Section 9
Panelboards
PANELBOARDS
NF
Pricing Procedures Merchandised Main Lug Panelboards Merchandised Main Circuit Breaker Panelboards Merchandised Main Lug & Main Circuit Breaker Merchandised Accessories QOB Branch Circuit Breakers Factory Assembled Panelboards and Circuit Breakers Factory Assembled Common Features Merchandised Main Lugs Panelboards Merchandised Main Circuit Breaker Panelboards Merchandised Main Lug & Main Circuit Breaker Panelboards with TVSS Merchandised Accessories EDB, EGB, EJB Branch Circuit Breakers Factory Assembled Panelboards Factory Assembled Common Features Merchandised Single Row (Column Width) Panelboards 14 inch Wide Panelboards
9-5 9-6 9-7 9-8 9-9 9-10 9-11 9-12 9-13 9-13 9-13 9-14 9-15 9-18 9-19 9-16 9-41
M NQ New!
9-1
Series Ratings
This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure. Table 9.1: NQ Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses MG HD, JD HG, JG HJ, JJ HL, JL Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges cde Type QO (B) QO (B) PL QO (B) PL QO (B) PL QO (B) PL QO (B) QO (B) GFI QO (B) AFI QO (B) AFI, QO (B) CAFI QO (B) VH QO (B) EPD QO (B) QO (B) AS QO (B) GFI QO (B) VH QO (B) PL QO (B) AFI QO (B) QO (B) GFI QO (B) AFI, QO (B) CAFI QO (B) EPD QO (B) VH QO (B) QO (B) GFI QO (B) AFI, QO (B) CAFI QO (B) EPD QO (B) VH QO (B) QO (B) GFI QO (B) AFI, QO (B) CAFI QO (B) EPD QO (B) VH 1 Pole 1530A 1530A 1570 A 1530 A 1520 A 1520 A 1530 A 1570 A 1530 A 1530 A 1530 A 1520 A 1570 A 1530 A 1520 A 1530 A 1570 A 1530 A 1520 A 1530 A 1570 A 1530 A 1520 A 1530 A 2 Pole 1560 A 15125 A 4060 A 150 A 1560 A 15125 A 1530 A 1560 A 150 A 1560 A 1570 A 1560 A 1560 A 15100 A 1560 A 1560 A 15100 A 1560 A 1560 A 3 Pole
NQ Panelboards
Class 1640
www.schneider-electric.us
Table 9.1:
9
PANELBOARDS
Max. Short Circuit Current Rating 22,000 42,000 65,000 100,000 125,000
LC400A
120/240 1PH
15150 A 1530 A 1530 A 1530 A 35150 A 1530 A 1570 A 15100 A 15100 A 240
65,000
QG
208Y/120
30,000
QG, HG, JG 65,000 HG, JG FC_ or KC_22___ FC_ or KC_32___ FC_ or KC_24___ FC_ or KC_34___ DJ 400A 100,000 EJ, FJ
208Y/120
30,000
208Y/120
30,000
208Y/120
18,000
LA/LH (L) 34200MC LA/LH (L) 34225MC LA/LH (L) 34250MC LA/LH (L) 34400MC
QD
HD, JD
LA, MA
QO (B) QO (B) AS QO (B) GFI QO (B) PL QO (B) AFI QO (B) QO (B) GFI QO (B) AFI QO (B) QO (B) AS QO (B) GFI QO (B) VH QO (B) PL QO (B) AFI QO (B) QO (B) GFI QO (B) AFI QO (B) QO (B) AS QO (B) GFI QO (B) AFI QO (B) QO (B) VH QO (B) GFI QO (B) AFI QO (B) H QOB2150VH Q2L-H QDL QO (B) QO (B) VH QOBVH QO (B) GFI QO (B) AFI QO (B) VH QOBVH QO (B) GFI QO (B) AFI QO (B) VH
1570 A 1530 A 1530 A 1530 A 1520 A 1570 A 1530 A 1520 A 1570 A 1530 A 1530 A 1530 A 1520 A 1570 A 1530 A 1520 A 1570 A 1530 A 1530 A 1520 A 1570 A 1530 A 1520 A 1570 A 1530 A 1530 A 1520 A 1530 A 1520 A 1530 A
15125 A 1530 A 1560 A 1530 A 15100 A 1530 A 15125 A 1530 A 1560 A 150 A 1560 A 15125 A 1560 A 15125 A 1530 A 1560 A 15125 A 1560 A 15100 A 150 A 100225 A 70225 A 15125 A 150 A 1560 A 15125 A 150 A 1560 A 1530 A
15100 A 1530 A 1530 A 1530 A 1530 A 35150 A 1530 A 15100 A 15100 A 1530 A 15100 A 35150 A 100225 A 70225 A 15100 A 15100 A 1530 A
200,000
FI, KI 400 A Max. Class J or T6 Fuses 200 A Max. Class T3 Fuses 200 A Max. Class J or T6 Fuses and 400 A Max. Class T3 Fuses
65,000 100,000
200,000
a b c d e f
For shown circuit breakers rated less than this maximum voltage, the indicated short circuit current rating also applies, but at the voltage rating of the circuit breaker. Short circuit tests are conducted at 100105% of the maximum rated voltage of the panelboard. Suffixes HID, SWD, and SWN may also be applied to the applicable branch circuit breakers shown above. Suffix SWN may not be applied in combination with LC main breakers. Where QO (B) circuit breakers are shown above, QO (B) H, QO (B) VH, and QH (B) circuit breakers may also be used. Where QO (B) GFI circuit breakers are shown above, QO (B) EPD circuit breakers may also be used. To acheive selective coordiantion, the rating of the DJ main circuit breaker must be at least two times greater than the ampere rating of any branch circuit breaker.
9-2
Series Ratings
www.schneider-electric.us
This page contains UL Tested and Certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure
Table 9.2: NF Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Max. Maximum Short System Circuit Voltage, Current AC a Rating Square D Brand Integral or Remote Main Circuit Breakers and Remote Main Fuses Square D Brand Branch Circuit Breaker Catalog Designation and Allowable Ampere Ranges
(continued)
Max. Short Maximum Circuit System Current Voltage, Rating AC a (RMS Symm.) Square D Branch Circuit Breakers Integral or Remote 2- or 3-pole Main Circuit Breaker Designation Poles
EDB, EDB-EPD 65,000 EG, FH, FG, KH, LH, MH, MX, HG, JG, DG EG ECB-G3 EJ, FC, FJ, KC, LC, LX, HJ, JJ EDB, EDB-EPD, EGB 100,000 EJ, FC, KC, HJ, JJ ECB-G3 120 DJ EDG. EGB 120/240 240 125,000 HL, JL EDB, EDB-EPD, EGB, ECB-G3 FI, KI, LI, LXI EDB, EDB-EPD, EGB, EJB 200,000 FI, KI ECB-G3 Class J or T (600 V) 200 A Max Fuses ECB-G3 EG, FG, KH, LH, HG, JG, DG EDB, EDB-EPD 35,000 EG, HG, JG ECB-G3 EJ, FC, FJ, KC, LC, LX, HJ, JJ, DJ EDB, EDB-EPD, EGB 65,000 EJ, FC, KC, HJ, JJ ECB-G3 HL, JL EDB, EDB-EPD, EGB, EJB 277 480Y/277 100,000 DL EDG, EGB, EJB 400 A Max Fuses EDB, EDB-EPD, EGB, EJB FI, KI, LI, LXI EDB, EDB-EPD, EGB, EJB 200,000 FI, KI ECB-G3 200 A Max Fuses EDB, EDB-EPD, EGB, EJB, ECB-G3 18,000 HG, JG, MG EDB EDB, EGB 25,000 EJ, FI, KH, KI, LC, LE, LX, LI, LXI, HJ, JJ LH (1570 A), EDB, EGB LC, LE, LX EDB, EGB, EJB 600Y/347 35,000 50,000 HL, JL EDB, EGB, EJB FI, KI EDB, EGB, EJB 65,000 LI, LXI EJB 200,000 Class J or T (600 V) 200 A max Fuses EDB, EGB, EJB a
.
240
200k
25k 35k
277
1 2, 3 2, 3
Short circuit tests are conducted at 100105% of the maximum rated voltage of the panelboard.
2, 3
Table 9.3: I-Line Series Connected Circuit Breaker Ratings (RMS Symmetrical)
Max. Short Maximum Circuit System Current Voltage, Rating AC a (RMS Symm.) 42k 65k 120 100k 208Y/120 100k 35k 240 42k 50k Square D Branch Circuit Breakers Integral or Remote 2- or 3-pole Main Circuit Breaker MG QG, LH FJa, QJ QJ, LC QJ QJ, PH, PJ, RJ MG KA LA, MA MG MG HG, JG JG QG LH, MH, PA, PG, RG FGa, FH, MH, MX, PJ FC, KC, KH, LC, LH LH LH MG DG RL FC, KC, LC, LX PH, PJ, RJ QJ FJa FC, KC LC, LX KC, LC, LX KC, LC LC LC HJ, JJ JJ LC, LX, MJ, PJ, RJ MJ DJ RL HL, JL JL PC, PH, PL, RL PC, PL, RL Designation FY FA, FDa FDa FA FA, FDa QD, QG FA FDa HD, JD, QD FA FA (25 A Max.) FA, HD JD, QD FA, FDa, QD HD, JD, QD FDa FDa, FGa FA LA HD, JD, KA FH, HD, JD, KA, LA, MA FH, KH FDa, FGa, FJ QD, QG FDa FDa FA, FH, FDa, FGa, FJa FH, FDa, FGa, FJa KA KH LA, LH, MG FA FA, FH, HD, HG JD, JG HD, HG, JD, JG LA, LH FH, HD, HG, JD, JG, KA, LA, MA, MG RG HD, HG, HJ, FA, FH JD, JG, JJ HD, HG, JD, JG HH, JJ Poles
42k 50k
2, 3 2, 3
480 65k
2, 3
2, 3
200k
2, 3 2, 3 2, 3 2, 3 2, 3
240
65k
85k
2, 3
2, 3 2, 3 2, 3
2, 3
35k 50k
240
100k
1, 2, 3
2, 3
2, 3
600Y/347 2, 3 a
240
125k
Obsolescent. Contact the Square D/Schneider Electric local Field Sales Office for the replacement circuit breaker.
9-3
65k
FI, KI, LI, LXI HD, HG, HJ KI, LI, LXI JD, JG, JJ FI, KI, LI, LXI FDa, FGa, FJ FI,KI FA, FH, FC, FDa, FGa, FJa LI, LXI FH, FDa, FGa, FJa LI FC KI, LI, LXI KA, QD, QG, QJ LI KC FH, KA FDa FGa, KH, LH FDa DG FH, FY FJa FDa FC, KC FA, FH, FY, FDa, FGa LC, LX (400 A Max.) FH LC, LX (600 A Max.) FY, FDa, FGa DJ FH, FY DL FH, FJ FI, KI FA, FH, FY, FDa, FGa, FJ LI, LXI (400 A Max.) FH LI, LXI (600 A Max.) FY, FDa, FGa, FJ MG FA KH, LA, MA, MX, PA, PC, FH LA, MA, PA, PC, PX KA LA, MA, PA HD, JD FA (25 A Max.), MG MH, MX, PA HD, JD HG, JG FA, HD JG JD LH, MG, PG, RG HD, JD LH HG, JG DG FH, HD, JD, KA, LA, MA MJ FH (25 A Max.) RL RG MJ KA, KH FC, KC FA, FH HJ, JJ FA, FH, HD, HG JJ JD, JG LC, LI, LX, LXI HD, HG, JD, JG LC, LX (400 A Max.) FH KC, LC, LX KA LC, LX LA DJ FH, HD, HG, JD, JG, KA, LA, MA HL, JL FA, FH, HD, HG, HJ JL JD, JG, JJ LI, LXI (600 A Max.) KA DL FH, HD, HG, HJ, JD, JG, JJ, KA, LA, MA PC, PH, PL, RL HJ, JJ RL RG FI, KI FA, FH, FC, HD, HG, HJ KI JD, JG, JJ, KA LI FC, KA, KC, LA, HJ, HL, JJ, JL LXI KA, HJ, HL, JJ, JL FH, KA FDa FGa, KH, LH FDa FJa FDa FC, KC FDa, FGa LC, LX (600 A Max.) FDa, FGa FI, KI FDa, FGa, FJa LI, LXI (600 A Max.) FDa, FGa, FJa HG, JG FA, HD JG JD MG, PG, RG HD, JD MG FA HJ, JJ FA, HD, HG JJ JD PJ, RJ MG FH, HD, HG, HJ, LC HL, JL FA, HD, HG, HJ JL JD, JG, JJ PK HJ, JJ, MJ FI, KI HD, HG, HJ KI JD, JG, JJ KI, LI FH LI LA MG FA (25 A max.) MJ FA (30 A max.) HL, JL FJ
2, 3 1
2, 3
1 1
PANELBOARDS
Series Ratings
I-Line Panelboards
Class 2110
www.schneider-electric.us
Table 9.4:
9
PANELBOARDS
120/240 1 208Y/120
240
65,000
240
240
200,000
480
100,000
480
200,000
600 A
600
100,000
600
200,000
Note: The fuse used in this UL test is an envelope (umbrella) fuse. This fuse is designed as a worst case fuse. Thus, no matter what manufacturers fuse is used, the Square D circuit breaker is protected. The line side fused switch may be in a separate enclosure, or in the same enclosure as the loadside circuit breaker. A line side fused switch may be a submain, integral main, or remote main. A load side circuit breaker may be a branch, submain, or an integral main used on the load side of a remote main. This series combination short circuit current rating shall not exceed that of the line side fused switch. The charts apply to Square D Company load side circuit breakers only. However, the line side fuse ratings are independent of the fuse manufacturer. Not applicable to Corner Grounded Systems. Limiters used in Square D DSL and DSL II fused power circuit breakers are not class L fuses and do not have series ratings.
9-4
1. 2.
Select BASE PRICE for main lugs or main circuit breaker from BASE PRICE TABLE. Include equipment ground bar when required. List BRANCH CIRCUIT BREAKERS (either plug-on or bolt-on) and determine total spaces required. Select price from BRANCH CIRCUIT BREAKERS TABLE. Include space only charge for future requirements. If total spaces required exceeds the maximum listed, price as two or more panelboards and add price for sub-feed or feed-through lugs, so installer can cable between sections. Add price for special features from appropriate page. Contact field office for additional special features.
4.
3.
4. 5.
5. 6.
NOTE: Additional special price adders can be found in the Supplemental and Obsolescence Digest, Section 4.
6. Apply appropriate discount schedule.
NQ Merchandised Example
Table 9.5: 208Y/120 Vac, 34W, 10 kA SCCR, 225 A, MLO, Type-1 surface mount, bolt-on branch circuit breakers, main sub-feed lugs
Page No. 9-10 9-10 9-10 Catalog Number (20) QOB120 two QOB240 two QOB330 Spaces 20 4 6 Total 30 Total Price : $ Price 795. 177. 585.
Item 225 A MLO Base Price (20) 20/1 Bolt-on two 40/2 Bolt-on two 30/3 Bolt-on Sub-feed Lugs
NF Merchandised Example
Table 9.6: 480Y/277 Vac, 34W, 25 kA SCCR, fully rated, copper bus, 100 A, main circuit breaker, Type 1 flush mount, bolt-on branch circuit breakers
Page No. 9-15 9-15 9-15 Catalog No. EGB14020 EGB24040 EGB34050 Spaces 13 2 3 Total 18 Total Price: $ Price 3315. 776. 1131.
Item 250 A Main Circuit Breaker Base Price Copper bus adder (13) 20/1 one 40/2 one 50/3
Main circuit breaker adapter kit (less circuit breaker) Main circuit breaker 125 A MLO Cu Bus Int. Box Cover
Discount Schedule
9-5
NQ Merchandised Panelboards
Table 9.9:
9
PANELBOARDS
Pole Spaces
Mains Rating
Height (In.)
Type 1
20 in. Wide Cabinet gSingle Phase 3-Wire 18 100 30 30 42 225 72d 84d 30 42 84d 30 42 84d 600 400 1395. 1474. 1585. 1675. 1744. 1819. 2002. 2080. 3073. 3206. 3521 3677. 2462. 2579. 2620. 2738. 4853. 2705. 2861. 5099. 2977. 3056. 3149. 3239. 3308. 3383. 3556. 3634. 4900. 5033. 5288. 5444. 4229. 4346. 4387. 4505. 6534. 4548. 4704. 6873. NQ18L1 NQ18L1C NQ30L1 NQ30L1C NQ30L2 NQ30L2C NQ42L2 NQ42L2C NQ72L2 NQ72L2C NQ84L2 NQ84L2C NQ30L4 NQ30L4C NQ42L4 NQ42L4C NQ84L4C NQ30L6C NQ42L6C NQ84L6C 785. 864. 945. 1035. 1104. 1179. 1340. 1418. 2297. 2430. 2679. 2835. 1620. 1737. 1778. 1896. 3792. 1863. 2019. 4038. MH68 MH50 MH68 113. NC68V ( ) NC50V ( ) NC68V ( ) 948. 729. 948. NC68V( )HR NC50V( )HR NC68V( )HR 1185. 912. 1185. MH68WP MH62WPe MH80WPe 2742. 2685. 2835. 68 50/62 68/80 MH50 113. NC50V ( ) 729. NC50V( )HR 912. MH50WP 2609. 50 MH26 113. MH32 MH32 MH38 113. MH44 MH50 NC44 ( ) NC50 ( ) 663. 729. NC44( )HR NC50( )HR 830. 912. MH44WP MH50WP 2603. 2609. 44 50 NC32 ( ) NC32 ( ) NC38 ( ) 527. 527. 549. NC32( )HR NC32( )HR NC38( )HR 657. 657. 687. MH32WP MH32WP MH38WP 2204. 2204. 2216. 32 32 38 NC26 ( ) 497. NC26( )HR 620. MH26WP 2192. 26
20 in. Wide Cabinet g Three Phase 4-Wire 18 100 30 30 42 54 72d 84d 30 42 72d 84d 30 42 84d a b c d e f g 600 225 1486. 1561. 1752. 1831. 1855. 1932. 2138. 2213. 2559. 2655. 3307. 3436. 3794. 3944. 2704. 2822. 2854. 400 2975. 4449. 4657. 5327. 2983. 3116. 5609. 3068. 3143. 3316. 3395. 3419. 3496. 3692. 3767. 4113. 4209. 5134. 5263. 5561. 5711. 4471. 4589. 4621. 4742. 6134. 6342. 7008. 4826. 4959. 7383. NQ418L1 NQ418L1C NQ430L1 NQ430L1C NQ430L2 NQ430L2C NQ442L2 NQ442L2C NQ454L2 NQ454L2C NQ472L2 NQ472L2C NQ484L2 NQ484L2C NQ430L4 NQ430L4C NQ442L4 NQ442L4C NQ472L4 NQ472L4C NQ484L4C NQ430L6C NQ442L6C NQ484L6C 876. 951. 1112. 1191. 1215. 1292. 1476. 1551. 1898. 1994. 2531. 2660. 2952. 3102. 1862. 1980. 2012. 2133. 3449. 3657. 4266. 2141. 2274. 4548. MH62 MH68 MH50 MH68 113. MH50 113. NC62V ( ) NC68V ( ) NC50V ( ) NC68V ( ) 887. 948. 729. 948. NC62V( )HR NC68V( )HR NC50V( )HR NC68V( )HR 1109. 1185 912. 1185. MH62WP MH68WP MH62WPe MH80WPe 2685. 2742. 2685. 2835. 62 68 50/62 68/80 NC50V ( ) 729. NC50V( )HR 912. MH50WP 2609. 50 MH44 MH50 MH38 113. NC44 ( ) NC50 ( ) 663. 729. NC44( )HR NC50( )HR 830. 912. MH44WP MH50WP 2603. 2609. 44 50 NC38 ( ) 549. NC38( )HR 687. MH38WP 2216. 38 MH26 113. MH32 MH32 NC32 ( ) NC32 ( ) 527. 527. NC32( )HR NC32( )HR 657. 657. MH32WP MH32WP 2204. 2204. 32 32 NC26 ( ) 497. NC26( )HR 620. MH26WP 2192. 26
C suffix indicates copper bussing. Embossed mounting holes add a .25 inch standoff to back of MH box. Add F for flush, S for surface. Use only if the Local Jurisdiction where this panelboard interior is being applied has adopted the 2008 NEC, which allows single panelboard interiors greater than 42 circuits. When NEMA 3R, 5, or 12 enclosures are selected, an NQ12RDE kit should also be selected. See Table 9.17. Enclosure includes trim kit. For 14 in. wide offer, see the Supplemental & Obsolescence Digest.
