FIRE SAFETY MANUAL 

 
 
 
 
 
Environmental Health and Safety 
Florida Atlantic University 
777 Glades Road 
Boca Raton, FL  33431 
 
Phone: 561‐297‐3129 
Fax: 561‐297‐2210 
Email: ehs@fau.edu 
Web: www.fau.edu/ehs 
 
 
 
 
 
 
Revised: May, 2002 
TABLE OF CONTENTS
INTRODUCTION......................................................................................................................... 5

IMPLEMENTATION................................................................................................................... 5

COMPLIANCE AND RESPONSIBILITIES............................................................................. 6


RESPONSIBLITIES ..............................................................................................................................6
President, Vice-Presidents, Deans, Chairs, Directors............................................................ 6
Supervisors .............................................................................................................................. 6
Employees................................................................................................................................ 6
Students ................................................................................................................................... 6
ENVIRONMENTAL HEALTH & SAFETY ..................................................................................................6
PHYSICAL PLANT.....................................................................................................................................7
HOUSING AND RESIDENTIAL LIFE .........................................................................................................7
FACILITIES PLANNING.............................................................................................................................7
CONTRACTORS.........................................................................................................................................8
FIRE PREVENTION MEASURES ............................................................................................ 8
HOUSEKEEPING, ELECTRICAL WIRING AND APPLIANCES.......................................................................9
FIRE SAFETY EDUCATION AND TRAINING .................................................................... 10
FIRE SAFETY TRAINING ........................................................................................................................10
FIRE SAFETY EQUIPMENT .....................................................................................................................10
FIRE ALARM ACTIVATION PROCEDURE ..............................................................................................10
EVACUATION .........................................................................................................................................11
FIRE DRILLS ...........................................................................................................................................11
FIRE SAFETY INSPECTIONS AND CORRECTIVE ACTIONS ....................................... 11
STATE FIRE MARSHAL ..........................................................................................................................11
ENVIRONMENTAL HEALTH AND SAFETY ............................................................................................11
UNIVERSITY DEPARTMENTS.................................................................................................................11
EMERGENCY EVACUATION PROCEDURES.................................................................... 12

INDIVIDUALS REQUIRING ASSISTANCE ......................................................................... 13

FIRE DRILLS ............................................................................................................................. 13


PURPOSE OF FIRE DRILLS: ....................................................................................................................13
GENERAL FIRE DRILL PROCEDURES ...................................................................................................14
FIGHTING FIRES AND RESCUE ..............................................................................................................14
MEANS OF EGRESSES ............................................................................................................ 15

PUBLIC ASSEMBLY EVENTS................................................................................................ 17


DEFINITION OF PUBLIC ASSEMBLY......................................................................................................17
EVENTS COORDINATOR ........................................................................................................................17

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 1


Indoor Events ........................................................................................................................ 18
Outdoor Events...................................................................................................................... 18
ROOM CAPACITY ...................................................................................................................................18
EXITS REQUIREMENTS ..........................................................................................................................19
SET-UP PLANS ........................................................................................................................................19
OUTDOOR SPACES .................................................................................................................................19
TENTS .....................................................................................................................................................19
EXPOSITIONS ..........................................................................................................................................19
EVENT DECORATIONS ...........................................................................................................................20
Light Decorations.................................................................................................................. 20
PARADES ................................................................................................................................................20
OPEN BURNING ......................................................................................................................................21
Open Burning (Indoors) ........................................................................................................ 21
Open Burning (Outdoors) ..................................................................................................... 21
FIREWORKS ............................................................................................................................................22
BONFIRES ...............................................................................................................................................23
STORAGE-FIRE SAFETY........................................................................................................ 23
GENERAL STORAGE ..............................................................................................................................23
FLAMMABLE STORAGE .........................................................................................................................24
HIGH STACK STORAGE .........................................................................................................................24
STORAGE OF HAZARDOUS MATERIALS ...............................................................................................25
ELECTRICAL FIRE SAFETY ................................................................................................. 25
HAZARDS OF ELECTRICITY ...................................................................................................................25
ELECTRICAL FIRE PREVENTION ...........................................................................................................26
Wiring.................................................................................................................................... 26
Extension Cords .................................................................................................................... 26
Electrical Panels ................................................................................................................... 27
Electrical Outlets/Switches ................................................................................................... 28
FIRE EXTINGUISHERS ........................................................................................................... 28
THE FIRE TRIANGLE ..............................................................................................................................28
RULES FOR FIGHTING FIRES .................................................................................................................29
CLASSES OF FIRES..................................................................................................................................29
TYPES OF FIRE EXTINGUISHERS ...........................................................................................................30
HOW TO USE A FIRE EXTINGUISHER ..................................................................................................31
MOUNTING EXTINGUISHERS ................................................................................................................31
INSPECTION ............................................................................................................................................31
MAINTENANCE ......................................................................................................................................32
TAMPERING/VANDALISM .....................................................................................................................32
REPORTING DAMAGED OR DISCHARGED EXTINGUISHER .................................................................32
INSPECTION AND TESTING OF
FIRE PROTECTION AND LIFE-SAFETY EQUIPMENT................................................... 32
FIRE PROTECTION EQUIPMENT AND SYSTEMS ...................................................................................32
SERVICING, TESTING, AND MAINTENANCE ........................................................................................33

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 2


SERVICE TAGS .......................................................................................................................................33
NEW INSTALLATION ..............................................................................................................................33
UPGRADE OF EQUIPMENT .....................................................................................................................33
INSPECTION AND MAINTENANCE RECORDS........................................................................................33
NOTIFICATION OF SYSTEMS OUT OF SERVICE ....................................................................................33
LIFE-SAFETY SYSTEMS......................................................................................................... 34
FIRE ALARM SYSTEMS ..........................................................................................................................34
TEST OF SYSTEMS..................................................................................................................................34
EMERGENCY LIGHTING SYSTEMS ........................................................................................................34
GENERATOR SYSTEMS ..........................................................................................................................34
BATTERY SYSTEMS ...............................................................................................................................34
EMERGENCY POWER SUPPLY SYSTEMS (EPSS) ................................................................................34
ENGINE DRIVEN GENERATOR SYSTEMS .............................................................................................35
TEST OF AUTOMATIC FANS AND DAMPERS .......................................................................................35
WATER BASED FIRE PROTECTION ................................................................................... 35
AUTOMATIC WET-PIPE SPRINKLER SYSTEMS ....................................................................................35
Routine Inspection and Test of Systems ................................................................................ 35
Wet and Dry Standpipe Systems............................................................................................ 35
FIRE DEPARTMENT CONNECTIONS ......................................................................................................36
Inspection and Test of System ............................................................................................... 36
MINIMUM INSPECTION, TESTING AND MAINTENANCE FOR SPRINKLER SYSTEMS ............................37
FIRE PUMPS ............................................................................................................................................38
Diesel Driven Pumps............................................................................................................. 38
Electrically Driven Pumps .................................................................................................... 38
Pump Tests ............................................................................................................................ 38
Private Fire Service Mains ................................................................................................... 38
SUMMARY OF FIRE PUMP INSPECTION, TESTING, AND MAINTENANCE...........................................39
FIRE DOORS AND DAMPERS................................................................................................ 39
FIRE DOOR INSPECTION ........................................................................................................................39
FIRE DOOR TESTING .............................................................................................................................40
FIRE DAMPER INSPECTIONS .................................................................................................................40
SPECIAL FIRE SUPPRESSION .............................................................................................. 40
COMMERCIAL KITCHEN HOOD SYSTEMS............................................................................................40
“TYPE K” EXTINGUISHING SYSTEMS AND PORTABLE FIRE EXTINGUISHERS .................................40
FIXED DRY CHEMICAL EXTINGUISHING SYSTEMS ............................................................................40
FIXED WET CHEMICAL EXTINGUISHING SYSTEMS ............................................................................41
INSPECTION, TESTING AND MAINTENANCE FORMS
FOR FIRE DETECTION AND SUPPRESSION SYSTEMS................................................. 42
INSPECTIONS, TESTING AND MAINTENANCE-FIRE ALARM SYSTEM................................................42
INSPECTION ........................................................................................................................ 42
TESTING ............................................................................................................................... 43
TESTING OF FIRE ALARM CONTROL PANELS ............................................................... 43

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 3


MAINTENANCE.................................................................................................................... 44
FIRE DETECTION AND ALARM SYSTEMS.............................................................................................45
MONTHLY TESTS AND MAINTENANCE ...........................................................................................45
MONTHLY INSPECTION................................................................................................................46
ANNUAL TEST AND MAINTENANCE ............................................................................................47
FIRE SAFETY MANUAL INSPECTION FORMS ..................................................................48
FORM F-1 AUTOMATIC SPRINKLER SYSTEMS – WEEKLY INSPECTION ............................. 48
FORM F-2 AUTOMATIC SPRINKLER SYSTEMS – MONTHLY INSPECTION ........................... 49
FORM F-3 AUTOMATIC SPRINKLER SYSTEMS – QUARTERLY INSPECTION AND TESTS ..... 50
FORM F-4 AUTOMATIC SPRINKLER SYSTEMS – SEMI-ANNUAL INSPECTION AND TESTS.. 51
FORM F-5 AUTOMATIC SPRINKLER SYSTEMS – ANNUAL INSPECTION, TESTS & MAINT.. 52
FORM F-6 AUTOMATIC SPRINKLER SYSTEMS – 5-YEAR INSPECTION ............................... 53
FORM F-7 STANDPIPE AND HOSE SYSTEMS – STANDPIPE HYDROSTATIC & FLOW TEST .. 54
FORM F-8 STANDPIPE AND HOSE SYSTEMS – ANNUAL INSPECTION & MAINTENANCE .... 55
FORM F-9 HYDRANT-INSPECTIONS – SEMI-ANNUAL INSPECTION FOR DRY BARREL
HYDRANTS, ANNUAL INSPECTION FOR WET BARREL HYDRANTS ................... 56
FORM F-10 FIRE PUMPS – MONTHLY INSPECTION ........................................................... 57
FORM F-11 FIRE PUMPS – MONTHLY TESTS .................................................................... 58

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 4


INTRODUCTION

he Fire Safety Program was implemented to protect faculty, staff, students, visitors, contractors,
property and assets of Florida Atlantic University (FAU). The Fire Safety Manual serves as a guide
for establishing and maintaining fire safety conditions at the University. FAU is under the jurisdiction of
the office of the Florida State Fire Marshal (SFM), which has the authority to enter FAU or any state-
owned property to conduct an inspection or investigation. Although the Fire Safety inspections are
primarily conducted by the office of the SFM, the University Fire Safety Coordinator also makes regular
inspections at all the facilities of FAU and works and interacts with the University community. The
National Fire Protection Association (NFPA) and the Occupational Safety and Health Administration
(OSHA) are the primary standards used in the development of this Manual. Any area not specifically
covered may be referenced in one of the above standards and will apply as necessary.

