Tomorrows energy systems...

today

Cell Specifications
Container and Cover: Impact-Resistant Polypropylene
28% L.O.I. (Optional)

Separators: Microporous Glass Mat


Safety Vent: Low Pressure, Self-Sealing
Life: 20 Years in Float Applications77F (25C)
Float Voltage: 2.25 1% Volts per Cell

Self-Discharge: <2% Per Month


Terminals: Lead Plated Solid Copper
Intercell Connectors: Plated Solid Copper
Positive Plate: 99.2% Pure Lead, 0.8% Tin
Negative Plate: Lead Calcium

(Temperature Compensated)

Made in U.S.A.

Features

Standards

Module Features

Battery design and construction meet the requirements in UL


924, file number MH17218.

A. Open spaces allow the middle cells to be cooled by


convection, preventing the damage and short life caused by
cells operating at unequal temperatures.

Quality Assurance
Cells are manufactured to the standards and procedures of
East Penns Total Quality Assurance Program, which is
derived from ISO9001 and Ford Motor Companys Q-1
System. East Penn is a Ford Q-1 certified supplier.

Cell Construction
A. Grids
The alloys used in the grids are: positive plate99.2% pure
lead with a 0.8% trace of tin for hardening purposes, and
negative platea lead-calcium alloy.
B. Tank Formation
The plates are initially charged using a tank formation
procedure, which is unique in U.S. manufacturing. This
procedure ensures full and uniform plate charging.
Although it is more expensive than the jar formation
process used by other U.S. manufacturers of valve
regulated batteries, it results in batteries that provide 100%
of rated capacity upon shipment. In addition, all cells are
voltage matched in this formation process, guaranteeing
uniform voltage.
C. Plate Growth Provision
Positive plates are constructed from a lead-tin alloy, which
exhibits slower plate growth than calcium alloys. Despite
this advantage, East Penn also installs a collapsible
element support beneath the plate groups in the bottom of
the cell to accommodate plate expansion as the battery
ages. When the plates expand vertically, the support
collapses at a controlled rate, allowing expansion without
damage to plates, covers, jar to-cover seal, or post seals. In
addition, this element support helps prevent shock damage
to the cell during transport and installation.
D. Posts
The cell terminals are solid copper with lead plating and are
designed for maximum conductivity. They have the largest
connector-to-post surface area of any valve-regulated
battery in the industry, which simplifies cell voltage checks.
Cells with up to 15 plates have two posts, cells with 17 to
27 plates have four posts, and cells with 29 to 33 plates
have six posts.
E. Post Seals
Our new Epox-z post seals have been tested to 176F
(80C) for 1000 hours to guarantee seal integrity against
leaks. The post seals are color coded for safety.
F. Jars and Covers
The jars and covers are made of a high-impact resistant
polypropylene.

B. Design allows the modules to be stacked and connected by


only four bolts, for quick and safe battery installation.
C. Mounting bases are high enough to allow easy installation
of anchor bolts with standard equipment.
D. Seismic Zone 4 modules are standard.
E. The modules are coated and protected with a thick layer of
powdered epoxy.
F. The cell terminal and inter-connection hardware are
protected by a clear flame-retardant plastic cover which
mounts in four places on the module, for easy installation
and removal.
G. Modules for 23" equipment rack installations are also
available.

Flame-Retardant
Standard products are constructed in polypropylene - UL 94 V-O/
28% L.O.I. jars and covers are optional.

Battery Life
The design life for the Unigy II battery is 20 years in float
applications at 77F (25C).

New Battery Performance


All Unigy II cells perform at 100% rated capacity upon
shipment. This benefit is a result of East Penns unique tank
formation process of plate activation and the repeated cycling
of plates in the final formation process. Although IEEE
standards allow for new lead-acid batteries to be accepted at
90% of rated capacity, Unigy II batteries deliver full rated
capacity (@ 8-hour rate) at installation.

Float Voltage Matching Cells


Cells are checked for float voltage consistency in the
acceptance procedure. Any cell that does not float at a voltage
within .05 volts of the voltage average will be rejected. All test
data is available upon request.

Battery Stabilization
Battery stabilization requires a very short amount of time
because of the tank formation process of forming plates. East
Penns unique activation process guarantees the proper
amount of acid in each cell. Voltage stabilization should be
reached in a matter of days after initiation of float charge.

Recombination Efficiency
The recombination efficiency is greater than 99% after
stabilization is reached.

Self Discharge Rate


G. Jar-To-Cover Seal
The cover is heat-bonded to the jar. A two-cycle jar-tocover seal is applied. The jar and cover undergo a bead
compression process. This forms a double barrier against
jar to-cover leaks. Tests are conducted on 100% of the
seals by submerging the cells in liquid and applying internal
pressure to the cells.
H. Valve
The safety valve opens when the cells internal pressure
reaches a level of 4 1 PSI. The valve has a flame
arrestor to prevent the possibility of external sparks
entering the cell.

