EVR AUTOMATIC RECLOSER


USERS MANUAL

ENTEC

ENTEC
ELECTRIC & ELECTRONIC CO., LTD

Copyright 2002 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved.

Forerunner Distribution & Automation

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

TABLE OF CONTENTS

GENERAL GUIDANCE............................................................................................................ 5

1. INTRODUCTION ........................................................................................................... 6 2. STANDARD RATINGS .................................................................................................. 7 3. CONSTRUCTION........................................................................................................... 8


3.1. INTERRUPTER................................................................................................................ 10 3.2. MAGNETIC ACTUATOR................................................................................................ 10 3.3. BUSHING ......................................................................................................................... 11 3.4. MANUAL TRIP/LOCKING DEVICE ............................................................................. 12 3.5. SF6 GAS ........................................................................................................................... 13 3.5.1. General ................................................................................................................... 13 3.5.2. Specification of Sulphur Hexa Fluoride Gas (SF6)................................................ 13 3.5.3. SF6 gas pressure-Temperature Curve..................................................................... 14 3.6. MOLECULAR SIEVE...................................................................................................... 14 3.7. BATTERY AND BATTERY CHARGER ......................................................................... 15 3.8. CONTROL CUBICLE ...................................................................................................... 16 3.9. AUXILIARY POWER SUPPLY....................................................................................... 17 3.10. GAS FILLING VALVE................................................................................................... 20 3.11. ACCESSORIES............................................................................................................... 20

4. PACKING, HANDLING AND STORAGE ................................................................. 21


4.1. PACKING AND DESPATCH ........................................................................................... 21 4.2. UNPACKING AND HANDLING .................................................................................... 21 4.3. RECEIVING ..................................................................................................................... 22 4.4. STORAGE ........................................................................................................................ 22

5. INSTALLATION ........................................................................................................... 23
5.1. INSPECTION BEFORE INSTALLATION ...................................................................... 23 5.1.1. General ................................................................................................................... 23 5.2. TESTING .......................................................................................................................... 23 5.2.1. Gas pressure ........................................................................................................... 23 5.2.2. Battery check.......................................................................................................... 24

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

5.2.3. Contact life of vacuum interrupter.......................................................................... 24 5.2.4. Resistance test on current carrying main circuit..................................................... 24 5.2.5. High voltage insulation test .................................................................................... 24 5.2.6. Operation test ......................................................................................................... 25 5.2.7. Secondary current injection test ............................................................................. 25 5.3. INSTALLATION............................................................................................................... 25 5.3.1-1. Standard pole mounting of recloser tank............................................................. 25 5.3.1-2. Substation mounting frame ................................................................................. 28 5.3.1-3. Surge Arrester mounting frame ........................................................................... 29 5.3.2. Control cubicle ....................................................................................................... 30 5.3.3. Earthing .................................................................................................................. 31 5.3.4. High voltage connection......................................................................................... 33 5.3.5 Bushing.................................................................................................................... 33

6. RECLOSER OPERATION .......................................................................................... 35


6.1. GENERAL ........................................................................................................................ 35 6.2. OPERATION PROCEDURE ............................................................................................ 35

7. MAINTENANCE .......................................................................................................... 36
7.1. GENERAL ........................................................................................................................ 36 7.2. DISMOUNTING OF RECLOSER ................................................................................... 36 7.3. CONTACT LIFE OF VACUUM INTERRUPTER........................................................... 36 7.4. SF6 GAS REFILLING ...................................................................................................... 38 7.4.1. General ................................................................................................................... 38 7.4.2. Refilling procedure................................................................................................. 38

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

GENERAL GUIDANCE
ENTEC automatic vacuum recloser hereinafter as EVR is designed to operate after installation on an outdoor pole and substation. This product consists of the minimum number of components to achieve maintenance free, maximum safety and endurance. To ensure the maximum life and the best quality of operation, operate EVR in accordance with the instruction manual and keep the following guidance. Be fully aware of the instruction manual before operating EVR. Safety check is required before installing, operating, and maintenance EVR. After installation, connect AC 110/220V from the distribution line to the CONTROL CUBICLE and run a test operation. If works need to be done after opening the control CUBICLE middle cover, turn the main circuit breaker (MCB) OFF to avoid any accident due to the high voltage. Avoid any flame work such as welding and brazing on EVR because the main tank is filled with SF6 gas for insulation.

