Tendering

SF6-insulated, metal-clad switchgear with vacuum circuit-breakers and single busbar

Contents:

1. 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8

Technical specifications General Circuit-breakers Disconnectors Interlocks Busbars Instrument transformers Panel connections Low-voltage compartment

2.

Standards

3.

Technical data

4.

Scope of supply

C:\Documents and Settings\in217595\Local Settings\Temporary Internet Files\OLK15\36kV GIS Specs (4).doc

03/01

1.

Technical specifications

1.1

General

The switchgear concerned is of the SF 6-insulated, type-tested, metal-clad type with vacuum circuit-breakers. The gas insulated switchgear shall be type tested for internal arc fault of 31.5 kA for 1 Sec.

1.1.1

The factory-assembled type-tested panels should be of uniform dimensions, regardless of the rated current. A panel width of 600 mm is preferred. All control and monitoring elements should be accessible from the front.

1.1.2

For reasons of operating reliability, the switchgear should feature singlephase encapsulation. All high-voltage components must be sealed hermetically and safe to touch. SF6 may be used only as an insulating medium, not for quenching. The prescribed insulation levels should be upheld without additional insulating material inside the gas compartments. Reliable operation of the switchgear must be assured even in the event of pressure drop to normal level.

1.1.3

Short disconnection times for expansion work at each end of the system must be assured. If possible, equipment allowing expansion without disconnection should be offered, provided that it does not take up any space in the panel width and depth.

1.1.4

The degree of protection of the high-voltage section should be IP 65. The minimum degree of protection prescribed for mechanical protection of all external parts is IP 3XD.

1.1.5

The arrangement of the circuit-breaker in the panel must be such that in the event of any necessary inspections both the operating mechanism and the arcing chambers can be removed and reinstalled from the front or back in a verifiably short time. The busbars must remain in uninterrupted operation and there must be no reduction in either the insulation level (additional measures such as protective barriers are not permitted) or personnel safety. Confirmation must be provided with the quotation.

1.1.6

Each sealed-off gas compartment must have its own pressure relief facility and without any arc fault limiter arrangment, which, in the event of an arcing 2

fault, prevents uncontrolled rupturing of the compartment. The manufacturers must guarantee an adequate pressure reserve between the operating value of the pressure relief and the rupturing pressure of the vessels. The pressure relief facilities must limit the effects of a fault arc to one compartment. Gas escaping under pressure must be diverted in a direction that is not dangerous for operating personnel; the same applies to fixed parts (rupture diaphragms etc.). The manufactuerer must furnish type test report for internal arc fault level of 31.5 kA for 1 Sec. 1.1.7 Pressure monitoring takes place with contact-making manometer gauges, which function independently for each busbar section, circuit-breaker gas compartment, three-position switch gas compartment or busbar voltage transformer set respectively. Manometer shall have positive indication without use of any proximity switch or auxiliary supply. The gas compartments must be well sealed both mutually and to their surroundings. The gas loss must not exceed 0,5 % per year and compartment. The filling pressure must be selected so that after 20 years of operation the full test voltages can still be withstood, without any topping up. 1.1.8 The use of plastics must be minimized, in order to likewise minimize the risk of fire in the event of a fault. The switchgear operation must be independent of the protection equipments like relays, meters being used.

1.1.9

1.1.20 There shall be mechanical mimic to indicate the positions of Breaker, 3 position switch ( disconnector ) and earthing switch. 1.1.21 Switchgear shall be suitable for manual ON and OFF operation in case motor supply not available.

1.2

Circuit-breakers

1.2.1

Vacuum circuit-breakers with maintenance-free fixed contact systems shall be used. Plug in contact or contact spring arrangement inside gas compartment for breaker poles connection shall be avoided. The breaker poles are to be mounted within the metal enclosure. Any insulated enclosure for breaker poles within metal enclosure is not permitted.

1.2.2

The vacuum circuit-breakers are to be equipped with Spring-stored-energy operating mechanism with motor, auto-reclosing Mechanical OPEN and CLOSE buttons 1 closing solenoid 1 shunt release Operating cycle counter Auxiliary switch with at least 4NO + 3NC available Auxiliary switch for "spring charged" signal Breaker tripping signal

1.2.3

To reduce the number of mechanical parts inside the enclosure, the operating mechanism shafts are to be located outside it. The circuit-breaker has to control at least 20,000 breaking operations at rated current or 50 breaking operations at rated short-circuit breaking current without maintenance. The mechanical life of the vacuum interrupter has to comprise at least 30,000 operating cycles.

