Digital Operators connection cable cannot be wired. Using the Case also enables mounting to a control panel. The Digital Operator Connection Cable is required to connect a Digital Operator to a 3G3JV Inverter. The RS-422/485 Communications Unit (3G3JV-PSI485J) functions as an interface for RS-422/485 general-purpose communications. The communications protocol conforms to MODBUS (same protocol as 3G3MV and 3G3RV Inverters). Communications can be used for Inverter control inputs, frequency references, monitoring Inverter operating status, and reading/writing parameter settings.

Digital Operator

40

Digital Operator Connection Cable RS-422/485 Communications Unit

3G3IV-PCN126 (1 m) 3G3IV-PCN326 (3 m) 3G3JV-PSI485J

41 41

Recommended Options
Name Model Description Reference page 42

AC Reactor (Yaskawa Electric) EMC-conforming Input Noise Filter (Rasmi) Simple Input Noise Filter (Yaskawa Electric) Output Noise Filter (Tokin)

3G3IV-PUZBABj

Suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much larger than that of the Inverter. A Noise Filter on the input side meeting the EC Directives EMC requirements. Each of these Filters connected to the power input side eliminates noise in the power line connected to the Inverter and suppresses noise leaking from the Inverter to the power line. Connect this Filter to the output side of the Inverter to suppress the noise generated by the Inverter from being transmitted to the output line.

3G3JV-PRSj 3G3EV-PLNFDj

43 45

3G3IV-PLFj

46

35
Downloaded from www.Manualslib.com manuals search engine

Options
Fan Unit
3G3IV-PFANj
The Fan Unit is a replacement for the presently installed cooling fan of the Inverter. Replace the cooling fan if it has reached the end of its service life or a warning of cooling fan failure (FAN) is indicated.
Inverter 3-phase 200 3 p 00 V AC C 3G3JV-A2007 3G3JV-A2015/-A2022 3G3JV-A2037 Single-phase 200 V AC 3-phase 3 p 400 00 V AC C 3G3JV-AB015 3G3JV-A4015/-A4022 3G3JV-A4022 3G3JV-A4037 3G3IV-PFAN2037 3G3IV-PFAN2007 3G3IV-PFAN2015J 3G3IV-PFAN2037 3G3IV-PFAN2015J 3G3IV-PFAN2015J 3G3 0 5J Fan Unit

Process Meter
K3MA-J
The Process Meter is connected to the analog monitor output of the Inverter to display the rpm and speed values of machines and lines in actual units.

Models and Applications


Input p type yp Output O p type yp Power supply voltage 100 to 240 V AC (50/60 Hz) DC voltage/ current inputs None Relay: 2SPST-NO K3MA-J: 100 to 240 V AC K3MA-J-A2, 100 to 240 V AC 24 V AC (50/60 Hz), 24 V DC K3MA-J: 24 V AC/DC K3MA-J-A2, 24 V AC/DC

Standard Specifications
Input signals A/D conversion Input impedance Sampling period Display refresh period Max. displayed digits Display type Sign display Zero suppression (leftmost digits) Scaling DC voltage/current (0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V, 10 V) Double integral method Current input: 45 max.; voltage input: 1 M min. 250 ms Sampling period (with average value processing: Sample period x No. of averages) 5 (19,999 to 99,999) 7-segment digital display Minus sign () displayed automatically for negative input signals. Supported Programmed (The displayed range corresponds to the maximum number of displayed digits.) The decimal point position can be set as required. Memory protection Hold functions Comparative output hysteresis Other functions Maximum value hold, minimum value hold Programmed with front-panel keys (0001 to 9999) Forcedzero by front-panel keys, zero reset, scaling teaching, display color switching (green [red], green, red [green], red), comparative output switching (upper limit, lower limit, upper/lower limits), average value processing (simple averaging: OFF, 2, 4, or 8 times) Relay: DPST-NO 750 ms max. Front panel: NEMA4X for indoor use (equivalent to IP66), Rear case: IP20 Terminals: IP00 + finger protection (VDE0106/100) Nonvolatile memory (100,000 overwrites)

Output form Comparative output response time Enclosure ratings

Wiring Example
Circuit breaker Three- for wiring phase power supply Inverters internal circuitry Analog output Analog monitor
10 to +10 V DC

Dimensions (mm)
Terminal cover (included)

Recommended panel cutout

Terminals: M3, Terminal cover included. Main display LED size

36
Downloaded from www.Manualslib.com manuals search engine

Options
DC Reactor
3G3HV-PUZDABj
The DC Reactor suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter. The DC Reactor suppresses harmonic current more effectively than the AC Reactor. Furthermore, the DC Reactor can be used in combination with the AC Reactor. Used with 3-phase or single-phase 200-V AC Inverters, or 3-phase 400-V AC Inverters.

