Technical guide
This Technical Guide has been produced to allow transformer manufacturers, and their designers and engineers, access to all the technical information required to assist them in their selection of the appropriate Transformer Bushing. The Guide should be used in conjunction with the Selection Guide to allow the optimum selection to be made. The technical information pertaining to bushings manufactured by ABB has been divided into separate documents, with one document for each type. The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB, or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice.
Table of Contents
Design _______________________
Test tap ____________________________ 4 4 5 5 6 6 7 7 7
Testing _______________________
Test tap adapter _____________________
52 170 kV
Dimensions _________________
8 Bushings without oil level gauge ______ 8 Shed form _______________________ 9 Bushings with oil level gauge _________ 10 Shed form _______________________ 11 12 Bushings without oil level gauge ______ 12 Bushings with oil level gauge _________ 14 16 16 16 16 17 17
300 kV
Dimensions _________________
18 Type GOB 1050 ___________________ 18 Shed form _______________________ 18 19 Type GOB 1050 ___________________ 19 20
Design
The bushing is built up around a centre tube on which the condenser body is wound. The upper insulator, lower insulator and mounting flange are held between the end plates by the centre tube. Sealing is accomplished by oil-resistant rubber gaskets in grooves. The annular space between the condenser body and the porcelain is filled with transformer oil. A gas-filled expansion space is left at the top. For GOB bushings without oil level gauge the oil level can be checked by means of a dipstick in the oil filling hole. The lower end is shielded by an epoxy resin insulated aluminium shield. The shield is integrated for 52 170 kV, and separate for 300 kV bushings. The inner terminal is attached to the centre tube by means of a through-going resilient pin which becomes locked when the outer terminal is screwed on. This design, patented by ABB, ensures effective electrical contact between the inner and outer terminals. The inner terminal can be chosen for connection to leads either by brazing or crimping. The outer terminal is available in aluminium or copper alloy and can be supplemented by terminal plates of corresponding material. The upper insulator is made in one piece of high quality electrical porcelain. The mounting flange is manufactured of corrosion-resistant aluminium alloy. The mounting flange, the top housing and the top washer are protected by painting with a two-component primer and a grey-blue finishing coat of paint. The standard colour is Munsell 5.5B 55/1.25, environmental class C3. The bushings are delivered oil-filled and ready for use. If the bushing is mounted with an inclination of more than 45 from the vertical, special measures may have to be taken to ensure the condenser body is fully submerged in oil. Further information can be obtained on request.
Outer terminal stud Oil filling holes with sealing plug Expansion space Oil Top washer Top housing
Flange extension Top housing Prism glass Oil filling holes with sealing plug
Porcelain insulator oil side Condenser body Insulated shield (integrated or separate)
Test tap
The outer conducting layer of the condenser body is connected to an insulated test tap on the flange. During operation the test tap cover must be screwed on, in order to earth the bushing. The max. test voltage of the tap is 2 kV, 50 Hz for 1 minute. Max. service voltage is 600 V.
goh_0010
Testing
During the manufacture and on its completion the bushing is subjected to a number of routine tests, in compliance with IEC 60137. A tightness test is carried out on the assembled bushing after the final drying and impregnation. The test is made with an oil overpressure of 180 kPa (1.8 bar) for 12 hours at ambient temperature. No sign of leakage is allowed. Each bushing is subjected to a final electrical routine test. The test is made at room temperature with the bushing submerged in oil. Capacitance and tan are measured in steps up to the power frequency withstand voltage, which is maintained for one minute. Capacitance and tan are also measured at decreasing voltage at the same voltage levels as before the one minute test. Measurements for detection of internal partial discharge (PD measurements) are also made. These measurements are carried out at the same time as the power frequency withstand test. PD measurements are made in steps up to the full test voltage and down. It is always demonstrated that the PD value is max. 5 pC at test voltage equal to the rated system voltage. GOB 1050 is also routine tested with a dry lightning impulse voltage withstand test. Fig. 3. Test tap adapter, 2769 531-D. Type tests have been carried out according to IEC 60137 and IEEE. Type test reports are available on request.
goh_0011
Electrical data
Rating Highest voltage for equipment Um kV, RMS 52 52 72.5 100 100 123 170 170 170 170 300 Phase-toearth voltage Uy kV, RMS 52 52 72.5 72.5 72.5 90 123 123 145 170 173 Dry lightning impulse kV, peak 250 250 350 380 380 450 550 550 650 750 1050 Wet power frequency AC kV, RMS 105 105 140 150 150 185 230 230 275 325 510 Routine test 1 min. dry 50 Hz kV, RMS 120 120 160 162 162 195 260 260 300 365 510 Design data Dry switching impulse kV, peak 230 230 300 330 330 410 470 470 580 670 810 Wet switching impulse kV, peak 750 Type GOB 250-800 250-1250 325-800 380-800 380-1250 450-800 550-800 550-1250 650-1250 750-1250 1050-1100
Wet power frequency values apply to both IEC and ANSI requirements.
