Sie sind auf Seite 1von 12

BRITISH STANDARD

BS EN 50288-6-1:2003

Multi-element metallic cables used in analogue and digital communication and control
Part 6-1: Sectional specification for unscreened cables characterised up to 250 MHz Horizontal and building backbone cables

The European Standard EN 50288-6-1:2003 has the status of a British Standard

ICS 33.120.10

12 &23<,1* :,7+287 %6, 3(50,66,21 (;&(37 $6 3(50,77(' %< &23<5,*+7 /$:

BS EN 50288-6-1:2003

National foreword
This British Standard is the official English language version of EN 50288-6-1:2003. The UK participation in its preparation was entrusted by Technical Committee EPL/46, Cables, wires, waveguides, R.F. connectors, R.F. and microwave passive components and accessories, to Subcommittee EPL/46/1, Communication cables, which has the responsibility to: aid enquirers to understand the text; present to the responsible international/European committee any enquiries on the interpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and promulgate them in the UK.

A list of organizations represented on this subcommittee can be obtained on request to its secretary. Cross-references The British Standards which implement international or European publications referred to in this document may be found in the BSI Catalogue under the section entitled International Standards Correspondence Index, or by using the Search facility of the BSI Electronic Catalogue or of British Standards Online. This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations.

This British Standard was published under the authority of the Standards Policy and Strategy Committee on 2 February 2004

Summary of pages This document comprises a front cover, an inside front cover, the EN title page, pages 2 to 9 and a back cover. The BSI copyright notice displayed in this document indicates when the document was last issued.

Amendments issued since publication Amd. No.


BSI 2 February 2004

Date

Comments

ISBN 0 580 43345 5

EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM


ICS 33.120.10

EN 50288-6-1
December 2003

English version

Multi-element metallic cables used in analogue and digital communication and control Part 6-1: Sectional specification for unscreened cables characterised up to 250 MHz Horizontal and building backbone cables
Cbles mtalliques lments multiples utiliss pour les transmissions et les commandes analogiques et numriques Partie 6-1: Spcification intermdiaire pour les cbles non blinds pour applications jusqu' 250 MHz Cbles horizontaux et verticaux de btiment Mehradrige metallische Datenund Kontrollkabel fr analoge und digitale bertragung Teil 6-1: Rahmenspezifikation fr ungeschirmte Kabel bis 250 MHz Kabel fr den Horizontal- und Steigbereich

This European Standard was approved by CENELEC on 2003-10-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Lithuania, Luxembourg, Malta, Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels
2003 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50288-6-1:2003 E

EN 50288-6-1:2003

Foreword This European Standard was prepared by SC 46XC, Multicore, Multipair and Quad Data communication cables, of Technical Committee CENELEC TC 46X, Communication cables. The text of the draft was submitted to the Unique Acceptance Procedure and was approved by CENELEC as EN 50288-6-1 on 2003-10-01. The following dates were fixed: - latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement - latest date by which the national standards conflicting with the EN have to be withdrawn This Part 6-1 is to be read in conjunction with EN 50288-1.
_____________

(dop) (dow)

2004-10-01 2006-10-01

EN 50288-6-1:2003

Contents Page 1 2 3 4 Scope.............................................................................................................................. 4 Normative references .................................................................................................... 4 Definitions...................................................................................................................... 4 Cable construction ........................................................................................................ 4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 Conductor............................................................................................................... 4 Insulation................................................................................................................ 4 Cabling elements.................................................................................................... 4 Identification of cabling elements............................................................................ 5 Screening of cabling elements................................................................................ 5 Cable make-up ....................................................................................................... 5 Filling compound .................................................................................................... 5 Interstitial fillers....................................................................................................... 5 Screening of the cable core.................................................................................... 5

4.10 Moisture barriers .................................................................................................... 5 4.11 Wrapping layers ..................................................................................................... 5 4.12 Sheath.................................................................................................................... 5 5 Tests and requirements for completed cables............................................................ 6 5.1 5.2 5.3 5.4 Electrical tests ........................................................................................................ 6 Mechanical tests..................................................................................................... 8 Environmental tests ................................................................................................ 9 Fire performance tests ........................................................................................... 9