9-6
PE1A
Discount Schedule
NQ Merchandised Panelboards
www.schneider-electric.us
Table 9.10:
Main Circuit Breaker InteriorsWill accept plug-on and bolt-on circuit breakers
Type 3R, 5, 12 Enclosure e Enclosure 20 in. W x 6.5in. D Height (In.) Catalog $ Price No.
20 in. Wide Cabinet hSingle Phase 3-Wire 16k 28k 18 30 30 42 72d 84d 30 42 84d 1395. 100 1474. backfed 1585. 1675. 100 100 225 225 225 225 400 400 400 2227. 2306. 2501. 2591. 2660. 2735. 2962. 3040. 3976. 4109. 4459. 4615. 3400. 3517. 3558. 3676. 5686. 2977. 3056. 3149. 3239. 3781. 3860. 4328. 4418. 4487. 4562. 4729. 4807. 5729. 5862. 6144. 6300. 5085. 5202. 5243. 5361. 7407. NQ18L1 NQ18L1C NQ30L1 NQ30L1C NQ18L1 NQ18L1C NQ30L1 NQ30L1C NQ30L2 NQ30L2C NQ42L2 NQ42L2C NQ72L2 NQ72L2C NQ84L2 NQ84L2C NQ30L4 NQ30L4C NQ42L4 NQ42L4C NQ84L4C 785. 864. 945. 1035. 785. 864. 945. 1035. 1104. 1179. 1340. NQMB2HJ 1418. NQMB2Q 2297. 2430. NQMB2KI 2679. 2835. 1620. 1737. 1778. 1896. NQMB4LA NQMB4LA NQMB2HJ NQMB2HJ 780. HD, HG, HJ, HLl 100A maximum 780. 780. HD, HG, HJ, HLl 780. or JD, JG, JJ, JL QB,QD,QG,QJ 780. 780. 780. 780. 780. LA/LHm LA/LHm LA/LHm KI MH62 MH62 MH62 MH80 MH38 MH44 MH44 MH50 MH56 Select QOB 2-pole or QOB-VHi MH26 MH32 113. 113. 113. 113. 113. 113. 113. 113. NC26 ( ) NC32 ( ) NC38 ( ) NC44 ( ) NC44 ( ) NC50 ( ) NC56 ( ) NC62 ( ) 497. NC26( )HR 527. NC32( )HR 549. NC38( )HR 663. NC44( )HR 663. NC44( )HR 729. NC50( )HR 786. NC56( )HR 887. NC62( )HR 887. NC62V( )HR 887. NC62V( )HR 1001. NC80V( )HR 620. MH26WP 657. MH32WP 687. MH38WP 830. MH44WP 830. MH44WP 912. MH50WP 983. MH56WP 1109. MH62WP 1109. MH62WP 1109. MH62WP 1245. MH80WP 2192. 2204. 2216. 2603. 2603. 2609. 2652. 2685. 2685. 2685. 2835. 26 32 38 44 44 50 56 62 62 62 80
3792. NQMB4LA
20 in. Wide Cabinet hThree Phase 4-Wire 15k 27k 18 100 30 30 42 54 72d 84d 30 42 72d 84d a b c d e f g h i j k l m 225 1395. 100 1474. backfed 1585. 1675. 2318. 2393. 2668. 2747. 2771. 2848. 3098. 3173. 3519. 3615. 4210. 4339. 4732. 4882. 3642. 3760. 3792. 400 3913. 5314. 5522. 6160. 2977. 3056. 3149. 3239. 3872. 3947. 4495. 4574. 4598. 4675. 4865. 4940. 5286. 5382. 5963. 6092. 6417. 6567. 5327. 5445. 5477. 5598. 6986. 7194. 7881. NQ418L1 NQ418L1C NQ430L1 NQ430L1C NQ418L1 NQ418L1C NQ430L1 NQ430L1C NQ430L2 NQ430L2C NQ442L2 NQ442L2C NQ454L2 NQ454L2C NQ472L2 NQ472L2C NQ484L2 NQ484L2C NQ430L4 NQ430L4C NQ442L4 NQ442L4C NQ472L4 NQ472L4C NQ484L4C 785. 864. 945. 1035. 876. 951. 1112. 1191. 1215. 1292. 1476. 1551. NQMB2HJ 1898. NQMB2Q 1994. NQMB2KI 2531. 2660. 2952. 3102. 1862. 1980. 2012. 2133. 3449. 3657. NQMB4LA 780. 780. LA/LHm LA/LHm MH74 MH80 113. NC74V ( ) 113. NC80V ( ) 972. NC74V( )HR 1001. NC80V( )HR 1215. MH74WP 1245. MH80WP 2757. 2835. 74 80 MH62 NQMB4LA 780. LA/LHm 113. NC62V ( ) 887. NC62V( )HR 1109. MH62WP 2685. 62 780. HD, HG, HJ, HL or JD, JG, JJ, JL QB,QD,QG,QJ 780. 780. KI MH56 MH62 113. 113. NC56 ( ) NC62 ( ) 786. NC56( )HR 887. NC62( )HR 983. MH56WP 1109. MH62WP 2652. 2685. 56 62 MH50 113. NC50 ( ) 729. NC50( )HR 912. MH50WP 2609. 50 780. MH44 NQMB2HJ HG, HJ, HL 780. HD, 100A maximum MH38 MH44 Select QOB 3-pole or QOB-VHj MH26 MH32 113. 113. 113. 113. 113. NC26 ( ) NC32 ( ) NC38 ( ) NC44 ( ) NC44 ( ) 497. NC26( )HR 527. NC32( )HR 549. NC38( )HR 663. NC44( )HR 663. NC44( )HR 620. MH26WP 657. MH32WP 687. MH38WP 830. MH44WP 830. MH44WP 2192. 2204. 2216. 2603. 2603. 26 32 38 44 44
4266. NQMB4LA
C suffix indicates copper bussing. Embossed mounting holes add a .25 inch standoff to back of MH box. Add F for flush, S for surface. Use only if the Local Jurisdiction where this panelboard interior is being applied has adopted the 2008 NEC, which allows single panelboard interiors greater than 42 circuits. Enclosure includes trim kit. Select the appropriate main circuit breaker from tables starting on page 7-22 and add the circuit breaker price to the total price of the panelboard. Circuit breaker interrupt ratings, see tables starting on page 7-22. For 14 in. wide offer, see the Supplemental & Obsolescence Digest. QOB2150VH takes four pole spaces; all other QOB two pole circuit breakers take two pole spaces. QOB3110VH to QOB3150VH take six pole spaces; all other QOB three pole circuit breakers take three pole spaces. Pole spaces shown are available for branch circuits, with spaces deducted for the back fed main breaker. For single phase applications, order a 3-pole breaker. Example: HDL36100. For 400A applications order short handle circuit breaker (LAL36400MB).
PE1A
Discount Schedule
9-7
PANELBOARDS
Total $ Price Type 1 Enclosure Interior Only Interior, Front, (Order Circuit Breaker Adapter Kit Branch Circuit Main Box and (Less Circuit Breaker) f Box Front Pole Mains Adapter Breakers Separately) Mono-Flat Hinged Front Kit f 20 in. W x 5.75 in. D b Spaces Rating 3R, Circuit Breaker Catalog Type 1 Type $ Price Catalog No. $ Price 5, 12 Catalog No. a $ Price Catalog No. $ Price Frame Size g Catalog No. $ Price No. c
NQ Merchandised Panelboards
Table 9.11:
NQ Main Lug and Main Circuit Breaker Interiors with TVSS240 Vac, 48 Vdc
Class 1640 / Refer to Catalog 1640CT0701
www.schneider-electric.us
9
PANELBOARDS
Voltage
Surge Rating
Type 1 120,000 A 225 A 30 208Y/120 Vac 160,000 A 120,000 A 225 A 42 208Y/120 Vac 160,000 A 225 A 72d 208Y/120 Vac 120,000 A 120,000 A 400 A 42 208Y/120 Vac 160,000 A 400 A a b c d e 72d 208Y/120 Vac 120,000 A 24026. 24103. 28141. 28218. 24344. 24419. 28459. 28534. 25500. 25629. 25042. 25163. 29156. 29278. 26532. 26740.
Type 3R, 5, 12 Catalog Number a 25793. 25870. 29908. 29984. 26097. 26172. 30212. 30287. 27185. 27314. 26723. 26844. 30837. 30959. 28253. 28461. NQ430L2TVS212 NQ430L2TVS212C NQ430L2TVS216 NQ430L2TVS216C NQ442L2TVS212 NQ442L2TVS212C NQ442L2TVS216 NQ442L2TVS216C NQ472L2TVS212 NQ472L2TVS212C NQ442L4TVS212 NQ442L4TVS212C NQ442L4TVS216 NQ442L4TVS216C NQ472L4TVS212 NQ472L4TVS212C
$ Price 23184. 23261. 27299. 27375. 23445. 23520. 27560. 27635. 24500. 24629. 23981. 24102. 28095. 28217. 25418. 25626.
MH50
113.
NC50( )
912.
MH50WP
2609.
MH56
113.
NC56( )
983.
MH56WP
2652.
MH62
113.
NC62( )
1109.
MH62WP
2685.
MH68
113.
NC68V( )
1185.
MH68WP
2742.
MH80
113.
NC80V( )
1245.
MH80WP
2835.
C suffix indicates copper bussing. Embossed mounting holes add a .25 inch standoff to back of MH box. Add F for flush, S for surface. Use only if the Local Jurisdiction where this panelboard interior is being applied has adopted the 2008 NEC, which allows single panelboard interiors greater than 42 circuits. Enclosure includes trim kit.
Table 9.12:
Surge Rating
225 A
30
26726. NQ430L2TVS212C 23261. 30840. NQ430L2TVS216C 27375. NQMB2HJ or 26967. NQ442L2TVS212 23445. NQMB2Q 27042. NQ442L2TVS212C 23520. or 31082. NQ442L2TVS216 27560. NQMB2KI 31157. NQ442L2TVS216C 27635. 28037. NQ472L2TVS212 27596. NQ442L4TVS212 31710. NQ442L4TVS216 24500. 23981. 28095. NQMB4LA 28166. NQ472L2TVS212C 24629. 27717. NQ442L4TVS212C 24102. 31832. NQ442L4TVS216C 28217.
225 A
42
225 A
72f
780.
MH74
113. NC74( )
400 A
42
MH80
a b c d e f
Select the appropriate main circuit breaker from tables starting on page 7-22 and add the circuit breaker price to the total price of the panelboard. C suffix indicates copper bussing. Embossed mounting holes add a .25 inch standoff to back of MH box. Add F for flush, S for surface. Enclosure includes trim kit. Use only if the Local Jurisdiction where this panelboard interior is being applied has adopted the 2008 NEC, which allows single panelboard interiors greater than 42 circuits.
9-8
PE1A
Discount Schedule
NQ Merchandised Panelboards
www.schneider-electric.us
NQ Merchandised Accessories
Class 1640 / Refer to Catalog 1640CT0701
Table 9.13:
Mains Ampacity 100 225 400 600 a b
NQ Merchandised Neutrals
200% Neutral Kit Catalog No. NQNL1 NQNL2 or NQNL2ACCYb NQNL4a Price 315. 426. 639. Not Available Box Add no adder no adder Schedule PE-1A PE-1A Catalog No. NQN1CU NQN2CU NQN6CU NQN6CUa Copper 100% Neutral Kit Price 192. 585. Box Add no adder no adder Schedule PE-1A
Not to be used with SFL, FTL or SFB. These combinations are factory assembled only. For 225A panel with SFL, FTL or SFB, use NQNL2ACCY (enclosure size increases by 6 inches). Otherwise, use NQNL2.
Table 9.14:
Mains Ampacity 100 A 225 A 400 A 600 A
Note: See Table 9.15 & Table 9.16 for box selection table. a The final character L indicates the kit is used for Low circuit count interiors 30 and 42. b The final character H indicates the kit is used for High circuit count interiors 54, 72 and 84.
Table 9.15:
Feature Circuits 18 30 42 72 84 a
Table 9.16:
Feature Circuits 18 30 42 72 84 a
Box Selection Table: Merchandised NQ Vertically Mounted Main Breaker Panelboards w/ Accessories
Feed-through Lugs 100A 225 A MH50 MH62 MH68 400A MH62 MH68 MH80 MH80 600A Factory Asm. Only 100A Sub-feed Circuit Breakers 225 A (one) MH62 MH68 MH74 MH80 400A (two) MH86 MH86 a a 600A (two) Factory Asm. Only
Table 9.17:
NQ Accessories
Description Catalog No. QOB2125SL QOB3125SL PK27GTA PK23GTAL PK27GTACU PKGTAB NQFP15a NQ102OE NQ204OE NQ102S NQ204S NQ6RDE NQ12RDE NQ18RDE NQ24RDE PK49SP HLO1 QO1HT QO1PA QO1PL QO3HT QO1PAF QO2PAF QOGFI1PAF QOGFI2PAF QO70AN Q1100AN Q1150AN 8011010501 8011010401 $ Price 176.00 176.00 33.80 40.70 84.00 43.80 68.00 7.90 7.90 7.90 7.90 252.00 283.00 343.00 397.00 39.00 9.90 3.80 10.70 10.70 13.40 43.50 25.80 51.00 38.40 9.90 11.10 32.40 41.10 41.10 Schedule
Sub-feed (Bolt-on) 2-pole 3-pole Equipment Ground Bars Aluminum PK23GTA+ #1 to #4/0 Al or Cu lug Copper Ground Bar Insulator Kit Filler plate (15 per package) Circuit I.D. Number Strips 1102 odd/even (left side numbered 1,3,5 ...101) 103204 odd/even (left side numbered 103,105,107 ... 203) 1102 sequential (left side numbered 1,2,3 ... 102) 103204 sequential (left side numbered 103,104,105 ... 204) 6 in. Extension 12 in. Extension Rail & Deadfront Extensions 18 in. Extension 24 in. Extension Touch-up paint USAS #49 Gray (Aerosol can) Handle AttachmentsBranch Circuit Breakers Handle lock-off Handle tie - (QO and QOB only) Handle padlock attachment1-pole 2- and 3-pole Handle tie & lock-off for three 1-pole (QO, QOB) Handle Padlock Attachment for Padlocking in OFF position For padlocking 1P QO circuit breaker in OFF position only, fixed attachment For padlocking 2P and 3P QO circuit breaker in OFF position only, fixed attachment For padlocking 1P QO-GFI, QO-AFI, QO-CAFI and QO-EPD circuit breakers in OFF position only, fixed attachment For padlocking 2P QO-GFI and QO-EPD circuit breakers in OFF position only, fixed attachment Neutral or Ground Lugs #10 to #2 Al or #14 to #4 Cu #4 to #1/0 Al or Cu #1 to #4/0 Al or Cu Endwalls for MH Enclosures Blank (one per package) With Knockouts (one per package) a Filler Plates are $3.00 each and must be ordered in packages of 15.
DE2A
PE1A
DE1
DE2A
DE2E
DE3A
PE1A
PE1A
DE2A
DE2E
DE3A
Discount Schedule
9-9
PE-1A
PANELBOARDS
PE-1A
Table 9.19:
Ampere Rating a QOB Bolt-On
9
PANELBOARDS
Catalog No.
Catalog No. $ Price Catalog No.$ Price Catalog No. $ Price 240 Vac10 k AIR 48 Vdc5 k AIR j QOB310 293. QOB315 i 293. QOB320 i 293. QOB325 i 293. QOB330 i 293. QOB335 i 293. QOB340 i 293. QOB345 i 293. QOB350 i 293. QOB360 i 293. QOB370 ij 369. QOB380 ij 419. QOB390 ij 419. QOB3100 ij 419. QOB300 293. QOB3000 507.
QOB-GFIQOB QWIK-GARD Circuit Breaker With Ground Fault Circuit Interrupter UL Class A 46 mA People Protection. b 120/240 Vac 120 Vac10 k AIR 208Y/120 Vac10 k AIR 10 k AIR 15 QOB115GFI 248. QOB215GFI 444. QO315GFI 791. 20 QOB120GFI 248. QOB220GFI 444. QO320GFI 791. 25 QOB125GFI 248. QOB225GFI 444. 30 QOB130GFI 248. QOB230GFI 444. QO330GFI 791. 40 QOB240GFI 444. QO340GFI 791. 50 QOB250GFI 444. QO350GFI 791. 60 QOB260GFI c 444. QOB-VHGFI d 120 Vac22,000 AIR 15 QOB115VHGFI 497. 20 QOB120VHGFI 497. 25 QOB125VHGFI 497. 30 QOB130VHGFI 497. QOB-EPDQOB Equipment protection circuit breakers with UL Listed 30 mA (EPD) or 100 mA (EPE) equipment protection. 120 Vac 240 Vac10 k AIR 10,000 AIR 15 QOB115EPD 417. QOB215EPD 671. QO315EPDm 1077. QO315EPEm 1077. 20 QOB120EPD 417. QOB220EPD 671. QO320EPDm 1077. QO320EPE 1077. 25 QOB125EPD 417. QOB225EPD 671. 30 QOB130EPD 417. QOB230EPD 671. QO330EPDm 1077. QO330EPEm 1077. 40 QOB240EPD 671. QO340EPDm 1077. QO340EPEm 1077. 50 QOB250EPD 671. QO350EPDm 1077. QO350EPEm 1077. 60 QOB260EPD 671. QOB-HMHigh magnetic trip circuit breakers 15 QOB115HMe 39.80 20 QOB120HMe QOB-KKey operated QOB circuit breakers f 120 Vac10,000 AIR 10 QOB110K 168. 15 QOB115K 168. 20 QOB120K 168. 25 QOB125K 168. 30 QOB130K 168.
