Sie sind auf Seite 1von 16

Durable

Corrosion Resistant
Cooling Towers

THERMAL PERFORMANCE CERTIFIED


BY THE COOLING TECHNOLOGY INSTITUTE
VALIDATION NO. 00-22-02

REYMSA COOLING TOWERS, INC. has been committed for over 30 years to the Commercial and Industrial
Market in providing solutions to their particular cooling needs, always looking for the total satisfaction of our
customers.
This commitment and the experience of our Engineers, combined with supreme quality, premium materials and
components used to manufacture our products, gave birth to the state of the art HRFG Series by REYMSA
Cooling Towers.
Certified by the CTI (Cooling Technology Institute), Certificate Number: 00-22-02 and 100% FRP manufactured in
order to provide the highest performance and longest service life possible, to serve those who demand the best
and we are also committed to maintaning all producion equipment at its optimum condition.

FIBERGLASS REINFORCED POLYESTER (FRP) PROPERTIES


HIGH MECHANICAL RESISTANCE
FRP material is highly resistant to tension and
compression stresses and to impact forces as well; making
it a frequently used material in structural applications.
As a rule of thumb, an FRP laminate requires three times
the thickness than a steel laminate in order to have the
same mechanical resistance.
A very simple analogy can be used to have a clear
understanding of the FRP properties: The Polyester Resin
can be seen as the Cement and the Fiberglass as the
corrugated bars in reinforced concrete.
FRP has at least twice the mechanical resistance of HDPE.
GREAT CHEMICAL AND WEATHER RESISTANCE
There are several types of polyester resin available in the
market for different applications and resistances. The
highest protection against environmental attacks is
reached by using Premium Isophalic Polyester Resin with
UV inhibitor in the manufacturing process of all our Cooling
Towers. The life of FRP with Premium Isopthalic resin is
said to be endless, however, REYMSA recommends using
30 years when making a life-cycle cost analysis.
CORROSION RESISTANCE
Great Resistance to Corrosion and many chemical agents.

LIGHT WEIGHT
An FRP laminate is 5 times lighter than its equivalent of the
same size and thickness made from steel. You will also find
that when compared to a steel laminate of the same
mechanical resistance, the FRP laminate is about half as
heavy.
STABILITY
The low coefficient of expansion of the FRP material
makes it highly resistant to wide variations of temperature
and humidity without showing any deformation. These
properties allow REYMSA Cooling Towers to withstand
many different types of environments.
ZERO OR NO MAINTENANCE REQUIRED
Only for appearance purposes, such as dusting or waxing.
VERY EASY TO WORK WITH
It is very easy to perform minor repair work on the
fiberglass. Materials are available all across the country,
and the fixing process is as easy as grinding the surface,
applying the Polyester Resin, which is in the form of a
liquid, to a layer of fiberglass cloth and applying the resin
again. Finally, wait until the resin is dried.

HRFG SERIES FEATURES


All FRP unitized casing and internal structure
UV Protection for extended life & strength
Optimum Design for all season performance including freezing climates
Fiberglass-Reinforced-Polyamide adjustable pitch Fans
Self extinguish PVC fill & PVC drift eliminator
Direct drive, low speed, TEFC, NEMA fan motors
Low noise operation
No moving internal parts
Fixed distribution nozzles with variable flow rates
Triple-pass PVC Air Inlet Louvers
Large, easily removable access doors
Corrosion resistant strainers
Single or multiple fan configurations with common sump

Maximum Reliability with Efficiency


ALL FIBERGLASS, ONE PIECE, SEAMLESS CONSTRUCTION WITH HIGH MECHANICAL
RESISTANCE, LONG LIFE CONSTRUCTION, AND MINIMUM OR ZERO MAINTENANCE,
WITHOUT WATER LEAKAGE PROBLEMS
Corrosion resistant.
Major longevity, life expectancy of 30 plus years.
No risk of water leakage, a unique seamless, one piece construction.
Better appearance, aesthetically superior.
Excellent mechanical resistance and stabilty, capable of working in all kinds of environments weathers.
Exterior and interior gelcoat protective layer with UV Inhibitor:
* Great resistance against :
1- Agressive chemical conditions of the water
2- Weathering
3- Harmful industrial contaminates
Not affected by corrosive sediments caused by airborne impurities collected in the basin that require all
the cold water in the basin of galvanized and stainless steel towers to be drained, cleaned and flushed
quarterly.
Greater resistance to a wide spectrum of pHs, total dissolved solids, chlorides and sulfates from the
water treatement.
REYMSA Cooling Towers have the capacity to endure higher levels of concentration of chlorides in the
water than Steel (galvanized and/or stainless) Towers. Typically a Pulsed Power Non Chemical water
treatment is able to handle up to 400 ppm of concentration of chlorides in the recirculation water, which
means more cycles of concentration and less water losses caused by bleeds or blowdowns.

REYMSA COOLING TOWERS, INC.