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

1. INTRODUCTION
This manual contains the information required for installation, operation, and maintenance of ENTEC EVR Automatic Recloser. EVR is designed to be powered from AC 110/220V low voltage distribution line. EVR complies with the international standard specifications and ratings. EVR consists of the corrosion-resistance stainless steel tank (main tank) and the control cubicle, which are connected by separable shielded cable that is insulated. The main tank contains the vacuum interrupter and the magnetic actuator. Although the main tank can be disconnected from the Control Cubicle, none of them can be exchanged with other products. If replacement is required, please consult with the ENTEC E&E Co. Ltd. The inside of the main tank is filled with SF6 gas for insulation and the control cubicle is equipped with two of DC 12V batteries in series together. Batteries supply DC 24V control power to a control circuit after rectifying from low voltage AC source. General configuration of recloser is shown as below.
H.V Connector

Polymeric or Porcelain bushing Manual trip & locking device


LOCK TRIP

Pressure rupture device Gas filling valve

Earth terminal Control cable receptacle ON-OFF Indicator

Figure 1-1. Recloser Lay-Out Table 1-1. Dimension(mm) kV 15kV 27kV 38kV/630A 38kV/800A A 715 760 841 841 B 375 460 475 475 C 925 1020 1058 1078 D 300 300 320 320

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

2. STANDARD RATINGS
The standard ratings of EVR Recloser are as follows; Table 2-1. STANDARD RATINGS
Maximum system voltage Rated frequency Rated continuous current Rated short circuit interrupting current Rated making current (peak value) Power frequency withstand voltage - dry - wet Rated impulse withstand voltage Mechanical operation life Auxiliary power supply Control circuit voltage Protection current transformer (CT) ratio Weight - main tank - control cubicle 160kg 85kg 170kg 85kg 210kg 90kg DC 24V 1000:1 A 50kV(1 min) 45kV(10 sec) 110kV BIL 10,000 operations 60kV(1 min) 50kV(10 sec) 150kV BIL 10,000 operations 70kV(1 min) 60kV(10 sec) 170kV BIL 10,000 operations (peak value) (peak value) 15kV 50/60Hz 630A 12.5/16kA 32.5kA 27kV 50/60Hz 630A 12.5/16kA 32.5kA 38kV 50/60Hz 630/800A 12.5/16kA 32.5/ 40kA

AC110/220V external power sources DC 24V 1000:1 A DC 24V 1000:1 A

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

3. CONSTRUCTION
The Recloser can be mounted on an outdoor pole by assembling a mounting bracket connected to the top of main tank and also installed at substation with substation mounting frame. The vacuum interrupter, magnetic actuator, and current transformer (CT) are contained in the TIG-welded main tank and filled with SF6 gas for the insulation of recloser main tank. The interruption of Recloser is performed by the vacuum interrupter and SF6 gas is used to insulate. The recloser filled with SF6 gas does not produce any by-products by arc during interruption. Thus it maintains permanent insulation capability and prevent corrosion of the main tank components. The Recloser interrupter arranged with the 3-phase dielectric mold frame, consists of the vacuum interrupter and the trip spring with the same distance. The driving arm connected at the end of moving contact transfers a driving force of the magnetic actuator to the interrupter for close and open operation. The 6 bushings on the top of main tank can be supplied with porcelain, polymeric(E.P.D.M. rubber or silicone rubber) bushing upon to user's request. The current transformer (CT) is installed at the bushing connected at the fixed contact of interrupter in the main tank, and CT can monitor phase fault currents, earth fault currents and load currents, and send signals to the control electronics. If the control cable of CT is disconnected at both end, the CT is automatically shorted by the automatic CT protection circuit. The manual Trip/Locking device is positioned on the front side of main tank. The indicator points an interrupter's open/close status and the operation counter are located at the bottom of main tank. The Recloser operation sequence is performed by the microprocessor-based relay. The relay is installed in the control cubicle protected by rain-proof case. The Recloser immediately performs a preset operation sequence to re-close when a phase/ground fault current is higher than the preset value. If a fault current is not cleared at the end of full protection sequence, the Recloser will be lockout as tripped, and remains until the next close operation. If a fault current is cleared during the protection sequence, the Recloser is closed, and then returns into sleep mode after the reset time.

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

When a fault current is detected, the recloser operates the pre-set full protection sequence again. EVR is powered by AC 110/220V low voltage distribution line source without an additional transformer and is designed to consume low energy to operate reclosing and remote control. Thus EVR does not need any extra cost for installation of additional transformer, in case, low voltage source by utility is available. In case that low voltage power source is not available, the recloser is fitted with an auxiliary voltage transformer to supply auxiliary power to the control cubicle. During open and close operations, the relay sends the pulse type current to the open and close coils, and the magnetic force is induced by those coils and moves the plunger of the magnetic actuator. This driving force is transferred to the vacuum interrupter, which makes contact point tripped or closed. During trip and close operations, arc is produced and rapidly extinguished in the vacuum interrupter. The relay setting in control circuit can be modified at the control panel, a PC or remotely controlled communication method. For more details, refer to EVRC2A manual.

