GENERAL

The protective relay serves for signalling a fault in the diverter switch / selector switch oil compartment and is to limit the damage to the on-load tap changer in case of a failure.It is, therefore, part of our delivery as a standard with all OLTC supplies.

2. TECHNICAL DATA

Housing

outdoor design

Protection

IP 54

Relay drive

flap valve with aperture

Critical oil flow tripping the flap valve

- 0.65 0.15m/s

- 3.00 0.30 m/s

Switch

Reed -contact, available as N/O-contact For other contact line-up see section 8, specialdesign.

Make / break curent capability

Max. 2 Amperes, 24...250 V a.c., 400VA

Max 2 Amperes, 24...250 V d.c., 250W

Test voltage to ground

2.0 Kilo Volts, 50Hz, 1 min.

Shock-proof

Up to 3 G

3. DESIGN

The housing is provided with 2 flanges for connecting

pipes leading to the tap changer head and to the oil conservator.

The flap valve position can be checked through the inspection glass on front of the housing.

The terminals are housed in a terminal box sealed against the oil of the relay.

For checking the tripping function of the relay as well as for subsequently resting the flap valve, two test push buttons are installed in the terminal box.

3.2 Relay (Fig.2)

The relay drive element consists of the flap valve with attached permanent magnet. The magnet actuates thereed- contact and serves for fixing the flap valve in position Transformer in service An intermediate position of the flap valve is not possible.

4. FUNCTION

The protective relay is energized by an oil flow from the tap changer head to the oil conservator only.

The oil flow operates the flap valve , being tripped in to the OFF position. At that moment the reedcontact is actuated, the circuit breakers are operated and the transformer is switched off the line.

The protective relay is not energised by the tapchanger being subject to nominal load or permissible overload.

OIL SURGE RELAY RS 2001

General & Operating Manual

5. INSTALLATION PROCEDURE5.1

Mounting

The protective relay has to be mounted in the

pipeleading from the tap changer head to the oil conservator. The relay must be located as near as

ossible to the tap changer head.

5.1.1 Prior to mounting, the protective relay function should be checked. Remove the cover of the

terminal box and operate.

Test push button : TRANSFORMER OFF

Flap valve is inclined ( line marker in the middle of the inspection window, Fig. 3)

Test push button TRANSFORMER SERVICE.: flap valve is vertical ( fig.4)

To megger terminals please refer to the dimension drawing B21000 (contact Positions) Check always

the position of the flap valve.

2. Housing Opened

1. Flap valve

2. Permanent Magnet 3. Reed contact

IN

5.1.2 Take care that the protective relay is installed in a horizonatl position with the test push buttons on top of the housing. The arrow on the terminal box cover must point towards the oil conservator.

3. Position OFF

Flap valve in Transformer off

3. Position IN SERVICE

Flap valve in position Transformer in Service

Fig. 3

Fig. 4