Common specifications
Application: Classification: Ambient temperature: Altitude of site: Level of rain and humidity: Pollution level: Type of immersion medium: Oil level below bushing flange: Max. pressure of medium: Markings: Transformers Oil impregnated paper, capacitance graded, outdoor-immersed bushing +40 to -40 C, minimum value as per temperature class 2 of IEC 60137 < 1 000 m 1-2 mm rain/min horizontally and vertically, as per IEC 60060-1 According to specified creepage distance and IEC 60815 1 Transformer oil. Maximum daily mean oil temperature 90 C. Maximum temporary oil temperature 115 C Maximum 30 mm 100 kPa overpressure Conforming to IEC/ IEEE
1) IEC 60815 "Guide for selection of insulators with respect to polluted conditions."
Conductor loading
The rated currents listed in this catalogue are the standardised values according to IEC 60137 which, with the largest possible conductor, fulfil the temperature rise test.
Rated current of bushing A 800 1100, 1250 800, 1100, 1250 800, 1100, 1250 800, 1100, 1250 800, 1100, 1250 1100, 1250 1100, 1250
The GOB bushings fulfil the temperature rise test requirements according to IEC 60137 and IEEE C57.19.00-1991:
300 kV Permissible current IEC IEEE A A 1100 155 190 240 330 380 540 1000 130 160 195 275 320 450
Conductor Solid rod LF 170 019 Solid rod LF 170 052 Stranded cable 50 mm2 Stranded cable 70 mm2 Stranded cable 95 mm2 Stranded cable 150 mm
2
52-170 kV Permissible current IEC IEEE A A 800 1250 165 225 300 475 530 665 730 1200 150 210 285 415 460 570
Overloading of bushings
If the conductor for the bushing is selected with 120 % of the rated current of the transformer, the bushing is considered to be able to withstand the overload conditions stated in IEC 60354 without further clarifications or tests, according to IEC 60137.
For draw-lead of stranded copper values are given for 100 mm2. For other areas the short-time current is directly proportional to the area.
Rated current A 800 1100/1250 Short-time current (Ith) 1s 2s kA, RMS kA, RMS 30 70 21 50 Dynamic current (Id) kA, peak 52 125
Area mm2 -
Short-time current
The rated thermal short-time current (Ith) is calculated according to IEC 60137. Read more in product information 2750 515-118.
Stranded draw-lead
365
100
9.6
6.8
17
52 170 kV
Dimensions
Bushings without oil level gauge
Draw lead length =
Fig. 4.4
The bushings can be provided with a longer shield L9 + 50 mm, in which case dimensions L, L1 and L5 also increase by 50 mm.
