Cascading and enhanced

discrimination

Complementary
technical information

With traditional circuit breakers, cascading between two devices generally results in
the look of discrimination.
With Compact circuit breakers, the discrimination characteristics in the tables remain
applicable and are in some cases even enhanced. Protection discrimination is
ensured for short-circuit currents greater than the rated breaking capacity of the
circuit breaker and even, in some cases, for its enhanced breaking capacity. In the
later case, protection discrimination is total, i.e. only the downstream device trips
for any and all possible faults at its point in the installation.
Example
Consider a combination between:
bb a Compact NSX250H with trip unit TM250D
bb a Compact NSX100F with trip unit TM25D.
The discrimination tables indicate total discrimination. Protection discrimination is
therefore ensured up to the breaking capacity of the NSX100F, i.e. 36 kA.
The cascading tables indicate an enhanced breaking capacity of 70 kA.
The enhanced discrimination tables indicate that in a cascading configuration,
discrimination is ensured up to 70 kA, i.e. for any and all possible faults at that point
in the installation.

Enhanced discrimination tables - 380/415 V

For each combination of two circuit breakers, the tables indicate the:

15 / 25

Downstream device
breaking capacity enhanced
by cascading (in kA)

Selectivity limit enhanced by cascading


(in kA)

In a table, a box containing two equal values indicates that discrimination is provided
up to the reinforced breaking capacity of the downstream device.
These tables apply only to cases with combined discrimination and cascading
between two devices. For all other cases, refer to the normal cascading and
discrimination tables.

Technical principle

DB125677.eps

Enhanced discrimination is the result of the exclusive Compact NSX Roto-active


breaking technique which operates as follows:
bb due to the short-circuit current (electrodynamic forces), the contacts in both
devices simultaneously separate. The result is major limitation of the short-circuit
current
bb the dissipated energy provokes the reflex tripping of the downstream device,
but is insufficient to trip the upstream device.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

557E4200

Version : 1.2

02/03/2012

553

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX160, NSX250, TM-D


Downstream: iC60, C120, NG125

220-240 V
Upstream

NSX160B

NSX160F

NSX160N

NSX160H

NSX160S

NSX160L

Breaking capacity (kA)

40

85

90

100

120

150

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

TM-D

Downstream
80-100

Rating (A)
Breaking
capacity (kA)
iC60a
iC60N
iC60H
iC60L

C120N/H
NG125N
NG125H

y 25 A
32-40 A
50-63 A
y 40 A
50 to 125 A
y 40 A
50 to 125 A
y 40A
50 to 80 A

125-160 80-100

125-160 80-100

125-160 80-100

125-160 80-100

125-160 80-100

125-160

30/30
40/40
50/50
65/65
65/65
65/65
40/40

30/30
60/60
80/80
80/80
80/80
80/80
50/50

30/30
60/60
80/80
80/80
80/80
80/80
50/50

30/30
60/60
80/80
80/80
80/80
80/80
70/70

30/30
60/60
80/80
80/80
80/80
80/80
70/70

60/60

70/70

70/70

85/85

85/85

85/85

85/85

85/85

100/100

100/100

Reinforced breaking capacity (kA)

10
20
30
50
36
30
20/30
20/30
50
50
70
70

30/30
30/30
40/40
40/40
40/40
40/40

Upstream

NSX250B

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

40

85

90

100

120

150

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

TM-D

200-250

200-250

200-250

200-250

200-250

200-250

30/30
40/40
50/50
65/65
65/65
40/40
40/40

30/30
60/60
65/65
80/80
80/80
65/65
50/50

30/30
60/60
65/65
80/80
80/80
65/65
50/50

30/30
60/60
65/65
80/80
80/80
65/65
70/70

30/30
60/60
65/65
80/80
80/80
65/65
70/70

60/60

70/70

70/70

85/85

85/85

85/85

85/85

85/85

100/100

100/100

Downstream
Rating (A)

iC60a
iC60N
iC60H
iC60L

C120N/H
NG125N
NG125H

y 25 A
32-40 A
50-63 A
y 100 A
125 A
y 100 A
125 A

Breaking
capacity (kA)

Reinforced breaking capacity (kA)

10
20
30
50
36
30
20/30
20/30
50
50
70

30/30
30/30
40/40
40/40
40/40
40/40

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

554

Version : 1.2

02/03/2012

557E4200

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX100, NSX160, Micrologic


Downstream: iC60

220-240 V
Upstream

NSX100B

NSX100F

NSX100N

NSX100H

NSX100S

NSX100L

Breaking capacity (kA)

40

85

90

100

120

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

40

40

40

100

40

100

40

100

40

100

30/30

30/30
30/30
60/60
60/60

30/30

30/30
30/30
60/60
60/60

30/30

30/30
30/30
60/60
60/60

30/30

30/30
30/30
60/60
60/60

Downstream
Rating (A)

100

100

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N

iC60H

iC60L

y 25 A
32 to 63 A
y 25 A
32-40 A
50-63 A
y 25 A
32-40 A
50-63 A
y 25 A
32-40 A
50-63 A

10
10
20
20
20
30
30
30
50
36
30

30/30
40/40

40/40

30/30
30/30
40/40
40/40
40/40
40/40

30/30
40/40

30/30
30/30
40/40
40/40

60/60

60/60

60/60

60/60

50/50

50/50
50/50

80/80

80/80
80/80

80/80

80/80
80/80

80/80

80/80
80/80

80/80

80/80
80/80

65/65

65/65
65/65

80/80

80/80
80/80

80/80

80/80
80/80

80/80

80/80
80/80

80/80

80/80
80/80

Upstream

NSX160B

NSX160F

NSX160N

NSX160H

NSX160S

NSX160L

Breaking capacity (kA)

40

85

90

100

120

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

80

80

80

160

80

160

80

160

80

160

30/30

30/30
30/30
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80

30/30

30/30
30/30
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80

30/30

30/30
30/30
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80

30/30

30/30
30/30
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80

Downstream
Rating (A)

160

160

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N
iC60H

iC60L

y 50 A
63 A
y 50 A
63 A
y 50 A
50 A
63 A
y 25 A
32-40 A
50 A
63 A

10
10
20
20
30
30
30
50
36
30
30

30/30
40/40
40/40
40/40

40/40

30/30
30/30
40/40
40/40
40/40
40/40
40/40

40/40
40/40

30/30
40/40
50/50
50/50
65/65
65/65
65/65

30/30
30/30
40/40
40/40
50/50
50/50
50/50
65/65
65/65
65/65
65/65

60/60
80/80
80/80
80/80
80/80
80/80

60/60
80/80
80/80
80/80
80/80
80/80

60/60
80/80
80/80
80/80
80/80
80/80

60/60
80/80
80/80
80/80
80/80
80/80

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

557E4200

Version : 1.2

02/03/2012

555

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX250, Micrologic


Downstream: iC60, C120, NG125

220-240 V
Upstream

NSX250B

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

40

85

90

100

120

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

250

250

250

250

250

250

30/30
60/60
65/65
80/80
80/80
65/65
50/50
70/70
85/85

30/30
60/60
65/65
80/80
80/80
65/65
50/50
70/70
85/85

30/30
60/60
65/65
80/80
80/80
65/65
70/70
85/85
100/100

30/30
60/60
65/65
80/80
80/80
65/65
70/70
85/85
100/100

Downstream
Rating (A)

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N
iC60H
iC60L

C120N/H
NG125N
NG125H

y 25 A
32-40 A
50-63 A

10
20
30
50
36
30
20/30
50
70

30/30
40/40
40/40

40/40
40/40

30/30
40/40
50/50
65/65
65/65
65/65
40/40
60/60
85/85

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

556

Version : 1.2

02/03/2012

557E4200

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX250, TM-D, Micrologic


Downstream: NG160, NSC100, NSX100

220-240 V
Upstream

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

85

90

100

120

150

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

Downstream
Rating (A)

160

200-250

160

200-250

160

200-250

160

200-250

160

200-250

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NG160E
NG160N/H
NSC100N
NSX100B, y 25 A
TM-D
40-100 A
NSX100F, y 25 A
TM-D
40-100 A
NSX100N, y 25 A
TM-D
40-100 A
NSX100H, y 25 A
TM-D
40-100 A
NSX100S, y 25 A
TM-D
40-100 A
NSX100B Micrologic
NSX100F Micrologic
NSX100N Micrologic
NSX100H Micrologic
NSX100S Micrologic

25
50
42
40
40
85
85
90
90
100
100
120
120
40
85
90
100
120

40/40
85/85
85/85
85/85
36/85

50/50
90/90
90/90
90/90
36/90
90/90
36/90

50/50
100/100
100/100
100/100
36/100
100/100
36/100
100/100
36/100

60/60
100/100
100/100
100/100
36/120
120/120
36/120
120/120
36/120
120/120
36/120

36/85

36/90
36/90

36/100
36/100
36/100

36/120
36/120
36/120
36/120

60/60
100/100
100/100
100/100
36/150
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/100
36/150
36/150
36/150
36/150

Upstream

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

85

90

100

120

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Downstream
Rating (A)

160

200-250

160

200-250

160

200-250

160

200-250

160

200-250

60/60
100/100
100/100
100/100
36/150
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/100
36/150
36/150
36/150
36/150

60/60
100/100
100/100
100/100
36/150
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/100
36/150
36/150
36/150
36/150

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NG160E
NG160N/H
NSC100N
NSX100B, y 25 A
TM-D
40-100 A
NSX100F, y 25 A
TM-D
40-100 A
NSX100N, y 25 A
TM-D
40-100 A
NSX100H, y 25 A
TM-D
40-100 A
NSX100S, y 25 A
TM-D
40-100 A
NSX100B Micrologic
NSX100F Micrologic
NSX100N Micrologic
NSX100H Micrologic
NSX100S Micrologic

25
50
42
40
40
85
85
90
90
100
100
120
120
40
85
90
100
120

40/40
85/85
85/85
85/85
36/85

40/40
85/85
85/85
85/85
36/85

50/50
90/90
90/90
90/90
36/90
90/90
36/90

50/50
90/90
90/90
90/90
36/90
90/90
36/90

50/50
100/100
100/100
100/100
36/100
100/100
36/100
100/100
36/100

50/50
100/100
100/100
100/100
36/100
100/100
36/100
100/100
36/100

60/60
100/100
100/100
100/100
36/120
120/120
36/120
120/120
36/120
120/120
36/120

60/60
100/100
100/100
100/100
36/120
120/120
36/120
120/120
36/120
120/120
36/120

36/85

36/85

36/90
36/90

36/90
36/90

36/100
36/100
36/100

36/100
36/100
36/100

36/100
36/120
36/120
36/120

36/100
36/120
36/120
36/120

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

557E4200

Version : 1.2

02/03/2012

557

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX400-630, NS800-1000, Micrologic


Downstream: NG160, NSC100, NSX100-630

220-240 V
Upstream

NSX400
N
H

NSX630
N
H

NS800
L
LB

NS1000
L

Breaking capacity (kA)

85

120

150

85

120

150

150

150

Trip unit

Micrologic

100

100

Micrologic

200

Micrologic

Micrologic

1000

Downstream
Rating (A)

400

400

400

400

630

630

630

630

800

50/50
85/85
85/85
85/85

50/50
90/90
90/90
90/90
90/90
100/100

60/60
100/100
100/100
100/100
120/120
120/120
120/120

60/60
100/100
100/100
100/100
150/150
150/150
150/150
150/150

50/50
150/150
150/150
150/150
150/150

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NG160E
NG160N/H
NSC100N
NSX100B, TM-D
NSX100F, TM-D
NSX100N, TM-D
NSX100H, TM-D
NSX100S, TM-D
NSX100L, TM-D
NSX160B, TM-D
NSX160F, TM-D
NSX160N, TM-D
NSX160H, TM-D
NSX160S, TM-D
NSX160L, TM-D
NSX250B, TM-D
NSX250F, TM-D
NSX250N, TM-D
NSX250H, TM-D
NSX250S, TM-D
NSX250L, TM-D
NSX100B Micrologic
NSX100F Micrologic
NSX100N Micrologic
NSX100H Micrologic
NSX100S Micrologic
NSX100L Micrologic
NSX160B Micrologic
NSX160F Micrologic
NSX160N Micrologic
NSX160H Micrologic
NSX160S Micrologic
NSX160L Micrologic
NSX250B Micrologic
NSX250F Micrologic
NSX250N Micrologic
NSX250H Micrologic
NSX250S Micrologic
NSX250L Micrologic
NSX400F Micrologic
NSX400N Micrologic
NSX400H Micrologic
NSX400S Micrologic
NSX400L Micrologic
NSX630F Micrologic
NSX630N Micrologic
NSX630H Micrologic
NSX630S Micrologic

25
50
42
40
85
90
100
120
150
40
85
90
100
120
150
40
85
90
100
120
150
40
85
90
100
120
150
40
85
90
100
120
150
40
85
90
100
120
150
40
85
100
120
150
40
85
100
120

50/50
85/85
85/85
85/85

50/50
90/90
90/90
90/90
90/90
100/100

60/60
100/100
100/100
100/100
120/120
120/120
120/120

60/60
100/100
100/100
100/100
150/150
150/150
150/150
150/150

85/85

90/90
100/100 100/100 85/85
90/90
120/120 150/150
100/100 120/120 150/150
120/120 150/150
150/150

90/90
100/100 100/100 50/50
90/90
120/120 150/150 150/150
100/100 120/120 150/150 150/150
120/120 150/150 150/150
150/150 150/150

85/85

90/90
100/100 100/100 50/50
90/90
120/120 150/150 150/150
100/100 120/120 150/150 150/150
120/120 150/150 150/150
150/150 150/150

85/85

90/90
100/100 100/100 85/85
90/90
120/120 150/150
100/100 120/120 150/150
120/120 150/150
150/150

90/90
100/100 100/100 50/50
90/90
120/120 150/150 150/150
100/100 120/120 150/150 150/150
120/120 150/150 150/150
150/150 150/150

85/85

90/90
100/100 100/100 85/85
90/90
120/120 150/150
100/100 120/120 150/150
120/120 150/150
150/150

90/90
100/100 100/100 50/50
90/90
120/120 150/150 150/150
100/100 120/120 150/150 150/150
120/120 150/150 150/150
150/150 150/150

85/85

90/90
100/100 100/100 50/50
90/90
120/120 150/150 150/150
100/100 120/120 150/150 150/150
120/120 150/150 150/150
150/150 150/150
10/150
10/150
10/150
10/150

50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
10/150
10/150
10/150
10/200
10/200

50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
15/150
15/150
15/150
15/150
10/150
10/150
10/150
10/150

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

558

Version : 1.2

02/03/2012

557E4200

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NG160, TM-D


Downstream: iC60

380-415 V
Upstream

NG160E

NG160N

Breaking capacity (kA)

16

25

Trip unit

TM-D

TM-D

Downstream
Rating (A)

63

80

100

125

160

63

80

100

125

160

15/15
15/15
15/15
15/15
15/15
8/15
8/15
6/15

10/20
6/20
10/20
6/20
4/20

15/20
6/20
15/20
6/20
4/20
4/20

20/20
20/20
20/20
20/20
7/20
7/20
5/20

10/25
6/25
4/25

15/25
6/25
4/25
4/25

25/25
25/25
7/25
7/25
5/25

10/25
6/25
4/25

15/25
6/25
4/25
4/25

25/25
25/25
7/25
7/25
5/25

20/20
20/20
20/20
20/20
20/20
8/20
8/20
6/20
25/25
25/25
25/25
8/25
8/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25

20/20
20/20
20/20
20/20
20/20
8/20
8/20
6/20
25/25
25/25
25/25
8/25
8/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N

iC60H

iC60L

y 20 A
25 A
y 20 A
25 A
32 A
40 A
50 A
63 A
y 20 A
25 A
32 A
40 A
50 A
63 A
y 20 A
25 A
32 A
40 A
50 A
63 A

6
6
10
10
10
10
10
10
15
15
15
15
15
15
25
25
20
20
15
15

10/15
6/15
10/15
6/15
4/15

15/15
6/15
15/15
6/15
4/15
4/15

15/15
15/15
15/15
15/15
7/15
7/15
5/15

15/15
15/15
15/15
15/15
15/15
8/15
8/15
6/15

Upstream

NG160H

Breaking capacity (kA)

36

Trip unit

TM-D

Downstream
Rating (A)

63

80

100

125

160

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N

iC60H

iC60L

y 20 A
25 A
y 20 A
25 A
32 A
40 A
50 A
63 A
y 20 A
25 A
32 A
40 A
50 A
63 A
y 20 A
25 A
32 A
40 A
50 A
63 A

6
6
10
10
10
10
10
10
15
15
15
15
15
15
25
25
20
20
15
15

10/20
6/20
10/20
6/20
4/20

15/20
6/20
15/20
6/20
4/20
4/20

20/20
20/20
20/20
20/20
7/20
7/20
5/20

10/25
6/25
4/25

15/25
6/25
4/25
4/25

25/25
25/25
7/25
7/25
5/25

10/25
6/25
4/25

15/25
6/25
4/25
4/25

25/25
25/25
7/25
7/25
5/25

20/20
20/20
20/20
20/20
20/20
8/20
8/20
6/20
25/25
25/25
25/25
8/25
8/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25

20/20
20/20
20/20
20/20
20/20
8/20
8/20
6/20
25/25
25/25
25/25
8/25
8/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576..