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

3.1. INTERRUPTER
The vacuum interrupter of the recloser can provides versatilities to operate trip/close with the ratings and capacity based on the fully capable of interruption. The closing status of the contacts is held by contact springs that provide the required force at all condition of contact wear. As a vacuum interrupter is fully sealed for the lifetime of the recloser and it requires only a small contact stroke and low interruption energy. it is suitable for application of magnetic actuator mechanism and also vacuum interrupter has a capability of a large number of operations, which is ideal for the reclosers application. Thus, vacuum interrupter with magnetic actuator provides a high reliability in operation and minimum maintenance if the replacement of the vacuum interrupter is required with any reasons, please consult with manufacturer.

Fixed busbar

Moving busbar

Vacuum interrupter

Opening spring

Figure 3-1. Recloser Interrupter

3.2. MAGNETIC ACTUATOR


The magnetic actuator designed by the newest technology delivers force to the interrupter. Since the magnetic actuator consumes low energy, actuator switching operation can be simply achieved through rectifying circuit with the low voltage AC 110 or 220V supplied from an external power sources and battery charged with the low voltage sources.

10

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

The permanent magnetic actuator mechanism has just one moving part. Thus the dramatic reduction in part gives a corresponding increase in reliability. Especially, as the actuator uses magnetic latching and uses trip and close coil separately, the actuator consists of the fewest components and can provides zero-maintenance operation. The actuator driving arm is made of high strength aluminum alloy and delivers force to the interrupter. When pulse current flows into the close coil, the plunger of magnetic actuator is moved by the induced magnetic force to drive the interrupter to close position, and the actuator is then held in the closed position. In contrast, when pulse current flows into the trip coil, the plunger is released from the magnetic latch and the interrupter is moved to trip position.

Figure 3-2. The principles of magnetic actuator operation

3.3. BUSHING
Bushing is mounted on the top of the recloser tank and supplied with either porcelain or polymeric bushing(EPR or Silicone rubber) depending upon users requirements. The ring core CT is mounted on the lower part of bushing inside of the recloser tank arranged at the fixed position of interrupter and senses the current flow. This current information is transmitted to the micro-processor based relay via the multi-core cable. Capacitor voltage divider (CVD) is available in case of using polymeric bushing to measure and sense the secondary voltage for signaling use.

ENHANCED TECHNOLOGY

11

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

3.4. MANUAL TRIP/LOCKING DEVICE


During control circuit faults or line repair, users can locally trip or lock the Recloser with the manual Trip/Locking device positioned on the front side of main tank. It can be manually operated by COS hot stick. If Trip/Locking device lever is in lock position, the Recloser can't be operated by local/remote control due to actuator power-off. In this lock position, the user should push the manual Trip/Locking device up to the trip position to release the locking status of the recloser and then the recloser can be operated by local or remote control. The recloser can be opened manually by using a hot stick to pull down the manual trip handle and the recloser with further pulling down can be locked.

Manual trip & Locking device


LOCK TRIP

Hot stick

Figure 3-3. Manual Trip/Locking device of the recloser

12

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

3.5. SF6 GAS


3.5.1. General
The high purity SF6 gas filled with 0.5bar gauge keeps the insulation of the equipment and prevent corrosion of the main tank components.

3.5.2. Specification of Sulphur Hexa Fluoride Gas (SF6)


Table 3-1. Specification Determination Purity CF4 Air Water Acidity as HF Hydrolye, fluor Specification > 99.9 0.05 0.05 50 0.3 1 Unit % wt % wt % wt Vppm mg/kg mg/kg Analysis > 99.9 < 0.03 < 0.03 < 50 < 0.3 <1

Table 3-2. Physical properties Sublimation point (1.0133 bar) Melting point (2.26 bar) Vapour pressure (20) Critical temperature Critical pressure Critical density Gas density (20, 1bar) Liquid density (0, 12.65 bar) Acoustic velocity in SF6 -63.9 -50.8 21.08 bar 45.55 37.59 bar 0.74 kg/l 6.07 g/l 1.56 kg/l 129.06 m/sec.

ENHANCED TECHNOLOGY

13

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

3.5.3. SF6 gas pressure-Temperature Curve

Figure 3-4. SF6 gas pressure -Temperature curve

3.6. MOLECULAR SIEVE


The molecular sieve to be used is type 13X and other designations must not be used in SF6 gas. The 13X has a controlled pore size of about 9 angstrom (0.9) as typical chemical Na2O, A2O3, 2.5SiO2, nH2O. A polyester bag containing molecular sieve beads is placed inside the enclosure and the control cubicle. Molecular sieve 13X is commonly used for the concurrent removal of H2O and CO2 from gas, air streams and removal of H2S. Molecular sieve 13X can be regenerated by evacuating or purging, usually at elevated temperatures ranging from 200 to 300. Higher temperature may cause physical degradation of the molecular sieve structure.

