2009 2nd International Conference on Power Electronics and Intelligent Transportation System
Analysis on Fault Voltage and Secondary Arc Current
of Single Phase Refusing-Shut of the 500kV Extra High Voltage Transmission Line Yang Huping' , Wu Dongwerr', Gu Yin l , Bi Zhipeng l (1 School a/Information Engineer, Nan-chang University, NanChang, Jiangxi, China 330031) (2 JiangXi Electric Power co. Extra High Voltage Branch, NanChang, Jiangxi,China 330006) Abstract-It is common knowledge that 500kV extra high voltage and long distant transmission line join a shunt reactor and a neutral grounding via small reactor; This paper analysis systematically an possible condition of the frequency-regulating resonance over-voltage on single phase cut fault to refusing-shut of the 500kV exra high voltage transmission line which join a shunt reactor, the system compose an complex series resonance circuits, and present a rational mode of reactive compensation. This paper also build rational mathematic mode on systemic parameter of 500kV ci-yong transmission line, and resolute detailedly its power frequency component , low frequency component and its DC component of single phase cut fault voltage and secondary arc current by the mean of Laplacian transformation ruling formula. All the this is to offer an farther analysis on switching over-voltage and secondary arc current interrupter of long distant transmission line. In the end, this system also implemented using MATLAB software, compute the transient process on single phase cut fault voltage and secondary arc current. Key words - shunt reactor, frequency-regulating resonance over-voltage, reactive compensation; secondary arc current, series resonance circuits, single phase cut fault I. INTRODUCTION 500kV EHV transmission line usually has access shunt reactor, shunt reactors to compensate for line capacitance of the role, especially because of restrictions on open-circuit or light load voltage caused by increased load. When the operating line asymmetric operation, such as single-phase circuit breaker broken cause refusing to move, then breaking relative capacitance and capacitance of the reclosing phase and to-ground reactance of breaking phase may be composed of series resonant circuit, may lead to resonance over-voltage. To limit the resonance, common method is reactor small reactor to ground in neutral point, the effect is producing the equivalent interaction induction reactance extension wire interaction electric capacity, thereby undermining the conditions of their resonance. No-load line reclosing is a common operation. When single-phase circuit breaker refused to move because of various reasons, the open phase may cause resonance over- voltage. Although the operation of single-phase circuit breaker refuse to move is an abnormal state, when the ultra-high pressure systems with single-phase automatic reclosing device, single-phase to ground, there may be breaking the single-phase 978-1-4244-4543-1/09/$25.00 2009 IEEE 9 state, it is normal operation mode. Make single-phase opening, although the breaking phase lose power, but because of the other two-phase is still running, through the lines of non-fault phase and fault phase with the capacitive coupling between the electromagnetic coupling, in the fault phase is still a considerable number of current flow, at this time the current known as the arc current.. This paper detailed analysis the size of fault generated voltage and arc current which caused by magnetic South Reclosing 500kV line with shunt reactors lines switching happened single-phase line refusing to move. Proved the transient electrical fault in the process of the amount of frequency components, free weight and DC component of the derivation in detail, and proved the use of reactive power compensation coefficient is reasonable. To further study the single-phase circuit automatic reclosing success factors and electrical equipment insulation coordination provides a solid theoretical basis. II. THE STRUCTURE AND WORKI NG PRINCIPLE OF SINGLE- PHASE LINE FAULT SYSTEM Assume that the end ofline shunt reactor to ground directly without small reactor, then switch on no-load line of ingle- phase system after refusing to move, the three-phase equivalent circuit show in Figure 1. Due to the parallel slip potential CO and XO the reclosing phase (B-phase, C-phase) are being fixed, may cause resonance line components for the fault phase (A phase) capacitance to ground CO, to non-fault phase of interphase C12 to ground capacitance and the