Design of Reinforced Concrete Shear wall


Example 1: Design of reinforced concrete non-load bearing shear wall. Example 2: Design of Reinforced Concrete load bearing shear wall

Design examples
Example 1: Design of reinforced concrete non-load bearing shear wall.

Design code: ACI 318-05 Design data:


Seismic shear force: (service load) Roof: Vr = 100 kips 4th floor: V4 = 75 kips, , 3rd floor: V3 = 50 kips 2nd floor: V2 = 25 kips Floor height: H = 15 ft Length of wall: lw = 18 ft

http://ce-ref.com/sh-wall_example.htm

4/7/2013

Sh-wall example

Page 2 of 7

Width of wall: h = 10 in Concrete strength: fc' = 4000 psi Yield strength of steel: fy = 60 kis

Assumption:
1.out-of-plan moment is neglectable. 2.The wall is an exterior wall.

Requirement:
Design reinforcement for shear wall

Solution:
Maximum shear occurs at load combination: 1.2D+1.4E+1.0L Calculate maximum vertical and shear force at first floor Maximum factored shear: Vu = 1.4 (100+75+50+25) = 350 kips Check maximum shear strength permitted Assume effective depth, d = 0.8 (18) = 14.4 ft Strength reduction factor,

= 0.75
> 350 kips O.K.

Vn = 10 fc' h d = 819 kips

Critical section for shear at smaller of 18 ft/2 = 9 ft , H/2 = 7.5 ft Calculate factored overturning moment and weight of wall at critical section Mu = 1.4 [100 (60-7.5)+75(45-7.5)+50(30-7.5)+25 (25-7.5)] = 13130 ft-kips Nu = (0.15)(10/12)(18)(60-7.5) = 118.1 kips Calculate shear strength of concrete:

Vc = 0.75 [3.3 fc' h d + Nu d/ (4 lw)] = 288.2 kips


Mu/Vu - lw/2 = 28.5 ft

Vc = 0.75 { 0.6 fc' + lw ( 1.25 fc' + 0.2 [Nu/(lw* h)]) /( Mu/Vu - lw/2)} h d = 163.8 kips
Or Vc = 0.75 (2 fc' h d) = 163.9 kips Design horizontal shear reinforcement: Vs = Vu - Vc = 186.1 kips Use #5 bar in one layer, area of reinforcement, Av = 0.3 in2. Spacing: S = Av fy d /Vs = 12.6 in, Use 12" O.C. Check maximum spacing: (18x12)/5 = 43 in, 3 (10) = 30 in, or 18 in O.K. Use

http://ce-ref.com/sh-wall_example.htm

4/7/2013

Sh-wall example

Page 3 of 7

Check minimum reinforcement: t = 0.3 in2 / (12x10) = 0.0025 O.K. Design vertical reinforcement:

l = 0.0025 + 0.5 (2.5 - hw/ lw )( t - 0.0025) = 0.0025


Use l = 0.0025 Area of reinforcement: Av = 0.0025 (10)(12) = 0.3 in2/ft Use #5 bars at 12" O.C Design flexural reinforcement: Calculate factored moment at base: Mu = 1.4 [(100)(60)+(75)(45)+(50)(30)+(25)(15)]=15750 ft-kip Tension control section,

= 0.9

Factor: Rn = (15750)(12000)/[0.9(10)(14.4x12)2] = 703 psi, and m = fy/(0.85fc')=17.7 Reinforcement ratio, = (1/m)[1-(1- 2 m Rn/fy)] = 0.013 Area of reinforcement, As = 0.013 h d = 22.9 in2. Use #10 bars, number of bars, n = 22.9/1.27 = 18 Check effective depth Concrete cover = 2" for exterior wall. Use 3" spacing between #10 bars in two layers Effective depth, d = (18)(12) - 2-(3)(8)/2 =202 in Recalculate reinforcement, Factored Rn = Mu / h d2 = 514.7 psi, m = 17. Reinforcement ratio,

= 0.0094

Area of reinforcement, As = 18.9 in2. Use #10 bars, number of bars, n = 18.9 /1.27 = 15, Use 16 # 10 Use #4 closed shape ties to enclose tension reinforcement, Area of reinforcement for shear As = 0.4 in2. Check clear spacing between bars, S = 10-(2)(2)-(0.5)(2)-1.27 = 3.73 in O.K. Reinforcement detail

http://ce-ref.com/sh-wall_example.htm

4/7/2013

Sh-wall example

Page 4 of 7

Example 2: Design of Reinforced Concrete load bearing shear wall


Situation: A reinforced concrete load bearing shear wall supporting for a four story building