1.2.4

1.2.5

The operating mechanism must be maintenance-free without time limit up to 10,000 operating cycles. Its service life has to comprise at least 30,000 operating cycles.

1.3

Disconnectors

1.3.1

Three-position switches reduce the number of functioning parts inside the enclosure. In combination with the circuit-breaker, the three-position switch is for makeproof earthing of the feeder.

1.3.2

1.3.3

The operating mechanism of the three-position switch should be actuated manually. There should be a facility for conversion to motor control.

1.3.4

Maintenance of the operating mechanism shall not be necessary before 2,000 operating cycles at the earliest, respectively after 10 years.

1.4

Interlocks

1.4.1

The combination of three-position switch and circuit-breaker must meet the following panel-internal interlock conditions: To prevent the disconnectors from switching under load, they may only be actuated with the circuit-breaker open. The three-position switch must be prevented from switching through from the closed state into the "ready-to-earth" state. The three-position switch may only be brought into the earthing position if the circuit-breaker is open. Closing of the circuit-breaker is blocked for as long as the three-position switch has not reached a definite switching position.

1.4.2

For earthing of the feeder, reliable "interrogation interlocking" must be provided: Only after the three-position switch has been switched into the "ready-to-earth" position may the feeder be earthed in a short-circuit-proof way by switching in the circuit-breaker.

1.4.3

The feeder earthing must be protected against "disconnection from earth": The remote control and protective tripping facility of the circuit-breaker must automatically become ineffective as soon as the three-position switch is switched into the "ready-to-earth" position. It must be posible to lock the local mechanical tripping by blocking the tripping mechnism mechanically.

1.5

Busbars

1.5.1

The busbars must be of flat copper of rectangular cross-section to DIN and must be continuous in the section concerned without transverse barrier. Individual pieces may be bolted together panel by panel.

1.5.2

To absorb thermal expansion and contraction movements, suitable compensation joints must be fitted if necessary.

1.5.3

High-grade cast resin components must be used for bracing the conductor; they must feature high resistance to creepage.

1.5.4

It must be possible to earth all busbar sections in a make-proof way.

1.6

Instrument transformers

1.6.1

Current and Voltage transformer shall be conventional type. Rogowski coil and or other non standard arrangement is not acceptable.

1.6.2

Current transformers must be of the dielectrically non-stressed toroidal-core type outside the enclosure.

1.6.3 1.6.4

Voltage transformers should preferably be inductive type. Voltage transformers must be totally insulated and metal-enclosed. SF6insulated transformers for bus voltage measurement must be accommodated in their own gas-tight compartments sealed off from the main conducting path. To allow voltage tests of the system, there should be a facility for disconnecting and earthing the transformer. Cast resin-insulated voltage transformers for line voltage measurement with direct metal enclosure should preferably be connected directly with the system at specially provided sockets.

1.6.5

Busbar/Line Voltage transformer shall be located within the panel without use of any additional metering panel. Bus VT should be equipped with motorized disconnector.

1.6.5

Capacitive dividers in the bushing leading to the cable termination should allow safe testing of the cable for dead state at the switchpanel front. These dividers must be a fixed integral part of the system. Capacitive layers on the plug connector may be used only for additional testing.

1.7

Panel connections

1.7.1

Totally insulated panel connections (cable plug connectors featuring the internal tapering system to DIN 46637) are preferred. They must be completely safe to touch.

1.7.2

There must be sufficient space available for connection of up to six cables of interface type 2 or of up to four cables of interface type 3.

1.8

Line Side Disconnector:

An additional Line side disconnector to be provided to isolate the feeder to ensure operator safety.

1.9

Low-voltage compartment

1.8.1 1.8.2

The low-voltage compartment must be arranged at the front. The control and signalling circuit wiring must be flexible and of cross-section 1.0 mm; for transformer circuits the figure is 2.5 mm. The signalling and control leads must be led to a terminal block via plug connectors in which they are grouped together according to function.

2.

Standards

The switchgear must comply with the following VDE standards and IEC publications: 1. 2. DIN VDE 0670, Part 1000 DIN VDE 0670, Part 6 Common clauses for high-voltage switchgear and controlgear Metal-enclosed high-voltage switchgear for rated voltages up to 72.5 kV, factoryassembled, type-tested 3. 4. 5. 6. 7. DIN VDE 0670, Part 101-108 DIN VDE 0414, Part 1 DIN VDE 0414, Part 2 DIN VDE 0414, Part 3 DIN VDE 0670, Part 601 High-voltage AC circuit-breakers Standards for instrument transformers Special standards for inductive current transformers Special standards for inductive voltage transformers Metal-enclosed high-voltage switchgear for rated voltages up to 72.5 kV, factoryassembled, type-tested. Test of behaviour in the event of internal faults 8. DIN VDE 0670, Part 402 Selection of current-limiting fuse links for transformer circuits

1. 2. 3. 4. 5.

