LonWorks Gateway

Protocol Converter

LonWorks Gateway Features :


DIN Rail or Panel Mounted compact Protocol Converter Hardware with two communication ports COM1: RS232 / RS422 / 2 or 4 wire RS485 / CMOS COM2: LonWorks TP FT10 (78 Kbps, free topology) Connect your LonWorks device to serial device or vice versa Connect your LonWorks device on Modbus Network (as a Master / Slave) Same model can be re-configured for connecting different devices Supports up to 62 network variables Free software for Gateway and SNVT variables configuration!! CE with UL certification We welcome opportunity to develop new / customized drivers for UNVT templates

Automation Simplified

Possible Applications :
1. Multiple LonWorks Devices connected to one PLC
Genset 1
Genset 2

LonWorks Gateway

Genset 3

PLC

X Inverter

2. Multiple LonWorks Devices connected to Modbus Host


Genset 1
Genset 2

LonWorks Gateway

Genset 3

X Inverter

Modbus Host

3. Multiple LonWorks Networks and multiple LonWorks Gateways


Genset 1 LonWorks Gateway
Genset 2

X Inverter

Genset 1
Modbus Host

Genset 2

X Inverter

LonWorks Gateway
* Images not to Scale.

GWY-100 Operations :
The LonWorks Gateway communicates between a LonWorks network interface on one side and various serial protocols on the other side (e.g. Modbus ASCII / RTU etc.). It allows LonWorks devices to make available their LonWorks variables for PLCs or SCADA. It also makes possible for serial device to act as a LonWorks node. It is externally powered from 3 pin terminal block and power is isolated from both communication ports. Both the communication ports are also isolated from each other. Microsoft Windows based configuration software, Gateway Setup, helps the user to configure Gateway unit. Configuration means making the Gateway unit work as per the system requirements. The complete configuration for a unit is termed as Project. Project comprises of device names, Register addresses, Conditions for block execution etc. Block may contain information like copy number of Words, Bits etc. from one device to other device and conditions for copy, if any. Gateway transfers data between two devices by execution of blocks. After the Project is defined, Drivers for required devices and Project should be downloaded. Gateway can now communicate with the connected devices and transfers data between them. System requirements for Gateway Setup Software are: Programming software is common for the entire Gateway family. Windows Version : Microsoft Windows XP / 2000, Windows 7 / VISTA Processor : PENTIUM or higher Hard disk Space : 5 MB or more RAM : 64 MB or more Display resolution : 800 X 600 (VGA) or better Display colors : 16 bit color Other Accessories required for the GWY-100 configuration and to use in actual application: 1. Gateway Configuration / Connecting Cable.** 2. Gateway Setup Software . 3. Devices with communication cables. 4. Network Management Tool (Lonmaker) for installation of a node and binding of network variables.
Note : GWY-100 Supports up to 62 network variables. LonWorks Wizard allows the user to configure Gateway for SNVT variables. We welcome opportunity to develop new / customized drivers for UNVT templates.

Communication Ports :
GWY-100 has two communication ports COM1 and COM2. COM1 port is compatible to RS232 / RS422 / RS485 and CMOS signal levels. The Pin-outs of these ports are as shown below :
LonWorks Side : TP/FT-10 (port 2)

3. Signal Ground 2. B 1. A
3 Pin T erminal Block
*Do not use pin no. 6 of PLC1 / COM1.
**Refer our website (www.renuelectronics.com) for your specific Cable requirements

LED Status :
Service LED: Flashing : Node has application but is not installed in the network. (Unconfigured node) Solid : Node is unconfigured and applicationless. Indicates errors detected by the neuron self test routine OFF : Node is configured and installed in the network. OK LED : Flashing : IBM Download mode Solid : PLC Communication OK OFF : No firmware LON LED : Flashing : Receiving frames from LonWorks network PLC1 LED : Flashing : Receiving frames from PLC1 Port