The self discharge rate at 77F (25C) is <2% per month.

Module Dimensional Information

4.00
RN

LE

TU

AD

RE

48 volt
assembly with
standard
covers.

RECYCLE

No. of
Cells
per
Module

No.
Plts.
5
7
9

6
11
13
15
17
19
21
23
3

25
27
29
31
33
39
45
51
57

63
69
75
81
87
93
99

L
20.19
512.8
24.62
625.4
29.12
739.7
33.62
853.9
38.12
968.3
42.62
1082.6
27.62
701.6
29.88
758.9
32.10
815.8
34.38
873.3
36.62
930.2
38.88
987.6
41.12
1044.5
43.38
1101.9
45.62
1158.8
23.12
587.2
25.38
644.7
27.62
701.6
29.88
758.9
32.12
815.9
34.38
873.3
36.62
930.2
38.88
987.6
41.12
1044.5
43.38
1101.9
45.62
1158.8

H
8.50
215.9
8.50
215.9
8.50
215.9
8.50
215.9
8.50
215.9
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5
8.56
217.5

45 Amps per Positive

75 Amps per Positive

D*

Wt.

D*

Wt.

17.50
444.5
17.50
444.5
17.50
444.5
17.50
444.5
17.50
444.5
17.50
444.5

179
81.19
225
102.06
271
122.93
317
143.79
362
164.20
408
185.07

24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3
24.50
622.3

259
117.48
330
149.69
397
180.08
471
213.65
542
245.85
612
277.60
382
173.28
420
190.51
458
207.75
496
224.99
530
240.41
568
257.65
606
274.88
634
287.58
681
308.90

Chart contains dimensions in inches over millimeters and weight in pounds over kilograms.
* Over insulation shield.

85 Amps per Positive


D*

Wt.

27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9
27.12
688.9

357
161.94
439
199.13
521
236.33
603
273.52
682
309.36
428
194.14
472
214.10
508
230.43
557
252.66
598
271.25
639
289.85
683
309.81
724
328.41
770
349.27
320
145.15
375
170.10
428
194.14
472
214.10
508
230.43
557
252.66
598
271.25
639
289.85
683
309.81
724
328.41
770
349.27

Cell Construction

Look into UNIGY II and Discover


Todays Best Valve-Regulated Battery
Polypropylene
Cover and Jar
(28% L.O.I.
Optional)

Copper Posts
with Large
Contact Area

All Seals
100% Air and
Water Tested

Pure Lead
Positive Grid
Alloy (99.2%)

Epox-ZTM
Post Seal
Tested to 176F
(80C)

Tank-Formed
Plates
(All cells
shipped at
100% capacity.)

Hovosorb II
Glass Mat
Separators

Tear Guard

The Unigy II cells are available in


modules designed for installation in 23"
equipment racks. Three, four, and six
cell modules ranging from 140 to 615
A.H. can be used in the rack or free
standing if required. Drawings showing
exact layouts and dimensions are
available. Contact East Penn for details.
4

Collapsible
Bottom
Bridge

Discharge Rates 1.75 VPC

UNIGY II Discharge Rates in Amperes to 1.75 VPC Final @ 77F (25C)


CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33
1AVR85-39
1AVR85-45
1AVR85-51
1AVR85-57
1AVR85-63
1AVR85-69
1AVR85-75
1AVR85-81
1AVR85-87
1AVR85-93
1AVR85-99

Nom. A.H. Cap.


(8 Hr. Discharge Rate)

24

12

10

Hours
6

90
140
185
230
275
320

5
7
9
11
14
16

8
13
17
21
25
29

10
14
19
24
29
34

11
17
23
29
34
40

14
22
29
36
43
50

16
25
33
41
49
58

19
29
39
48
58
68

24
36
48
60
71
83

32
47
63
79
95
110

52
78
105
131
157
183

160
235
310
390
470
550
630
705
785
865
945
1025
1100
1175
1255

8
12
16
20
23
27
31
35
39
43
47
51
55
59
63

14
21
28
35
42
50
57
64
71
78
85
92
99
106
113

16
25
33
41
49
57
66
74
82
90
98
107
115
123
131

20
29
39
49
59
69
79
88
98
108
118
128
138
147
157

25
37
49
61
73
86
98
110
122
135
147
159
171
184
196

28
42
56
70
84
98
112
127
141
155
169
183
197
211
225

33
50
66
83
100
116
133
150
166
183
200
216
233
250
266

41
61
82
102
123
143
163
184
204
225
245
265
286
306
327

54
80
107
134
161
187
214
241
268
295
321
348
375
402
428

80
121
162
220
242
283
323
364
404
444
485
525
554
606
664

265
350
440
530
615
695
785
875
960
1050
1135
1225
1310
1400
1585
1845
2095
2360
2625
2890
3145
3405
3675
3935
4200