e r u s s e r p g n i t a r e p o e c i v e d y t f a S e r u s s) eC r5 p2 gt na i lG l im fc / lg ak m5 r. o0 N(

e) rG um sc s/ eg rk p2 . m0 a( l A

14

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

Typical properties shows as follows; Table 3-3. Typical properties Typical properties Nominal pore diameter Type of crystal structure Bulk density Water content(as shipped) Heat of absorption(max) Bead size(nominal) 9 angstrom(0.9) hexagonal 680g/ 1.5% wt (max) 4200kj/kgwater 2.55, 23, 12 48mesh, 812mesh, 1018mesh

3.7. BATTERY AND BATTERY CHARGER


The battery for operating the Reclosers components and control circuit is placed in the lower part of the control cubicle and can be easily replaced. The battery life is usually 5 years, but it can be shortened depending on how it is handled. The fully charged battery is enough for 30 hours operation without an external power source. Battery specification shows as follows; Table 3-4. Battery Specification Battery Specification Battery Type Nominal Voltage Nominal Capacity Battery Dimension Self-discharge Versus Time Service life Time Battery Connector(CN11) Battery Charger Charge Voltage Charge Current 27.5Vdc(0.5V) Max 300mA ES18-12 12V 18 amp-hours 181 76 167mm +20 3%/month, +40 10%/month Max. 5 years at +20 Molex Connector 3191-2R

ENHANCED TECHNOLOGY

15

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

3.8. CONTROL CUBICLE


The Recloser control cubicle is designed for outdoor pole mounted and substation operation which is made of anti-corrosion stainless steel. The door is locked with three position locking devise and sealed with replaceable urethane foaming packing. All vents are screened against vermin entry and the cubicle inside is fully covered with adiabatic faming material which protects the inside components from the rapid temperature variation. The control cubicle outside is protected with a sunshine shield cover which is required for keeping the life cycle from shortening because the temperature sensitive electronic components and battery is affected by sunshine heating. The microprocessor based control compartment is completely sealed against water entry even though the hatch door is opened in the rain during the recloser operation. The condensation of the cubicle inside can be expected to foam due to the temperature variation under the atmospheric conditions such as tropical and moderate climate, however, any condensation does not affect any electronic components arranged with fully insulated sealed and well vented design.

Figure 3-5. Control cubicle layout Consequently, any condensation on metal surface will run out of the bottom and automatically dried without affecting the electronic modules by ventilation and self heating. The standard control cubicle contains the relay, batteries for control power and mechanism driving power.

16

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

The control cubicle must not installed outdoors without the sunshine shield cover in the places of solar heating. Detailed control and relay, Please refer to our separate EVRC2A manual. The control cubicle is shown in Figure 3-5 on previous page.

3.9. AUXILIARY POWER SUPPLY


Auxiliary power source is derived from either of the following; y y y From an external power source of 110V and 220V supplied by auxiliary power transformer. From low voltage supply connected to the utility distribution line. In addition to above, it is preferred to use from an external DC 110V supply for substation application as option. Actually, auxiliary supply is used to operate the auto recloser through rectifying circuit and maintain charge on the sealed lead-acid batteries. The operation of recloser is fulfilled with the auxiliary power supply through the rectifying circuit regardless of charging of the sealed lead-acid batteries. The battery is used for the back-up operation of the recloser when auxiliary power supply is lost. The battery for operating the recloser is placed in the lower part of the control cubicle and arranged to be easily replaced. The battery life is predicted to use for 5 years service as recommended by the battery manufacturers data, but it can be shortened for its life on how it is handled and fitted with the environments. The battery is enough to operating the recloser for 30hours and over 500 events without external power supply. When the batteries are nearly exhausted in showing below DC 15V when battery is tested with load, please replace the batteries with new one as indicated in section 3.7 battery specification or consult with manufacturer. CAUTION: Auxiliary Power Transformer shall be installed in the source side of user system. External Power of EVRC2A Control shall be supplied from Source side in order to perform a normal sequence in case that a fault line occurs. When the recloser trips, the external power of EVRC2A Control shall not be lost.

ENHANCED TECHNOLOGY

17

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

110V OR 220V 500VA Epoxy Mold Transformer

EARTH TERMINAL MOUNTING BRACKET

EARTH CABLE CONTROL CABLE

THE DIGITAL CONTROL CUBICLE OF RECLOSER

Figure 3-6. Auxiliary power supply

18

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

AUX. TRANSFORMER

EARTH TERMINAL 110V OR 220V 5KVA Tr. or LOW VOLTAGE SOURCE SUPPLIED BY UTILITYE MOUNTING BRACKET

EARTH CABLE CONTROL CABLE

THE DIGITAL CONTROL CUBICLE OF RECLOSER

Figure 3-7. Auxiliary power supply

ENHANCED TECHNOLOGY

19

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

3.10. GAS FILLING VALVE


This valve is on the side of the recloser tank and CARE must be paid, not to be opened with protection cap for preventing the gas leakage on the filling value. SF6 gas filling valve detail is shown in Figure 3-8.