IMPLEMENTATION

he University Safety Committee (USC) was established by the President to guard the health and
safety of all students, faculty, staff, visitors and the environment. The purpose of the USC is to
provide a forum for and to facilitate the interaction between and with the University community regarding
the identification and resolution of safety-related issues, including fire safety. The USC was also formed
to discover, analyze, and propose solutions to hazardous situations and subsequently advise EH&S and
Administration on corrective measures. The USC meets at least every three months or whenever
necessary. Various sub-committees, such as the Fire Safety Committee, meet when conditions or
incidents require. The areas represented on the Committee include the following:

Environmental Health and Safety University Advancement

University Police Academic Affairs

Physical Plant Northern Campuses

Student Affairs Broward Campuses


AFSCME employees union Boca Raton Campuses
Personnel Service University Attorney
Student Government

Campus fire safety is a vitally important area of concern for FAU. The potential for loss of life or injury
from a fire-related incident is one of the most serious risks a university must face. Therefore, an
institution of higher education must have a comprehensive fire-safety program. It requires an on-going
commitment on the part of the community, the institution, and the administration. Careful planning,
implementation, and maintenance are all essential ingredients of a successful fire safety program.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 5


COMPLIANCE AND RESPONSIBILITIES

ue to the danger of injury or death from fire-related emergencies, faculty, staff, students and
contractors must comply with this program. Any hazardous or emergency situation must be
reported to the proper authorities. Failure to do so could result in the possible loss of life and
property. Persons who knowingly and/or willingly violate the provisions of this program may be subject
to disciplinary action. The responsibility for campus fire prevention rests on all levels of the University
and are outlined as follows:

RESPONSIBLITIES

The President of the University

As the chief executive, has ultimate responsibility for establishing and maintaining environmental
health and safety programs for the University, and provides continuing support for the Fire Safety
Program.

Vice-Presidents, Deans, Chairs, and Directors

These administrators are responsible for enforcing fire safety programs in areas under their
control, and providing assistance to EH&S in conducting safety inspections, correcting violations,
and implementing fire prevention and evacuation policies.

Supervisors

Supervisors must brief employees on the specific hazards of their work area, on fire reporting and
evacuation plans, and fire extinguisher locations.

Employees

New employees, when attending the initial orientation, will receive an overview of the safety
programs provided by EH&S and should become familiar with the services.

Employees should comply with fire safety guidelines and receive refresher training annually.

Students

Students should familiarize themselves with the fire safety guidelines of FAU and Housing and
Residential Life. They should report vandalism and fire hazards to EH&S or Housing and
Residential Life.

Environmental Health & Safety

• Provides a fire-safe environment for employees, faculty, students and visitors.

• Coordinates and reports code compliance inspections.

• Responds to fire incidents and does the follow-up.

• Assists in the response to reports from the State Fire Marshal and the follow up.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 6


• Acts as liaison to other local and state regulatory agencies.

• Assists and advises University departments on allowable quantities of flammable materials in


storage and compatibility issues.

• Monitors fire detection and fire suppression systems.

• Develops and publicizes university fire policy.

• Serves on the University Safety Committee.

• Conducts emergency evacuation exercises.

• Provides fire safety education and training.

• Participates in the design of fire detection and alarm system standards.

• Participates in the design, construction, and renovation of buildings.

Physical Plant

• Inspects, tests, and maintains fire detection and suppression systems.

• Inspects and tests emergency exit signs and lighting.

• Participates on University Fire Safety Committee.

• Corrects fire code deficiencies in a timely manner.

• Assists in the design of fire suppression, detection and alarm systems.

Housing and Residential Life

• Provides fire safety education for student residents and housing staff.

• Conducts monthly in-house code compliance inspections for residence halls and apartments.

• Participates on the University Fire Safety Committee.

• Inspects, tests, and maintains all fire safety equipment.

• Assists and coordinates emergency evacuation exercises for housing units.

• Corrects fire code violations in a timely manner.

Facilities Planning

• Develops and maintains a university design manual.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 7


• Develops fire suppression and detection system specifications.

• Participates on University Fire Safety Committee.

• Ensures Life Safety Code Compliance for new and renovated buildings.

• Executes fire code corrections that require Capital Outlay funding.

Contractors

• Comply with local, state, and federal safety standards. If the contractor has an established
program that meets or exceeds FAU policy, it may be used on the job site. If the contractor
has not such program, FAU policies may be mandated. The more restrictive requirements
will apply.

FIRE PREVENTION MEASURES

t is of the utmost importance to be aware of conditions that may cause a fire emergency and thereby
endanger the safety of occupants in the workplace and the residence halls. The major causes of
fire at the workplace include overloaded electrical outlets and extension cords, misuse of space heaters,
mishandling of flammables, improper storage of combustibles, unsupervised cooking, and improper
disposal of smoking materials on campus grounds. Implementing fire prevention measures is the key in
an attempt to insure one’s personal safety and the safety of roommates, officemates, and friends. In
cooperation with EH&S, building officials should do the following:

Prevention Measures

• Make certain that a copy of the "Fire and Emergency Procedures" is posted in a conspicuous
location on each floor.

• Have an understanding and knowledge of the contents of the "Fire and Emergency Procedures."

• Regularly observe emergency evacuation routes, fire extinguishers and emergency and exit lights.
Immediately report any missing equipment or any other problems discovered to EH&S.

• Encourage occupants to actively participate in fire drills that are conducted regularly.

• Regularly observe the lobby, corridors, stairwells, and keep them clear of obstructions.

• Regularly observe all exits to keep them clear of obstructions AT ALL TIMES.

• Report any tampering with the fire alarm, smoke detection and suppression systems to EH&S.

• Regularly observe fire doors to make certain they are closed at all times; report inoperable doors
to Physical Plant or the respective maintenance offices.

• Inspect offices in search of:


1. Overloaded circuits
2. Frayed or damaged electrical cords

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 8


3. Improperly used extension cords
4. Improperly used appliances

• Forbid the use of candles or any other open-flame devices for any purpose in the University
buildings.

• Respect the "No Smoking Policy" in all FAU facilities.

• Enforce all Florida Atlantic University safety regulations. If there are questions, contact EH&S.

Housekeeping

• Fire doors must be kept closed at all times unless they are held open by an approved device
connected to the fire alarm system.

• Exits, stairways and passageways leading to and from exits must be kept free of obstructions at
all times. Furnishings, decorations, combustible objects, or flammables must not block exits,
access to exits, or any means of egress. Dispose of all trash as soon as possible in trashcans or
dumpsters. Waste materials must never be piled in corridors or stairwells while awaiting removal.

• Flammable and combustible materials should be present in the work area only in the quantities
required for the day’s job. These materials must be placed in an approved storage area at the end
of each day.

• Materials must not obstruct sprinkler head or be piled around fire extinguishers, fire alarm pull
stations, or sprinkler and stand pipe control values. To obtain proper distribution of water from
sprinklers, a minimum of 18 inches of clear space is required below sprinkler deflectors.

Electrical Wiring and Appliances

• Supervisors should periodically inspect all electrical equipment and cords to ensure proper use
and safe conditions. Improper use of electrical devices to obtain more outlet capacity can result in
overloaded circuits and fire.

• The use of extension cords should be minimal and used only when a flexible, temporary
connection is necessary. The cord and the outlet should be checked periodically to ensure
overheating is not occurring. Extension cords cannot be used for fixed wiring, and should never
be tacked, stapled, tied, hidden under rugs or draped over pipes or other supports, fastened to or
through woodwork, ceilings or walls. When there is a permanent need of an electrical outlet, one
should be installed.

• Be sure all electrical equipment is properly grounded. If any evidence is found of frayed, cracked
or damaged wiring or electrical outlets, the equipment affected should be taken out of service
until repairs are made.

• Space heaters, coffee makers, and all other appliances with exposed heating elements should
never be left unattended while in operation. Space heaters should not be placed under desks or in
other enclosed areas. These appliances should be unplugged after each use and stored only after
they are cool enough to touch. They should be operated away from combustible materials such as
files, curtains, trash containers, etc.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 9


FIRE SAFETY EDUCATION AND TRAINING

ducating and training the University community is a vital component of the fire safety program.
This section has been designed to address these issues and should be used as a resource for all
employees and students. The goal of EH&S is to educate and train staff, faculty, residence hall assistants,
and student clubs and organizations in the following areas:

1. Fire prevention and safety measures.

2. Proper use of fire equipment.

3. Fire drill and emergency evacuation procedures.

4. Dangers of tampering with safety equipment and failing to respond to safety procedures.

5. Detection and reporting of fire and safety hazards.

Fire Safety Training

1. Fire reporting and fire drill evacuation procedures - this type of training is site specific since
various buildings have different reporting and evacuation procedures.

2. Proper use of fire extinguishers.

3. Fire prevention and safety measures.

4. Emergency response - this training is specific to those individuals designated to respond to certain
types of emergencies in order to perform specialized functions.

Specific training requirements can be provided by EH&S upon request.

Fire Safety Equipment

Modern office buildings are designed with fire detection and suppression equipments to protect
life and property from fire. These fire safety equipments include sprinkler systems, smoke alarms
and heat detectors. A major step has been made in the installation of dependable fire safety
equipment in FAU residence halls and other buildings. Today, most FAU buildings are sprinkled
and equipped with updated fire alarm systems and other alarm monitoring companies.

Fire Alarm Activation Procedure

All employees should be familiar with fire alarm pull station locations in their building. The
building’s alarm should be immediately activated in the event of a fire, or if a person smells or
sees smoke. Even if the fire is small, the alarm should be activated, because a fire can grow
quickly and endanger building occupants. After activating the alarm, get out of the building and
call “911” from a safe location. Provide the emergency dispatcher with the name and location of
the building, and information about the fire. The FAU Police Department or the Alarm
Monitoring Company will notify the respective city Fire Department. Any attempts to extinguish
the fire can be made only after the alarm has been activated, if the fire is small, and if you have
been trained by EH&S.
FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 10
Evacuation

The primary concern in the event of a fire is to evacuate everyone from the building as quickly
and safely as possible. In order to accomplish this, occupants must be prepared in advance for a
quick and orderly evacuation. Evacuations must be practiced periodically in order to get used to
the procedures.

Fire Drills

EH&S conducts fire drills in all University buildings as required by State law. Before the drill is
held, Florida Atlantic University’s Police Department and other monitoring companies will be
notified in advance of the time and location of the drill. Following each drill, the person in
charge of administering the drill must complete a Fire Drill Report.

Fire Safety Inspections and Corrective Actions

State Fire Marshal

All University buildings are inspected annually by the State Fire Marshal to ensure they comply
with all applicable State Fire Codes. All fire code deficiencies identified are subsequently noted
in a detailed report and forwarded to Environmental Health and Safety to coordinate corrective
actions.

Environmental Health and Safety

EH&S performs periodic fire safety inspections of campus facilities, and ensures buildings
comply with state fire codes and are safe for occupancy. EH&S also assists the State Fire Marshal
by conducting follow-up inspections to evaluate the status of corrective actions. EH&S facilitates
fire code correction by assigning responsibility for specific corrective actions to Physical Plant,
Facilities Planning, Housing Department, Department Chairpersons, and deans and directors
where applicable.

University Departments

Each department is responsible for correcting code violations that are reported to departmental
personnel by EH&S. Departments must forward corrective actions reports to EH&S within the
time frame specified in the notice of violation correspondence.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 11


EMERGENCY EVACUATION PROCEDURES

he purpose of the Emergency Evacuation Procedures is to establish minimum requirements that will
provide a reasonable degree of life safety from fire and similar emergencies in Florida Atlantic
University (FAU) buildings and structures. The Emergency Evacuation Procedures will be utilized to
evacuate all occupants regardless of the type of emergency. Failure to leave the building when a fire
evacuation alarm is sounding is a violation of State law.

GENERAL

A fire emergency exists whenever:

• A building fire evacuation alarm is sounding. (Campus buildings will be immediately and totally
evacuated whenever the building fire alarm is sounding.)

• There is presence of smoke, or the odor of burning.

• An uncontrolled fire, or imminent fire hazard occurs in any building or area of the campus.

