Sie sind auf Seite 1von 4

Model:

250REOZJE
Diesel

208-600 V Tier 3 EPA-Certified for Stationary Emergency Applications

Standard Features
D Kohler Co. provides one-source responsibility for the generating system and accessories. D The generator set and its components are prototype-tested, factory-built, and production-tested. D The 60 Hz generator set offers a UL 2200 listing. D The generator set accepts rated load in one step. D The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards. D A one-year limited warranty covers all systems and components. Two- and five-year extended warranties are also available. D Alternator features: d The unique Fast-Responset II excitation system delivers excellent voltage response and short-circuit capability using a permanent magnet (PM)-excited alternator. d The brushless, rotating-field alternator has broadrange reconnectability. D Other features: d Kohler designed controllers for guaranteed system integration and remote communication. See Controllers on page 3. d The low coolant level shutdown prevents overheating (standard on radiator models only). d Integral vibration isolation eliminates the need for under-unit vibration spring isolators. d Multiple circuit breaker configurations.

Ratings Range
Standby: Prime: kW kVA kW kVA 60 Hz 250--255 313--319 225--230 281--288

Generator Set Ratings


Alternator Voltage Ph 120/208 127/220 120/240 4UA10 139/240 220/380 240/416 277/480 347/600 120/208 127/220 120/240 4UA13 139/240 220/380 240/416 277/480 347/600 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Hz 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 130_C Rise Standby Rating kW/kVA Amps 250/313 250/313 250/313 250/313 250/313 250/313 250/313 250/313 255/319 255/319 255/319 255/319 255/319 255/319 255/319 255/319 867 820 752 752 475 434 376 301 885 837 767 767 484 442 383 307 105_C Rise Prime Rating kW/kVA Amps 225/281 225/281 225/281 225/281 225/281 225/281 225/281 225/281 230/288 230/288 230/288 230/288 230/288 230/288 230/288 230/288 781 738 677 677 427 390 338 271 798 754 692 692 437 399 346 277

RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. Obtain technical information bulletin (TIB-101) for ratings guidelines, complete ratings definitions, and site condition derates. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.

G5-340 (250REOZJE) 5/12e

Alternator Specifications
Specifications Manufacturer Type Exciter type Leads: quantity, type Voltage regulator Insulation: Material Temperature rise Bearing: quantity, type Coupling Amortisseur windings Voltage regulation, no-load to full-load One-step load acceptance Unbalanced load capability Peak motor starting kVA: 480 V 4UA10 (12 lead) 480 V 4UA13 (12 lead) Alternator Kohler 4-Pole, Rotating-Field Brushless, Permanent-Magnet 12, Reconnectable Solid State, Volts/Hz NEMA MG1 Class H 130_C, Standby 1, Sealed Flexible Disc Full Controller Dependent 100% of Rating 100% of Rated Standby Current (35% dip for voltages below) 785 960

D NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting. D Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds. D Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field. D Self-ventilated and dripproof construction. D Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life. D Superior voltage waveform from a two-thirds pitch stator and skewed rotor. D Fast-Responset II brushless alternator with brushless exciter for excellent load response.

Application Data
Engine
Engine Specifications Manufacturer Engine model Engine type Cylinder arrangement Displacement, L (cu. in.) Bore and stroke, mm (in.) Compression ratio Piston speed, m/min. (ft./min.) Main bearings: quantity, type Rated rpm Max. power at rated rpm, kWm (BHP) Cylinder head material Crankshaft material Valve material: Intake Exhaust Governor: type, make/model Frequency regulation, no-load to full-load Frequency regulation, steady state Frequency Air cleaner type, all models John Deere 6090HF484 4-Cycle, Turbocharged, Charge Air-Cooled 6 Inline 9.0 (548) 118.4 x 136 (4.66 x 5.35) 16.0:1 457 (1500) 7, Replaceable Insert 1800 287 (385) Cast Iron Forged Steel Chromium-Silicon Steel Stainless Steel JDEC Electronic L14 Denso HP4 Isochronous 0.25% Fixed Dry

Engine Electrical
Engine Electrical System Battery charging alternator: Ground (negative/positive) Volts (DC) Ampere rating Starter motor rated voltage (DC) Battery, recommended cold cranking amps (CCA): Quantity, CCA rating each Battery voltage (DC) 24 Volt Negative 24 60 24

Two, 950 12

Fuel
Fuel System Fuel supply line, min. ID, mm (in.) Fuel return line, min. ID, mm (in.) Max. lift, fuel pump: type, m (ft.) Max. fuel flow, Lph (gph) Max. return line restriction, kPa (in. Hg) Fuel prime pump Fuel filter Secondary Primary Water Separator Recommended fuel 11.0 (0.44) 6.0 (0.25) Electronic, 3 (10) 240.0 (63.4) 20 (5.9) Electronic 2 Microns @ 98% Efficiency 10 Microns Yes #2 Diesel

Exhaust
Exhaust System Exhaust manifold type Exhaust flow at rated kW, m3/min. (cfm) Exhaust temperature at rated kW, dry exhaust, _C (_F) Maximum allowable back pressure, kPa (in. Hg) Engine exhaust outlet size, mm (in.) Dry 54.1 (1911) 625 (1157) Min. 0 (0) Max. 7.5 (2.2) 98 (3.86)

Lubrication
Lubricating System Type Oil pan capacity, L (qt.) Oil pan capacity with filter, L (qt.) Oil filter: quantity, type Oil cooler Full Pressure 32.5 (34.4) 33.4 (35.3) 1, Cartridge Water-Cooled