557E4200

Version : 1.2

02/03/2012

559

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX160, NSX250, TM-D


Downstream: iC60, C120, NG125

380-415 V
Upstream

NSX160B

NSX160F

NSX160N

NSX160H

NSX160S

NSX160L

Breaking capacity (kA)

25

36

50

70

100

150

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

TM-D

Downstream
Rating (A)

80-100

125-160 80-100

125-160 80-100

125-160 80-100

125-160 80-100

125-160 80-100

125-160

15/15
10/10
25/25
36/36
30/30
36/36
36/36
30/30
25/25

15/15
10/10
30/30
40/40
30/30
40/40
40/40
30/30
25/25

15/15
10/10
30/30
40/40
30/30
40/40
40/40
30/30
25/25

15/15
10/10
30/30
40/40
30/30
40/40
40/40
30/30
25/25

15/15
10/10
30/30
40/40
30/30
40/40
40/40
30/30
25/25

36/36

36/36

36/36

36/36

70/70

50/50

50/50

50/50

100/100

70/70

100/100

150/150

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a

6
6
iC60N
10
iC60H
y 40 A
15
50-63 A
15
iC60L
y 25 A
25
32-40 A
20
50-63 A
15
C120N/H y 40 A
10/15
50 to 125 A 10/15
NG125N y 40 A
25
50 to 125 A 25
NG125H y 40 A
36
50 to 80 A
36
NG125L y 40 A
50
50 to 80 A
50
y 25 A
32 to 63 A

15/15
10/10
20/20
25/25
25/25
25/25
25/25
25/25

Upstream

NSX250B

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

25

36

50

70

100

150

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

TM-D

200-250

200-250

200-250

200-250

200-250

200-250

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
36/36
50/50

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
36/36
50/50
70/70

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
50/50
70/70
100/100

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
70/70
100/100
150/150

Downstream
Rating (A)

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N
iC60H
iC60L

C120N/H
NG125N
NG125H
NG125L

y 25 A
32 to 63 A
y 40 A
50-63 A
y 40 A
50-63 A
y 25 A
32-40 A
50-63 A

6
6
10
10
15
15
25
20
15
10/15
25
36
50

15/15
10/10
20/20
20/20
25/25
25/25
25/25
25/25
25/25

15/15
10/10
25/25
25/25
30/30
25/25
30/30
30/30
25/25
25/25
36/36

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

560

Version : 1.2

02/03/2012

557E4200

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX100, NSX160, Micrologic


Downstream: iC60, C120, NG125

380-415 V
Upstream

NSX100B

NSX100F

NSX100N

NSX100H

NSX100S

NSX100L

Breaking capacity (kA)

25

36

50

70

100

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

40

40

40

100

40

100

40

100

40

100

15/15

15/15
10/10
30/30
30/30

20/20

20/20
15/15
30/30
30/30

20/20

20/20
15/15
30/30
30/30

20/20

20/20
15/15
30/30
30/30

Downstream
Rating (A)

100

100

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N

iC60H

iC60L

y 25 A
32 to 63 A
y 25 A
32-40 A
50-63 A
y 25 A
32-40 A
50-63 A
y 25 A
32-40 A
50-63 A

6
6
10
10
10
15
15
15
25
20
15

15/15
20/20

25/25

15/15
10/10
20/20
20/20
25/25
25/25

15/15
25/25

15/15
10/10
25/25
25/25

30/30

30/30

30/30

30/30

36/36

36/36
36/36

40/40

40/40
40/40

40/40

40/40
40/40

40/40

40/40
40/40

40/40

40/40
40/40

36/36

36/36
36/36

40/40

40/40
40/40

40/40

40/40
40/40

40/40

40/40
40/40

40/40

40/40
40/40

25/25

Upstream

NSX160B

NSX160F

NSX160N

NSX160H

NSX160S

NSX160L

Breaking capacity (kA)

25

36

50

70

100

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

80

80

80

160

80

160

80

160

80

160

15/15
10/10

15/15
10/10
10/10
25/25
25/25
40/40
30/30
30/30
40/40
40/40
30/30
30/30

20/20
15/15

20/20
15/15
15/15
25/25
25/25
40/40
30/30
30/30
40/40
40/40
30/30
30/30

20/20
15/15

20/20
15/15
15/15
25/25
25/25
40/40
30/30
30/30
40/40
40/40
30/30
30/30

20/20
15/15

20/20
15/15
15/15
25/25
25/25
40/40
30/30
30/30
40/40
40/40
30/30
30/30

Downstream
Rating (A)

160

160

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a

iC60N
iC60H

iC60L

y 25 A
32 to 50 A
63 A
y 50 A
63 A
y 40 A
50 A
63 A
y 25 A
32-40 A
50 A
63 A

6
6
6
10
10
15
15
15
25
20
15
15

15/15
10/10
20/20
25/25
25/25

25/25
25/25

15/15
10/10
10/10
20/20
20/20
25/25
25/25
25/25
25/25
25/25
25/25

15/15
10/10
25/25
36/36
30/30
36/36
36/36
30/30

15/15
10/10
10/10
25/25
25/25
36/36
30/30
30/30
36/36
36/36
30/30
30/30

25/25
40/40
30/30
40/40
40/40
30/30

25/25
40/40
30/30
40/40
40/40
30/30

25/25
40/40
30/30
40/40
40/40
30/30

25/25
40/40
30/30
40/40
40/40
30/30

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

557E4200

Version : 1.2

02/03/2012

561

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX250, Micrologic, TM-D


Downstream: iC60, C120, NG125, NG160,
NSC100, NSX100

380-415 V
Upstream

NSX250B

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

25

36

50

70

100

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

250

250

250

250

250

250

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
36/36
50/50

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
36/36
50/50
70/70

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
36/36
50/50
100/100

15/15
10/10
30/30
25/25
30/30
25/25
30/30
30/30
25/25
25/25
70/70
100/100
150/150

Downstream
Rating (A)

Breaking capacity Reinforced breaking capacity (kA)


(kA)
iC60a
iC60N
iC60H
iC60L

y 25 A
32 to 63 A
y 40 A
50-63 A
y 40 A
50-63 A
y 25 A
32-40 A
50-63 A

C120N/H
NG125N
NG125H
NG125L
NG125LMA

6
6
10
10
15
15
25
20
15
10/15
25
36
50

15/15
10/10
20/20
20/20
25/25
25/25

15/15
10/10
25/25
25/25
30/30
25/25
30/30
30/30
25/25
25/25
36/36

25/25
25/25
25/25

Upstream

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

36

50

70

100

150

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

Downstream
Rating (A)

160

200-250

160

200-250

160

200-250

160

200-250

160

200-250

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NG160E
NG160N
NG160H
NSC100N 16-100 A
NSX100B, y 25 A
TM-D
40-100 A
NSX100F, y 25 A
TM-D
40-100 A
NSX100N, y 25 A
TM-D
40-100 A
NSX100H, y 25 A
TM-D
40-100 A
NSX100S, y 25 A
TM-D
40-100 A
NSX100B Micrologic
NSX100F Micrologic
NSX100N Micrologic
NSX100H Micrologic
NSX100S Micrologic

16
25
36
18
25
25
36
36
50
50
70
70
100
100
25
36
50
70
100

25/25
36/36
36/36
36/36
36/36

36/36

30/30
36/36
50/50
50/50
36/36
36/36
50/50
36/50

30/30
50/50
50/50
50/50
50/50
36/50
70/70
36/70
70/70
36/70

30/30
50/50
50/50
50/50
50/50
36/50
100/100
36/100
100/100
36/100
100/100
36/100

36/36
36/50

36/50
36/70
36/70

36/50
36/100
36/100
36/100

30/30
50/50
50/50
50/50
50/50
36/50
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/50
36/150
36/150
36/150
36/150

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

562

Version : 1.2

02/03/2012

557E4200

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX400-630, Micrologic


Downstream: NG160, NSC100, NSX100-250

380-415 V
Upstream

NSX400
F
N

NSX630
F
N

Breaking capacity (kA)

36

70

100

150

36

50

70

100

150

Trip unit

Micrologic

50

Micrologic

Downstream
Rating (A)

400

400

400

400

400

630

630

630

630

630

25/25
36/36

30/30
36/36
50/50
36/36
36/36

30/30
50/50
50/50
50/50
50/50

30/30
50/50
50/50
50/50
50/50

30/30
50/50
50/50
50/50
50/50

50/50

70/70

100/100

150/150

70/70

100/100

150/150

100/100

150/150

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NG160E
NG160N
NG160H
NSC100N
NSX100B,
TM-D
NSX100F,
TM-D
NSX100N,
TM-D
NSX100H,
TM-D
NSX100S,
TM-D
NSX160B,
TM-D
NSX160F,
TM-D
NSX160N,
TM-D
NSX160H,
TM-D
NSX160S,
TM-D
NSX250B,
TM-D
NSX250F,
TM-D
NSX250N,
TM-D
NSX250H,
TM-D
NSX250S,
TM-D
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S

16-100 A

16
25
36
18
25

25/25
36/36
36/36
36/36

36

30/30
36/36
50/50
36/36
36/36

30/30
50/50
50/50
50/50
50/50

30/30
50/50
50/50
50/50
50/50

30/30
50/50
50/50
50/50
50/50

50/50

70/70

100/100

150/150

70/70

100/100

150/150

100/100

150/150

50
70
100
25

36/36
36/36

150/150
36/36

36

36/36

50/50

50/50

50/50

50/50

70/70

100/100

150/150

70/70

100/100

150/150

100/100

150/150

50
70
100

150/150
36/36

36/36

50/50

50/50

50/50

50/50

70/70

100/100

150/150

70/70

100/100

150/150

100/100

150/150

150/150

25

150/150
36/36

36

36/36

50/50

50/50

50/50

50/50

70/70

100/100

150/150

70/70

100/100

150/150

100/100

150/150

50
70
100
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic

25
36
50
70
100
25
36
50
70
100
25
36
50
70
100

150/150
36/36

50/50
50/50

50/50
70/70
70/70

50/50
100/100
100/100
100/100

36/36

50/50
50/50

50/50
70/70
70/70

50/50
100/100
100/100
100/100

50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150

36/36

50/50
50/50

50/50
70/70
70/70

50/50
100/100
100/100
100/100

36/36

50/50
50/50

50/50
70/70
70/70

50/50
100/100
100/100
100/100

36/36

50/50
50/50

50/50
70/70
70/70

50/50
100/100
100/100
100/100

50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

557E4200

Version : 1.2

02/03/2012

563

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX250, Micrologic


Downstream: NG160, NSC100, NSX100

380-415 V
Upstream

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

36

50

70

100

150

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

250

250

250

250

250

30/30
36/36
50/50
50/50
36/36
36/36
50/50
36/50

30/30
50/50
50/50
50/50
50/50
36/50
70/70
36/70
70/70
36/70

30/30
50/50
50/50
50/50
50/50
36/50
100/100
36/100
100/100
36/100
100/100
36/100

36/36
36/50

36/50
36/70
36/70

36/50
36/100
36/100
36/100

30/30
50/50
50/50
50/50
50/50
36/50
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/50
36/150
36/150
36/150
36/150

Downstream
Rating (A)

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NG160E
NG160N
NG160H
NSC100N 16-100 A
NSX100B, y 25 A
TM-D
40-100 A
NSX100F, y 25 A
TM-D
40-100 A
NSX100N, y 25 A
TM-D
40-100 A
NSX100H, y 25 A
TM-D
40-100 A
NSX100S, y 25 A
TM-D
40-100 A
NSX100B Micrologic
NSX100F Micrologic
NSX100N Micrologic
NSX100H Micrologic
NSX100S Micrologic

16
25
36
18
25
25
36
36
50
50
70
70
100
100
25
36
50
70
100

25/25
36/36
36/36
36/36
36/36

36/36

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

564

Version : 1.2

02/03/2012

557E4200

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NS800-1000-1600, Micrologic


Downstream: NSX100-630

380-415 V
Upstream

NS800
N

LB

NS1000
N
H

NS1250
N
H

NS1600
N
H

Breaking capacity (kA)

50

70

150

200

50

150

50

50

Trip unit

Micrologic

70

Micrologic

70

70

Micrologic

Micrologic

Downstream
Rating (A)

800

800

800

800

1000

1000

1000

1250

1250

1600

1600

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NSX100B,
TM-D/Micrologic
NSX100F,
TM-D/Micrologic
NSX100N,
TM-D/Micrologic
NSX100H,
TM-D/Micrologic
NSX100S,
TM-D/Micrologic
NSX100L,
TM-D/ Micrologic
NSX160B,
TM-D/ Micrologic
NSX160F,
TM-D/Micrologic
NSX160N,
TM-D/Micrologic
NSX160H,
TM-D/Micrologic
NSX160S,
TM-D/Micrologic
NSX160L,
TM-D/Micrologic
NSX250B,
TM-D/Micrologic
NSX250F,
TM-D/ Micrologic
NSX250N,
TM-D/Micrologic
NSX250H,
TM-D/ Micrologic
NSX250S,
TM-D/Micrologic
NSX250L,
TM-D/Micrologic
NSX400F Micrologic
NSX400N Micrologic
NSX400H Micrologic
NSX400S Micrologic
NSX400L Micrologic
NSX630F Micrologic
NSX630N Micrologic
NSX630H Micrologic
NSX630S Micrologic

25

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

36

50/50

70/70

150/150

150/150

50/50

70/70

150/150

50/50

70/70

50/50

70/70

70/70

150/150

150/150

70/70

150/150

70

150/150

150/150

150/150

100

150/150

200/200

150/150

50

150

70/70

70/70

200/200

25

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

36

50/50

70/70

150/150

150/150

50/50

70/70

150/150

50/50

70/70

50/50

70/70

70/70

150/150

150/150

70/70

150/150

70

150/150

150/150

150/150

100

150/150

200/200

150/150

50

150

70/70

70/70

200/200

25

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

36

50/50

70/70

150/150

150/150

50/50

70/70

150/150

50/50

70/70

50/50

70/70

70/70

150/150

150/150

70/70

150/150

70

150/150

150/150

150/150

100

150/150

200/200

150/150

50

150
36
50
70
100
150
36
50
70
100

70/70

70/70

200/200
50/50

70/70
70/70

10/150
10/150
10/150
10/150

10/150
10/150
10/150
10/200
10/200

50/50

70/70
70/70

15/150
15/150
15/150
15/150

50/50

70/70
70/70

50/50

70/70
70/70

50/50

65/70
65/70

10/150
10/150
10/150
10/150

50/50

65/70
65/70

50/50

65/70
65/70

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

557E4200

Version : 1.2

02/03/2012

565

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX250, TM-D, Micrologic


Downstream: NSX100

440 V
Upstream

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

35

50

65

90

130

Trip unit

TM-D

TM-D

TM-D

TM-D

TM-D

Downstream
Rating (A)

200

250

200

250

200

250

200

250

200

250

50/50
35/50
130/130
35/130
130/130
35/130
130/130
35/130
130/130
35/130
35/50
35/50
35/130
35/130
35/130

50/50
35/50
130/130
35/130
130/130
35/130
130/130
35/130
130/130
35/130
35/50
35/50
35/130
35/130
35/130

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NSX100B, y 25 A
TM-D
40-100 A
NSX100F, y 25 A
TM-D
40-100 A
NSX100N, y 25 A
TM-D
40-100 A
NSX100H, y 25 A
TM-D
40-100 A
NSX100S, y 25 A
TM-D
40-100 A
NSX100B Micrologic
NSX100F Micrologic
NSX100N Micrologic
NSX100H Micrologic
NSX100S Micrologic

20
20
35
35
50
50
65
65
90
90
20
35
50
65
90

35/35
35/35

35/35
35/35

35/35
35/35
35/35
35/35

35/35
35/35
35/35
35/35

50/50
35/50
65/65
35/65
65/65
35/65

50/50
35/50
65/65
35/65
65/65
35/65

50/50
35/50
90/90
35/90
90/90
35/90
90/90
35/90

50/50
35/50
90/90
35/90
90/90
35/90
90/90
35/90

35/35

35/35

35/35
35/50

35/35
35/50

35/50
35/50
35/65

35/50
35/50
35/65

35/50
35/50
35/90
35/90

35/50
35/50
35/90
35/90

Upstream

NSX250F

NSX250N

NSX250H

NSX250S

NSX250L

Breaking capacity (kA)

35

50

65

90

130

Trip unit

Micrologic

Micrologic

Micrologic

Micrologic

Micrologic

250

250

250

250

250

50/50
35/50
130/130
35/130
130/130
35/130
130/130
35/130
130/130
35/130
35/50
35/50
35/130
35/130
35/130

Downstream
Rating (A)

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NSX100B, y 25 A
TM-D
40-100 A
NSX100F, y 25 A
TM-D
40-100 A
NSX100N, y 25 A
TM-D
40-100 A
NSX100H, y 25 A
TM-D
40-100 A
NSX100S, y 25 A
TM-D
40-100 A
NSX100B Micrologic
NSX100F Micrologic
NSX100N Micrologic
NSX100H Micrologic
NSX100S Micrologic

20
20
35
35
50
50
65
65
90
90
20
35
50
65
90

35/35
35/35

50/50
35/50
50/50
35/50
50/50
35/50

50/50
35/50
65/65
35/65
65/65
35/65

50/50
35/50
90/90
35/90
90/90
35/90
90/90
35/90

35/35

35/35
35/35

35/50
35/50
35/65

35/50
35/50
35/90
35/90

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

566

Version : 1.2

02/03/2012

557E4200

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NSX400-630, Micrologic


Downstream: NSX100-250

440 V
Upstream

NSX400
F
N

NSX630
F
N

Breaking capacity (kA)

30

65

90

130

30

42

65

90

130

Trip unit

Micrologic

42

Micrologic

Downstream
Rating (A)

400

400

400

400

400

630

630

630

630

630

50/50
130/130
130/130
130/130
130/130
50/50
130/130
130/130
130/130
130/130

30/30

30/30
42/42

50/50
65/65
65/65

50/50
90/90
90/90
90/90

30/30

30/30
42/42

50/50
65/65
65/65

50/50
90/90
90/90
90/90

35/35

30/30
42/42

50/50
65/65
65/65

50/50
90/90
90/90
90/90

50/50
130/130
130/130
130/130
130/130
50/50
130/130
130/130
130/130
130/130
50/50
130/130
130/130
130/130
130/130

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S

Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic

20
35
50
65
90
20
35
50
65
90
20
35
50
65
90

30/30

30/30
42/42

50/50
65/65
65/65

50/50
90/90
90/90
90/90

30/30

30/30
42/42

50/50
65/65
65/65

50/50
90/90
90/90
90/90

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

557E4200

Version : 1.2

02/03/2012

567

Cascading and enhanced


discrimination

Complementary
technical information

Upstream: NS800-1000-1600, Micrologic


Downstream: NSX100-630

440 V
Upstream

NS800
N

LB

Breaking capacity (kA)

50

65

130

200

Trip unit

Micrologic

NS1000
N
H

50

130

65

Micrologic

NS1250
N
H

NS1600
N
H

50

50

65

65

Micrologic

Micrologic

Downstream
Rating (A)

800

800

800

800

1000

1000

1000

1250

1250

1600

1600

Breaking capacity Reinforced breaking capacity (kA)


(kA)
NSX100B,
TM-D/Micrologic
NSX100F,
TM-D/Micrologic
NSX100N,
TM-D/Micrologic
NSX100H,
TM-D/Micrologic
NSX100S,
TM-D/Micrologic
NSX100L,
TM-D/Micrologic
NSX160B,
TM-D/Micrologic
NSX160F,
TM-D/Micrologic
NSX160N,
TM-D/Micrologic
NSX160H,
TM-D/Micrologic
NSX160S,
TM-D/Micrologic
NSX160L,
TM-D/Micrologic
NSX250B,
TM-D/Micrologic
NSX250F,
TM-D/Micrologic
NSX250N,
TM-D/Micrologic
NSX250H,
TM-D/Micrologic
NSX250S,
TM-D/Micrologic
NSX250L,
TM-D/Micrologic
NSX400F Micrologic
NSX400N Micrologic
NSX400H Micrologic
NSX400S Micrologic
NSX400L Micrologic
NSX630F Micrologic
NSX630N Micrologic
NSX630H Micrologic
NSX630S Micrologic

20

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

35

50/50

65/65

130/130

130/130

50/50

65/65

130/130

50/50

65/65

50/50

65/65

65/65

130/130

130/130

65/65

130/130

65

130/130

130/130

130/130

90

130/130

200/200

130/130

50

130

65/65

65/65

200/200

20

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

35

50/50

65/65

130/130

130/130

50/50

65/65

130/130

50/50

65/65

50/50

65/65

65/65

130/130

130/130

65/65

130/130

65

130/130

130/130

130/130

90

130/130

200/200

130/130

50

130

65/65

65/65

200/200

20

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

50/50

35

50/50

65/65

130/130

130/130

50/50

65/65

130/130

50/50

65/65

50/50

65/65

65/65

130/130

130/130

65/65

130/130

65

130/130

130/130

130/130

90

130/130

200/200

130/130

50

130
30
42
65
90
130
30
42
65
90

65/65

65/65

200/200
50/50

65/65
65/65

10/130
10/130
10/130
10/130

10/200
10/200
10/200
10/200
10/200

50/50

65/65
65/65

15/130
15/130
15/130
15/130

50/50

65/65
65/65

50/50

65/65
65/65

50/50

65/65
65/65

10/130
10/130
10/130
10/130

50/50

65/65
65/65

50/50

65/65
65/65

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569 and 557E4305.indd/576.