Applicable Models
Inverter Voltage class 200 V 400 V Max. applicable motor capacity (kW) 0.1 to 0.75 1.5 to 3.7 0.2 to 0.75 1.5 to 2.2 3.7 Model 3G3HV-PUZDAB5.4A8MH 3G3HV-PUZDAB18A3MH 3G3HV-PUZDAB3.2A28MH 3G3HV-PUZDAB5.7A11MH 3G3HV-PUZDAB12A6.3MH 800 V DC DC Reactor Rated voltage (V) 800 V DC Rated current (A) 5.4 18 3.2 5.7 12 Inductance (mH) 8 3 28 11 6.3 8 18 9 11 16 Loss (W)

External Dimensions (mm)


External Dimensions 1 External Dimensions 2
Two, d2 mounting holes

Two, d1 mounting holes Four, d1 mounting holes

Model 3G3HVPUZDABj 5.4A8MH 18A3MH 3.2A28MH 5.7A11MH 12A6.3MH

External dimensions di i 1 2 1 1 2 53 76 53 60 76

Dimension (mm) H 85 86 85 90 86 W 74 60 74 80 60 W1 60 72 60 60 72 D 32 55 32 32 55 D1 --80 ----80 D2 0.8 1.2 0.8 0.8 1.2 t d1 M4 M4 M4 M4 M4 --M5 ----M5 d2

Weight g (k ) (kg) 0.8 2.0 0.8 1.0 2.0

37
Downloaded from www.Manualslib.com manuals search engine

Options
DIN Track Mounting Bracket
3G3IV-PEZZ08122j
An adapter making it possible to easily mount the Inverter to DIN tracks.

Applicable Models
Inverter 3-phase 3 p 200 00 V AC C 3G3JV-A2001/-A2002/-A2004/-A2007 3G3JV-A2015/-A2022 3G3JV-A2037 Single-phase S g p 200 00 V AC C 3-phase 3 p 400 00 V AC C 3G3JV-AB001/-AB002/-AB004 3G3JV-AB007/-AB015 3G3JV-A4002/-A4004/-A4007/-A4015/-A4022 3G3JV-A4037 DIN Track Mounting Bracket 3G3IV-PEZZ08122A 3G3IV-PEZZ08122B 3G3IV-PEZZ08122C 3G3IV-PEZZ08122A 3G3IV-PEZZ08122B 3G3IV-PEZZ08122B 3G3IV-PEZZ08122C

External Dimensions (mm)


3G3IV-PEZZ08122A 3G3IV-PEZZ08122B

DIN track

Four, M4 tap

Four, M4 tap

3G3IV-PEZZ08122C

Four, M4 tap

38
Downloaded from www.Manualslib.com manuals search engine

DIN track

(35.1)

(35.1)

Options
Adapter Panel
3G3JV-PSI232Jj
An Adapter Panel is required as an interface to connect a Digital Operator (3G3IV-PJVOP140 or 3G3IV-PJVOP146) to the 3G3JV Inverter. There are two models of Adapter Panel available. The 3G3JV-PSI232J is permanently installed and cannot be removed and the 3G3JV-PSI232JC for copying parameters is installed so that it can be removed.

Connections
3G3JV Inverter Adapter Panel 3G3JV-PSI232J (permanent) 3G3JV-PSI232JC (removable) Digital Operator 3G3IV-PJVOP146 3G3IV-PJVOP140 + 3G3IVPEZZ08386A (Digital Operator Case)

Digital Operator Connection Cable 3G3IV-PCN126 (1 m) 3G3IV-PCN326 (3 m)

External Dimensions (mm)


3G3JV-PSI232J (Permanent)

3G3JV-PSI232JC (Removable)

39
Downloaded from www.Manualslib.com manuals search engine

Options
Digital Operator
3G3IV-PJVOP140/PJVOP146
The Digital Operator (3G3IV-PJVOP140/PJVOP146) is used to control the Inverter from a distance. There are two models available. The 3G3IV-PJVOP140 is equipped with an adjuster and the 3G3IV-PJVOP146 is not. Always use the 3G3IV-PJVOP140 together with a Digital Operator Case (3G3IV-PEZZ08386A). Without the Case, the Digital Operators connection cable cannot be wired. Using the Case also enables mounting to a control panel. Note: When a Digital Operator is connected, the Operator on the Inverter cannot be used to control operation (i.e., only display functions will work).