Durability & Minimum Maintenance


DIRECT DRIVE ON ALL OF OUR TOWER MODELS, FOR A MORE RELIABLE OPERATION
WITH MUCH LOWER SERVICE AND OPERATION COSTS, AND MINIMAL RISK OF A
FAILURE
Direct drive transmission that eliminates the use of pulleys, belts
and bearings.
Our direct drive motors eliminate the frequent service required by
the V-belt drive transmissions that have higher operational and
maintenance costs. Typically a V-belt drive transmission requires
quarterly service for checking and readjusting the tension of the
belt, lubrication of fan shaft bearings, lubrication of the motor base
adjusting screws and drive alignment to ensure maximum belt life.
Also, by having fewer components between the fan and the motor,
the risk of a failure causing a sudden stop of the fan and higher
operational water temperatures that may in turn stop the entire air
conditioning system is reduced to a minimum.
REYMSA uses the best fan in the market; manufactured using
cast aluminum hubs and adjustable pitch air foil blades molded
with engineering thermoplastics.
Blade materials: fiberglass reinforced polyamide, which is spark
and corrosive resistant and is able to resist high vibration levels
and high temperatures. Ambient operating air temperatures may
fluctuate from 50F to 250F.
Fan Motors: all our Tower models feature motors that exceed the
Cooling Tower duty characteristics. REYMSA Fan Motors are
NEMA Premium Efficient, TEFC, 1.15 service factor, 100% cast
iron construction for SEVERE DUTY, INVERTER DUTY, and
MARINE DUTY applications, EPOXY PAINT, inpro/ seal vbx
bearing isolators on both ends of the shaft, brass drain and
breather, 6-60 hz variable torque.

REYMSA COOLING TOWERS, INC.

Maximum Reliability with Efficiency


THE MOST RELIABLE HOT WATER DISTRIBUTION SYSTEM
The hot water manifold is manufactured out of PVC, with PVC welded branches tested at 100 psig., to assure
reliability and prevent water leakages that affect the tower efficiency. This avoids wearing of the union gasket
unlike other tower manufacturers.

NON CLOGGING SPRAY NOZZLES


Fixed, non-clogging, 2 ", N.P.T., large orifice nozzles are the largest on the market. They are manufactured
out of ABS plastic and are able to handle water temperatures up to 180 F. Nozzles have with interchangeable
internal devices so that water is efficiently and uniformly distributed across the entire fill surface. Nozzle body
has a threaded connection and is easy to remove.
2" N.P.T. ABS-Spray Nozzles
with interchangeable
internal devices

HIGHEST SURFACE TO VOLUME RATIO PVC FILL FOR SMALLER FOOTPRINT


2

By having the highest specific surface area (ft /ft ),


our fill provides the highest surface area for heat
transfer for all HVAC and most Industrial
applications. The PVC compounds used in our fill
have outstanding resistance to weather exposure
and are nearly impervious to chemical degradation
by alkali, acids, grease, fats, oils and biological
attack. Our fill also has an excellent fire rating due
to its self-extinguishing characteristics and meets
or exceeds Cooling Technology Institute (CTI)
PVC materials standard 136.

REYMSA COOLING TOWERS, INC.

5
6

Durability & Minimum Maintenance


EASY, REMOVABLE, ENVIRONMENTALLY FRIENDLY AIR INLET LOUVER DESIGN
Our triple pass PVC air inlet louvers are designed to block direct sunlight to the water, to minimize splash-out,
and to reduce noise; while at the same time having a low pressure drop that results in less fan motor energy
consumption. By blocking direct sunlight and allowing very little light to pass into the tower, the potential of algae
growth is reduced and therefore so are the water treatment and maintenance costs. Additionally, the Louvers
are durable, corrosion resistant, and impervious to chemical attacks. The PVC is specially formulated for UV
and fire resistance and is non-combustible and self-extinguishing.

EASY MAINTENANCE AND CLEANING ACCESS


Wide and easy access for monitoring or cleaning the inside of the Tower and the cold water basin by removing
the access door or the air inlet louvers.
Removable
Access Door

Removable
Air inlet Louvers

CTI CERTIFICATION OF THERMAL PERFORMANCE


In Addition to our Guarantee of the Thermal Performance of our Cooling Towers,
the HRFG Series are Certified by the Cooling Technology Institute (CTI)
according to the Standard Std-201. Validation No. 00-22-02

REYMSA COOLING TOWERS, INC.

Maximum Reliability with Efficiency


FACTORY TESTS
Every single tower is assembled and tested at
our factory prior to shipment.

EASY AND ECONOMICAL ASSEMBLY


AND INSTALLATION COST
Assembly is reduced to placing and bolting
the fan cylinder on top of the one-piece body
and basin section. No gasket or caulking is
required.
The reduced footprint of our Induced Draft,
Counterflow design requires less structural
base support, and frequently less piping than
the crossflow towers.

FRIENDLY, EASY TO DEAL WITH


COMPANY
A family owned Company founded in 1969 who
really understands the importance of having
satisfied customers to build long term
relationships.