568

Version : 1.2

02/03/2012

557E4200

Complementary
technical information

Coordination between circuit


breakers
Discrimination (Selectivity)

E002487-37.eps

IEC/EN 60947-2
What is discrimination?

It is the coordination of automatic cut-off devices for a fault that occurs at any point in
the network to be eliminated by the upstream circuit breaker, the circuit breaker that
is immediately upstream of the fault and by that circuit breaker alone!

DB403499.eps

Continuity of service

Discrimination is an essential element that must be taken into account as early as in


the design of a low voltage installation to enable continuity of the electricity service.

Production and safety

Discrimination provides much convenience for all users, but it is an essential


requirement when continuity of service is of utmost importance.
Discrimination means that only the part with the fault is disconnected. It enables:
bb continuity of supply for adjacent circuits,
bb localization of the faulty circuit.
D1 and D2 in series.

For some installations or installation parts:


bb operating theatre in clinics and hospitals,
bb marine,
bb safety equipment,
bb production site.
The requirements for continuous electricity often make it necessary to verify the
discrimination between upstream and downstream protection devices.
If there is a total lack of discrimination, it will be necessary to try to achieve partial
discrimination. Likewise, if there is a limit to the level of discrimination and this
proves satisfactory in the majority of cases, it can still be attempted to make it total.
Of course, any modification must be made while observing the following main
parameters:
bb protection of personnel,
bb are the thermal stresses I2t of the cables always taken into account?
bb are the breaking capacities of the devices higher than the prospective Isc?
Finally, when it is not possible to achieve discrimination and it is essential for the
correct operation of the installation, the installation of uninterruptible power supplies
(UPS) must be considered. Generator units, inverters, etc. are then used.
There are several types of discrimination that can be used separately or together.
For protection against overcurrent, this generally concerns current discrimination
and time discrimination.
The principle is as follows.

557E4300

Version : 1.3

02/03/2012

569

Complementary
technical information

Coordination between circuit


breakers
Discrimination (Selectivity)

DB403501.eps

Current and energy discrimination

Discrimination involves ensuring coordination between two circuit breakers in series,


so that, in the event of a fault, only one circuit breaker, located immediately upstream
of the fault, trips. A discrimination current Is is defined so that:
bb Ifault < Is: only D2 eliminates the fault, discrimination is ensured,
bb Ifault > Is: both circuit breakers may trip, discrimination is not ensured.

Slight overcurrent or overload

Under the effect of an abnormal inrush current, for example an increase in the
resistive torque of a motor, the current going through the circuit is higher than the
rated current. These currents may damage the installation (risk of an electrical fire).
Devices to protect against overcurrent can be characterized by their operating
curves as a function of prospective current Ip:
bb the operating curve is time-based when the breaking time is greater than 50 ms
(curve t = f (Ip). Discrimination is achieved if the ln upstream / In downstream
operation threshold ratio is > 1.3 and if the current offset of the magnetic curves is
observed.

DB403503.eps

This is current discrimination

The greater the difference between the ratings of the upstream and downstream
circuit breakers, the more extensive the discrimination.

Short circuit

For example when there is contact between two phases we are faced with a full
insulation fault which risks damaging the installation.
The function that makes it possible to protect against this type of fault is magnetic
protection.
To ensure discrimination, we must maintain a ratio between the upstream and
downstream protection devices. This is energy discrimination.
bb Energy: when the intervention time is less than 50 ms and more particularly less
than the time of one half wave (10 ms) of current with limiting circuit breakers.

DB403505.eps

This is energy discrimination

570

Version : 1.3

02/03/2012

557E4300

Coordination between circuit


breakers

Complementary
technical information

Discrimination (Selectivity)

DB124205.eps

Time discrimination

The principle is based on the time difference (t) of the upstream magnetic curve.
To achieve this, it is necessary to have an upstream circuit breaker with time-delay
bands.
The delay introduced must make it possible to improve discrimination without
endangering the cable or busbars which would then have to withstand the
overcurrent for longer (greater thermal effects I2t and electrodynamic stresses).

Total or partial discrimination

DB403507.eps

Discrimination may be partial or total, up to the breaking capacity of the downstream


circuit breaker. For total discrimination, the characteristics of the upstream device
must be higher than those of the downstream device (higher than the breaking
capacity of the downstream circuit breaker MCCB).

Standard IEC 60947-2 on industrial circuit breakers, and in particular Appendix A,


deals with coordination between a circuit-breaker and another device to protect
against short circuits combined in the same circuit.
This protection device may be a fuse or another circuit breaker.

557E4300

Version : 1.3

02/03/2012

571

Coordination between circuit


breakers

Complementary
technical information

Discrimination (Selectivity)

Discrimination between modular circuit breakers

DB403509.eps

We use two types of discrimination when these circuit breakers are combined:
bb current discrimination,
bb energy discrimination.
For discrimination to be ensured whatever the prospective fault current, 3 conditions
have to be fulfilled:
bb the upstream and downstream circuit breakers must have different ratings
(ratio > 1.3),
bb the envelope of their magnetic curves must be different,
bb the energy allowed to pass through the downstream circuit breaker when it cuts off
must still be less than the operating energy of the upstream trip.

Example

DB403510.eps

bb Let us take the example of a single phase network where we have a 32 A curve D
circuit breaker in series with a 10 A curve D circuit breaker:
vv the 32 A circuit breaker protects the 62 cables and the 10 A circuit breaker protects
the 1.52 cables. This combination allows discrimination, but up to what threshold?
vv if current discrimination is considered (t = f (Ip)) it can be seen that the tripping
curve of the downstream circuit breaker is well below the non-tripping curve of the
upstream circuit breaker,
vv furthermore, each circuit breaker is well below the maximum stress permitted by
the cables.

When considering energy discrimination, it is necessary to compare the maximum

.stresses characterized by the integrals ft relative to the development of the arc in the
DB403512.eps

downstream device and by the sensitivity of the trip unit, still in ft, of the upstream
device (curves I2t = f (Ip)).

572

Version : 1.3

02/03/2012

557E4300

Complementary
technical information

Coordination between circuit


breakers
Discrimination (Selectivity)

Discrimination between Compact NSX upstream


and modular circuit breakers downstream

Compact NSX circuit breakers have been designed to ensure total discrimination
with Acti9 range.
bb Total discrimination between Compact NSX 100 A with electronic trip unit and
Acti9 circuit breaker up to 40 A.
bb Total discrimination between Compact NSX u 160 A with TMD trip unit u125 A or
electronic trip unit and Acti9 up to 63 A.

Discrimination between Compact NSX circuit


breakers
DB115814.eps

Thanks to the Roto-Active breaking principle in the Compact NSX, a combination of


Schneider Electric circuit breakers provides an exceptional level of discrimination
between protection devices.
This performance is due to the combination and optimization of 3 principles:
bb current discrimination,
bb energy discrimination,
bb time discrimination.
Protection against overloads: current discrimination
The protection is selective if the ratio between the setting thresholds is higher than 1.6 (in the
case of two distribution circuit breakers).

Protection against weak short circuits: time discrimination


Tripping of the upstream device has a slight time delay; tripping of the downstream device is
faster.
The protection is selective if the ratio between the short-circuit protection thresholds is no less
than 1.5.

Protection against high short circuits: energy discrimination


This principle combines the exceptional limiting power of the Compact NSX devices and reflex
release, sensitive to the energy dissipated by the short circuit in the device.
When a short circuit is high, if it is seen by two devices, the downstream device limits it greatly.
The energy dissipated in the upstream device is insufficient to cause it to trip: there is
discrimination whatever the value of the short circuit.
The range has been designed to ensure energy discrimination between NSX630/NSX250/
NSX100 or NSX400/NSX160.

Discrimination between Masterpact or Compact NS


u 630 A upstream and Compact NSX downstream

Thanks to their high-performance control units and a very innovative design,


Masterpact and Compact NS u 630 A devices offer, as standard, a very high level of
discrimination with downstream Compact NSX up to 630 A
Respect the basic rules of discrimination for overload and short-circuit, or check that
curves do not overlap with Ecodial software.
Check the discrimination limit in tables for high short-circuit current or when using
limiter circuit breakers (Masterpact NT L1 or Compact NS L or LB) upstream.

Discrimination between Masterpact or Compact NS


u 630 A upstream and downstream

The utilization category of these devices (excepted limiters ones) is B according to


IEC 60947 standard. Discrimination is ensured by a combination of current
discrimination and time discrimination.
Respect the basic rules of discrimination for overload and short-circuit, or check that
curves do not overlap with Ecodial software.
Check the discrimination limit in tables for high short-circuit current or when using
limiter circuit breakers (Masterpact NT L1 or Compact NS L or LB).

Basic rules of discrimination for overload and shortcircuit


Upstream
TM
Micrologic

557E4300

Version : 1.3

Upstream

Thermal protection

Magnetic protection

Ir upstream / Ir downstream

Im upstream / Im downstream

TM or MCB

u 1.6

u2

Micrologic

u 1.6

u 1.5

TM or MCB

u 1.6

u 1.5

Micrologic

u 1.3

u 1.5

02/03/2012

573

Complementary
technical information

Coordination between circuit


breakers
Discrimination (Selectivity)

DB125679.eps

Additional conditions according to the trip units

Short time trip pickup current (Isd)


The tables show the limit of discrimination assuming the short time trip pickup
current Isd = 10 x Ir.
In many cases, when discrimination is total, a different adjustment may be used
provided that the ratio between the magnetic thresholds indicated above is
observed.
When the limit of discrimination indicated in the table is 10 x Ir, the limit of
discrimination is in fact the upstream magnetic threshold Isd.
Instantaneous trip pickup current (Ii)
The tables show the limit of discrimination assuming the instantaneous trip pickup
current set to its maximum value and when it is inhibited (category B circuit breaker
only).
bb When the limit of discrimination indicated in the table is 15 x In of the upstream
device, the limit of discrimination is in fact the instantaneous trip pickup current of the
upstream device.
bb When the upstream device is a type B circuit breaker and the downstream device
is type A, the instantaneous trip pickup current of the upstream device may be set to
below 15 x In as long as it remains higher than the reflex release threshold of the
downstream device.
bb When a Micrologic 5.x is used downstream of a Micrologic 2.x, the downstream
Tsd should be set to band 0 and Ii = Isd.

DB117227.eps

Short time tripping delay (Tsd)


When the upstream and downstream circuit breakers are fitted with a Micrologic 5.x,
6.x, 7.x: trip unit, the minimum non-tripping time of the upstream device must be
greater than the maximum tripping time of the downstream device.

Tsd D1 > Tsd D2 (One band)


I2t Off / On

The tables show the limit of discrimination assuming function I2t OFF. If this is not the
case, the user must verify that the curves do not overlap.
Ground Fault Protection (GFP) (Ig, Tg)
When the upstream and downstream circuit breakers are fitted with a Micrologic 6.x
trip unit, the user must verify current and time discrimination:

current discrimination

The setting of the tripping threshold of the upstream GFP is greater than that of the
downstream GFP. Because of the tolerances on the settings, a difference of 30 %
between the upstream threshold and the downstream threshold is sufficient.

time discrimination

The intentional time-delay setting for the upstream GFP is higher than the opening
time of the downstream protection device. Furthermore, it is essential that the
intentional time-delay applied to the upstream protection device observes the
maximum insulation fault elimination time defined by NEC 230.95 (i.e. 1 s for
3000A).

Ig D1 u 1.3 Ig D2 Tg D1 > Tg D2 (One band)


*GFP : Ground Fault Protection.
DB125678.eps

Residual current devices


Discrimination of residual current devices (RCD) is also necessary to ensure good
continuity of service for the final user. Consequently, any pair of upstream/
downstream residual current devices on the distribution network must meet the
following conditions:
bb the sensitivity of the upstream residual current device must be at least equal to
three times the sensitivity of the downstream residual current device (In D1 u 3 x
In D2),
bb the upstream residual current device must be:
vv of the selective (S) type (or setting) if the downstream residual current device is an
instantaneous type,
vv of the delayed (R) type (or setting) if the downstream residual current device is a
selective type.
The minimum non-tripping time of the upstream device will therefore be greater than
the maximum tripping time of the downstream device for all current values (t (D1) >
t (D2)).

574

Version : 1.3

02/03/2012

557E4300

Coordination between circuit


breakers

Complementary
technical information

Discrimination of modular circuit breakers


Using the discrimination tables

Depending on the network and the type of downstream circuit breaker, the selection
table below indicates which table should be consulted to find out the discrimination
value.
The discrimination values are given in colour-coded tables.
bb For 220-240 V/380-415 V networks:
vv in the case of a 2P downstream circuit breaker in a single-phase network
(220-240 V), refer to the light green tables,
vv in the case of 1P, 1P+N, 3P, 3P+N, 4P and 2P circuit breakers in a two-phase
network (380-415 V), refer to the dark green tables.

Selection table

DB123998.eps

DB123997.eps

Ph/N
220-240 V

Ph/N
220-240 V

Ph/Ph
380-415 V

Ph/Ph
380-415 V

DB123991.eps

DB124079.eps

Type of
Type of Downstream
Downstream protection device
network

DB123996.eps

Upstream network

DB124191.eps

DB123992.eps

1P

1P+N

DB123991.eps

DB124192.eps

2P

DB123993.eps

DB124080.eps

2P

DB123994.eps

DB124081.eps

3P

DB123993.eps

DB123995.eps

4P

3P

3P+N
Note: this selection table shows you the colour.
By taking your downstream protection device, the type of upstream network and its voltage you
can refer to the corresponding discrimination table.

576

Version : 1.2

02/03/2012

557E4305

Coordination between circuit


breakers

Complementary
technical information

Discrimination of modular circuit breakers

DB403514.eps

Example: solution diagram

Upstream we have a NG125N 80 A 2P curve C


and downstream an iC60N 16 A 2P curve C.
The network is 230 V between phase and
neutral.
By referring to the light green table on the
discrimination page for NG125N curve C with
iC60 downstream, we find 1800 amps.

Specifications

We want to achieve continuity of service in the event of a fault downstream of the


NG125N 80 A. This circuit has an Isc of 1 kA under a voltage of 230 V.
By referring to the table for 230 V, 1P+N network, we find that for an upstream
NG125N we can have total discrimination up to 16 A if we use an iC60N 1P+N (up to
25 A with an iC60N 2P).

If the downstream product is replaced by an


iDPN N 16 A 1P+N curve C, you will use the dark
green table for NG125N curve C and iDPN N
1P+N downstream.
The discrimination level is 1100 amps.

Upstream

NG125N/H/L

In (A)

10

16

20

25

32

40

50

63

80

100

125

T
950
210

T
T
1900
670
310
190

T
T
3500
1300
590
290

T
T
10000
4700
1100
510
200

T
T
T
T
3600
1500
890
760

T
T
T
T
13000
2700
1200
770
620

T
T
T
T
T
7200
2700
2000
1600
1100

T
T
T
T
T
9000
5400
3800
2700
1700
1100

T
T
T
T
T
9000
3700
2700
1800
1400
1200
960

T
T
T
T
T
T
6600
4000
3600
2200
2000
1400
1200

T
T
T
T
T
T
T
7200
4600
3600
2600
2300
2000
1700

Curve C
Downstream

2P (220-240 V)
single-phase
network

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

4000

Discrimination limit = 4 kA.

Total discrimination.

Is > Isc
Total discrimination

No discrimination.

557E4305

Version : 1.2

02/03/2012

577

Coordination between circuit


breakers

Complementary
technical information

Discrimination of modular circuit breakers


Contents
Downstream

Upstream

Type

iDPN, iDPN N

iDPN

iDPN N

iC60N/H/L

C120,
NG125

iC60N/H/L

NG125N/H/L,
C120N/H

Curve

B
C
D
B
C
D
B

page 579
page 579
page 579
page 579
page 579
page 579

page 580
page 580
page 580
page 580
page 580
page 580

page 581
page 581
page 581
page 581
page 581
page 581

page 582
page 582
page 582
page 582
page 582
page 582
page
586-587
page
586-587
page
586-587

page 589
page 589
page 589
page 589
page 589
page 589
page
588-589
page
588-589
page
588-589

page 584
page 584
page 584
page 584
page 584
page 584
page
590-591
page
590-591
page
590-591

page 592
page 592
page 592
page 593
page 593
page 593
page
598-605
page
598-605
page
598-605
page
604-605
page
604-605
page
604-605

page 594
page 594
page 594
page 595
page 595
page 595
page
600-601
page
600-601
page
600-601
page
606-607
page
606-607
page
606-607

page 596
page 596
page 596
page 597
page 597
page 597
page
602-603
page
602-603
page
602-603
page
608-609
page
608-609
page
608-609

Discrimination between circuit breakers

In the following tables we show the level of discrimination between two LV circuits
that are protected by modular circuit breakers.
This discrimination will be either:
bb total: represented by a T (up to the breaking capacity of the downstream device),
bb partial: discrimination limit current (Is) indicated. Below this value discrimination is
ensured, above this value the upstream device is also involved in breaking,
bb zero: no discrimination ensured.

578

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: iDPN, iDPN N curve B


Downstream: iDPN/iDPN N curves B, C, D

220-240/380-415 V
Upstream

iDPN, iDPN N
Curve B

In (A)

Downstream

10

16

20

25

32

40

12

20
16

30
30

70
60
40
40

150
110
64
64
64

250
180
140
120
80
80

350
240
190
160
100
100

610
340
280
220
130
130
130

980
450
350
280
160
160
160
160

20

30

70
60

150
110
64
64

250
180
140
120

350
240
190
160
100

610
340
280
220
130

980
450
350
280
160
160

30

70
60

150
110
64

250
180
140
120

350
240
190
160

610
340
280
220
130

980
450
350
280
160

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
iDPN N
Curve B

1
2
3
4
6
10
16
20
25

Discrimination limit (A)


iDPN
iDPN N
Curve C

1
2
3
4
6
10
16

Discrimination limit (A)


iDPN
iDPN N
Curve D

4000

1
2
3
4
6
10

Note: if you cannot find your combination, refer to the selection table on page 576.

Discrimination limit = 4 kA.


No discrimination.