electric reactor zero-sequence inductance XLO, its equivalent circuit can be further simplified to Figure 2(a). Figure 1. Three phase system equivalent circuit diagram In this figure: CO- -Line-to-ground capacitance C12- -Phase capacitance XL,XLO- -Shunt Reactor inductance positive sequence, zero sequence inductance Xn- -Neutral point reactor inductance PEITS 2009 rs, XS- -Line resistance, inductance Taking into account the positive sequence inductance XL of the three-phase reactor greater than zero sequence inductance XLO, Equivalent circuits are required to add a calculated equivalent inductance XI2,XL Size should satisfy the wiring method into a star with zero-sequence parallel value equal inductance XLO Reactor positive sequence inductance XL, that is: I I 3 -=-+- XL X w X 12 to: CO)/3,By Type (2) the availability of single-phase resonant breaking when conditions are as follows: 8 Q L =-Q c '" 0.9Q c 9 Wish to restrict the occurrence of resonance, it would take the destruction of their resonant conditions, the methods are easy to take compensation for man-made device so that alternate routes were open state parameters, even breaking with zero voltage. Know from Figure 1 to prevent the resonance condition is: (I) For three single-phase reactor consisting of three-phase reactor, and its positive sequence inductance XL equal its zero- sequence inductance XLO, the XI2- >oo, equivalent to open circuit. (4) Its physical meaning is to enable the interphase capacitance 1 jmC 12 and capacitive reactance of the equivalent reactor components inductance jX12 parallel resonance, circuit impedance and white tends to infinity. Figure 2. system equivalent calculation circuit diagram (a) equivalent calculation circuit diagram (b) single phase equivalent circuit diagram Figure 2 (a) in fpoint is Open-phase fault point, application of the principle of equivalent generators, open the f point,
voltage of its fracture is 2 ,at three single-phase shunt reactor circuit, near infinite large XI2 can be omitted, single-phase equivalent circuit in Figure 2 (b). It is clear, breaking phase voltage U A is: I (5) 1 X L 0 = ----,\----- --- 3mC X L 12 500KV CI - YONG TRANSMISSION LINE PARAMETERS TABLE!. To meet formula (5), Must have the condition XLO>XL, it is impossible for three-phase or three single-phase reactor group, Currently widely used methods are at the neutral point reactor by the reactor small Xn to ground, At this point, the reactor zero-sequence reactance should be (XLO +3 Xn), the installation of small electric reactor Xn, the effect of which is generated equivalent white wire and white inductance compensation capacitor, and reactor are compensated positive sequence line wire capacitance, so small reactor are secondary compensation. Here as 500kV EHV Transmission Line Magnetic Wing line for an example, select the line parameters, proved the small neutral reactor grounding electric wiring on the single- phase line voltage fault.Yong-line magnetic circuit length is 201.42km, a full-line transposition. Wire models for the 4 x LGJ-400/35, its circuit parameters are presented in Table I. (2) (b) -i'. I 2 C,. x., C, j wC + _ 1_ o j OJx LO 1 j aJc o +_._I _ j 2wCl 2 2 2 j WX LO 2 (a) From this single-phase breaker when resonant conditions are: It can be seen above the resonance conditions and line-to- ground capacitance CO, interphase capacitance C12, single- phase reactor zero-sequence-to-ground inductance XLO and zero-sequence inductance xsO relevant. Above the resonance o U; conditions can also be power reactor capacity - , x , and line charging capacity Q c =u;wc\ express , Ue is system nominal voltage,CI is line positive sequence capacitance. Because of the zero-sequence line inductance xsO is small, so negligible,
choose the lme 3 ,White line capacitanceCI2=(CI- Line Name .ength Posit ive sequence Zero-s equence parameters parameters km rl xl cl rO xO cO Qlkm Qlkm J.l FIk Qlkm Qlkm J.lFIk Magnetic 201.4 0.021 0.28 0.013 0.259 0.88 Lake 2 1 3 1 Yongxin (6) XL(X LO +3X n ) X n Lake-SIde installation of the magnetic variable capacity ofa group of highly resistant 120MVar line, single-phase high resistance capacity of 40MVar, the system rated voltage, then we can see single-phase shunt reactor impedance XLO=2520Q, the neutral point reactor converted electric resistance value of Xn=600Q, the reactor zero-sequence impedance (XLO+3Xn) into (I): x' = 3XL(XI.O +3Xn ) 12 [(X LO +3Xn> - XJ (3) 1 +_ l_+j m x,o= O j mC +_1_ j2mC\2 2 jmX Lo 10 Because of Line equivalent circuit is Increase of the equivalent reactance X;2 ,so at this time the fault phase voltage of breaking phase U A is: voltage Laplacian equivalent circuit diagram. Because of the lines anti-electricity, circuit resistance is relatively smalI, in order to facilitate the analysis, in-the-Ioop calculation be ignored. j mC +_ 1_ V A= EA ' jXLO (7) _--'------,-_+ I + jX sO