REYMSA COOLING TOWERS, INC.

Durability & Minimum Maintenance


OPTIONAL DESIGNS WITH CUSTOMIZED COMPONENTS OR COLORS FOR SPECIAL
APPLICATIONS

Special Colors, Designs or Configurations

Special fills for industrial applications with


bigger flutes, vertical design or for higher than
130F water temperature.
Tower casing construction with flame
retardant resin according to the ASTM-E84
Standard.

Sickle Fans for Low Noise applications

OPTIONAL EQUIPMENT

Sound Deflectors
Access Ladder
Stainless Steel Handrail
Vibration Cut off Switch
Electric Heaters
Electric Water Level Control
Bottom Outlet (Dry Sump)
Basin Equalizer Connections
Stainless Steel Davit Support
Special Fan Motor Construction
Stainless Steel Non-Skid Catwalk

Automatic Sand Filtration System for


Suspended Solids RFS Series
Sweeper Piping for Water Filtration
Vibration Isolators
Variable Frequency Drive
Basket Non-Corrosive Strainers for Outlet
Connection (Standard)

REYMSA COOLING TOWERS, INC.

Construction Details

1
2
3

4
5
6

8
9
10
11

12
13

1. Fan Section
2. Plenum
3. Drift Eliminator
4. Lifting Eyes
5. Spray Nozzle Manifold

6. Hot Water Inlet


7. Body Section
8. Cellular Fill
9. Air Inlet Louvers
10. Basin Section

11. Water Make up


12. Cold Water Outlet
13. Mounting Holes
14. Overflow (back side)
15. Drain (back side)
16. Purge (back side)

REYMSA COOLING TOWERS, INC.

10

Engineering Data

Quadruple Fan

Single

Double Fan
W

CONNECTION DIAMETER

DIMENSIONS

WEIGHT

MODEL

*Nominal
Tons

Height W/O
Fan

Cold Water
Outlet

Overflow

Water
Makeup

Hot Water
Inlet

Drain

Purge

Shipping

Operating

Motor
HP

HRFG-303115
HRFG-303102

24
26

35
35

35
35

107
107

90
90

2
2

2
2

1
1

727
727

1427
1427

1.5
2

HRFG-404103
HRFG-404105

43
53

48
48

48
48

122
122

98
98

2
2

2
2

1
1

1022
1022

2234
2234

3
5

HRFG-505103
HRFG-505105

61
75

61
61

61
61

127
127

97
97

4
4

1
1

4
4

1
1

1366
1366

3189
3189

3
5

HRFG-606105
HRFG-606175

90
107

73
73

73
73

128
128

98
98

4
4

1
1

4
4

1
1

1890
1890

4415
4415

5
7.5

HRFG-707175
HRFG-707110

141
155

83
83

83
83

134
134

98
98

6
6

1
1

1
1

6
6

1
1

2553
2553

5624
5624

7.5
10

HRFG-708175
HRFG-708110
HRFG-708115

152
169
192

96
96
96

84
84
84

134
134
134

98
98
98

6
6
6

1
1
1

1
1
1

6
6
6

1
1
1

2717
2717
2717

6230
6230
6230

7.5
10
15

HRFG-709175
HRFG-709110
HRFG-709115

163
184
205

110
110
110

85
85
85

134
134
134

98
98
98

6
6
6

1
1
1

1
1
1

6
6
6

1
1
1

2912
2912
2912

6863
6863
6863

7.5
10
15

HRFG-808175
HRFG-808110
HRFG-808115

171
190
210

96
96
96

96
96
96

154
154
154

119
119
119

6
6
6

1
1
1

1
1
1

6
6
6

1
1
1

2986
2986
2986

6992
6992
6992

7.5
10
15

HRFG-810110
HRFG-810115
HRFG-810120

210
243
266

120
120
120

96
96
96

153
153
153

118
118
118

6
6
6

2
2
2

1
1
1

6
6
6

2
2
2

3548
3548
3548

8522
8522
8522

10
15
20

HRFG-812115
HRFG-812120
HRFG-812125

267
291
313

145
145
145

96
96
96

154
154
154

119
119
119

8
8
8

2
2
2

1
1
1

8
8
8

2
2
2

4028
4028
7028

9965
9965
9965

15
20
25

HRFG-714275
HRFG-714210

281
311

167
167

83
83

134
134

98
98

8
8

2
2

1
1

8
8

1
1

4674
4674

10818
10818

(2)7.5
(2)10

HRFG-816275
HRFG-816210
HRFG-816215

343
380
420

199
199
199

104
104
104

159
159
159

123
123
123

8
8
8

2
2
2

1
1
1

8
8
8

2
2
2

5476
5476
5476

13213
13213
13213

(2)7.5
(2)10
(2)15

HRFG-822215**
HRFG-822220**

477
528

268
268

98
98

282
282

246
246

10
10

2
2

1
1

8
8

2
2

9105
9105

19990
19990

(2)15
(2)20

HRFG-827215**
HRFG-827220**

578
618

328
328

98
98

301
301

263
263

10
10

2
2

1
1

8
8

2
2

11165
11165

25665
25665

(2)15
(2)20

HRFG-1414475
HRFG-1414410

565
622

175
175

174
174

134
134

98
98

(2) 8
(2) 8

(2) 2
(2) 2

(2)1
(2)1

(2) 8
(2) 8

(2) 2
(2) 2

(2)
(2)