557E4305

Version : 1.2

02/03/2012

579

Discrimination table

Complementary
technical information

Upstream: iDPN, iDPN N curve C


Downstream: iDPN/iDPN N curves B, C, D

220-240/380-415 V
Upstream

iDPN, iDPN N
Curve C

In (A)

Downstream

10

16

20

25

32

40

16

24
24

32
32

70
48
48

180
140
80
80

400
270
210
130
130
130

630
350
290
240
160
160

1200
510
380
320
200
200
200

T
820
630
480
320
260
260
260

T
830
650
510
380
320
320
320
320
320

24

32

70
48

180
140
80

400
270
210
130

630
350
290
240
160

1200
510
380
320
200
200

T
820
630
480
320
260

T
830
650
510
380
320
320

24

32

70
48

180
140
80

400
270
210
130

630
350
290
240
160

1200
510
380
320
200

T
820
630
480
320
260

T
830
650
510
380
320

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
iDPN N
Curve C

1
2
3
4
6
10
16
20

Discrimination limit (A)


iDPN
iDPN N
Curve D

1
2
3
4
6
10
16

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

580

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: iDPN, iDPN N curve D


Downstream: iDPN/iDPN N curves B, C, D

220-240/380-415 V
Upstream

iDPN, iDPN N
Curve D

In (A)

Downstream

10

16

20

25

32

40

24

36
36

70
48

170
130
72

380
250
210
120
120

1200
490
410
330
190
190

T
780
640
500
390
240

T
1100
890
670
520
300
300

T
1600
1400
970
740
580
380
380

T
2300
1900
1400
1000
810
480
480
480
480
480

36
36

70
48

170
130
72

380
250
210
120

1200
490
410
330
190

T
780
640
500
390
240

T
1100
890
670
520
300
300

T
1600
1400
970
740
580
380

T
2300
1900
1400
1000
810
480
480
480

36

70
48

170
130
72

380
250
210

1200
490
410
330
190

T
780
640
500
390
240

T
1100
890
670
520
300
300

T
1600
1400
970
740
580
380

T
2300
1900
1400
1000
810
480
480

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
iDPN N
Curve C

1
2
3
4
6
10
16
20
25
32

Discrimination limit (A)


iDPN
iDPN N
Curve D

1
2
3
4
6
10
16
20
25

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

557E4305

Version : 1.2

02/03/2012

581

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve B


Downstream: iDPN/iDPN N curves B, C, D

220-240/380-415 V
Upstream

iC60N/H/L
Curve B

In (A)

Downstream

10

13

16

20

25

32

40

50

63

12

16
16

30
24
24

60
40
40
40

80
50
50
50

110
90
64
64
64

130
80
80
80
80
80

150
100
100
100
100
100

270
220
210
190
130
130
130

410
300
270
270
240
160
160
160

450
330
300
300
250
200
200
200
200

620
440
410
380
250
250
250
250
250
250

16

30

60
40

80
50

110
90
64
64

130
80
80
80

150
100
100
100
100

270
220
210
190
130

410
300
270
270
240
160

450
330
300
300
250
200

620
440
410
380
250
250
250

30

60

80
50

110
90
64

130
80
80
80

150
100
100
100

270
220
210
190
130

410
300
270
270
240

450
330
300
300
250
200

620
440
410
380
250
250

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
iDPN N
Curve C

1
2
3
4
6
10
16
20

Discrimination limit (A)


iDPN
iDPN N
Curve D

4000

1
2
3
4
6
10
16

Note: if you cannot find your combination, refer to the selection table on page 576.

Discrimination limit = 4 kA.


No discrimination.

582

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve C


Downstream: iDPN/iDPN N curves B, C, D

220-240/380-415 V
iC60N/H/L

Upstream

Curve C
In (A)

Downstream

10

13

16

20

25

32

40

50

63

16

24

32
32

48
48
48

80
80
80
80

100
100
100
100
100

210
130
130
130
130
130

270
160
160
160
160
160

390
300
200
200
200
200
200

540
410
260
260
260
260
260
260

790
540
510
480
320
320
320
320
320

1500
910
750
720
400
400
400
400
400
400

1600
930
760
760
500
500
500
500
500
500

24

32

48
48

80
80
80

100
100
100
100

210
130
130
130
130

270
160
160
160
160

390
300
200
200
200
200

540
410
260
260
260
260

790
540
510
480
320
320
320

1500
910
750
720
400
400
400
400

1600
930
760
760
500
500
500
500
500

24

32

48
48

80
80

100
100
100

210
130
130
130

270
160
160
160

390
300
200
200
200

540
410
260
260
260
260

790
540
510
480
320
320

1500
910
750
720
400
400
400

1600
930
760
760
500
500
500
500

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
iDPN N
Curve C

1
2
3
4
6
10
16
20
25
32

Discrimination limit (A)


iDPN
iDPN N
Curve D

4000

1
2
3
4
6
10
16
20
25

Note: if you cannot find your combination, refer to the selection table on page 576.

Discrimination limit = 4 kA.


No discrimination.

557E4305

Version : 1.2

02/03/2012

583

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve D


Downstream: iDPN/iDPN N curves B, C, D

220-240/380-415 V
Upstream

iC60N/H/L
Curve D

In (A)

Downstream

10

13

16

20

25

32

40

50

63

12

30

50
36

70
48
48

72
72
72
72

120
120
120
120
120

260
160
160
160
160
160

350
190
190
190
190
190

540
390
360
240
240
240

700
510
450
450
300
300
300

1100
700
580
580
380
380
380
380

1500
960
840
780
720
480
480
480
480

2000
1500
1200
1100
1000
600
600
600
600
600

2000
2000
1500
1400
1200
760
760
760
760
760
760

30

50
36

70
48
48

72
72
72
72

120
120
120
120
120

260
160
160
160
160

350
190
190
190
190
190

540
390
360
240
240
240

700
510
450
450
300
300
300

1100
700
580
580
380
380
380
380

1500
960
840
780
720
480
480
480
480

2000
1500
1200
1100
1000
600
600
600
600
600

2000
2000
1500
1400
1200
760
760
760
760
760
760

30

50
36

70
48
48

72
72
72
72

120
120
120
120
120

260
160
160
160
160

350
190
190
190
190
190

540
390
360
240
240
240

700
510
450
450
300
300
300

1100
700
580
580
380
380
380
380

1500
960
840
780
720
480
480
480
480

2000
1500
1200
1100
1000
600
600
600
600
600

2000
2000
1500
1400
1200
760
760
760
760
760
760

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
iDPN N
Curve C

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
iDPN N
Curve D

4000

1
2
3
4
6
10
16
20
25
32
40

Note: if you cannot find your combination, refer to the selection table on page 2.

Discrimination limit = 4 kA.


No discrimination.

584

Version : 1.2

02/03/2012

557E4305

557E4305

Version : 1.2

02/03/2012

585

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve B


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

iC60N/H/L

In (A)

10

13

16

20

25

32

40

50

63

10
10

40
12

60
16
16

T
40
30
30

T
70
60
40
40
40

T
120
90
70
52
52

T
170
130
90
90
64
64

T
210
140
120
80
80
80
80

T
300
200
150
100
100
100
100
100

T
780
370
250
250
190
130
130
130
130

T
1300
520
380
310
290
240
240
160
160
160

T
1700
630
460
380
300
200
200
200
200
200
200

T
4000
960
670
470
440
380
250
250
250
250
250
250

10

40

60
16

T
30

T
70
60
40

T
120
90
70
52

T
170
130
90
90

T
210
160
120
80
80

T
300
200
150
100
100

T
780
370
250
250
190
130

T
1300
520
380
310
290
240
160

T
1700
630
460
380
300
200
200
200

T
4000
960
670
470
440
250
250
250
250

30

50

T
30

T
60
40

T
120
70

T
170
110
90

T
210
140
120
80

T
300
180
150
100

T
780
370
250
220
190

T
1300
520
380
310
240

T
1700
630
460
340
300
200

T
4000
860
670
470
380
250
250

Curve B

Downstream

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25

Discrimination limit (A)


iC60N/H/L
Curve D

0.5
1
2
3
4
6
10
13
16

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

586

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve B


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
iC60N/H/L

Upstream

Curve B
In (A)

Downstream

10

13

16

20

25

32

40

50

63

210
10

T
20

T
20
16

T
60
30
30

T
110
70
40
40
40

T
260
140
90
70
52

T
530
200
130
110
64
64

T
790
250
160
120
80
80
80

T
2000
400
250
180
100
100
100
100

T
T
880
550
370
270
190
130
130
130

T
T
1700
800
520
380
290
240
240
160
160

T
T
2500
1100
630
460
300
200
200
200
200
200

T
T
5300
1400
960
630
440
380
250
250
250
250
250

170

T
20

T
60

T
110
70
40

T
260
140
90
70

T
530
200
130
90

T
790
250
160
120
80

T
2000
400
230
180
100

T
T
880
550
370
230
130

T
T
1700
800
520
380
240
240

T
T
2500
1100
630
410
300
200
200

T
T
5300
1400
860
630
440
380
250
250

T
50

T
110
60

T
260
120

T
530
200
110

T
790
250
140
80

T
2000
350
230
150

T
T
1100
490
310
230

T
T
1700
800
450
330

T
T
2500
960
630
410
200

T
T
5300
1400
860
500
380
250

2P (220-240 V)
single-phase
network

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25

Discrimination limit (A)


iC60N/H/L
Curve D

557E4305

0.5
1
2
3
4
6
10
13
16

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

587

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve C


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

iC60N/H/L

In (A)

10

13

16

20

25

32

40

50

63

60
16

T
24
24

T
32
32

T
70
48
48
48

T
180
140
120
80
80

T
210
160
104
104
104

T
370
220
190
130
130
130

T
590
310
280
240
160
160
160

T
1100
460
380
300
200
200
200
200

T
2400
780
580
430
380
260
260
260
260

T
7000
1200
820
590
480
320
320
320
320
320

T
T
2000
1400
1000
770
680
600
600
400
400
400

T
T
2000
1400
1100
850
500
500
500
500
500
500
500

50
16

T
24

T
32
32

T
70
48

T
180
120
80
80
80

T
210
160
104
104
104

T
370
220
190
130
130
130

T
590
310
280
160
160
160
160

T
1100
460
380
300
200
200
200
200

T
2400
780
480
430
380
260
260
260
260

T
7900
1200
820
590
480
320
320
320
320
320

T
T
2000
1400
1000
770
680
600
400
400
400
400

T
T
2000
1400
1100
850
500
500
500
500
500
500
500

50

T
24

T
32

T
70
48

T
180
120
80

T
210
160
104

T
370
220
130
130
130

T
590
310
240
160
160

T
1100
460
380
300
200
200

T
2400
680
480
430
260
260
260

T
7900
1200
710
590
480
320
320
320

T
T
2000
1400
1000
770
600
600
400
400

T
T
2000
1400
910
760
500
500
500
500
500

Curve C

Downstream

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve D

0.5
1
2
3
4
6
10
13
16
20
25
32

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

588

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve C


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

iC60N/H/L
Curve C

In (A)

Downstream

10

13

16

20

25

32

40

50

63

20

T
20

T
40
24

T
50
32

T
120
70
48
48

T
540
210
140
120
80

T
940
260
180
160
104

T
2700
430
250
220
130
130

T
T
800
450
310
240
160
160

T
T
1500
710
460
350
200
200
200

T
T
3600
1200
680
510
380
260
260
260

T
T
7900
2100
940
770
550
480
320
320
320

T
T
52000
9800
2000
1100
950
760
500
500
400
400

T
T
53000
11000
2000
1300
930
770
680
600
500
500
500

20

T
20

T
40

T
50
32

T
120
70

T
540
210
140
120
80

T
940
260
180
104
104

T
2700
430
250
190
130
130

T
T
660
380
310
160
160
160

T
T
1500
710
460
350
200
200
200

T
T
3600
1200
680
510
260
260
260
260

T
T
7900
2100
940
620
480
480
320
320
320

T
T
60000
9800
2000
1100
850
760
500
500
400
400

T
T
53000
11000
2000
1300
770
770
680
600
500
500
500

T
30

T
50

T
120
48

T
540
210
120

T
940
260
160

T
2700
430
250
190
130

T
T
800
380
280
160

T
T
1500
630
460
300
200

T
T
3600
1200
680
450
260
260

T
T
7900
2100
940
620
480
320
320

T
T
60000
9800
2000
1100
850
760
500
400

T
T
53000
11000
2000
1100
770
680
600
500
500

2P (220-240 V)
single-phase
network

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve D

557E4305

0.5
1
2
3
4
6
10
13
16
20
25
32

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

589

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve D


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

iC60N/H/L

In (A)

10

13

16

20

25

32

40

50

63

20

T
30

T
50
36

T
70
48

T
150
110
72

T
290
210
180
120
120

T
510
300
230
160
160

T
770
450
330
290
190
190

T
2000
730
550
410
360
240
240

T
3900
890
670
560
450
300
300
300

T
52000
1400
1100
840
660
380
380
380
380

T
T
2300
1300
1000
910
720
480
480
480
480

T
T
5000
2800
2000
1300
1100
900
900
600
600
600

T
T
6800
4300
2400
1600
1400
1100
1100
760
760
760
760

20

T
30

T
50
36

T
70
48

T
150
110

T
290
210
120
120
120

T
510
300
230
160
160

T
770
450
330
290
190
190

T
2000
730
550
410
360
240

T
3900
890
670
560
450
300
300

T
60000
1600
1100
710
660
380
380
380

T
T
2300
1300
1000
910
720
480
480
480

T
T
5000
2800
2000
1300
1100
900
900
600
600

T
T
6800
4300
2400
1600
1100
1100
760
760
760
760
760

20

T
30

T
50
36

T
70
48

T
150
110

T
290
210
120

T
510
300
230
160
160

T
770
370
330
190
190

T
2000
640
450
410
240
240

T
3900
890
670
560
450
300
300

T
68000
1600
970
710
580
380
380
380

T
T
2300
1300
1000
810
480
480
480
480

T
T
5000
2800
1600
1300
1100
900
900
600
600

T
T
6800
3800
2400
1600
1100
1100
760
760
760
760
760

Curve D

Downstream

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve D

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

590

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: iC60N/H/L curve D


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

iC60N/H/L
Curve D

In (A)

Downstream

10

13

16

20

25

32

40

50

63

T
50

T
100
50

T
130
80

T
340
150
110

T
1600
350
240
180
120

T
10000
650
370
270
160

T
T
1100
530
370
290
190

T
T
2600
920
640
480
360
240

T
T
5800
1600
890
590
450
450
300

T
T
16000
3800
1400
900
660
580
380
380

T
T
45000
9500
2300
1300
910
810
720
480
480

T
T
T
T
7100
2200
1500
1300
1100
900
900
600

T
T
T
T
12000
2600
1900
1600
1400
1100
760
760
760

T
50

T
100
50

T
130
70

T
340
150

T
1600
350
240
180
120

T
10000
580
370
270
160

T
T
1100
530
370
290
190

T
T
2600
920
640
480
360

T
T
5800
1600
890
590
450
300

T
T
16000
3800
1400
900
660
580
380

T
T
45000
9500
1900
1300
910
810
720
480

T
T
T
T
7100
2200
1500
1300
1100
900
600

T
T
T
T
12000
2600
1900
1600
1400
1100
760
760
760

T
40

T
80
50

T
130
70

T
340
150

T
1600
350
210

T
10000
650
300
230
160

T
T
1200
530
370
190

T
T
2600
920
640
420
240

T
T
5800
1600
890
590
450
300

T
T
16000
3800
1400
900
660
380
380

T
T
45000
9500
1900
1100
910
720
480
480

T
T
T
T
7100
2200
1500
1300
1100
900
600

T
T
T
T
12000
2600
1900
1600
1400
1100
760
760
760

2P (220-240 V)
single-phase
network

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Discrimination limit (A)


iC60N/H/L
Curve D

557E4305

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

591

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve B


Downstream: iDPN curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve B

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

60
40
40
40

130
110
64
64
64

190
150
80
80
80
80

330
230
180
150
100
100

490
280
240
130
130
130
130

2000
560
420
350
260
160
160
160

2800
630
460
360
200
200
200
200
200

T
1100
860
620
470
250
250
250
250
250

T
1700
1500
1000
700
520
320
320
320
320
320

T
3000
2400
1400
1000
770
600
400
400
400
400

T
T
T
2800
1800
1200
940
800
500
500
500

200
60

T
130
110

T
190
150
80

T
330
230
180

T
490
280
240
130

T
2000
560
420
350

T
2800
630
460
360
200

T
T
1100
860
620
380
250

T
T
1700
1500
1000
590
520

T
T
3000
2400
1400
850
770
600

T
T
T
T
2800
1300
1200
940
800

200
60

T
130
110

T
190
150
80

T
330
230
180

T
490
280
240
130

T
2000
560
420
350

T
2800
630
460
360
200

T
T
1100
860
620
380

T
T
1700
1500
1000
590
520

T
T
3000
2400
1400
850
770
600

T
T
T
T
2800
1300
1200
940
800

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
Curve C

1
2
3
4
6
10
16
20
25
32

Discrimination limit (A)


iDPN
Curve D

1
2
3
4
6
10
16
20
25
32

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

592

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve B


Downstream: iDPN N curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve B

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

60
40
40
40

130
110
64
64
64

190
150
80
80
80
80

330
230
180
150
100
100

490
280
240
130
130
130
130

2000
560
420
350
260
160
160
160

2800
630
460
360
200
200
200
200
200

T
1100
860
620
470
250
250
250
250
250

T
1700
1500
1000
700
520
320
320
320
320
320

T
3000
2400
1400
1000
770
600
400
400
400
400

T
T
T
2800
1800
1200
940
800
500
500
500

200
60

T
130
110

T
190
150
80

T
330
230
180

T
490
280
240
130

T
2000
560
420
350

T
2800
630
460
360
200

T
T
1100
860
620
380
250

T
T
1700
1500
1000
590
520

T
T
3000
2400
1400
850
770
600

T
T
6400
6400
2800
1300
1200
940
800

200
60

T
130
110

T
190
150
80

T
330
230
180

T
490
280
240
130

T
2000
560
420
350

T
2800
630
460
360
200

T
T
1100
860
620
380

T
T
1700
1500
1000
590
520

T
T
3000
2400
1400
850
770
600

T
T
6400
6400
2800
1300
1200
940
800

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN N
Curve C

1
2
3
4
6
10
16
20
25
32

Discrimination limit (A)