n1 Holes D = 16
Cat. No. LF 123 013 015 083 LF 123 017 019 085 LF 123 025 027 089 LF 123 037 039 095 LF 123 041 043 097 LF 123 049 051 053 LF 123 061 063 107 LF 123 065 067 109 LF 123 073 075 113 LF 123 077 078 079
Space for current transformer mm 300 500 300 500 300 500 300 500 300 500 300 500 100 300 500 100 300 500 150 300 500 200 300 500
Net mass kg 23 25 27 26 29 31 27 31 35 33 37 39 37 39 43 42 45 48 70 73 77 105 109 115 116 122 126 180 190 200
Top design Dimensions in mm acc. to Fig. 6 L1 ) L1 1) L2 2 2 3 2 2 3 2 2 3 2 2 3 2 2 3 2 2 3 2 3 3 2 3 3 2 3 3 2 3 3 998 1258 1558 1063 1323 1623 1198 1458 1758 1303 1543 1843 1368 1608 1908 1473 1713 2013 1823 2108 2308 1868 2153 2353 2153 2413 2613 2468 2683 2883 240 500 700 255 515 715 295 555 755 345 585 785 360 600 800 345 585 785 495 680 880 495 680 880 580 740 940 685 800 1000 590 590 690 605 605 705 735 735 835 790 790 890 805 805 905 960 960 1060 1160 1260 1260 1170 1270 1270 1370 1470 1470 1580 1680 1680
L3 65
L4 555 555 655 580 580 680 700 700 800 755 755 855 780 780 880 925 925 1025 1125 1225 1225 1145 1245 1245 1345 1445 1445 1555 1655 1655
L5 1) 60
L6 260 460 260 460 260 460 240 440 240 440 240 440 95 280 480 95 280 480 120 280 480 165 280 480
L7 480
L8 70
L9 1) 15
250
1250
65
75
480
70
25
325
800
93
60
625
70
15
380
800
98
60
680
70
15
380
1250
98
75
680
70
25
450
800
98
60
850
70
15
550
800
60
90
1050
60
25
550
1250
68
100
1050
60
30
650
1250
60
100
1250
60
30
750
1250
70
100
1460
60
30
52 170 kV
Shed form
The shed form is of the anti-fog type with alternating long and short sheds. For each pair of sheds the ratio between nominal creepage distance and the axial length is 3.43 and the ratio between protected and nominal creepage distance is 0.40. According to IEC 60815 the creepage factor C.F. is <3.2 and the profile factor P.F. is >1.1. For special customer demands regarding creepage distance, other shed forms may be used. Fig. 4.5. Shed form, GOB 52 170 kV.
Dimensions are subject to modification without notice. Cantilever load Creeepage distance D1 86 D2 22 D3 86 D4 115 D5 88 D6 185 D7 225 D8 230 D10 46 n1 6 R1 8 R2 6 T 16 total mm 150050 protected mm 580 Max. permitted loading perpendicular 60 s to the terminal Test N N 1800 2340
101
34
112
120
101
250
290
245
70
12
10
16
150050
580
3000
4000
95
22
86
115
96
185
225
230
46
16
198050
775
1500
1950
95
22
86
115
96
185
225
240
46
16
221070
870
1400
1800
112
34
112
120
112
250
290
245
70
12
10
16
221070
870
2900
3750
95
22
86
115
96
185
225
245
46
16
272080
1060
1150
1500
126
22
118
145
150
250
290
280
50
12
12
18
3430100 1350
1300
1700
160
34
140
175
200
290
335
300
70
12
15
15
20
3430100 1350
2400
3100
160
34
140
175
200
290
335
305
70
12
15
15
20
4080110 1620
2600
3380
184
34
140
230
184
290
335
350
70
12
15
15
20
4800150 1700
2600
3350
52 170 kV
Dimensions
Bushings with oil level gauge
Draw lead length =
Fig. 5.4
The bushings can be provided with a longer shield L9 + 50 mm, in which case dimensions L, L1 and L5 also increase by 50 mm.
Cat. No. LF 123 171 173 175 LF 123 167 168 169 LF 123 177 179 181 LF 123 183 185 187 LF 123 101 102 103 LF 123 145 147 149 LF 123 189 190 191 LF 123 142 143 144 LF 123 192 193 194 LF 123 104 105 106
Space for current transformer mm 300 500 300 500 300 500 300 500 300 500 300 500 100 300 500 100 300 500 150 300 500 200 300 500
Net mass kg 24 26 28 28 30 33 28 32 36 34 38 40 38 41 44 43 46 49 71 74 78 106 110 116 118 124 128 187 197 207
Top design Dimensions in mm acc. to Fig. 7 L 1) L1 1) L2 2 1138 1398 1598 1203 1463 1663 1338 1598 1798 1443 1683 1883 1508 1748 1948 1613 1853 2053 1963 2148 2348 2008 2193 2393 2293 2453 2653 2718 2833 3033 240 500 700 255 515 715 295 555 755 345 585 785 360 600 800 345 585 785 495 680 880 495 680 880 580 740 940 685 800 1000 730
L3 65
L4 695
L5 1) 60
L6 260 460 260 460 260 460 240 440 240 440 240 440 95 280 480 95 280 480 120 280 480 165 280 480
L7 480
L8 70
L9 1) 15
250
1250
745
65
720
75
480
70
25
325
800
875
93
840
60
625
70
15
380
800
930
98
895
60
680
70
15
380
1250
945
98
920
75
680
70
25
450
800
1100
98
1065
60
850
70
15
550
800
1300
60
1265
90
1050
60
25
550
1250
1310
68
1285
100
1050
60
30
650
1250
1510
60
1485
100
1250
60
30
750
1250
1830
70
1805
100
1460
60
30
10
52 170 kV
Shed form
The shed form is of the anti-fog type with alternating long and short sheds. For each pair of sheds the ratio between nominal creepage distance and the axial length is 3.43 and the ratio between protected and nominal creepage distance is 0.40. According to IEC 60815 the creepage factor C.F. is <3.2 and the profile factor P.F. is >1.1. For special customer demands regarding creepage distance, other shed forms may be used. Fig. 5.5. Shed form, GOB 52 170 kV.