9349
9349

21637
21637

(4)7.5
(4)10

HRFG-1616475
HRFG-1616410
HRFG-1616415

685
760
840

199
199
199

201
201
201

159
159
159

123
123
123

(2) 10
(2) 10
(2) 10

(2) 2
(2) 2
(2) 2

(2) 1
(2) 1
(2) 1

(2) 8
(2) 8
(2) 8

(2) 2
(2) 2
(2) 2

(2)
(2)
(2)

10953
10953
10953

26427
26427
26427

(4)7.5
(4)10
(4)15

HRFG-1622415
HRFG-1622420

954
1056

268
268

197
197

205
205

246
246

(2) 10
(2) 10

(2) 2
(2) 2

(2) 1
(2) 1

(2) 8
(2) 8

(2) 2
(2) 2

(2)
(2)

18210
18210

39980
39980

(4)15
(4)20

HRFG-1627415
HRFG-1627420

1156
1236

328
328

197
197

282
282

263
263

(2) 10
(2) 10

(2) 2
(2) 2

(2) 1
(2) 1

(2) 8
(2) 8

(2) 2
(2) 2

(2)
(2)

22330
22330

51330
51330

(4)15
(4)20

* A Nominal TON is defined as 3 GPM of water cooled from 95F to 85F with a 78F entering wet bulb.
** Modular sections to be assembled for higher tonage requirements. Minimum two modules. Contact your Rep for proper selection.
1. All dimensions, weights and capacities are in inches, pounds and gallons. Physical dimensions of each tower are approximate and are subject to change.
2. All double and quadruple models have double fittings and connections.

REYMSA COOLING TOWERS, INC.

11

Maximum Reliability with Efficiency


HRFG SERIES TOWER SELECTION
EXAMPLE:
Select the HRFG Model REYMSA Cooling Tower to cool 1200 GMP of clear water from 95 F to 85 F at
entering air wet bulb of 78 F.
STEP 1 RANGE is equal to the temperature differential between the entering water temperature ( T1 ) and the
leaving water temperature ( T2). (95 F - 85 F ) = 10
STEP 2 APPROACH is equal to the temperature differential between the leaving cool water temperature ( T2 )
and wet bulb temperature ( TWB ). ( 85 F - 78 F ) = 7
STEP 3 From Section A: TOWER SELECTION FACTORS; Select the apropriate wet bulb temperature table (
78 F ). Select the range column ( 10 ) and in Approach row ( 7 ), the Tower Selection Factor = 4.8
STEP 4 Next, go to Section B: CAPACITY TABLES; Enter the column headed by the Tower Selection Factor
determined from Section A ( 4.8 ) and read down that column to the desired cooling water flow rate equal to or
greater than that specified ( 1200 gmp ). Look to the left on the row with the desired cooling water flow and read
the corresponding
HRFG816215 REYMSA Cooling Tower model to satisfy your requirements.

Seccin A: TOWER SELECTION FACTORS

60 Deg. Wet Bulb


APPROACH

5
6
7
8
10
12
14
16

3.15
3.60
4.05
4.50
5.49
6.36

2.70
3.03
3.42
3.75
4.50
5.31
6.00

RANGE
15
10 12
2.43
2.73
3.00
3.36
3.96
4.59
5.25
5.91

2.49
2.73
3.00
3.60
4.14
4.65
5.25

2.49
2.70
3.21
3.66
4.14
4.62

20

2.40
2.79
3.18
3.60
4.05

62 Deg. Wet Bulb


26

2.55
2.88
3.21
3.60

30

35

2.40
2.76 2.61
3.09 2.88
3.45 3.21

RANGE
15
12

APPROACH

10

5
6
7
8
10
12
14
16

3.33
3.78
4.26
4.65
5.70
6.75

2.85
3.21
3.75
3.96
4.71
5.55
6.45

2.55
2.88
3.18
3.51
4.14
4.80
5.55
6.21

2.34
2.61
2.91
3.18
3.78
4.32
4.95
5.55

2.37
2.61
2.85
3.33
3.84
4.35
4.85

20

26

30

35

2.34
2.55
2.88
3.36
3.81
4.23

2.31
2.67
3.00
3.39
3.78

2.55
2.91
3.24
3.63

2.40
2.73
3.06
3.45

REYMSA COOLING TOWERS, INC.