EN 50288-6-1:2003

1 Scope This sectional specification covers unscreened cables, characterised up to 250 MHz, to be used in horizontal floor and building backbone wiring as defined in EN 50173. The electrical, mechanical, transmission and environmental performance characteristics of the unscreened cables, related to their reference test methods, are detailed. This sectional specification is to be read in conjunction with EN 50288-1 which contains the essential provisions for its application. 2 Normative references This European Standard incorporates by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the cited publications are listed hereafter. For dated references, subsequent amendments to or revisions of these publications apply to this European Standard only when incorporated in it by amendment or revision. For undated references, the latest edition of the cited publication applies, together with any amendments. EN 50173 EN 50288-1 EN 50289 EN 50290 IEC 60189-2 Series Series Information technology - Generic cabling systems Generic specification for multi-element metallic cables used in analogue and digital communication and control Communication cables - Specifications for test methods Communication cables Low-frequency cables and wires with PVC insulation and PVC sheath - Part 2: Cables in pairs, triples, quads and quintuples for inside installations

3 Definitions For the purposes of this European Standard the definitions of EN 50288-1 apply. 4 Cable construction 4.1 Conductor The conductor shall be solid copper and meet the requirements of 4.1 of EN 50288-1. The conductor shall be plain or metal coated. The nominal conductor diameter shall be 0,5 mm and 0,8 mm. 4.2 Insulation The insulation shall be of a suitable material according to the relevant part of EN 50290-2 4.3 Cabling elements The cable element shall be a pair or a quad.

EN 50288-6-1:2003

4.4 Identification of cabling elements Unless otherwise specified, the colour coding for identification is given in IEC 60189-2. The colours shall meet the requirements of 4.4 of EN 50288-1. 4.5 Screening of cabling elements Not applicable. 4.6 Cable make-up The cable elements shall be laid up in concentric layer(s) or units to form the cable core. 4.7 Filling compound Not applicable. 4.8 Interstitial fillers Where fillers are used they shall meet the requirements of 4.8 of EN 50288-1. 4.9 Screening of the cable core Not applicable. 4.10 Moisture barriers Not applicable. 4.11 Wrapping layers Where wrapping layers are used they shall be in accordance with 4.11 of EN 50288-1. 4.12 Sheath The sheath shall be of a suitable material according to the relevant part of EN 50290-2.

EN 50288-6-1:2003

5 Tests and requirements for completed cables The following tables give the tests to be applied, together with the respective limits, in order to demonstrate compliance with this specification. 5.1 Electrical tests 5.1.1 Low-frequency and d.c. electrical measurements
EN 50288-1 Subclause no. 5.1.1.1 5.1.1.2 5.1.1.3 Parameter Requirement

Conductor loop resistance Conductor resistance unbalance Dielectric strength conductor/conductor Insulation resistance Mutual capacitance Capacitance unbalance to earth

19,0 /100 m 2,0% 1,0 kV d.c. or 0,7 kV a.c. for 1 min or 2,5 kV d.c. or 1,7 kV a.c. for 2 s 500 M km using 100 V - 500 V test voltage No requirement specified 1 600 pF/km

5.1.1.4 5.1.1.5 5.1.1.6

5.1.2 High-frequency electrical and transmission measurements


EN 50288-1 Subclause no. 5.1.2.1 5.1.2.2 5.1.2.3 Parameter Requirement

Velocity of propagation Propagation delay difference (skew) Longitudinal 2) 3) attenuation


4)

Phase delay 534+36/f ns/100 m, 1 MHz f 250 MHz 40 ns/100 m at 100 MHz

1 2,1

4 3,8

10 6,0

16 7,6

20 8,5

31,25 62,5 10,7 15,5

100 19,9

155 25,3

200 29,1

250 MHz 33,0 dB/100m

1,82 f+0,0169f+0,25/ f, 1 MHz f 250 MHz 5.1.2.5 Near-end crosstalk 1) 2) (NEXT)