• There is a spontaneous or abnormal heating of any material, an uncontrolled release of combustible


or toxic gas or other material, or a flammable liquid spill.

When a fire emergency exists, an individual will accomplish, or attempt to accomplish, the following
actions:

• Activate fire alarm system located along exit routes.

• Evacuate the building. Do not use elevators.

• Call 911 from a safe area and give name, location, and nature of emergency.

• Remain at a safe location at least 100 feet away from the building until you are told to re-enter by the
City Fire Department, University Fire Safety Officer, or other emergency personnel.

EVACUATION PROCEDURES

When a fire evacuation alarm is sounding, all occupants will:

• Shut down any experiments or procedures that should not be left unattended.

• Take or secure all valuables, wallets, purses, keys, etc.

• Evacuate the building immediately and in an orderly manner. The last occupant to leave a room
should close the door leading to the corridor.

• Never use the elevators. In most university buildings, elevators are automatically recalled to the
street floor or transfer level upon the activation of the buildings’ fire alarm system.

• Proceed to the nearest and safest exit.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 12


• If possible, assist non-ambulatory occupants to areas of refuge, or to ground level exits. (All
members of the University Community are responsible, within the limits of their abilities, to assist
those individuals requiring assistance prior to, during, or after an emergency. Normally, assistance is
in the form of notifying emergency workers of the location of these individuals or by actually
providing guidance to safe areas. [Presidential Memorandum #56])

• Remain at a safe location at least 100 feet away from the building until instructed to re-enter by the
City Fire Department, University Fire Safety Officer, or other emergency personnel.

INDIVIDUALS REQUIRING ASSISTANCE

ndividuals requiring assistance should proceed to the nearest stairway and request assistance from
other evacuees. Do not obstruct the stairway or door leading to the stairway. If the location
becomes unsafe, move to a different exit stairway and call for help until rescued.

It is suggested that people with disabilities prepare for emergencies in advance by learning the locations
of exit corridors and exit stairways, by planning an escape route, and by showing a classmate, co-worker,
or instructor how to assist him/her in case of an emergency. Individuals with speech impairment should
carry a whistle or have other means of attracting attention. All exit corridors and stairways are marked
with exit signs and are protected with self-closing fire rated doors. These are the safest areas during an
emergency. Rescue personnel will check all exit stairways first for trapped persons.

Ways to help individuals who require assistance

 Become familiar with the individuals who require assistance in your area.
 Inform hearing impaired/deaf persons when a fire evacuation alarm is sounding.
 Assist visually impaired/blind persons to an exit stairway.
 Inform University Police, Command Post outside the building, or 911 of disabled persons
located inside the building that you are unable to evacuate safely.
 In the extreme case where you must physically evacuate a disabled person, you should ask that
person how to safety carry or assist him/her.

FIRE DRILLS

nvironmental Health and Safety conducts Fire Drills in all University buildings as required by
State law. The primary concern in the event of a fire is to get everyone out of the building as
quickly as possible. To do this, occupants must be prepared in advance for a quick and orderly
evacuation. A trained group will act more calmly under emergency situations, thereby dispelling panic,
which has caused more casualties than fire itself. Slow evacuation and panic account for the large
majority of all fatalities in fires.

Purpose of Fire Drills:

• To allow occupants to familiarize themselves with drill procedures, location of fire exits, and the
sound of the fire alarm.

• To allow EH&S to monitor the timeliness and effectiveness of evacuations.


FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 13
• To detect technical problems with the Fire Alarm Equipment.

• To gauge whether or not persons evacuate the building as legally required.

• To check if fire protection equipment, such as fire doors, is being used properly.

• To gauge how long it takes to evacuate each building, and which exits are generally used.

General Fire Drill Procedures

1. Fire drills are arranged and supervised by the University Fire Safety Officer, or representative, with
the cooperation of Building Supervisors and the Police Department.

2. The date and time will be scheduled when most occupants are in the building.

3. The University Fire Safety Officer will inform Campus Police of the exact times the alarm will be
pulled for the drill.

4. The University Fire Safety Officer will activate the fire alarm.

WHEN THE EVACUATION ALARM SOUNDS, “EVERYONE MUST LEAVE THE


BUILDING

5. After evacuation occupants shall proceed to a pre-determined location and wait for the instruction of
emergency personnel to re-enter.

6. The University Fire Safety Officer shall silence and reset the panel when everyone has evacuated the
building.

7. Fire drills will be monitored for effectiveness and documented.

8. The Building Supervisor shall receive a completed copy of the drill report from the University Fire
Safety Officer after the completion of every drill.

9. Fire drills will be held at least:

 Once per semester in residential occupancies.


 10 times a year at Henderson University School and Slattery Child Care Center.
 Annually in all other buildings.

Fighting Fires and Rescue

Search and rescue is the responsibility of emergency personnel. If the emergency is fire, and it is small or
in its earliest stages and can be fought effectively with the available extinguishers, then trained persons
may attempt to extinguish such fires providing there is no life safety hazard to the user, and such action
will not endanger others. The proper selection of a fire extinguisher and knowledge of its operation are
critical to containing and extinguishing the fire, and preventing injury to the user. Fire fighting
procedures for University buildings have been pre-planned by the City Fire Department and the
University Fire Safety Officer.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 14


MEANS OF EGRESSES

ooking at the typical causes of fire deaths, blocked exits are probably the most preventable and the
one most likely to result in criminal negligence charges. We have a very definite responsibility to
provide a safe environment to anyone working, learning or attending events within a building. It is
therefore essential that there is access for quick evacuation during an emergency. The following fire
safety requirements must be strictly observed with regard to means of egresses.

Fire Safety Requirements for Fire Doors, Corridors, Egress Routes and Exit Doors

Fire/Smoke Doors

Two of the most important functions of doors in terms of life safety are to act as a barrier to fire and
smoke and to serve as components in a means of egress.

1. Fire and smoke rated doors shall not be blocked open.

2. The self-closing devices shall not be disconnected or rendered inoperable.

3. For special situations that the door must be held open for movement of furniture, equipment or
other large size items, the person responsible for the move will provide an individual at the door
to ensure the door is not left open, if the building is evacuated.

4. Door chocks or foot stops may not be installed on any fire rated door. Also, furniture, appliances,
etc., may not be used to hold the door open.

5. Doors that need to be left open for high traffic areas or for visual security, may be authorized by
EH&S. If authorized, the door will require an automatic magnetic release device installed which
will release the door when any emergency alarm device is activated.

6. Obstructions that will prohibit fire and smoke rated doors from closing and latching without
human intervention are not permitted.

Corridors, Egress Routes and Exit Doors

In an emergency, one of the most important requirements is to ensure that all occupants can leave the
building safely. To accommodate this, corridors, hallways and exits are designed and constructed to
allow people to leave the building by the safest and quickest method possible.

Obstructions

• No corridor, aisle way or component of a means of egress may be obstructed.

• Non-combustible furniture in lobbies must not obstruct the minimum width of egress and
be arranged so there is a direct path through the lobby to the EXIT.

• Wires, cables or extension cords may not be laid across corridors, aisles or pathways.

• EXIT doors must remain unlocked during hours in which the building is occupied. Special
locking devices must be approved by the State Fire Marshal's office.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 15


Minimum widths

• Minimum widths (which increase according to the number of people) range from twenty-eight
inches between desks to forty-four inches for corridors.

• Furniture, artwork, wall hangings, statues, etc. which protrude from the walls must not obstruct
the minimum width, nor present a tripping, injury or other safety hazard.

• Minimum aisle widths must be maintained at all times.

Protrusions

• Minimum ceiling height in exit passageways is seven feet six inches. Lights, decorations, signs,
or any other items hung from the ceiling may not be lower than six feet eight inches.

• Wires or cables hung from the ceiling must not present a safety hazard, such as snagging
equipment being transported through the corridor.

Items Not Permitted in Corridors

• Flammable storage cabinets of any size.

• Compressed gas bottles of any size.

• Carts, cabinets, shelves or other items on which combustibles or flammables are likely to be
stored.

• Chemicals, munitions, pyrotechnics or any other hazardous material.

• Any item that will impede the normal or emergency flow of traffic, or will obstruct any
emergency device.

• Portable heaters, coffee pots, food warmers ,or other devices that may present a hazard.

• Unprotected high voltage, electrical or gas powered equipment of any sort.

• Any combustible material and overstuffed furniture, boxes, etc.

Atriums and Large corridors

The open spaces at the base of atriums and large corridors must be left clear at all times. If there is a need
to use these open spaces temporarily for any kind of function, it must be done in a way that is not
obstructing passage. Environmental Health & Safety must be consulted in advance for proper safety
precautions.

Fire Lanes and Emergency Access

In the event a fire should occur, it is critical that emergency responders be able to access the building, or
location of the emergency. Fire lanes and emergency access routes have been provided for this purpose.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 16


Fire Lanes

Fire Lanes (normally marked in red on the curb) may not be blocked at any time. This includes
temporary parking for the purpose of "just dropping something off."

Emergency Access

Fire hydrants, fire department connections, or other emergency equipment may not be obstructed
at any time. Parking is prohibited within fifteen feet of a fire hydrant, or fire department
connections.

Emergency Vehicle Response

All vehicles will, when an emergency vehicle approaches from any direction, immediately pull
over to the right side of the road to allow the vehicle to pass.

PUBLIC ASSEMBLY EVENTS

ersons planning events should contact the Office of Space Utilization and Analysis
(OSUA) for events management procedures. EH&S should be contacted for safety
requirements, clearance for public assembly events, and events that attract large crowds.

Definition of Public Assembly

The Fire Prevention Code defines a public assembly occupancy as follows: Assembly occupancies
include, but are not limited to, all buildings or portions of buildings used for gathering together 50 or
more persons for such purposes as deliberation, worship, entertainment, eating, drinking, amusement, or
awaiting transportation (NFPA Life Safety Code).

Fire And Life Safety

Public assembly events involve various risk factors associated with having large numbers of people in one
location. The primary risk factors are the high occupant density, and occupants not being familiar with
the area. This risk can be reduced through proper event planning and management.

Examples of assemblage occupancies found on FAU campuses include large meeting rooms and
classrooms, auditoriums with fixed or loose chair seating, multi-purpose rooms, concert halls, theaters,
sport arenas, field houses, restaurants, bars, libraries, and outside areas.

In order to comply with the requirements of the Fire Prevention Code, it is necessary for the Office of the
State Fire Marshal or the City Fire Department to make certain approvals for events as noted in these
guidelines. Required approvals and inspections should be requested as far in advance as possible. Large
scale events, and events that use pyrotechnics and fireworks, require the Office of the State Fire Marshal
and the City Fire Department to be present during the event.

Events Coordinator

Persons hosting an event should assign an events coordinator to oversee on-site logistics for
indoor and outdoor events.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 17


Indoor Events

The events coordinator must:


1. Become familiar with the location of fire alarms, fire extinguishers, and emergency exits. In the
event of an emergency, the coordinator will pull the fire alarm, supervise evacuation of the
building, and call 911 from a safe location.
2. Ensure the maximum allowable occupant load numbers posted inside the assembly area are not
exceeded.
3. Ensure exits are unobstructed at all times during the event.
4. Ensure decorations are in accordance with event decorations guidelines.

Outdoor Events

The events coordinator must:


1. Provide a site plan to EH&S indicating locations of activities and equipment, tents and canopies,
electrical outlets and cords, propane heaters, booths, etc. to verify that proper clearances and
access are maintained.
2. In the event of an emergency, supervise evacuation of the area and call 911.
3. Provide fire extinguishers throughout the event site. Contact EH&S for the type, quantity, and
placement of the fire extinguishers.