13
17
22
26
31
35
39
44
48
52
57
61
65
70
78
92
105
118
131
144
157
170
183
196
209

24
32
40
47
55
63
71
79
87
95
103
111
118
126
142
166
189
213
237
260
284
308
332
355
379

27
37
46
55
64
73
82
91
100
110
119
128
137
146
164
192
219
247
274
301
329
356
383
411
438

33
44
55
66
77
87
98
109
120
131
142
153
164
175
197
230
262
295
328
361
393
426
459
492
525

41
55
68
82
95
109
123
136
150
164
177
191
204
218
245
286
327
368
409
449
490
531
572
613
654

47
63
78
94
110
125
141
157
172
188
204
219
235
250
282
329
376
423
470
517
564
611
658
705
751

56
74
93
111
130
148
167
185
204
222
241
259
278
296
333
389
444
500
555
611
666
722
777
833
888

68
91
114
137
159
182
205
228
250
273
296
319
341
364
410
478
546
615
683
751
819
888
956
1024
1092

90
119
149
179
209
239
268
298
328
358
387
417
447
477
536
626
715
804
894
983
1073
1162
1251
1341
1430

139
185
231
278
324
370
417
463
509
555
602
648
694
740
833
972
1111
1250
1388
1527
1666
1805
1944
2083
2221

Discharge Rates 1.78 VPC

UNIGY II Discharge Rates in Amperes to 1.78 VPC Final @ 77F (25C)


CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33
1AVR85-39
1AVR85-45
1AVR85-51
1AVR85-57
1AVR85-63
1AVR85-69
1AVR85-75
1AVR85-81
1AVR85-87
1AVR85-93
1AVR85-99

Nom. A.H. Cap.*


(8 Hr. Discharge Rate)

24

12

10

Hours
6

90
140
185
230
275
320

5
7
9
11
14
16

8
12
16
20
25
29

10
14
19
24
29
33

11
17
23
28
34
40

14
21
28
35
42
49

16
24
32
40
49
57

19
29
38
48
57
67

23
35
46
58
69
81

31
46
61
77
92
107

50
75
99
124
149
174

160
235
310
390
470
550
630
705
785
865
945
1025
1100
1175
1255

8
11
15
19
22
26
30
34
37
41
45
49
52
56
60

14
20
27
34
41
48
54
61
68
75
82
88
95
102
109

16
24
31
39
47
55
63
71
79
86
94
102
110
118
126

19
28
38
47
57
66
75
85
94
104
113
123
132
141
151

23
35
47
59
70
82
94
105
117
129
140
152
164
175
187

27
40
53
67
80
94
107
120
134
147
160
174
187
201
214

31
47
63
79
94
110
126
141
157
173
188
204
220
235
251

38
58
77
96
115
135
154
173
192
212
231
250
269
289
308

51
76
101
126
151
176
201
227
252
277
302
327
352
377
402

80
120
160
200
240
280
320
360
400
440
480
520
560
600
640

265
350
440
530
615
695
785
875
960
1050
1135
1225
1310
1400
1585
1845
2095
2360
2625
2890
3145
3405
3675
3935
4200

13
17
22
26
30
34
39
43
47
52
56
60
64
69
77
90
103
116
129
142
155
168
181
193
206

23
31
39
47
55
63
70
78
86
94
102
109
117
125
141
164
187
211
234
258
281
305
328
351
375

27
36
45
54
63
72
81
90
99
108
117
126
135
144
162
189
216
243
270
298
325
352
379
406
433

33
43
54
65
76
87
98
108
119
130
141
152
163
173
195
228
260
293
325
358
390
423
455
488
520

40
54
67
81
94
108
121
134
148
161
175
188
202
215
242
282
322
363
403
443
484
524
564
604
645

46
61
77
92
108
123
138
154
169
184
200
215
231
246
277
323
369
415
461
507
553
600
646
692
738

54
73
91
109
127
145
163
181
199
217
236
254
272
290
326
380
435
489
543
598
652
706
761
815
869

66
89
111
133
155
177
199
221
244
266
288
310
332
354
399
465
531
598
664
731
797
864
930
996
1063

86
115
144
173
201
230
259
287
316
345
374
402
431
460
517
603
689
776
862
948
1034
1120
1206
1292
1379

132
177
221
265
309
353
397
441
486
530
574
618
662
706
795
927
1059
1192
1324
1457
1589
1721
1854
1986
2119

*Nominal A.H. capacity, 8 hour discharge rates are to 1.75 VPC.