Switch Settings :
There are 4 switches which decide: Switch 1. IBM Download Switch 2,3,4. Specific Template Selection (If applicable)

Protocols supported for :


The GWY-100 currently supports Modbus Master(RTU), Modbus Slave (ASCII / RTU), AB DF1, Schneider Inverters and Toshiba inverter protocols. GWY-100 also supports LONMARK Functional Profile for Variable Speed Motor Drives-6010. GWY-100 can also support following PLCs on request: ABB Aromat FP0 / FP1 / FP2 / FP Sigma and FPM Delta DVP Series IDEC Micro3 / C, IDEC MicroSmart, IDEC Open Net LG MasterK 80S-300S Omron Host Link Taian TP02 Series Toshiba T series (Programming Port) AB DF1 Full Duplex (Micrologix / SLC5/0x /PLC5/30) Baldor Drives GE Fanuc Series 90-30, VersaMax Keyence KV Messung XMP-8 / NEXGEN 4000 / NEXGEN 5000 Siemens-S7-200 Series Telemecanique 17, 47 & 67 Series Twido AB DH485 (SLC5 / 0x series) Crouzet Idec Micro 1 / FA2Jr PLCs Koyo Mitsubishi FX Siemens S7-300 Series Telemecanique TSX07/37/57 Yaskawa Drives

GWY-100 can communicate with all the above PLCs using different communication cables. For detailed information on Gateway, visit our Website: www.renuelectronics.com or contact factory. New PLC drivers are constantly added. Please contact factory for more information. We welcome an opportunity to develop new, custom drivers and customization of Gateway products.

Specifications :
: 12 V DC to 32 V DC, 1.6 W : 3 LEDs for status indication and 1 LED for device configuration status Communication Ports : 2 Communication ports with COM1 : RS232 / RS422 / RS485 / CMOS COM2 : LonWorks Network Interface. TP FT-10 (78 Kbps, free topology) (Isolation between communication ports and Power supply, through DC-DC coupler is 1 KV) COM1 / PLC1 : Connects to PC for setup download or connects to PLC1 at runtime. COM2 / PLC2 : LonWorks Network Interface. TP FT-10 (78 Kbps, free topology) (Isolation between communication ports, through opto-isolation is 1KV rms for 1 min) Temperature : Operating : 0O to +60O C Storage : -20O to +80O C Humidity : 10% to 90% (Non condensing) Mounting : DIN rail or back panel mounting Dimensions (DIN rail) : 105mm(L) X 40mm(D) X 51mm(W) Weight : 125 gm approx. Certifications : CE with UL certification Immunity to ESD : as per IEC61000-4-2 Immunity to Fast Transients : as per IEC61000-4-4 Immunity to Radiated electromagnetic field : as per IEC61000-4-3 Immunity to Conducted disturbances : as per IEC61000-4-6 Surge : as per IEC61000-4-5 Radiated emission : as per EN61000-6-4 Power LEDs

Models :
Series/Model GWY-00 GWY-100 GWY-300 GWY-500 GWY-610 GWY-800 GWY-900 Technology Protocol Serial LonWorks CANBUS Profibus Ethernet HART GSM Various LonTalk CAN ( J1939/CANopen) Profibus-DP-V0 Modbus TCP/IP HART Various

Note:

Contact factory for customized LonWorks Gateway applications (UNVT Templates).

Dimensions :
GWY-100 unit is shipped with a separate DIN rail plate which has to be attached to the unit, if needed. User can use the unit with or without the DIN rail plate. Following sketch shows dimensional details of GWY-100 with the DIN rail plate.

GWY-100 All dimensions are in mm.

FACTORY
Survey No. 2/6, Baner Road, Pune - 411045, India. Tel : +91 20 2729 2840 Fax : +91 20 2729 2839 Email : info@renuelectronics.com Website: www.renuelectronics.com
An ISO 9001 : 2008 and ISO 14001 : 2004 certified company
(Specifications subject to change without prior notice. DS-GWY-100: Rev. 3I)