Room Capacity

Information on room capacities can be obtained from the OSUA or EH&S. The Life Safety Code
will determine the size of the occupant load. Be aware that the occupant load is the maximum
capacity based on the net clear floor area. Stages and other obstructions, seating arrangements and
use of tables will decrease the capacity. The type of event is also a determining factor when planning.

The following are examples of occupant load for areas that are frequently used:

Use Area per person


Concentrated – (Auditorium and dance floor) 7 sq. ft./net
Less concentrated – no fixed seating (Conference 15 sq. ft.
room and classroom, gymnasium and dining
lounge)
Fixed seats No. of fixed seats
Stage (persons on stage) 15 sq ft
Kitchen 100 sq ft. gross
Library (stack area) 100 sq ft. gross
Library (reading) 50 sq ft. gross
Swimming Pool (water surface) 50 sq ft. gross
Swimming Pool (deck area) 30 sq ft. gross

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 18


Exit Requirements

The placement of stages, seats, equipment (including wiring), and security arrangements affect exits and
access to exits. Exits must remain unobstructed and provide clear access to the outside at all times.
Wires or cables cannot be placed in front of exits or on steps, and must be properly taped down to the
floor, or covered to avoid tripping hazards.

The number of exits required is based on room capacity.

Number of Persons Minimum No. of Exits


≤ 49 1
50-100 2
101-600 3
601 or more 4

Set-up Plans

The Boca Raton campus has standard set-up plans for the gymnasium, the Live Oak Pavilion, and the
dining halls. Physical Plant and the respective facilities maintain these plans and should be contacted.
Set-up plans for other spaces not routinely used for public assembly (including lobbies and atriums), or
any plans that are different from existing standard plans, must be approved in advance by the Office of
the State Fire Marshal for conformance with life safety regulations.

Outdoor Spaces

Enclosed open areas such as a stadium must meet the same requirements as buildings. Fenced open areas
must have at least two exits. A registered professional engineer must certify the bleachers, grandstands
and platforms as structurally sound.

Tents

Tents are considered buildings and must meet most of the same requirements. Tent materials must be
properly certified as flame retardant. Some tents have attached labels, but when labels are not attached
sponsors, promoters, or other production personnel must have documentation that certifies the tent
material is flame retardant. Certification must be based on NFPA 701, Standard Methods of Fire Tests
for Flame Propagation of Textiles and Films. Flooring for tents must be non-combustible, straw, hay,
wood chips, mulch, or other similar materials are prohibited from use as flooring. EH&S must approve in
advance the use of open flames (including those used for cooking or warming food) and heaters.

Tent suppliers must be able to certify that tents have been erected in accordance with manufacturer
recommendations, industry standards, and code requirements.

Expositions

Expositions of products or other displays have a number of special requirements. Contact EH&S for
consultation and event planning.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 19


Event Decorations

Decorations are common factors in the spread of fire. It is necessary to ensure that all decorations used
meet the requirements of safety and fire resistance.

• Decorations cannot conceal or obstruct, in whole or part, exits, exit lights, fire alarm pull boxes,
fire hose cabinets, fire extinguishers, sprinkler heads, smoke detectors, or other fire related items.

• All decorations used in corridors, lobbies, assembly rooms, dining rooms, classrooms and offices
must be non-combustible or flame retardant.

• If trees or plants (natural or artificial) are used, keep them out of corridors and away from
doorways.

• No candles or open flame devices are permitted.

• Do not decorate corridors with wrapping paper.

• Remove all decorations, wrappings and trees immediately after the event.

Light Decorations

• Use only electric decorative lights and associated wiring for decorative lights that are UL or FM
listed.

• Flame producing devices such as, but not limited to candles, may not be used.

• Mixing and matching lights can create a fire hazard. Keep outside lights outside and inside lights
inside.

• Check the light bulbs, sockets, wires and plugs to make sure nothing is cracked, broken or
exposed. Discard any defective light strands.

• Keep lights away from flammable and/or combustible materials.

• Extension cords used for temporary decorations must be UL listed.

• Do not connect more than three sets of lights to an extension cord.

• Keep all cords out of high-traffic areas where they could create a tripping hazard.

• Do not run cords through, under or behind a door, furniture or carpet. Such practice could lead to
a fire.

• Electrical outlets should not be overloaded.

• All lights should be turned off before leaving the building.

Parades

There are special hazards associated with parades that must be addressed. The use of open flames on
floats is strictly prohibited. Vehicles, both for towing and trailers used in the construction of floats,
FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 20
should be currently registered and in good operating condition.

All occupants should be able to easily exit the vehicle in the event of a fire. Fire extinguishers must be
carried on all vehicles used to pull floats in parades. Contact EH&S for the type and quantity of fire
extinguishers needed.

Open Burning

Open burning is defined as any open/exposed flame, whether indoors or outdoors, which could cause a
potential fire hazard. Examples are bonfires, campfires, leaf burning, artwork involving flames,
pyrotechnics of any kind, etc. Open burning on any FAU property must be approved in writing by EH&S
after consultation with the Office of the State Fire Marshal and the City Fire Department.

Open Burning (Indoors)

Open burning indoors (particularly when such burning might activate any type of fire alarm detection/
suppression system) is normally prohibited. Special exceptions may be authorized under the following
conditions.

1. A written request is sent to EH&S at least two weeks in advance prior to the event.

2. The proposed burning will not endanger the occupants of the facility.

3. The burn location will not block any emergency device or access to exits.

4. The event coordinator will contact EH&S, Campus Police, and the building manager 24 hours in
advance of the event for final coordination.

5. The event coordinator will be responsible for providing a Fire Watch of the entire building during
the time of the open burning if any safety system must be shut down.

6. The event coordinator will be responsible for assigning a Fire Guard in the burning area.

7. The event coordinator will be responsible for complete extinguishing and removal of all
materials.

8. At the end of the burning, a thirty-minute watch will be made of the area to ensure there is no
residual heat left in the material burned.

Open Burning (Outdoors)

Open burning outdoors will be authorized under the following conditions.

1. A written request is sent to EH&S at least two weeks in advance of the event.

2. The proposed burning will not endanger any adjacent building, vehicles or vegetation.

3. The burn location will not block access for emergency vehicles to any building, street, or
emergency device.

4. Open flame fires will not be within fifty feet from any building, vehicle, or vegetation, or twenty-
five feet from any flammable storage. The distance may vary according to the size of the event.
FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 21
5. The event coordinator will be responsible for providing Fire Guards in the burning area.

6. The event coordinator will contact EH&S, Campus Police, and occupants of adjacent buildings
24 hours in advance prior to the event or operation for final coordination.

7. The host will be responsible for complete extinguishing and removal of all materials used in the
open burning.

8. A five to thirty minute watch will be made of the area to ensure there is no residual heat left in the
material.

Fireworks

Fireworks displays will be coordinated through EH&S, and will be authorized under the following
conditions:

1. A written request is sent to EH&S at least two weeks in advance of the event.

2. A permit is obtained from the State Fire Marshal, or the City Fire Department.

3. The individual handling the fireworks submits a written proposal to the event’s host and EH&S
including the type of display, type and amount of materials to be used, current certification by a
recognized agency, proof of insurance and method of transportation and storage, two weeks in
advance of the event for review.

4. Individuals providing fireworks displays meet the requirements of any and all applicable federal,
state, county, and city laws, or safety standards pertaining to licensure and permits, certificates of
competency, and display methods.

5. The individual handling the fireworks is a licensed handler of the material to be used and will be
responsible for the proper storage, handling, transportation, use and disposal.

6. The sponsor of the fireworks event, or the contractor, furnishes a certificate of liability insurance
in the amount of $1,000,000.00 naming the University and the Board of Trustees as additional
insurers.

7. The display contractor conducts an on-site safety assessment prior to, and at the termination or
the end of the display.

8. The contractor is the only one handling and launching the fireworks. The contractor and/or
sponsor provides adequate personnel to monitor the perimeter of the discharge and landing site
before the exhibit begins, and continues the monitoring until the site has been inspected after the
display, and the "all clear" signal has been given.

9. Remote ignition systems that are not under the direct control of an on-site operator are not used.
Displays are set up using methods for interrupting firing in the event any unforeseen safety
problem arises.

10. The discharge site is positioned at a distance meeting current National Fire Protection Association
criteria.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 22


11. The maximum number of serial displays is 800 shells. Free floating devices or shells less than
four inches in diameter are not permitted unless specifically approved by the Department of
Environmental Health and Safety.

12. The host of the event will provide a Fire Guard for the length of time the material is being
handled.

Bonfires

Bonfires are having a greater number of requirements placed upon them from fire safety and
environmental aspects. A permit from the City Fire Department is required for bonfires. EH&S applies
for the permit after a written request is received from the host two weeks prior to the event. The following
requirements must be met in order to ensure everyone’s safety.

• Bonfires will only be permitted when climatic conditions are acceptable.

• The bonfire location must be completely cleared (including grass and plants) by Physical Plant.

• Gasoline cannot be used to ignite the fire.

• Fire materials must not contain treated wood, plastics, rubber or other toxic producing material.

• If possible, a water hose should be available, otherwise a 4A or larger chemical extinguisher, or


two 2A rated water extinguishers must be provided.

• The site must be guarded if the bonfire is not lit immediately after it is prepared to prevent
premature ignition by others.

• A barrier should be constructed around the bonfire to keep spectators back.

• The sponsoring organization is responsible for lighting the fire, monitoring the extinguishing, and
cleaning up the site.

• The fire cannot burn for more than 3 hours.

• The host of the event will assign a Fire Guard for the length of the bonfire. A thirty-minute watch
must be made to ensure there is no residual fire left in the burned material.

• The host must meet other requirements mentioned in the open burning section.

STORAGE-FIRE SAFETY

torage in itself does not constitute a fire hazard. A fire hazard is created when items are stored
improperly or in a hazardous location, or block egress and exits.

General Storage

This section pertains to any room or building used for temporary or long-term storage of combustibles.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 23


• Combustible materials must be separated from other hazardous materials such as flammables,
corrosives, explosives, oxidizers etc. Contact EH&S for approval of separations.

• Storage areas must be separated from other areas by a one-hour fire barrier with a fire rated, self-
closing door, and be protected by fire detection and/or suppression systems.

• Stored materials must be kept at least thirty-six inches from any heat source.

• Aisles in storage rooms must have a minimum width of twenty-eight inches to allow for
evacuation, and permit firefighters to gain access to the most remote area of the room.

• Storage cannot block fire extinguishers, fire alarm pull stations, emergency or exit lighting,
access to evacuation routes or the exit door, emergency equipment or prevent entry of emergency
personnel.

• Storage under stairs is not permitted unless the area is enclosed and protected with a one-hour fire
rated enclosure and a detection and/or suppression system.

• Doors to storage rooms may not be "propped" open at any time.

• Contact Property Management for proper disposal of surplus, obsolete and unused property.

• Smoking is not permitted in any storage area under any conditions.

Flammable Storage

It is critical that flammables are used properly and stored safely.

• Rooms used for flammable storage must be constructed to meet the requirements for one-hour
fire rating, ventilation, heating, electrical systems, fire detection and/or suppression systems.

• Flammables generally are not permitted to be stored in basements of buildings. Exceptions will
be determined by EH&S and must be authorized in writing.

• A "daily use" of flammable liquids may be stored on open shelves. “Daily use” refers to a small
amount of consumable flammables that are expected to be used in a repetitive nature, and the
amount used would not constitute more of a hazard than other ordinary combustibles in the room.

