QC~PLAN.
Project No. & Name: Name of Client/ Consultant: SL ACTIVITY No. 1 Selection & approval of materials CONTROLLING NATURE & EXTENT DOCUMENT OF INSP./TEST Contract specs. Verification, 100% drawings BS 8000 : Part 13 Mfr's catalogue Contract drawings Verification, 100% BS 8000 : Part 13 ACCEPTANCE CRITERIA - All materials approved by client - Type, length, diameter, grade, colour and class of pipe as per drawings Drainage (a) Above Ground Level & Sanitary Appliances Doc. No. M & E QC~Plan- 063a/ REV. 0 PERSON RESP. AT LOCATION Engineer/ Foremen/ Quality Engineer RECORD Mfr's instructions Material approval sheet Inspection report M & E QC~Form063a-01/ REV. 0

Receiving inspection and storage

Drainage pipe laying

Contract drawings Visual, 100% BS 8000 : Part 4 BS 8000 : Part 13

Bending

Fixing

Contract specs. Visual, 100% BS 8000 : Part 4 BS 8000 : Part 13 Contract specs. Visual drawings

- Materials comply with approved sample Store Keeper - Free from defects - Stored in clean level ground with adequate support & avoid soiling - Large dia pipe stacked at bottom - Control stacking height to limit deflection - Line, level, width & branch connections as per Engineer/ drawings. Foremen/ - Vertical stacks are in plumb Quality Engineer - Branches laid to uniform/specified gradient - Adequate clearance for pipes which need painting and cleaning - Layout, walls, floors, openings & levels to be in order - Pipe ends cut square, burr removed & bores cleaned before jointing - Manhole connections to be located as per drawings - Spacing and support as per drawing - For metal pipe rippling, throating and Engineer/ reduction in bore dia while bending Foremen/ is avoided Quality Engineer - Approved clamps & fixing method Engineer/ Foremen/ Quality Engineer

180979517.xls.ms_office

Date: January 26, 2001

XYZ

Page 2 of 2

QC~PLAN.
Project No. & Name: Name of Client/ Consultant: SL ACTIVITY No. 6 Jointing CONTROLLING DOCUMENT Contract Specifications NATURE & EXTENT OF INSP./TEST Visual ACCEPTANCE CRITERIA Type - Copper pipe - PVC Visual - Fixing as per manufacturer's instruction - Seal gaps with sealant - No leakage Drainage (a) Above Ground Level & Sanitary Appliances Doc. No. M & E QC~Plan- 063a/ REV. 0 PERSON RESP. AT LOCATION Engineer/ Foremen/ Quality Engineer Engineer/ Foremen/ Quality Engineer Leak Test Inspection Report M & E QC~Form063-02/ REV. 0 RECORD

Fixing sanitary appliances On completion Inspection & testing

Contract specs. drawings

Contract Specifications

Verification Leak test

Pipe work Engineer/ - Water testing done for ordinary pipe work, Foremen/ static head not to exceed 6m Quality Engineer Rain water gutter - Plugging & filling with water. Check for leaks after 5 min. of filling Sanitary appliances - Minimum water seal of 25mm in every trap - Positioning & maintaining the levels as per drawing - Operation satisfactory - No damage on pipe work & sanitary fittings

Work Location: Remarks:

Quality Engineer: Date:

Engineer / Foremen: Date:

180979517.xls.ms_office

Date: January 26, 2001