Copyright 2002 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved.
http://www.entecene.co.kr
TABLE OF CONTENTS
GENERAL GUIDANCE............................................................................................................ 5
5. INSTALLATION ........................................................................................................... 23
5.1. INSPECTION BEFORE INSTALLATION ...................................................................... 23 5.1.1. General ................................................................................................................... 23 5.2. TESTING .......................................................................................................................... 23 5.2.1. Gas pressure ........................................................................................................... 23 5.2.2. Battery check.......................................................................................................... 24
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
5.2.3. Contact life of vacuum interrupter.......................................................................... 24 5.2.4. Resistance test on current carrying main circuit..................................................... 24 5.2.5. High voltage insulation test .................................................................................... 24 5.2.6. Operation test ......................................................................................................... 25 5.2.7. Secondary current injection test ............................................................................. 25 5.3. INSTALLATION............................................................................................................... 25 5.3.1-1. Standard pole mounting of recloser tank............................................................. 25 5.3.1-2. Substation mounting frame ................................................................................. 28 5.3.1-3. Surge Arrester mounting frame ........................................................................... 29 5.3.2. Control cubicle ....................................................................................................... 30 5.3.3. Earthing .................................................................................................................. 31 5.3.4. High voltage connection......................................................................................... 33 5.3.5 Bushing.................................................................................................................... 33
7. MAINTENANCE .......................................................................................................... 36
7.1. GENERAL ........................................................................................................................ 36 7.2. DISMOUNTING OF RECLOSER ................................................................................... 36 7.3. CONTACT LIFE OF VACUUM INTERRUPTER........................................................... 36 7.4. SF6 GAS REFILLING ...................................................................................................... 38 7.4.1. General ................................................................................................................... 38 7.4.2. Refilling procedure................................................................................................. 38
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
GENERAL GUIDANCE
ENTEC automatic vacuum recloser hereinafter as EVR is designed to operate after installation on an outdoor pole and substation. This product consists of the minimum number of components to achieve maintenance free, maximum safety and endurance. To ensure the maximum life and the best quality of operation, operate EVR in accordance with the instruction manual and keep the following guidance. Be fully aware of the instruction manual before operating EVR. Safety check is required before installing, operating, and maintenance EVR. After installation, connect AC 110/220V from the distribution line to the CONTROL CUBICLE and run a test operation. If works need to be done after opening the control CUBICLE middle cover, turn the main circuit breaker (MCB) OFF to avoid any accident due to the high voltage. Avoid any flame work such as welding and brazing on EVR because the main tank is filled with SF6 gas for insulation.
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
1. INTRODUCTION
This manual contains the information required for installation, operation, and maintenance of ENTEC EVR Automatic Recloser. EVR is designed to be powered from AC 110/220V low voltage distribution line. EVR complies with the international standard specifications and ratings. EVR consists of the corrosion-resistance stainless steel tank (main tank) and the control cubicle, which are connected by separable shielded cable that is insulated. The main tank contains the vacuum interrupter and the magnetic actuator. Although the main tank can be disconnected from the Control Cubicle, none of them can be exchanged with other products. If replacement is required, please consult with the ENTEC E&E Co. Ltd. The inside of the main tank is filled with SF6 gas for insulation and the control cubicle is equipped with two of DC 12V batteries in series together. Batteries supply DC 24V control power to a control circuit after rectifying from low voltage AC source. General configuration of recloser is shown as below.