IEC Publ. 694 IEC Publ. 62271-200 IEC Publ. 62271-100 IEC Publ. 185 IEC Publ. 186

Common clauses for high-voltage switchgear and controlgear standards A.C. metal-enclosed switchgear and controlgear up to 52 kV A.C. high-voltage circuit breakers Current transformers Voltage transformers

3.

Technical data

Rated voltage Operating voltage Rated power frequency withstand voltage Rated lightning impulse withstand voltage Frequency Rated short-circuit breaking current Rated short-circuit making current Rated short-time current 3 s Rated current of busbar Rated current of incoming feeders Rated current of outgoing feeders External paint finish Ambient temperature Degree of protection of high-voltage section Degree of protection of low-voltage section Control voltage of motor operating mechanisms Operating voltage for control and protection Dimensions per panel Width Depth Height Weight Minimum height of switchgear compartment Width of operating aisle

36kV 33kV 70kV 170kV 50Hz 31.5 kA 80kA 31.5 kA

SN 7000 40 C IP 65 IP 3XD

600 mm 1625mm 2350mm 3300 mm 1000 mm

4.

Scope of supply

The switchgear system should be equipped with the following panels in accordance with block diagram no. .... . The panels are described in more detail in the complement list:

Item

Qty.

4.1

...

Incoming feeder, panel no. ...

4.2

...

Coupling, panel no. ...

4.3

...

Outgoing feeder panel with busbar voltmeter, panel no. ...

4.4

...

Outgoing feeder panel, panel no.. ...

4.5

...

System end cover with busbar gas monitoring

4.6

1 set

Accessories

10

Item

Qty.

4.1

...

Incoming feeder, panel no. ...

Switchpanel equipped with: 1 set Busbars,

Three-position switch with manual operating mechanism, with auxiliary switch with at least 4NO + 4NC for disconnector and earthing switch function

Toroidal-core current transformer .../1/1A 1st core: ... 5 VA/0.5/M10 2nd core: ... 5 VA/10/P10

Metal-enclosed cast-resin insulated voltage transformer directly connectable to cable termination


0,1 0,1 kV 3 3

Class 0.5, 30 VA

1 set

Panel connections for 2 cables ... mm with cable plug connector

1 set

Capacitive dividers with wiring and sockets in switchpanel front.

11

Item

Qty.

Vacuum circuit-breaker ... A with: Spring-stored-energy operating mechanism with motor, autoreclosing Mechanical OPEN and CLOSE buttons Open actuation locking facility 1 shunt release Operating cycle counter Auxiliary switch 4NO + 4NC Auxiliary switch for "spring charged" signal Breaker tripping signal

Gas monitoring for circuit-breaker gas compartment with 1 pressure gauge with 2 signalling contacts for "pressure rising" and "pressure falling" signals

The following should be installed in the low-voltage compartment:

Miniature circuit-breaker, 2-pole, for motor circuit with auxiliary switch 1NO, 1NC

Miniature circuit-breaker, 2-pole, for control and protection with auxiliary switch 1NO, 1NC

...

Voltage transformer circuit-breaker, 3-pole, 3 A with auxiliary switch 1NO, 1NC

...

Ammeter, moving-iron, 96 x 96 mm

...

Voltmeter, moving-iron, 96 x 96 mm (with transfer switch)

...

Protective relay type ...................

12

Item

Qty.

4.2

...

Coupling with circuit-breaker, panel no. ...

Left-hand panel (circuit-breaker) equipped with:

1 set

Busbars

Three-position switch with manual operating mechanism, with auxiliary switch with at least 4NO + 4NC for disconnector and earthing switch function

Toroidal-core current transformer .../1/1A 1st core: ... 5 VA/0.5/M10 2nd core: ... 5 VA/10/P10

Vacuum circuit-breaker ... A with: Spring-stored-energy operating mechanism with motor, autoreclosing Mechanical OPEN and CLOSE buttons Mechanical CLOSE button sealable Mechanical OPEN button lockable Electrical button for closing actuation 1 closing solenoid 1 shunt release Operating cycle counter Auxiliary switch 5NO, 5NC Auxiliary switch for "spring charged" signal Breaker tripping signal

13

Item

Qty.

