Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:
Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA Project: SISTEMA DE ALIVIOS Y VENTEOS VALVE ID Tag No. PSV-001 Service GLP PID No. SC-E02-PR-00-03-02 de 02 Line No. 6"-0.280-B-(V-3)-3001 End-User Ref. No.: Project Ref. No.:
Date
Revision
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
41 42 43 44 Quantity 45 1 46 GENERAL 47 Valve Type Pilot-Op, Modulating, Non-Flowing Pilot 48 Safety / Relief Safety Relief Balanced Yes 49 Nozzle Semi Bonnet Closed 50 CONNECTIONS 51 Inlet 3" Flngd. 600# RF Standard 52 Outlet 4" Flngd. 150# RF ASME B16.5 53 MATERIALS OF CONSTRUCTION 54 Body CS SA216-WCB/WCC 55 Cap CS SA516-70 56 MainValve Trim Stainless Steel 57 Seat Teflon 58 Seals Buna-N 59 Body SS A479-316 60 17-7 PH SST Trim Spring SST 61 PilotValve Seat Buna-N 62 Seals Buna-N 63 Diaphragm N/A 64 Tubing Fittings 304 SST CS CPI 65 Integral Sense NACE MR0175 (2002) No 66 67 68 69 70 SIZING / SELECTION SUMMARY 71 Valve Model No. 46312-34/S1 72 Brand Anderson Greenwood 73 Area Calculated Selected 6,308 6,733 74 (in) Data Set Orifice ASME FB, 3x4 75 Unit Required lb/hr 70010 76 Flow Rated Actual 74726,325 83029,250 77 78 Estimated Reaction Force 609,42 daN 79 Estimated Noise Level (db) 75,9 at 100-ft 80
SIZING DATA Design Code ASME Section VIII Sizing Std. API 520 Sizing Basis Blocked Discharge Fluid State at Inlet Gas / Vapor Relieving Case Pressure Relief Fluid Properties Fluid Name Propane Molecular Weight, M 47,88 Compressibility, Z 0,845 Ratio of Sp. Heats, k (Cp / Cv) 1,197 Gas Constant, C 336,9
Kd, Gas Kc
0,956 1,0
Unit 70010
lb/hr
Accessories
Pressures Unit psig MAWP Operating 112 Set CDTP 150 Over Pressure 15,0 10% Constant Superimposed 0 Variable Superimposed 0 Back Pressure Built-Up 133 Total 133 Inlet Loss 4,500 3% Atmospheric (Barometric) 14,696 psia Relieving (Flowing) 175,196 psia Temperatures Unit F Operating Relieving 95 95 Design Min Design Max A 6,12 B 7,00 C 25,16 Weight 147 Valve Dimensions lb in Page : 1
Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.
Date Revision Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA End-User Ref. No.: Project: SISTEMA DE ALIVIOS Y VENTEOS Project Ref. No.: VALVE ID CALCULATION NOTES 1 11 Tag No. PSV-001 2 12 Valve Model No. 46312-34/S1 Qty. 1 3 13 SIZING DATA 4 14 Design Code ASME Section VIII Sizing Std. API 520 15 5 Gas / Vapor 6 Fluid State at Inlet 16 CALCULATION SUMMARY 7 Required 70010 lb/hr Required 6,308 in 8 18 Flow Area Rated 74726,325 lb/hr Selected 6,733 in 9 19 Estimated Reaction Force 609,42 daN Estimated Noise Level (db) 75,9 at 100 ft 10 20 Variable Type Variable Name Symbol Input Value Equation Value Fluid Properties Molecular Weight M 47,88 47,88 Ratio of Specific Heats k 1,197 1,197 Compressibility Z 0,845 0,845 Process Cond. Required Mass Flow Wreq 70010 lb/hr 70010 lb/hr Set Pressure Pset 150 psig 150 psig Over Pressure Pover 15,0 psig 15,0 psig Inlet Line Loss Ploss 4,500 psig 4,500 psig Back Pressure Pback 133 psig 133 psig Atmospheric Pressure Patm 14,696 psia 14,696 psia Relieving Temperature T 95 F 554,670 R Distance from Valve (noise) r 100 ft 100 ft Rupture Disc CCF Kc 1,0 1,0 Valve Data Discharge Coefficient (actual) Kd 0,956 0,956 Discharge Coefficient (derated) K 0,860 0,860 Orifice Area A 6,733 in 6,733 in Back Pressure Correction Factor Kb 0,684 0,684 Outlet Diameter Do 4,06 in 4,06 in Calculate Inlet Relieving Pressure, Outlet Pressure, Absolute Pressure Ratio P1 = Pset + Pover - Ploss + Patm P1 175,196 psia P2 = Pback + Patm P2 147,696 psia PR = P2 / P1 PR 0,843 Calculate Gas Constant C = 520 * {k * [2 / (k + 1)]^[(k + 1) / (k - 1)] }^0.5 Calculate Mass Critical Flow W = A * C * K * P1 * Kb * Kc * [M / (T * Z)]^0.5 Calculate Required Orifice Area Areq = A * Wreq / W Calculate Mass Critical Flow (for Noise Calc) W = A * C * Kd * P1 * Kb * Kc * [M / (T * Z)]^0.5 C 336,9
Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:
74726,325 lb/hr
74726,325 lb/hr
Areq
6,308 in
6,308 in
83029,25 lb/hr
Calculate Noise Level at 100-ft (30-m) L100 L100 = [87.75 * log( 1/PR ) + 14.09] + [10 * log(0.29354 * W * k * T / M)]
75,9 db
Page : 2
Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.
Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:
Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA Project: SISTEMA DE ALIVIOS Y VENTEOS VALVE ID 1 Tag No. PSV-001 2 Valve Model No. 46312-34/S1 Qty. 1 3 SIZING DATA 4 Design Code ASME Section VIII Sizing Std. API 520 5 Gas / Vapor 6 Fluid State at Inlet CALCULATION SUMMARY 7 Required 70010 lb/hr 8 Flow Rated 74726,325 lb/hr 9 Estimated Reaction Force 609,42 daN 10 Calculate Noise Level at Distance, r Lp Lp = L100 - 20 * log(r / 100) Calculate Outlet Static Pressure Po Po = [(0.00245 * A * C * Kd * P1 * Kc) / (Do^2 * (k * Z)^0.5)] - Patm Calculate Reaction Force for Open Discharge Fr Ao = ( * Do^2) / 4 Fr = (A * C * Kd * P1 * Kc / 366) * {k / [(k + 1) * Z]}^0.5 + (Ao * Po) Printed On: 25-sep-2013 609,42 daN End-User Ref. No.: Project Ref. No.: 11 12 13 14 15 16 18 19 20
Date
Revision
CALCULATION NOTES
Area
41,447 psig
1370,0 lbf
Page : 3
Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.
Santa Cruz , Bolivia 591 (3) 355-9618 int 113 | www.prosertec-srl.com; Fax:591 (3) 311-7427 No Prpd. Chk. Appr. Quote Number:
Client: YPFB TRASPORTE SA Location: ESTACION SAMAIPATA Project: SISTEMA DE ALIVIOS Y VENTEOS VALVE ID Tag No. PSV-001 Service GLP PID No. SC-E02-PR-00-03-02 de 02 Line No. 6"-0.280-B-(V-3)-3001 End-User Ref. No.: Project Ref. No.: 7 8 9 10 11 12
Date
Revision
1 2 3 4 5 6
SELECTION SUMMARY
Valve Model No. Brand Inlet Outlet 3" 4" Flngd. Flngd. 46312-34/S1 Anderson Greenwood
CONNECTIONS
600# 150# RF RF Standard ASME B16.5
Quantity 1
Wt.= A= B= C= D= E= F= G= H=
= = = = = = = = =
Dimension Notes
Accessories not shown. Weight and dimensions shown are approximate. Actual valve may vary from. image.
Tag Notes
Printed On: 25-sep-2013
Page : 4
Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.
Summary Report
Project Information
Company: Location: My Company Project: Project Ref. No.: My Project
Tag Information
Tag Number: Revision: Prepared By: PSV-001 Last Modified: Checked By: 20/09/2013 06:32:08 p.m. Approved By:
Page : 5
Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license agreement. Not for resale. All rights reserved. All trademarks, trade names and/or registered trademarks referred to in this program are the property of their respective owners. Copyright 2012 Pentair Valves & Controls.