Specifications
TECHNICAL SPECIFICATIONS
Cooling Heating Cooling Heating Cooling Heating Material Unit Height Width Depth mm mm mm kg Nr of Rows Fin Pitch Face Area mm m 200 900 620 27 3 1.5 0.176 12 10.5 9.5 8.5 44 15 62 kW kW kW kW kW kW
FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
1-1
Capacity
5.6 6.3 0.165 0.152 0.185 0.170 Galvanised steel plate 200 900 620 28 3 1.5 0.176 12 Sirocco fan 12.5 11.0 10.0 44 15 130 Direct drive
7.1 8.0 0.181 0.168 0.192 0.179 200 1,100 620 31 3 1.5 0.227 12 16.5 14.5 13.0 44 15 130
1
1
Unit Dimensions
Nr of Stages Fan Air Flow Rate Type Cooling High high m/min High Low Fan External static pressure Motor High Standard Output (high) Drive Cooling Sound Pressure Liquid (OD) Gas Drain Air Filter Refrigerant control Temperature control Safety devices Standard Accessories Standard Accessories High high dBA High Low Piping connections Type Diameter Type Diameter Diameter Sound absorbing insulation mm mm mm dBA dBA m/min m/min Pa Pa W
34 32 30 6.35 12.7
35 33 31 Flare connection 6.35 Flare connection 12.7 VP20 (I.D. 20/O.D. 26) Foamed polyethylene Removable/washable/Mildew proof Electronic expansion valve Microprocessor thermostat for cooling and heating Fuse Fan motor thermal protector Operation manual Installation manual Drain hose Sealing pads Clamps Washer Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air filter Product Quality Certificate
36 34 32 9.52 15.9
1
1-1
Notes
Specifications
TECHNICAL SPECIFICATIONS
FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
Nominal cooling capacities are based on : indoor temperature : 27CDB, 19CWB, outdoor temperature : 35CDB, equivalent refrigerant piping : 7,5m (horizontal) Nominal heating capacities are based on : indoor temperature : 20CDB, outdoor temperature : 7CDB, 6CWB, equivalent refrigerant piping : 7.5m (horizontal) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. External static pressure is changeable to set by the remote control; this pressure means : high static pressure standard static pressure. The operation sound levels are conversion values in anechoic chamber. In practice, sound levels tend to be higher than the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction, sound level will increase
3 1
1
FXDQ40NBVE
FXDQ50NBVE
FXDQ63NBVE
VE 1~ 50 1.0 15 0.8 50 220-240 1.0 15 0.8 -10% +10% Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA is smaller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse, use a circuit breaker 1.1 15 0.9 50
FXDQ40NBVE
FXDQ50NBVE
FXDQ63NBVE
VE 1~ 60 220 1.1 15 0.9 60 220 1.3 15 1.0 -10% +10% Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA is smaller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse, use a circuit breaker 60 220 1.4 15 1.1
FXDQ20,25,32PB FXDQ40,50,63NB
1
2
FXDQ20PB
FXDQ25PB
FXDQ32PB 250V 5A
FXDQ40NB
FXDQ50NB
FXDQ63NB
4D060926
Options
3 1
3
Other options
Kit name Adapter for wiring Wiring adapter for electrical appendices (1) Wiring adapter for electrical appendices (2) Remote sensor Installation box for adapter PCB. Electrical box with earth terminal 2 blocks 3 blocks FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE FXDQ40NBVE FXDQ50NBVE KRP1B56 KRP2A53 KRP4A54 KRCS01-1B KBP1BA101 KJB212AA KJB311AA DST301BA51 FXDQ63NBVE
Noise filter (for electromagnetic interface use only) External control adapter for outdoor unit (must be installed on indoor units) Insulation kit for high humidity KDT25N32
4D060939
4
4-1
Capacity tables
Cooling capacity tables
TC: Total capacity;kW SHC: Sensible capacity;kW Indoor air temperature 19.0WB 27.0DB TC SHC 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9
FXDQ40,50,63NB
1
4
Unit size 40
50
63
