INDIAN OIL CORPORATION LTD. PANIPAT, 194 MW CPP Date Rev. Purpose 13/08/07 0 For Review Spec. No.6556-EPCC4-52-SP-I-0002 Page: 1 of 1 Data sht. No: 6556-EPCC4-52-DS-I-0002 Prep. Reviewed Appd. Inst. Mech. AS MD FLOW: M3PH Installation Detail Drawing Measurement Principle SIZE: CM Please refer Specsheet 653SY Electronic measurement

EPC Contractor:

PMC

EPC Engineer:

TEMPERATURE TRANSMITTER DATASHEET


UNITS: GENERAL 1 3 5 7 Manufacturer Model No. Function and Type Range and Accuracy (including Linearity and Hysteresis) Rangeability Supply voltage effect Output Type Sensing Element Type PRESS: Bar ABB Limited 653SY13Y8132023 Transmit and Indicate TEMP: Degree's 2 4 6 8

CHARACTERISTIC

+/- 0.1 %of URV 10 12 14 16 18 20 Response Time Stability

0.5 Sec < 0.1 K per year 788 ohms Max

9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69

-200 to 850 deg C 0.05% / 10 V 4-20 mA with HART RTD

Load Capability

IS Exia group I IIA IIB IIC + CCoE 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 Hazardous Area Classification Input Configuration Transmitter Output Zero Adjustment Measuring Error Enclosure Class(Weather) Explosion Protection Type UP-Down Scale Protection Cable Entry Terminals Reference junction Intrinsically Safe Single sensor input 4-20 mA current signal YES Maximum error '+/-0.1% for RTD input , +/-0.2% for T/c IP 67 FLAMEPROOF Yes 1/2 "NPT(F) YES Internal Yes Yes

TRANSMITTER

Body Material Cable Gland Type / Size Span Adjustment Power Supply Requirement Temperature Effect Integral Indicator Integral Local Indication Type Mounting Failure mode Sensor monitoring

Die-cast Aluminium Double Compression YES 8.5 to 30 VDC YES Provided Digital LCD type 2" Pipe Mounting Yes Pipe mounting bracket Aluminium YES HART PROTOCOL YES 4-20 mA @24V DC, 2-wire

Case
Self Diagnostic Facility Protocol CALLIBRA TION Calibration Output Signal Range

Burn Out Protection

Output Isolated Load Impedance (Ohms)

YES 600

ACCESSORIES

Mounting Accessories SS Tag Plate

YES(Mounting Bracket with clamps YES

Certification Others Transient Surge Protector Certification Statutory

YES (CCOE) YES Yes

Cable Gland Type Cable Gland Material

Double Compression type 66 (CG) 68 Nickel-Plated brass with Sleeves


70

This document contains information which is confidential and proprietary to L&T-Sargent & Lundy (L&T-S&L). It shall not be reproduced in whole or in part or released to any third party without the prior written consent of L&T-S&L. Copyright L&T-Sargent & Lundy 2006 all rights reserved. Standards located on the network are to be considered as the official version of the Standard.

DATA SHEET NO. : DS_ICS-MP-011_29; REV. NO. : 0; DATE : 10-FEB-2006

172011738.xls.ms_office

OWNER PMC PMC PMC PMC PMC

INDIAN OIL CORPORATION LTD. PANIPAT


Rev. 0 INDIAN OIL CORPORATION LTD. PANIPAT, 194 MW CPP Date Purpose 13/08/07 For review Spec. No.6556-EPCC4-52-SP-I-0002 Page: 1 of 1 Data sht. No: 6556-EPCC4-52-DS-I-0002 Prep. Reviewed Appd. Inst. Mech. AS MD

LSTK

LSTK ENGINEER

Data Sheet for PRESSURE TRANSMITTER GENERAL

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 101 103

Manufacturer Model No. Range

ABB Limited 264HSSSNA1/VA/E7/L1/B1 + 2VM + CG 0 to 160 Bar

2 Function 4 6 8 10 12 14 16 18 20 22 24 26 28 30

Transmitter

CONSTRUCTION

Sensing Element Sensing Element Material Body Material Wetted Part Material Process Connection Case Case Colour Mounting Transmitter Type Power Supply

Diaphragam SS 316 L SS 316 L SS 316 L 1/2" NPT(F) Low copper Aluminium with Epoxy coating ABB Std. 2" Pipe Mounting Dual Inductance 10.5 -42 V DC

Facing and Finish NA Capillary Material NA Body Rating NA Flushing/ Filling connection withNA plug Size and Rating NA

Armour Type Armour Material Number of Cable Entry Self Diagnostic Feature

NA NA 2 Provided

FEATURES ACCESSORIES CHARACTERISTIC

Transmitter Output Size and Rating Integral Indicator Instrument Connection Cable Entry Connection

4-20 mA O/P (2-wire Smart Type with HART 32 Protocol Protocol) HART PROTOCOL 150# 34 Provided 36 1/2" NPT (F) 38 1/2" NPT(F) 40 42 44 Accuracy(including Linearity, Repeatability +/- 0.075% for and TD Hysteresis) of 15:1 46 Enclosure Protection(Weather) IP 67 Driving Capability of Load 600 Ohms (Min) at 24 V DC 48 Zero / Span Adjustment Yes - External Turn Down Ratio 100:1 50 Zero Elevation / Suppression 100% of span Overange Protection 210 bars for sensor code G to S 52 Stability Over 6 Months +/- 0.15% of URL over a period of 5 yrs. and 900bars for code V Load Resistance 600 ohms 54 Sensor Over Range Protection Please see over pressure limits in Hazardous Area Class FM/CMRI approval for IS, EX-ia, 56 Zone 1, Gr IIC + CCoE Driving Voltage for Transmitter 24 V DC 58 60 Indication Provided 62 Flushing Connection NA Indicator Type Integral Digital LCD type 64 Flushing Connection Quantity NA Syphon NA 66 Flushing Connection Size NA Syphon Material N/A 68 70 72 2-valve/3-Valve/5 valve/Closed2way Couple Valve Manifold Manifold (2VM) Manifold Material SS 316 Cable Gland Type Double Compression type (CG) Cable Gland Material Name Plate Nickel-Plated brass with Sleeves SS 74 76 78 80 82

Diaphragm Seal Type Diaphragm Material Capillary Type Capillary Length Adj. Damping Mounting Accessories

NA NA NA NA Provided 2" Pipe Mounting bracket

84 86 88 90 Certification 92 Integral Sq. Rt. Ext. 94 CCOE Approval Condensate Pot 96 Test Jack, Calibrating 98 100 102

Test/calibration report provided Provided Provided NA Provided

Note: 1. Process parameters and pipeline data indicated are preliminary and will be finalized before placement of order. 2. The operating range for transmitters shall be 30 - 80 % of the specified range of the instrument. 3. Counter Flanges with Nuts, Bolts, Washers and Gaskets to be offered by the Bidder as optional with flanged diaphragm seal transmitters.the prior written consent of L&T-S&L. Copyright L&T-Sargent & Lundy 2002 all rights reserved. Standards located on the network are to be considered as the official version of the Standard. 4. Bottom entry connection for Model code V, Drain / vent through 2 way valve manifold.