Gas monitoring for circuit-breaker and riser enclosure with 1 pressure gauge with 2 signalling contacts for "pressure rising" and "pressure falling" signals

Right-hand panel (riser) equipped with:

1 set

busbars

Three-position switch with manual operating mechanism with auxiliary switch with at least 4NO + 4NC for disconnector and earthing switch function with electromagnetically actuated blanking cover for manual operating mechanism interlock

The following should be installed in the low-voltage compartment:

Miniature circuit-breaker, 2-pole, for motor circuit with auxiliary switch 1NO, 1NC

Miniature circuit-breaker, 2-pole, for control and protection with auxiliary switch 1NO, 1NC

...

Voltage transformer circuit-breaker, 3-pole, 3 A with auxiliary switch 1NO, 1NC

...

Ammeter, moving-iron, 96 x 96 mm

...

Voltmeter, moving-iron, 96 x 96 mm (with transfer switch)

...

Protective relay type ...................

14

Item

Qty.

4.3

...

Outgoing feeder panel with busbar voltmeter, panel no. ...

Switchpanel equipped with: 1 set Busbars

Three-position switch with manual operating mechanism, with auxiliary switch with at least 4NO + 4NC for disconnector and earthing switch function

Toroidal-core voltage transformer .../1/1A 1st core: ... 5 VA/0.5/M10 2nd core: ... 5 VA/10/P10

Panel connection for 1 cable ... mm with cable plug connector

1 set

Capacitive dividers with wiring and sockets in switchpanel front

Voltage transformers on busbar 1 in SF6-filled enclosures with gas-tight compartmentalization from the busbar with threeposition switch in busbar compartment for disconnecting and earthing the voltage transformer

15

Vacuum circuit-breaker ... A with: Spring-stored-energy operating mechanism with motor, autoreclosing Mechanical OPEN and CLOSE buttons 1 closing solenoid 1 shunt release Operating cycles counter Auxiliary switch 5NO + 5NC Auxiliary switch for "spring charged" signal Breaker tripping signal

Gas monitoring for circuit-breaker gas compartment with 1 pressure gauge with 2 signalling contacts for "pressure rising" and "pressure falling" signals"

Gas monitoring as above, but for voltage transformer gas compartment

The following should be installed in the low-voltage compartment:

Miniature circuit-breaker, 2-pole, for motor circuit with auxiliary switch 1NO, 1NC

Miniature circuit-breaker, 2-pole, for control and protection with auxiliary switch 1NO, 1NC

...

Ammeter, moving-iron, 96 x 96 mm

...

Protective relay type .........

16

Item

Qty.

4.4

...

Outgoing feeder panel, panel no. ...

Switchpanel equipped with: 1 set Busbars

Three-position switch with manual operating mechanism, with auxiliary switch with at least 4NO + 4NC for disconnector and earthing switch function

Toroidal-core current transformer .../1/1A 1st core: ... 5 VA/0.5/M10 2nd core: ... 5 VA/10/P10

Panel connection for 1 cable ... mm with cable plug connector

1 set

Capactive dividers with wiring and sockets in switchpanel front.

Vacuum circuit-breaker ... A with: Spring-stored-energy operating mechanism with motor, autoreclosing Mechanical OPEN and CLOSE buttons OPEN actuation locking facility 1 shunt release Operating cycle counter Auxiliary switch 4NO + 4NC Auxiliary switch for "spring charged" signal Breaker tripping signal

Gas monitoring for circuit-breaker gas compartment with 1 pressure gauge with 2 signalling contacts for "pressure rising" and "pressure falling" signals"

17

Item

Qty.

The following should be installed in the low-voltage compartment:

...

Miniature circuit-breaker, 2-pole, for motor circuit with auxiliary switch 1NO, 1NC

...

Miniature circuit-breaker, 2-pole, for control and protection with auxiliary switch 1NO, 1NC

...

Ammeter, moving-iron, 96 x 96 mm

...

Protective relay ...

4.5

...

Switchgear system end cover

consisting of:

2 lateral end cover walls for the left and right system ends

2 blanking covers with gas monitoring for the left and right busbar section with shut-off valve and contact-making pressure gauges each with 2 signalling contacts for "pressure rising" and "pressure falling" signals

18

Item

Qty.

4.6

Accessories

consisting of: 1 Hand crank for charging the closing spring of the circuit-breaker

Lever for the operating mechanism of the three-position switch

Socket spanners for the low-voltage compartment door and the lower cover

Voltage detectors for capacitive voltage dividers

19