120 Vac10 k AIR 120/240 Vac10 k AIR 240 Vac 48 Vdc5 k AIR 48 Vdc5 k AIR j 10 k AIR 10 QOB110 39.80 QOB210 89. 15 QOB115 ie 39.80 QOB215 i 89. QOB215H 240. 20 QOB120 ie 39.80 QOB220 i 89. QOB220H 240. 25 QOB125 i 39.80 QOB225 i 89. QOB225H 240. 30 QOB130 i 39.80 QOB230 i 89. QOB230H 240. 35 QOB135 i 39.80 QOB235 i 89. 40 QOB140 i 39.80 QOB240 i 89. QOB240H 240. 45 QOB145 i 39.80 QOB245 i 89. 50 QOB150 i 39.80 QOB250 i 89. QOB250H 240. 60 QOB160 i 39.80 QOB260 i 89. QOB260H 240. 70 QOB170 i 78. QOB270 i 168. QOB270H 308. 80 QOB280 ij 240. QOB280H 366. 90 QOB290 ij 240. QOB290H 366. 100 QOB2100 ij 240. QOB2100H 366. 110 QOB2110 ij 501. 125 QOB2125 ij 501. 89. Molded Case Switch 60 A max 240 Vac QOB200 Molded Case Switch 100 A max 240 Vac QOB2000 234.
Table 9.20:
Ampere Rating a QOB-VH 15 20 25 30 40 50 60 70 80 90 100 110 125 150 QHB
120 Vac22,000 AIR QOB115VHie 72. QOB120VHie 72. QOB125VHi 72. QOB130VHi 72.
120/240 Vac 22,000 AIR QOB215VHi 171. QOB220VHi 171. QOB225VHi 171. QOB230VHi 171. QOB240VHi 171. QOB250VHi 171. QOB260VHi 171. QOB270VHi 273. QOB280VHi 384. QOB290VHi 384. QOB2100VHi 384. QOB2110VHi 1110. QOB2125VHi 1110. QOB2150VH k 1223.
240 Vac22,000 AIR QOB315VHi 440. QOB320VHi 440. QOB325VHi 440. QOB330VHi 440. QOB340VHi 440. QOB350VHi 440. QOB360VHi 440. QOB370VHi 560. QOB380VHi 629. QOB390VHi 629. QOB3100VHi 629. QOB3110VH k 1809. QOB3125VH k 1809. QOB3150VH k 1809. 240 Vac65,000 AIR QHB315i 596. QHB320i 596. QHB325i 596. QHB330i 596. 240 Vac10,000 AIR QOB315HID 327. QOB320HID 327. QOB325HID 327. QOB330HID 327. 2-pole3-Wire 3 Spaces120/240 Vac QOB310SWN 170. QOB315SWN 170. QOB320SWN 170. QOB325SWN 170. QOB330SWN 170. QOB340SWN 170. QOB350SWN 170.
120 Vac65,000 AIR 120 Vac/240 Vac65,000 AIR 15 QHB115i e 122. QHB215i 342. 20 QHB120i e 122. QHB220i 342. 25 QHB125i 122. QHB225i 342. 30 QHB130i 122. QHB230i 342. QOB-HIDHID circuit breakers g 120 Vac10,000 AIR 120/240 Vac10,000 AIR 15 QOB115HIDe 49.50 QOB215HID 108. 20 QOB120HID e 49.50 QOB220HID 108. 25 QOB125HID 49.50 QOB225HID 108. 30 QOB130HID 49.50 QOB230HID 108. 40 QOB140HID 49.50 QOB240HID 108. 50 QOB150HID 49.50 QOB250HID 108. QOB-SWNSwitch NeutralCommon TripNEC 514.11 1-pole2-Wire 2 Spaces 120 Vac QOB210SWN 116. QOB215SWN 116. QOB220SWN 116. QOB225SWN 116. QOB230SWN 116. QOB240SWN 116. QOB250SWN 116.
g h i j k l m
10 15 20 25 30 40 50
Table 9.21:
Breaker Type QOB 1-pole
Table 9.22:
QOB 2-pole
Catalog Number $ Price Catalog Number $ Price Combination 15 QOB115CAFI 306. QOB115VHCAFI 612. Arc-Fault 20 QOB120CAFI 306. QOB120VHCAFI 612. Interupter Note: See page 7-12 for accessories. a UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment having motor group combinations and marked for use with HACR type circuit breakers. b QO arc-fault circuit breakers provide branch feeder protection (i.e. QO115AFI) or combination protection (i.e. QO115CAFI) as required by the NEC and local code adoption, and comply with UL 1699. c 1030 A circuit breakers are suitable for use with 60 C or 75 C conductors. 3560 A circuit breakers are suitable for use with 75 C conductors.
1030 A circuit breakers are suitable for use with 60 C or 75 C conductors. 3560 A circuit breakers are suitable for use with 75 C conductors. Discount Schedule 2009 Schneider Electric All Rights Reserved
9-10
DE2A
Table 9.23:
Mains Rating 60 A 100 A 150 Ac 225 Ac
8680. 9672.
Table 9.24:
Circuit Breaker Ampere Rating
Table 9.25:
Circuit Breaker Ampere Rating
Specialty Branch Circuit Breakers (10,000 AIR) For High Intensity Discharge LightingQO-HID, QOB-HID 1530 78. 148. 376. 4050 78. 148. Switch NeutralQO-SWN, QOB-SWN 1-pole 2-pole 2-Wire 3-Wire 1550 (2 spaces) (3 spaces) 154. 220. High Magnetic Trip (For applications subject to high initial inrush) QO-HM, QOB-HM 1520 68.
Space Only All Space Only 28. 58. 58. 86. Except below QOBVH, Space 116. 174. Only (125150 A) 10,000 AIRBranch Circuit BreakersQO, QOB, QO-H, QOB-H 1560 68. 134. 260. a 352. 70 100. 208. 296. a 396. 80100 262. 380. a 458. 110125 482. 10,000 AIRCombination Arc Fault Circuit InterruptersQO-CAFI, QOB-CAFI 1520 470. 10,000 AIRQwikGardClass AQO-GFI, QOB-GFI Provided with a 5 mA setting on ground fault sensor 1530 272. 488. 920. 4050 488. 920. 60 488. 10,000 AIRQwikGardClass AQO-EPD, QOB-EPD Provided with a 30 mA setting on ground fault sensor 1530 462. 828. 1210. 4050 828. 1210. 60 828. 10,000 AIRQwikGardClass AQO-EPE, QOB-EPE Provided with a 100 mA setting on ground fault sensor 1530 1210. 4050 1210. (High Interrupting Capacity) 22,000 AIR Branch Circuit BreakersQO-VH, QOB-VH 1530 92. 212. 462. 3560 212. 462. 70 292. 556. 80100 378. 606. 110125 1022. 1746. b 150 1140. b 22,000 AIRCombination Arc Fault Circuit InterruptersQO-VHCAFI, QOB-VHCAFI 1520 940. 22,000 AIRQwik-GardClass AQO-VHGFI, QOB-VHGFI 1530 294. 42,000 AIR Branch Circuit BreakersQOH 3560 368. c 70 596. c 80100 688. c 110125 1402. c 65,000 AIR Branch Circuit BreakersQH, QHB 1530 144. 348. 596. Note: Shunt Trip, Auxiliary Switch, and Alarm Switchaccessories for circuit breakersadd $ Price from page 7-12. a UL Listed for use on 3, grounded B systems, (5,000 AIR for this application). b Bolt-On only, 2-pole requires 4 vertical spaces, 3-pole requires 6 vertical spaces. c Plug-On only.
Table 9.26:
(Refer to Cabinet Data table below for correct box size) No. of Ampacity QB QD QG a HD HG a JD JG a Poles 2 110225 A 1218. 1762. 3812. 2456. 3500. 3020. 4220. 3 110225 A 1848. 2296. 4608. 2872. 3798. 3370. 5100. Space 110225 A 826. 826. 826. 826. 826. 826. 826. a QJ, HJ, HL, JJ and JL circuit breakers are also available.
Table 9.27:
Max. No. of Branch Spaces (Does not include sub-feed circuit breaker spaces)
Main Main Main Main Main Circuit Circuit Circuit Lug Lug Breaker Breaker Breaker 30 50 62 74 86 74 42 56 68 80 86 80 not 54 56 68 80 80 available with MCB 72 62 74 86 86 84 68 80 Not Available in Type 3R, 5, 12 if subfeed breaker is over 150 A.
PE1
Discount Schedule
9-11
250 Ac JG 5040. 6020. 400 Ac 1422. 1634. LH 7708. 8834. 600 Abc 2082. 2326. Note: Equipment Ground Bar38. a QL, HJ, HL, JJ and JL circuit breakers are also available. b Copper bus standard c Prices are for 54-circuit and less interiors. Consult the Product Selector for 72- and 84-circuit interior pricing.
PANELBOARDS
Common Features
Class 1640 / Refer to Catalog 1640CT0701
www.schneider-electric.us
Table 9.37:
9
PANELBOARDS
Price per Panel one #6-2/0 Al or Cu one #6-2/0 Al or Cu $128. one 1/0-350 kcmil Al or Cu one 1/0-350 kcmil Al or Cu $128. one 1/0-750 kcmil Cu only one 1/0-750 kcmil Cu only $164.
Panelboard Actual Lug Wire Neutral Conductors Required Ampacity Range 100/125 (2) 1/0 Cu or Al (2) #4-300kcmil 225 (2) 4/0 Cu or (2) 300 kcmil Al (2) #4-300 kcmil (4) 3/0 Cu or (4) 250 kcmil Al (2) 1/0-300 kcmil or 400 A (2) 600 kcmil Cu (1) 750 kcmil (2) 750 kcmil Al Note: Neutral conductors must be of size and quantity per table above.
Table 9.29:
Max. No. of Branch Spaces 18 30 42 72 84
Table 9.38:
Table 9.39:
Hinged Door-in-Door Trim Hinged Door-in-Door Trim has piano hinge down one side. Inner door has a lock, outer door is retained with screws Hinged Door-in-Door with Outer Door Lock in place of screws
Feed-through Lugs
Table 9.30:
Mains Rating 100 A 225 A 400 A 600 A
Feed-through Lugs
Feed-Through Wire Range Per Phase $ Price 344. 344. 826. 826.
Table 9.40:
one #6-2/0 Al or Cu one #6350 kcmil Al or Cu one 1/0750 kcmil or two 1/0350 kcmil Al or Cu two 1/0750 kcmil Al or Cu
Weatherproof or Dusttight Cabinets Note: 600 A LC main circuit breaker NQ panelboards are not available with a weatherproof enclosure (Use I-Line) 400 and 600 A NQ panelboards with sub-feed circuit breakers are not available with a weatherproof enclosure (Use I-Line).
1516.
Table 9.31:
Max. No. of Branch Spaces 225 A Main Lugs 38 38 50 56
Table 9.41:
Main Lug Interiors: Aluminum Compression Lugs Copper Mechanical Lugs Copper Compression Lugs
30 42 72 84 a
Table 9.42:
Table 9.32:
Ground Bars
Ground Bars
$ Price Adder 38. 52. 86. Main Circuit Breaker Interiors:
Equipment Ground Bar Copper Ground Bar (Add to Equipment Ground Bar Price) Insulated/Isolated Ground Bar (Add to Equipment Ground Bar Price)
H Frame J Frame LA Frame LC Frame Aluminum Compression Lugs 58. 98. 148. 148. Copper Mechanical Lugs 70. 108. 148. 168. Copper Compression Lugs 70. 108. 148. 168. Note: Optional lugs are not available for Q frame main or QOB circuit breakers
Table 9.33:
Name Plates
Name Plates
$ Price Adder 78.
Table 9.43:
Standard white face/black letter laminated bakelite, 1 in. x 3.5 in., adhesive backed or screw mountable with screws in a bag assembly (Price includes engraving)
Table 9.34:
Copper Bus Bars 100 A, 225 A, 250 A 400 A 600 A
Copper Neutrals
$ Price Adder 132.
Description Surge Counter Dry Contacts Remote Monitor Note: Additional factory modifications, see 9-37.
Table 9.36:
Panelboards with 200% rated neutrals are not available with 250 A J- and K-frame main circuit breakers or integral lighting contactors 100 Aa one #6-2/0 kcmil Al or Cu per lug 225 Aa one #6-350 kcmil Al or Cu per lug #1/0-750 kcmil Al or Cu per lug or 400 Aa one two 1/0-300 kcmil per lug a Two incoming neutral lugs per panel
9-12
PE1
Discount Schedule
NF Merchandised Panelboards
Class 1670 / Refer to Catalog 1670CT0701
www.schneider-electric.us
NF Main Lug Interiors Use I-LINE Panelboards on 480 V 33W DELTA Applications
NEMA 1 Enclosure $ Total Price a Interior Only b Box 20 in. W x 5.75 in. D d $ Price Mono-Flat Front e Catalog No. $ Price Hinged Front Catalog No. NC26( )HR NC26( )HR NC32( )HR NC32( )HR NC38( )HR NC38( )HR NC44( )HR NC44( )HR NC62( )HR NC62( )HR NC50V( )HR NC50V( )HR NC56V( )HR NC56V( )HR NC74V( )HR NC74V( )HR NC86V( )HR NC86V( )HR NC50V( )HR NC56V( )HR NC74V( )HR NC86V( )HR $ Price NEMA 3R, 5, 12 Enclosure f Enclosure 20 in. W x 6.5 in. D Height (In.) Catalog No. $ Price MH26WP MH26WP MH32WP MH32WP MH38WP MH38WP MH44WP MH44WP MH62WP MH62WP MH50WP MH50WP MH56WP MH56WP MH74WP MH74WP MH86WP MH86WP Factory Assembled Only
NEMA NEMA 1 Catalog No. c $ Price Catalog No. 3R, 5, 12 (Single Phase 3-Wire: Factory Assembled Only) Three Phase 4-Wire 2056. 3638. NF418L1 1446. MH26 18 125 2448. 4030. NF418L1C 1838. MH26 2406. 3970. NF430L1 1766. MH32 30 125 2802. 4366. NF430L1C 2162. MH32 2881. 4435. NF430L2 2219. MH38 30 250 3286. 4840. NF430L2C 2624. MH38 3194. 5021. NF442L2 2418. MH44 42 250 3602. 5429. NF442L2C 2826. MH44 4800. 6485. NF466L2 3800. MH62 66g 250 5442. 7127. NF466L2C 4442. MH62 3308. 5075. NF430L4 2466. MH50 30 400 3716. 5483. NF430L4C 2874. MH50 3572. 5325. NF442L4 2673. MH56 42 400 3895. 5648. NF442L4C 2996. MH56 5285. 6957. NF466L4 4200. MH74 66 g 400 5792. 7464. NF466L4C 4707. MH74 6524. 8261. NF484L4 5346. MH86 84g 400 7169. 8906. NF484L4C 5991. MH86 30 600 3838. NF430L6C 2996. MH50 42 600 4087. NF442L6C 3188. MH56 66g 600 6094. NF466L6C 5009. MH74 84g 600 7553. NF484L6C 6375. MH86 800
Mains Rating
NC26( ) 497. NC26( ) NC32( ) 113. 527. NC32( ) NC38( ) 113. 549. NC38( ) NC44( ) 113. 663. NC44( ) NC62( ) 113. 887. NC62( ) NC50V( ) 113. 729. NC50V( ) NC56V( ) 113. 786. NC56V( ) NC74V( ) 113. 972. NC74V( ) NC86V( ) 113. 1065. NC86V( ) 113. NC50V( ) 729. 113. NC56V( ) 786. 113. NC74V( ) 972. 113. NC86V( ) 1065. FACTORY ASSEMBLED ONLY 113.
620. 657. 687. 830. 887. 912. 983. 1215. 1430. 912. 983. 1215. 1430.
26 32 38 44 62 50 56 74 86 50 56 74 86
NOTE: For footnotes, see Table 9.46 footnotes. Table 9.46: NF Main Circuit Breaker Interiors Use I-LINE Panelboards on 480 V 33W DELTA Applications
NEMA 1 Enclosure NEMA 3R, 5, 12 Enclosure f Max. No. of Main Circuit Main $ Total Price a Interior Only b One-pole Mains Box Enclosure Breaker Adapter Kit Circuit Mono-Flat Front e Hinged Front EDB 20 in. W x 5.75in. D d 20 in. W x 6.5 in. D Height Breaker Circuit Rating (In.) NEMA NEMA 1 Kit $ Price Frame Catalog No. c $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price Catalog No. $ Price Breakers 3R, 5, 12 (Single Phase 3-Wire: Factory Assembled Only) Three Phase 4-Wire 2056. 3638. NF418L1 1446. MH26 NC26( ) NC26( )HR MH26WP 15 125 113. 497. 620. 2192. 26 2448. 4030. Back-fed 1838. MH26 NC26( ) NC26( )HR MH26WP EDB, EGB NF418L1C Main or EJB 2406. 3970. Breakerh NF430L1 1766. MH32 NC32( ) NC32( )HR MH32WP 27 125 113. 527. 657. 2204. 32 2802. 4366. NF430L1C 2162. MH32 NC32( ) NC32( )HR MH32WP 2888. 4442. NF418L1 1446. MH38 NC38( ) NC38( )HR MH38WP 18 125 113. 549. 687. 2216. 38 HD/HG/ 3280. 4834. N150MH NF418L1C 1838. MH38 NC38( ) NC38( )HR MH38WP or 780. HJ/HL 3322. 5149. N100MFIi NF430L1 1766. MH44 NC44( ) NC44( )HR MH44WP or FI 30 125 113. 663. 830. 2603. 44 3718. 5545. NF430L1C 2162. MH44 NC44( ) NC44( )HR MH44WP 3841. 5608. NF430L2 2219. MH50 NC50( ) NC50( )HR MH50WP 30 250 780. 113. 729. 912. 2609. 50 4246. 6013. NF430L2C 2624. MH50 NC50( ) NC50( )HR MH50WP JD/JG/ 4097. 5850. N250MJ NF442L2 2418. MH56 NC56( ) NC56( )HR MH56WP 42 250 or 780. JJ/JL 113. 786. 983. 2652. 56 4505. 6258. N250MKCi NF442L2C 2826. MH56 NC56( ) NC56( )HR MH56WP or KI 5665. 7337. NF466L2 3800. MH74 NC74( ) NC74( )HR MH74WP 66g 250 780. 113. 972. 1215. 2757. 74 6307. 7979. NF466L2C 4442. MH74 NC74( ) NC74( )HR MH74WP 4246. 5931. NF430L4 2466. MH62 NC62V( ) NC62V( )HR MH62WP 30 400 N400Mi 780. LA/LH 113. 887. 1109. 2685. 62 4654. 6339. NF430L4C 2874. MH62 NC62V( ) NC62V( )HR MH62WP (LC and LI 4514. 6195. NF442L4 2673. MH68 NC68V( ) NC68V( )HR MH68WP 42 400 N400Mi 780. factory 113. 948. 1185. 2742. 68 4837. 6518. 2996. MH68 NC68V( ) NC68V( )HR MH68WP assembled NF442L4C 6158. 7895. NF466L4 4200. MH86 NC86V( ) NC86V( )HR MH86WP only) 66 g 400 N400Mi 780. 113. 1065. 1430. 2915. 86 6665. 8402. NF466L4C 4707. MH86 NC86V( ) NC86V( )HR MH86WP a b c d e f g h i Total Price includes: interior, front, main circuit breaker adapter kit, and enclosure. Order branch circuit breakers separately. C suffix indicates copper bussing. Embossed mounting holes add a .25 inch standoff to back of MH box. Add F for flush, S for surface. Enclosure includes trim kit. Use only if the Local Jurisdiction where this panelboard interior is being applied has adopted the 2008 NEC, which allows single panelboard interiors greater than 42 circuits. Back-fed EDB 125 A 3 pole main circuit breaker must be ordered separately and field installed. Maximum breaker rating opposite is 20A. Select the appropriate main circuit breaker from pages starting on 7-21 and add the circuit breaker Price to the total Price of the panelboard.