3G3IV-PJVOP140 (with Adjuster)


8 max.

3.6 dia

3G3IV-PJVOP146 (without Adjuster)


Four, 4.4-dia. mounting holes

Four depressions for M4 bolts (Depth: 3.5)

40
Downloaded from www.Manualslib.com manuals search engine

Options
Digital Operator Case
3G3IV-PEZZ08386A
The Digital Operator Case (3G3IV-PEZZ08386A) is used to secure the 3G3IV-PJVOP140 Digital Operator. Without this Case, the Digital Operators connection cable cannot be wired. Always use the 3G3IV-PJVOP140 and the Digital Operator Case together.
Four, 4.4-dia. mounting holes

Four depressions for M4 bolts (Depth: 3.5)

Digital Operator Connection Cable


3G3IV-PCN126/PCN326
The Digital Operator Connection Cable (3G3IV-PCN126/PCN326) is required to connect a Digital Operator to a 3G3JV Inverter.

Models and Specifications


Digital Operator Connection Cable 3G3IV-PCN126 3G3IV-PCN326 1m 3m Cable length

RS-422/485 Communications Unit


3G3JV-PSI485J
The RS-422/485 Communications Unit (3G3JV-PSI485J) functions as an interface for RS-422/485 general-purpose communications. The communications protocol conforms to MODBUS (same protocol as 3G3MV and 3G3RV Inverters). Communications can be used for Inverter control inputs, frequency references, monitoring Inverter operating status, and reading/writing parameter settings.

External Dimensions (mm)

41
Downloaded from www.Manualslib.com manuals search engine

Options
AC Reactor
3G3IV-PUZBABj (Yaskawa Electric)
The AC Reactor suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much larger than that of the Inverter. Select the AC Reactor model from the following table according to the motor capacity. Note: The AC Reactor can be used with either 3-phase or single-phase 200-V AC Inverters.

Connection Example
MCCB AC Reactor Motor

Applicable Range
AC Reactor required for smooth operation under present power supply conditions Power supply capacity (kVA) AC Reactor not required

Inverter capacity (kVA)

Applicable Models and Dimensions


200-V Class
Max. applicable motor capacity (kW) 0.1 to 0.2 0.4 0.75 1.5 2.2 3.7 Model 3G3IVPUZBABj 2A7.0MH 2.5A4.2MH 5A2.1MH 10A1.1MH 15A0.71MH 20A0.53MH Current (A) Inducta nce (mH) 7.0 4.2 2.1 1.1 0.71 0.53 8 15 15 25 30 35 Loss (W) Weight (kg) A 2.5 2.5 2.5 3 3 3 120 120 120 130 130 130 B 71 71 71 88 88 88 B1 ----------114 C 115 120 120 130 130 105 D 40 40 40 50 50 50 Dimension (mm) E 50 50 50 65 65 65 F 105 105 105 130 130 130 H 20 20 20 22 22 22 J M6 M6 M6 M6 M6 M6 K 10.5 10.5 10.5 11.5 11.5 11.5 7 7 7 7 7 7 L M M4 M4 M4 M4 M4 M5

2 2.5 5 10 15 20

400-V Class
Max. applicable motor capacity (kW) 0.2 to 0.4 0.75 1.5 2.2 3.7 Model 3G3IVPUZBABj 1.3A18.0MH 2.5A8.4MH 5A4.2MH 7.5A3.6MH 10A2.2MH Current (A) Inducta nce (mH) 18.0 8.4 4.2 3.6 2.2 Loss (W) Weight (kg) A 15 15 25 35 43 2.5 2.5 3 3 3 120 120 130 130 130 B 71 71 88 88 88 B1 ----------C 120 120 130 130 130 D 40 40 50 50 50 Dimension (mm) E 50 50 70 70 65 F 105 105 130 130 130 H 20 20 22 22 22 J M6 M6 M6 M6 M6 K 10.5 10.5 9 9 11.5 7 7 7 7 7 L M M4 M4 M4 M4 M4

1.3 2.5 5 7.5 10

External dimensions for AC Reactors are shown below. External Dimensions 2 shows the dimensions of the 200-V-class AC Reactor for 3.7-kW motors. External Dimensions 1 shows the dimensions of all other models.

External Dimensions 1

M Terminal

External Dimensions 2

M Terminal

Nameplate

Nameplate

Mounting Dimensions Mounting Dimensions 4-J mounting bolt 4-J mounting bolt

42
Downloaded from www.Manualslib.com manuals search engine

Options
EMC-conforming Input Noise Filter
3G3JV-PRSj (Rasmi)
The Input Noise Filter is connected between the power supply input terminals (R/L1, S/L2, T/L3) of the Inverter and the power supply in order to meet the EC Directives EMC requirements.