jmC, +_1_ j 2mC l 2 2 2 jX'j) jX12 Table 1 Data and Xn=600 Qare Separated into the type (2) and type (6) (7),The yong-line A-phase fault phase voltage can be calculated is: Figure 3. Fault switching-off phase's voltage Laplacian equivalent diagram . . V A= - 0.286E A = 82.56kV . . V A=-0.172.< = 49.7kV In the fromer, the fault port voltage has analysised -EA/2, so we can set up the equivalent power for u2" sl n rc r + 0 ) , therefore the fault port voltage for the Laplace transform is Vj (s) ,So: One of: (8) (9) 1 ())Cose+ssine V 2 sl + tt l 1/ U . v/S) = S'[- -"- sm({))t +e)] = 2 Into the table 1 data was: To type inverse transform was: U/ <t ) = sinrot +k 2 sinro,t {)) z =262.6 u/ t t l = [-O.172sin314t +O.052sin262.6t]U n / 1 2 + 211)
k, = Because of the impact of current DC, arc current arc extinguished the general admission happened at the nearest zero-axis current moment, when the checke= o Into (8) (9) style. Solution was: Ignore the relatively smalI line resistance, available the folIowing equation: III. SINGLE-PHASE LINE FAULT TRANSIENT PROCESS ANALYSIS Of course, alI previously obtained steady-state power frequency voltage, the actual for the complex equivalent circuit, when the operation or failure to change their job status, it will have the transition process. During the transition process, because of the power to continue to supply energy, which is stored in the inductor or capacitor in the magnetic energy of the electrostatic field energy is released, or conversion, and its equivalent equivalent inductance L, capacitance C composition of the complex electrical circuit, resulting in an impact component in larger freedom. Only when the circuit frequency and from outside the processing of frequency equal to or close to each other, may have a linear resonator. For the neutral through smalI electric circuits to grounding reactor such as single-phase reclosing disconnect happened failure, because of shunt reactor current should not mutation, arc current will produce a larger amplitude, decay time longer DC component. Analysis of circuit breaker switch on the folIowing no-load line of single-phase refusing to move the port voltage transient process. Established the original line for the no-load circuit, so the initial state for the fault relative to interphase capacitance and the basic energy storage capacitor to zero, of course, electric reactor storage energy also zero, fulIy available on the conditions shown in Figure 3 fault switching-off phases This shows that the increase in neutral grounding reactor can be very effective in reducing single-phase line of the phase voltage, and can effectively avoid the fracture occurrence of resonance over-voltage. For this reactive power compensation coefficient, can be incorporated into the same data in table I to calculate the charge capacity of this line, and thus the reactive power compensation degrees of this line high resistance can achieve I) =Q,. =0.475 is Qc Because of the compensation of lines paralIel high resistance to the general requirements is 0.6 0.9, so there is a need to increase the line capacity of reactive power compensation, therefore paralIel a group of capacity of the bus 120MYar reactor on Yongxiu SOOkYI side bus in order to improve the transmission line reactive power compensation degrees. 11 So the same can be: I ( ) = _[23.8 + 7.78s + 0.38s ]A g f s S 2 +W 2 S 2 +w; So: I , (f ) =- [23.8 + 7.78cos314t + 0.38cos262.6t]A So no-load circuit breaker reclosing happened single-phase refusing to move the fault voltage and arc current all contain the same frequency component and free weight. Frequency component is also a mandatory component, will continue to supply line fault with energy; freely component, and its oscillation frequency is self-loop frequency, size of 41.8Hz. Using MATLAB software to calculate the fault systems, setting fault happened at t = O.2s moment, can get no-load energy lines are not single-phase disconnection happened fault voltage and arc current transient waveform, see Figure 4. Of course fault voltage and the free components of current after a few cycles have been attenuated to a very small, the decay time of DC component is longer. Because of the system