Dimensions are subject to modification without notice. Cantilever load Creepage distance D1 86 D2 22 D3 86 D4 140 D5 88 D6 185 D7 225 D8 230 D10 46 n1 6 R1 8 R2 6 T 16 total mm 150050 protected mm 580 Max. permitted loading perpendicular 60 s to the terminal Test N N 1800 2340
101
34
112
140
101
250
290
245
70
12
10
16
150050
580
3000
4000
95
22
86
140
96
185
225
230
46
16
198050
775
1500
1950
95
22
86
140
96
185
225
240
46
16
221070
870
1400
1800
112
34
112
140
112
250
290
245
70
12
10
16
221070
870
2900
3750
95
22
86
140
96
185
225
245
46
16
272080
1060
1150
1500
126
22
118
200
150
250
290
280
50
12
12
18
3430100 1350
1300
1700
160
34
140
265
200
290
335
300
70
12
15
15
20
3430100 1350
2400
3100
160
34
140
265
200
290
335
305
70
12
15
15
20
4080110 1620
2600
3380
184
34
140
265
184
290
335
350
70
12
15
15
20
4800150 1700
2600
3350
11
52170 kV
Ordering particulars
Bushings without oil level gauge
When ordering, please state: Type and catalogue number for bushings. Catalogue number for inner and outer terminal assembly. Additional accessories or modifications. Test required, in addition to the normal routine tests. Test tap adapter, if required. Note: The catalogue number should have one of the following letters added to it, to indicate the type of insulator and oil end shield: K Normal oil end shield, brown porcelain L Normal oil end shield, light grey porcelain M Longer oil end shield, brown porcelain N Longer oil end shield, light grey porcelain
Oil end shield
Bushings
Space for current transformer mm 300 500 300 500 300 500 300 500 300 500 300 500 100 300 500 100 300 500 150 300 500 200 300 500 Bushing tube (See fig.) D2, mm 22
Connection details
Inner terminal stud: Cat. No. LF 170
Cat. No. LF 123 013 015 083 LF 123 017 019 085 LF 123 025 027 089 LF 123 037 039 095 LF 123 041 043 097 LF 123 049 051 053 LF 123 061 063 107 LF 123 065 067 109 LF 123 073 075 113 LF 123 077 078 079
For crimping or brazing For brazing Conductor area Conductor area Undrilled with 2 2 2 50 mm 70 mm 95 mm <150 mm2 <285 mm2 pilot hole 010-M 010-N 010-L 011-S 011-U
250
1250
34
011-T
011-V
325
800
22
010-M
010-N
010-L
011-S
011-U
380
800
22
010-M
010-N
010-L
011-S
011-U
380
1250
34
011-T
011-V
450
800
22
010-M
010-N
010-L
011-S
011-U
550
800
22
010-M
010-N
010-L
011-S
011-U
550
1250
34
011-T
011-V
650
1250
34
011-T
011-V
750
1250
34
011-T
011-V
12
52170 kV
LF 170 019800 A
LF 170 0521250 A
Outer terminal assembly: Cat. No. LF 170 Stud with O-ring and locking pin Aluminium 001-A Copper alloy 002-A Separate terminal plate with bolts Aluminium 014-A Tin-plated copper 021-A Solid rod conductor Cat. No. LF 170 Alt. 1 019 -A -D -E 052 -A -D -E 019 -F -K -L 019 -M -R -S 052 -V -Z -AA 019 -BL -BM -BP 019 -T -X -Y 052 -AM -AN -AR 052 -F -K -L 052 -M -R -S Alt. 2 019 -B -C 052 -B -C 019 -G -H 019 -N -P 052 -X -Y 019 -BN -BR 019 -U -V 052 -AP -AS 052 -G -H 052 -N -P Mass kg 2.6 3.3 4.2 6.8 8.4 10.6 3.1 3.9 4.7 3.5 4.2 5.0 8.6 10.4 12.7 4.0 4.7 5.5 4.9 5.7 6.3 12.0 14.1 15.5 14.0 15.9 17.5 16.3 18.0 19.5 Arcing horns Cat. No. LF 170 004 -A -A -B 004 -A -A -B 004 -A -A -B 004 -A -A -B 004 -B -B -B 004 -B -B -C 004 -B -C -C 004 -B -C -C 005 -A -B -B 005 -B -E -E