Connection Example

MCCB

Noise Filter

Clamp core

3-phase 200 V AC, single-phase 200 V AC, or 3-phase 400 V AC

Applicable Models
Inverter Voltage 3-phase 200 3 p 00 V AC C Model 3G3JV-A2001/-A2002/-A2004/-A2007 3G3JV-A2015/-A2022 3G3JV-A2037 Single-phase 200 S g p 00 V AC C 3-phase 3 p 400 00 V AC C 3G3JV-AB001/-AB002/-AB004 3G3JV-AB007/-AB015 3G3JV-A4002/-A4004 3G3JV-A4007/-A4015/-A4022 3G3JV-A4037 Model 3G3JV-PRS2010J 3G3JV-PRS2020J 3G3JV-PRS2030J 3G3JV-PRS1010J 3G3JV-PRS1020J 3G3JV-PRS3005J 3G3JV-PRS3010J 3G3JV-PRS3020J 10 16 26 10 20 5 10 15 EMC-conforming Input Noise Filter Rated current (A) 0.8 1.0 1.3 0.6 1.0 1.0 1.0 1.1 Weight (kg)

External Dimensions 3G3JV-PRS2010J


Three, 5-dia. holes

3G3JV-PRS2030J
Three, 5-dia. holes

Two, M4 holes

Four, M4 holes (for Inverter mounting use)

3G3JV-PRS2020J
Three, 5-dia. holes

3G3JV-PRS1010J
Four, M4 holes Three, 5-dia. holes

Two, M4 holes

43
Downloaded from www.Manualslib.com manuals search engine

Options
3G3JV-PRS1020J
Three, 5-dia holes

3G3JV-PRS3010J
Three, 5-dia holes

Four, M4 holes

Four, M4 holes (for Inverter mounting use)

3G3JV-PRS3005J

3G3JV-PRS3020J

Three, 5-dia holes

Three, 5-dia holes

Four, M4 holes (for Inverter mounting use)

Four, M4 holes (for Inverter mounting use)

44
Downloaded from www.Manualslib.com manuals search engine

Options
Simple Input Noise Filter
3G3EV-PLNFDj (Yaskawa Electric)
The Simple Input Noise Filter is connected to the power input side to eliminate the noise in the power line connected to the Inverter and suppress noise leaking from the Inverter to the power line.

Applicable Models
Inverter Voltage 3-phase 200 3 p 00 V AC C Model 3G3JV-A2001/-A2002/-A2004/-A2007 3G3JV-A2015 3G3JV-A2022 3G3JV-A2037 Single-phase S g p 200 00 V AC C 3G3JV-AB001/-AB002 3G3JV-AB004 3G3JV-AB007 3G3JV-AB015 3-phase 3 p 400 00 V AC C 3G3JV-A4002/-A4004/-A4007 3G3JV-A4015/-A4022 3G3JV-A4037 Model 3G3EVPLNFD2103DY PLNFD2153DY PLNFD2203DY PLNFD2303DY PLNFB2102DY PLNFB2152DY PLNFB2202DY PLNFB2302DY PLNFD4053DY PLNFD4103DY PLNFD4153DY Simple Input Noise Filter Rated current (A) 10 15 20 30 10 15 20 30 5 10 15 0.2 0.2 0.4 0.5 0.1 0.2 0.2 0.3 0.3 0.4 0.4 Weight (kg)

Connection Example
3-phase input
Noise filter

Single-phase input
Noise filter

Input Noise Filter Connection Example

Input Noise Filter Connection Example External Dimensions 3 (Three-phase Input)

External Dimensions
External Dimensions 1 (Single-phase Input) External Dimensions 2 (Three-phase Input)

Model 3G3EVPLNFD2103DY PLNFD2153DY PLNFD2203DY PLNFD2303DY PLNFB2102DY PLNFB2152DY PLNFB2202DY PLNFB2302DY PLNFD4053DY PLNFD4103DY PLNFD4153DY

External dimensions figure (above) 2 120 120 170 3 1 170 120 120 120 130 3 170 170 170

Dimension (mm) W 80 80 90 110 80 80 80 90 130 130 130 D 55 55 70 70 50 50 50 65 75 95 95 H max. 108 108 158 --108 108 108 118 ------A ------79 --------79 79 79 A 68 68 78 98 68 68 68 78 118 118 118 B Mounting screw M4 4, 20 mm M4 4, 20 mm M4 4, 20 mm M4 4, 20 mm M4 6, 20 mm M4 4, 20 mm M4 4, 20 mm M4 4, 20 mm M4 6, 30 mm M4 6, 30 mm M4 6, 30 mm

45
Downloaded from www.Manualslib.com manuals search engine

Options
Output Noise Filter
3G3IV-PLFj (Tokin)
The Output Noise Filter suppresses the generated noise of the Inverter from being transmitted to the output line. Connect the Output Noise Filter to the output side of the Inverter.