G5-340 (250REOZJE) 5/12e

Application Data
Cooling
Radiator System Ambient temperature, _C (_F) * Engine jacket water capacity, L (gal.) Radiator system capacity, including engine, L (gal.) Engine jacket water flow, Lpm (gpm) Heat rejected to cooling water at rated kW, dry exhaust, kW (Btu/min.) Heat rejected to air charge cooler at rated kW, dry exhaust, kW (Btu/min.) Water pump type Fan diameter, including blades, mm (in.) Fan, kWm (HP) Max. restriction of cooling air, intake and discharge side of radiator, kPa (in. H2O) 50 (122) 16 (4.25) 36 (9.5) 265 (70) 97 (5521) 70.5 (4013) Centrifugal 863.6 (34.0) 9.0 (12.1) 0.125 (0.5) Decision-Makerr 3000 Controller Provides advanced control, system monitoring, and system diagnostics for optimum performance and compatibility. D Digital display and menu control provide easy local data access D Measurements are selectable in metric or English units D Remote communication thru a PC via network or serial configuration D Controller supports Modbusr protocol D Integrated hybrid voltage regulator with 0.5% regulation D Built-in alternator thermal overload protection D NFPA 110 Level 1 capability Refer to G6-100 for additional controller features and accessories.

Controllers

* Enclosure with enclosed silencer reduces ambient temperature capability by 5C (9F).

Operation Requirements
Air Requirements Radiator-cooled cooling air, m3/min. (scfm)] Combustion air, m3/min. (cfm) Heat rejected to ambient air: Engine, kW (Btu/min.) Alternator, kW (Btu/min.) ] Air density = 1.20 kg/m3 (0.075 lbm/ft3) Fuel Consumption Diesel, Lph (gph) at % load 100% 75% 50% 25% Diesel, Lph (gph) at % load 100% 75% 50% 25% Standby Rating 66.5 50.4 35.0 20.5 59.1 45.3 31.6 18.4 (17.6) (13.3) (9.2) (5.4) (15.6) (12.0) (8.3) (4.9) Decision-Makerr 6000 Paralleling Controller Provides advanced control, system monitoring, and system diagnostics with remote monitoring capabilities for paralleling multiple generator sets. D Paralleling capability with first-on logic, synchronizer, kW and kVAR load sharing, and protective relays D Digital display and keypad provide easy local data access D Measurements are selectable in metric or English units D Remote communication thru a PC via network or modem configuration D Controller supports Modbusr protocol D Integrated voltage regulator with 0.25% regulation D Built-in alternator thermal overload protection D NFPA 110 Level 1 capability Refer to G6-107 for additional controller features and accessories. 53.8 (3060) 20.6 (1170) 368.1 (13000) 21.8 (770) Decision-Makerr 550 Controller Provides advanced control, system monitoring, and system diagnostics with remote monitoring capabilities. D Digital display and keypad provide easy local data access D Measurements are selectable in metric or English units D Remote communication thru a PC via network or modem configuration D Controller supports Modbusr protocol D Integrated voltage regulator with 0.25% regulation D Built-in alternator thermal overload protection D NFPA 110 Level 1 capability Refer to G6-46 for additional controller features and accessories.

Prime Rating

G5-340 (250REOZJE) 5/12e

KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com

Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455 Paralleling System - Manual Speed Adjust - Voltage Sensing Miscellaneous Air Cleaner, Heavy Duty Air Cleaner Restriction Indicator Crankcase Emissions Canister Engine Fluids (oil and coolant) Added Rated Power Factor Testing Rodent Guards Literature General Maintenance NFPA 110 Overhaul Production Warranty - 2-Year Basic - 5-Year Basic - 5-Year Comprehensive Other Options _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________

Standard Features
D Alternator Protection D Battery Rack and Cables D Customer Connection (standard with Decision-Makerr 6000 controller only) D Local Emergency Stop Switch D Oil Drain Extension D Operation and Installation Literature

Available Options
Approvals and Listings California OSHPD Approval CSA Approval IBC Seismic Certification UL 2200 Listing

Enclosed Unit - Sound Enclosure and Subbase Fuel Tank Packages - Weather Enclosure and Subbase Fuel Tank Packages Open Unit - Exhaust Silencer, Critical (kit: PA-354809) - Flexible Exhaust Connector, Stainless Steel Fuel System - Flexible Fuel Lines - Fuel Pressure Gauge - Subbase Fuel Tanks Controller - Common Failure Relay - Communication Products and PC Software (Decision-Makerr 550 and 6000 controllers only) - Customer Connection (Decision-Makerr 550 controller only) - Decision-Makerr Paralleling System (DPS) (Decision-Makerr 6000 controller only) - Dry Contact (isolated alarm) (Decision-Makerr 550 and 6000 controllers only) - Input/Output Module (Decision-Makerr 3000 controller only) - Remote Audiovisual Alarm Panel (Decision-Makerr 550 controller only) - Remote Emergency Stop - Remote Serial Annunciator Panel - Run Relay Cooling System Block Heater, 2500 W, 90--120 V Block Heater, 2500 W, 190--208 V Block Heater, 2500 W, 208--240 V Block Heater, 2500 W, 380--480 V (recommended for ambient temperatures below 0C [32F]) Electrical System Alternator Strip Heater Battery Battery Charger, Equalize/Float Type Battery Heater Line Circuit Breaker (NEMA type 1 enclosure) Line Circuit Breaker with Shunt Trip (NEMA type 1 enclosure)

Dimensions and Weights


Overall Size, L x W x H, mm (in.): Weight (radiator model), wet, kg (lb.): 3000 x 1300 x 1891 (118.1 x 51.2 x 74.4) 2313--2449 (5100--5400)

NOTE: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.

- Radiator Duct Flange -

DISTRIBUTED BY:

2009, 2010, 2011, 2012 by Kohler Co. All rights reserved. G5-340 (250REOZJE) 5/12e