1 66,0 4 65,3 10 59,3 16 56,2 20 54,8 31,25 62,5 51,9 47,4 100 44,3 155 41,4 200 39,8 250 MHz 38,3 dB

74,3-15log(f), 1 MHz f 250 MHz (maximum 66 dB)

7 EN 50288-1 Subclause no. 5.1.2.7.1 Parameter Requirement

EN 50288-6-1:2003

Power sum near2) end crosstalk (PSNEXT)

1 64,0

4 63,3

10 57,3

16 54,2

20 52,8

31,25 62,5 49,9 45,4

100 42,3

155 39,4

200 37,8

250 MHz 36,3 dB

72,3-15log(f) 1 MHz f 250 MHz (maximum 64 dB) 5.1.2.6 Equal level far-end 2) crosstalk (ELFEXT)
1 66,0 4 58,0 10 50,0 16 45,9 20 44,0 31,25 62,5 40,1 34,1 100 30,0 155 26,2 200 24,0 250 MHz 22,0 dB

70-20log(f), 1 MHz f 250 MHz (maximum 66 dB), values referenced to 100 m 5.1.2.7.2 Power sum equal level far-end 2) crosstalk (PSELFEXT)
1 64,0 4 55,0 10 47,0 16 43,0 20 41,0 31,25 62,5 37,1 31,1 100 27,0 155 23,2 200 21,0 250 MHz 19,0 dB

67-20log(f), 1 MHz f 250 MHz (maximum 64 dB), values referenced to 100 m 5.1.2.8 5.1.2.9 Mean characteristic Impedance Return loss
5)

100 5 , 120 5 , at 100 MHz

4 23,1

8 24,5

10 25,0

16 25,0

20 25,0

31,25 62,5 23,6 21,5

100 20,1

155 18,8

200 18,0

250 MHz 17,3 dB

20+5log(f), 4 MHz f 10 MHz; 25,0 dB, 10 MHz f 20 MHz; 25-7log(f/20), 20 MHz < f 250 MHz; f.f.s. 5.1.2.4 Near-end unbalance attenuation Coupling attenuation 40-10log(f) dB, 1 MHz f 250 MHz f.f.s

5.1.2.10

40 dB, 30 MHz f 100 MHz f.f.s 40-20log(f/100) dB, 100 MHz < f 1 000 MHz

f.f.s

1)

For hybrid and multi-unit cables and cables, PSNEXT between all non fibre recognised cable units shall be 3 dB better than the specified pair to pair NEXT at all specified frequencies.
2)

The values in the table are for information only. The formula given shall be used to determine compliance, rounded to one decimal place. Above 20 C the attenuation shall meet values adjusted for temperature. Up to 40 C the temperature coefficient of 0,4 % per degree rise shall be used and for temperatures from 40 C to 60 C the temperature coefficient shall be 0,6 % per degree.
4) 5) 3)

Values between 1 MHz and 4 MHz are for information only.

For the measurement of return loss, a test sample having a round trip loss 40 dB at any measured frequency should be used.

EN 50288-6-1:2003

5.2 Mechanical tests


EN 50288-1 Subclause no 5.2.1 5.2.2 5.2.3 Parameter Requirement

Conductor elongation at break EN 50289-3-2 Shrinkage of insulation EN 50289-3-4 Crush resistance of the cable EN 50289-3-5

10 % 5 % for 1 h at 100 C 2 C 1 000 N / 1 min / 100 mm Near-end crosstalk, return loss and characteristic impedance shall remain within the specified limits

5.2.4

Impact resistance of the cable EN 50289-3-6

12,5 mm radius / 1 J / 3 impacts at 1 m from the measured end Near-end crosstalk, return loss and characteristic impedance shall remain within the specified limits

5.2.5

Abrasion resistance of the sheath markings EN 50289-3-8 Simulated installation testing of the cable Simulated installation testing of the cable Single bend EN 50289-3-9, Clause 4, procedure 2