Table 9.47:
Mains Rating 250 A 250 A 400 A 400 A Max. Breaker Spaces 42 42 42 42
NF Merchandised Interiors with TVSS Use I-LINE Panelboards on 480 V 33W DELTA Applications
TVSS Ratings Voltage 480Y/277 3P4W Surge Rating 120 160 120 160 Interior Catalog No. NF442L2TVS412 NF442L2TVS412C NF442L2TVS416 NF442L2TVS416C NF442L4TVS412 NF442L4TVS412C NF442L4TVS416 NF442L4TVS416C $ Price 30141. 30504. 34256. 34664. 30396. 30719. 34511. 34833. Components for adding Vertical Main Circuit Breaker MCB Kit Main Circuit Breaker Frame Select the appropriate MCB and price Catalog No. $ Price from the tables starting on page 7-22 N250MJ or N250MKC N400M N400M 780. 780. 780. 780. JD/G/J/L or KI JD/G/J/L or KI LAL/LHL (LC and LI F/A only)
480Y/277 3P4W
Table 9.48:
Mains Rating 250A 400 A Max. Breaker Spaces 42 42
PE1A
9-13
PANELBOARDS
NF Merchandised Panelboards
Table 9.49:
Mains Ampacity
Accessories
Class 1670 / Refer to Catalog 1670CT0701
www.schneider-electric.us
NF Merchandised Neutrals
200% Neutral Kit Copper 100% Neutral Kit $ Price 405. 1148. Box Add No Adder No Adder Schedule PE-1A PE-1A
9
PANELBOARDS
$ Price Box Add Schedule Catalog No. 125 1029. NFN1CU No Adder PE-1A 250 1277. NFN2CU 400 1914. No Adder PE-1A NFN6CU 600 Factory Assembled Only NFN6CUa a Not to be used with SFL, FTL, or SFB. These combinations are factory assembled only.
Table 9.50:
Mains Ampacity
$ Price Schedule Catalog No. 167. 213. 356. PE-1A PE-1A PE-1A NF125FTL NF250FTL NF400FTL e
PE1A
FACTORY ASSEMBLED ONLY 800 Note: NF250SFBH and NF600SFBH are for use with HDL, HGL, HJL, and HLL circuit breakers. NF600SFBJ are for use with JDL, JGL, JJL, and JLL circuit breakers. a Available factory assembled only on non-linear panelboards. b Select box from the Box Selection Table. c Order appropriate circuit breaker. d Use copper wire only. e Available factory assembled only.
Table 9.51:
Feature No. of Ckts Ampacity 100/125 250 400 600 800 a
Table 9.52:
Feature No. of Ckts Ampacity 100/125 250 400a 600 a
Table 9.53:
Ampacity 125 250 400 600 800 a b c
Use copper wire only. Use of this kit requires an additional 6 in. added to box height. Use of this kit to terminate larger than standard wire size requires an additional 6 in. added to box height.
Table 9.54:
NF Accessories
Catalog No. PK27GTA PK27GTACU PK23GTAL PKGTAB NF102OE NF204OE NF102S NF204S NF6RDE NF12RDE NF18RDE $ Price Schedule 33.80 DE-3A 84.00 PE-1A 40.70 DE-3A 43.80 Description Filler plate (15 per package) EXB Fixed padlock attachment, Lock ON/OFF for ED, EG & EJ Circuit Breakers 1, 2, or 3 poles EXB Fixed padlock attachment, Lock OFF only for ED, EG & EJ Circuit Breakers 1, 2, or 3 poles Oversized Lugs for Neutral or Ground Bar #10 to #2 Al or #14 to #4 Cu #4 to #1/0 Al or Cu #1 to #4/0 Al or Cu Drip Hood for 20 in. wide enclosures Catalog No. $ Price Schedule NFFP15 113.00a PE-1A EDPA EDPAF 26.00 30.00 DE-2 DE-2
Description Aluminum Equipment Ground Bar Copper Equipment Ground Bar Large Aluminum Lug for Equipment Ground Bar Equipment Ground Bar Insulator Kit Circuit I.D. number strips 1102 odd/even (left side numbered 1,3,5 ...101) 103204 odd/even (left side numbered 103,105,107 ... 203) 1102 sequential (left side numbered 1,2,3 ... 102) 103204 sequential (left side numbered 103,104,105 ... 204) Rail and Deadfront Extensions 6 in. Extension 12 in. Extension 18 in. Extension a
7.90
PE-1A
DE-3A PE-1A
PE-1A
Filler plates are $7.50 each and must be ordered in packages of 15.
9-14
PE1A
DE3A
DE1
Discount Schedule
Circuit Breakers
www.schneider-electric.us
Table 9.55:
Ampere Rating
ED, EG, EJ (480Y/277 Vac) Hold Trip 1-pole, 277 Vac 15 20 270 875 25 30 35 40 45 630 1800 50 60 70 2-pole, 480Y/277 Vac c 15 20 270 875 25
150.
255.
408.
150. 302.
225. 507.
408. 812.
AL100FD #142/0 Al or Cu
536.
776.
1241.
30 35 40 AL100FD 536. 776. 1241. 45 630 1800 #142/0 50 Al or Cu 60 70 756. 1280. 2048. 80 756. 1280. 2135. 90 AL100FD 100 1000 2300 #142/0 Al or Cu 110 1946. 2586. 3879. 125 3-pole, 480Y/277 Vac 15 EDB34015b EGB34015b EJB34015b AL30FD 20 EDB34020b EGB34020b EJB34020b 270 875 669. 1131. 1358. #14#6 25 EDB34025b EGB34025b EJB34025b Al or Cu 30 EDB34030b EGB34030b EJB34030b 35 EDB34035b EGB34035b EJB34035b 40 EDB34040b EGB34040b EJB34040b AL100FD 45 EDB34045b 669. EGB34045b 1131. EJB34045b 1358. 630 1800 #142/0 50 EDB34050b EGB34050b EJB34050b Al or Cu 60 EDB34060 EGB34060 EJB34060 70 EDB34070 911. EGB34070 1292. EJB34070 2562. 80 EDB34080 EGB34080 EJB34080 911. 1292. 2562. 90 EDB34090 EGB34090 EJB34090 AL100FD 100 1000 2300 EDB34100 EGB34100 EJB34100 #142/0 Al or Cu 110 EDB34110 EGB34110 EJB34110 2421. 3216. 4826. 125 EDB34125 EGB34125 EJB34125 EPDs (Equipment Protection Devices), 1-pole, 277 Vac, Thermal-magnetic with 30 mA ground-fault protectiond 15 EDB14015EPDab EGB14015EPDab EJB14015EPDab 20 270 875 EDB14020EPDab 1151. EGB14020EPDab 1256. EJB14020EPDab 1409. #14#6 Cu 30 EDB14030EPDb EGB14030EPDb EJB14030EPDb or #12#4 Al 40 EDB14040EPDb EGB14040EPDb EJB14040EPDb 630 1800 1151. 1256. 1409. 50 EDB14050EPDb EGB14050EPDb EJB14050EPDb Note: All EDB, EGB, and EJB circuit breakers are UL Listed as HACR Type. For 50 oC calibration, use a CA suffix. NF branch circuit breakers are fungus proof as standard. a UL Listed as SWD (Switching duty rated). b UL Listed as HID (High Intensity Discharge rated). c UL Listed for use on 240 V Corner-grounded Delta Systems (Grounded B Phase). See: 2700DB0202. d All EPDs occupy two spaces, with or without Alarm Switch option. For alarm switch add 158 list Price and the suffix BA.
AL30FD #14#6 Al or Cu
Table 9.56:
Monitors circuit breaker contact status and provides Used with control circuits and is actuated a remote signal indicating the circuit breaker only when the circuit breaker has tripped. contacts are OPEN or CLOSED. APPLICATION APPLICATION Max Load = Max Load = 7 A @ 120 Vac 50/60 Hz 10 A @ 120 Vac 50/60 Hz Terminals for #14 AWG Cu wire. Terminals for #14 AWG Cu wire
Shunt Trip Trips the circuit breaker from a remote location by means of a coil energized from a separate circuit. A 120 V shunt trip will operate at 55% or more of rated voltage. APPLICATION For use with momentary or maintained push button. 120 Vac 50/60 Hz Terminals for #14 AWG Cu wire.
Table 9.57:
Factory Installed Electrical Accessory Packages for ED, EG, EJ Circuit Breakers
$ Price 312. 755. 1067. 237.
Table 9.59:
Handle Accessories
$ Price 39.00 45.00 25.50 16.80 17.85
Accessory Package Suffix Auxiliary Switch/Alarm Switch Packageab AABA Shunt Trip Packageab SA Auxiliary Switch/Alarm AABASA Alarm Switch (N.O.) Package for EPDs only BA a Accessory package takes an additional pole space. b Not available for EPD.
Table 9.58:
Circuit Breaker Type No. of Poles Catalog No. EXB Fixed Padlock Attachment, Lock ON/OFF ED, EG, EJ 1, 2, or 3 EDPA EXB Fixed padlock attachment, Lock OFF only ED, EG, EJ 1, 2, or 3 EDPAF EXB Removable padlock attachment, Lock OFF only ED, EG, EJ 1, 2, or 3 HPAFD EXB Handle Ties Ties 2 1P EGB2HT ED, EG, EJ Ties 3 1P EGB3HT
Table 9.60:
120 V 240 V 480Y/277 V
Table 9.61:
EDB, EGB, EJB 2-pole 15125 Amperes
Standard EDB, EGB, EJB
Mechanical Lug Kit Information (Al lugs for use with Al or Cu wire)
Circuit Breaker Application Ampere Rating Optional 1530 35125 EDB, EGB, EJB Ampere Rating 1530a Number of Wires Per Lug and Wire Range one #12#6 AWG Al or one #14#6 AWG Cu one #122/0 AWG Al or one #142/0 AWG Cu one #141/0 AWG Cu Catalog Number AL30FD AL100FD CU100FD Lugs Per Kit 3 3 3 41.30 $ price Per Kit
EDB, EGB, EJB 15125 a Factory installed only. Use suffix LH Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .pages starting on 7-55 2009 Schneider Electric All Rights Reserved
DE2
Discount Schedule
9-15
PANELBOARDS
AL30FD #14#6 Al or Cu
9
PANELBOARDS
Table 9.62:
Max. No. of Poles Mains Rating
Table 9.64:
Max. No. Mains of Poles Rating
1 Phase 3-Wire Main Lugs Only 30 225 1669. NQ830L2C Main Circuit Breaker2-pole 20 100 1818. NQ820B1C 3 Phase 4-Wire Main Lugs Only 30 100 1608. NQ8430L1C 42 225 1938. NQ8442L2C Main Circuit Breaker3-pole 30 100 2363. NQ8430B1C 42 225 4961. NQ8442B2C a 60 A Maximum BranchCopper Bus Standard.
Main Lugs Only3 Phase 4-Wire 30 125 2410. 42 225 3281. Main Circuit Breaker3-pole 30 42 100 225 3767. 6660.
Table 9.63:
Table 9.65:
42
MPX81542
479.
42
MPX81542
479.
Cable troughs are standard with a trough barrier. Box width = 8.625 in., width at front, including flange, is 9.625 in..
20"
15"
Cable Trough
858"
9-16
PE1A
Discount Schedule
100 A 225 A
Note: Copper bus standard. Equipment Ground Bar $ Price adder$38.00. Copper Equipment Ground Bar (Add to Equipment Ground Bar $ Price) $ Price adder$52.00.
Table 9.67:
$ Price
$ Price
Space Only All Space Only Except Below 28. 58. 10,000 AIRBranch Circuit BreakersQOB, QOB-H 1560 68. 134. 10,000 AIRQWIK-GUARDClass AQOB-GFI 1530 272. 488. 4060 488. Specialty Branch Circuit Breakers (10,000 AIR) For High Intensity Discharge LightingQO-HID, QOB-HID 1530 78. 148. 4050 78. 148. High Magnetic Trip (For applications subject to high initial inrush)QO-HM, QOB-HN 1520 68. Provides 30 mA Equipment ProtectionQO-EPD, QOB-EPD 1530 462. 828. (High Interrupting Capacity) 22,000 AIR Branch Circuit BreakersQO-VH, QOB-VH 1530 92. 212. 3560 212. 22,000 AIRQWIK-GUARDClass AQO-VHGFI, QOB-VHGFI 1530 294.
376.
462. 462.
2-Pole
3-Pole
FA 2184. FH 100 A 1074. 2842. HD HG 125 A 3222. 150 A HD 3222. HG 1272. 225 A JD 4784. JG Note: Copper busstandard. Copper Neutral $ Price adder$132.00. Equipment Ground Bar $ Price adder$38.00. Copper Equipment Ground Bar (Add to Equipment Ground Bar $ Price) $ Price adder$52.00.
Table 9.69:
Circuit Breaker Ampere Rating 1560 A Space Only
Table 9.70:
Circuit Breaker Ampere Rating 1560 A
PE-1
Discount Schedule
9-17
PANELBOARDS
NF Panelboards a
9
Table 9.71:
Mains Rating Main Lugs 2-pole 100 A 100 A 125 A 150 A 225 A d 250 A d 400 A d 600 A de 800 A e a b c d e 846. 1002 1326. 2366. 3550. 3-pole 972. 1152. 1524. 2622. 3900.
PANELBOARDS
HL and JL frame circuit breakers are also available as main circuit breakers. Contact the Square D/Schneider Electric local Field Sales Office for Micrologic trip main circuit breaker pricing. Back-fed main circuit breaker. Prices are for 54 ckts and less. Consult the Product Selector for 66 and 84 ckt interior pricing. Copper bus only.
Table 9.72:
Circuit Breaker Ampere Rating
1-pole 2-pole $ Price $ Price 324. 1560 A 192. 442. 748. 746. 70 A 342. 872. 1046. 578. 1474. 80100 A 872. 1046. 1474. 110125 A 2210. 2724. 4114. Space Only 42. 84. 126. 42. 84. Note: All ED, EG and EJ branch circuit breakers are UL Listed as HACR type.
Table 9.73:
Circuit Breaker Ampere Rating
1560 A a b
All 1-pole EDB-EPD branches use 2 poles of mounting space. For bell alarm in EDB-EPD branch breaker, add 158. to branch breaker price.
Table 9.74:
No. of Poles 2 3 a
Table 9.75:
Max. No. of Branch Spaces (Does not include sub-feed circuit breaker spaces) 30 42 54 66 84 a b c d
600 A main lug panelboards require a 8.75 in. deep box. 600 A main circuit breaker panelboards require an 8 in. deep, 26 in. wide box. 800 A main lug panelboards require an 8.75 in. deep, 26 in. wide box. Dimensions also for 400 A LC/LI main circuit breaker panels.
9-18
PE1
Discount Schedule
Common Features
Class 1670 / Refer to Catalog 1670CT9601 Table 9.84: 200% Rated Neutrals
Table 9.76:
An additional mains end termination point that can be used to feed out to another panelboard or device from the incoming service lines.
Table 9.85:
Panelboard Ampacity 125 250 400 A 600 800 A a 74 80 86
Table 9.77:
Max. No. of Branch Spaces 12 18 30 42 54 a
Table 9.86:
Metal Directory Frame Not available with LC/LI main circuit breaker (Replaces standard plastic stick-on directory pouch)
Table 9.78:
Table 9.87:
A second set of lugs assembled at the opposite end from the mains of the panelboard. Often used to connect another panelboard or device to the incoming lines. Available on main lugs and main circuit breaker panelboards.
Mains Rating 125 A 250 A 400 A 600 A Feed-through Wire Range Wire Bending Space per NEC Table 373-6 one #62/0 kcmil Al or Cu one #6350 kcmil Al or Cu one 1/0750 kcmil or two 1/0350 kcmil Al or Cu two 1/0600 kcmil Al or Cu $ Price 344. 344. 826. 826.
Hinged Door-in-Door Trim has piano hinge down one side. Inner door has a lock, outer door is retained with screws Hinged Door-in-Door with Outer Door Lock in place of screws
Table 9.88:
Weatherproof or Dusttight Cabinets Type 3R, 5, 12 (Not available with panelboards having LC/LE/LI/LX/LXI main circuit breakers)
Table 9.79:
Max. No. of Branch Spaces
Table 9.89:
125 A
Main Lug Interiors: Aluminum Compression Lugs Copper Mechanical Lugs Copper Compression Lugs
12 18 30 42 54 a b c
Main Main Breaker Main Main Main Main Main Main (Back-fed Lugs Breaker Lugs Breaker Lugs Breaker Lugs a only) 32 44 38 32 44 44 38 50 50 62 56 68 56 50 56 68 62 74 62 62 74 68 80 68
Table 9.90:
Main Circuit Breaker Interiors: Aluminum Compression Lugs Copper Mechanical Lugs Copper Compression Lugs
600 A main lug panelboards require a 26 in. wide box. 600 A main circuit breaker panelboards require an 8 in. deep, 26 in. wide box. 800 A main lug panelboards require an 8.75 in. deep, 26 in. wide box.