• Flammables, required to be stored away from combustibles, will be stored in an approved


flammable storage cabinet. This cabinet will be labeled and incorporate self-closing doors.

• Flammable storage will be kept at least 50 feet from open flames or other heat sources.

• Oily or grease-laden rags must be placed in a self-closing oily rag can for proper cleaning or
disposal.

• Ordinary combustibles may not be stored in flammable storage.

High Stack Storage

This type of storage has become increasingly popular for space saving purposes for records and

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 24


commodities. This also presents a different type of hazard for fire safety and fire fighting.

• It is highly recommended that non-combustible materials be used in the construction of storage


racks. This reduces the amount of fire spread should a fire occur.

• Under no circumstances may storage of materials be closer than eighteen inches of sprinkler
heads.

• Aisle widths in high rack storage, which also requires the use of mechanical devices such as
forklifts or carts, must be of sufficient width to allow personnel evacuation if a cart is in the aisle.

Storage of Hazardous Materials

Hazardous products may produce a substantial amount of toxic vapors, as well as react with a fire to
create a fast moving or explosive situation. Storage of such materials must be strictly controlled. See
FAU Chemical Hygiene Plan, Appendix B, “Hazardous Materials Manual.”

• Proper storage and handling of these materials will be determined by EH&S.

• Hazardous materials may not be stored within 50 feet of any open flame or heat source.

• Hazardous materials must not obstruct evacuation routes or be stored under stairs.

• Hazardous materials must be stored in separate cabinets or rooms according to their reactive
properties.

• Smoking is not permitted within 50 feet of a hazardous materials storage building.

ELECTRICAL FIRE SAFETY

lectrical fires claim the lives of 200 Americans each year and injure 1,500 more. Some of these fires
are caused by electrical system failures and appliance defects, but many are caused by misuse and
poor maintenance of electrical appliances, incorrectly installed wiring, overloaded circuits, and
improper use of extension cords.

Hazards of Electricity

The primary hazards associated with the use of electricity are:

• Shock

Electric shock occurs when the human body becomes part of a path through which electrons can
flow. The resulting effect on the body can be either direct or indirect.

Direct

The electric current itself causes injury or death when electric current flows through the
human body.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 25


Indirect

Although the electric current through the human body may be well below the values
required to cause noticeable injury, reaction to the current can result in falls from ladders or
scaffolds, or movement into operating machinery. Such reaction can result in serious injury
or death.

• Burns

Burns can result when a person touches electrical wiring or equipment that is improperly used or
maintained. Typically, such burn injuries occur on the hands, chest and face.

• Arc blast

Arc blasts occur from high amperage currents arcing through air. This abnormal current flow
(arc-blast) is initiated by contact between two energized points. This contact can be caused by
persons who have an accident while working on energized components, or by equipment failure due
to fatigue or abuse. Arc blast research has recorded temperatures as high as 35,000 degrees
Fahrenheit. The two primary hazards associated with an arc-blast are:

Explosions

Explosions occur when electricity provides a source of ignition for an explosive mixture in
the atmosphere. Ignition can be due to overheated conductors or equipment, or normal
arcing (sparking) at switch contacts. OSHA standards, the National Electrical Code, and
related safety standards have precise requirements for electrical systems and equipment to
prevent such occurrences.

Fires

Electricity is one of the most common causes of fire both in the residence and in the
workplace. Defective or misused electrical equipment is a major cause, with high resistance
connections being one of the primary sources of ignition. High resistance connections occur
where wires are improperly spliced or connected to other components such as receptacle
outlets and switches.

Electrical Fire Prevention

The following are simple steps to take to prevent the loss of life and property resulting from electrical
fires.

• Wiring

In order to prevent high resistance connections, only licensed electricians are permitted to work
on electrical wiring or electrical equipment. (See paragraph “Fires” above.)

• Extension Cords

Electrical extension cords are an acceptable means of providing TEMPORARY electrical power;
however, they cannot be used as a substitute for permanent electrical wiring.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 26


Extension cords can be use provided they are:

 Used temporarily only, not to exceed 90 days.

 Used for non-heat producing devices (i.e.: radios, computers, answering machines, etc.).

 UL approved and Factory Mutual listed, and three-wire grounded cords.

 Not connected, spliced together, or piggybacked.

 Visible and protected from damage.

 Used as temporary wiring for holiday displays, artwork, or vendors at special events provided
they meet the above requirements.

 Plugged into a permanent outlet.

 Used for applications where equipment is not routinely used.

Extension cords will not be permitted when they are:

 Used as permanent wiring.

 Used on heat producing or high voltage devices such as heaters, coffee pots, high wattage
lamps, refrigerators, microwave ovens, etc.

 A tripping hazard for normal traffic or emergency evacuation.

 Run through openings in walls, ceilings, or doorways; or under carpets or flooring.

 Draped over light or electrical fixtures, ventilation ducts, or pipes.

 Showing signs of wear, defects, bulging, exposed wire or other damage.

 Used in corrosive areas or near any substance that would deteriorate the cord.

 Plugged into a power strip or another extension cord.

• Electrical Panels

Electrical Panels must:

 Be accessible to the occupants in an emergency.

 Not be obstructed for 36 inches in all directions around the panel and in front for access.

 Have the panel cover and panel door securely in place and closed.

 Have all breaker and main switches clearly marked as to the equipment area they control.

 Be identifiable as an electrical panel. Do not cover or paint to match the wall, etc.
FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 27
Electrical Panels must not:

 Be locked.

 Have the breakers taped or otherwise secured in the “on” position.

 Have any work performed on the panel by anyone who is not a licensed electrician.

• Electrical Outlets/Switches

Electrical outlets are quite often not thought of as being a fire hazard. It is possible that an
overload on the electrical system can cause an outlet to spark. The following safety requirements
must be complied with.

Outlets must:

 Have the cover plate securely fastened to the outlet box.

 Be replaced when broken.

 Have an approved cover.

 Have a ground fault circuit interrupter if within 6 feet of a water source.

 Be at least one foot from combustible items such as trashcans, boxes of paper, etc.

• Multi-outlet assemblies

Power strips must be properly placed, equipped with fuses or circuit breakers, plugged to a
permanent outlet, grounded 3-wire type, and UL approved.

FIRE EXTINGUISHERS

H&S is responsible for the installation, tracking and maintenance of fire extinguishers in all FAU-
owned buildings. Extinguishers in leased property are the responsibility of the landlord. EH&S
gives hands-on-training to FAU employees and students on a regular basis.

Fire extinguishers are special pressurized devices that release chemicals or water to aid in putting out a
fire. They keep small fires from spreading, assist in fighting fires until the Fire Department arrives, and
may help provide an escape route for you. REMEMBER: A fire extinguisher is no substitute for the Fire
Department. Always call the Fire Department first no matter how small you think the fire is. In order to
understand how a fire extinguisher works, you need to know about fire.

The Fire Triangle

Four things must be present at the same time in order to produce fire

1. Enough oxygen to sustain combustion

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 28


2. Enough heat to raise the material to its ignition temperature

3. Some sort of fuel or combustible material, and

4. The chemical, exothermic reaction that is fire

Oxygen, heat and fuel are frequently referred to as the “fire triangle.” Add the fourth element, the
chemical reaction, and you actually have the “fire tetrahedron.” The important thing to remember is when
you take any of these four things away, you will not have a fire, or the fire will be extinguished.

Essentially, fire extinguishers put out fires by taking away one or more elements of the fire
triangle/tetrahedron. Fire safety, at it’s most basic, is based upon the principle of keeping fuel sources and
ignition sources separate.

Rules for Fighting Fires

Fires can be very dangerous and you should always make certain to not endanger yourself or others when
attempting to put out a fire. For this reason, when a fire is discovered:

• Assist any person, who is in any immediate danger to safety, if it can be accomplished without
risk to you.

• Activate the building fire alarm system or notify the fire department by dialing 911. When you
activate the building fire alarm system, it will automatically notify the fire department and get
help on the way. It will also sound the building fire alarm system to notify other occupants, and it
will shut down the air-handling units to prevent the spread of smoke throughout the building.

• Only after completing the above two, you may use an extinguisher if you are trained and the fire
is small.

However, before deciding to fight the fire, keep these rules in mind:

NEVER FIGHT A FIRE IF:

• You do not know what is burning and you do not know what type of fire extinguisher to use.
Even if you have an ABC extinguisher, there may be something in the fire, which could explode
or produce toxic smoke. Chances are you know what is burning, or at least have a pretty good
idea, but if you do not know, let the fire department handle it.

• The fire is spreading rapidly beyond the spot where it is started. The time to use the fire
extinguisher is in the recipient, or beginning stages of the fire. If the fire is spreading quickly, it
is best to simply evacuate the building, closing windows and doors as you leave.

Classes of fires

There are five classes of fires. All fire extinguishers are labeled using symbols for the classes of fires they
can put out. A red slash through any of the symbols tells you the extinguisher cannot be used on that class
of fire. A missing symbol tells you only that the extinguisher has not been tested for that class of fire.

1. Class A fires involve paper, wood, and other ordinary combustibles.

2. Class B fires involve flammable liquids, such as gasoline, oil, and some paints and solvents.
FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 29
3. Class C fires involve energized electrical equipment such as power tools, wiring, fuse boxes,
appliances, TVs, computers, electric motors, etc.

4. Class D fires involve combustible metals, such as magnesium, potassium, and sodium.

5. Class K fires involve grease in commercial cooking equipment.

Types of Fire Extinguishers

The extinguisher must be appropriate for the type of fire being fought. Multi-purpose fire extinguishers,
labeled ABC, may be used on the three classes of fires. Using the wrong type of extinguisher can cause
harm to a person and make the fire worse. In some cases, it may be dangerous to use a fire extinguisher,
regardless of the type. For example, an extinguishing agent released under pressure could spread a grease
fire in a frying pan rather than put it out.

1. Pressurized water extinguishers are being phased out because they do


not work with class B and C fires. They can be used for ordinary
combustibles like wood, paper, many plastics, cloth and rubber.

2. Carbon dioxide extinguishers are generally


used in areas of sensitive electrical or
electronic equipment since it is gas and leaves
no residue that damage the equipment.
Carbon dioxide functions by removing or
displacing the oxygen in a fire.

3. Dry chemical fire extinguishers are by far the most


common on campus. They are effective on all three
classes of fires. Dry chemicals function by interrupting
the chain reaction of the fire tetrahedron.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 30


How to Use A Fire Extinguisher

It is easy to remember how to use a fire extinguisher if you can remember the acronym PASS, which
stands for PULL, AIM, SQUEEZE, and SWEEP.

Pull the pin.


This will allow you to discharge the fire extinguisher.

Aim at the base of the fire.


If you aim at the flames (which is usually the temptation), the extinguisher agent will
fly right through and do no good. You have to hit the fuel.

Squeeze the top handle or lever.


This depresses a button that releases the pressurized extinguishing agent in the
extinguisher.

Sweep from side to side until the fire is completely out.


Start using the extinguisher from a safe distance away moving forward sweeping the nozzle
from side to side. Once the fire is out, keep an eye on the area in case it re-ignites.

Mounting Extinguishers

Most extinguishers are mounted on walls or columns by securely fastened hangers so that they are
supported adequately, although some extinguishers are mounted in cabinets or wall recesses. In any case,
the operating instructions must face outward, and the extinguisher should be placed so that it can be
removed easily. Cabinets should be kept clean and dry.