12

Durability & Minimum Maintenance


64 Deg. Wet Bulb

63 Deg. Wet Bulb


APPROACH

5
6
7
8
10
12
14
16

3.42
3.90
4.35
4.80
5.85

2.88
3.30
3.66
4.05
4.80
5.61
6.54

RANGE
10 12
15
2.58
2.91
3.21
3.54
4.23
4.89
5.61
6.36

2.40
2.67
2.94
3.24
3.81
4.41
5.04
5.64

2.43
2.67
2.91
3.42
3.96
4.44
5.04

20

2.40
2.61
3.00
3.48
3.90
4.35

26

2.37
2.73
3.12
3.54
3.90

30

2.64
2.97
3.36
3.75

APPROACH

10

2.49
2.79
3.15
3.54

5
6
7
8
10
12
14
16

3.54
4.02
4.47
5.01
6.00

2.97
3.39
3.75
4.14
4.95
5.79
6.60

2.64
2.91
3.30
3.63
4.29
5.01
5.70
6.36

5
6
7
8
10
12
14
16

RANGE
12 15

10

3.72
4.26
4.74
5.31
6.36

3.21
3.63
3.99
4.41
5.19
6.09

2.82
3.15
3.54
3.84
4.59
5.31
6.06

2.61
2.91
3.21
3.54
4.17
4.80
5.52
6.15

2.37
2.61
2.88
3.12
3.72
4.26
4.80
5.46

20
2.37
2.61
2.82
3.27
3.75
4.26
4.71

26

2.37
2.55
2.91
3.36
3.78
4.23

30

5
6
7
8
10
12
14
16

RANGE
12 15

10

4.05
4.56
5.16
5.46

3.54
3.96
4.41
4.89
5.82
6.90

3.12
3.51
3.90
4.26
5.04
5.91
6.75

2.88
3.21
3.54
3.90
4.56
5.34
6.00

2.61
2.91
3.21
3.51
4.11
4.65
5.34
5.94

20
2.37
2.61
2.85
3.06
3.60
4.14
4.65
5.28

2.43
2.82
3.21
3.60
3.99

APPROACH

10

2.34
2.70
3.03
3.42
3.81

5
6
7
8
10
12
14
16

3.93
4.41
4.95
5.55
6.75

3.33
3.75
4.17
4.59
5.52
6.45

2.94
3.30
3.69
4.05
4.74
5.58
6.36

26
2.40
2.64
2.85
3.30
3.78
4.23
4.74

30

5
6
7
8
10
12
14
16

4.38
4.98
5.58
6.15

8
3.78
4.29
4.71
5.25
6.21

10
3.39
3.81
4.23
4.62
5.55
6.36

12
3.12
3.54
3.93
4.26
4.89
5.79
6.60

15
2.82
3.18
3.51
3.78
4.44
5.10
5.79
6.45

20
2.55
2.85
3.09
3.42
3.96
4.50
5.10
5.70

2.73
3.03
3.39
3.72
4.35
5.04
5.76
6.51

2.49
2.91
3.00
3.30
3.90
4.44
5.04
5.70

2.31
2.52
2.73
3.15
3.60
4.02
4.47

RANGE
12 15

35

APPROACH

10

2.43
2.67
3.00
3.48
3.87
4.32

5
6
7
8
10
12
14
16

4.35
4.95
5.55
6.09

3.69
4.14
4.59
5.04
6.00

3.27
3.72
4.11
4.47
5.34
6.15

26

30

35

2.46
2.70
3.09
3.60
3.99
4.50

2.43
2.82
3.21
3.63
4.02

2.31
2.67
3.00
3.39
3.78

2.55
2.91
3.24
3.63

20

26

30

35

2.25
2.49
2.70
2.94
3.42
3.93
4.41
4.95

2.28
2.49
2.70
3.09
3.57
3.99
4.41

2.40
2.61
2.97
3.39
3.81
4.26

2.31
2.49
2.85
3.21
3.60
4.02

3.00
3.42
3.75
4.11
4.80
5.55
6.36

2.73
3.03
3.36
3.69
4.32
5.01
5.64
6.36

20

26

30

35

2.52
2.79
3.03
3.30
3.84
4.38
5.04
5.61

2.31
2.55
2.79
3.00
3.51
3.93
4.44
5.04

2.43
2.67
2.85
3.30
3.78
4.26
4.71

2.34
2.55
2.79
3.18
3.60
4.05
4.50

74 Deg. Wet Bulb

RANGE

20

72 Deg. Wet Bulb

73 Deg. Wet Bulb


APPROACH

2.49
2.76
2.97
3.54
4.02
4.56
5.16

RANGE
12 15

35

70 Deg. Wet Bulb


APPROACH

2.43
2.73
3.00
3.30
3.90
4.50
5.16
5.85

68 Deg. Wet Bulb

66 Deg. Wet Bulb


APPROACH

RANGE
12 15

35

26
2.40
2.64
2.91
3.09
3.60
4.11
4.65
5.16

30
2.28
2.52
2.73
2.94
3.42
3.90
4.35
4.86

RANGE
12 15

35

APPROACH

10

2.40
2.64
2.85
3.27
3.72
4.17
4.59

5
6
7
8
10
12
14
16

4.47
5.19
5.76
6.90

3.84
4.35
4.86
5.34
6.36

3.48
3.90
4.32
4.74
5.61
6.60

3.18
3.60
3.96
4.32
5.13
5.88
6.75

2.91
3.24
3.60
3.90
4.56
5.31
6.00

20

26

30

35

2.67
2.91
3.21
3.48
4.05
4.59
5.22
5.85

2.43
2.67
2.91
3.18
3.66
4.14
4.68
5.25

2.37
2.58
2.82
3.00
3.54
3.99
4.47
5.04

2.28
2.49
2.70
2.91
3.39
3.84
4.29
4.77

REYMSA COOLING TOWERS, INC.