Markings shall remain legible

5.2.6 5.2.6.1

Single bend 4 dia / 4 cycles Near-end crosstalk, return loss, characteristic impedance and coupling attenuation (u/c) shall remain within the specified limits S bend 8 dia / 100 m / 1 cycle / 120 deg / 1 m/s

5.2.6.2

Simulated installation testing of the cable S bend EN 50289-3-9, Clause 8

Near-end crosstalk, return loss, characteristic impedance and coupling attenuation (u/c) shall remain within the specified limits Load shall be 25 N per pair (i.e.100 N for 4 pairs) Near-end crosstalk, return loss, characteristic impedance and coupling attenuation (u/c) shall remain within the specified limits

5.2.7

Tensile performance EN 50289-3-16 combined with 5.2.6 of this standard

EN 50288-6-1:2003

5.3 Environmental tests


EN 50288-1 Subclause no 5.3.1 Parameter Requirement

Cold bend performance of the cable EN 50289-3-9

Mandrel diameter 8 OD, no. of turns 4, temp -20 C 2 C No cracks when examined visually without magnification

5.3.2

Temperature cycling EN 50289-4-6

The attenuation shall meet the adjusted values according to note 3 in Table 5.1.2 when subjected to 2 temperature cycles between 20 C and 60 C

5.4 Fire performance tests Fire performance tests shall be in accordance with 5.4 of EN 50288-1.

BS EN 50288-6-1:2003

BSI British Standards Institution


BSI is the independent national body responsible for preparing British Standards. It presents the UK view on standards in Europe and at the international level. It is incorporated by Royal Charter. Revisions British Standards are updated by amendment or revision. Users of British Standards should make sure that they possess the latest amendments or editions. It is the constant aim of BSI to improve the quality of our products and services. We would be grateful if anyone finding an inaccuracy or ambiguity while using this British Standard would inform the Secretary of the technical committee responsible, the identity of which can be found on the inside front cover. Tel: +44 (0)20 8996 9000. Fax: +44 (0)20 8996 7400. BSI offers members an individual updating service called PLUS which ensures that subscribers automatically receive the latest editions of standards. Buying standards Orders for all BSI, international and foreign standards publications should be addressed to Customer Services. Tel: +44 (0)20 8996 9001. Fax: +44 (0)20 8996 7001. Email: orders@bsi-global.com. Standards are also available from the BSI website at http://www.bsi-global.com. In response to orders for international standards, it is BSI policy to supply the BSI implementation of those that have been published as British Standards, unless otherwise requested. Information on standards BSI provides a wide range of information on national, European and international standards through its Library and its Technical Help to Exporters Service. Various BSI electronic information services are also available which give details on all its products and services. Contact the Information Centre. Tel: +44 (0)20 8996 7111. Fax: +44 (0)20 8996 7048. Email: info@bsi-global.com. Subscribing members of BSI are kept up to date with standards developments and receive substantial discounts on the purchase price of standards. For details of these and other benefits contact Membership Administration. Tel: +44 (0)20 8996 7002. Fax: +44 (0)20 8996 7001. Email: membership@bsi-global.com. Information regarding online access to British Standards via British Standards Online can be found at http://www.bsi-global.com/bsonline. Further information about BSI is available on the BSI website at http://www.bsi-global.com. Copyright Copyright subsists in all BSI publications. BSI also holds the copyright, in the UK, of the publications of the international standardization bodies. Except as permitted under the Copyright, Designs and Patents Act 1988 no extract may be reproduced, stored in a retrieval system or transmitted in any form or by any means electronic, photocopying, recording or otherwise without prior written permission from BSI. This does not preclude the free use, in the course of implementing the standard, of necessary details such as symbols, and size, type or grade designations. If these details are to be used for any other purpose than implementation then the prior written permission of BSI must be obtained. Details and advice can be obtained from the Copyright & Licensing Manager. Tel: +44 (0)20 8996 7070. Fax: +44 (0)20 8996 7553. Email: copyright@bsi-global.com.

BSI 389 Chiswick High Road London W4 4AL