PROJECT : 1W09 2x10MIG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

DUCAB Cables 6/10 (12) kV Three Core Copper Conductors XLPE Insulated to IEC 60502-2 Steel Tape Armoured Sr. No 1 2 3 4 5 6 Voltage (V) 11000 11000 11000 11000 11000 11000 Current in Amps 269.00 269.00 22.31 22.31 22.31 22.31 Length (mtr) 300 300 20 20 20 20 voltage Drop (V) 3.95 3.95 0.04 0.04 0.04 0.04

From

To

Load (KW)

Power Cable Size 2R- 3C x 240 sqmm XLPE/SWA/PVC 2R- 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC 3C x 240 sqmm XLPE/SWA/PVC

Cable Type

V/A/km

Incoming Supply-1 Incoming Supply-2 MV panel MV panel MV panel MV panel

MV Panel MV Panel VFD Panel-1 VFD Panel-2 VFD Panel-3 VFD Panel-4

4100 4100 340 340 340 340

XLPE/SWA/PVC XLPE/SWA/PVC XLPE/SWA/PVC XLPE/SWA/PVC XLPE/SWA/PVC XLPE/SWA/PVC

0.098 0.098 0.098 0.098 0.098 0.098

PROJECT :1W09 2x10MIG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

11kV Incoming cable sizing calculation


Source : 132/11 kV Substation Destination : 11 kV switchgear panel Source : 300 Meters TOTAL LOAD DETAILS OF 11kV SWITCGEAR CIRCUIT PROTECTION Total Connected Load (Bus A + Bus B) Maximum Demand (Bus A + Bus B) Maximum Demand Current (Bus A + Bus B) Rating of incomer Breaker Recommended (at 132/11kV switchgear) CABLE SELECTION 1 2 3 4 5 6 7 8 a) b) c) d) Number of Cable Runs Cable Size Selected :- 3 Core XLPE/SWA/PVC Cu Cable Short Circuit Rating of Conductor For 3 Sec (1 run) Short Circuit Rating of Conductor For 3 Sec (2 runs) Current Carrying Capacity in Ground Current Carrying Capacity of 2 Runs of Cable in Ground Cable Installation Type Derating Factors Ground Temperature at 35oC Thermal Resistivity of Soil at 2.5oCm/W Depth at 0.8 Meter Group factor (0.45 m spacing) Total Derating 9 10 11 Derated Current Rating for 2 Runs of Maximum connected load current Maximum Demand current 3x240 Sq. mm R = = = = = = = = = = = = = = = = = 2 3C*240 20 40 436 872 Ground = = = = 4100 KW 4100 KW 269.00 A 1250 A

I I

Sq.mm kA kA A A

K1 K2 K3 K4 K IZ IL IMD

0.96 0.74 1 0.72 (K1 x K2 x K3 x K4) 0.5 (I x K x R) 446.02 A 269.00 A 269.00 A

Result :

The Above selected 2 runs of 3Cx 240 sq. mm cable is suitable to carry the given maximum load current Encl : 1. Short Circuit Current Curves for 11kV MV cable 2. Datasheet of the cable attached for reference

Cable catalogue

PROJECT :1W09 2x10MIG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

MV Panel to VFD Panel - Cable Sizing


Source : MV Panel Destination : VFD Panel Source : 20 Meters TOTAL LOAD DETAILS OF 11kV SWITCGEARCIRCUIT PROTECTION Total Connected Load Maximum Demand Maximum Demand Current Rating of Breaker Recommended = = = = 340 KW 340 KW 22.31 A 1250 A

CABLE SELECTION 1 2 3 4 5 6 a) b) c) d) Number of Cable Runs Cable Size Selected :- 3 Core XLPE/SWA/PVC Cu Cable Current Carrying Capacity in Ground One Second Short Circuit current Rating of Conductor Cable Installation Type Derating Factors Ground Temperature at 35oC Thermal Resistivity of Soil at 2.5oCm/W Depth at 0.8 Meter Group factor (0.45 m spacing) Total Derating 7 8 9 Derated Current Rating for 2 Runs of Maximum connected load current Maximum Demand current 3x50 Sq. mm K1 K2 K3 K4 K IZ IL IMD R I kA = = = = = = = = = = = = = = = 1 3C*240 Sq.mm 436 A 34.4 Ground 0.96 0.74 1 0.72 (K1 x K2 x K3 x K4) 0.5 (I x K x R) 223.01 A 22.31 A 22.31 A

Result :

The Above selected 1runs of 3Cx 240 sq. mm cable is suitable to carry the given maximum load current Encl : 1. Datasheet of the cable attached for reference 2. Maximum permitted release time is 100 msec.

PROJECT :1W09 2x10MIG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

MV Panel to VFD Panel - Cable Sizing


Source : VFD Panel Destination : Motors TOTAL LOAD DETAILS OF 11kV SWITCGEARCIRCUIT PROTECTION Total Connected Load Maximum Demand Maximum Demand Current Rating of Breaker Recommended = = = = 340 KW 340 KW 74.36 A 1250 A

CABLE SELECTION 1 2 3 4 5 6 a) b) c) d) Number of Cable Runs Cable Size Selected :- 3 Core XLPE/SWA/PVC Cu Cable Current Carrying Capacity in Ground One Second Short Circuit current Rating of Conductor Cable Installation Type Derating Factors Ground Temperature at 35oC Thermal Resistivity of Soil at 2.5oCm/W Depth at 0.8 Meter Group factor (0.45 m spacing) Total Derating 7 8 9 Derated Current Rating for 2 Runs of Maximum connected load current Maximum Demand current 3x50 Sq. mm K1 K2 K3 K4 K IZ IL IMD R I kA = = = = = = = = = = = = = = = 1 3C*240 Sq.mm 436 A 34.4 Ground 0.96 0.74 1 0.72 (K1 x K2 x K3 x K4) 0.5 (I x K x R) 223.01 A 74.36 A 74.36 A

Result :

The Above selected 1 runs of 3Cx 240 sq. mm cable is suitable to carry the given maximum load current Encl : 1. Datasheet of the cable attached for reference 2. Maximum permitted release time is 100 msec.

IG RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

hree Core Copper Conductors XLPE Insulated to IEC 60502-2 Steel Tape Armoured voltage Drop Vd % 0.036 0.036 0.001 0.001 0.001 0.001

RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

(K1 x K2 x K3 x K4)

RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

(K1 x K2 x K3 x K4)

RCC WATER TANKS & PUMPING STATION AT AL ZAWARA -AJMAN

(K1 x K2 x K3 x K4)