13

Maximum Reliability with Efficiency


76 Deg. Wet Bulb

75 Deg. Wet Bulb


APPROACH

5
6
7
8
10
12
14
16

4.62
5.31
5.91
6.45

3.96
4.44
5.01
5.52
6.06

RANGE
10 12 15
3.54
3.99
4.41
4.89
5.76
6.66

3.27
3.66
4.05
4.41
5.16
6.00

3.00
3.36
3.69
4.02
4.71
5.46
6.15

20

26

30

35

2.70 2.52 2.40 2.34


2.97 2.79 2.67 2.55
3.30 3.00 2.88 2.79
3.60 3.30 3.09 2.97
4.17 3.81 3.60 3.36
4.71 4.32 4.05 3.90
5.40 4.86 4.56 4.38
6.00 5.40 5.16 4.89

10

5
6
7
8
10
12
14
16

4.71
5.40
6.00
6.75

4.05
4.56
5.10
5.61
6.75

3.69
4.14
4.53
5.04
5.91

5
6
7
8
10
12
14
16

10

RANGE
12 15

4.86 4.20 3.75 3.48


5.55 4.71 4.23 3.87
6.15 5.28 4.59 4.29
5.79 5.10 4.65
6.00 5.52
6.36

3.18
3.54
3.87
4.26
4.95
5.70
6.45

20

26

30

35

APPROACH

2.91
3.21
3.51
3.84
4.41
5.04
5.70
6.36

2.67
2.91
3.18
3.45
3.99
4.50
5.16
5.76

2.55
2.79
3.06
3.30
3.81
4.35
4.86
5.52

2.49
2.70
2.94
3.21
3.69
4.17
4.65
5.19

5
6
7
8
10
12
14
16

5
6
7
8
10
12
14
16

10

RANGE
12 15

5.10 4.44 3.93 3.69


5.79 5.04 4.41 4.11
6.51 5.55 4.89 4.50
6.15 5.40 4.92
6.36 5.85
6.75

3.36
3.75
4.11
4.44
5.25
6.00

APPROACH

5
6
7
8
10
12
14
16

5.49 4.65 4.20 3.84


6.15 5.31 4.62 4.32
6.90 5.88 5.16 4.74
6.54 5.70 5.16
6.75 6.15

3.54
3.96
4.32
4.71
5.49
6.36

3.06
3.45
3.78
4.14
4.80
5.55
6.24

20

26

30

35

2.79
3.09
3.42
3.72
4.29
4.89
5.55
6.15

2.61
2.85
3.12
3.42
3.90
4.44
5.04
5.58

2.49
2.73
2.97
3.24
3.72
4.26
4.74
5.28

2.40
2.64
2.85
3.06
3.60
4.05
4.50
5.10

10

RANGE
12 15
3.21
3.60
3.93
4.32
5.07
5.85
6.60

20

26

30

35

2.97
3.27
3.60
3.90
4.50
5.19
5.85
6.60

2.70
2.97
3.27
3.57
4.11
4.65
5.25
5.85

2.67
2.91
3.15
3.45
3.93
4.47
5.04
5.64

2.52
2.76
2.97
3.21
3.75
4.26
4.74
5.28

80 Deg. Wet Bulb

20

26

30

35

APPROACH

3.00
3.36
3.69
3.96
4.59
5.25
5.94
6.75

2.82
3.09
3.42
3.69
4.26
4.80
5.46
6.00

2.70
2.94
3.21
3.51
4.02
4.59
5.16
5.79

2.58
2.88
3.09
3.39
3.90
4.38
4.92
5.52

5
6
7
8
10
12
14
16

10

RANGE
12 15

5.28 4.50 4.11 3.78


6.00 5.10 4.56 4.20
6.75 5.70 5.10 4.65
6.24 5.61 5.10
6.60 6.00

3.45
3.81
4.20
4.56
5.40
6.15

20

26

30

35

3.09
3.48
3.78
4.14
4.74
5.46
6.09

2.85
3.15
3.45
3.75
4.35
4.92
5.55
6.15

2.79
3.03
3.33
3.63
4.14
4.68
5.34
5.85

2.70
2.94
3.21
3.51
3.99
4.50
5.10
5.64

82 Deg. Wet Bulb

81 Deg. Wet Bulb


RANGE
10 12 15

5.04 4.38 3.87 3.57


5.70 4.95 4.32 3.99
6.36 5.52 4.80 4.38
6.00 5.28 4.80
6.24 5.67
6.60

79 Deg. Wet Bulb


APPROACH

3.42
3.78
4.17
4.56
5.40
6.15

78 Deg. Wet Bulb

77 Deg. Wet Bulb


APPROACH

RANGE
12 15

APPROACH

20

26

30

35

APPROACH

3.21
3.57
3.90
4.26
4.89
5.61
6.36

2.94
3.24
3.57
3.81
4.41
5.04
5.70
6.36

2.85
3.18
3.48
3.75
4.29
4.86
5.49
6.09

2.73
3.00
3.30
3.60
4.08
4.65
5.16
5.79

5
6
7
8
10
12
14
16

RANGE
10 12 15

5.55 4.74 4.26


6.33 5.40 4.74
6.00 5.28
6.60 5.79
6.90

3.96
4.44
4.89
5.40
6.30

3.60
3.99
4.38
4.77
5.64
6.45

20

26

30

35

3.20
3.63
3.93
4.29
5.01
5.70
6.45

3.03
3.36
3.69
3.96
4.56
5.25
5.85
6.60

2.94
3.21
3.54
3.81
4.35
5.04
5.64
6.21

2.85
3.09
3.42
3.63