Inspection

A visual inspection is a quick check to see if the fire extinguisher is in its proper location, it is not
blocked, it is fully charged, and it appears to be in good working order. This inspection generally consists
of walking to the extinguisher and confirming the following:

• The extinguisher is in its proper place.

• No obstructions and clear access and visibility.

• The extinguisher’s operating instructions face outward.

• Seals or tamper indications are intact.

• Pressure gauge is in the normal range.

• Noting any obvious physical damage.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 31


Maintenance

Maintenance should include a thorough examination of the extinguisher’s mechanical parts, the
extinguishing agent and the expelling means.

The purpose of the maintenance program is to make sure that the extinguisher will operate properly,
and will not pose a potential hazard to the operator or people nearby. Certified personnel will perform
maintenance once every year as per NFPA 10.

Tampering/Vandalism

Tampering or vandalizing a fire extinguisher consists of the following:

• Discharging the extinguisher for any other reason than to extinguish a fire.

• Relocating an extinguisher without approval.

• Damaging any part of the extinguisher intentionally or accidentally through carelessness.

Reporting Damaged or Discharged Extinguisher

Never put an extinguisher back in its place after use. If an extinguisher is discharged, even for a few
seconds or if it is damaged in any way, report the fire extinguisher and its location to
Environmental Health and Safety by calling 7-3129.

INSPECTION AND TESTING OF


FIRE PROTECTION AND LIFE-SAFETY EQUIPMENT

AU is working to provide a level of life safety and property protection that will meet the needs
of the people occupying its buildings while meeting the safety requirements of local building
codes and the authority having jurisdiction. Fire detection devices and alarm systems are the key
elements among the fire protective features of any facility. Detection and alarm systems help limit
property losses in buildings regardless of the type of occupancy, and significantly reduce the loss of
life from fire since many of the fire deaths in the United States result from building fires.

Fire Protection Equipment and Systems

Fire Protection Equipment and systems are specially designed, either alone or as a system, to limit
the spread of fire and smoke by assisting in extinguishments, either by automatic, semi-automatic
or manual means. This includes, but is not limited to:

• Portable fire extinguishers


• Fire hoses
• Fire pumps
• Wet and dry standpipe systems
• Automatic sprinkler systems
• Halon systems and other special extinguishing systems
• Fire doors, dampers and other fire protection systems and appurtenances
• Fire alarm systems

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 32


Fire protection and life-safety equipment and systems shall be inspected, tested and maintained in
all occupancies and locations where required or installed as set forth in NFPA Codes, Federal,
State, local standards, and as may be required by the State Fire Marshal.

The provisions of this Standard apply to the inspection, maintenance, and testing of both fire
protection and life-safety systems and equipment. The requirements presented in this Standard
are to be considered as a MINIMUM.

Servicing, Testing, and Maintenance

Qualified, certified and/or licensed personnel shall conduct all servicing, testing, repair,
maintenance and tagging of fire protection and life-safety equipment. Personnel not licensed,
certified, or approved by the City Fire Department or State of Florida may be required to provide
documentation of licensing or certification by similar approved agencies or authorities, or
identification as manufacturer’s representative or authorized service personnel.

Service Tags

After installation or service, an approval service tag shall be completed in detail indicating all work
that has been done and then attached to the equipment or system in such a position as to permit
convenient inspection and not hamper its actuation or operation. A new service tag must be
attached each time service is performed. If impairments to the system constitute emergency
impairments as defined in applicable NFPA Standards, then a completed tag shall be attached
indicating the nature of the impairment or what corrective action is necessary. The office of the
State Fire Marshal and/or the City Fire Department shall be notified as soon as possible whenever
fire protection or life-safety equipment is TAGGED.

New Installation

All new installations of fire protection equipment and fire alarm systems shall have installation
acceptance tags affixed to them.

Upgrade of Equipment

All fire protection and life-safety equipment shall be maintained in accordance with requirements of
the manufacturer and local, State, Federal or nationally recognized standards in effect at the time of
original installation and acceptance, unless otherwise required by the State Fire Marshall or other
regulatory agencies.

Inspection and Maintenance Records

All logs or records of inspection, testing, maintenance and major repairs of fire protection and life-
safety equipment and systems shall be maintained on file for not less than 3 years, and made
available to the State Fire Marshal or fire inspector upon request.

Notification of Systems Out of Service

The Fire Department should be notified immediately when a required fire protection or life-safety
system is placed out of service for emergency or non-scheduled repairs, replacement, or service.
The Fire Department shall again be notified when the system is restored to normal operational
status.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 33


The office of the State Fire Marshal shall be notified, in writing, not less than 7 days prior to any
lengthy routine or scheduled repairs, or replacement time period. Notification shall be prior to,
where possible, placing the system out of service. Certification and documentation of repairs and
operational readiness of the system shall be provided to the State Fire Marshal or fire inspector
upon request.

No fire protection or life-safety system shall be placed permanently out of service unless prior
written approval is obtained from the State Fire Marshal.

LIFE-SAFETY SYSTEMS

Fire Alarm Systems

Fire alarm systems shall be tested, and service tagged at the main alarm panel, not less than
annually. Testing shall include all smoke detectors, manual pull devices, annunicators, visual
indicators and strobes, control units, voice/alarm communications systems and other devices that
may be part of the fire alarm system.

Test of Systems

An approved fire alarm service company shall test the fire alarm system. All testing and
maintenance shall be in accordance with NFPA Standard No. 72 and this Standard. Test operation
of all auxiliary functions of alarm system including, but not limited to: electronic locking devices,
automatic fire and smoke door and damper function, elevator recall, stair pressurization operation
and HVAC shutdown.

Emergency Lighting Systems

Provide for the quarterly testing of emergency lighting systems that are part of an approved exit
system and shall include, but is not limited to: lighted exit signs, stairway lighting, and egress
lighting, where required both inside and outside of a building or structure.

Generator Systems

A “run check” of the generator unit shall be performed at least monthly, for a period of at least 30
minutes, under load conditions. System shall be checked for proper fuel, oil and coolant levels
prior to starting test. Authorized building or contract personnel may perform ‘Run Tests’ and
maintenance. All testing should be done in accordance with manufacturer’s guidelines and NFPA
Standard No. 110. A written record of monthly test shall be maintained by the generator room.

Battery Systems

Battery units shall be inspected quarterly. Authorized building or contract personnel may perform
inspections using procedures in accordance with manufacturer’s guidelines and NFPA Standard No.
110. A written record of inspections shall be maintained.

Emergency Power Supply Systems (EPSS)

These systems provide emergency power for continuous operation of, but are not limited to: exit
lighting systems, fire alarm system, fire pump, stair pressurization and smoke removal systems,

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 34


elevators, and associated electrical transfer switch gear. The unit shall be inspected quarterly.

Engine Driven Generator Systems

An authorized generator company shall conduct an annual ‘Load Test’. Load test shall be
performed under temperature conditions and at a capacity not less than 50 percent of the total
connected emergency power supply load manufacturer’s nameplate rating for the unit, for a
continuous period of not less than 90 minutes. Load test shall include building load with all
required equipment on the emergency circuit(s) operational for the duration of the test. Elevator
recall and firefighter control operations shall be checked, but need not be continuous for the test
period.

Test Of Automatic Fans And Dampers

Operational test of all automatic fans and dampers connected to building fire alarm systems shall be
tested annually in conjunction with fire alarm systems tests. Results shall be included with the fire
alarm system inspection test reports.

WATER BASED FIRE PROTECTION

Automatic Wet-Pipe Sprinkler Systems

Routine Inspection

Approved contract personnel or building personnel, fully trained to perform such inspections or
checks, may perform routine visual inspections and equipment checks in accordance with NFPA
Standard No. 25. A written record of weekly and monthly inspections of system components shall
be maintained.

Test of Systems

All automatic dry-pipe sprinkler systems shall be tested annually in accordance with NFPA
Standard No. 25 and State requirements, and service tagged by an approved fire protection sprinkler
company.

Wet Standpipe System

Standpipe systems should contain water in the piping at all times. A flow test shall be conducted for
each zone of the standpipe system every 5 years. An approved service company shall conduct flow
tests with required volume of water at the system’s design pressure and provide required service
tagging of the system at the main control valves and risers. Testing shall be conducted in
accordance with NFPA Standard No. 25.

Dry Standpipe System

Standpipe systems do not normally contain water in the piping and have to be supplied with water
from an outside source. An approved service company performing such testing shall conduct
hydrostatic test on the standpipe system every 5 years.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 35


Regardless of the type of system, all automatic fire sprinklers must remain clean at all times. They
must not be caked with dust, grease, or paint, particularly on the heat-responsive element. They
must be provided with guards if located in the areas prone to damage. Light fixtures, HVAC
equipment, cables, stored materials, or movement of overhead doors and windows should not
obstruct sprinklers. NFPA 25 requires this type of evaluation to be performed once a year.

Sprinklers must be free from corrosion. A sufficient supply of spare sprinkler heads of each type
and ratings used by the system and the special wrench needed to replace them, must be available on
the premises.

Piping must be checked once a year when the sprinklers are being inspected to make sure it is in
good condition, free from mechanical damage, and not being used to support fixtures, ladders, or
any other loads. NFPA 25 requires that the pressure gauge of a wet pipe system be read monthly
and the reading must be recorded.

Fire Department Connections

Inspection

Fire Department Connections (FDC) shall be inspected quarterly. Inspections should check for:
missing protective caps or covers, damaged hose couplings, couplings not operating freely, the
presence of foreign material that might interfere with operation of system, water in the piping that
could indicate possible check valve leaks, and missing standpipe or sprinkler connection
identification signs.

Test of System

An approved service company shall conduct flow and pressure tests of all fire department
connections, piping and check valve assemblies, not less than every 5 years. Testing should be
conducted as a part of the standpipe system 5-year test when possible, and in accordance with
NFPA Standard No. 25.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 36


Summary of Minimum Inspection, Testing and Maintenance for Sprinkler Systems,
NFPA 25

Item Activity Frequency


Gauges (dry, pre-action deluge Inspection Weekly/Monthly
systems)

Control Valves Inspection Weekly/Monthly

Alarm Devices Inspection Monthly

Gauges (wet pipe systems) Inspection Monthly

Hydraulic Nameplate Inspection Quarterly

Buildings Inspection Annually (prior to freezing weather)

Hanger/Science Bracing Inspection Annually

Piping Inspection Annually

Sprinklers Inspection Annually

Fire Department Connections Inspection Quarterly

Valves (all types) Inspection Weekly/Monthly

Alarm Devices Test Quarterly

Main Drain Test Quarterly

Antifreeze Solution Test Annually

Gauges Test 5 years

Sprinklers-High Temp. Test 5 years

Sprinklers-Fast Response Test 20 years and every 10 years thereafter

Sprinkler Test 50 years and every 10 years thereafter

Valves (all types) Maintenance Annually or as needed


Obstruction Investigation Maintenance 5 years or as needed

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 37


Fire Pumps

Diesel Driven Pumps

Operating test of diesel engine driven fire pumps shall be conducted weekly without water flowing.
This test shall be conducted by allowing automatic starting of the pump to occur and running the
pump for a minimum of 30 minutes. Run test may be performed by authorized building or contract
personnel and shall be in accordance with the manufacturer’s guidelines and NFPA Standard No.
25. A written record of all weekly tests shall be maintained.

Electrically Driven Pumps

Operating test of electrical motor driven fire pumps shall be conducted weekly without water
flowing. This test shall be conducted by allowing automatic starting of the pump to occur, and
running the pump for a minimum of 10 minutes. May be performed by authorized building or
contract personnel and shall be in accordance with the manufacturer’s guidelines and NFPA
Standard No. 25. A written record of all weekly tests shall be maintained by the pump room.