001-B
002-B
014-A
021-A
001-A
002-A
014-A
021-A
001-A
002-A
014-A
021-A
001-B
002-B
014-A
021-A
001-A
002-A
014-A
021-A
001-A
002-A
014-A
021-A
001-B
002-B
014-A
021-A
001-B
002-B
014-A
021-A
001-B
002-B
014-A
021-A
13
52170 kV
Ordering particulars
Bushings with oil level gauge
When ordering, please state: Type and catalogue number for bushings. Catalogue number for inner and outer terminal assembly. Additional accessories or modifications. Test required, in addition to the normal routine tests. Test tap adapter, if required. Note: The catalogue number should have one of the following letters added to it, to indicate the type of insulator and oil end shield: K Normal oil end shield, brown porcelain L Normal oil end shield, light grey porcelain M Longer oil end shield, brown porcelain N Longer oil end shield, light grey porcelain
Oil end shield
Bushings
Space for current transformer mm 300 500 300 500 300 500 300 500 300 500 300 500 100 300 500 100 300 500 150 300 500 200 300 500 Bushing tube (See fig.) D2, mm 22
Connection details
Inner terminal stud: Cat. No. LF 170
Cat. No. LF 123 171 173 175 LF 123 167 168 169 LF 123 177 179 181 LF 123 183 185 187 LF 123 101 102 103 LF 123 145 147 149 LF 123 189 190 191 LF 123 142 143 144 LF 123 192 193 194 LF 123 104 105 106
For crimping or brazing Conductor area 50 mm2 70 mm2 95 mm2 010-M 010-N 010-L
For brazing Conductor area Undrilled with <150 mm2 <285 mm2 pilot hole 011-S 011-U
250
1250
34
011-T
011-V
325
800
22
010-M
010-N
010-L
011-S
011-U
380
800
22
010-M
010-N
010-L
011-S
011-U
380
1250
34
011-T
011-V
450
800
22
010-M
010-N
010-L
011-S
011-U
550
800
22
010-M
010-N
010-L
011-S
011-U
550
1250
34
011-T
011-V
650
1250
34
011-T
011-V
750
1250
34
011-T
011-V
14
52170 kV
LF 170 019800 A
LF 170 0521250 A
Outer terminal assembly: Cat. No. LF 170 Stud with O-ring and locking pin Aluminium 001-A Copper alloy 002-A Separate terminal plate with bolts Aluminium 014-A Tin-plated copper 021-A Solid rod conductor Cat. No. LF 170 Alt. 1 019 -AM -AS -BB 052 -BC -BF -BG 019 -AN -AU -BD 019 -AP -AX -BF 052 -BK -BN -BP 019 -BS -BT -BV 019 -AR -AZ -BH 052 -AT -AU -AV 052 -AD -AE -AG 052 -AZ -BA -AK Alt. 2 019 -AT -BC 052 -BD -BE 019 -AV -BE 019 -AY -BG 052 -BL -BM 019 -BU -BX 019 -BA -BK 052 -AX -AY 052 -AF -AH 052 -BB -AL Mass kg 3.0 3.7 4.3 7.7 9.3 10.8 3.5 4.3 4.8 3.9 4.6 5.1 9.6 11.4 12.6 4.4 5.1 5.6 5.3 5.8 6.4 13.0 14.4 15.8 14.9 16.1 17.7 18.0 19.0 20.5 Arcing horns Cat. No. LF 170 004-B -B -B 004-B -B -B 004-B -B -B 004-B -B -B 004-B -B -B 004-C -C -C 004-C -C -C 004-C -C -C 005-B -B -B 005-F -F -F
001-B
002-B
014-A
021-A
001-A
002-A
014-A
021-A
001-A
002-A
014-A
021-A
001-B
002-B
014-A
021-A
001-A
002-A
014-A
021-A
001-A
002-A
014-A
021-A
001-B
002-B
014-A
021-A
001-B
002-B
014-A
021-A
001-B
002-B
014-A
021-A
15
52 170 kV
Connection details
Inner terminal
Stud made of copper for connection of draw lead. The inner terminal must be provided with an outer terminal.