Table 9.80:
Ground Bars
Ground Bars
$ Price Adder Equipment Ground Bar 38. Copper Ground Bar (Add to Equipment Ground Bar Price) 52. Insulated/Isolated Ground Bar (Add to Equipment Ground Bar Price) 86.
Table 9.91:
Surge Current Rating kA 100 120 160 200 240 a
Table 9.81:
Name Plates
$ Price Adder 78.
Name Plates Standard white face/black letter laminated bakelite, 1 in. x 3.5 in., adhesive backed or screw mountable with screws in a bag assembly (Price includes engraving)
Panelboard box height with TVSS unitContact the Square D/Schneider Electric local Field Sales Office.
Table 9.82:
100 A, 250 A 400 A 600 A, 800 A
Table 9.92:
Table 9.83:
100600 A 800 A
Copper Neutral
$ Price Adder 132. 176.
Copper Neutral
PE1
Discount Schedule
9-19
Note: Neutral conductors must be of size and quantity per table above.
PANELBOARDS
Panelboards with 200% rated neutrals are available with Add Per Panel sub-feed lugs, feed-through lugs, and main circuit breakers $ Price 250 A 769. 400 A 950. 600 A 1262. 800 A 1894.
9
PANELBOARDS
3. 4. 5. 6.
Table 9.93:
600 Vac, 33W, 400 A, MLO, 14k AIR, Type 1 enclosure, 4 piece surface trim without door. Description 400 Amp MLO Interior 4 Piece Surface Trim Without Door Type 1 Enclosure (8) 60/3 one 100/2 one 4.5 in. Blanks one 1.5 in. Blank
Table 9.94:
600 Vac, 33W, 400 A, MLO, 14k AIR, Type 1 enclosure, 4 piece surface trim without door. Description 400 A MLO Base Price (8) 60/3 one 100/2 (3) 250/3
Table 9.95:
600 Vac, 33W, 400 A, Fusible 10k AIR, Type 1 Enclosure Branches 400 A MLO Base Price (4) 60/3 one 100/3 one 30/3
9-20
Discount Schedule
TYPE HCN
225 A max. (240 V max.) branch circuit breaker QB, QD, QG, QJ 150 A max. branch circuit breaker FA, FH, FY, HD, HG, HJ, HL l
Table 9.96:
Mains Ampere Rating Total Circuit Breaker Mounting Space (In.)
(100 A and 225 A interiors include solid neutral, all others without solid neutral. Order solid neutral from 9-23) Complete Front a Box c Surface $ Price Interior Assembly (4 Piece Trim) NEMA (Less Branch 4 Piece Trim (Less Branch Trim With Door Type 1 3R/5/12 d Circuit Breakers) Without Door b Circuit (Includes Front) Breakers) Type Type 1 3R/ Catalog Catalog Catalog Catalog Catalog $ Price $ Price $ Price Number $ Price Number $ Price $ Price 5/12 Number Number Number $ Price HCN Main Lugs Only 3-poleSuitable for use as service equipment when provided with a main circuit breaker. i 225 2171. 4004. HCN14522N 1593. HC2652B HC2652WP 27 400 2195. 4028. HCN14524 1617. HCN52T( ) 335. HCN52T( )D 411. 243. 2411. 600 2392. 4225. HCN14526 1814. 225 2674. 4402. HCN23652N 1991. HC2665B HC2665WP 45 400 2702. 4430. HCN23654 2019. HCN65T( ) 440. HCN65T( )D 530. 243. 2411. 600 2960. 4688. HCN23656 2277. 225 3135. 4709. HCN32742N 2298. HC2674B HC2674WP 63 400 3156. 4730. HCN32744 2319. HCN74T( ) 594. HCN74T( )D 717. 243. 2411. 600 3396. 4970. HCN32746 2559. 225 3548. 6233. HCN41832N 2552. HC2683B HC2683WP 81 400 3564. 6249. HCN41834 2568. HCN83T( ) 753. HCN83T( )D 890. 243. 3681. 600 3824. 6509. HCN41836 2828. 225 4175. 6767. HCN50922N 3086. HC2692B HC2692WP 99 400 4341. 6933. HCN50924 3252. HCN92T( ) 846. HCN92T( )D 1001. 243. 3681. 600 4434. 7026. HCN50926 3345. HCN Main Circuit Breaker e k Includes 3-pole, vertically mounted main circuit breakerSuitable for use as service equipment 27 400 6649. 8377. HCN14654M 5966. HC2665B 100 3860. 5588. HCN18651MN 3177. HCN65T( ) 440. HCN65T( )D 530. 243. HC2665WP 2411. 36 225 5303. 7031. HCN18652MN 4620. 45 400 7287. 8861. HCN23744M 6450. 100 4323. 5897. HCN27741MN 3486. HCN74T( ) 594. HCN74T( )D 717. HC2674B 243. HC2674WP 2411. 54 225 5759. 7333. HCN27742MN 4922. 225 6068. 8753. HCN32832MN 5072. HCN83T( )D 890. HC2683B 243. HC2683WP 3681. 63 HCN83T( ) 753. 400 7836. 10521. HCN32834M 6840. 81 400 8154. 10746. HCN41924M 7065. HCN92T( ) 846. HCN92T( )D 1001. HC2692B 243. HC2692WP 3681. 90 225 6590. 9182. HCN45922M 5501. HCM Main Lugs Only 3-poleSuitable for use as service equipment when provided with a main circuit breaker. i 225 2279. 4566. HCM14482N 1644. HC3248B HC3248WP 400 2404. 4691. HCM14484 1769. 27 HCM48T( ) 392. HCM48T( )D 483. 243. 2922. 600 3175. 5462. HCM14486 2540. 800 3709. 5996. HCM14488 3074. 225 2795. 5717. HCM23642N 2036. HC3264B HC3264WP 400 2891. 5813. HCM23644 2132. 45 HCM64T( ) 516. HCM64T( )D 633. 243. 3681. 600 3530. 6452. HCM23646 2771. 800 4041. 6963. HCM23648 3282. 225 3263. 6002. HCM32732N 2321. HC3273B HC3273WP 400 3350. 6089. HCM32734 2408. 63 HCM73T( ) 699. HCM73T( )D 864. 243. 3681. 600 3921. 6660. HCM32736 2979. 800 4644. 7383. HCM32738 3702. 225 4205. 7918. HCM50912N 2966. HC3291B HC3291WP 400 4281. 7994. HCM50914 3042. 99 HCM91T( ) 996. HCM91T( )D 1217. 243. 4952. 600 4586. 8299. HCM50916 3347. 800 5321. 9034. HCM50918 4082. HCM Main Circuit Breaker e k Includes 3-pole, vertically mounted main circuit breakerSuitable for use as service equipment. 27 400 7563. 10485. HCM14644M 6804. HCM64T( ) 516. HCM64T( )D 633. HC3264B 243. HC3264WP 3681. 225 5582. 8504. HCM18642MN 4823. 36 600 11648. 10706. HCM18736MP 10706. HC3273DB9 m HCM73T( ) 699. HCM73T( )D 864. 243. Use HCP 800 14549. 13607. HCM18738MP 13607. 45 400 8007. 10746. HCM23734M 7065. HCM73T( ) 699. HCM73T( )D 864. HC3273B 243. HC3273WP 3681. 54 225 5969. 8708. HCM27732MN 5027. 600 12377. 11138. HCM36916MP 11138. HC3291DB9 m 72 HCM91T( ) 996. HCM91T( )D 1217. 243. Use HCP 800 15431. 14192. HCM36918MP 14192. 81 400 9315. 13028. HCM41914M 8076. HCM91T( ) 996. HCM91T( )D 1217. HC3291B 243. HC3291WP 4952. HCP-SU g Universal Single Row Main Lugs or Main Circuit Breaker k 3-poleSuitable for use as service equipment when provided with a main circuit breaker. i 54 800 5858. 9466. HCP54868SU 4514. HC2686T( )4P 1101. HC2686T( )HRf 1658. HC2686DB 243. HC2886WP 4952. a b c d e f g h i Box Height (In.) 52 65 74 83 92 65 74 83 92 48 64 73 91 64 73 91 86
S N
TYPE HCM
250 A max. branch circuit breaker FA, FH, FY, FI, QB, QD, QG, QJ, HD, HG, HJ, HL, JD, JG, JJ, JL
QB, QD QG, QJ FA, FH FI, FY HD, HG HJ, HL JD, JG JJ, JL Total Breaker Mounting Space Each Side
12
S N
TYPE HCP-SUh
800 A max. main circuit breaker 600 A max. branch circuit breaker DG, DJ, DL, FY, FA, FH, FI, KI, LA, LH, LC, LX, LI, LXI, LE, MG, MJ, PG, PJ, PL, PGC, PJC, PLCj, QB, QD, QG, QJ, HD, HG, HJ, HL, JD, JG, JJ, JL
FY, FA, FH, FI HD, HG, HJ, HL QB, QD, QG, QJ JD, JG, JJ, JL, KI DG, DJ, DL, LA, LH LC, LX, LE, LXI, LI MG, MJ, PG, PJ, PL PGC, PJC, PLC
S N
j k l m
Add F for Flush or S for Surface. Add-on door kit available from Peru. Example: For HCM48TS surface trim kit, order HCM48DS door kit. For Type 1 applications, order interior, front, and box. For Type 3R/5/12 applications, order interior and box only. The front is included with the box. Remove drain screws for Type 3R rating. Bottom feed standard, for top feed main circuit breaker specify at time of order. Hinged trim with door. For main lugs panel, order sub-feed lug kit and back-feed as main lugs. For main circuit breaker panel, order plug-on I-LINE type PG, PJ, PL, MG or MJ circuit breakers from 9-28 through 9-30 and backfeed as the main breaker (order solid neutral from 9-22). Suitable for use as service equipment if equipped with an integral main circuit breaker or when not more than six main disconnecting means are provided and the panelboard is not used as a lighting and appliance branch circuit panelboard. PG, PJ, PL circuit breakers are available with both thermal-magnetic equivalent and Micrologic trip. The Micrologic circuit breakers are available 80% and 100% rated. C suffix denotes a 100% rating. Circuit breaker interrupt ratings, starting on page 7-2. I-Line Surgelogic TVSS not available. DB9 box is 9.5 inches deep.
PE1A
Discount Schedule
9-21
PANELBOARDS
Table 9.97:
(1200 A Interiors Include solid neutral, all others without solid neutral. Order solid neutral from 9-23.)
Max. No. of LC, MJ, PL, RL Circuit Breakers Complete Surface $ Price (4 Piece Trim) (Less Branch Breakers) Type 1 Front a Interior Assembly (Less Branch Circuit Breakers) 4 Piece Trim Without Door b Catalog Number $ Price Box c Trim With Door Catalog Number Catalog Number Box Height (In.)
9
PANELBOARDS
Catalog Number
$ Price
$ Price
$ Price
S N
HCP Main Lugs Only3-pole Suitable for use as service equipment when provided with a main circuit breaker. d 400 2751. HCP14504 1902. 600 3513. HCP14506 2664. 27 1PL HCW50T( ) 606. HCW50T( )D 743. HC4250DB 243. 800 4521. HCP14508 3672. 1200 6365. HCP145012N 5516. 400 3212. HCP23594 2298. 600 3860. HCP23596 2946. 45 2PL HCW59T( ) 671. HCW59T( )D 827. HC4259DB 243. 800 4874. HCP23598 3960. 1200 7133. HCP235912N 6219. 400 3795. HCP32684 2706. 600 4476. HCP32686 3387. 63 3PL HCW68T( ) 846. HCW68T( )D 1052. HC4268DB 243. 800 5309. HCP32688 4220. 1200 7763. HCP326812N 6674. 400 4716. HCP50864 3372. 600 5208. HCP50866 3864. 99 5PL HCW86T( ) 1101. HCW86T( )D 1344. HC4286DB 243. 800 6194. HCP50868 4850. 1200 8529. HCP508612N 7185. HCP Main Circuit BreakereIncludes 3-pole Vertically mounted main circuit breakerSuitable for use as service equipment. 600 12179. HCP18686M 11090. 36 2LC HCW68T( ) 846. HCW68T( )D 1052. HC4268DB 243. 800 15399. HCP18688M 14310. 600 12987. HCP36866M 11643. 72 4LC HCW86T( ) 1101. HCW86T( )D 1344. HC4286DB 243. 800 16296. HCP36868M 14952. HCR-U Universal Main Lugs or Main Circuit Breakere3-pole Suitable for use as service equipment when provided with a main circuit breaker. For MAIN LUGS panel, order sub-feed lug kit catalog number S33930 and back feed as main lugs. For MAIN CIRCUIT BREAKER panel, order plug-on I-LINE type PG, PJ, PL, RGC, RJC or RLCf circuit breakers from pages 9-27 through 9-29, and back feed as the main circuit breaker. (Order solid neutral separately) 108g a b c d e f g h 1200 6PL or 3RLC 12557. HCR548612U 11213. HCR86T( )h 1101. HCR86T( )D 1344. HC4486DB 243.
50
59
68
86
68 86
86
Add F for Flush or S for Surface. Add-on door kit available. Example: For HCW50TS trim kit, order HCW50D door kit. See 9-23 for 42 in. wide weatherproof enclosures. Suitable for use as service equipment if equipped with an integral main circuit breaker or when not more than six main disconnecting means are provided and the panelboard is not used as a lighting and appliance branch circuit panelboard. Circuit breaker interrupt ratings, starting on page 7-2. When RL main circuit breakers with equipment ground fault are applied on a 34W system, order solid neutral catalog number HCR12SNCT. The HCR12SNCT includes a neutral current transformer. 15 in. of mounting space is taken up by the back fed main lug kit or RG, RJ, RL main circuit breaker, leaving 93 in. of branch circuit breaker mounting space. Add-on door kit available. Example: For HCR86TS trim kit, order HCW86D door kit.
FA, FH, FY HD, HG HJ, HL QB, QD QG, QJ FI, KI, JD JG, JJ, JL DG, DJ, DL, LA, LH LC, LI, LX LXI, LE MG, MJ
QB, QD QG, QJ FA, FH, FY HD, HG HJ, HL FI, KI, JD JG, JJ, JL
Table 9.98:
Type of Circuit Breaker FY FA, FH FA, FH FA, FH, FI, SL-100 HD, HG HD, HG, HJ, HL QB, QD, QG, QJ
S/N
2, 3
Table 9.99:
Table 9.100:
Merchandised copper interiors are not available in all ampacities. Example: Application calls for a HCN 225A copper bus interior, order a HCN 600A interior See table 9.100
9-22
PE1A
Discount Schedule
Accessories
Class 690, 2110 / Refer to Catalog 2110CT9701 Table 9.101: I-Line Merchandised Panelboard Accessories
Description Blank Fillers1.5 in. (3 per pkg.) Blank Fillers4.5 in. (5 per pkg.) Solid Neutral Assemblies 225 A 400 A 600 A Catalog No. HNM1BL HNM4BL HC2SN HC4SN a, HCW4SN b HC6SN a, HCW6SN b HC8SN a, HCW8SN b HCPSU8SNc HCPSU8SNCTc HCW12SNb HCWM12SNd HCR12SNCTd PK27GTA PK32DGTA HLW1BL HLW4BL $ Price 14.30 25.20 252.00 333.00 464.00 717.00 1151.00 1269.00 843.00 1151.00 1269.00 33.80 104.00 14.30 25.20
Blank Fillers
Solid Neutral
800 A 1200 A 1200 A, for use with HCR-U universal panel only 1200 A, Including neutral CT for 34W systems Equipment Ground Bar KitsHCN HCM, HCP , HCR-U Blank Extensions(For replacement purposes only in 1.5 in. (3 per pkg.) Type HCP, HCR-U panelboards) 4.5 in. (5 per pkg.) a b c d
Blank Extensions
Used on Type HCN, HCM. Used on 400 A, 600 A, 800 A, 1200 A HCP (main lugs), and 600 A, 800 A (main circuit breaker). Used on Type HCP-SU. Used on Type HCR-U.
Table 9.102:
For use with MLO panel, order VCEL lugs seperately. Not for use with P- or R-frame circuit breakers or sub-feed kits S33930 or S33931.
Table 9.103:
Table 9.104:
Box Extensions
Interior Type HCP-SU HCN HCM HCP HCR-U HCR-U Extension 9 in. 9 in. 9 in. 12 in. 6 in. 12 in. $ Price 552. 552. 552. 641. 552. 641.
Box Extension
Table 9.105:
Ampere Rating 100 250 250 400 800 1200 1200 a b Height
IN (mm) 4.5 114 SL100 4.5 114 SL250 4.5 114 SL250 6 152 SL400 b 9 9 15 229 SL800
Plug-on in same manner as a branch circuit breaker SL400 cannot be used in HCM panelboards due to inadequate wire bending space.
Table 9.106:
Catalog No. (Prefix) SL100 SL250 SL400 SL800 S33931 S33930 a
Unless otherwise specified, wire sizes apply to both aluminum and copper conductors.
For Surgelogic I-Line plug-on TVSS unit pricing and information, refer to Section 6 pages 3-4. For Field Installable I-Line Door Kits see the Supplemental & Obsolescence Digest section 4.
2009 Schneider Electric All Rights Reserved
PE1A
Discount Schedule
9-23
PANELBOARDS
Table 9.107:
QO Distribution Panel240 Vac Max. Only Mounts in Type HCN, HCM, HCP, HCP-SU, or HCR-U I-Line panelboards, 30 A max. branch circuit breaker. Order QO plug-on circuit breakers from page 9-33.
Mounting Height IN 4.5 4.5 4.5 4.5 mm 114 114 114 114 2-pole Catalog Number HQO206AB HQO206BC HQO206AC 3-pole Catalog Number HQO306 $ Price a 369. 369. 369. 369.
Table 9.111:
Ampere Rating
9
PANELBOARDS
Hold 2-pole, 240 Vac a 15 20 275 25 30 35 40 400 45 50 60 800 70 80 90 900 100 3-pole, 240 Vac 15 20 275 25 30 35 40 400 45 50 60 800 70 80 90 900 100 a
600
850
1450 1700
600
572.
AL50FA #14#4 AWG Cu or #12#4 AWG Al AL100FA #14#1/0 AWG Cu or #12#1/0 AWG Al AL100FA #14#1/0 AWG Cu or #12#1/0 AWG Al AL100FA #14#1/0 AWG Cu
850
1450 1700
Table 9.108:
Example: FJA, 20 A 1-pole, 277 Vac and 70 A 2- and 3-pole QB 240 Vac. Use phase option number for HD, HG, HJ, HL, JD, JG, JJ, JL, MG and MJ.
Phase Connection A B C AB AC BA BC CA CB ABC CBA 1-pole FJA140201 FJA140203 FJA140205 2-pole QBA220701 QBA220702 QBA220703 QBA220704 QBA220705 QBA220706 3-pole QBA32070 QBA320706
1- and 2-pole circuit breaker catalog numbers are completed by adding the required phase connection letters as a suffix.
