Sie sind auf Seite 1von 4

S.C. SMART INDUSTRIAL SOLUTIONS CENTER S.R.L. Adresa: Str.

George Cosbuc 223 A Romania, Galati 800506 J17/1057/2010 RO 27715023

CONT RO37 RNCB 0144 1191 8415 0001

Nr. Inregistrare: 219/28.04.2011 Denumire: FISA TEHNICA SMARTGEN SGP 110

SMARTGEN SGP 110 General Features


Every generator set is subjected to a comprehensive test program which includes 50% load, 75% load, 100% load, 110% load and the checking and proving of all control and safety shut-down functions. Equipped with battery charger and 12V high performance maintenance-free lead-acid starting batteries and connecting with cables. Equipped with industrial silencer and flexible exhaust hose. Equipped with 8-hours operation base tank; Designed to Comply with ISO8528/GB2820; Powered by Perkins engine and coupled with Leroy Somer alternator.

Galati, BCR Sucursala Traian Tel: + 4 0336 401 226 Tel: + 4 0772 218 301 Fax: +4 0336 401 225 www.smart-id.ro office@smart-id.ro

Genset Technical Data


Prime power Standby power Rated speed Output frequency Phase Rated voltage Noise dB(A) @7m Engine model Alternator model Fuel consumption of 100% load Fuel consumption of 75% load Voltage regulation rate Random voltage variation 100 kVA 110 kVA 1500 RPM 50 Hz 3 400 V 70
11 04C-44TAG2 LSA 44.2 VS45 22.6 Litres/h 17.1 Litres/h

Benefits
Function stability credibility, service convenience; Low operating cost results in optional economy; Gets the job done wherever you are; Ease of installation, operation and maintenance.

Dimension and Weight


Length(L) Width(W) Height(H) Weight Tank capacity mm mm mm kg L 2800 1130 1640 1650 300

Frequency regulation rate Random frequency variation

1% 1% 5% 0.5%

Prime Power: This rating is for the supply of continuous electrical power (at variable load). There is no limit on the annual hours of operation and 10% overload power can be supplied for 1 hour in 12. Standby power: This rating is for the supply of continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted. Rated voltage: Available with customer requirements.

Environment Condition
Environment temperature Relative humidity Altitude

% m

50 90 1000

Engine Specifications
Engine model Engine manufacturer Emissions statement Number of cylinders Cylinder arrangement Cycle Aspiration BoreStroke (mmmm) Displacement (Liter) Compression Ratio Prime power/speed (kW/RPM) Standby power/speed (kW/RPM) Speed governor Cooling system Total lubrication system capacity Coolant capacity Starter motor Alternator

11 04C-44TAG2 Perkins EU2007 (EU 97/68/EC Stage II) EPA Tier2 4 Vertical in-line Four stroke Turbocharged, air to air charge cooled 105 x 127 4.41 17.25:1 89/1500 98/1500 Electrical Forced Water Cooling Cycle (L) 8.0 12.6 205 (at 1500RPM) DC12V AC 12V L

Fuel consumption at 100% load (g/kWh)

Alternator Specifications
Alternator model Alternator manufacturer Exciter type Rated output continuous power Rated speed Rated frequency Phase Rated voltage Power factor Voltage adjust range Voltage regulation NL-FL Insulation grade Protection grade Remark Alternator option: Other alternator manufacturer: Stamford, Lisite, Marathon and Mecc Alte. LSA 44.2 VS45 Leroy Somer Single bearing, Brushless, Self-excited 105 kVA 1500 RPM 50 Hz 3 400 V(Available with customer requirements) 0.8
5% 1%

H IP23

Control System DSE31 10


All SMARTGEN SGP series genset have a control cubicle (the deepsea controller DSE3 110 as standard) mounted on a isolated support, which has the following features: Electronic digital control module with monitoring/control facility and warning indicators; Automatic shutdown protection Emergency stop button (lock-down type) AC output circuit breaker with over-current protection; DC circuit control switch.

The control module gives digital readouts of:


Generator voltage; Output frequency; Engine speed; Battery voltage; DSE3 110

Engine hours run. Note:

1. The engine coolant temperature used temperature meter display; 2. The engine oil pressure used oil pressure meter display; 3. Generator current used current meter display and used change switch for each phase displayed separately

The control module has indicators for failure information:


Overspeed/underspeed, Emergency stop Low oil pressure; High water temperature Failure to start Battery charger failure

Automatic shutdown occurs under:


Low engine oil pressure; High engine water temperature; Overspeed/underspeed; Failure to start after three attempts.

The controller option:

DSE7110

DSE7120

DSE7510

Remark: the controller detail information please refer to the file Control System Choice

Generator Set Options and Accessories


Generator set

Open generator set Trailer generator set ABB MCCB circuit breaker
Fuel system

Alternator

PMG excitation Space heater

Low environment temperature

12 hour base tank(single wall) 24 hour base tank(single wall) Dual wall base fuel tank Outside fuel tank
Exhaust system

Water heater Oil heater Battery heater

Control system AMF function

Residential exhaust silencer

ATS control cabinet Multiple generator automatic synchrorising

Smart Industrial Solutions Center reserves the right to implement specifications or design changes without notice. WARNING: Do not connect generator to any buildings electrical system unless a disconnect switch has been installed.

In speranta unei bune colaborari, asteptam cu interes sa ne contactati.

Cu stima, SIS Romania Cristina Costache domestic@smart-id.ro 0772 218 301

S.C. SMART INDUSTRIAL SOLUTIONS CENTER S.R.L. Str. George Cosbuc 223 A, Romania, Galati 800506 J17/1057/2010 RO 27715023 CONT RO37 RNCB 0144 1191 8415 0001 Galati, BCR Sucursala Traian tel: +4 0336 401 226 fax: +4 0336 401 225 www.smart-id.ro office@smart-id.ro