Pump Tests

A flow test at pressure shall be conducted on fire pump(s) annually. Flow tests shall be performed
by an approved service company, and shall be conducted and service tagged in accordance with
manufacturer’s guidelines and NFPA Standard No. 25.

Private Fire Service Mains

Private dry barrel and wet barrel fire hydrants, and wall hydrants, installed for fire department use
shall be inspected and flow tested by an approved service company annually. Testing shall be
conducted in accordance with NFPA Standard No. 25, and a written report of the test findings shall
be provided to EH&S.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 38


Summary of Fire Pump Inspection, Testing, and Maintenance

Item Activity Frequency Reference to NFPA 25


(1995 edition)
Pump house,
Heating Inspection Weekly Table 5-2.2
Ventilating louvers Inspection Weekly Table 5-2.2
Fire pump system Inspection Weekly Table 5-2.2
Pump operation,
No-flow condition Test Weekly 5-3.2.1, 5-3.2.2
Flow condition Test Annually 5-3.3.1
Hydraulic Maintenance Annually 5-5.1
Mechanical transmission Maintenance Annually 5-5.1
Electrical system Maintenance Varies 5-5.1
Controller, various components Maintenance Varies 5-5.1
Motor Maintenance Annually 5-5.1
Diesel engine system, various Maintenance Varies 5-5.1
components

FIRE DOORS AND DAMPERS

Fire Door Inspection

Fire doors, shutters and windows shall be inspected at least quarterly. Inspections should include
the following:

1. Guides and bearing should be well lubricated.

2. Doors normally held open by automatic closing devices should be operated to assure they
are working properly. Closing devices and coordinators should be adjusted to assure that
the doors close and latch properly.

3. Chains and cables should be regularly inspected for excessive wear and stretching. Ropes
or other non-approved chain or cable replacements shall not be installed or used on fire
doors.

4. Check fusible links for paint or other non-approved coating materials. Replace any painted
or coated links.

5. Check door rollers for paint, dirt or grime buildup. Remove paint or buildup as necessary to
assure that rollers will not bind.

6. Check doors for holes or other damage that would violate their fire rating.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 39


Inspections may be performed by authorized building or contract personnel and shall be in
accordance with the manufacturer’s guidelines and NFPA Standard No. 80. A written record of all
inspections shall be maintained.

Fire Door Testing

All sliding and rolling fire doors, shutters and windows shall be allowed to close completely at least
annually to check operations of the guides and rollers, and to make sure the doors have adequate
clearance to close completely. Chains and cables should be adjusted as needed. An approved
service company shall perform any required repairs of fire doors or assemblies. A written record of
all inspections and repairs shall be maintained.

Fire Damper Inspections

All accessible fire damper assemblies in mechanical, electrical or air handler rooms and spaces, in
firewalls or rated occupancy separation walls, or in floors, shall be visually inspected at least
quarterly to verify that their operations are not obstructed or impaired. Authorized building or
contract personnel may perform visual inspections. A written record of inspections shall be
maintained.

SPECIAL FIRE SUPPRESSION

Commercial Kitchen Hood Systems

All vent hood fire suppression systems installed in commercial kitchens shall be inspected and
service tagged not less than every 6 months, and after any activation of the system by an approved
fire protection equipment company. Inspections shall be in accordance with manufacturer’s
guidelines.

Additionally, all commercial kitchen vent hoods, exhaust ducts, exhaust fans and appurtenances
shall be cleaned and inspected by approved personnel in accordance with manufacturer’s guidelines
as often as necessary to insure against excess grease accumulations.

“Type K” Extinguishing Systems and Portable Fire Extinguishers

“Type K” extinguishing systems and portable fire extinguishers, installed for use in the protection
of cooking areas within commercial kitchens, shall be inspected, tested, service tagged and
maintained in accordance with manufacturer’s guidelines and new NFPA 10.

Fixed Dry Chemical Extinguishing Systems

Fixed dry chemical extinguishing systems where installed for protection of, but not limited to, the
following: dip tanks or process hazards as spray booths, chemical hood systems or laboratory hood
systems; shall have an actuating test of the system performed (discharge of the agent is not
required) and service tags affixed every 6 months by an approved fire protection equipment
company.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 40


Fixed Wet Chemical Extinguishing Systems

Fixed wet chemical extinguishing systems where installed for protection of, but not limited to, the
following: dip tanks or process hazards as spray booths, chemical hood systems or laboratory hood
systems; shall have an actuating test of the system performed (discharge of the agent is not
required) and service tags affixed every 6 months by an approved fire protection equipment
company. Inspections shall be in accordance with manufacturer’s guidelines.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 41


INSPECTION, TESTING AND MAINTENANCE
FORMS FOR FIRE DETECTION AND SUPPRESSION SYSTEMS

Inspections, Testing and Maintenance-Fire Alarm System

INSPECTION
Weekly
□ Check electrolyte level and connection for lead acid batteries.

Monthly

Fire Alarm Systems-General:


□ Check all fire alarm equipment to make sure it is not damaged or inoperative.
□ Check power supply for normal indication.
□ Illuminate lamps and light emitting diodes (LEDs) on fire alarm and annunciator
panels.
□ Conduct operational test of engine generator, if connected to generator.
□ Check water level of rechargeable batteries if wet cell batteries are used.

Voice Alarm Systems:


□ Check speakers for damage.
□ Check pre-amplifier and its controls for normal indication.
□ Check amplifier and its controls for normal indication.
□ Check voice tape (if the system requires one) for normal indication.

Manual Stations:
□ Check all manual stations for damage or obstruction.

Detectors:
□ Check all detectors for damage or obstruction. Obstruction means that the detector is
located in a dead air pocket; is too close to an air handling unit discharge outlet, covers
too large a space, or is blocked by storage.

Semi-Annually

Fire Alarm Systems-General


□ Remove fuses, check ratings, and reinstall.
□ Check voltage of each rechargeable battery cell.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 42


Inspections, Testing and Maintenance-Fire Alarm System

TESTING

Monthly
□ Test the primary power supply for initiating and notification appliance circuits. The
primary power supply is usually a 120-V AC circuit controlled either by a fused safety
switch or by a circuit breaker. Disconnect the primary power and make sure the fire
alarm system switches normally to the secondary source of power.

□ Test the two-way communications system either by removing the telephone receiver
from its cradle or by inserting a plug-in, two-way communications device in its jack.
This should sound a signal in the central control center and allow two-way
communications. Record the specific device tested on the two-way communications
circuit so that different devices are used in subsequent tests.

Quarterly
□ Test the supervisory device circuit by disconnecting a conductor from its terminal in
the control panel. Once a trouble signal is received, reconnect the wire to its terminal and
reset the control panel. Repeat the test for all supervised circuits.

TESTING OF FIRE ALARM CONTROL PANELS

Monthly
□ Activate one device on each initiating device circuit.
□ Activate notification appliance circuits and confirm proper operation of all audible and
visual alarms.
□ Test Sprinkler water flow circuits by activating a flow switch on each circuit.

Semi-Annually

Fire Alarm Systems-General:


□ Test each manual station.
□ Activate extinguishing system alarm switches.
□ Activate supervisory signal initiating devices (e.g., gate valve switches, high air
pressure switches, low air pressure switches, temperature sensors, water level).
□ Test 10% of rate-of-rise heat detectors. (Test a different 10% every 6 months so that all
detectors are tested in 5 years.)
□ Test 10% of rate compensation heat detectors. (Test a different 10% every 6 months so
that all detectors are tested in 5 years.)
□ Test each smoke detector.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 43


Inspections, Testing and Maintenance-Fire Alarm System

Annually

Fire Alarm Systems-General:


□ Test supervisory device circuits.
□ Verify primary power supply. (Disconnect all secondary (standby) power and test
under maximum load, including all alarm appliances operating for 5 minutes. Be sure
to reconnect all power supplies at end of tests.)
□ Disconnect primary power supply to test secondary power supply. (Disconnect primary
power. Verify that the control panel operates properly from secondary power. Verify
that trouble indicator comes on upon primary power loss. Measure standby current
using manufacturer’s data. Test system under maximum load, including all alarm
appliances operating for 5 minutes. Be sure to reconnect all power supplies at end of
tests.)
□ Activate alarm notification appliances.
□ Test voice alarm system functions.
□ Test operation of speakers.
□ Verify that annunicators accurately report all alarm and trouble signals.
□ Test all control unit functions.
□ Test each alarm initiating and signaling circuit for trouble signals.
□ Calibrate and test of smoke detectors. All smoke detectors, regardless of type, are
tested in the same manner. This operating test consists either of spraying a smoke
detector test aerosol into the detector chamber. Each detector has a self-contained light,
which illuminates, flashes or loses illumination when the detector operates.
□ Test operation of two-way communications.
□ Confirm operation of all audible and visible alarm notification appliances.
□ Remove fuses and verify ratings and supervision
MAINTENANCE

Maintenance is the work necessary to keep fire alarm equipment operable and to make
repairs. Repair of fire detection and alarm equipment must be made immediately to
assure that the system will operate properly when needed.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 44


Fire Detection and Alarm Systems
Monthly Tests and Maintenance

YES = SATISFACTORY SYSTEM____________


NO = UNSATISFACTORY (EXPLAIN ON REVERSE) DATE____________
N/A = NOT APPLICABLE
INSPECTOR__________________________

YES NO N/A

The recorded message was tested and is operational.

All engine-driven generators for fire alarm systems are tested weekly and a
log of the tests is kept.

Radio fire alarm signal receiving equipment was tested hourly and a log of
the tests is kept.

All radio, fire alarm boxes transmit a test alarm daily and a log of the tests
is kept.

Telegraphic fire alarm signal receiving equipment was tested daily and a
log of the tests is kept.

All telegraphic fire alarm boxes are tested bi-monthly and are operational.

One initiating device on each circuit was tested and all circuits are
operational:

Each indicating appliance circuit was tested and all circuits are operational:

Each speaker circuit was tested and all circuits are operational:

One device on each two-way communication circuit was tested and each
circuit is operational.

Test each supervisory device circuit by removing a wire from its terminal.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 45


Fire Detection and Alarm Systems
Monthly Inspection

YES = SATISFACTORY SYSTEM____________


NO = UNSATISFACTORY (EXPLAIN ON REVERSE) DATE____________
N/A = NOT APPLICABLE
INSPECTOR_____________________

YES NO N/A
Fire alarm panel appears operational.

Lights and LEDs on fire alarm and annunciator panels are operational.

Battery electrolyte level is satisfactory.

All heat detectors appear operational.

All smoke detectors appear operational.

All flame detectors appear operational.

All manual stations appear operational.

All bells or horns appear operational.

All speakers appear operational.

Pre-amplifier appears operational.

Amplifier appears operational.

Voice tape appears operational.

Power supplies appear operational.


All radio fire alarm transmitting equipment appears operational.
All radio fire alarms receiving equipment appears operational.

All telegraphic fire alarms transmitting equipment appears operational.