Table 9.112:
The absence of a phase option number after a 3-pole catalog number will result in an ABC phase connection.
Table 9.109:
Phase Option Letter A B C AB AC BC ABC CBA
Example: FA, 30 A, 480 Vac. Use phase option letters for FH, FI, KI, LA, LH, LC, and LI.
1-pole FA14035A FA14035B FA14035C 2-pole FA24030AB FA24030AC FA24030BC 3-pole FA34030 FA34030CBA
Table 9.110:
240 V 277 V 480 V 600 V
AC Magnetic Standard Interrupting Extra High Interrupting Terminal Wire Range Ampere Trip Settings Rating Catalog Catalog FY/FA FJ/FC Lugs Hold Trip $ Price Number $ Price Number Lugs 1-pole, 277 Vac, 125 Vdc a 15 FY14015( )b FJA14015( ) AL50FA AL30FD #14-#4 #12#6 20 FY14020( )b FJA14020( ) 275 600 149. 651. AWG Cu, or AWG Al, or 25 FY14025( )b FJA14025( ) #12-#4 #14#6 30 FY14030( )b FJA14030( ) AWG Al AWG Cu 35 FA14035( )c FJA14035( ) 40 FA14040( )c FJA14040( ) 400 850 302. 651. 45 FA14045( )c FJA14045( ) AL100FA AL100FD 50 FA14050( )c FJA14050( ) #14#1/0 #12#2/0 AWG Al 60 FA14060( )c FJA14060( ) 651. AWG Cu or or 800 1450 FA14070( )c 302. FJA14070( ) 70 720. #12#1/0 #14#2/0 AWG Al AWG Cu 80 FA14080( )c 90 FA14090( )c 900 1700 302. 100 FA14100( )c 2-pole, 480 Vac, 250 Vdc abc AL50FA CU30FA4 15 FA24015( ) 20 FA24020( ) #14#4 one #14 651. 275 600 Cu or #10 AWG 25 FA24025( ) AWG #12#4 Cu only 30 FA24030( ) AWG Al 35 FA24035( ) 40 FA24040( ) 400 850 651. 45 FA24045( ) AL100FA AL100FA4 50 FA24050( ) #14#1/0 one #14#3 AWG Cu 60 FA24060( ) 651. AWG Cu or or 800 1450 FA24070( ) 70 #12#1/0 one #12#1 833. AWG Al AWG Al 80 FA24080( ) 90 FA24090( ) 900 1700 833. 100 FA24100( ) 3-pole, 480 Vac, 250 Vdc a 15 FA34015 AL50FA CU30FA4 20 FA34020 #14#4 one #14 275 600 833. Cu or #10 AWG 25 FA34025 AWG #12#4 Cu only 30 FA34030 AWG Al 35 FA34035 40 FA34040 400 850 833. 45 FA34045 AL100FA AL100FA4 50 FA34050 #14#1/0 one #14#3 AWG Cu 60 FA34060 833. AWG Cu or or 800 1450 70 FA34070 #12#1/0 one #12#1 996. AWG Al AWG Al 80 FA34080 90 FA34090 900 1700 996. 100 FA34100 a b c 1- and 2-pole circuit breaker catalog numbers are completed by adding the required phase connection letters as a suffix. Rated 277 Vac 15 and 20 ampere FY circuit breakers are rated for switching duty (SWD). 15, 20, 25 and 30 ampere FA I-LINE circuit breakers are also available (no SWD rating). Rated 277 Vac, 125 Vdc, except FY circuit breakers, which have no dc rating. 1530 ampere circuit breakers suitable for use with 60oC or 75oC conductors. 35100 ampere circuit breakers are suitable for use with 75oC conductors. 2009 Schneider Electric All Rights Reserved
9-24
DE2
Discount Schedule
Circuit Breakers
www.schneider-electric.us
Table 9.113:
Ampere Rating
AC Magnetic Trip Settings Hold Trip 1-pole, 277 Vac, 125 Vdc a 15 20 275 600 25 30 35 40 400 850 45 50 60 70 800 1450 80 90 900 1700 100 2-pole, 600 Vac, 250 Vdc a 15 20 275 600 25 30 35 40 400 850 45 50 60 70 800 1450 80 90 900 1700 100 3-pole, 600 Vac, 250 Vdc 15 20 275 600 25 30 35 40 400 850 45 50 60 70 800 1450 80 90 900 1700 100 a
507.
) ) ) ) ) ) ) )
971.
1446.
1- and 2-pole circuit breaker catalog numbers are completed by adding the required connection letters as a suffix, see 9-24.
Table 9.114:
QB/QD/QG/QJ Mounting Height: 2-pole3 in (76 mm) 3-pole4.5 in (114 mm)
AC Magnetic Ampere Trip Settings Rating Hold Trip 2-pole, 240 Vac b 70 80 1000 1800 90 100 110 125 150 1200 2400 175 200 225 3-pole, 240 Vac c 70 80 1000 1800 90 100 110 125 150 1200 2400 175 200 225 a b c
600.
1202.
1593.
1992.
600.
1202.
1593.
1992.
1913.
2069.
2835.
3245.
1913.
2069.
2835.
3245.
Replacement lugs are not available on QB, QD, QG, or QJ circuit breakers. Lugs for QB, QD, QG or QJ circuit breakers accept one #4 AWG300 kcmil. No accessories are available for PowerPact Q Frame breakers. 2-pole QB, QD, QG and QJ circuit breakers are completed by adding the required phasing numbers as indicated in the parentheses, see 9-24. 3-pole QB, QD, QG and QJ circuit breakers for ABC phasing are complete without additional phasing number. For CBA phasing, complete the catalog number by inserting the number 6 in the parentheses.
Table 9.115:
240 V 480 V 600 V a
F-Frame accessories. . . . . . . . . . . . . . Supplemental & Obsolescence Digest F-Frame optional lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-49 F-Frame dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-54 Q-Frame dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 7-54 2009 Schneider Electric All Rights Reserved Discount Schedule
DE2
9-25
780.
1214.
PANELBOARDS
Circuit Breakers
H- and J-frame
Table 9.116:
Ampere Rating
9
PANELBOARDS HD/HG 2-pole 3 in. (76 mm) Mounting Height H-frame 3-pole 4.5 in. (114 mm) Mounting Height J-frame 3-pole 4.5 in (114 mm) Mounting Height
H-frame 150 A Standard Rated Thermal Magnetic (600 Vac) with Factory Sealed Trip Units
D Interrupting Catalog No. HDA26015( ) HDA26020( ) HDA26025( ) HDA26030( ) HDA26035( ) HDA26040( ) HDA26045( ) HDA26050( ) HDA26060( ) HDA26070( ) HDA26080( ) HDA26090( ) HDA26100( ) HDA26110( ) HDA26125( ) HDA26150( ) HDA36015 HDA36020 HDA36025 HDA36030 HDA36035 HDA36040 HDA36045 HDA36050 HDA36060 HDA36070 HDA36080 HDA36090 HDA36100 HDA36110 HDA36125 HDA36150 $ Price G Interrupting Catalog No. HGA26015( ) HGA26020( ) HGA26025( ) HGA26030( ) HGA26035( ) HGA26040( ) HGA26045( ) HGA26050( ) HGA26060( ) HGA26070( ) HGA26080( ) HGA26090( ) HGA26100( ) HGA26110( ) HGA26125( ) HGA26150( ) HGA36015 HGA36020 HGA36025 HGA36030 HGA36035 HGA36040 HGA36045 HGA36050 HGA36060 HGA36070 HGA36080 HGA36090 HGA36100 HGA36110 HGA36125 HGA36150 $ Price J Interrupting a Catalog No. HJA26015( ) HJA26020( ) HJA26025( ) HJA26030( ) HJA26035( ) HJA26040( ) HJA26045( ) HJA26050( ) HJA26060( ) HJA26070( ) HJA26080( ) HJA26090( ) HJA26100( ) HJA26110( ) HJA26125( ) HJA26150( ) HJA36015 HJA36020 HJA36025 HJA36030 HJA36035 HJA36040 HJA36045 HJA36050 HJA36060 HJA36070 HJA36080 HJA36090 HJA36100 HJA36110 HJA36125 HJA36150 $ Price L Interrupting a Catalog No. HLA26015( ) HLA26020( ) HLA26025( ) HLA26030( ) HLA26035( ) HLA26040( ) HLA26045( ) HLA26050( ) HLA26060( ) HLA26070( ) HLA26080( ) HLA26090( ) HLA26100( ) HLA26110( ) HLA26125( ) HLA26150( ) HLA36015 HLA36020 HLA36025 HLA36030 HLA36035 HLA36040 HLA36045 HLA36050 HLA36060 HLA36070 HLA36080 HLA36090 HLA36100 HLA36110 HLA36125 HLA36150 $ Price Terminal Wire Range
AC Magnetic Trip Setting Hold Trip 2-pole, 600 Vac 50/60 Hz 15 20 350 750 25 30 35 40 400 850 45 50 60 70 800 1450 80 90 100 110 900 1700 125 150 3-pole, 600 Vac 50/60 Hz 15 20 350 750 25 30 35 40 400 850 45 50 60 70 800 1450 80 90 100 110 900 1700 125 150 a 2 pole in 3p module
899.
1338.
1589.
2483.
1124.
1575.
1988.
2993.
Table 9.117:
Ampere Rating
J-frame 250 A Standard Rated Thermal Magnetic (600 Vac) with Factory Sealed Trip Units
D Interrupting b Catalog No. JDA26150( ) JDA26175( ) JDA26200( ) JDA26225( ) JDA26250( ) JDA36150 JDA36175 JDA36200 JDA36225 JDA36250 2867. 3936. 2283. 2283. 3138. $ Price G Interrupting b Catalog No. JGA26150( ) JGA26175( ) JGA26200( ) JGA26225( ) JGA26250( ) JGA36150 JGA36175 JGA36200 JGA36225 JGA36250 3968. 5252. 3372. 3372. 4463. $ Price J Interrupting b Catalog No. JJA26150( ) JJA26175( ) JJA26200( ) JJA26225( ) JJA26250( ) JJA36150 JJA36175 JJA36200 JJA36225 JJA36250 5705. 7599. 4904. 4904. 6536. $ Price L Interrupting b Catalog No. JLA26150( ) JLA26175( ) JLA26200( ) JLA26225( ) JLA26250( ) JLA36150 JLA36175 JLA36200 JLA36225 JLA36250 7299. 9173. 5985. 5985. 7338. $ Price Terminal Wire Range
AC Magnetic Trip Setting Low High 2-pole, 600 Vac 50/60 Hz 150 750 1500 175 875 1750 200 1000 2000 225 1125 2250 250 1250 2500 3-pole, 600 Vac 50/60 Hz 150 750 1500 175 200 225 250 b 875 1000 1125 1250 1750 2000 2250 2500
AL175JD #1/04/0 AWG Al or Cu AL250JD #3/0350 kcmil Al or Cu AL175JD #1/04/0 AWG Al or Cu AL250JD #3/0350 kcmil Al or Cu
2 pole in 3p module
Table 9.118:
Ampere Rating
Catalog Number
G Interrupting 150 HGA26000S15( )b 1416. 1919. HGA36000S15 JGA36000S17 JGA36000S25 HLA36000S15 JLA36000S17 JLA36000S25 1889. 2400. 65 65 35 35 18 18
175 JGA26000S17( ) 250 JGA26000S25( ) L Interrupting 150 175 250 a b HLA26000S15( ) HLA26000S17( ) JLA26000S25( )
1670. 2079.
2087. 2600.
125 125
100 100
50 50
The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when protected by a circuit breaker with an equal continuous current rating. 2-pole device with 3 in. (76 mm) mounting height, all other 2-pole circuit breakers use 3-pole module 4.5 in. (114 mm) mounting height.
Table 9.119:
Phase Option Number 1 2 3 4 5 6 Standard 6
Table 9.120:
240 V 480 V 600 V D 25 18 14
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-36 Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-39 2009 Schneider Electric All Rights Reserved
9-26
DE2
Circuit Breakers
www.schneider-electric.us
Table 9.121:
Ampere Rating
125 150 175 200 225 250 200 225 250 3-pole, 600 Vac, 250 Vdc 70 80 90 100 110 125 150 175 200 225 250 200 225 250 a
2-pole circuit breaker catalog numbers are completed by adding required phase connection letters as suffix to catalog number. See 9-24.
Table 9.122:
Table 9.123:
Voltage 240 Vac 480 Vac 600 Vac
Table 9.124:
PowerPact R-frame 1200 A (600 Vac, 50/60 Hz) 3Pa Circuit Breaker with Electronic Trip Unit
$ Price Sensor Rating 3.0 5.0 3.0A 5.0A 6.0A 5.0P 6.0P 5.0H 6.0H 1000 A 1200 A 1000 A 1200 A 1000 A 1200 A 1000 A 1200 A 1000 A 1200 A 1000 A 1200 A 1000 A 1200 A 1000 A 1200 A 1000 A 1200 A Cat. No. bc R( )A36100CU31A R( )A36120CU31A R( )A36100CU33A R( )A36120CU33A R( )A36100CU41A R( )A36120CU41A R( )A36100CU43A R( )A36120CU43A R( )A36100CU44A R( )A36120CU44A R( )A36100CU63AE1 R( )A36120CU63AE1 R( )A36100CU64AE1 R( )A36120CU64AE1 R( )A36100CU73AE1 R( )A36120CU73AE1 R( )A36100CU74AE1 R( )A36120CU74AE1 G Interruptingbc J Interruptingbc K Interruptingbc L Interruptingbc 100% Rated 33945. 34401. 35141. 36581. 38378. 40826. 41867. 44754. 45795. 100% Rated 36111. 36599. 37383. 38916. 40829. 43431. 44540. 47610. 48719. 100% Rated 36111. 36599. 37383. 38916. 40829. 43431. 44540. 47610. 48719. 100% Rated 38418. 38934. 39770. 41400. AL1200R53K 43434. (4) 3/0-600 kcmil Al or Cu 46205. 47382. 50649. 51827. Terminal Wire Range
Electronic Trip Unit Type Micrologic Interchangeable Standard Trip Unit Function Code LI LSI LI Micrologic Interchangeable Ammeter Trip Unit LSI LSIG Micrologic Interchangeable Power Trip Unit Micrologic Interchangeable Harmonic Trip Unit a b c LSI LSIG LSI LSIG
For 2P and 4P information see Catalog 0612CT0101. To complete the catalog number, replace the blank ( ) with the appropriate interrupt rating (G, J, K or L). See page 9-123 for interrupt ratings table.
DE2
Discount Schedule
9-27
PANELBOARDS
Circuit Breakers
Table 9.125:
Ampere Rating
L-frame400 A, I-Line LA/LH MC High Magnetic Withstand Circuit Breaker For Mission Critical Loads
Standard Interrupting Catalog Number $ Price High Interrupting Catalog Number LH34200MC LH34225MC LH34250MC LH34400MC $ Price Terminal Wire Range
9
PANELBOARDS LA/LH 2- and 3-pole 6 in (152 mm) Mounting Height LI 2- and 3-pole 7.5 in (190 mm) Mounting Height LC 2- and 3-pole 7.5 in (190 mm) Mounting Height
3-pole, 480 Vac, LA/LH MC Circuit Breaker 200 4000 LA34200MC 225 4500 LA34225MC 250 5000 LA34250MC 400 8000 LA34400MC
AL250LA one #4 AWG350 kcmil AL or Cu AL400LA one #1 AWG600 kcmil or two #1 AWG250 kcmil AL or Cu
Table 9.126:
Ampere Rating
2-pole, 600 Vac, 250 Vdc a 125 625 150 750 175 875 200 1000 225 1125 250 1250 300 1500 350 1750 400 2000 3-pole, 600 Vac, 250 Vdc 125 625 150 750 175 875 200 1000 225 1125 250 1250 300 1500 350 1750 400 2000
LA26400( ) LA36125 LA36150 LA36175 LA36200 LA36225 LA36250 LA36300 LA36350 LA36400
LH26400( ) LH36125 LH36150 LH36175 LH36200 LH36225 LH36250 LH36300 LH36350 LH36400
Table 9.127:
Ampere Rating
2-pole, 600 Vac a 300 1500 350 400 450 500 600 3-pole, 600 Vac 300 350 400 450 500 600 a b 1750 2000 2250 2500 3000 1500 1750 2000 2250 2500 3000 3200
8312.
4200
8691.
3200
9234.
4200
9657.
2-pole circuit breaker catalog numbers are completed by adding required phase connection letters as suffix to catalog number. See 9-24. Type LC and LI circuit breakers are NOT recommended for use on single-motor branch circuits.
Accessories . . . . . . . . . . . . . . . . . . . . Supplemental & Obsolescence Digest Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-51 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-54
Table 9.128:
240 V 480 V 600 V
9-28
DE2
Discount Schedule
Circuit Breakers
www.schneider-electric.us
Table 9.129:
Electronic Trip Unit Type
D-Frame (600 A 480 Vac) 3P 50/60 Hz Circuit Breaker with Electronic Trip Units
Trip Unit Continuous Currentb 150 A 250 A 400 A 600 A 150 A 250 A 400 A 600 A 150 A 250 A 400 A 600 A G interrupting Catalog No. DGA34150E20 DGA34250E20 DGA34400E20 DGA34600E20 DGA34150E53 DGA34250E53 DGA34400E53 DGA34600E53 DGA34150E58 DGA34250E58 DGA34400E58 DGA34600E58 $ Price J Interrupting Catalog No. $ Price L Interrupting Catalog No. $ Price 10468. Terminal Wire Range (1) 2600 Cu or (1) 2500 Al
Trip Function
L interrupting rating is not available in M-frame. 600 V interrupt ratings not available for D-frame.
13702. (2) 2/0350 Cu or (2) 2/0500 Al 11587. (1) 2600 Cu or (1) 2500 Al
14821. (2) 2/0350 Cu or (2) 2/0500 Al 13048. (1) 2600 Cu or (1) 2500 Al
Ammeter a b
LSI
STR53-UPFIa
F = Fault Indicator, I = Ammeter. D-frame circuit breakers 400 A and below are 100% rated. 600 A is standard (80%) rated only.
Ampere Rating 300 350 400 450 500 600 700 800 300 350 400 450 500 600 700 800
Adjustable Instantaneous Trip Range b Low 600 700 800 900 1000 1200 1400 1600 600 700 800 900 1000 1200 1400 1600 High 3000 3500 4000 4500 5000 6000 7000 8000 3000 3500 4000 4500 5000 6000 7000 8000
G Interrupting Catalog Number c MGA26300( ) MGA26350( ) MGA26400( ) MGA26450( ) MGA26500( ) MGA26600( ) MGA26700( ) MGA26800( ) MGA36300 MGA36350 MGA36400 MGA36450 MGA36500 MGA36600 MGA36700 MGA36800 $ Price
J Interrupting Catalog Number c MJA26300( ) MJA26350( ) MJA26400( ) MJA26450( ) MJA26500( ) MJA26600( ) MJA26700( ) MJA26800( ) MJA36300 MJA36350 MJA36400 MJA36450 MJA36500 MJA36600 MJA36700 MJA36800 $ Price
6633.