Discharge Rates 1.81 VPC

UNIGY II Discharge Rates in Amperes to 1.81 VPC Final @ 77F (25C)


CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33
1AVR85-39
1AVR85-45
1AVR85-51
1AVR85-57
1AVR85-63
1AVR85-69
1AVR85-75
1AVR85-81
1AVR85-87
1AVR85-93
1AVR85-99

Nom. A.H. Cap.*


(8 Hr. Discharge Rate)

24

12

10

Hours
6

90
140
185
230
275
320

5
7
9
11
13
16

8
12
16
20
24
28

9
14
19
23
28
33

11
17
22
28
34
39

14
21
28
35
42
49

16
24
32
40
48
56

19
28
37
47
56
65

23
34
46
57
68
80

30
45
60
75
90
105

47
71
95
119
142
166

160
235
310
390
470
550
630
705
785
865
945
1025
1100
1175
1255

7
11
15
19
22
26
30
33
37
41
45
48
52
56
59

13
20
27
34
40
47
54
60
67
74
80
87
94
101
107

16
23
31
39
47
54
62
70
78
86
93
101
109
117
124

19
28
37
47
56
65
74
84
93
102
112
121
130
140
149

23
35
46
58
69
81
92
104
115
127
138
150
161
173
184

26
39
53
66
79
92
105
118
131
145
158
171
184
197
210

31
46
62
77
93
108
124
139
154
170
185
201
216
232
247

38
57
75
94
113
132
151
170
189
207
226
245
264
283
302

49
74
98
123
147
172
196
221
245
270
294
319
343
368
392

76
114
153
191
229
267
305
343
381
420
458
496
534
572
610

265
350
440
530
615
695
785
875
960
1050
1135
1225
1310
1400
1585
1845
2095
2360
2625
2890
3145
3405
3675
3935
4200

13
17
21
26
30
34
38
43
47
51
55
60
64
68
77
90
102
115
128
141
153
166
179
192
205

23
31
39
47
54
62
70
78
85
93
101
109
116
124
140
163
186
209
233
256
279
302
326
349
372

27
36
45
54
63
71
80
89
98
107
116
125
134
143
161
188
214
241
268
295
321
348
375
402
429

32
43
53
64
75
85
96
107
118
128
139
150
160
171
192
224
256
288
320
352
384
417
449
481
513

40
53
66
80
93
106
119
132
146
159
172
185
199
212
238
278
318
358
397
437
477
516
556
596
636

45
60
76
91
106
121
136
151
166
181
196
212
227
242
272
317
363
408
453
499
544
589
635
680
725

53
71
89
107
124
142
160
178
195
213
231
249
266
284
320
373
426
479
533
586
639
692
746
799
852

65
87
109
131
152
174
196
218
239
261
283
305
326
348
392
457
522
588
653
718
783
849
914
979
1044

85
113
141
170
198
226
254
282
311
339
367
395
423
452
508
593
677
762
847
931
1016
1101
1185
1270
1355

126
168
210
252
294
336
378
420
462
504
546
588
630
672
756
882
1008
1134
1260
1386
1512
1638
1764
1890
2016

*Nominal A.H. capacity, 8 hour discharge rates are to 1.75 VPC.

Discharge Rates 1.84 VPC

UNIGY II Discharge Rates in Amperes to 1.84 VPC Final @ 77F (25C)


CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33
1AVR85-39
1AVR85-45
1AVR85-51
1AVR85-57
1AVR85-63
1AVR85-69
1AVR85-75
1AVR85-81
1AVR85-87
1AVR85-93
1AVR85-99

Nom. A.H. Cap.*


(8 Hr. Discharge Rate)

24

12

10

Hours
6

90
140
185
230
275
320

4
7
9
11
13
15

8
12
16
20
24
28

9
14
18
23
27
32

11
16
22
27
33
38

14
20
27
34
41
48

15
23
31
39
46
54

18
27
36
45
54
63

22
33
44
55
66
77

29
43
58
72
86
101

44
66
88
110
132
154

160
235
310
390
470
550
630
705
785
865
945
1025
1100
1175
1255

7
11
15
18
22
26
29
33
36
40
44
47
51
55
58

13
20
26
33
39
46
53
59
66
72
79
85
92
99
105

15
23
30
38
46
53
61
68
76
84
91
99
106
114
122

18
27
36
45
54
63
72
82
91
100
109
118
127
136
145

23
34
45
56
68
79
90
101
112
124
135
146
157
169
180

26
39
51
64
77
90
103
116
129
141
154
167
180
193
206

30
45
60
75
90
105
120
135
150
165
180
195
210
225
240

37
55
73
91
110
128
146
165
183
201
219
238
256
274
293

48
71
95
119
143
166
190
214
237
261
285
309
332
356
380

71
106
142
177
213
248
283
319
354
390
425
461
496
531
567

265
350
440
530
615
695
785
875
960
1050
1135
1225
1310
1400
1585
1845
2095
2360
2625
2890
3145
3405
3675
3935
4200

13
17
21
25
29
34
38
42
46
50
55
59
63
67
76
88
101
113
126
138
151
164
176
189
201

23
30
38
45
53
60
68
76
83
91
98
106
113
121
136
159
181
204
226
249
272
294
317
340
362

26
35
44
52
61
70
79
87
96
105
114
122
131
140
157
183
210
236
262
288
314
340
367
393
419