All telegraphic fire alarms receiving equipment appears operational.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 46


Fire Detection And Alarm Systems
Annual Test and Maintenace

YES = SATISFACTORY SYSTEM____________


NO = UNSATISFACTORY (EXPLAIN ON REVERSE) YEAR ____________
N/A = NOT APPLICABLE

YES NO N/A
DATE INSPECTOR
Alarm indicating appliances (visual and audible) were tested and are
operational.
The primary power supply was tested and is operational.
The secondary power supply was tested and is operational.
The lamp and LED circuits were tested and are satisfactory.
Smoke detectors were recalibrated and operate satisfactory.
Batteries were discharged for two hours and remain operational.
Battery charging devices were tested for proper operation.
Battery voltage was measured under full load with charger disconnected.
Batteries had the float voltage measured in each cell and are satisfactory.
Bell or horns were tested and are operational.
Annunciators were tested and are operational.
Control units were tested and all functions are operational.
Voice alarm system components were tested and are operational.
Each initiating and signaling circuit was tested for trouble signals.

Two fixed temperature heat detectors for every 100 present were removed
and satisfactory tested by a testing laboratory. The two fixed temperature
detectors were replaced with new fixed temperature heat detectors.
DATE THE SYSTEM WAS INSTALLED:
DATE THE FIXED TEMPERATURE HEAT DETECTORS WERE TESTED:
NOTE: If the tested fixed temperature heat detectors fail, all fixed temperature heat detectors in
the building must be replaced.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 47


AUTOMATIC SPRINKLER SYSTEMS FORM F-1

Weekly Inspection
SYSTEM_______________________
This form covers a 6-month period
1. Date of inspection. 5-8. Record pressure readings (psi). A loss of more than 10%
2. Inspector’s name, initials or badge number. should be investigated.
3. If valves are sealed, note “yes” in this block. If any are 9. Record any notes about the system which the inspector
not sealed, reseal and note “resealed” in this block. believes to be significant. Use separate sheet if needed.
4. If all sprinklers are in good condition and storage is
maintained at least 18 in. below the sprinklers, note
“yes” in this block. If not, see that corrections are
made and briefly describe under “notes.”
1 2 3 4 5 6 7 8 9
DATE INSPECTOR VALVE(S) SPRINKLERS ALARM DRY PIPE PREACTION DELUGE VALVE NOTES
SEALED OK VALVE VALVE VALVE WATER
OK Air Water Air Water PRESSURE
Pres. Pres. Pres. Pres.

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 48


AUTOMATIC SPRINKLER SYSTEMS FORM F-2

Monthly Inspection
SYSTEM_______________________

1. Date of inspection. 6. Assure there is proper number and type of sprinklers


2. Inspector’s name, initials or badge number. and a sprinkler wrench.
3. If fire department connections are unobstructed and in 7. Check for physical damage and that electrical
good condition, note “OK” in block. If not, see that connections are secure.
corrections are made and briefly describe under 8. Record pressure readings (psi). A loss of more than 10%
“notes.” should be investigated.
4. If valves are locked, note “yes” in this block. If any are 9. Record any notes about the system which the inspector
not locked, relock and note “relocked” in this block. believes to be significant. Place a number in this block
5. Inspect alarm valves to assure no leakage from retard and number the corresponding note at the end of the
chamber or alarm drains. inspection form.
1 2 3 4 5 6 7 8 9
DATE INSPECTOR FIRE DEPARTMENT VALVES ALARM SPARE ALARM WATER NOTES
CONNECTIONS LOCKED VALVES SPRINKLERS DEVICES PRESSURE

NOTES _______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 49


AUTOMATIC SPRINKLER SYSTEMS FORM F-3

Quarterly Inspection and Tests


SYSTEM_______________________

DATE

INSPECTOR
MAIN DRAIN TEST
Conduct a main drain test as follows:

1. Record the static water supply pressure (psi) as indicated on the lower pressure
gauge.

2. Open the main drain and allow water flow to stabilize.

3. Record the residual water supply pressure while water is flowing from the 2-inch
main drain as indicated on the lower pressure gauge.

4. Close the main drain (slowly).


WET PIPE SYSTEM FLOW ALARM
Test water flow alarms by opening the inspectors test valve.
DRY PIPE PRIMING LEVEL
Check dry valve priming water level by opening the test valve and checking for a small
amount of water to discharge. If no water flows out of the test line, add priming water.
DRY PIPE SYSTEM LOW AIR PRESSURE ALARM
Close the water supply valve, carefully open inspector test valve to reduce air pressure
slowly (Do not reduce air pressure sufficiently to trip the dry pipe valve). Confirm operation
of low pressure alarm, record air pressure at which low pressure alarm activated, close
inspector test, allow air pressure to rise to normal, then open water supple valve.
DRY PIPE SYSTEM FLOW ALARM
Open the alarm by-pass valve.
PREACTION SYSTEM FLOW ALARM
Open the alarm by-pass valve.
DELUGE SYSTEM FLOW ALARM
Open the alarm by-pass valve.
CONTROL VALVES
Close valves and reopen until spring or tension is felt - back valve ¼ turn.
HYDRAULIC NAME PLATE
If system was hydraulically calculated, assure nameplate is legible and securely attached
to riser.

COMMENTS ____________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 50


AUTOMATIC SPRINKLER SYSTEMS FORM F-4

Semi-Annual Inspection and Tests


SYSTEM_______________________

DATE

INSPECTOR
DRY PIPE SYSTEMS
Quick opening devices and accelerators, if provided, should be tested semi-annually.
Low point drains should be drained thoroughly before cold weather and after any
system trip.
DELUGE SYSTEM
Test fire detection system for proper operations.
PREACTION SYSTEM
Test fire detection system for proper operation.
Record any notes about the system which the inspector believes to be significant.
Place a number in this block and number the corresponding note at the end of the
inspection form.
COMMENTS __________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 51


AUTOMATIC SPRINKLER SYSTEMS FORM F-5

Annual Inspection, Tests and Maintenance


SYSTEM____________________
INSPECTOR _________________________ DATE____________________
GENERAL CONDITION
Inspect sprinklers, sprinkler piping, pipe hangers and seismic braces to make sure they are in
good condition.
FREEZING
Before freezing weather, inspect building to assure exterior wall openings will not expose sprinkler
piping to freezing temperature.
MAINTAIN VALVES
Valves should be maintained, including exercising each valve and lubricating each valve stem.
CLEAN STRAINERS
Shut the water supply valve and remove the strainer for thorough cleaning.
TEST ANTIFREEZE
Wet pipe systems with antifreeze solution should have the solution checked for proper freeze
level. Record freezing point.
DRY PIPE SYSTEM
Trip test the dry pipe valve. Record the time from opening the inspectors test valve until the dry
pipe valve trips.
Internally inspect dry pipe valve.

Test air pressure maintenance device.


PREACTION SPRINKLER SYSTEM
Trip test the preaction system. (Refer to manufacturer’s instructions.)
Internally inspect preaction valve.
DELUGE SPRINKLER SYSTEM
Trip test the deluge system. (Refer to manufacturer’s instructions.)
Record time from activation of detector until water in discharged.

Check to see that water discharge pattern is adequate.

Record water pressure at hydraulically most remote sprinkler.

Record water pressure at deluge valve.

Internally inspect deluge valve.


COOKING EQUIPMENT SPRINKLERS
Replace sprinklers with fusible links.

COMMENTS
____________________________________________________________________________________________________________

____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 52


AUTOMATIC SPRINKLER SYSTEMS FORM F-6

5-Year Inspection
SYSTEM_______________________
INSPECTOR _________________________ DATE ______________________
ALARM VALVE INTERNAL INSPECTION
Verify that all components operate properly, move freely, and are in good condition.
CHECK VALVE INTERNAL INSPECTION
Verify that all components operate properly, move freely, and are in good condition.

COMMENTS ____________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 53


STANDPIPE AND HOSE SYSTEMS FORM F-7

Standpipe Hydrostatic and Flow Test


DATE______________________
INSPECTOR______________________

STANDPIPE SYSTEM ____________________________________________________________________________


INITIAL TEST PRESSURE. Record the hydrostatic test pressure at the start of the test. Test
pressure should be 200 psi or 50 psi above normal pressure if normal pressure exceeds 150 psi.
START TIME. Record the time at the start of the test after the test pressure is reached.
END TIME. Record the time at the conclusion of the hydrostatic test. The system should hold the
pressure for at least 2 hours.
END TEST PRESSURE. Record the hydrostatic test pressure at the conclusion of the test.
FLOW TEST. Flow water from the hydraulically most remote standpipe outlet.
Record:
Static Pressure __________ psi Residual pressure __________ psi
Nozzle diameter __________ in. Pivot pressure __________ psi
Flow __________ gpm.

Note: The minimum flow should be 500 gpm at 65 psi residual pressure.

NOTES ________________________________________________________________________________________________________________
_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 54


STANDPIPE AND HOSE SYSTEMS FORM F-8

Annual Inspection and Maintenance


SYSTEM______________________
INSPECTOR _________________________ DATE______________________
VISUALLY INSPECT DRY PIPING. Visually inspect all accessible piping for damage and
corrosion. If piping is in good condition, note “OK” in block. If not, see that corrections are
madeand briefly describe actions taken.
CHECK NOZZLES. Open and close all nozzles to assure they operate easily. Lubricate with
graphite if needed. If nozzles are in good condition, note “OK” in block. If not, see that corrections
are made and briefly describe actions taken.
LUBRICATE SWING-OUT RACKS. Lubricate swing-out racks with graphite to assure they
operate properly. Record “OK” in block if no problems are found.
RERACK HOSE. Remove and rerack hose so that different parts of hose are located at bends.
Check gaskets for deterioration and replace if necessary.

NOTES ________________________________________________________________________________________________________________
_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

_________________________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 55


HYDRANTS – INSPECTIONS FORM F-9

Semi-Annual Inspection for Dry Barrel Hydrants


Annual Inspection for Wet Barrel Hydrants
DATE_______________________
INSPECTOR_______________________
YES = SATISFACTORY NO = UNSATISFACTORY (EXPLAIN BELOW)
YES NO

Hydrants are accessible.

Hydrant outlets are slightly more than hand-tight.

There are no leaks in the top of the hydrant.

There are no leaks in the gasket under the caps

There are no cracks in the hydrant barrel.

Hydrant drains properly (in dry barrel hydrants).

Operating nut is not worn and does not have rounded corners.

Nozzle threads are not damaged.

Check hose houses to assure all equipment is in good condition.

COMMENTS __________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

_____________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 56


FIRE PUMPS FORM F-10

Monthly Inspection YES = SATISFACTORY


NO = UNSATISFACTORY (EXPLAIN ON REVERSE)
YEAR ____________________

DATE
INSPECTOR
REMOVE BATTERY CORROSION AND CLEAN BATTERY
CASE
CHECK BATTERY CHARGER AND CHARGER DATE
INSPECT CIRCUIT BREAKERS OR FUSES FOR PROPER
OPERATION
EQUALIZE CHARGE IN BATTERY SYSTEM

COMMENTS_____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 57


FIRE PUMPS FORM F-11

Monthly Tests YES = SATISFACTORY


NO = UNSATISFACTORY (EXPLAIN ON REVERSE)
YEAR ____________________

DATE
INSPECTOR

EXERCISE ISOLATING SWITCH AND CIRCUIT BREAKER

OPERATE MANUAL STARTING MEANS (SEMI-ANNUALLY)

TEST ANTIFREEZE TO DETERMINE PROTECTION LEVEL


TEST BATTERIES FOR SPECIFIC GRAVITY OR STATE OF
CHARGE
OPERATE SAFETY DEVICES AND ALARMS (SEMI-ANNUALLY)
TEST CIRCUIT BREAKERS AND FUSES FOR PROPER
OPERATION

COMMENTS_____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________

FLORIDA ATLANTIC UNIVERSITY, FIRE SAFETY MANUAL 58