Outdoor Nominal air temp. capacity CDB 4.5 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 5.6 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 7.1 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0
14.0WB 20.0DB TC SHC 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8
16.0WB 23.0DB TC SHC 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3
18.0WB 26.0DB TC SHC 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8
20.0WB 28.0DB TC SHC 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.7 3.2 4.7 3.2 4.6 3.2 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 5.9 4.0 5.8 4.0 5.7 3.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.5 4.8 7.4 4.8 7.2 4.7
22.0WB 30.0DB TC SHC 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.3 3.3 5.2 3.3 5.2 3.2 5.1 3.2 5.0 3.2 4.9 3.2 4.9 3.1 4.8 3.1 4.7 3.1 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.6 4.2 6.5 4.1 6.4 4.1 6.3 4.0 6.2 4.0 6.1 4.0 6.0 3.9 5.9 3.9 5.8 3.9 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.4 5.1 8.3 5.0 8.1 5.0 8.0 4.9 7.9 4.9 7.8 4.8 7.7 4.8 7.5 4.7 7.4 4.7
24.0WB 32.0DB TC SHC 5.9 3.5 5.8 3.5 5.8 3.5 5.7 3.5 5.6 3.4 5.5 3.4 5.5 3.4 5.4 3.3 5.3 3.3 5.3 3.3 5.2 3.3 5.1 3.2 5.0 3.2 5.0 3.2 4.9 3.1 4.8 3.1 7.4 4.1 7.3 4.1 7.2 4.1 7.1 4.0 7.0 4.0 6.9 4.0 6.8 4.0 6.7 3.9 6.6 3.9 6.6 3.9 6.5 3.8 6.4 3.8 6.3 3.8 6.2 3.7 6.1 3.7 6.0 3.7 9.3 5.7 9.2 5.6 9.1 5.5 9.0 5.4 8.8 5.4 8.7 5.3 8.7 5.3 8.5 5.2 8.4 5.1 8.3 5.1 8.2 5.0 8.1 4.9 7.9 4.9 7.8 4.8 7.7 4.8 7.6 4.7 ED39226A
4
4-2
Capacity tables
Heating capacity tables
Outdoor air temperature CDB CWB -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 Indoor air temperature CDB 20.0 21.0 kW kW 2.9 2.9 3.0 3.0 3.2 3.2 3.4 3.4 3.6 3.5 3.7 3.7 3.8 3.8 3.9 3.9 4.0 4.0 4.2 4.2 4.4 4.4 4.6 4.6 4.9 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 3.7 3.7 3.8 3.8 4.0 4.0 4.3 4.2 4.5 4.5 4.7 4.7 4.8 4.8 4.9 4.9 5.1 5.1 5.3 5.3 5.5 5.5 5.8 5.8 6.2 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 4.7 4.7 4.8 4.8 5.1 5.1 5.4 5.4 5.7 5.7 6.0 6.0 6.1 6.1 6.2 6.2 6.4 6.4 6.7 6.7 7.0 7.0 7.4 7.4 7.8 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7
FXDQ40,50,63NB
3
16.0 kW 3.0 3.0 3.2 3.4 3.6 3.7 3.8 3.9 4.0 4.2 4.4 4.7 4.9 5.1 5.2 5.4 5.6 5.6 5.6 3.7 3.8 4.1 4.3 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.9 6.2 6.4 6.6 6.8 7.0 7.1 7.1 4.7 4.9 5.1 5.4 5.7 6.0 6.1 6.3 6.5 6.8 7.0 7.5 7.9 8.1 8.4 8.7 8.9 9.0 9.0 18.0 kW 2.9 3.0 3.2 3.4 3.6 3.7 3.8 3.9 4.0 4.2 4.4 4.6 4.9 5.1 5.2 5.3 5.3 5.3 5.3 3.7 3.8 4.0 4.3 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.9 6.2 6.4 6.6 6.7 6.7 6.7 6.7 4.7 4.9 5.1 5.4 5.7 6.0 6.1 6.3 6.5 6.7 7.0 7.4 7.8 8.1 8.4 8.5 8.5 8.5 8.5 22.0 kW 2.9 3.0 3.2 3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 3.7 3.8 4.0 4.2 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.7 4.8 5.1 5.4 5.7 6.0 6.1 6.2 6.4 6.7 7.0 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 24.0 kW 2.9 3.0 3.2 3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.7 3.8 4.0 4.2 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.7 4.8 5.1 5.4 5.7 5.9 6.1 6.2 6.4 6.7 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 ED39226A
Unit Size 40
1
4
50
6.3
63
8.0
5
5-1
FXDQ40,50NB
20 or more
20 or more
620
20 or more
900
620
(All around) 22 - 4.7 hole 8 x P100 = 800 940 (Suspension bolt pitch) Suspension bolt 4 - M8 ~ M10
12.5 21 57.5
60
Adjustable (0~600)
90
130 90
47 90
63
550
300 or less
Allow view A Inspection door (Ceiling opening) 20-M5 Holes (All around)
50 20 10
50 170
100
300
900
300
30 33
23
280 330
150 100 90 80
130 100 90 80
Nr 1 2 3 4 5 6 7 8 9 10 11
Part name Liquid pipe connection port Gas pipe connection port Drain pipe connection port Drain hose (Accessory) Control box Transmission wiring connection Power supply connection Suspension bracket Inspection door Socket for drain Air filter (Accessory)
