Introduction
Cooling towers are commonly used to remove
excess heat that is generated & represent a relatively inexpensive and dependable means of removing low-grade heat from cooling water.
Cooling towers make use of evaporation whereby
some of the water is evaporated into a moving air stream and subsequently discharged into the atmosphere in the form of vapours.
but I will limit my talk to a Air draft (Natural Draft) Cooling Tower
1. 2. 3. 4. 5. 6. 7.
Cold water basin Tower Framework Water distribution System Fill Drift Eliminator Casing / Shell Structure Louvers
1. 2. 3.
Frame & Casing Concrete & Steel Fill - PVC/Polyproplene Nozzles - PVC/Polyproplene
Tower Problems
Scale deposit Fouling due to presence of silt ,dirt ,sand etc. Microbiological growth due to presence of
Operation Considerations
Water make-up
To compensate the water loss due to : 1. Evaporation , 2. Drift (water entrained in discharge vapor), estimated to be About 0.2% of water supply 3. Blow down (water released to discard solids).
Design Parameter Total design capacity Height of top of tower above sill -do- at throat -do- at top Dry Bulb Temp. Design wet bulb Temp Cold Water outlet Temp Hot water Inlet Temp PVC Fill
CT- Stage I 33000cum / Hr. 120 m 36.93 m 42.67 m 35.1 28.5 32.5 42.5
Size 1600x600x300 in two layers; munters type C-10-19 double folded edge on one side and with black UV Stabilization , 0.25 mm thick and having a flute size of 19mm 2.8 m
CT Stage II 36500 m3/hr 104.625 m 49.856 51.856 35.05 28.25 33 41.1 1220x1830 of varying depths of 915mm,1120mm &1525 mm of Paharpur M67 make
10
Basin Depth
2.0-2.30 m
Patches of dampness on external surface of RCC shell. Minor cracks on staircase beams & columns. Holes & Patches in the inside of shell Water distribution Pipes Silt Deposit in the distribution pipes Exposure of Concrete surface of Supports Deposit of Scale / Corrosion of MS pipe surface PVC Fills Green algae found on fills Fills are almost choked with scale deposit mainly consisting of CaCo3 & sio2 & other organic matter. water at operating COC is scaling in nature. Pre chemical treatment / dozing be adopted to prevent organic growth. PVC Nozzles Chocking of nozzles due to the presence of silt, clay, sand & scale deposits. Nozzles are cleaned as a matter of routine in every shut down Presence of algae, fungi & bacteria are causing biological fouling in Nozzles Strainers & chemical treatment can be used to prevent biological fouling.