H.V Connector
Figure 1-1. Recloser Lay-Out Table 1-1. Dimension(mm) kV 15kV 27kV 38kV/630A 38kV/800A A 715 760 841 841 B 375 460 475 475 C 925 1020 1058 1078 D 300 300 320 320
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
2. STANDARD RATINGS
The standard ratings of EVR Recloser are as follows; Table 2-1. STANDARD RATINGS
Maximum system voltage Rated frequency Rated continuous current Rated short circuit interrupting current Rated making current (peak value) Power frequency withstand voltage - dry - wet Rated impulse withstand voltage Mechanical operation life Auxiliary power supply Control circuit voltage Protection current transformer (CT) ratio Weight - main tank - control cubicle 160kg 85kg 170kg 85kg 210kg 90kg DC 24V 1000:1 A 50kV(1 min) 45kV(10 sec) 110kV BIL 10,000 operations 60kV(1 min) 50kV(10 sec) 150kV BIL 10,000 operations 70kV(1 min) 60kV(10 sec) 170kV BIL 10,000 operations (peak value) (peak value) 15kV 50/60Hz 630A 12.5/16kA 32.5kA 27kV 50/60Hz 630A 12.5/16kA 32.5kA 38kV 50/60Hz 630/800A 12.5/16kA 32.5/ 40kA
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
3. CONSTRUCTION
The Recloser can be mounted on an outdoor pole by assembling a mounting bracket connected to the top of main tank and also installed at substation with substation mounting frame. The vacuum interrupter, magnetic actuator, and current transformer (CT) are contained in the TIG-welded main tank and filled with SF6 gas for the insulation of recloser main tank. The interruption of Recloser is performed by the vacuum interrupter and SF6 gas is used to insulate. The recloser filled with SF6 gas does not produce any by-products by arc during interruption. Thus it maintains permanent insulation capability and prevent corrosion of the main tank components. The Recloser interrupter arranged with the 3-phase dielectric mold frame, consists of the vacuum interrupter and the trip spring with the same distance. The driving arm connected at the end of moving contact transfers a driving force of the magnetic actuator to the interrupter for close and open operation. The 6 bushings on the top of main tank can be supplied with porcelain, polymeric(E.P.D.M. rubber or silicone rubber) bushing upon to user's request. The current transformer (CT) is installed at the bushing connected at the fixed contact of interrupter in the main tank, and CT can monitor phase fault currents, earth fault currents and load currents, and send signals to the control electronics. If the control cable of CT is disconnected at both end, the CT is automatically shorted by the automatic CT protection circuit. The manual Trip/Locking device is positioned on the front side of main tank. The indicator points an interrupter's open/close status and the operation counter are located at the bottom of main tank. The Recloser operation sequence is performed by the microprocessor-based relay. The relay is installed in the control cubicle protected by rain-proof case. The Recloser immediately performs a preset operation sequence to re-close when a phase/ground fault current is higher than the preset value. If a fault current is not cleared at the end of full protection sequence, the Recloser will be lockout as tripped, and remains until the next close operation. If a fault current is cleared during the protection sequence, the Recloser is closed, and then returns into sleep mode after the reset time.
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
When a fault current is detected, the recloser operates the pre-set full protection sequence again. EVR is powered by AC 110/220V low voltage distribution line source without an additional transformer and is designed to consume low energy to operate reclosing and remote control. Thus EVR does not need any extra cost for installation of additional transformer, in case, low voltage source by utility is available. In case that low voltage power source is not available, the recloser is fitted with an auxiliary voltage transformer to supply auxiliary power to the control cubicle. During open and close operations, the relay sends the pulse type current to the open and close coils, and the magnetic force is induced by those coils and moves the plunger of the magnetic actuator. This driving force is transferred to the vacuum interrupter, which makes contact point tripped or closed. During trip and close operations, arc is produced and rapidly extinguished in the vacuum interrupter. The relay setting in control circuit can be modified at the control panel, a PC or remotely controlled communication method. For more details, refer to EVRC2A manual.
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
3.1. INTERRUPTER
The vacuum interrupter of the recloser can provides versatilities to operate trip/close with the ratings and capacity based on the fully capable of interruption. The closing status of the contacts is held by contact springs that provide the required force at all condition of contact wear. As a vacuum interrupter is fully sealed for the lifetime of the recloser and it requires only a small contact stroke and low interruption energy. it is suitable for application of magnetic actuator mechanism and also vacuum interrupter has a capability of a large number of operations, which is ideal for the reclosers application. Thus, vacuum interrupter with magnetic actuator provides a high reliability in operation and minimum maintenance if the replacement of the vacuum interrupter is required with any reasons, please consult with manufacturer.
Fixed busbar
Moving busbar
Vacuum interrupter
Opening spring
10
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
The permanent magnetic actuator mechanism has just one moving part. Thus the dramatic reduction in part gives a corresponding increase in reliability. Especially, as the actuator uses magnetic latching and uses trip and close coil separately, the actuator consists of the fewest components and can provides zero-maintenance operation. The actuator driving arm is made of high strength aluminum alloy and delivers force to the interrupter. When pulse current flows into the close coil, the plunger of magnetic actuator is moved by the induced magnetic force to drive the interrupter to close position, and the actuator is then held in the closed position. In contrast, when pulse current flows into the trip coil, the plunger is released from the magnetic latch and the interrupter is moved to trip position.
3.3. BUSHING
Bushing is mounted on the top of the recloser tank and supplied with either porcelain or polymeric bushing(EPR or Silicone rubber) depending upon users requirements. The ring core CT is mounted on the lower part of bushing inside of the recloser tank arranged at the fixed position of interrupter and senses the current flow. This current information is transmitted to the micro-processor based relay via the multi-core cable. Capacitor voltage divider (CVD) is available in case of using polymeric bushing to measure and sense the secondary voltage for signaling use.