8253.
8370.
10104.
8168.
9929.
10608.
12630.
a b c
The ET 1.0 trip unit cannot be field replaced, nor does it allow adjustment of the long-time trip point setting. It is considered an electronic equivalent of a thermal-magnet circuit breaker. UL magnetic trip setting tolerances are 10% from the nominal values shown. Fill in parentheses with the following phase connection options: (2) for AC and (5) for CA.
L-Frame accessories . . . . . . . . . . . . . Supplemental & Obsolescence Digest L-Frame dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .starting on page 7-54 L-Frame optional lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-51 M & P-Frame accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-36 M & P-Frame dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-55 M & P -Frame optional lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-39
Ampere Rating
LA/LH MC Circuit Breaker, 3P, 480 Vac 200 A 3400 A 4000 A 225 A 3825 A 4500 A 250 A 4250 A 5000 A 400 A 6000 A 7200 A
(1) 250350 kcmil Al (1) 3/0 AWG350 kcmil Cu (1) 1 AWG600 kcmil Al or (2) 1 AWG250 kcmil Al
DE2
Discount Schedule
9-29
Table 9.130:
PowerPact M-frame: with ET1.0 Factory sealed trip unit (not field adjustable)800 A a
PANELBOARDS
LS
STR23SP
DJA34150E20 5631. DJA34250E20 DJA34400E20 8865. DJA34600E20 DJA34150E53 6750. DJA34250E53 DJA34400E53 9984. DJA34600E53 DJA34150E58 8211. DJA34250E58 DJA34400E58 11445. DJA34600E58
DLA34150E20 9028. DLA34250E20 DLA34400E20 12262. DLA34600E20 DLA34150E53 10147. DLA34250E53 DLA34400E53 13381. DLA34600E53 DLA34150E58 11608. DLA34250E58 DLA34400E58 14842. DLA34600E58
Circuit Breakers
Table 9.132:
Ampere Rating 600 800 1000 1200 a b
9
PANELBOARDS
The withstand rating is the fault current, at rated voltage, that the molded case switch will withstand without damage when protected by a circuit breaker with an equal ampere rating. Fill in parentheses with the following phase connection options: (2) for AC or (5) for CA.
Table 9.133:
PowerPact P-frame 1200 A (600 Vac, 50/60 Hz) 3P a Circuit Breaker with Electronic Trip Unit
$ Price Sensor Rating Code 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A 250 A 400 A 600 A 800 A 1000 A 1200 A P( )A36060 P( )A36080 P( )A36100 P( )A36120 P( )A36025(C)U31A P( )A36040(C)U31A P( )A36060(C)U31A P( )A36080(C)U31A P( )A36100U31A P( )A36120U31A P( )A36025(C)U33A P( )A36040(C)U33A P( )A36060(C)U33A P( )A36080(C)U33A P( )A36100U33A P( )A36120U33A P( )A36025(C)U41A P( )A36040(C)U41A P( )A36060(C)U41A P( )A36080(C)U41A P( )A36100U41A P( )A36120U41A P( )A36025(C)U43A P( )A36040(C)U43A P( )A36060(C)U43A P( )A36080(C)U43A P( )A36100U43A P( )A36120U43A P( )A36025(C)U44A P( )A36040(C)U44A P( )A36060(C)U44A P( )A36080(C)U44A P( )A36100U44A P( )A36120U44A P( )A36025(C)U63AE1 P( )A36040(C)U63AE1 P( )A36060(C)U63AE1 P( )A36080(C)U63AE1 P( )A36100U63AE1 P( )A36120U63AE1 P( )A36025(C)U64AE1 P( )A36040(C)U64AE1 P( )A36060(C)U64AE1 P( )A36080(C)U64AE1 P( )A36100U64AE1 P( )A36120U64AE1 P( )A36025(C)U73AE1 P( )A36040(C)U73AE1 P( )A36060(C)U73AE1 P( )A36080(C)U73AE1 P( )A36100U73AE1 P( )A36120U73AE1 P( )A36025(C)U74AE1 P( )A36040(C)U74AE1 P( )A36060(C)U74AE1 P( )A36080(C)U74AE1 P( )A36100U74AE1 P( )A36120U74AE1 Cat. No.bc G Interrupting b 80% Rated 14603. 20003. 21207. 100% Rated c J Interrupting b 80% Rated 15480. 21207. 100% Rated c K Interrupting b 80% Rated 15480. 22410. 100% Rated c L Interrupting bd 80% Rated 16359. 100% Rated c Terminal Wire Range
Basic Electronic Fixed long-time, Trip Unit Adjustable ET1.0I (Not Interchangeable) Instantaneous
15390.
22479.
16268.
23897.
16268.
23897.
17147.
3.0
kcmil 25314. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 25668. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 26204. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 27770. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 29721. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 32379. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 33510. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 36645 (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu kcmil 37776. (3) 3/0 AWG500 Al or Cu kcmil (4) 3/0 AWG500 Al or Cu
20790.
21995.
21995.
23198.
15729.
22794.
16608.
24231.
16608.
24231.
17487.
5.0
21131.
22334.
22334.
23538.
16242.
23270.
17121.
24737.
17121.
24737.
17999.
LI
3.0A
21642.
22845.
22845.
24051.
17739.
24659.
18618.
26214.
18618.
26214.
19497.
LSI
5.0A
23141.
24345.
24345.
25548.
19607.
26393.
20486.
28058.
20486.
28058.
21365.
LSIG
6.0A
25008.
26211.
26211.
27416.
22151.
28754.
23030.
30566.
23030.
30566
23909.
5.0P
27552.
28757.
28757.
29960.
23234.
29757.
24111.
31634.
24111.
31634.
24990.
6.0P
28634.
29838.
29838.
31041.
26234.
32541.
27113.
34593.
27113.
34593.
27992.
5.0H
31634.
32837.
32837.
34043.
27315.
33545.
28194.
35661.
28194.
35661.
29073.
6.0H
32717.
33921.
33921.
35124.
a b c d
For 2P and 4P information see Catalog 0612CT0101. To complete the catalog number, replace the ( ) with the appropriate interrupt rating (G, J, K or L). For 100% rated circuit breakers add a C in the 9th character place. For example, the catalog number for a 100% standard-type trip unit with LI trip functions at 250A would be PGA36025CU31A. The L interrupt rating is supplied in 480 V only. Change the 5th character (voltage rating) from a 6 (600V) to a 4 (480V); for example, PLA34025U31A. Alternate Rating Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-44 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-36
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-55 Trip Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-43 Optional Lugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-39
9-30
DE2
Discount Schedule
Table 9.134:
When required, add the $ Price of a solid neutral from Table 9.136.
Table 9.135:
Panel Type
No. Poles 2 3 2 3 2 3
Panel Type
Micrologic 80% Micrologic 100% 14778. 17456. 14778. 19346. 15830. 16830. 21090. 16542. 18510. 24250. 17456. 23416. 18312. 20280. 24540. 20144. 22300. 28220. 1200 A bcd
MJ
PL a
PG b
PJ b
PL b
Panel Type
PG
PJ
PL
RGC
RJC
RLC
Micrologic 80% 22380. 24980. 27980. 28710. 31310. 35570. 22380. 24980. 27980. 28710. 31310. 35570.
Micrologic 100% 24618. 24478. 32178. 31582. 34442. 40906. 24618. 24478. 32178. 31582. 34442. 40906.
When required, add the $ Price of a solid neutral from Table 9.136. Std. construction back-fed main. PG, PJ, PL circuit breakers are available with both thermal-magnetic equivalent and Micrologic trip. The Micrologic circuit breakers are available 80% and 100% rated. The C suffix denotes a 100% rating. For 1200 A frame thermal magnetic circut breaker with 600 kcmil lugs, select a R-Frame Thermal Magnetic circuit breaker in the Product Selector.
Table 9.136:
Solid Neutral
Table 9.138:
Table 9.137:
LS LSI LSIG
Note: Micrologic circuit breakers come with a standard LI trip unit. Use the above $ Price adder for increase in trip functionality. Note: Refer to page 7-42 for trip unit descriptions.
Table 9.139:
Panel Type
a Type 1 Enclosure H Inches 91 91 91 91 86 68 86 86 mm 2311 2311 2311 2311 2184 1727 2184 2184 Inches 32 32 32 32 44 42 42 26 W mm 813 813 813 813 1118 1067 1067 660 Inches 8.25 9.50 8.25 9.50 9.50 9.50 9.50 9.5 D mm 210 241 210 241 241 241 241 241
Neutral Terminals Quantity & Size Main (8) 750 kcmil (8) 750 kcmil (8) 750 kcmil (8) 750 kcmil (8) 750 kcmil (8) 750 kcmil (8) 750 kcmil (8) 750 kcmil Branch
HCM
600 A 600 A (MG, MJ) 800 A 800 A (MG, MJ) 1200A 600A
(35) 350 kcmil, (9)#14-1/0, (17)#14-#4 (8) 600 kcmil, (15) 350 kcmil (9) #14-1/0, (17)#14-#4 (35) 350 kcmil, (9)#14-1/0, (17)#14-#4 (35) 350 kcmil, (9)#14-1/0, (17)#14-#4 (8) 750 kcmil, (21) 350 kcmil, (9) #14-1/0, (17) #14-#4
HCR-Ub
Available in Type 1 enclosure only; for pricing see 9-33. 6 in. enclosure extension is required for HCRU I-Line panelboard. 9 in. enclosure extension is required for HCP-SU I-Line panelboard.
PE1
Discount Schedule
9-31
PANELBOARDS
Branch Circuit Breakers (See pages 7-2 through 7-8 for interrupt rating, voltage ratings, Fed. Specs, etc.)
Circuit Breaker 3-pole a 240 V 480 Vac 250 Vdc 882. b 1142. b 2080. 2470. 20360. 24526. 5687. 8954. 9118. 12385. 10573. 13839. 15400. 20570. 22220. 29850. 16940. 22620. 24440. 600 V 1006. 1218. 1442. 1940. 4254. 1350. 1570. 2710. 1710. 2198. 3310. 2380. 2700. 4500. 3910. 4054. 5530. 2820. 3800. 3990. 4180. 6110. 6500. 7320. 8900. 7972. 9268. 4916. 5312. 10156. 10422. 11622. 15834. 8152. 10600. 10126. 13306. 19966. 21960. 8900. 13310. 14730. 21240. 10400. 15570. 17220. 24850. 9790. 14642. 16200. 11960. 17900. 19800. 24460. 26710. 32580. Space Only 98. 98. 98. 98. 98. 98. H 4.5 4.5 4.5 3 4.5 4.5 240 Vac 520. 632. 1050. 1250. 1250. 1450. 560. 1300. b 2800. 3000. 3600. 4600. 3900. 4000. 4300. 4300. 4550. 2-pole a 480 Vac 250 Vdc 600 Vac 708. 956. 1660. 1980. 5434. 6672. 5434. 6672. 16290. 22046. 4550. 7163. 7295. 9908. 8458. 11071. 12320. 16450. 17780. 23880. 13550. 18100. 19560. 786. 964. 1218. 1620. 3466. 1150. 1370. 2370. 1352. 1508. 3110. 2002. 2364. 3980. 3250. 3402. 4600. 2600. 3430. 2790. 3620. 5770. 6450. 6000. 6800. 6216. 7262. 3980. 4500. 8634. 8920. 9878. 14248. 6322. 8180. 8536. 10944. 17940. 19724. 7120. 10648. 12402. 16992. 9240. 12450. 13780. 19880. 7832. 11714. 13642. 9570. 14330. 15840. 19580. 21380. 26080. Space Only 82. 98. 98. b 98. 98. H 120 V 354. 277 V 384. 664. 832. 1-pole a 277 Vac 125 Vdc 270. c 384. c 518. 650. Space Only 72. 72. 72. 72. 72. 72. H 1.5 1.5 1.5 1.5 1.5 1.5
9
PANELBOARDS
Thermal-magnetic Circuit Breakers 1560 A FA (FY-1P) 720. 70100 A FA 832. 1560 A 1100. FH 70100 A 1300. 1560 A 1300. FJ d 70100 A 1500. 20100 A FI 1560 A 70100 A HD 110150 A 1560 A 70100 A HG 110150 A 1560 A 70100 A HJ 110150 A 1560 A 70100 A HL 110150 A 70225 A QB 1696. 70225 A QD 2208. 70225 A QG 2870. 70225 A QJ 3070. 150225 A JD 250 A 150225 A JG 250 A 150225 A JJ 250 A 150225 A JL 250 A 150225 A KI 250 A 300400 A LA 300400 A LH 300400 A 5460. LC 450600 A 300400 A LI 450600 A 300600 A MG 700800 A 300600 A MJ 700800 A 600800 A PL 6001200 A PG 6001200 A PJ /PK 10001200 A PL Electronic Trip Circuit Breakers (% Rated) 60400 A DG (100%)e 600 A DG (80%)e 60400 A DJ (100%)e 600 A DJ (80%)e 60400 A DL (100%)e 600 A DL (80%)e 250400 A 450600 A PG (80%) f 700800 A 10001200 A 250400 A 450600 A PJ/PK (80%) f 700800 A 10001200 A 250400 A 450600 A PL (80%) f 700800 A 10001200 A 250400 A 450600 A PGC (100%) f 700800 A 250400 A PJC/PKC 450600 A (100%) f 700800 A 250400 A 450600 A PLC (100%) f 700800 A RGC (100%) f 10001200 A RJC (100%) f RLC (100%) f a b c d e f
3 3 3 4.5 3
98.
4.5
98.
98.
4.5
98.
4.5
98. 98. 98. 98. 98. 98. 98. 98. 98. 98. 252. 456. 456. 662. 662. 662. 662. 662. 662. 252. 252. 252. 252. 252. 252. 662.
4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 6 7.5 7.5 9 9 9 9 9 9 6 6 6 6 6 6 9
98. 82. 82. 82. 82. 98. 98. 98. 98. b b 98. 252. 456. b b 456. 662. 662. 662. 662. 662. 252. 252. 252. 252. 252. 252. 662.
662.
662.
662.
662.
662.
662.
662.
662.
662.
662.
662.
15
662.
15
Refer to pages 7-4 through 7-8 for additional dc ratings. ac only. FA, 1P. 480Y/277 Volt rated circuit breakerDo not use on 480 Volt 33W Delta systems. Refer to Table 9.137 on page 9-31 for DG, DJ & DL Electronic trip unit price adders. Refer to Table 9.138 on page 9-31 for P and R Frame Micrologic trip unit price adders.
9-32
PE1
Discount Schedule
Class 2110 / Refer to Catalog 2110CT9701 Table 9.141: QO Plug-On Branch Circuit Breakers
$ Price Transition Charge per 6 QO one-pole spaces (H=4.5 in. per 6 one-pole spaces) $ Price for QO Branch circuit breakers 328. on page 7-10
Table 9.150:
Table 9.142:
Ampere Rating $ Price
Sub-feed/Feed-through Lugs
2 or 3-pole Branch Mounted; SL Kit used for both SFL and TFL. 225 A 368. 400 A 600. 600 A 858. 800 A 1490. 1200 A 1890.
Table 9.151:
Ampere Rating 100/125 A 250 A 400 A 600 A 800 A 1200 A a
Table 9.143:
Ground Bars
$ Price 180. 148. $ Price Addl. Neutral Assembly
Table 9.145:
Ampere Rating 225 A 400 A 600 A 600 A 800-1200 A
Compression lugs are not available on LC, LI, LE, LX, LXI, MG, MJ, PG, PJ,PL, RGC, RJC, RLC I-Line circuit breakers. Available on MA and MH circuit breakers.
Table 9.153:
Ampere Rating
Table 9.146:
Ampere Rating 100400 A 600 A 800 A 1200 A
Neutrals
Type Copper Neutral Copper Neutral Copper Neutral Copper Neutral $ Price Adder 868. 894. 1108. 1352.
Table 9.147:
Ampere Rating 225 A 400 A 600 A 800 A 1200 A 225 A 400 A 600 A 800 A 1200 A
Note: Additional factory modifications, see 9-37. a Compression lugs are not available on LC, LI, LE, LX, LXI, MG, MJ, PG, PJ,PL, RGC, RJC, RLC I-Line circuit breakers. Available on MA and MH circuit breakers.
Table 9.148:
Metal Directory Frame Frame attached to trim (not available on four piece trim)
Door-in-Door Trim Trim has piano hinge down one side. Door opens by single latch; Entire trim opens by removing screws. Hinged Door-in-Door with Outer Door Lock Added
Surgelogic TVSS Options Surge Counter Dry Contacts Remote Monitor Note: Requires HCM interior minimum.
Table 9.155:
Voltage 120/240 1P3W 208Y/120 3P4W 240/120 3P4W 480Y/277 3P4W 600Y/347 3P4W
PE1
9-33
Equipment Ground Bar Copper Ground Bar (Add to equipment ground bar $ Price)
Compression lugs are not available on LC, LI, LE, LX, LXI, MG, MJ, PG, PJ,PL, RGC, RJC, RLC I-Line circuit breakers. Available on MA and MH circuit breakers.