iDPN N
Curve D

1
2
3
4
6
10
16
20
25
32

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

557E4305

Version : 1.2

02/03/2012

593

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve C


Downstream: iDPN curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve C

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

120
80
80
80

430
270
210
130
130

730
380
290
160
160
160

2300
550
380
320
200
200

T
1600
1200
870
570
450
420

T
1700
1400
880
620
480
320
320

T
T
4900
2200
1400
1000
720
680
640

T
T
T
3700
1900
1300
950
800
800
500

T
T
T
4100
2300
1500
1100
960
640
640
640

T
T
T
T
3800
2200
1600
1300
1200
800
800

T
T
T
T
T
3400
2300
1900
1800
1500
1000

120
80
80

430
270
210
130

730
380
290
160
160

2300
550
380
320
200
200

T
1600
1200
870
570
450

T
1700
1400
880
620
480
320

T
T
4900
2200
1400
1000
720
680

T
T
T
3700
1900
1300
950
800
800

T
T
T
4100
2300
1500
1100
960
640
640

T
T
T
T
3800
2200
1600
1300
1200
800
800

T
T
T
T
T
3400
2300
1900
1800
1500
1000

120
80

430
270
210
130

730
380
290
160

2300
550
380
320

T
1600
1200
870
570
450

T
1700
1400
880
620
480

T
T
4900
2200
1400
1000
720

T
T
T
3700
1900
1300
950
800

T
T
T
4100
2300
1500
1100
960
640

T
T
T
T
3800
2200
1600
1300
1200
800

T
T
T
T
T
3400
2300
1900
1800
1500
1000

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
Curve C

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
Curve D

1
2
3
4
6
10
16
20
25
32
40

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

594

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve C


Downstream: iDPN N curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve C

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

120
80
80
80

430
270
210
130
130

730
380
290
160
160
160

2300
550
380
320
200
200

T
1600
1200
870
570
450
420

T
1700
1400
880
620
480
320
320

T
6200
4900
2200
1400
1000
720
680
640

T
T
T
3700
1900
1300
950
800
800
500

T
T
T
4100
2300
1500
1100
960
640
640
640

T
T
T
8300
3800
2200
1600
1300
1200
800
800

T
T
T
T
6400
3400
2300
1900
1800
1500
1000

120
80
80

430
270
210
130

730
380
290
160
160

2300
550
380
320
200
200

T
1600
1200
870
570
450

T
1700
1400
880
620
480
320

T
6200
4900
2200
1400
1000
720
680

T
T
T
3700
1900
1300
950
800
800

T
T
T
4100
2300
1500
1100
960
640
640

T
T
T
8300
3800
2200
1600
1300
1200
800
800

T
T
T
T
6400
3400
2300
1900
1800
1500
1000

120
80

430
270
210
130

730
380
290
160

2300
550
380
320

T
1600
1200
870
570
450

T
1700
1400
880
620
480

T
6200
4900
2200
1400
1000
720

T
T
T
3700
1900
1300
950
800

T
T
T
4100
2300
1500
1100
960
640

T
T
T
8300
3800
2200
1600
1300
1200
800

T
T
T
T
6400
3400
2300
1900
1800
1500
1000

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN N
Curve C

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN N
Curve D

1
2
3
4
6
10
16
20
25
32
40

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

557E4305

Version : 1.2

02/03/2012

595

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve D


Downstream: iDPN curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve D

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

350
240
180
120

T
770
610
450
340

T
830
640
500
360
240

T
2000
1600
1000
730
550

T
2200
1700
1100
740
580
380

T
4800
3800
1900
1200
860
480
480

T
T
T
4600
2600
1600
1200
1000
950

T
T
T
T
4700
2800
1900
1500
1400
1100

T
T
T
T
T
3500
2400
2000
1700
1600
1400

T
T
T
T
T
5600
3600
2900
2600
2200
2100

T
T
T
T
T
T
4200
3300
2900
2600
2400

350
240
180

T
770
610
450

T
830
640
500

T
2000
1600
1000
730
550

T
2200
1700
1100
740
580
380

T
4800
3800
1900
1200
860
480

T
T
T
4600
2600
1600
1200
1000

T
T
T
T
4700
2800
1900
1500
1400
1100

T
T
T
T
T
3500
2400
2000
1700
1600

T
T
T
T
T
5600
3600
2900
2600
2200
2100

T
T
T
T
T
T
4200
3300
2900
2600
2400

350
240

T
770
610
450

T
830
640
500

T
2000
1600
1000

T
2200
1700
1100
740
580
380

T
4800
3800
1900
1200
860
480

T
T
T
4600
2600
1600
1200

T
T
T
T
4700
2800
1900
1500

T
T
T
T
T
3500
2400
2000
1700
1600

T
T
T
T
T
5600
3600
2900
2600
2200
2100

T
T
T
T
T
T
4200
3300
2900
2600
2400

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
Curve C

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN
Curve D

1
2
3
4
6
10
16
20
25
32
40

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

596

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve D


Downstream: iDPN N curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve D

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

350
240
180
120

T
770
610
450
340

T
830
640
500
360
240

T
2000
1600
1000
730
550

T
2200
1700
1100
740
580
380

T
4800
3800
1900
1200
860
480
480

T
T
T
4600
2600
1600
1200
1000
950

T
T
T
T
4700
2800
1900
1500
1400
1100

T
T
T
T
6200
3500
2400
2000
1700
1600
1400

T
T
T
T
T
5600
3600
2900
2600
2200
2100

T
T
T
T
T
7300
4200
3300
2900
2600
2400

350
240
180

T
770
610
450

T
830
640
500

T
2000
1600
1000
730
550

T
2200
1700
1100
740
580
380

T
4800
3800
1900
1200
860
480

T
T
T
4600
2600
1600
1200
1000

T
T
T
T
4700
2800
1900
1500
1400
1100

T
T
T
T
6200
3500
2400
2000
1700
1600

T
T
T
T
T
5600
3600
2900
2600
2200
2100

T
T
T
T
T
7300
4200
3300
2900
2600
2400

350
240

T
770
610
450

T
830
640
500

T
2000
1600
1000

T
2200
1700
1100
740
580
380

T
4800
3800
1900
1200
860
480

T
T
T
4600
2600
1600
1200

T
T
T
T
4700
2800
1900
1500

T
T
T
T
6200
3500
2400
2000
1700
1600

T
T
T
T
T
5600
3600
2900
2600
2200
2100

T
T
T
T
T
7300
4200
3300
2900
2600
2400

1P+N
3P, 3P+N

Discrimination limit (A)


iDPN N
Curve B

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN N
Curve C

1
2
3
4
6
10
16
20
25
32
40

Discrimination limit (A)


iDPN N
Curve D

1
2
3
4
6
10
16
20
25
32
40

Note: if you cannot find your combination, refer to the selection table on page 576.

4000

Discrimination limit = 4 kA.

Total discrimination.
No discrimination.

557E4305

Version : 1.2

02/03/2012

597

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve B


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H

In (A)

10

16

20

25

32

40

50

63

80

100

125

T
70
60
40
40

T
150
110
90
64
64

T
210
140
120
80
80
80

T
350
230
180
150
100
100
100

T
550
310
220
190
130
130
130
130

T
2000
590
380
310
290
240
160
160
160

T
2500
630
460
380
300
200
200
200
200
200

T
T
1200
770
570
440
380
380
250
250
250
250

T
T
2100
1400
940
620
550
480
320
320
320
320
320

T
T
3900
2000
1400
930
770
680
600
400
400
400
400
400

T
T
9700
5300
2400
1700
1300
1100
940
850
750
500
500
500
500

T
70
40

T
150
110
64
64

T
210
140
120
80

T
350
230
180
150
100

T
550
250
220
190
130

T
2000
590
380
310
290
160
160

T
2500
630
460
340
300
200
200

T
T
1200
770
570
440
380
250
250

T
T
2100
1400
940
620
550
480
320
320

T
T
3900
2000
1400
930
770
680
600
400
400

T
T
9700
5300
2400
1700
1100
940
940
850
750
500

T
60
40

T
150
90
64

T
210
140
80
80

T
350
200
180
150

T
550
250
220
190
130

T
2000
520
380
310
240

T
2500
630
380
340
200
200

T
T
1200
770
570
440
380
250

T
T
2100
1200
820
620
480
480
320

T
T
3900
2000
1100
930
770
680
600
400

T
T
9700
5300
2400
1700
1100
940
940
750
500

Curve B

Downstream

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40

Discrimination limit (A)


iC60N/H/L
Curve D

0.5
1
2
3
4
6
10
13
16
20
25
32

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

598

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve B


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve B

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

T
120
60
40
40

T
490
160
110
64
64

T
T
350
170
80
80
80

T
T
500
250
190
150
100
100

T
T
1200
520
280
130
130
130
130

T
T
4200
1300
630
350
160
240
160
160

T
T
8100
1900
750
430
200
200
200
200
200

T
T
T
6700
1400
810
500
440
380
250
250
250

T
T
T
T
2700
1400
840
770
520
320
320
320
320

T
T
T
T
6200
2100
1300
1100
770
600
400
400
400
400

T
T
T
T
T
6100
2500
1900
1400
1000
890
840
790
750
500

T
120
60

T
490
160
110
64

T
T
350
170
80

T
T
500
250
190
150

T
T
1200
520
280
130

T
T
4200
1300
630
350
160
240

T
T
8100
1900
750
430
200
200

T
T
T
6700
1400
810
500
440
380

T
T
T
T
2700
1400
840
620
520
320

T
T
T
T
6200
2100
1300
1100
770
600
400

T
T
T
T
T
6100
2500
1900
1400
1000
890
840

T
120
60

T
490
160
110

T
T
350
170
80

T
T
500
250
190

T
T
1200
520
280
130

T
T
4200
1300
630
350

T
T
8100
1900
750
430
200

T
T
T
6700
1400
810
500
380

T
T
T
T
2700
1400
840
620
520

T
T
T
T
6200
2100
1300
930
770
600

T
T
T
T
T
6100
2500
1900
1400
1000
890

2P (220-240 V)
single-phase
network

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40

Discrimination limit (A)


iC60N/H/L
Curve D

557E4305

0.5
1
2
3
4
6
10
13
16
20
25
32

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

599

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve C


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L

In (A)

10

16

20

25

32

40

50

63

80

100

125

T
140
80
80
80

T
490
250
190
130
130

T
920
380
280
240
160
160

T
2300
550
380
300
200
200
200

T
T
1800
1200
870
630
510
450
380

T
T
2400
1400
820
620
480
320
320
320

T
T
8800
4600
2000
1400
1100
930
770
680
600

T
T
10000
8000
2300
2300
1300
1100
950
850
760
500

T
T
13000
8500
3400
2300
1600
1400
1200
960
960
640
640
640

T
T
T
14000
7000
3600
2200
2000
1700
1500
1200
1200
800
800
800

T
T
T
T
13000
6400
3600
2600
2300
2100
1800
1500
1500
1500
1000

T
140
80

T
490
250
190
130
130

T
920
380
280
160
160

T
2300
550
380
300
200
200

T
T
2100
1200
780
630
510
450

T
T
2400
1400
820
620
480
320
320

T
T
8800
4600
2000
1400
930
770
770
680

T
T
10000
8000
2300
2300
1300
1100
950
850
760

T
T
13000
8500
3400
2300
1400
1200
1200
960
960
640

T
T
T
14000
6000
3600
2200
2000
1700
1500
1200
1200
800

T
T
T
T
13000
5500
3100
2600
2300
1800
1800
1500
1500
1000

T
140
80

T
490
250
190

T
920
380
280
160
160

T
2300
550
380
300
200

T
T
1800
1200
780
510
450

T
T
2400
1200
820
620
480
320

T
T
8800
4600
2000
1400
930
770
770

T
T
10000
8000
2300
1900
1300
950
950
760

T
T
13000
8500
3400
1800
1400
1200
960
960
640

T
T
T
14000
6000
3600
2200
1700
1500
1200
1200
800

T
T
T
T
13000
5500
3100
2600
2300
1800
1500
1500
1000

Curve C

Downstream

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve D

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

600

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve C


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L
Curve C

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

T
950
210
120
80

T
T
1900
780
310
190

T
T
4200
1300
590
330
160

T
T
10000
4700
1100
510
300
200

T
T
T
T
4000
1500
1000
760
630

T
T
T
T
13000
2700
1400
910
620
480

T
T
T
T
T
7200
2700
2000
1600
1100
930

T
T
T
T
T
9000
6200
3800
2700
1900
1300
930

T
T
T
T
T
9000
3500
2700
1800
1600
1200
960
960
640

T
T
T
T
T
T
7400
4900
3600
2200
2000
1700
1400
1200
1200

T
T
T
T
T
T
T
8100
5500
3600
2600
2300
2000
1900
1700

T
950
210

T
T
1900
670
310
190

T
T
3500
1300
590
290

T
T
10000
4700
1100
510
200

T
T
T
T
3600
1500
890
760

T
T
T
T
13000
2700
1200
770
620

T
T
T
T
T
7200
2700
2000
1600
1100

T
T
T
T
T
9000
5400
3800
2700
1700
1100

T
T
T
T
T
9000
3700
2700
1800
1400
1200
960

T
T
T
T
T
T
6600
4000
3600
2200
2000
1400
1200

T
T
T
T
T
T
T
7200
4600
3600
2600
2300
2000
1700

T
950
210

T
T
1700
550

T
T
3500
1300
520
240

T
T
10000
4700
960
460

T
T
T
T
3600
1500
890

T
T
T
T
13000
2700
1100
620

T
T
T
T
T
6400
2700
2000
1400

T
T
T
T
T
9000
5400
3500
2300
1500

T
T
T
T
T
9000
3700
2300
1800
1400
960

T
T
T
T
T
T
6600
4000
3100
2200
1700
1400

T
T
T
T
T
T
T
7200
4600
3100
2600
2000
1800

2P (220-240 V)
single-phase
network

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve D

557E4305

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

601

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve D


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H

In (A)

10

16

20

25

32

40

50

63

80

100

125

T
410
240
180

T
3800
770
610
450
340

T
5200
920
640
450
360
240

T
T
2600
1300
890
730
590

T
T
2700
1600
1100
740
660
580
380

T
T
7400
3600
1900
1300
910
810
720
480

T
T
14000
11000
4100
2600
1700
1500
1300
1100
900
900

T
T
T
T
11000
4700
2600
2100
1900
1600
1400
1100
1100

T
T
T
T
13000
6200
3500
2500
2300
2000
1700
1700
1400
1400

T
T
T
T
T
T
5200
4600
3600
3000
2400
2400
2100
2000
2000

T
T
T
T
T
T
6800
4800
4200
3600
2900
2600
2300
2300
2300

T
410
240

T
3800
770
530
450
340

T
5200
920
640
450
360
240

T
T
2600
1300
890
730
590

T
T
2700
1600
1100
740
580
580
380

T
T
7400
3600
1900
1300
910
720
480

T
T
T
11000
4100
2200
1700
1300
1100
1100

T
T
T
T
11000
4700
2600
2100
1900
1600
1400
1100

T
T
T
T
13000
6200
3500
2500
2300
2000
1700
1400
1400

T
T
T
T
T
12000
5200
4100
3600
2700
2400
2400
2100
2000
1800

T
T
T
T
T
T
5900
4800
4200
2900
2900
2600
2300
2300
2300

T
410
240

T
3800
770
530
370
340

T
5200
920
550
450
360
240

T
T
2600
1300
890
730
520

T
T
2700
1600
970
740
580
380

T
T
6300
3600
1600
1100
810
720
480

T
T
T
11000
3700
2200
1500
1300
1100
900

T
T
T
T
11000
4700
2600
2100
1900
1400
1400
1400

T
T
T
T
13000
5400
3000
2500
2300
1700
1700
1400
1400

T
T
T
T
T
12000
5200
4100
3600
2700
2400
2100
2100
1800
1800

T
T
T
T
T
T
5900
4800
4200
2900
2600
2600
2300
1500
1500

Curve D

Downstream

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve D

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

4000

Discrimination limit = 4 kA.

Total discrimination.

Note: if you cannot find your combination, refer to the selection table on page 576.

No discrimination.

602

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve D


Downstream: iC60N/H/L curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve D

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

T
T
1200
520

T
T
T
3400
1200
700

T
T
T
3400
1300
720
540

T
T
T
T
5800
1900
1200

T
T
T
T
5600
1900
1200
900
740

T
T
T
T
T
6000
2600
1800
1500
910

T
T
T
T
T
11000
4200
3400
2200
1700
1500
1300

T
T
T
T
T
T
10000
7300
4700
3500
2600
2000
1800

T
T
T
T
T
T
T
8000
5400
3500
2500
2400
1900
1900

T
T
T
T
T
T
T
T
T
6900
5200
3400
2900
2800
2300

T
T
T
T
T
T
T
T
T
T
6800
4400
4000
3300
2800

T
T
1200

T
T
T
3400
1200
700

T
T
T
3400
1300
720
480

T
T
T
T
5800
1900
1200

T
T
T
T
5600
1900
1200
900
740

T
T
T
T
T
6000
2200
1800
1300

T
T
T
T
T
11000
4200
3000
2200
1700

T
T
T
T
T
T
10000
7300
4700
3500
2600
2000

T
T
T
T
T
T
T
8000
5400
3500
2500
2200
1900

T
T
T
T
T
T
T
T
T
6900
4600
3400
2900
2300
2300

T
T
T
T
T
T
T
T
T
T
6800
4400
3500
2800
2800

T
T
1200

T
T
T
3000
1100
600

T
T
T
3400
1300
600
420

T
T
T
T
5800
1600
1000

T
T
T
T
4500
1600
1100
900

T
T
T
T
T
5300
2200
1700
1300

T
T
T
T
T
11000
3400
2600
2200
1500

T
T
T
T
T
T
10000
6400
3900
3000
2100
1800

T
T
T
T
T
T
T
7100
4500
3500
2500
2200
1700

2P (220-240 V)
single-phase
network

Discrimination limit (A)


iC60N/H/L
Curve B

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve C

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

Discrimination limit (A)


iC60N/H/L
Curve D

557E4305

0.5
1
2
3
4
6
10
13
16
20
25
32
40
50
63

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6000
T
4100
5900
3400
4400
2400
2900
2300
2800
2000
2300
Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

603

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve B


Downstream: C120, NG125 curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H

In (A)

10

Curve B

Downstream

16

20

25

32

40

50

63

80

100

125

80

100

130
130

160
160
160

200
200
200
200

250
250
250
250
250

320
320
320
320
320
320

400
400
400
400
400
400
400

800
750
750
500
500
500
500
500

160

200

250
250

320
320
320

400
400
400
400

750
500
500
500
500

200

250

320
320

400
400
400

750
500
500
500

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


C120,
NG125
Curve B

10
16
20
25
32
40
50
63
80

Discrimination limit (A)


C120,
NG125
Curve C

10
16
20
25
32
40

Discrimination limit (A)


C120,
NG125
Curve D

4000

10
16
20
25
32

Note: if you cannot find your combination, refer to the selection table on page 576.

Discrimination limit = 4 kA.


No discrimination.