ENHANCED TECHNOLOGY
11
http://www.entecene.co.kr
Hot stick
12
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
Table 3-2. Physical properties Sublimation point (1.0133 bar) Melting point (2.26 bar) Vapour pressure (20) Critical temperature Critical pressure Critical density Gas density (20, 1bar) Liquid density (0, 12.65 bar) Acoustic velocity in SF6 -63.9 -50.8 21.08 bar 45.55 37.59 bar 0.74 kg/l 6.07 g/l 1.56 kg/l 129.06 m/sec.
ENHANCED TECHNOLOGY
13
http://www.entecene.co.kr
e r u s s e r p g n i t a r e p o e c i v e d y t f a S e r u s s) eC r5 p2 gt na i lG l im fc / lg ak m5 r. o0 N(
e) rG um sc s/ eg rk p2 . m0 a( l A
14
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
Typical properties shows as follows; Table 3-3. Typical properties Typical properties Nominal pore diameter Type of crystal structure Bulk density Water content(as shipped) Heat of absorption(max) Bead size(nominal) 9 angstrom(0.9) hexagonal 680g/ 1.5% wt (max) 4200kj/kgwater 2.55, 23, 12 48mesh, 812mesh, 1018mesh
ENHANCED TECHNOLOGY
15
http://www.entecene.co.kr
Figure 3-5. Control cubicle layout Consequently, any condensation on metal surface will run out of the bottom and automatically dried without affecting the electronic modules by ventilation and self heating. The standard control cubicle contains the relay, batteries for control power and mechanism driving power.
16
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
The control cubicle must not installed outdoors without the sunshine shield cover in the places of solar heating. Detailed control and relay, Please refer to our separate EVRC2A manual. The control cubicle is shown in Figure 3-5 on previous page.
ENHANCED TECHNOLOGY
17
http://www.entecene.co.kr
18
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
AUX. TRANSFORMER
EARTH TERMINAL 110V OR 220V 5KVA Tr. or LOW VOLTAGE SOURCE SUPPLIED BY UTILITYE MOUNTING BRACKET
ENHANCED TECHNOLOGY
19
http://www.entecene.co.kr
3.11. ACCESSORIES
1) ON/OFF indication is located on the bottom inside of the main tank to be seen transparently from the underneath of the tank. 2) Operating counter is provided in the control cubicle and if fitted, available at the bottom of the main tank. 3) SF6 gas pressure sensor is available, if required as option. 4) Pressure rupture device is mounted on the side of recloser tank for protection of overpressure due to overheating of internal arc.
20
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
ENHANCED TECHNOLOGY
21
http://www.entecene.co.kr
Min. 100mm
Figure 4-1. Lifting configuration of the reclsoer CAUTION: Do not touch severely Bushing or Bushing Terminal during transporting the main tank of recloser. It causes a leakage of SF6 gas or damage on the bushing which leads to a severe malfunctions of the recloser.
4.3. RECEIVING
A packing list will be attached to the packing case or recloser if not packed. On receipt, the recloser should be checked for the contents of deficiency or damage during transportation. Please inform within 3 days to either the carriers, supplying agent or customer services department of the ENTEC Electric & Electronic Company., Ltd., if any damage was found.
4.4. STORAGE
As the recloser is designed for outdoor use, it can be stored both outdoor and indoor but the recloser should not be stored in a wet place and should not stacked up doubled.
22
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
5. INSTALLATION
5.1. INSPECTION BEFORE INSTALLATION
5.1.1. General
Upon receipt of the recloser, a visual inspection for damage during transportation should be paid for the followings. 1) Circuit breaker - Bushings - Bulkhead fitting and connectors - ON/OFF indicator window - Lifting bracket - Trip and lockout lever 2) Mounting bracket 3) Control cubicle - Door - Door seal/ Door handle - Control and relay on the front panel - LED normal - LCD normal 4) SF6 gas pressure - Normal: 0.5bar.g at 20 - Lower limit: 0.2bar.g at 20 CAUTION: If Gas low lamp is on, stop installing immediately and consult with the manufacturer.
5.2. TESTING
5.2.1. Gas pressure
The unit (Recloser) is filled with SF6 gas pressure at least 0.5bar gauge at 20. If the pressure within the unit falls below 0.2bar gauge at 20, the following procedures should be taken.