Connection Example
Noise filter

Output Noise Filter Connection Example

Applicable Models
Inverter Voltage class 200-V class Max. applicable motor capacity (kW) 0.1 0.2 0.4 0.75 1.5 2.2 3.7 400-V class 0.2 0.4 0.75 1.5 2.2 3.7 Inverter capacity (kVA) 0.3 0.6 1.1 1.9 3.0 4.2 6.7 0.9 1.4 2.6 3.7 4.2 6.6 3G3IV-PLF310KB 10 3G3IV-PLF320KA 20 Model 3G3IV-PLF310KA 10 Output Noise Filter Rated current (A)

External Dimensions

Model 3G3IV 3G3IVPLF310KA PLN320KA PLF310KB

Dimensions (mm) Terminal board TE-K5.5 M4 TE-K5.5 M4 TE-K5.5 M4 A 140 140 140 B 100 100 100 C 100 100 100 90 90 90 D 70 70 70 E 45 45 45 F G 7 4.5 dia. 7 4.5 dia. 7 4.5 dia. H 4.5 dia.

Weight g (k ) (kg) 0.5 0.6 0.5

46
Downloaded from www.Manualslib.com manuals search engine

Inverter Models
Inverter Models
Rated voltage 3-phase p 200 V AC Degree of protection Closed wall-mounting g type yp ( (equivalent q to IP20) ) Max. applicable motor capacity 0.1 kW 0.2 kW 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW 0.1 kW 0.2 kW 0.4 kW 0.75 kW 1.5 kW 0.2 kW 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW Model 3G3JV-A2001 3G3JV-A2002 3G3JV-A2004 3G3JV-A2007 3G3JV-A2015 3G3JV-A2022 3G3JV-A2037 3G3JV-AB001 3G3JV-AB002 3G3JV-AB004 3G3JV-AB007 3G3JV-AB015 3G3JV-A4002 3G3JV-A4004 3G3JV-A4007 3G3JV-A4015 3G3JV-A4022 3G3JV-A4037

Single-phase g p 200 V AC

Closed wall-mounting g type yp ( (equivalent q to IP20) )

3-phase p 400 V AC

Closed wall-mounting g type yp ( (equivalent q to IP20) )

Explanation of Product Code

3G3JV-A2007
Series name: 3G3JV Series Max. applicable motor capacity 001 002 004 007 015 022 037 0.1 kW 0.2 kW 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW

Voltage class 3-phase 200 V AC (200-V class) 2 Single-phase 200 V AC (200-V class) B 3-phase 400 V AC (400-V class) 4 Degree of protection A Panel-mounting type (IP10 or higher)/closed wall-mounting type

47
Downloaded from www.Manualslib.com manuals search engine

48
Downloaded from www.Manualslib.com manuals search engine

Warranty and Application Considerations


Read and Understand this Catalog Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRONs exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRONS ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customers application or use of the products. At the customers request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products. Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the users programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRONs test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.

49
Downloaded from www.Manualslib.com manuals search engine

OMRON Corporation FA Systems Division H.Q. 66 Matsumoto Mishima-city, Shizuoka 411-8511 Japan Tel: (81)55-977-9181/Fax: (81)55-977-9045 Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 1 East Commerce Drive, Schaumburg, IL 60173 U.S.A. Tel: (1)847-843-7900/Fax: (1)847-843-8568 OMRON IDM CONTROLS, INC. 9510 N. Houston-Rosslyn Rd. Houston, Texas 77088 Tel: (1)713-849-1900/Fax: (1)713-849-4666 OMRON ASIA PACIFIC PTE. LTD. 83 Clemenceau Avenue, #11-01, UE Square, Singapore 239920 Tel: (65)6835-3011/Fax: (65)6835-2711 Authorized Distributor:

Cat. No. I905-E1-04

Note: Specifications subject to change without notice.

Downloaded from www.Manualslib.com manuals search engine

Printed in Japan 0503-0.6M

Das könnte Ihnen auch gefallen