31
42
52
62
73
83
94
104
114
125
135
146
156
166
187
218
249
281
312
343
374
405
437
468
499

39
52
65
78
90
103
116
129
142
155
168
181
194
207
232
271
310
349
387
426
465
503
542
581
620

44
59
74
88
103
118
133
147
162
177
192
206
221
236
265
310
354
398
442
486
531
575
619
663
708

52
69
86
104
121
138
155
173
190
207
224
242
259
276
311
362
414
466
518
569
621
673
725
776
828

63
84
105
126
147
168
189
210
231
252
273
294
315
336
378
441
504
567
630
693
756
819
882
945
1008

81
109
136
163
190
217
244
271
298
325
352
379
406
433
488
569
650
731
812
894
975
1056
1137
1218
1300

120
160
200
240
280
320
360
400
440
480
520
560
600
640
720
840
960
1080
1200
1320
1440
1560
1680
1800
1920

*Nominal A.H. capacity, 8 hour discharge rates are to 1.75 VPC.

Discharge Rates 1.88 VPC

UNIGY II Discharge Rates in Amperes to 1.88 VPC Final @ 77F (25C)


CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33
1AVR85-39
1AVR85-45
1AVR85-51
1AVR85-57
1AVR85-63
1AVR85-69
1AVR85-75
1AVR85-81
1AVR85-87
1AVR85-93
1AVR85-99

Nom. A.H. Cap.*


(8 Hr. Discharge Rate)

24

12

10

Hours
6

90
140
185
230
275
320

4
6
8
11
13
15

8
12
15
19
23
27

9
13
18
22
26
31

10
16
21
26
31
37

13
19
26
32
39
45

15
22
29
37
44
51

17
26
34
43
52
60

21
31
42
52
62
73

28
41
55
68
82
96

41
62
82
103
123
144

160
235
310
390
470
550
630
705
785
865
945
1025
1100
1175
1255

7
11
14
18
21
25
28
32
35
39
42
46
49
53
56

13
19
25
32
38
44
50
57
63
69
76
82
88
95
101

15
22
29
36
44
51
58
65
73
80
87
95
102
109
116

17
26
35
43
52
61
69
78
87
95
104
113
121
130
139

22
32
43
54
65
75
86
97
107
118
129
140
150
161
172

24
37
49
61
73
86
98
110
122
135
147
159
171
183
196

29
43
57
71
85
100
114
128
142
156
171
185
199
213
228

34
51
69
86
103
120
137
154
171
189
206
223
240
257
274

44
66
88
110
132
154
176
198
220
241
263
285
307
329
351

66
99
132
165
198
231
264
297
330
363
396
429
462
495
528

265
350
440
530
615
695
785
875
960
1050
1135
1225
1310
1400
1585
1845
2095
2360
2625
2890
3145
3405
3675
3935
4200

12
16
20
24
28
32
36
40
44
48
52
56
60
64
72
84
96
109
121
133
145
157
169
181
193

22
29
36
43
51
58
65
72
80
87
94
101
108
116
130
152
173
195
217
238
260
282
304
325
347

25
33
42
50
59
67
75
84
92
100
109
117
125
134
150
176
201
226
251
276
301
326
351
376
401

30
40
50
60
70
79
89
99
109
119
129
139
149
159
179
209
238
268
298
328
357
387
417
447
477

37
49
62
74
86
99
111
123
136
148
160
173
185
197
222
259
296
333
370
407
444
481
518
555
592

42
56
70
84
98
112
126
140
154
168
182
196
210
224
253
295
337
379
421
463
505
547
589
631
673

49
66
82
98
115
131
147
164
180
196
213
229
245
262
295
344
393
442
491
540
589
638
687
736
785

59
79
98
118
138
157
177
197
216
236
256
275
295
315
354
413
472
531
590
649
708
767
826
885
944

75
100
125
150
175
200
225
250
275
300
325
350
375
400
450
525
600
675
750
825
900
975
1050
1125
1200

107
143
179
214
250
286
321
357
393
429
464
500
536
571
643
750
857
964
1071
1178
1286
1393
1500
1607
1714

*Nominal A.H. capacity, 8 hour discharge rates are to 1.75 VPC.