Figure 3-8. Gas Filling Valve

3.11. ACCESSORIES
1) ON/OFF indication is located on the bottom inside of the main tank to be seen transparently from the underneath of the tank. 2) Operating counter is provided in the control cubicle and if fitted, available at the bottom of the main tank. 3) SF6 gas pressure sensor is available, if required as option. 4) Pressure rupture device is mounted on the side of recloser tank for protection of overpressure due to overheating of internal arc.

20

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

4. PACKING, HANDLING AND STORAGE


4.1. PACKING AND DESPATCH
Each recloser is normally packed in one non returnable case or wooden crate for exporting and in home is mounted on a transit pallet. The recloser is despatched in the closed position for convenience and filled with SF6 gas to the commissioning pressure before despatch. The recloser and control cubicle are disconnected with umbilical cable connection for transportation and standard pole mounting bracket of the main Tank are despatched as loose equipment in the wooden crate of the recloser. Table 4-1. Approximate weights Unit Circuit breaker with gas Control Cubicle with battery Control cable Mounting bracket Gross weight in packing kgf kgf kgf kgf kgf 15kV 160 80 3.5 38 320 27kV 170 80 3.5 38 330 38kV 210 85 3.5 42 380

4.2. UNPACKING AND HANDLING


The wooden crate should be transported by hand pallet or forklift truck. The lifting procedures should be kept for safety and we recommend slinging as shown in Figure 41 and ensure the following procedures. 1) The slings should be approved and in good condition. 2) The lifting hook should be placed above the level of the bushings. 3) When moving the unpacked units, please maintain the lifting level to 30 above ground level, if possible, to avoid the damage due to unexpected failure. 4) 4Please be sure to balance the main tank weight so that the rope does not touch both sides of bushings throughout the transportation. 5) When moving and lifting, special care should be taken not to damage the bushings and bushing terminals.

ENHANCED TECHNOLOGY

21

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

6) Lifting method is shown in Figure 4-1.

Min. 100mm

Figure 4-1. Lifting configuration of the reclsoer CAUTION: Do not touch severely Bushing or Bushing Terminal during transporting the main tank of recloser. It causes a leakage of SF6 gas or damage on the bushing which leads to a severe malfunctions of the recloser.

4.3. RECEIVING
A packing list will be attached to the packing case or recloser if not packed. On receipt, the recloser should be checked for the contents of deficiency or damage during transportation. Please inform within 3 days to either the carriers, supplying agent or customer services department of the ENTEC Electric & Electronic Company., Ltd., if any damage was found.

4.4. STORAGE
As the recloser is designed for outdoor use, it can be stored both outdoor and indoor but the recloser should not be stored in a wet place and should not stacked up doubled.

22

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

5. INSTALLATION
5.1. INSPECTION BEFORE INSTALLATION
5.1.1. General
Upon receipt of the recloser, a visual inspection for damage during transportation should be paid for the followings. 1) Circuit breaker - Bushings - Bulkhead fitting and connectors - ON/OFF indicator window - Lifting bracket - Trip and lockout lever 2) Mounting bracket 3) Control cubicle - Door - Door seal/ Door handle - Control and relay on the front panel - LED normal - LCD normal 4) SF6 gas pressure - Normal: 0.5bar.g at 20 - Lower limit: 0.2bar.g at 20 CAUTION: If Gas low lamp is on, stop installing immediately and consult with the manufacturer.

5.2. TESTING
5.2.1. Gas pressure
The unit (Recloser) is filled with SF6 gas pressure at least 0.5bar gauge at 20. If the pressure within the unit falls below 0.2bar gauge at 20, the following procedures should be taken.

ENHANCED TECHNOLOGY

23

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

1) If the gas pressure is above 0.1bar gauge, the filling of SF6 gas should be done directly with attaching the gas handling equipment and fill upto the required pressure. 2) If the gas pressure is below 0.1bar gauge, a vacuum must be drawn out of the tank before filling SF6 gas. Draw a vacuum of 10mbar, hold this vacuum for 15 min and fill upto the required pressure (0.5bar gauge at 20). The unit is capable of keeping basic impulse level with an SF6 gas rich environment at zero bar gauge.

5.2.2. Battery check


Please press battery load test button in the control cubicle, battery voltage is displayed on LCD panel. 1) Normal voltage: over 21V 2) Over discharged voltage: 15V~21V 3) Require to replacement: below 15V If battery voltage shows below 15V, the battery should be replaced with new one.