4.20
4.74
5.34
5.94

REYMSA COOLING TOWERS, INC.

14

Durability & Minimum Maintenance


Section B: CAPACITY TABLES

GPM
SELECTION FACTORS

MODEL

2.4

2.8

3.2

3.6

4.4

4.8

5.4

5.8

6.2

6.6

303115
303102

36
39

42
46

48
52

54
59

60
65

66
72

72
78

75
81

81
88

87
94

93
101

99
107

404103
404105

65
80

75
93

86
106

97
119

108
133

118
146

129
159

134
166

145
179

156
192

167
205

177
219

505103
505105

92
113

107
131

122
150

137
169

153
188

168
206

183
225

191
234

206
253

221
272

236
291

252
309

606105
606175

135
161

158
187

180
214

203
241

225
268

248
294

270
321

281
334

304
361

326
388

349
415

371
441

707175
707110

212
233

247
271

282
310

317
349

353
388

388
426

423
465

441
484

476
523

511
562

546
601

582
639

708175
708110
708115

228
254
288

266
296
336

304
338
384

342
380
432

380
423
480

418
465
528

456
507
576

475
528
600

513
570
648

551
613
696

589
655
744

627
697
792

709175
709110
709115

245
276
308

285
322
359

326
368
410

367
414
461

408
460
513

448
506
564

489
552
615

509
575
641

550
621
692

591
667
743

632
713
794

672
759
846

808175
808110
808115

257
285
315

299
333
368

342
380
420

385
428
473

428
475
525

470
523
578

513
570
630

534
594
656

577
641
709

620
689
761

663
736
814

705
784
866

810110
810115
810120

315
365
399

368
425
466

420
486
532

473
547
599

525
608
665

578
668
732

630
729
798

656
759
831

709
820
898

761
881
964

814
942
1031

866
1002
1097

812115
812120
812125

401
437
470

467
509
548

534
582
626

601
655
704

668
728
783

734
800
861

801
873
939

834
909
978

901
982
1056

968
1055
1135

1035
1128
1213

1101
1200
1291

714275
714210

422
467

492
544

562
622

632
700

703
778

773
855

843
933

878
972

948
1050

1019
1127

1089
1205

1159
1283

816275
816210
816215

513
570
630

599
665
735

684
760
840

770
855
945

855
950
1050

941
1045
1155

1026
1140
1260

1069
1188
1313

1154
1283
1418

1240
1378
1523

1325
1473
1628

1411
1568
1733

822215
822220

716
792

834
925

954
1056

1074
1189

1193
1321

1311
1454

1431
1585

1490
1651

1609
1782

1729
1915

1849
2046

1967
2179

827215
827220

869
929

1012
1083

1157
1237

1302
1391

1448
1547

1590
1701

1736
1855

1807
1933

1952
2087

2098
2241

2243
2395

2385
2552

1414475
1414410

848
933

989
1089

1130
1244

1271
1400

1413
1555

1554
1711

1695
1866

1766
1944

1907
2099

2048
2255

2189
2410

2331
2566

1616475
1616410
1616415

1028
1140
1260

1199
1330
1470

1370
1520
1680

1541
1710
1890

1713
1900
2100

1884
2090
2310

2055
2280
2520

2141
2375
2625

2312
2565
2835

2483
2755
3045

2654
2945
3255

2826
3135
3465

1622415
1622420

1432
1584

1668
1850

1908
2112

2148
2378

2386
2642

2622
2908

2862
3170

2980
3302

3218
3564

3458
3830

3698
4092

3934
4358

1627415
1627420

1738
1858

2024
2166

2314
2474

2604
2782

2896
3094

3180
3402

3472
3710

3614
3866

3904
4174

4196
4482

4486
4790

4770
5104

REYMSA COOLING TOWERS, INC.