Design code: ACI 318-05 Design data:


Vertical load: (service load) Dead load at each floor and roof: PD = 40 kips Live load at each floor and roof: PL = 25 kips Seismic shear force: (service load) Roof: Vr = 100 kips 4th floor: V4 = 75 kips, , 3rd floor: V3 = 50 kips

http://ce-ref.com/sh-wall_example.htm

4/7/2013

Sh-wall example

Page 5 of 7

2nd floor: V2 = 25 kips Floor height: H = 15 ft Length of wall: lw = 18 ft Width of wall: h = 12 in Concrete strength: fc' = 4000 psi Yield strength of steel: fy = 60 kis

Assumptions:
1. out-of-plan moment is neglectable. 2. The wall is an exterior wall.

Requirement:
Design reinforcement for shear wall

Solution
Maximum shear occurs at load combination: 1.2D+1.4E+1.0L Calculate maximum vertical and shear force at first floor Maximum factored shear: Vu = 1.4 (100+75+50+25) = 350 kips Check maximum shear strength permitted Assume effective depth, d = 0.8 (18) = 14.4 ft Strength reduction factor,

= 0.75
> 350 kips O.K.

Vn = 10 fc' h d = 819 kips

Critical section for shear at smaller of 18 ft/2 = 9 ft , H/2 = 7.5 ft Calculate factored overturning moment and weight of wall at critical section Mu = 1.4 [100 (60-7.5)+75(45-7.5)+50(30-7.5)+25 (25-7.5)] = 13130 ft-kips Nu = 1.2 [(0.15)(10/12)(18)(60-7.5)+4 PD ]+1.0 (4 PL ) = 462.1 kips Calculate shear strength of concrete:

Vc = 0.75 [3.3 fc' h d + Nu d/ (4 lw)] = 393.9 kips


Mu/Vu - lw/2 = 28.5 ft

Vc = 0.75 { 0.6 fc' + lw ( 1.25 fc' + 0.2 [Nu/(lw* h)]) /( Mu/Vu - lw/2)} h d = 228.2 kips (Use)
Or Vc = 0.75 (2 fc' h d) = 196.7 kips Design horizontal shear reinforcement: Vs = Vu - Vc = 112.1 kips

http://ce-ref.com/sh-wall_example.htm

4/7/2013

Sh-wall example

Page 6 of 7

Use #4 bar in two layer, area of reinforcement, Av = 0.4 in2. (Code requires two layers for 12" wall) Spacing: S = Av fy d /Vs = 25.7 in Check maximum spacing: (18x12)/5 = 43 in, 3 (10) = 30 in, or 18 in Use 18"

Check minimum reinforcement: t = 0.4 in2 / (18x10) = 0.0019 < 0.0025 Use t =0.0025, spacing S = 0.4 in2 / (0.0025)(h) = 13.3 in Use 12 in Design vertical reinforcemnt

l = 0.0025 + 0.5 (2.5 - hw/ lw )( t - 0.0025) = 0.0025


Use l = 0.0025 Use #4 bars in two layers at 12" O.C Calculate factored moment and axial load at base: Mu = 1.4 [(100)(60)+(75)(45)+(50)(30)+(25)(15)]=15750 ft-kip Nu = 1.2 [(0.15)(10/12)(18)(60)+4 PD ]+1.0 (4 PL ) = 486.4 kips Design as a column subjected to axial load and bending Gross area, Ag = (18)(12)(12) = 2592 in2. Assume tension control section, = 0.9

Nu/Ag = 0.141 ksi Mu/(Ag lw) = 0.253 ksi


From ACI column design chart (See column design section), Area of reinforcement, = 0.011 Area of reinforcement, As = (0.01)(18x12)(12) = 22.8 in2. Use #10 bars, number of bar, n = 22.8/1.27 = 18 Use 10#10 bars at each end of shear wall, column ties is required since > 0.01. Use #4 ties at 12" O.C.

http://ce-ref.com/sh-wall_example.htm

4/7/2013

Sh-wall example

Page 7 of 7

Disclaimer: The content of this website was obtained and edited from various resources. The editor made reasonable effort of editing. Nevertheless, the editor does not warrant, and assume no liability for accuracy and completeness of its content. The viewer shall use his/her professional knowledge and judgment in use of the web content. Webmaster: www.ce-ref.com