5.2.3. Contact life of vacuum interrupter


The life of the vacuum interrupter is dependent upon the accumulation of the number of faults interrupted and the magnitude of fault current. Consequently, it is very important to record the short circuit operations. If 10,000 operations have been exceeded or the LCD displayed in the control cubicle is indicated below 20%, the vacuum interrupters may need to be replaced. If the replacement of the vacuum interrupter is required, please consult with the manufacturer at any time.

5.2.4. Resistance test on current carrying main circuit


Ensure that the recloser is in the closed position. The electrical resistance of each phases should be determined by measuring voltage drop with a DC current of 100 Amperes passing through. The resistance measurement of any phases should not be exceeded over 20% compared with the recommended value from the manufacturer.

5.2.5. High voltage insulation test


The recloser has been routine tested at the works in accordance with ANSI C37.60, 1981. It is recommended that the 50/60 high voltage test should be carried out prior to energizing the recloser for the first time.

24

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

One minute dry withstand voltage supply should be applied across each phase of the open position and between each phase and earth in the closed position of the recloser. The recommended site test voltage is 75% of the factory test voltage.

5.2.6. Operation test


The umbilical cable with plug-in connector should be connected between the recloser tank and control cubicle. All switches involved should be activated by powered-up control cubicle. Local mode on the front panel should be selected and then the recloser can be operated by using the open and close push buttons. If the battery is discharged, low voltage supply can be connected for charging the battery.

5.2.7. Secondary current injection test


If required, please perform secondary current injection as using recloser test kit.

5.3. INSTALLATION
5.3.1-1. Standard pole mounting of recloser tank.
Unpack the wooden crate and clean the bushing please check and confirm that all items are included. The pole mounting bracket should be assembled with the tank and hanger band is mounted on the pole and should be fixed tightly with bolts between the hanger band and the supporting bracket on the recloser as shown in Figure 3-7. Before lifting the recloser onto the pole, care should be taken to ensure that supporting bracket is correctly mounted with the tank and upper hanger band is mounted on the pole firstly and lower hanger band is mounted consequently. The range of possible attachment diameter of the hanger band for the pole mounting is 200m/m to 300m/m and other diameter is optional. The recloser should be lifted as shown in Figure 4-1 and the slinging procedure, Please refer to section 4.2 to avoid tilting of the recloser. The additional rope may be used to assist for lifting and mounting of the recloser. All standard pole mounting bracket and hanger bands with bolts and nuts are provided in the standard package.

ENHANCED TECHNOLOGY

25

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

CAUTION: If the manual trip lever is pulled approximately 45 degrees, the recloser will trip and may either be returned to the horizontal for normal operation. If the Trip lever is pulled to the latched position(locking), without releasing the trip lever to normal, no close operation occurs.

Figure 5-1. Mounting Bracket and Hanger Band

26

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

1000 max.

600

Pole Mounting Bracket Hanger Band

Control Cable Cable Cleats

Earth Cable

Control Cubicle

Manual trip & locking device

Figure 5-2. Pole Mounting Detail CAUTION: In Installation of recloser, Source Side of user system and recloser Source Side shall be matched in order to have a precise metering. A, B, C are indicated for Source Side in Recloser and R, S, T are indicated in Load Side

ENHANCED TECHNOLOGY

27

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

5.3.1-2. Substation mounting frame


If required, substation mounting frame can be supplied together with the recloser. Please assemble the mounting frame and adjust the height of mounting the recloser. Fasten tightly the recloser to the mounting frame with enclosed M16 bolts and nuts.
H.V Terminal

2600-2900 Adjustable

Anchor bolts dimension


M16 Anchor bolts

Figure 5-3. Substation mounting frame

28

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

5.3.1-3. Surge Arrester mounting frame


Mounting brackets are supplied for Surge Arrester on the recloser tank, if required.

LOCK TRIP

TOP VIEW

Figure 5-4. Surge Arrester mounting frame

ENHANCED TECHNOLOGY

29

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

5.3.2. Control cubicle


The control cubicle should be lifted using the mounting bracket and mounted with similarities using the procedure for the tank. When the control cubicle and the tank is mounted to the pole securely, then the umbilical cable plug may be connected as shown in Figure 5-2 and Figure 5-3.

Figure 5-5. Control cubicle mounting detail

30

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

The total length of the inter-connecting multi-core cable would be 6 meters as standard and the longer cable is available upon request by client as option. The fixing arrangement multi-core cable should be tightened by using tie band with every 1000 length against wind-waving. To prevent pulling weight, loosen slighty the control cable between the cable connector and the nearest hanger band.