604

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream : NG125N/H/L, C120N/H curve B


Downstream: C120, NG125 curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve B

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

80

100

130
130

260
240
160

200
200
200
200

400
250
250
250
250

540
480
320
320
320
320

670
630
600
400
400
400
400

1100
910
830
830
750
750
500
500

240

200

250
250

480
320
320

670
400
400
400

980
830
830
750
500

200

250

320
320

630
400
400

980
750
750
500

2P (220-240 V)
single-phase
network

Discrimination limit (A)


C120,
NG125
Curve B

10
16
20
25
32
40
50
63
80

Discrimination limit (A)


C120,
NG125
Curve C

10
16
20
25
32
40

Discrimination limit (A)


C120,
NG125
Curve D

557E4305

10
16
20
25
32

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

605

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve C


Downstream: C120, NG125 curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H

In (A)

10

16

20

25

32

40

50

63

80

100

125

10

130

160

200

260
260

320
320
320

650
600
400
400

820
760
500
500
500

960
800
640
640
640
640
640

1300
900
800
800
800
800
800

1700
1500
1500
1000
1000
1000
1000
1000
1000

200

260

320
320

650
400
400

760
500
500
500

900
640
640
640
640

1200
800
800
800
800
800

1700
1500
1000
1000
1000
1000
1000

260

320

600
400

760
500
500

900
640
640
640

1200
800
800
800
800

1600
1000
1000
1000
1000
1000

Curve C

Downstream

1P, 1P+N
2P (380-415 V)
two-phase
network
3P, 3P+N
4P

Discrimination limit (A)


C120,
NG125
Curve B

10
16
20
25
32
40
50
63
80
100

Discrimination limit (A)


C120,
NG125
Curve C

10
16
20
25
32
40
50
63

Discrimination limit (A)


C120,
NG125
Curve D

10
16
20
25
32
40
50

Note: if you cannot find your combination, refer to the selection table on page 576.

4000

Discrimination limit = 4 kA.


No discrimination.

606

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve C


Downstream: C120, NG125 curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve C

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

130

160

200

480
260

510
320
320

930
800
730
730

1100
990
910
830
830

1200
1100
1100
960
960
640
640

1700
1400
1400
1200
1200
800
800
800

2500
2000
1900
1600
1600
1500
1500
1000
1000

200

260

480
320

870
730
670

1100
910
830
500

1200
1100
960
640
640

1700
1400
1300
1200
800
800

2500
2000
1700
1600
1500
1000
1000

260

320

800
630

1100
830
760

1100
960
960
640

1600
1300
1300
800
800

2200
1900
1700
1500
1500
1000

2P (220-240 V)
single-phase
network

Discrimination limit (A)


C120,
NG125
Curve B

10
16
20
25
32
40
50
63
80
100

Discrimination limit (A)


C120,
NG125
Curve C

10
16
20
25
32
40
50
63

Discrimination limit (A)


C120,
NG125
Curve D

10
16
20
25
32
40
50

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

557E4305

Version : 1.2

02/03/2012

607

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve D


Downstream: C120, NG125 curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H

In (A)

10

Curve D

Downstream

16

20

25

32

40

50

63

80

100

125

190

240

300

380
380

480
480
480

970
600
600
600

1300
1100
1100
760
760

1600
1400
1400
960
960
960
960

2200
2000
2000
1200
1200
1200
1200
1200

2500
2300
2300
1500
1500
1500
1500
1500
1500

300

380

480
480

970
600
600

1300
1100
1100
760

1600
1400
1400
960
960
960

2200
2000
2000
1200
1200
1200
1200
1200

2500
2300
2300
1500
1500
1500
1500
1500
1500

300

380

480

970
600

1300
1100
1100

1600
1400
1400
960
960
960

2200
2000
2000
1200
1200
1200
1200
1200

2500
2300
2300
1500
1500
1500
1500
1500
1500

1P, 1P+N
2P (380-415 V)
two-phase
network3P, 3P+N
4P

Discrimination limit (A)


C120,
NG125
Curve B

10
16
20
25
32
40
50
63
80
100

Discrimination limit (A)


C120,
NG125
Curve C

10
16
20
25
32
40
50
63
80
100

Discrimination limit (A)


C120,
NG125
Curve D

4000

10
16
20
25
32
40
50
63
80
100

Note: if you cannot find your combination, refer to the selection table on page 576.

Discrimination limit = 4 kA.


No discrimination.

608

Version : 1.2

02/03/2012

557E4305

Discrimination table

Complementary
technical information

Upstream: NG125N/H/L, C120N/H curve D


Downstream: C120, NG125 curves B, C, D

220-240/380-415 V
Upstream

NG125N/H/L, C120N/H
Curve D

In (A)

Downstream

10

16

20

25

32

40

50

63

80

100

125

190

240

250

380
380

720
480
480

1300
1100
1100
600

2000
1600
1500
1200
1200

2400
1900
1800
1400
1400
960
960

3700
2600
2600
2100
2100
1200
1200
1200

4800
3200
2900
2400
2400
1500
1500
1500
1500

250

380

720
480

1300
1100
1100

2000
1600
1500
1200

2400
1900
1800
1400
1400
960

3700
2600
2600
2100
2100
1200
1200
1200

4800
3200
2900
2400
2400
1500
1500
1500
1500

250

380

720

1300
1100

2000
1600
1500

2400
1900
1800
1400
1400
960

3700
2600
2600
2100
2100
1200
1200
1200

4800
3200
2900
2400
2400
1500
1500
1500
1500

2P (220-240 V)
single-phase
network

Discrimination limit (A)


C120,
NG125
Curve B

10
16
20
25
32
40
50
63
80
100

Discrimination limit (A)


C120,
NG125
Curve C

10
16
20
25
32
40
50
63
80
100

Discrimination limit (A)


C120,
NG125
Curve D

557E4305

10
16
20
25
32
40
50
63
80
100

Note: the discrimination limits given in the table must be compared to the phase/neutral fault current (Ik1).
If the max. phase/earth fault current (If) is high, the discrimination of this fault current should also be verified by
referring to the limits given in the dark green part of the table.

Version : 1.2

02/03/2012

609

Discrimination table

Complementary
technical information

Discrimination of circuit breakers

Ue y 440 V
Contents
Downstream Upstream
Type
iDPN
iDPN N
iC60N/H/L
C120,
NG125
NG160,
NSC100
NSX100
NSX160
NSX250
NSX400

NG160

NSC100

NSX400

NSX630

TM-D

NSX100
Micrologic

TM-D

NSX160
Micrologic

TM-D

NSX250
Micrologic

Micrologic

Micrologic

page 611
page 611
page 611
page 611

page 611
page 611
page 611
page 611

page 612
page 612
page 612
page 612

page 613
page 613
page 613
page 613

page 612
page 612
page 612
page 612

page 613
page 613
page 613
page 613

page 612
page 612
page 612
page 612

page 613
page 613
page 613
page 613

page 616
page 616
page 616
page 616

page 616
page 616
page 616
page 616

page 612

page 613

page 612

page 613

page 612

page 613

page 616

page 616

page 614
page 614
page 614
-

page 615
page 615
page 615
-

page 614
page 614
page 614
-

page 615
page 615
page 615
-

page 614
page 614
page 614
-

page 615
page 615
page 615
-

page 616
page 616
page 616
page 616

page 616
page 616
page 616
page 616

Discrimination between circuit breakers

In the following tables we show the level of discrimination between two LV circuits
that are protected by modular circuit breakers.
This discrimination will be either:
bb total: represented by a T (up to the breaking capacity of the downstream device),
bb partial: discrimination limit current (Is) indicated. Below this value discrimination is
ensured, above this value the upstream device is also involved in breaking,
bb zero: no discrimination ensured.

610

Version : 1.3

02/03/2012

557E4310

Discrimination table

Complementary
technical information

Upstream: NG160E/N/H, NSC100N


Downstream: iDPN, iC60, C120, NG125

Ue y 440 V
Upstream

NG160E/N/H

In (A)

16

25

32

40

50

63

80

100

125

160

NC100N
16

25

32

40

50

63

80

100

5
3

5
3
3

5
3
3
3

T
T
T
T
4

T
T
T
T
4
4

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

5
3

5
3
3

5
3
3
3

T
T
T
T
4

T
T
T
T
4
4

T
T
T
T
T
T

5
3

5
3
3

5
3
3
3

T
T
T
6
4

T
T
T
6
4
4

T
T
T
T
7
7

T
T
T
T
T
8

T
T
T
T
T
8

5
3

5
3
3

5
3
3
3

T
T
T
6
4

T
T
T
6
4
4

T
T
T
T
7
7

5
3

5
3
3

5
3
3
3

10
10
10
6
4

T
T
T
6
4
4

T
T
T
T
7
7
5

5
3

5
3
3

5
3
3
3

10
10
10
6
4

T
T
T
6
4
4

T
T
T
T
7
7
5

5
3

5
3
3

5
3
3
3

10
10
10
6
4

15
15
15
6
4
4

T
T
T
T
7
7
5

T
T
T
T
T
8
8
6
T
T
T
T
T
8
8
6

T
T
T
T
T
8
8
6
T
T
T
T
T
8
8
6

5
3

5
3
3

5
3
3
3

10
10
10
6
4

15
15
15
6
4
4

T
T
T
T
7
7
5

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.8
0.8
0.8
0.8
0.8

0.8
0.8
0.8
0.8
0.8
0.8
0.8

1
1
1
1
1
1
1

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.8
0.8
0.8
0.8
0.8

0.8
0.8
0.8
0.8
0.8
0.8
0.8

1
1
1
1
1
1
1

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.8
0.8
0.8
0.8
0.8

0.8
0.8
0.8
0.8
0.8
0.8
0.8

1
1
1
1
1
1
1

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

0.6

0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.6
0.6
0.6
0.6

0.8
0.8
0.8
0.8
0.8

0.8
0.8
0.8
0.8
0.8
0.8
0.8

1
1
1
1
1
1
1

Downstream
Discrimination limit (kA)
iDPN
Curves B, C

y 10
16
20
25
32
40

Discrimination limit (kA)


iDPNN
Curves C, D

y 10
16
20
25
32
40

Discrimination limit (kA)


iC60N/H
Curves B, C, D

iC60L
Curves
B-C-D-K-Z

y 10
16
20
25
32
40
50
63
y 10
16
20
25
32
40
50
63

Discrimination limit (kA)


C120N/H
Curves B, C, D

10 (H)
16 (H)
20 (H)
25 (H)
32 (H)
40 (H)
50 (H)
63
80
100
125

Discrimination limit (kA)


NG125N/H/L
Curves B, C, D

10
16
20
25
32
40
50
63
80
100 (N)
125 (N)

Discrimination limit = 4 kA.

Total discrimination.

No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569.

557E4310

Version : 1.3

02/03/2012

611

Discrimination table

Complementary
technical information

Upstream: Compact NSX100-250 TM-D


Downstream: iDPN, iC60, C120,
NG125-160, NSC100N

Ue y 440 V
Upstream

NSX100B/F/N/H/S/L/R

NSX160B/F/N/H/S/L/R

Trip unit

TM-D

TM-D

In (A)

16

25

32

40

50

63

80

100

80

100

125

160

160

200

250

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

0.19

0.3
0.3

0.4
0.4
0.4

0.9
0.5
0.5
0.5

0.9
0.5
0.5
0.5

0.9
0.5
0.5
0.5
0.5
0.5

1.3
1
0.63
0.63
0.63
0.63
0.63

3
2
1.5
1.5
1
1
0.8
0.8

1.3
1
0.63
0.63
0.63
0.63
0.63

3
2
1.5
1.5
1
1
0.8
0.8

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T

0.19

0.3
0.3

0.4
0.4
0.4

0.5
0.5
0.5

0.5
0.5
0.5
0.5

0.5
0.5
0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

0.63
0.63
0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

T
T
T
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T

0.4

0.5
0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

2
2
2
2
2
2
2

2
2
2
2
2
2
2
2

2
2
2
2
2
2
2
2

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T

NSX250B/F/N/H/S/L/R
TM-D

Downstream
Discrimination limit (kA)
iDPN
Curves B, C

y 10
16
20
25
32
40

Discrimination limit (kA)


iDPNN
Curves C, D

y 10
16
20
25
32
40

Discrimination limit (kA)


iC60N/H
y 10
Curves B, C, D 16
20
iC60L
25
Curves
32
B-C-D-K-Z
40
50
63
Discrimination limit (kA)
C120N/H
10 (H)
Curves B, C, D 16 (H)
20 (H)
25 (H)
32 (H)
40 (H)
50 (H)
63
80
100
125
Discrimination limit (kA)
NG125N/H/L
10
Curves B, C, D 16
20
25
32
40
50
63
80
100 (N)
125 (N)
Discrimination limit (kA)
NG160E/N/H
NSC100N

16
25
32
40
50
63
80
100
125
160

Discrimination limit = 4 kA.

Total discrimination.

No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569.

612

Version : 1.3

02/03/2012

557E4310

Discrimination table

Complementary
technical information

Upstream: Compact NSX100-250 Micrologic


Downstream: iDPN, iC60, C120,
NG125-160, NSC100N

Ue y 440 V
Upstream

NSX100B/F/N/H/S/L/R

NSX160B/F/N/H/S/L/R

NSX250B/F/N/H/S/L/R

Trip unit

Micrologic

Micrologic

Micrologic

Downstream

Rating (A)

40

Setting Ir

16

25

32

40

100
40

63

80

100

160
80

100

125

160

250
160

200

250

T
T

T
T
T

T
T
T
T

T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
6

T
T
T
T
T
T
6
6

T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

0.6

0.6
0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

T
T
T
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T

0.6

0.6
0.6

0.6
0.6
0.6

0.6
0.6
0.6
0.6

1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

T
T
T
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T

0.6

1.5
1.5

1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5
1.5

2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


iDPN
Curves B, C

y 10
16
20
25
32
40

Discrimination limit (kA)


iDPNN
Curves C, D

y 10
16
20
25
32
40

Discrimination limit (kA)


iC60N/H
Curves B, C, D

y 10
16
20
iC60L
25
Curves B-C-D-K-Z 32
40
50
63
Discrimination limit (kA)
C120N/H
Curves B, C, D

10 (H)
16 (H)
20 (H)
25 (H)
32 (H)
40 (H)
50 (H)
63
80
100
125

Discrimination limit (kA)


NG125N/H/L
Curves B, C, D

10
16
20
25
32
40
50
63
80
100 (N)
125 (N)

Discrimination limit (kA)


NG160E/N/H
NSC100N

16
25
32
40
50
63
80
100
125
160

Discrimination limit = 4 kA.

Total discrimination.

No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569.

557E4310

Version : 1.3

02/03/2012

613

Discrimination table

Complementary
technical information

Upstream: Compact NSX100-250 TM-D


Downstream: Compact NSX100-250
TM-D - Micrologic

Ue y 440 V
Upstream

NSX100B/F/N/H/S/L/R

NSX160B/F/N/H/S/L/R

Trip unit

TM-D

TM-D

In (A)

16

25

32

NSX250B/F/N/H/S/L/R
TM-D

40

50

63

80

100

80

100

125

160

160

200

250

0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

1.25
1.25
1.25
1.25
1.25
1.25
1.25

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

0.5

0.5
0.5

0.5
0.5
0.5

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

0.63
0.63
0.63
0.63
0.63

0.8
0.8
0.8
0.8
0.8
0.8

1.25
1.25
1.25
1.25
1.25
1.25
1.25

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25

T
T
36
36
36
36
36
36

T
T
36
36
36
36
36
36

1.25
1.25

1.25
1.25
1.25

1.25
1.25
1.25

4
4
4

5
5
5
5

1.25

2
2

2.5
2.5
2.5

Downstream
Discrimination limit (kA)
Compact
16
NSX100
25
B/F
32
TM-D
40
50
63
80
100
Discrimination limit (kA)
Compact
16
NSX100
25
N/H/S/L/R
32
TM-D
40
50
63
80
100
Discrimination limit (kA)
Compact
y 63
NSX160
80
B/F/N/H/S/L/R
100
TM-D
160
Discrimination limit (kA)
Compact
y 100
NSX250
125
B/F/N/H/S/L/R
160
TM-D
200
Discrimination limit (kA)
Compact
40
NSX100
100
B/F/N/H/S/L/R
Micrologic
Discrimination limit (kA)
Compact
40
NSX160
100
B/F/N/H/S/L/R
160
Micrologic
Discrimination limit (kA)
Compact
y 100
NSX250
160
B/F/N/H/S/L/R
250
Micrologic

Discrimination limit = 4 kA.

Total discrimination.

0.5

0.63

0.8

0.63

0.8

1.25

1.25
1.25

1.25
1.25

2
2

2.5
2.5

0.5

0.63

0.8

0.63

0.8

1.25

1.25
1.25

1.25
1.25

2
2

2.5
2.5
2.5

1.25

2.5
2.5

No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569.

614

Version : 1.3

02/03/2012

557E4310

Discrimination table

Complementary
technical information

Upstream: Compact NSX100-250 Micrologic


Downstream: Compact NSX100-250
TM-D - Micrologic

Ue y 440 V
Upstream

NSX100B/F/N/H/S/L/R

NSX160B/F/N/H/S/L/R

NSX250B/F/N/H/S/L/R

Trip unit

Micrologic

Micrologic

Micrologic

Downstream

Rating (A)

40

Setting Ir

16

Discrimination limit (kA)


Compact NSX100 16
B/F
25
TM-D
32
40
50
63
80
100
Discrimination limit (kA)
Compact NSX100 16
N/H/S/L/R
25
TM-D
32
40
50
63
80
100

100
25

32

40

160

250

40

63

80

100

80

100

125

160

160

200

250

1.5
1.5

1.5
1.5
1.5

1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

1.5
1.5

1.5
1.5
1.5

1.5
1.5
1.5
1.5

1.5
1.5
1.5
1.5
1.5

2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

T
T
36
36
36
36
36
36

T
T
36
36
36
36
36
36

T
T
36
36
36
36
36
36

2.4

2.4
2.4

2.4
2.4
2.4

3
3
3

3
3
3

3
3
3
3

3
3

3
3
3

Discrimination limit (kA)


Compact NSX160 y 63
B/F/N/H/S/L/R
80
TM-D
100
160
Discrimination limit (kA)
Compact NSX250 y 100
B/F/N/H/S/L/R
125
TM-D
160
200
Discrimination limit (kA)
Compact NSX100 40
B/F/N/H/S/L/R
100
Micrologic
Discrimination limit (kA)
Compact NSX160 40
B/F/N/H/S/L/R
100
Micrologic
160

1.5

1.5

1.5

2.4

2.4

2.4

2.4
2.4

36
36

36
36

36
36

2.4

2.4

2.4

2.4
2.4

3
3

3
3

3
3
3

3
3

Discrimination limit (kA)


Compact NSX250 y 100
B/F/N/H/S/L/R
160
Micrologic
250

Discrimination limit = 4 kA.

Total discrimination.

No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569.