ENHANCED TECHNOLOGY
23
http://www.entecene.co.kr
1) If the gas pressure is above 0.1bar gauge, the filling of SF6 gas should be done directly with attaching the gas handling equipment and fill upto the required pressure. 2) If the gas pressure is below 0.1bar gauge, a vacuum must be drawn out of the tank before filling SF6 gas. Draw a vacuum of 10mbar, hold this vacuum for 15 min and fill upto the required pressure (0.5bar gauge at 20). The unit is capable of keeping basic impulse level with an SF6 gas rich environment at zero bar gauge.
24
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
One minute dry withstand voltage supply should be applied across each phase of the open position and between each phase and earth in the closed position of the recloser. The recommended site test voltage is 75% of the factory test voltage.
5.3. INSTALLATION
5.3.1-1. Standard pole mounting of recloser tank.
Unpack the wooden crate and clean the bushing please check and confirm that all items are included. The pole mounting bracket should be assembled with the tank and hanger band is mounted on the pole and should be fixed tightly with bolts between the hanger band and the supporting bracket on the recloser as shown in Figure 3-7. Before lifting the recloser onto the pole, care should be taken to ensure that supporting bracket is correctly mounted with the tank and upper hanger band is mounted on the pole firstly and lower hanger band is mounted consequently. The range of possible attachment diameter of the hanger band for the pole mounting is 200m/m to 300m/m and other diameter is optional. The recloser should be lifted as shown in Figure 4-1 and the slinging procedure, Please refer to section 4.2 to avoid tilting of the recloser. The additional rope may be used to assist for lifting and mounting of the recloser. All standard pole mounting bracket and hanger bands with bolts and nuts are provided in the standard package.
ENHANCED TECHNOLOGY
25
http://www.entecene.co.kr
CAUTION: If the manual trip lever is pulled approximately 45 degrees, the recloser will trip and may either be returned to the horizontal for normal operation. If the Trip lever is pulled to the latched position(locking), without releasing the trip lever to normal, no close operation occurs.
26
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
1000 max.
600
Earth Cable
Control Cubicle
Figure 5-2. Pole Mounting Detail CAUTION: In Installation of recloser, Source Side of user system and recloser Source Side shall be matched in order to have a precise metering. A, B, C are indicated for Source Side in Recloser and R, S, T are indicated in Load Side
ENHANCED TECHNOLOGY
27
http://www.entecene.co.kr
2600-2900 Adjustable
28
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
LOCK TRIP
TOP VIEW
ENHANCED TECHNOLOGY
29
http://www.entecene.co.kr
30
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
The total length of the inter-connecting multi-core cable would be 6 meters as standard and the longer cable is available upon request by client as option. The fixing arrangement multi-core cable should be tightened by using tie band with every 1000 length against wind-waving. To prevent pulling weight, loosen slighty the control cable between the cable connector and the nearest hanger band.
5.3.3. Earthing
Figure 5-6 shows the earthing common to the recloser tank and the control cubicle. To avoid the potential gradient differential among tank, control cubicle and surge arrester, Earthing path should be common and do not ground by a different path to all equipments and be sure to keep the ground cables away from the control cable by the maximum spacing available. The earthing conductor size should be at least 60
ENHANCED TECHNOLOGY
31
http://www.entecene.co.kr
EARTH TERMINAL
EARTH TERMINAL
32
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
Porcelain Bushing
The high voltage bare conductor should be placed in the hole of the universal clamp and fastened with nut upto tensile torque of 400kg-cm.
Polymer Bushing
For the polymer mold type of bushing, the stud clamp type made of anti-corrosive bronze is placed on the top of bushing. Insert HV cable directly into the center of stud clamps placed on the top of polymer bushing, and fasten four joint bolts evenly with tensile torque of 150kg-cm.
5.3.5 Bushing
Depending on request, Bushing of Recloser is made of either porcelain or polymer. Bushing and bushing housing is completely assembled and tested at the factory before dispatching. Simply users connect the high voltage cable onto High Voltage Terminal at the top of Bushing.