PANELBOARDS
Weatherproof or Dusttight Cabinets Maximum 26 in. wide box Maximum 28 in. wide box Maximum 42 in. wide box Maximum 44 in. wide box
9
PANELBOARDS
Electrical Interlock Kit 240 Vac Catalog Number a $ Price Std. 1 3 Max. 1 3
Horsepower Ratings i 480 Vac Std. 1 3 Max. 1 3 Std. 1 3 600 Vac Max. 1 3 5 5 10 10 20 20 40 250 Vdc
2-pole, 240 Vac 30-30 4.5 30-Blank 4.5 60-60 4.5 60-Blank 4.5 100-100 6 100-Blank 6 200 9 15 400 9 600
2 1 1 1 1 1
1.5 3 7.5
3 10 15 15
3-pole, 240 Vac 30-30 4.5 QMB321TW 827. 2 HRK30 30-Blank 4.5 QMB321HW b 587. 1 60-60 4.5 QMB322TW 827. 1 QMB36R 60-Blank 4.5 QMB322HW b 587. 100-100 6 QMB323TW 1265. 1 QMB100R 100-Blank 6 QMB323HW b 879. 200 9 QMB324W 1673. 1 HRK1020 15 QMB325W 4277. 1 QMB4060R 400 9 QMB325WT3 c 4143. 15 QMB326W 6249. 1 QMB4060R 600 15 QMB326WT3 c 6249. 800 15 QMB327WT3c 12140. 2-pole, 600 Vac, 250 Vdcd 30-30 4.5 QMB261TW 1050. 1 QMB36R 30-Blank 4.5 QMB261HW b 702. 60-60 6 QMB262TW 1050. 1 QMB60R 60-Blank 6 QMB262HW b 738. 100-100 7.5 QMB263TW 1536. 2 HRK1020 100-Blank 7.5 QMB263HW b 1083. 1 200 9 QMB264W 1791. 1 HRK1020 400 Use 3-pole Devices For 2-pole Application 600 e 3-pole, 600 Vacd 4.5 30-30 4.5 30-Blank 4.5 6 60-60 6 60-Blank 6 6 60-30 6 7.5 100-100 6 7.5 100-Blank 6 7.5 100-30 7.5 7.5 100-60 7.5 200 9 200-200 7.5 200-Blank 7.5 400f 15 400 9 400f 9 600 ef 15 600 15 800g 15 a b c d e f g h i QMB361TW QMJ361T QMB361HW b QMB362TW QMJ362T QMB362HW b QMB362T21W QMB363TW QMJ363T QMB363HW b QMJ363H b QMB363T31W QMB363T32W 1241. 1293. 861. 1241. 1293. 861. 1241. 1961. 2013. 1373. 1424. 1961. 1961. QMB36R QMB36R QMB60R QMB60R and 1 ea. QMB60R QMB36R 2 HRK1020 1 HRK1020 and 1 ea. HRK1020 QMB36R 1 1 1 1
1.5 3 7.5 15
3 10 15
3 5 10 25
5 15 25 50
7.5 20 30 50
15 30 60 125
3 10 15 30
10 25 40 50
5 10 20 40
QMB364W 2306. QMJ364T 4712. QMJ364H b 2357. QMB365W 5445. QMJ365 5561. QMB365WT6 h 5276. QMB366W 6735. QMJ366 6704. QMB367W 12140.
48.90 48.90 48.90 48.90 48.90 47.70 47.70 47.70 48.90 and 47.70 1 ea. HRK1020 QMB60R 48.90 1 HRK1020 47.70 1 QMB4060R 111.00 1 QMB4060R 111.00
QMB300EK(1 or 2) QMB300EK(1 or 2) QMB610EK(1 or 2) QMB610EK(1 or 2) QMB610EK(1 or 2) QMB610EK(1 or 2) QMB610EK(1 or 2) QMB610EK(1 or 2) QMB610EK(1 or 2) QMB200EK(1 or 2) QMB610EK(1 or 2) QMB200EK(1 or 2)
357. 357. 357. 357. 357. 357. 357. 357. 357. 357. 357. 357.
3 3 7.5 7.5 15 15 25 25 50 75
5 10 20 20 40 50 50
1 indicates one normally open and one normally closed contact. 2 indicates two normally open and two normally closed contacts. Blank units cannot be modified to accept a switch interior. Use 300 Vac Class T fuses only. Class J fuse provisionsto field modify switch, move load side fuse base to position indicated in switch. Not available on 100-30, 100-60 or 800 Ampere switch units. To adapt switch for 600 Vac Class T fuses, order kit Catalog Number QMB600T6, $ Price 194. (Use T6 fuses with standard horsepower ratings only). 250 Vdc rating. To adapt switch for 600 Vac Class T fuses, order kit Catalog Number QMB800T6, $ Price 467. (Use T6 fuses with standard horsepower ratings only). Use 600 Vac Class T fuses only. Horsepower rating applicable to 480Y/277 V system only.
See Supplemental & Obsolescence Digest for merchandised motor starter units, QMB RTI panelboards and replacement switches for Series 1-4 and D2 QMB panelboards.
9-34
PE1A
Discount Schedule
Table 9.157:
Mains Rating (Amperes) 225 400 600 800 1200 a b c d e
Base $ Price
Main Lugs Maximum Mounting Space (Inches) 60 b 60 b 60 b 60 b 45 Base $ Price (2- or 3-pole) 1098. 1344. 2066. 2550. 3550. Mains Rating (Amperes) 100 b 200 b 400 600 800 Maximum Mounting Space (Inches) 51 51 45 45 45 Main Switch a 240 Vac Base $ Price 2-pole 3-pole 2544. 3104. 2544. 3104. 4840. 6158. 7298. c 8758. c 11098. 13704. c Solid Neutral (Main Lugs and Main Switch) 600 Vac Base $ Price Ampere $ Price Rating 2-pole 3-pole 3026. 3632. 100 294. 3026. 3632. 200 294. 225 294. 5906. 7300. 400 384. 7968. de 9338. d 600 556. 11128.d 13724. d 800 786. 1200 912.
Pricing includes Class R or J Rejection Clips if requested at time of order. Class J fuses available only on 600 V switches. 800 A switch unit with provision for UL Class L fuses. Switches for use with 300 V Class T fuses are also available at no additional cost. For 600 Vac UL Class T fuse provision on main switch, add $ 321.00 250 Vdc rating.
Table 9.158:
Unit Ampere Rating
a 3-pole $ Price 240 Vac Space Only Unit Mounting Height $ Price (Inches) 294. 392. 396. 294. 294. 396. 580. 878. 580. 878. 878. 4.5 6 6 4.5 4.5 6 9 15 9 15 15 2-pole $ Price 852. 1276. 1984. 1216. 1822. 1216. c 1216. 1216. c 1216. 1822. e 1822. 3970. 1984. c 4300. c 4098.cd 4098. 5264. cf 5264. 10682. f 3-pole $ Price 600 Vac Space Only Unit Mounting Height $ Price (Inches) 294. 396. 462. 396. 462. 396. 462. 294. 396. 462. 396. 462. 580. 878. 580. 878. 4.5 6 7.5 6 7.5 6 7.5 4.5 6 7.5 6 7.5 9 15 9 15
Twin Mounted Branch Switches b 30-Blank QMB 60-Blank QMB QMB 100-Blank QMJ c 200-Blank QMJ c 60-30 QMB 100-30 QMB 100-60 QMB QMB 30-30 QMJc QMB 60-60 QMJ c QMB 100-100 QMJc 200-200 Single Mounted Branch Switches 200 QMB 400 QMB 400 d QMB 400 QMJ c 600 QMB 600 QMJ c 800 g QMB a b c d e f g
592. 898. 1822. 826. 826. 1282. 1484. 3204. 3040.d 4888. e 10682.
784. 1104. 2274. 1120. 1120. 1576. 2034. 4562. 4360.d 6374. ce 10682. e
1012. 1592. 2576. 1446. 2274. 1446. 1446. 2274. 5154. 2576. 5764. c 5552.cd 5552. 6962. cf 6962. 10682. f
Pricing includes Class R or J Rejection Clips if requested at time of order. Class J fuses available only on 600 V switches. $ Price is per twin switch. 250 Vdc rating. For use with Class T fuses only. Use 300 V Class T fuses on 240 Vac max. systems and 600 V Class T fuses on 600 Vac max. systems. Switches for use with 300 V Class T fuses are also available at no additional cost. For 600 Vac UL Class T fuse provision on branch switch, add $ 307.00 800 A switch unit with provision for UL Class L fuses.
Table 9.159:
Accessories
Copper Bus Bars 488. 488. 720. 1148. 1372. 1428.
Electrical Interlocks Mains Ampere Sub-feed Lugs a Feed-through Lugs for Number of Contacts Branch Switches Rating for Main Lugs Interior a Main Switch Interior Normally Open Normally Closed 30200 A $ Price 200 836. 225 282. 400 466. 872. b 1 1 472. 2 2 600 856. 1268. b 800 1150. 1512. b 1200 1440. a b No extra box height required. Box height increases 6 in. Not available in Type 3R/5/12 construction, or with door over QMB option.
Table 9.160:
Left Unit
$ Price3-pole 480 V 600 V HD HG HD HG HD HG 15150 A 15150 A 6 2914. 3572. 3324. 3814. 3674. 4018. Note: See Supplemental & Obsolescence Digest for merchandised motor starter units, QMB RTI panelboards and replacement switches for Series 1-4 & D2 QMB panelboards.
Table 9.161:
Table 9.162:
Starter Size 0 1 2 3
PE1
Discount Schedule
9-35
PANELBOARDS
Common Features
Class 4620 / Refer to Catalog 4620CT9601
www.schneider-electric.us
Table 9.169:
$ Price 180. 148.
9
PANELBOARDS
Equipment Ground Bar Copper Ground Bar (Add to Equipment Ground Bar $ Price) Insulated/Isolated Ground Bar $ Price an Additional Neutral Assembly from Table 9.157 on page 35 for Al insulated ground bar or from Table 9.164 for Cu insulated ground bar. (Add to Equipment Ground Bar $ Price) Name Plates Standard white face/black letter laminated bakelite, 1 in. x 3.5 in. adhesive backed or screw mountable with screws in a bag assembly ($ Price includes engraving)
Aluminum Compression Lugs VCEL 100 A #81/0 Al or Cu 200 A #4300 kcmil Al or Cu 400 A 2/0500 kcmil Al or Cu 600 A 2/0500 kcmil Al or Cu 800 A 2/0500 kcmil Al or Cu or 500 kcmil Cu or 500750kcmil Al.
78.
Table 9.170:
Table 9.164:
Copper Neutral
$ Price 868. 894. 1108. 1352. 1616. N/A 806. 3054.
Copper Neutral 125400 A 600 A 800 A 1200 A 1600 A Hinged Trim Door option for Type 1 enclosure Weatherproof or Dusttight CabinetsType 3R, 5, 12 800 A Maximum Mechanical Lugs 225 A1200 A
Table 9.171:
Voltage Surge Current 120/240 V 208Y/120 V 240/120 Vac 480Y/277 Vac 600Y/347 Vac Rating 34W kA 13W 34W 34W 34W High Leg 100 14310. 15410. 120 15654. 16754. 160 18586. 19686. 200 19196. 23596. 23596. 26896. 26896. 240 23760. 27440. 27440. 31460. 31460.
Standard
Table 9.172: Table 9.165: Copper Mechanical Lugs Main Lug Interiors
$ Price Standard
TVSS Options
$ Price 1650. Standard 2588.
Surgelogic TVSS Options Surge Counter Dry Contacts Remote Monitor a Requires 9 in. of mounting height.
Table 9.166:
Table 9.167:
100 A twin QMB 6" H @ 240 Volt 60 A twin QMB 6" H @ 600 Volt 100 A twin QMB 7.5" H @ 600 Volt 100 A twin QMJ 6" H @ 600 Volt 200 A QMB 9" mounting height, 200 Amp twin QMJ 7.5" mounting height 400 A QMJ 9" H, 400 A Class T 9" H, 400, 600 or 800 A QMB all require 15" H 38"
30/30 @ 240 or 600 V or 60/60 @ 240 V are 4.5" high Wiring Gutter
Table 9.168:
To maximize the quantity of branch switches, use QMJ switches on 9-35. Class K fuses are available in time delay construction suitable for motor and transformer loads.
9-36
PE1
Discount Schedule
Table 9.173:
Table 9.175:
Maximum Ampacity MLO
Ampacity
Square D Type PB b 30 A 2P PBM10B 60 A 2P 75 A 2P 100 A 2P 150 A 2P 200 A 2P 225 A 2P 30 A 3P 60 A 3P 75 A 3P 100 A 3P 150 A 3P 200 A 3P 225 A 3P ASCO Type 920 c 30 A 2P 60 A 2P 75 A 2P 100 A 2P 150 A 2P 200 A 2P 225 A 2P 30 A 3P 60 A 3P 75 A 3P 100 A 3P 150 A 3P 200 A 3P 225 A 3P a b c 9202030 9202060 9202075 9202100 9202150 9202200 9202225 9203030 9203060 9203075 9203100 9203150 9203200 9203225 PBP10B PBN10B PBQ10B PBR10B PBV10B PBW10B PBM11B PBP11B PBN11B PBQ11B PBR11B PBV11B PBW11B
44
3772. 4634. 4986. 5072. 7156. 8692. 9830. 3740. 4754. 5628. 6454. 8078. 8736. 10062.
18 18 18 18 18 18 18 18 18 18 18 18 18 18
56 62
When greater than 125 A lugs are required on the split section of the bus, consult your local Square D/Schneider Electric sales office for box height.
Table 9.176:
Ampacity MLO 225 A 400 A 600 A 800 A 1200 A
4694. 5954. 5954. 6194. 9242. 10882. 11875. 5436. 7638. 7638. 9184. 12998. 14434. 15750.
18 18 18 18 18 18 18 18 18 18 18 18 18 18
Note: For applications with main circuit breaker panelboards, contact the Square D/Schneider Electric local Field Sales Office. a For I-Line panelboards, dimension includes height of SL sub-feed lug kit from Digest, plus 3 in. from available branch mounting space.
(Not UL Listed) $ Price as standard main circuit breaker, No adder See page 7-35 for pricing.
NF panels require 18 in. of additional box height regardless of contactor ampacity or manufacturer. If two-wire control is required Square D Add 708. (No additional width or depth required) If two-wire control is required ASCO Add 1412. (No additional width or depth required)
Table 9.174:
Current Density Rated Panelboard Bus and Special Plating for Copper Bus
Copper Bus Special Plating $ List Price Adder a Tin or Silver Plating Current Density Rated Bus $ List Price Adder 1000 A/in2 Cu 510. 610. 830. 1050. 1490. 1710. 1940. c b 340. b 456. 572. 1244. 1432. Copper (Cu) Only c c c 750 A/in2 Al
Ampacity
1080. cd d d
Standard copper bus plating material NQ and NF: Silver plated bus/tin plated connectors I-Line and QMB: Tin. NQ available in 42 circuit only. Not available in NQ. HCN 600 A and all 8001200 A I-Line interiors available with copper bus only.
Powerlogic meteringa Customer equipment space (NQ and NF)a Increased box deptha Increased gutterstop, bottom and sidesa Non-standard painta Welded base channela Type 1 gasketeda Type 2 drip hooda Type 3R/4/4X/5/12 stainless steel enclosurea Type 4X fiberglass enclosurea Stainless steel trim fronta Padlockable haspa Special locks (Corbin, Yale, Best)a Equal height boxesa Common trim to cover two equal height boxesa Panelboard skirthides conduits feeding a panelboarda Panelboard wirewayfor terminating conduit in wireway endwalla Keyed mechanical interlocking of two or more circuit breakers (I-Line and QMB)a Motor operators (I-Line only) Panelboard interiors and special fronts to fit existing boxes A standard panelboard box has one blank endwall & one with knockouts. Blank endwalls or knockouts in both endwalls are also availablea
Supported by the Panelboard Product Selector
PE1
Discount Schedule
9-37
PANELBOARDS
Type
$ Price
NQ Panelboards125 A Maximum Lugs on Split Bus Section a 18 30 225 A 600. 900. 18 30 30 NF Panelboards125 A Maximum Lugs on Split Bus Section a 18 30 250 A 900. 18 30 30
Panelboards
9
Table 9.177:
Panel Type
PANELBOARDS
a a
NQ
400 600
Table 9.178:
Panel Type
The lug range shown is for the highest amperage of the circuit breaker frame shown in the table.
Table 9.179:
Panel Type
NF
Table 9.180:
Panel Type
NF
The lug range shown is for the highest amperage of the circuit breaker frame shown in the table.
9-38
Terminal Data
Class 2110, 4620 / Refer to Catalog 2110CT9701, 4620CT9601
Table 9.181:
Panel Type
I-Line
Table 9.182:
Panel Type
I-Line
Table 9.183:
Panel Type
QMB
Table 9.184:
Panel Type
QMB
Table 9.185:
Panel Type
QMB
Table 9.186:
Panel Type
QMJ
a b
Use only 90oC insulated conductors based on an ampacity of 75oC conductors. (#) = Number of conductors per phase.
9-39
PANELBOARDS
Speed-D Switchboards
9
PANELBOARDS Standard Unit Inverted Unit
Service Applications
Cold Sequence Metering
Standard Unit Inverted Unit
Table 9.187:
System
600 V Max.
Bus Link KitUtilized when installing window type current transformers Ground Fault Protection Factory installed onlyc a b c
Bottom Feed
Top Feed
Includes 8 in. box extension. Kits required per 3 application: 400600 AOrder one kit 8001200 AOrder two kits Must specify feed (top or bottom) and sequence (hot or cold) at the time of order. Ground fault protectionconsists of ground fault relay, ground fault sensor, and display. Available only on 1000 A and 1200 A Units. The Ground fault option adds 8 in. of height to the enclosure (78 in. + 8 in. = 86 in.).
Table 9.188:
Top Feed Bottom Feed
Ampere Rating 400 600 800 1000 1200 a
Lug Table
Main Circuit Breaker Lug Wire Range a (3) 3/0500 kcmil Al or Cu (3) 3/0500 kcmil Al or Cu (3) 3/0500 kcmil Al or Cu (4) 3/0500 kcmil Al or Cu (4) 3/0500 kcmil Al or Cu #6 AWG300 kcmil Al or Cu Ground Lug
CT bus lugs and neutral lugs are identical to the main circuit breaker lugs.
9-40
PE1A
Discount Schedule
NQ Merchandise Panelboards
www.schneider-electric.us
NQ Panelboards
Class 1640
New!
Features
Table 9.189:
New!
Pole Spaces 18 30 30 42 Mains Rating
100 225
Table 9.190:
Total $ Price Interior Only Interior, Front, (Order Branch Circuit Box and Pole Mains Breakers Separately) Spaces Rating Adapter Kit
Type 1 Type 12 Catalog No. $ Price Catalog No. $ Price 15 27 30 42 1407. 100 backfed 1647. 2528. 225 2808. NQ418L1C14 951. NQ430L1C14 1191. NQ430L2C14 1292. NQMB2HJ14 NQ442L2C14 1551. NQMB2Q14
Catalog $ Price Catalog $ Price Catalog $ Price No. No. No. NQB532 118. NQC32( ) 338. N/A Select QOB 3-pole or QOB-VH NQB532 118. NQC32( ) 338. N/A 780. HD, HG, HJ, HL or JD, JG, NQB544 118. NQC44( ) 338. N/A 780. JJ, JL, QB, QD, QG, QJ NQB550 118. NQC50( ) 359. N/A
Note: Copper bussing standard. Add F for flush, S for surface. SFL, TFL and SFC/B are not available (add footnote letter).
New!
PE1A
Discount Schedule
9-41
240 Vac, 48 Vdc maximum 225 A maximum main circuit breaker or main lugs 100 A maximum branch circuit breakers Visi-Trip indication on branch circuit breakers 10,000 A through 65,000 A Short Circuit Current Rating (SCCR) Interiors supplied with tin plated copper bus as standard Interiors accept both bolt-on and plug-on branch circuit breakers Three-phase, four-wire interiors available Panelboards available with Mono-Flat front Suitable for use as service entrance equipment Branch circuit filler plates provide fast and easy installation Both fully and series rated systems are available
PANELBOARDS
www.schneider-electric.us
9
PANELBOARDS
9-42