Material and Conductor design area mm Cat. No. Copper for crimping or brazing Copper for brazing only 50 70 95 < 150 undrilled < 285 undrilled LF 170 010-M -N -L LF 170 011-S -U -T -V Dimensions (mm) D1 D2 L 11 13 15 18 5 29 5 14,5 35 17 35 20 35 20 20 32 32 35 35 20 20 Mass kg 0,3 0,3 0,3 0,3 0,3 0,6 0,6
Outer terminal
Stud made of copper or aluminium with O-ring and locking pin. Other types can be provided on request.
Material Cat. No. For bushings with D2 mm 22 34 22 34 Width across flats N
16
52 170 kV
Arcing horns
Arcing horns of galvanised steel can be mounted on the bushing. The lower rod is fastened onto the flange with one of the fixing screws and the upper rod by means of a bracket on the outer terminal. The gap distances for standard arcing horns are shown in the table. Other gap distances on request.
Bushing type GOB 250 GOB 325 GOB 380 GOB 450 GOB 550 GOB 650 GOB 750 K mm 230440 320580 400620 400780 620960 7001080 8201290 C mm 315 315 315 315 315 380 380 H mm 112 112 112 112 114 224 224
17
300 kV
Dimensions
Type GOB 1050
D=265 D=355
When ordering, please state: Type and catalogue number for bushings. Catalogue number for inner and outer terminal assembly. Additional accessories or modifications. Test required, in addition to the normal routine tests. Test tap adapter, if required. Note: The catalogue number should have one of the following letters added to it, to indicate the type of insulator and oil end shield: K Brown porcelain L Light grey porcelain
L6 180 20
L L2 L7
D=200
L1 L3
L4
gob_0020
Dimensions are subject to modification without notice. Space for current transformer mm 300 600
Creepage distance Net mass kg 335 350 Dimensions in mm L 3690 3990 L1 930 1230 L2 2555 2555 L3 49 49 L4 2530 2530 L6 300 600 L7 2066 2066 total mm 7500 7500 protected mm 3200 3200
Shed form
R8
67.5
The shed form is of the anti-fog type with alternating long and short sheds. For each pair of sheds the ratio between nominal creepage distance and the axial length is 3.97 and the ratio between protected and nominal creepage distance is 0.4. According to IEC 60815 the creepage factor C.F. is 3.7 and the profile factor P.F. is >1.1. For special customer demands regarding creepage distance, other shed forms may be used.
18
10
31 70
R10
52.5
R4.5
gob_0021
18
300 kV
Ordering particulars
Type GOB 1050
M8 M8
Alt. 1 - 3
D=30
66 205 D=32
gob_0023
28
D=105 D=176
R1 5
The solid rod can be divided: Alt. 1: 20 mm below the bushing flange Alt. 2: 20 mm below the upper end of the bottom porcelain Alt. 3: 210 mm above the bottom end of the bushing
R6
gob_0024
19
250800 2501250 325800 380800 3801250 450800 Earthed layer Distance to uninsulated detail 550800 5501250 6501250 7501250 10501100
65 75 75 85 75 100 100 105 105 110 105 125 130 155 140 160 160 185 185 210 240 260 300
ABB
GOB250
Ludvika, Sweden
LF 123 013-K
No. 1ZSC 257 007 Um/Uy 52/52 kV Ir 800 A 50/60 Hz LI / AC 250/120 kV M 23 kg L 240 mm 0-90 C1 128 pF Tan 0.33 % C2 80 pF Tan 0.45 %
20
Notes:
21
Notes:
22
23
ABB Power Technologies AB Components Visiting address: Lyviksvgen 10 Postal address: SE-771 80 Ludvika, SWEDEN Tel.+46 240 78 20 00 Fax +46 240 121 57 E-mail: sales@se.abb.com www.abb.com/electricalcomponents