Discharge Rates 1.90 VPC

UNIGY II Discharge Rates in Amperes to 1.90 VPC Final @ 77F (25C)


CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33
1AVR85-39
1AVR85-45
1AVR85-51
1AVR85-57
1AVR85-63
1AVR85-69
1AVR85-75
1AVR85-81
1AVR85-87
1AVR85-93
1AVR85-99

Nom. A.H. Cap.*


(8 Hr. Discharge Rate)

24

12

10

Hours
6

90
140
185
230
275
320

4
6
8
10
12
14

7
11
15
18
22
25

8
13
17
21
25
29

10
15
20
25
30
35

12
18
25
31
37
43

14
21
28
35
41
48

16
24
32
40
49
57

20
29
39
49
59
68

26
38
51
64
77
89

37
56
74
93
111
130

160
235
310
390
470
550
630
705
785
865
945
1025
1100
1175
1255

7
10
14
17
20
24
27
31
34
38
41
44
48
51
55

12
18
24
31
37
43
49
55
61
67
73
79
86
92
98

14
21
28
35
42
49
56
63
70
77
84
91
98
105
112

17
25
33
42
50
58
67
75
83
92
100
108
117
125
133

21
31
41
52
62
72
83
93
103
113
124
134
144
155
165

23
35
47
58
70
82
93
105
117
128
140
152
163
175
186

27
41
54
68
81
95
108
122
135
149
162
176
189
203
216

32
48
65
81
97
113
129
145
161
178
194
210
226
242
258

41
62
82
102
123
143
164
184
205
225
245
266
286
307
327

59
88
118
147
177
206
235
265
294
324
353
383
412
441
471

265
350
440
530
615
695
785
875
960
1050
1135
1225
1310
1400
1585
1845
2095
2360
2625
2890
3145
3405
3675
3935
4200

12
16
20
23
27
31
35
39
43
47
51
55
59
62
70
82
94
105
117
129
140
152
164
175
187

21
28
35
42
49
56
63
70
77
84
91
98
105
112
126
147
168
189
210
231
252
273
295
316
337

24
32
40
48
57
65
73
81
89
97
105
113
121
129
145
170
194
218
242
266
291
315
339
363
387

29
38
48
57
67
76
86
96
105
115
124
134
143
153
172
201
229
258
287
315
344
373
401
430
459

36
47
59
71
83
95
107
118
130
142
154
166
178
189
213
249
284
320
355
391
426
462
497
533
568

40
53
67
80
94
107
120
134
147
160
174
187
201
214
241
281
321
361
401
441
481
522
562
602
642

46
62
77
93
108
124
139
154
170
185
201
216
232
247
278
324
370
417
463
509
556
602
648
694
741

55
74
92
110
129
147
165
184
202
221
239
257
276
294
331
386
441
496
551
607
662
717
772
827
882

69
93
116
139
162
185
208
231
254
277
300
323
346
369
416
485
554
623
692
762
831
900
969
1038
1108

97
129
161
194
226
258
291
323
355
387
420
452
484
516
581
678
775
872
968
1065
1162
1259
1356
1453
1549

*Nominal A.H. capacity, 8 hour discharge rates are to 1.75 VPC.

10

Discharge Rates 1.94 VPC

UNIGY II Discharge Rates in Amperes to 1.94 VPC Final @ 77F (25C)


CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33
1AVR85-39
1AVR85-45
1AVR85-51
1AVR85-57
1AVR85-63
1AVR85-69
1AVR85-75
1AVR85-81
1AVR85-87
1AVR85-93
1AVR85-99

Nom. A.H. Cap.*


(8 Hr. Discharge Rate)

24

12

10

Hours
6

90
140
185
230
275
320

4
6
7
9
11
13

7
10
13
16
20
23

8
11
15
19
23
26

9
13
18
22
27
31

11
17
22
28
33
39

13
19
25
31
38
44

15
22
29
37
44
51

18
27
36
45
53
62

23
34
46
57
68
80

33
50
66
83
99
116

160
235
310
390
470
550
630
705
785
865
945
1025
1100
1175
1255

6
9
12
16
19
22
25
28
31
34
37
40
43
47
50

11
17
22
28
33
39
44
50
56
61
67
72
78
83
89

13
19
26
32
38
45
51
58
64
70
77
83
89
96
102

15
23
30
38
45
53
60
68
75
83
90
98
106
113
121

19
28
37
47
56
65
74
84
93
102
112
121
130
139
149

21
31
42
52
63
73
84
94
105
115
126
136
146
157
167

24
36
48
60
72
84
96
108
120
132
144
156
168
180
192

29
43
57
71
86
100
114
129
143
157
171
186
200
214
229

36
54
72
90
108
126
144
162
180
198
216
234
252
270
288

52
78
104
130
156
182
208
234
260
286
312
338
364
390
416

265
350
440
530
615
695
785
875
960
1050
1135
1225
1310
1400
1585
1845
2095
2360
2625
2890
3145
3405
3675
3935
4200

11
14
18
21
25
28
32
35
39
42
46
49
53
56
63
74
84
95
106
116
127
137
148
158
169

19
26
32
38
45
51
57
64
70
76
83
89
96
102
115
134
153
172
191
210
229
248
268
287
306

22
29
37
44
51
59
66
73
81
88
95
103
110
117
132
154
176
198
220
242
264
286
308
330
352

26
35
43
52
61
69
78
86
95
104
112
121
130
138
156
182
207
233
259
285
311
337
363
389
415

32
43
54
64
75
86
96
107
118
128
139
150
160
171
193
225
257
289
321
353
385
417
449
481
513