complexity of calculate, fault map does not take into account component and DC component Freedom attenuation, the fault transient wave reference only. Figure 4. Single phase no load transmission line refusing-closing faulting voltage and Secondary Arc Current waveform IV. CONCLUSION Shunt Reactor's role is the inductance which can use to compensate between line and line-to-ground capacitance, reducing the flow through line capacitance current, capacitance effect weakened, If the reactive power compensation coefficient larger, equivalent capacitive reactance and inductance may be form a series resonant circuit. In this paper a single-phase disconnection happen resonant Reactive power compensation factor is 0.9, so the general EHV transmission line reactive power compensation factor should be between 0.6 - 0.9. Adopt neutral point reactor small inductance to compensation phase capacitance between lines, can effectively suppress the vibration frequency of occurrence, significantly reduces the fault voltage and arc current frequency amplitude. For shunt reactor with the no-load lines, its reclosing process happen single-phase line fault caused by single-phase refusing to move, and its equivalent circuit the job status to change is very complex. Because the inductance and 12 equivalent capacitance storage energy components exist, which will impose a larger quantity of freedom frequency on transition voltage and current in the circuit, the attenuation of freedom component is often required several cycles of time. Only when the circuit frequency and from outside the processing of frequency equal to or close to each other, may have a linear resonator. For the neutral through small electric circuits to grounding reactor, single-phase disconnected fault line arc current, because of shunt reactor current should not mutation, arc current will produce a larger amplitude, decay time longer DC component. In this paper, the process is also ignored line inductance parameters and the impact of mutual inductance, However, because these parameters compared with the shunt reactor impedance value, small value, the impact of the calculation results is not great, but for a very long lines, the impact can be significant, this analysis at a later introduction to the study. REFERENCES [I] Geng Huannian,Cao Meiyue. The power system harmonic vibration grounding[M] .Beijing:China Electric Power Press.2000 [2] Zhou Zecun,Sun Qigong,Fang Yu,Wang Dazhong. High Voltage Technology[M] . China Electric Power Press.1998 [3] He Yangzan,Wen Zengyin . Power System Analysis Upper and lower volumes[M] .Wuhan: Huazhong University of Science and Technology Publishing House.2005. [4] Li Bin,Li Yongli,Shen Kun.The Study on Single-Pole Adaptive Reclosure of EHV Transmission Lines with the Shunt Reactor [J J Proceedings of the Chinese Society for Electrical Engineering, 2004,24(5) :52-56. [5] Chen Jinqing,Li Duanjiao.The experimental verification of vacuum circuit-breaker opening-closing capacitor bank [ J J Guangdong Electric Power, 2002,15(4) :32-33. [6] Niu Xiaomin,Wang Xiaotong,Shi Wei,et al.Secondary arc current and recovery voltage of series compensated EHV transmission line[J].Power System Technology, I998, 22(9):9-16. [7] Cai Hansheng,Hu Danhui,Tu Caiqi . Study on the Shunt Comensation and Overvoltage in Zhengnan 500 kV System[J]. HIGH VOLTAGE ENGINEERING, 2000,26(5) :34-37. [8] Chen He,Chen Weixian.Choice of Inductance on Neutral of Shunt Reactors.HIGH VOLTAGE ENGINEERING, 2002, 28(8):9-10. [9] Xie Peng,Chen Liangjin,Shi Wei. Effect of neutral grounded by low reactance to the switching over-voltage for Gongboxia transformer[J] . Northwest Water Power, 2003(4):43-45 . [10] Zhang Li,Xu Yuqing. Application and development of shunt reactors in EHV & UHV transmission lines[J] . Electric Power Automation Equipment, 2007,21( 4):18-24. [II] Xiang Qiufeng,Wu Haiyan,Wu Zhiwei . Application and development of shunt reactors in EHV & UHV transmission lines[J].Guangdong Power Transmission Technology,2007,24( 4):4-6. [12] Pan Zhendong,Zhang Jiawen. Power frequency over-voltage of 500 kV four-circuit lines on the same power[J]. East China Electric Power, 2007,35(3) :24-27. [13] Han Yanhua,Shi Wei . Effects of Grounding Resistance on Secondary Arc Current in Extra-High-Voltage Transmission Lines[J]. Journal of Xi'an Jiaotong University, 2006,36(6) :555-558. [14] Niu Wanmin, Tong Liang, Li Cheng. Application Research of Laplace in Analysis of Complicated Linear Dynamic Circuit[J]. Journal of Suihua University,2006,26(6):173-174.