Porcelain Bushing
Table 5-1. Porcelain Bushing
Type EVR 1 EVR 2 Creepage distance 440 m/m 750 m/m Arcing distance 220m/m 300 m/m Terminal type Universal clamp Universal clamp Applicable cable size 24 m/m (diameter) 24 m/m (diameter) Rating (Amps) 630 630
Polymer Bushing
Type of Bushing is Separable connector type standardized by IEEE 386, the material of Insulation Housing can be made of either E.P.D.M or Silicone. Table 5-2. Polymer Bushing
Creepage Type distance EVR1 EVR2 EVR3 520 m/m 860 m/m 1100 m/m 220 m/m 330 m/m 400 m/m STUD clamp STUD clamp STUD clamp Arcing Distance Terminal type cable size 25 m/m(Max.dia.) 25 m/m(Max.dia.) 30 m/m(Max.dia.) (Amps) 630 630 800 Material EPDM/Silicone EPDM/Silicone EPDM/Silicone Applicable Rating Housing
ENHANCED TECHNOLOGY
33
http://www.entecene.co.kr
34
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
6. RECLOSER OPERATION
6.1. GENERAL
The recloser with the microprocessor-based digital control technology is designed to provide automatic distribution reclosing system for maximum continuity of electric service, please refer to EVRC2A manual in details.
ENHANCED TECHNOLOGY
35
http://www.entecene.co.kr
7. MAINTENANCE
7.1. GENERAL
1) The recloser has been designed as a low maintenance unit and using single moving part as adopting magnetic actuator mechanism does not require major maintenance like overhaul. 2) The control and relay maintenance, please refer to operation and maintenance instructions for EVRC2A. 3) Each equipment maintenance for recloser, please refer to section 3 and 4. 4) A general inspection of the recloser should be made giving attention for clean and normal condition of each equipment.
36
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
Actually since most faults are considerably lower than the maximum fault current and number of faults are considerably fewer than the guaranteed number of faults. The service life is expected to be much longer than the contact life of vacuum interrupter calculated by the amount of contact wear. Thus it keeps the operation of recloser to be satisfactory. The data of the anticipated contact life and mechanical operation shows as follows; Table 7-1. Contact life of vacuum interrupter Model EVR 1 EVR 2 EVR 3 Mechanical operations Rated load 10,000 10,000 10,000 10,000 10,000 10,000 Contact life Maximum fault current 100 100 100
ENHANCED TECHNOLOGY
37
http://www.entecene.co.kr
38
ENHANCED TECHNOLOGY
http://www.entecene.co.kr
Table. Replaceable spare parts (1/2) Part Epoxy Bushing Epoxy Bushing clamp Clamp Packing Insulation Housing 500m/m (EPDM) Insulation Housing 500 m/m (Silicon) Insulation Housing 860 m/m (EPDM) Insulation Housing 860 m/m (Silicon) Magnetic Counter High Voltage terminal (universal type) High Voltage terminal (STUD type) Gas filling valve O-ring Bushing seal O-ring Gas filling valve cap Silicone grease for H.V Insulation Silicone grease for O-ring Water proof packing for control cubicle Control cable with receptacle (37PIN) External power cable Control cubicle Mount Accessory Small Mount Accessory Large Battery Heater/40W NFB Magnetic Contactor Terminal Block and Fuse Holder Relay Module-CVD Type Relay Module-VT Type UPS Module Capacitor Communication Cable (CC201) Supplier / Description ENTEC ENTEC ENTEC ENTEC / 15kV ENTEC / 15kV ENTEC / 27kV ENTEC / 27kV ENTEC ENTEC ENTEC N.O.K / P12.5(EPDM) N.O.K / P85(EPDM) ENTEC ENTEC Shinetsu / HiVac-G ENTEC ENTEC ENTEC ENTEC ENTEC ENTEC Sealed leadacid Battery (Two 12V18Ah) ENTEC Korea(LG) / BS31a(20A) Schneider-electric / LC1K0910E7 ENTEC ENTEC ENTEC ENTEC Korea(Samyoung) / SMS 22000uF/160WV ENTEC Part No. EVR-SP0001 EVR-SP0002 EVR-SP0003 EVR-SP0004 EVR-SP0005 EVR-SP0006 EVR-SP0007 EVR-SP0008 EVR-SP0009 EVR-SP0010 EVR-SP0011-1 EVR-SP0011-2 EVR-SP0012 EVR-SP0013 EVR-SP0014 EVR-SP0015 EVR-SP0016 EVR-SP0017 EVR-SP0018 EVR-SP0019 EVR-SP0020 EVR-SP0021 EVR-SP0022 EVR-SP0023 EVR-SP0024 EVR-SP0025 EVR-SP0026 EVR-SP0027 EVR-SP0028 EVR-SP0029 EVR-SP0030
ENHANCED TECHNOLOGY
39
http://www.entecene.co.kr
Table. Replaceable spare parts (2/2) Part Communication Cable (CC202) Communication Cable (CC203) Firmware Upgrade Tools Supplier / Description ENTEC ENTEC ENTEC Part No. EVR-SP0031 EVR-SP0032 EVR-SP0033