36
48
60
72
84
96
108
120
132
144
156
168
180
192
216
252
288
324
360
396
432
468
504
540
576

42
56
69
83
97
111
125
139
153
166
180
194
208
222
250
291
333
374
416
457
499
541
582
624
665

50
66
83
99
116
133
149
166
182
199
215
232
249
265
298
348
398
447
497
547
597
646
696
746
795

62
83
103
124
144
165
185
206
227
247
268
288
309
329
371
432
494
556
617
679
741
802
864
926
988

84
112
140
168
196
224
252
280
308
336
364
392
420
448
504
588
672
756
840
924
1008
1092
1176
1260
1344

*Nominal A.H. capacity, 8 hour discharge rates are to 1.75 VPC.

11

Discharge Rates 1.67 VPC

UNIGY II Discharge Rates in Watts per Cell to 1.67 VPC Final @ 77F (25C)
CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75 AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85 AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33

12

Minutes
5

10

15

20

30

60

312
468
624
781
939
1093

271
406
542
678
813
949

234
350
469
585
703
819

210
315
421
526
631
736

175
262
350
437
524
612

115
172
231
288
346
403

362
542
723
903
1042
1042
1447
1627
1808
1988
2084
2084
2532
2712
2893

321
481
643
802
964
1042
1285
1445
1606
1766
1927
2084
2249
2408
2570

288
432
577
720
865
1009
1153
1297
1442
1585
1730
1874
2019
2162
2307

263
395
526
658
789
921
1052
1184
1316
1447
1579
1710
1842
1973
2105

225
338
450
564
677
789
901
1014
1128
1241
1353
1465
1578
1692
1805

160
239
320
398
479
558
637
716
796
877
956
1035
1116
1195
1274

621
828
1035
1042
1042
1657
1864
2072
2084
2084
2084
2900
3107
3126

553
737
920
1042
1042
1474
1658
1842
2025
2084
2084
2578
2763
2946

498
664
830
995
1042
1329
1494
1660
1827
1992
2084
2324
2491
2658

453
603
754
905
1042
1206
1353
1508
1659
1810
1960
2112
2263
2414

364
485
607
726
848
969
1090
1212
1333
1455
1576
1698
1819
1939

273
365
457
549
639
730
822
914
1005
1097
1187
1279
1370
1462

Discharge Rates 1.75 VPC

UNIGY II Discharge Rates in Watts per Cell to 1.75 VPC Final @ 77F (25C)
CELL
TYPE
45AH
6AVR45-5
6AVR45-7
6AVR45-9
6AVR45-11
6AVR45-13
6AVR45-15
75 AH
6AVR75-5
6AVR75-7
6AVR75-9
6AVR75-11
6AVR75-13
6AVR75-15
3AVR75-17
3AVR75-19
3AVR75-21
3AVR75-23
3AVR75-25
3AVR75-27
3AVR75-29
3AVR75-31
3AVR75-33
85 AH
6AVR85-7
6AVR85-9
6AVR85-11
6AVR85-13
6AVR85-15
3AVR85-17
3AVR85-19
3AVR85-21
3AVR85-23
3AVR85-25
3AVR85-27
3AVR85-29
3AVR85-31
3AVR85-33

Minutes
5

10

15

20

30

60

269
403
538
673
807
942

226
340
452
565
679
791

197
296
394
493
592
690

178
267
357
445
536
624

144
215
288
359
432
503

97
145
195
244
292
341

354
529
707
884
1042
1042
1413
1590
1767
1945
2084
2084
2474
2651
2828

312
469
624
781
938
1042
1250
1405
1562
1719
1874
2031
2186
2343
2500

280
420
560
700
840
980
1120
1260
1399
1539
1679
1819
1959
2099
2239

254
383
509
637
764
892
1018
1146
1273
1400
1527
1655
1782
1910
2036

215
325
433
540
648
756
865
973
1080
1188
1296
1405
1513
1621
1728

149
226
302
410
451
528
602
679
753
828
904
979
1033
1130
1205

607
811
1013
1042
1042
1620
1824
2026
2084
2084
2084
2837
3039
3126

538
717
897
1042
1042
1434
1614
1792
1992
2084
2084
2508
2688
2867

481
642
802
961
1042
1283
1442
1604
1763
1925
2084
2246
2406
2565

437
583
729
875
1021
1166
1312
1458
1605
1751
1895
2041
2188
2334

350
467
584
701
818
934
1051
1163
1285
1402
1518
1635
1752
1869

259
345
431
518
604
690
778
864
949
1035
1123
1208
1294
1380

13

Discharge Curves

Unigy II
Unigy II Performance
Curves

24
HR.

The following graphs can be


helpful in determining the ampere
hour capacity and the number of
amperes per positive plate for
selected battery types at different
end voltages from those given in
Tables 1, 2 and 3.
There is one set of performance curves for the 45, 75 and
85 ampere series Unigy II
batteries.
To find the ampere hour
capacity at a specified end
voltage, simply find the
intersection of the time and end
voltage curves. Multiply this value
by the number of positive plates
in the specified cell to obtain the
cell's A.H. rating. (Note: Cells
have one more negative plate
than positive plate, i.e., an
3AVR75-33 has 16 positive plates
and 17 negative plates.) By
aligning this intersection point
with the X axis, one can
determine the number of amperes
per positive plate delivered at the
specified discharge rate.