5.3.3. Earthing
Figure 5-6 shows the earthing common to the recloser tank and the control cubicle. To avoid the potential gradient differential among tank, control cubicle and surge arrester, Earthing path should be common and do not ground by a different path to all equipments and be sure to keep the ground cables away from the control cable by the maximum spacing available. The earthing conductor size should be at least 60

ENHANCED TECHNOLOGY

31

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

AUX. TRANSFORMER RECLOSER

EARTH TERMINAL

EARTH TERMINAL

EARTH CABLE CONTROL CABLE

THE DIGITAL CONTROL CUBICLE OF RECLOSER

EARTH TERMINAL EARTH TEE OFF

Figure 5-6. Earthing layout

32

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

5.3.4. High voltage connection


Before installation, all terminals and connectors should be cleaned and prepared to be able to keep low resistance connection. Please refer to bushing assembly drawings shown in Figure 5-7.

Porcelain Bushing
The high voltage bare conductor should be placed in the hole of the universal clamp and fastened with nut upto tensile torque of 400kg-cm.

Polymer Bushing
For the polymer mold type of bushing, the stud clamp type made of anti-corrosive bronze is placed on the top of bushing. Insert HV cable directly into the center of stud clamps placed on the top of polymer bushing, and fasten four joint bolts evenly with tensile torque of 150kg-cm.

5.3.5 Bushing
Depending on request, Bushing of Recloser is made of either porcelain or polymer. Bushing and bushing housing is completely assembled and tested at the factory before dispatching. Simply users connect the high voltage cable onto High Voltage Terminal at the top of Bushing.

Porcelain Bushing
Table 5-1. Porcelain Bushing
Type EVR 1 EVR 2 Creepage distance 440 m/m 750 m/m Arcing distance 220m/m 300 m/m Terminal type Universal clamp Universal clamp Applicable cable size 24 m/m (diameter) 24 m/m (diameter) Rating (Amps) 630 630

Polymer Bushing
Type of Bushing is Separable connector type standardized by IEEE 386, the material of Insulation Housing can be made of either E.P.D.M or Silicone. Table 5-2. Polymer Bushing
Creepage Type distance EVR1 EVR2 EVR3 520 m/m 860 m/m 1100 m/m 220 m/m 330 m/m 400 m/m STUD clamp STUD clamp STUD clamp Arcing Distance Terminal type cable size 25 m/m(Max.dia.) 25 m/m(Max.dia.) 30 m/m(Max.dia.) (Amps) 630 630 800 Material EPDM/Silicone EPDM/Silicone EPDM/Silicone Applicable Rating Housing

ENHANCED TECHNOLOGY

33

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

PORCELAIN BUSHING POLYMER BUSHING

Figure 5-7. Bushing assembly

34

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

6. RECLOSER OPERATION
6.1. GENERAL
The recloser with the microprocessor-based digital control technology is designed to provide automatic distribution reclosing system for maximum continuity of electric service, please refer to EVRC2A manual in details.

6.2. OPERATION PROCEDURE


1) Ensure that all programmable settings of the relays meet the user's requirements. 2) The detailed information for relay and control, Please refer to separate operation and maintenance instructions for EVRC2A. 3) Check that the recloser is properly installed and all electrical connections are made and it is filled with SF6 gas to at least the normal service pressure 0.5 bar.g at 20. 4) Check that any external wiring connections for control are placed in normal. 5) If the recloser does not close with electrical operation, push the manual trip lever up to reset from the lockout to the trip position. 6) If you intend to trip manually, pull the trip lever down and check whether indicator points off position or not. 7) If you intend to lock the recloser, then pull the manual trip lever down to the lockout position and then trip lever indicates at lockout position. If you intend to close electrically when the manual lever is positioned at the lockout position, the recloser remains "open" as closing power is removed. Consequently, you should return the manual trip lever to the trip position for normal operation. the position

ENHANCED TECHNOLOGY

35

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

7. MAINTENANCE
7.1. GENERAL
1) The recloser has been designed as a low maintenance unit and using single moving part as adopting magnetic actuator mechanism does not require major maintenance like overhaul. 2) The control and relay maintenance, please refer to operation and maintenance instructions for EVRC2A. 3) Each equipment maintenance for recloser, please refer to section 3 and 4. 4) A general inspection of the recloser should be made giving attention for clean and normal condition of each equipment.

7.2. DISMOUNTING OF RECLOSER


1) Ensure that the HV system is grounded for safety. 2) Dismantle high voltage connections and prepare the slinging wire to lift recloser. 3) Before the lifting of the recloser on the pole, with the lifting arm fitted and maintain to support the weight of the recloser with the lifting arm engaged. 4) Remove the multi-core connectors on the recloser. 5) Dismantle the lower hanger band fixing bolts and consequently the upper hanger band fixing bolts. 6) Lift the recloser and move to the ground level. 7) Dismantle the control cubicle mounting bolts. 8) Lift the control cubicle and move onto the ground level.