15

HRFG SERIES SPECIFICATIONS


1. GENERAL
Furnish and install an induced draft, counter flow, factory assembled, All-Fiberglass Reinforced Polyester (FRP) casing
and structure Cooling Tower(s) of ______ cells, as shown on plans. Tower shall be similar and equal in all respects to
REYMSA HRFG model ______________.
2. PERFORMANCE
The tower shall have the capacity to cool _______ GPM of water, from _______ F Entering Water Temperature, to
______F leaving water temperature, at a design entering air wet-bulb temperature of _______ F the performance shall
be certified by the Cooling Tower Institute (CTI) in accordance with CTI Certification Standard STD-201. Additionally, the
Cooling Tower manufacturer shall guarantee the performance of each cell as installed according to plans.
3. CONSTRUCTION
The entire casing and structure shall be constructed of Fiberglass Reinforced Polyester (FRP). Only a high grade isophalic
polyester resin with UV inhibitor shall be used in the manufacturing process. For One and Two Fan units, the entire body
and basin shall be constructed in one-piece, seamless, watertight FRP. No side fasteners will be allowed at the sidewalls of
the body or the basin. There shall not be any metal support or structure in direct contact with water. For the one and two Fan
units, there shall be one or two independent fan cylinders with a motor support to be constructed completely of FRP, no
metal motor support shall be allowed; to be mounted on top of the body structure held in place with stainless steel fasteners
provided by the manufacturer, no gasket shall be required, and shall include a corrosion resistant protective mesh screen
cover to prevent airborne objects from entering into the fan cylinder. Four fan units shall consist of three sections; the body
shall be composed of two independent, seamless, watertight FRP pieces, held together with stainless steel fasteners
provided by the manufacturer. The basin shall be composed of two independent, seamless, watertight FRP pieces, held
together by side stainless steel fasteners provided by the manufacturer. Multi-piece walls or sheet metal wall sections will
not be allowed. There shall not be any metal support or structure in direct contact with water. The fan cylinder structure shall
have a motor support constructed completely of FRP. No metal supports shall be allowed. All three sections shall be held
together by perimetral flanges with stainless steel fasteners provided by the manufacturer, no gasket shall be required. The
entire One, Two or Four Fan tower shall be designed and constructed to withstand wind pressure of no less than 30 poundsforce per square foot (psf) on external surfaces. The top of the body shall be designed and constructed to withstand a live
load of no less than 40 psf in addition to the concentrated loads of the fan or other equipment mounted thereon. The One,
Two and Four Fan unit basin shall be equipped with cold water outlet, drain with mesh screen cover, overflow, water makeup, drain equalizer and purge fittings. All drain fittings 3" and smaller shall be NPT and larger than 3" shall be ANSI flange
(FRP or PVC). A bottom sump drain shall be available for dry sump installation, if required.
4. FILL, DRIFT ELIMINATOR AND LOUVERS
Fill shall be cross corrugated film-type, thermoformed PVC, in sections not to exceed 1' x 1' x 6'. For hot water temperatures
higher than 130F, Aluminum or Polyestyrene fill may be used, as applicable. For Higher water temperatures, drift
eliminators shall be thermoformed PVC, in sections not to exceed 1' x 1/2' x 6'. Drift losses shall not exceed 0.005% of the
design circulating flow. Louvers shall be thermoformed PVC on all four sides of the tower(s).
5. HOT WATER DISTRIBUTION SYSTEM
The hot water shall enter the body through a single inlet per cell. All interior distribution piping shall be PVC. For industrial
applications with higher water temperatures, fiberglass or Stainless Steel piping may be used as applicable. Water shall be
evenly distributed over the fill media by removable, interchangeable ABS (2 ") Spray Nozzles. Nozzles shall each contain
internal, interchangeable flow devices to provide an optimal spray pattern with a 2 to 10 psig pressure differential.
6. FANS
Fan(s) shall be propeller type, fan blades shall be constructed with Fiberglass Reinforced Polyamide, spark and corrosive
resistant with adjustable pitch suitable for high temperature operation up to 250F. Hub(s) shall be aluminum alloy castings.
Fan(s) shall be directly driven. Towers utilizing gear reducers or belt driven units will not be accepted.
7. MOTORS
There shall be single speed, Totally Enclosed Fan Cooled (TEFC), phase, Hertz, volts. Electric Motor(s), NEMA rated for
continued operation at a 1.15 service factor. Each motor shall be horsepower for a total Horsepower at RPM.
8. MANUFACTURER
The Cooling Tower shall be manufactured by REYMSA COOLING TOWERS, INC.

REYMSA COOLING TOWERS, INC.


1641 World Trade Center, Millenium Industrial Park Laredo, Tx. 78045
Phone (210) 579-4837 Fax (210) 745-1513
R

Toll Free Number 1-866-445-2043


sales@reymsa.com

www.reymsa.com