Unigy II
24
HR.

120

6
HR.

5
HR.

8
HR.

4
HR.

3
HR.

90

80

70

A.H./POS.

60

50

1
HR.

40

30
1.84

20

1.81

1.78

1.75

1.88
1.90
1.94

10
0
0

10

15

20

25

30

35

40

45

AMPS/POS.

Unigy II

1 - 24 Hours

4
HR.

3
HR.

24
HR.

120

85A Series

12 10 8
HR.HR.HR.

6
HR.

5
HR.

1 - 24 Hours

4
HR.

3
HR.

110

110
2
HR.

100
90

90

80

80

70

70

60
1
HR.

50

2
HR.

100

A.H./POS.

A.H./POS.

5
HR.

1 - 24 Hours

2
HR.

75A Series

12 10 8
HR.HR.HR.

12
HR.

45A Series

60
1
HR.

50
1.75
1.78

1.75

40

1.81

40

1.78
1.81

1.84
1.88

1.84
1.88

30

1.90

30

1.90

1.94

1.94

20

20

10

10
0

0
0

10

15

20

25

30

AMPS/POS.

14

35

40

45

50

10

15

20

25

30

AMPS/POS.

35

40

45

50

Discharge Curves

4.00
3.75
3.50
3.25
3.00
2.75
2.50
2.25
2.00
1.75
1.50
1.25
1.00
0.75
0.50
0.25
0.00

Unigy II Cell Impedance Data


at 77F (25C)
1.10
1.00

Unigy II AVR-75 & 85

Unigy II AVR-45

Impedance (Milli-Ohms)

Conductance (Kmhos)

Unigy II Cell Conductance Data


at 77F (25C)

0.90
0.80
0.70
0.60
0.50

Unigy II AVR-45

0.40
0.30

Unigy II AVR-75 & 85

0.20
0.10
0.00

11 13 15 17 19 21 23 25 27 29 31 33

# Plates/Cell

11 13 15 17 19 21 23 25 27 29 31 33

# Plates/Cell

Batteries are Recyclable!


Scrap lead-acid batteries have been safely recycled
since the 1920s, and today these batteries have a higher
recycling rate than other waste products such as
aluminum, paper, and beverage containers made of glass
or plastic, just to name a few. Over 98% of all used
batteries are recycled today.

East Penn has an E. P. A.-permitted recycling system


which is important for you to know because hazardous
disposal laws place heavy penalties on offenders and
considerable paper work burden on everyone. You can be
assured that your scrap is being recycled in an
environmentally safe manner with East Penn.

he lead is
processed,
smelted, combined
with reagents and
alloyed into lead
for use in new
batteries.

attery
acid is
recycled in
a patented
acid
reclamation
plant.

15

Worlds Largest and Most Modern


Battery Manufacturing Facility
Keller Technical Center
Health & Safety Center
Smelter and Refinery

Maintenance/Machine Shop
Corporate Headquarters

Automotive Battery Plant A-3

Plastics Molding Plant

Specialty Battery Plant S-1

Industrial Battery Plant

ince 1946, East Penn has


been producing high quality
batteries for the stationary, industrial, automotive,
commercial, marine and specialty markets. A
progressive company committed to the future, East
Penn operates the largest single-site manufacturing
facility in the industry. To keep pace with the increasing
demand for our high quality products, East Penn is
pursuing an aggressive expansion plan. In fact, our new
high-tech facilities and computer monitoring and
control systems have made us the industrys most
technologically advanced battery manufacturer. All Deka
batteries and accessories are produced at a huge
single-site manufacturing plant, pictured above.
Facilities at this 260+ acre site include a specialty
battery plant, an industrial battery plant, three

Cable and Wire Plant

automotive battery plants, wire and cable manufacturing


plants, a state-of-the-art oxide facility, an acid reclamation
plant, a modern technical center, an E.P.A.-Part B
permitted lead smelter and refinery, a pilot plant, two
water purification plants, a fully equipped machine shop,
a fleet repair and maintenance garage, plus dozens of
other support facilities. Our innovative computerintegrated manufacturing techniques, combined with
more than 250 quality assurance checks, guarantee that
every Deka battery meets our rigid quality and
performance standards. Staffed with a stable, long-term
management team, East Penn is an independent company
dedicated to producing a world-class product, delivered
on time when and where its needed for complete
customer satisfaction.
No part of this document may be copied or reproduced, electronically
or mechanically, without written permission from the company.