7.3. CONTACT LIFE OF VACUUM INTERRUPTER


The life of the vacuum interrupter is normally over 20 years or 30,000 reclosing operations with light load operations stating by manufacturer. However, it can vary depending on the magnitude of fault currents and number of reclosing operations under loaded condition. The remaining life of the vacuum interrupter is displayed on LCD with percentage of wear-out at contact point based on calculating from magnitude of fault currents and number of trip operations. The vacuum interrupter is recommended to replace if the remaining life becomes lower than 20%. Be sure to consult with the manufacturer for replacement in details.

36

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

Actually since most faults are considerably lower than the maximum fault current and number of faults are considerably fewer than the guaranteed number of faults. The service life is expected to be much longer than the contact life of vacuum interrupter calculated by the amount of contact wear. Thus it keeps the operation of recloser to be satisfactory. The data of the anticipated contact life and mechanical operation shows as follows; Table 7-1. Contact life of vacuum interrupter Model EVR 1 EVR 2 EVR 3 Mechanical operations Rated load 10,000 10,000 10,000 10,000 10,000 10,000 Contact life Maximum fault current 100 100 100

ENHANCED TECHNOLOGY

37

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

7.4. SF6 GAS REFILLING


7.4.1. General
The recloser is filled with SF6 gas 0.5bar gauge pressure at 20. When the pressure of SF6 gas in the recloser tank is below 0.2bar gauge at 20, the instruction of refilling SF6 gas is as follows.

7.4.2. Refilling procedure


1) Connect SF6 gas tank to gas-filling valve on the side of recloser tank as shown in Figure 7-1 below. The gas-filling valve matches with DILO pressure coupling VK/F-02/8. 2) Measure the gas pressure in recloser tank. 3) When the gas pressure is above 0.1bar gauge, refilling SF6 gas work should be proceeded by attaching the gas filling equipment and filling the SF6 gas to 0.5bar gauge pressure. 4) When the gas pressure is below 0.1bar gauge, a vacuum must be drawn from the recloser tank before filling SF6 gas. Draw the vacuum of 10mbar and hold this vacuum condition for 15 min and refill the recloser tank with SF6 gas to 0.5bar gauge pressure at 20C

Figure 7-1. SF6 gas refilling configuration

38

ENHANCED TECHNOLOGY

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

Table. Replaceable spare parts (1/2) Part Epoxy Bushing Epoxy Bushing clamp Clamp Packing Insulation Housing 500m/m (EPDM) Insulation Housing 500 m/m (Silicon) Insulation Housing 860 m/m (EPDM) Insulation Housing 860 m/m (Silicon) Magnetic Counter High Voltage terminal (universal type) High Voltage terminal (STUD type) Gas filling valve O-ring Bushing seal O-ring Gas filling valve cap Silicone grease for H.V Insulation Silicone grease for O-ring Water proof packing for control cubicle Control cable with receptacle (37PIN) External power cable Control cubicle Mount Accessory Small Mount Accessory Large Battery Heater/40W NFB Magnetic Contactor Terminal Block and Fuse Holder Relay Module-CVD Type Relay Module-VT Type UPS Module Capacitor Communication Cable (CC201) Supplier / Description ENTEC ENTEC ENTEC ENTEC / 15kV ENTEC / 15kV ENTEC / 27kV ENTEC / 27kV ENTEC ENTEC ENTEC N.O.K / P12.5(EPDM) N.O.K / P85(EPDM) ENTEC ENTEC Shinetsu / HiVac-G ENTEC ENTEC ENTEC ENTEC ENTEC ENTEC Sealed leadacid Battery (Two 12V18Ah) ENTEC Korea(LG) / BS31a(20A) Schneider-electric / LC1K0910E7 ENTEC ENTEC ENTEC ENTEC Korea(Samyoung) / SMS 22000uF/160WV ENTEC Part No. EVR-SP0001 EVR-SP0002 EVR-SP0003 EVR-SP0004 EVR-SP0005 EVR-SP0006 EVR-SP0007 EVR-SP0008 EVR-SP0009 EVR-SP0010 EVR-SP0011-1 EVR-SP0011-2 EVR-SP0012 EVR-SP0013 EVR-SP0014 EVR-SP0015 EVR-SP0016 EVR-SP0017 EVR-SP0018 EVR-SP0019 EVR-SP0020 EVR-SP0021 EVR-SP0022 EVR-SP0023 EVR-SP0024 EVR-SP0025 EVR-SP0026 EVR-SP0027 EVR-SP0028 EVR-SP0029 EVR-SP0030

ENHANCED TECHNOLOGY

39

EVR AUTOMATIC RECLOSER

http://www.entecene.co.kr

Table. Replaceable spare parts (2/2) Part Communication Cable (CC202) Communication Cable (CC203) Firmware Upgrade Tools Supplier / Description ENTEC ENTEC ENTEC Part No. EVR-SP0031 EVR-SP0032 EVR-SP0033

40

ENHANCED TECHNOLOGY