557E4310

Version : 1.3

02/03/2012

615

Discrimination table

Complementary
technical information

Upstream: Compact NSX400-630 Micrologic


Downstream: iDPN, iC60, C120, NG125-160,
NSC100N, Compact NSX100-400

Ue y 440 V
Upstream

NSX400F/N/H/S/L/R

NSX630F/N/H/S/L/R

Trip unit

Micrologic

Micrologic

Downstream Rating (A)

400

630

160

200

250

320

400

250

320

400

500

630

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T

T
T
T

T
T
T
T

T
T
T
T

T
T
T
T

T
T
T
T

T
T
T
T

T
T
T
T

T
T
T
T

T
T
T
T

Compact
y 80
NSX100
100
B/F/N/H/S/L/R
TM-D
Discrimination limit (kA)

T
T

T
T

T
T

T
T

T
T

T
T

T
T

T
T

T
T

T
T

Compact
y 100
NSX160
125
B/F/N/H/S/L/R
160
TM-D
Discrimination limit (kA)

T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

Compact
NSX250
B/F/N/H/S/L/R
TM-D

4.8

4.8
4.8

4.8
4.8
4.8

4.8
4.8
4.8
4.8

4.8
4.8
4.8
4.8
4.8

T
T
T

T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

Compact
40
NSX100
100
B/F/N/H/S/L/R
Micrologic
Discrimination limit (kA)

T
T

T
T

T
T

T
T

T
T

T
T

T
T

T
T

T
T

T
T

Compact
40
NSX160
100
B/F/N/H/S/L/R
160
Micrologic
Discrimination limit (kA)

T
T

T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

T
T
T

Compact
y 100
NSX250
160
B/F/N/H/S/L/R
250
Micrologic
Discrimination limit (kA)

4.8

4.8

4.8
4.8

4.8
4.8

4.8
4.8
4.8

T
T

T
T

T
T
T

T
T
T

T
T
T

6.9

6.9
6.9

6.9
6.9
6.9

6.9
6.9
6.9
6.9

6.9
6.9
6.9
6.9
6.9

Setting Ir
Discrimination limit (kA)
iDPN
iDPNN
iC60N/H/L
Discrimination limit (kA)
C120N/H

y 80
100
125

Discrimination limit (kA)


NG125N/H/L

y 80
100
125

Discrimination limit (kA)


NG160E/N/H
NSC100N

y 80
100
125
160

Discrimination limit (kA)

y 100
125
160
200
250

Discrimination limit (kA)

Compact
NSX400
F/N/H/S/L/R
Micrologic

160
200
250
320
400

Discrimination limit = 4 kA.

Total discrimination.

No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569.

616

Version : 1.3

02/03/2012

557E4310

Protection discrimination

Complementary
technical information

Upstream: Masterpact NT06-16 H1/H2 Micrologic


Downstream: iDPN, iC60, C120, NG125-160,
NSC100N, Compact NSX100-630

Ue y 440 V
Upstream

Masterpact NT06/08/12/16 H1/H2

Trip unit

Micrologic 2.0

Downstream

Rating (A) 630


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In
800 1000 1250 1600 630

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

800 1000 1250 1600 630

800 1000 1250 1600

250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600 250 400 630 800 1000 1250 1600

Discrimination limit (kA)


iDPN, iDPNN
iC60
C120N/H
NG125N/H
NG125L
NG160E/N/H
NSC100N
Compact NSX100
B/F/N/H/S/L/R TM-D
Compact NSX160
B/F/N/H/S/L/R TM-D
Compact NSX250 y 125
B/F/N/H/S/L/R
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L/R
100
Micrologic
Compact NSX160 40
B/F/N/H/S/L/R
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L/R
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L/R
200
Micrologic
250
320
400
Compact NSX630 250
F/N/H/S/L/R
320
Micrologic
400
500
630
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.


No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

617

Protection discrimination

Complementary
technical information

Upstream: Masterpact NT06-16 H1


Micrologic
Downstream: Compact NS630b-1600

Ue y 440 V
Upstream

Masterpact NT06/08/12/16 H1

Trip unit

Micrologic 2.0

Downstream

Rating (A) 630


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

800

1000 1250 1600 630

800

1000 1250 1600 630

400

630

800

1000 1250 1600 400

630

800

1000 1250 1600 400

6.3
6.3
6.3

8
8
8
8

9.4
9.4
9.4

12
12
12
12

6.3
6.3

8
8
8

10
10
10
10
10
10
10
10
10

9.4
9.4

12
12
12

15
15
15
15
15
15
15
15
15

6.3

8
8

10
10
10

9.4

12
12

15
15
15

10
10

12.5
12.5
12.5

12

15
15

18.7
18.7
18.7

10

12.5
12.5

16
16
16

15

18.7
18.7

24
24
24

T
T
T
T
T
10
10
10
10

T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

800

1000 1250 1600

630

800

1000 1250 1600

T
T
T

T
T
T
T

T
T

T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Compact NS630b 250
N/H
320
Micrologic
400
500
630
Compact NS800 320
N/H
400
Micrologic
500
630
800
Compact NS1000 400
N/H
500
Micrologic
630
800
1000
Compact NS1250 500
N/H
630
Micrologic
800
1000
1250
Compact NS1600 630
N/H
800
Micrologic
960
1250
1600
Compact NS630b 250
L/LB
320
Micrologic
400
500
630
Compact NS800 320
L/LB
400
Micrologic
500
630
800
Compact NS1000 400
L
500
Micrologic
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

9.4

T
T
T

T
T
T
T

9.4
9.4

T
T
T

9.4

12
12

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T

18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

618

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NT06-16 H1 Micrologic


Downstream: Masterpact NT06-16

Ue y 440 V
Upstream

Masterpact NT06/08/12/16 H1

Trip unit

Micrologic 2.0

Downstream Rating (A) 630


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

800

1000

1250

1600

630

800

1000

1250

1600

630

800

1000

1250

1600

400

630

800

1000

1250

1600

400

630

800

1000

1250

1600

400

630

800

1000

1250

1600

6.3
6.3
6.3

8
8
8
8

12
12
12
12

T
T
T
T

T
T

T
T
T
T

8
8

10
10
10

9.4

12
12

15
15
15

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

10
10

12.5
12.5
12.5

12

15
15

18.7
18.7
18.7

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

T
T
T

12
12
12

18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

9.4
9.4

15
15
15
15
15
15
15
15
15

6.3

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

9.4
9.4
9.4

8
8
8

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

9.4

6.3
6.3

10
10
10
10
10
10
10
10
10

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

10

12.5
12.5

16
16
16

15

18.7
18.7

24
24
24

T
T

T
T
T

T
T
T
T
T
10
10
10
10

T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Masterpact
NT06 H1/H2
Micrologic

Masterpact
NT08 H1/H2
Micrologic

Masterpact
NT10 H1/H2
Micrologic

Masterpact
NT12 H1/H2
Micrologic

Masterpact
NT16 H1/H2
Micrologic

Masterpact
NT06 L1
Micrologic

Masterpact
NT08 L1
Micrologic

Masterpact
NT10 L1
Micrologic

250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000
500
630
800
1000
1250
630
800
960
1250
1600
250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

T
T
T

T
T
T
T

9.4
9.4

T
T
T

9.4

12
12

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

619

Protection discrimination

Complementary
technical information

Upstream: Masterpact NT06-16 H2 Micrologic


Downstream: Compact NS630b-1600

Ue y 440 V
Upstream

Masterpact NT06/08/12/16 H2

Trip unit

Micrologic 2.0

Downstream

Rating (A) 630


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

800

1000 1250 1600 630

800

1000 1250 1600 630

800

1000 1250 1600

400

630

800

1000 1250 1600 400

630

800

1000 1250 1600 400

630

800

1000 1250 1600

6.3
6.3
6.3

8
8
8
8

9.4
9.4
9.4

12
12
12
12

42
42
42
42

8
8
8

9.4
9.4

12
12
12

15
15
15
15
15
15
15
15
15

42
42
42

6.3
6.3

10
10
10
10
10
10
10
10
10

42
42

42
42
42
42

6.3

8
8

10
10
10

9.4

12
12

15
15
15

42

42
42

42
42
42
42
42
42
42
42
42
42
42
42
42

42
42
42
42
42
42
42
42
42
42
42
42
42
42

10
10

12.5
12.5
12.5

12

15
15

18.7
18.7
18.7

42
42

42
42
42

10

12.5
12.5

16
16
16

15

18.7
18.7

24
24
24

42

42
42

42
42
42

T
T
T
T
T
10
10
10
10

T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Compact NS630b 250
N/H
320
Micrologic
400
500
630
Compact NS800 320
N/H
400
Micrologic
500
630
800
Compact NS1000 400
N/H
500
Micrologic
630
800
1000
Compact NS1250 500
N/H
630
Micrologic
800
1000
1250
Compact NS1600 630
N/H
800
Micrologic
960
1250
1600
Compact NS630b 250
L/LB
320
Micrologic
400
500
630
Compact NS800 320
L/LB
400
Micrologic
500
630
800
Compact NS1000 400
L
500
Micrologic
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

9.4

T
T
T

T
T
T
T

9.4
9.4

T
T
T

9.4

12
12

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T

18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

42

42

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

620

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NT06-16 H2 Micrologic


Downstream: Masterpact NT06-16

Ue y 440 V
Upstream

Masterpact NT06/08/12/16 H2

Trip unit

Micrologic 2.0

Downstream Rating (A) 630


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

800

1000

1250

1600

630

800

1000

1250

1600

630

800

1000

1250

1600

400

630

800

1000

1250

1600

400

630

800

1000

1250

1600

400

630

800

1000

1250

1600

6.3
6.3
6.3

8
8
8
8

12
12
12
12

42
42
42
42

42
42

42
42
42
42

8
8

10
10
10

9.4

12
12

15
15
15

42

42
42

42
42
42
42
42
42
42
42
42
42
42
42
42

42
42
42
42
42
42
42
42
42
42
42
42
42
42

10
10

12.5
12.5
12.5

12

15
15

18.7
18.7
18.7

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24

42
42
42

12
12
12

18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7

42

9.4
9.4

15
15
15
15
15
15
15
15
15

6.3

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

9.4
9.4
9.4

8
8
8

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

9.4

6.3
6.3

10
10
10
10
10
10
10
10
10

42
42

42
42
42

42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42

10

12.5
12.5

16
16
16

15

18.7
18.7

24
24
24

42

42
42

42
42
42

T
T
T
T
T
10
10
10
10

T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Masterpact
NT06 H1/H2
Micrologic

Masterpact
NT08 H1/H2
Micrologic

Masterpact
NT10 H1/H2
Micrologic

Masterpact
NT12 H1/H2
Micrologic

Masterpact
NT16 H1/H2
Micrologic

Masterpact
NT06 L1
Micrologic

Masterpact
NT08 L1
Micrologic

Masterpact
NT10 L1
Micrologic

250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000
500
630
800
1000
1250
630
800
960
1250
1600
250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

T
T
T

T
T
T
T

9.4
9.4

T
T
T

9.4

12
12

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T

42

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

621

Protection discrimination

Complementary
technical information

Upstream: Masterpact NT06-10 L1 Micrologic


Downstream: iDPN, iC60, C120, NG125-160,
NSC100N, Compact NSX100-630

Ue y 440 V
Upstream

Masterpact NT06/08/10 L1

Trip unit

Micrologic 2.0

Downstream

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

Rating (A)

630

800

1000

630

800

1000

630

800

1000

Setting Ir

250

400

630

800

1000

250

400

630

800

1000

250

400

630

800

1000

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

36

36

36

36

36

36

36

36

36

20
20

20
20
20
20
T
T

20
20
20
20
T
T

T
T
T
T
T
T

T
T
T
T
T
T

20
20

20
20
20
20
T
T

20
20
20
20
T
T

T
T
T
T
T
T

T
T
T
T
T
T

20
20

20
20
20
20
T
T

20
20
20
20
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3

T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3

T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8

T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10

T
T
T
36
36
36
20
20
20
6.3
6.3
6.3

T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3

T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8

T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10

T
T
T
36
36
36
20
20
20
6.3
6.3
6.3

T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3

T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8

T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10

Discrimination limit (kA)


iDPN, iDPNN
iC60
C120N/H
NG125N/H
NG125L
NG160
NSC100N
Compact NSX100
B/FN/H/S/L/R TM-D
Compact NSX160
B/F
TM-D
Compact NSX160
N/H/S/L/R
TM-D
Compact NSX250 y 125
B/F/N//H/S/L/R
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L/R
100
Micrologic
Compact NSX160 40
B/F
100
Micrologic
160
Compact NSX160 40
N/H/S/L/R
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L/R
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L/R
200
Micrologic
250
320
400
Compact NSX630 250
F/N/H/S/L/R
320
Micrologic
400
500
630

T
T
T
T
T
36
36
36
20

6.3

6.3

T
T
T
T
T
36
36
36
20

6.3

6.3

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
36
36
36
20

6.3

6.3

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

622

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NT06-10 L1 Micrologic


Downstream: Compact NS630b-1000, Masterpact
NT06-10

Ue y 440 V
Upstream

Masterpact NT06/08/10 L1

Trip unit

Micrologic 2.0

Downstream

Rating (A)

630

Setting Ir

250

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In
800

1000

630

400

630

800

1000

250

6.3

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

10
10
10
10
10
10
10
10
10

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF
800

1000

630

400

630

800

1000

250

6.3

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

10
10
10
10
10
10
10
10
10

800

1000

400

630

800

1000

6.3

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

10
10
10
10
10
10
10
10
10

6.3

10
10

10
10
10

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

10
10
10
10
10
10
10
10
10

6.3

10
10

Discrimination limit (kA)


Compact NS630b 250
N/H/L/LB
320
Micrologic
400
500
630
Compact NS800 320
N/H/L/LB
400
Micrologic
500
630
800
Compact NS1000 400
N/H/L
500
Micrologic
630
800
1000
Masterpact NT06 250
H1/H2/L1
320
Micrologic
400
500
630
Masterpact NT08 320
H1/H2/L1
400
Micrologic
500
630
800
Masterpact NT10 400
H1/H2/L1
500
Micrologic
630
800
1000
4

10
10
10

6.3

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

10
10
10
10
10
10
10
10
10

10
10
10

6.3

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

10
10
10

10
10
10
10
10
10
10
10
10
10
10
10

6.3

10
10
10

Discrimination limit = 4 kA.


No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

623

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 N1/H1/H2/L1


Micrologic
Downstream: iDPN, iC60, C120, NG125-160,
NSC100N, Compact NSX100-630

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 N1/H1/H2/L1

Trip unit

Micrologic 2.0

Downstream

Rating (A) 800

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In
1000 1250 1600 2000 800

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000 1250 1600 2000 800

1000 1250 1600 2000

Setting Ir 320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000
Discrimination limit (kA)
iDPN, iDPNN
iC60
C120N/H
NG125N/H
NG125L
NG160E/N/H
NSC100N
Compact NSX100
B/F/N/H/S/L/R TM-D
Compact NSX160
B/F/N/H/S/L/R TM-D
Compact NSX250 y 125
B/F/N/H/S/L/R
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L/R
100
Micrologic
Compact NSX160 40
B/F/N/H/S/L/R
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L/R
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L/R
200
Micrologic
250
320
400
Compact NSX630 250
F/N/H/S/L/R
320
Micrologic
400
500
630
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T

T
T

T
T

T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.


No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

624

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 N1/H1/H2


Micrologic
Downstream: Compact NS630b-1600

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 N1/H1/H2

Trip unit

Micrologic 2.0

Downstream Rating (A) 800


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

6.3
6.3
6.3

8
8
8
8

12
12
12

T
T

T
T
T

T
T
T
T
T
T
T
T
T

10
10
10

12

12
12

15
15
15

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

10
10

12.5
12.5
12.5

12

15
15

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

10

12.5
12.5

16
16
16

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

T
T
T
T

12
12

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

T
T
T

8
8

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

15
15
15
15
15
15
15
15
15

6.3

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

12
12
12
12

8
8
8

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

12
12
12

6.3
6.3

10
10
10
10
10
10
10
10
10

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
10
10
10
10

T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T
T
T
T
T
T
T
T

12

12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Compact
NS630bN/H
Micrologic

Compact
NS800N/H
Micrologic

Compact
NS1000N/H
Micrologic

Compact
NS1250N/H
Micrologic

Compact
NS1600N/H
Micrologic

Compact
NS630bL/LB
Micrologic

Compact
NS800 L/LB
Micrologic

Compact
NS1000L
Micrologic

250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000
500
630
800
1000
1250
630
800
960
1250
1600
250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24

15

18.75 24
18.75 24
24

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

625

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 N1/H1/H2


Micrologic
Downstream: Masterpact NT06-16

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 N1/H1/H2

Trip unit

Micrologic 2.0

Downstream Rating (A) 800


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

6.3
6.3
6.3

8
8
8
8

12
12
12

T
T

T
T
T

T
T
T
T
T
T
T
T
T

10
10
10

12

12
12

15
15
15

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

10
10

12.5
12.5
12.5

12

15
15

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

10

12.5
12.5

16
16
16

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

T
T
T
T

12
12

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

T
T
T

8
8

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

15
15
15
15
15
15
15
15
15

6.3

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

12
12
12
12

8
8
8

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

12
12
12

6.3
6.3

10
10
10
10
10
10
10
10
10

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
10
10
10
10

T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T
T
T
T
T
T
T
T

12

12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Masterpact
NT06 H1/H2
Micrologic

Masterpact
NT08 H1/H2
Micrologic

Masterpact
NT10 H1/H2
Micrologic

Masterpact
NT12 H1/H2
Micrologic

Masterpact
NT16 H1/H2
Micrologic

Masterpact
NT06L
Micrologic

Masterpact
NT08L
Micrologic

Masterpact
NT10L
Micrologic

250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000
500
630
800
1000
1250
630
800
960
1250
1600
250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24

15

18.75 24
18.75 24
24

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

626

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 N1/H1 Micrologic


Downstream: Masterpact NW08-20

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 N1/H1

Trip unit

Micrologic 2.0

Downstream Rating (A) 800


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

6.3
6.3

8
8
8

10
10
10
10

15
15
15
15

T
T
T
T

12
12

15
15
15

T
T

T
T
T

T
T
T
T
T
T
T
T
T

10
10

12.5
12.5
12.5

12

15
15

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

10

12.5
12.5

16
16
16

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

T
T
T

12

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

T
T

10
10
10

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

12
12
12

8
8

16
16
16
16
16
16
16
16
16
16
16
16
16
16

12
12

6.3

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

12.5

16
16

20
20
20

T
T

T
T
T

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Masterpact
320
NW08 N1/H1/L1 400
Micrologic
500
630
800
Masterpact
400
NW10 N1/H1/L1 500
Micrologic
630
800
1000
Masterpact
500
NW12 N1/H1/L1 630
Micrologic
800
1000
1250
Masterpact
630
NW16 N1/H1/L1 800
Micrologic
960
1250
1600
Masterpact
800
NW20 N1/H1/L1 1000
Micrologic
1250
1600
Masterpact
320
NW08 H2
400
Micrologic
500
630
800
Masterpact
400
NW1 0H2
500
Micrologic
630
800
1000
Masterpact
500
NW12 H2
630
Micrologic
800
1000
1250
Masterpact
630
NW16 H2
800
Micrologic
960
1250
1600
Masterpact
800
NW20 H2
1000
Micrologic
1250
1600

