The transformers are single-phase, concentrically wound safety transformers with separate windings, designed for control panel installation. They comply with European standard EN60742 and bear the safety mark.
Type summary
Type N38SA N75SA N150SA N240SA N380SA Max. power [VA] 38 75 150 240 380 primary Fuse Nominal current Weight incl. or secondary Is packaging [kg] T1.6 A T3.15 A T3.6 A 1.58 3.12 6.25 10 15.80 A A A A A 1.2 1.8 3.5 4.8 8.1
Technical data
Primary voltage 1 Primary voltage 2 Secondary voltage Isolation voltage Protection standard Protection class Mounting position Ambient temperature 230 VAC, 50 ... 60 Hz 220 VAC, 50 ... 60 Hz 24 VAC 3750 V IP00 to IEC529 I Any 0 ... 50 C
Example
1 controller 1 heating valve, type M3P32G 1 cooling valve, type M3P40G (26 W.1.5) 1 damper actuator, type AUH250 Total Required transformer 4 VA VA 39 VA 5 VA 48 VA N75SA
Dimensions [mm]
93.00241
E B G
D A
Type A B C D E F G
1998 Siemens Building Technologies Ltd. CA1N5531E / 11.1998 2/2 Siemens Building Technologies Landis & Staefa Division