6.3
6.3

8
8
8

10
10
10
10

6.3

8
8

10
10
10

10
10

12.5
12.5
12.5

10

12.5
12.5

16
16
16

12.5

16
16

15

12
12

12
12
12

15
15
15
15

12

12
12

15
15
15

12

15
15

15

20
20
20

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24

18.75 24
24

30
30
30

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24

18.75 24
24

30
30
30

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T

T
T
T

T
T

T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

627

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 H2 Micrologic


Downstream: Masterpact NW08-20

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 H2

Trip unit

Micrologic 2.0

Downstream Rating (A) 800


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

1000 1250 1600 2000 800

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000 1250 1600 2000 800

630

800

1000 1250 1600 2000 630

800

1000 1250 1600 2000 630

6.3
6.3

8
8
8

10
10
10
10

12
12

12
12
12

15
15
15
15

6.3

8
8

10
10
10

12

12
12

15
15
15

10
10

12.5
12.5
12.5

12

15
15

10

12.5
12.5

16
16
16

12.5

16
16

20
20
20

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

1000 1250 1600 2000


800

1000 1250 1600 2000

T
T

T
T
T

T
T
T
T

T
T

T
T
T

T
T

T
T
T

T
T

T
T
T

T
T

T
T
T

82
82
82
82
82
82
82
82
82

82
82
82
82
82
82
82
82
82
82
82
82
82
82

82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82

Discrimination limit (kA)


Masterpact
320
NW08 N1/H1/L1 400
Micrologic
500
630
800
Masterpact
400
NW10 N1/H1/L1 500
Micrologic
630
800
1000
Masterpact
500
NW12 N1/H1/L1 630
Micrologic
800
1000
1250
Masterpact
630
NW16 N1/H1/L1 800
Micrologic
960
1250
1600
Masterpact
800
NW20 N1/H1/L1 1000
Micrologic
1250
1600
Masterpact
320
NW08 H2
400
Micrologic
500
630
800
Masterpact
400
NW10 H2
500
Micrologic
630
800
1000
Masterpact
500
NW12 H2
630
Micrologic
800
1000
1250
Masterpact
630
NW16 H2
800
Micrologic
960
1250
1600
Masterpact
800
NW20 H2
1000
Micrologic
1250
1600

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16

6.3
6.3

8
8
8

10
10
10
10

6.3

8
8

10
10
10

10
10

12.5
12.5
12.5

10

12.5
12.5

16
16
16

12.5

16
16

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

15

12
12

12
12
12

15
15
15
15

12

12
12

15
15
15

12

15
15

20
20
20

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

15

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

18.75 24
24

30
30
30

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24

18.75 24
18.75 24
24

18.75 24
24

30
30
30

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

82
82

82
82
82

82
82
82
82

82

82
82

82
82
82

82

82
82

82
82
82

82

82
82

82
82
82

82

82
82

82
82
82

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

628

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 L1 Micrologic


Downstream: Compact NS630b-1600

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 L1

Trip unit

Micrologic 2.0

Downstream Rating (A) 800


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

6.3
6.3
6.3

8
8
8
8

12
12
12

37
37

37
37
37

37
37
37
37
37
37
37
37
37

10
10
10

12

12
12

15
15
15

37

37
37

37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37

10
10

12.5
12.5
12.5

12

15
15

37

37
37

37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37

10

12.5
12.5

16
16
16

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

37
37
37
37

12
12

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

37
37
37

8
8

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

15
15
15
15
15
15
15
15
15

6.3

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

12
12
12
12

8
8
8

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

12
12
12

6.3
6.3

10
10
10
10
10
10
10
10
10

37

37
37

37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37

10
10
10
10
10
10
10
10
10

T
T
T
T
T
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

12
12

12
12
12

T
T

T
T
T

T
T
T
T
T
T
T
T
T

12

12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Compact
NS630bN/H
Micrologic

Compact
NS800N/H
Micrologic

Compact
NS1000N/H
Micrologic

Compact
NS1250N/H
Micrologic

Compact
NS1600N/H
Micrologic

Compact
NS630bL/LB
Micrologic

Compact
NS800L/LB
Micrologic

Compact
NS1000L
Micrologic

250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000
500
630
800
1000
1250
630
800
960
1250
1600
250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24

15

18.75 24
18.75 24
24

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

629

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 L1 Micrologic


Downstream: Masterpact NT06-16

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 L1

Trip unit

Micrologic 2.0

Downstream Rating (A) 800


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000

1250

1600

2000

800

1000

1250

1600

2000

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

630

800

1000

1250

1600

2000

6.3
6.3
6.3

8
8
8
8

12
12
12

37
37

37
37
37

37
37
37
37
37
37
37
37
37

10
10
10

12

12
12

15
15
15

37

37
37

37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37

10
10

12.5
12.5
12.5

12

15
15

37

37
37

37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37

10

12.5
12.5

16
16
16

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

37
37
37
37

12
12

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

37
37
37

8
8

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

15
15
15
15
15
15
15
15
15

6.3

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

12
12
12
12

8
8
8

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

12
12
12

6.3
6.3

10
10
10
10
10
10
10
10
10

37

37
37

37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37

10
10
10
10
10
10
10
10
10

T
T
T
T
T
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T

T
T
T

T
T
T
T

12
12

12
12
12

T
T

T
T
T

T
T
T
T
T
T
T
T
T

12

12
12

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (kA)


Masterpact
NT06 H1/H2
Micrologic

Masterpact
NT08 H1/H2
Micrologic

Masterpact
NT10 H1/H2
Micrologic

Masterpact
NT12 H1/H2
Micrologic

Masterpact
NT16 H1/H2
Micrologic

Masterpact
NT06L1
Micrologic

Masterpact
NT08L1
Micrologic

Masterpact
NT10L1
Micrologic

250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000
500
630
800
1000
1250
630
800
960
1250
1600
250
320
400
500
630
320
400
500
630
800
400
500
630
800
1000

6.3
6.3
6.3

8
8
8
8

6.3
6.3

8
8
8

6.3

8
8

10
10
10

24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24

15

18.75 24
18.75 24
24

T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

630

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW08-20 L1 Micrologic


Downstream: Masterpact NW08-20

Ue y 440 V
Upstream

Masterpact NW08/12/16/20 L1

Trip unit

Micrologic 2.0

Downstream Rating (A) 800


Setting Ir

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

1000 1250 1600 2000 800

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

1000 1250 1600 2000 800

1000 1250 1600 2000

630

800

1000 1250 1600 2000 630

800

1000 1250 1600 2000 630

800

1000 1250 1600 2000

6.3
6.3

8
8
8

10
10
10
10

12
12

12
12
12

15
15
15
15

37
37

37
37
37

37
37
37
37

6.3

8
8

10
10
10

12

12
12

15
15
15

37

37
37

37
37
37

10
10

12.5
12.5
12.5

12

15
15

37

37
37

37
37
37

10

12.5
12.5

16
16
16

37

37
37

37
37
37

12.5

16
16

20
20
20

37

37
37

37
37
37

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

37
37
37
37
37
37
37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37

Discrimination limit (kA)


Masterpact
320
NW08 N1/H1/H2 400
Micrologic
500
630
800
Masterpact
400
NW10 N1/H1/H2 500
Micrologic
630
800
1000
Masterpact
500
NW12 N1/H1/H2 630
Micrologic
800
1000
1250
Masterpact
630
NW16N 1/H1/H2 800
Micrologic
960
1250
1600
Masterpact
800
NW20 N1/H1/H2 1000
Micrologic
1250
1600
Masterpact
320
NW08 L1
400
Micrologic
500
630
800
Masterpact
400
NW10 L1
500
Micrologic
630
800
1000
Masterpact
500
NW12 L1
630
Micrologic
800
1000
1250
Masterpact
630
NW16 L1
800
Micrologic
960
1250
1600
Masterpact
800
NW20 L1
1000
Micrologic
1250
1600
4

12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5

16
16
16
16
16
16
16
16
16
16
16
16
16
16

6.3
6.3

8
8
8

10
10
10
10

6.3

8
8

10
10
10

10
10

12.5
12.5
12.5

10

12.5
12.5

16
16
16

12.5

16
16

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

15

12
12

12
12
12

15
15
15
15

12

12
12

15
15
15

12

15
15

20
20
20

15

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

18.75 24
24

30
30
30

18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24

18.75 24
18.75 24
24

18.75 24
24

30
30
30

37
37
37
37
37
37
37
37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37

37
37

37
37
37

37
37
37
37

37

37
37

37
37
37

37

37
37

37
37
37

37

37
37

37
37
37

37

37
37

37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37

37
37
37

Discrimination limit = 4 kA.


No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

631

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW25-40 H1/H2,


Masterpact NW40b-63 H1 Micrologic
Downstream: iDPN, iC60, C120, NG125-160,
NSC100N, Compact NSX100-630, NS630b-3200

Ue y 440 V
Upstream

Masterpact
NW25/32/40
H1/H2

Masterpact
Masterpact
NW40b 50/63 H1 NW25/32/40
H1/H2

Trip unit

Micrologic 2.0

Masterpact
Masterpact
NW40b 50/6 3H1 NW25/32/40
H1/H2

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Masterpact
NW40b 50/63 H1

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

Downstream Rating (A) 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300
Discrimination limit (kA)
iDPN, iDPNN
iC60
C120N/H
NG125N/H/L
NG160E/N/H
NSC100N
Compact NSX
B/F/H/N/S/L/R
TM-D

NSX100
NSX160
NSX250
Compact NSX
NSX100
B/F/H/N/S/L/R
NSX160
Micrologic
NSX250
F/H/N/S/L/R
NSX400
Micrologic
NSX630
Compact NS N NS630b
Micrologic
NS800
NS1000
NS1250
NS1600
Compact NS H NS630b
Micrologic
NS800
NS1000
NS1250
NS1600
Compact NS N NS1600b
Micrologic
NS2000
NS2500
NS3200
Compact NS H NS1600b
Micrologic
NS2000
NS2500
NS3200
Compact NS L NS630b
Micrologic
NS800
NS1000
Compact NS LB NS630b
Micrologic
NS800

T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
25
25
25
25

T
T
T
T
T
T
T
T
T
T
T
T
T
T
32
32
32
32
32
32
32
32
32
32
32
32
32

25
25

32
32
32

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
48
48
48

37.5
37.5

48
48
48

T
T
T
T
T

T
T
T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T

T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

632

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW25-40 H1 Micrologic


Downstream: Masterpact NT06-16,
Masterpact NW08-20

Ue y 440 V
Upstream

Masterpact NW25/32/40 H1

Trip unit

Micrologic 2.0

Downstream

Rating (kA)

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

2500

3200

4000

2500

3200

4000

2500

3200

4000

25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

T
T
T
T
T
48
48
48
48
48
T
T
T
T
48
48
48
48
48
48

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

32
32
32
32
32
32

37.5
37.5
37.5
37.5
37.5

48
48
48
48
48
48

T
T
T
T
T

T
T
T
T
T
T

25

32
32

37.5

48
48

T
T

T
T
T
25
25
25
25
25

T
T
T
32
32
32
32
32

T
T
T
37.5
37.5
37.5
37.5
37.5

T
T
T
48
48
48
48
48

T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
60
60
60
60
60

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

25
25
25
25
25

40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
40
40
40
40
40

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

Discrimination limit (A)


Masterpact NT
H1
Micrologic

Masterpact NT
H2
Micrologic 2.0

Masterpact NW
N1
Micrologic
Masterpact NW
H1
Micrologic

Masterpact NW
H2
Micrologic

Masterpact NW
H3
Micrologic
Masterpact NT
L1
Micrologic
Masterpact NW
L1
Micrologic

NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NT12
NT16
NW08
NW10
NW12
NW16
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW20
NW25
NW32
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.


No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

633

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW25-40 H2,


Masterpact NW40b-63 H1 Micrologic
Downstream: Masterpact NT06-16,
Masterpact NW08-50

Ue y 440 V
Upstream

Masterpact
NW25/32/40 H2

Trip unit

Micrologic 2.0

Masterpact
Masterpact
NW40b 50/63 H1 NW25/32/40 H2

Masterpact
Masterpact
NW40b 50/63 H1 NW25/32/40 H2

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Masterpact
NW40b 50/63 H1

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

Downstream Rating (A) 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300 2500 3200 4000 4000 5000 6300
Discrimination limit (kA)
Masterpact NT
H1
Micrologic

Masterpact NT
H2
Micrologic

Masterpact NW
N1
Micrologic
Masterpact NW
H1
Micrologic

Masterpact NW
H2
Micrologic

Masterpact NW
H1
Masterpact NW
H3
Micrologic
Masterpact NW
H2
Masterpact NT
L1
Micrologic
Masterpact NW
L1
Micrologic

NT06
NT08
NT10
NT12
NT16
NT06
NT08
NT10
NT12
NT16
NW08
NW10
NW12
NW16
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW08
NW10
NW12
NW16
NW20
NW25
NW32
NW40
NW40b
NW50
NW20
NW25
NW32
NW40
NW40b
NW50
NT06
NT08
NT10
NW08
NW10
NW12
NW16
NW20

T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

25
25
25
25
25

32
32
32
32
32
32

40
40
40
40
40
40
40

40
40
40
40
40
40
40

25

32
32

40
40
40

40
40
40

50
50
50
50
50

T
T
T
25
25
25
25
25

T
T
T
32
32
32
32
32

T
T
T
40
40
40
40
40

T
T
T
40
40
40
40
40

T
T
T
50
50
50
50
50

T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
63
63
63
63
63

37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

T
T
T
T
T
48
48
48
48
48
T
T
T
T
48
48
48
48
48
48

T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60

T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
75
75
75
75
75

37.5
37.5
37.5
37.5
37.5

48
48
48
48
48
48

37.5

48
48

60
60
60

60
60
60

75
75
75
75
75

T
T
T
37.5
37.5
37.5
37.5
37.5

T
T
T
48
48
48
48
48

T
T
T
60
60
60
60
60

T
T
T
60
60
60
60
60

T
T
T
75
75
75
75
75

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
T
T
T
94
94
94
94
94

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

82
82
82
82
82

82
82
82
82
82
82

82
82
82
82
82
82
82
82

T
T
T
T
T
T
T
T

82

82
82

82
82
82

T
T
T

T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

634

Version : 1.3

02/03/2012

557E4330

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW20-40 H3, Masterpact


NW40b-63 H2 Micrologic
Downstream: iDPN, iC60, C120, NG125-160,
NSC100N, Compact NSX100-630, NS630b-3200

Ue y 440 V
Upstream

Masterpact
NW20/25/32/40 H3

Trip unit

Micrologic 2.0

Masterpact
NW40b 50/63
H2

Masterpact
NW20/25/32/40 H3

Masterpact
NW40b 50/63
H2

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Masterpact
NW20/25/32/40 H3

Masterpact
NW40b 50/63
H2

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

DownstreamRating (A) 2000 2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300
Discrimination limit (kA)
iDPN, iDPNN
iC60
C120N/H
NG125N/H/L
NG160E/N/H
NSC100N
Compact
NSX100
B/F/H/N/S/L/R NSX160
TM-D
NSX250
Compact
NSX100
B/F/H/N/S/L/R NSX160
Micrologic
NSX250
Compact
NSX400
F/H/N/S/L/R
NSX630
Compact N
NS630b
Micrologic
NS800
NS1000
NS1250
NS1600
Compact H
NS630b
Micrologic
NS800
NS1000
NS1250
NS1600
Compact N
NS1600b
Micrologic
NS2000
NS2500
NS3200
Compact H
NS1600b
Micrologic
NS2000
NS2500
NS3200
Compact L
NS630b
Micrologic
NS800
NS1000
Compact LB NS630b
Micrologic
NS800

T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
20
20
20
20
20
20
20

T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
25
25
25
25

T
T
T
T
T
T
T
T
T
T
T
T
T
T
32
32
32
32
32
32
32
32
32
32
32
32
32

20

25
25

32
32
32

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
30
30
30
30
30
30
30
30
30
30
30

T
T
T
T
T
T
T
T
T
T
T
T
T
T
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

T
T
T
T
T
T
T
T
T
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
48
48
48

30

37.5 48
37.5 48
48

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
65

65

65
65

65
65
65

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
65
65
65
65
65
65
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.

557E4330

Version : 1.3

02/03/2012

635

Protection discrimination

Complementary
technical information

Upstream: Masterpact NW20-40 H3,


Masterpact NW40b-63 H2 Micrologic
Downstream: Masterpact NT06-16,
Masterpact NW08-50

Ue y 440 V
Upstream

Masterpact
NW20/25/32/40 H3

Trip unit

Micrologic 2.0

Masterpact
NW40b 50/63
H2

Masterpact
NW20/25/32/40 H3

Masterpact
NW40b 50/63
H2

Micrologic 5.0 - 6.0 - 7.0


Inst : 15 In

Masterpact
NW20/25/32/40 H3

Masterpact
NW40b 50/63
H2

Micrologic 5.0 - 6.0 - 7.0


Inst : OFF

Downstream Rating (A) 2000 2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300
Discrimination limit (kA)
Masterpact NT NT06
H1
NT08
Micrologic
NT10
NT12
NT16
Masterpact NT NT06
H2
NT08
Micrologic
NT10
NT12
NT16
Masterpact NW NW08
N1
NW10
Micrologic
NW12
NW16
Masterpact NW NW08
H1
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
NW40
Masterpact NW NW08
H2
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
NW40
Masterpact NW NW40b
H1
NW50
Masterpact NW NW20
H3
NW25
Micrologic
NW32
NW40
Masterpact NW NW40b
H2
NW50
Masterpact NT NT06
L1
NT08
Micrologic
NT10
Masterpact NW NW08
L1
NW10
Micrologic
NW12
NW16
NW20

T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25

32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32

40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40

20
20
20
20

25
25
25
25
25

32
32
32
32
32
32

40
40
40
40
40
40
40

40
40
40
40
40
40
40

20

25

32
32

40
40
40

40
40
40

50
50
50
50
50

T
T
T
20
20
20
20
20

T
T
T
25
25
25
25
25

T
T
T
32
32
32
32
32

T
T
T
40
40
40
40
40

T
T
T
40
40
40
40
40

T
T
T
50
50
50
50
50

T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
63
63
63
63
63

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5

T
T
T
T
T
48
48
48
48
48
T
T
T
T
48
48
48
48
48
48

T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60

30
30
30
30

37.5
37.5
37.5
37.5
37.5

48
48
48
48
48
48

T
T
T
30
30
30
30

60
60
60
60
60
60
60
60

T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
75
75
75
75
75

37.5 48
48

60
60
60

60
60
60

75
75
75
75
75

T
T
T
37.5
37.5
37.5
37.5
37.5

T
T
T
60
60
60
60
60

T
T
T
60
60
60
60
60

T
T
T
75
75
75
75
75

T
T
T
48
48
48
48
48

Total discrimination, up to the breaking capacity of the downstream circuit breaker.

Discrimination limit = 4 kA.

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
T
T
T
94
94
94
94
94

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

65
65
65
65

65
65
65
65
65

65
65
65
65
65
65

65
65
65
65
65
65
65
65

T
T
T
T
T
T
T
T

65

65
65

65
65
65

120
120
120

120
120
120
120
120

T
T
T
100
100
100
100
100

T
T
T
100
100
100
100
100

T
T
T
100
100
100
100
100

T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T

T
T
T
100
100
100
100

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T

T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
120
120
120
120
120
120
T
T
T
T
T
T
T
T

No discrimination.

Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page 557E4300.indd/569, or check curves with Curve Direct software.