Description 6.4 Flare connection 12.7 Flare connection IVP20 (O.D. 26 / I.D. 20) I.D. 25 (Outlet)
NOTES
2 3
In case of back-suction, mount chamber cover to bottom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. Location of units name plate: control box cover. Mount the air filter at the suction side. (Select its color (gravity method) 50% or more). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D045494B
FXDQ63NB
300 or more (Service space of installation box for adaptor PCB) 1100 300 or more (Service space)
20 or more
10 20 50
620
50 or more
20 or more
20 or more
620
Ceiling A (All around) 26 - 4.7 hole 10 x P100 = 1000 1140 (Suspension bolt pitch) Suspension bolt 4 - M8 ~ M10
12.5 21 57.5 60
(Service space)
300
130
47 90
63
550
300 or less
Adjustable (0~600)
100
50 170
30 33
23
280 330
150 100 90 80
130 100 90 80
Nr 1 2 3 4 5 6 7 8 9 10 11
Part name Liquid pipe connection port Gas pipe connection port Drain pipe connection port Drain hose (Accessory) Control box Transmission wiring connection Power supply connection Suspension bracket Inspection door Socket for drain Air filter (Accessory)
Description 6.4 Flare connection 12.7 Flare connection VP20 (O.D. 26 / I.D. 20) I.D. 25 (Outlet)
NOTES
2 3
In case of back-suction, mount chamber cover to bottom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. Location of units name plate: control box cover. Mount the air filter at the suction side. (Select its color (gravity method) 50% or more). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D045496C
10 20 50
50 20 10
900
300
5
5-2
FXDQ40,50NB
3 1
5
4D043886J
FXDQ63NB
4D043887H
Piping diagram
FXDQ20,25,32PB FXDQ40,50,63NB
1
6
Gas side
Liquid side
Filter
Filter
Fan
4D060927
7
7-1
Wiring diagram
Wiring diagram
FXDQ20,25,32PB FXDQ40,50,63NB
3 1
7
POWER SUPPLY
Note: 3 Input from outside Note: 1 Transmission wiring central remote control
Control box
A1P C1 F1U HAP KPR M1F M1P Q1M Printed circuit board Capacitor (M1F) Fuse (F5A, 250V) Light emitting diode (service monitor-green) Magnetic relay (M1P) Motor (indoor fan) Motor (drain pump) Thermal protector (M1F embedded) R1T R2T R3T S1L T1R V1TR X1M X2M Y1E Thermistor (air) Thermistor (coil - 1) Thermistor (coil - 2) Float switch Transformer (220V/22V) Phase control circuit Terminal block Terminal block Electronic expansion valve Z1CZ2C R1T SS1 X16A X18A Noise filter (ferrite core) Wired remote control Thermistor (air) Selector switch (main/sub) Connector for optional parts Connector (adapter for wiring) Connector (wiring adapter for electrical appendices)
: Terminal
,
Colors:
WHT: YLW:
White Yellow
3D060547
NOTES
1 2 3
In case of using central remote control, connect it to the unit in accordance with the attached installation manual. Remote control model varies according to the combination system, confirm enineering materials and catalogs, etc. before connecting. When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control. In details, refer to the installation manual attached to the unit.
10
8
8-1
Sound data
Sound pressure spectrum
FXDQ50NB
Octave band sound pressure level dB(0dB=0.0002bar) Octave band sound pressure level dB(0dB=0.0002bar)
FXDQ40NB
1
8
4D060948
NOTE NOTE
4D060949
Air flow rate H 33.0 39.0
1 2
3 4
Scale Over All (dB): HH (B, G, N is already rectified) A 34.0 C 39.0 Operating conditons: Power source: 220~240V 50Hz / 220V 60Hz Cooling: Return air temperature: 27C DB, 19C WB Outdoor temperature: 35C DB, 24 C WD Heating: Return air temperature: 20C DB, 15C WB Outdoor temperature: 7C DB, 6C WB Measuring place: Anechoic chamber Location of microphone
2m 1m Duct Suction Duct
L 30.0 37.0
1 2
3 4
Scale Over All (dB): HH (B, G, N is already rectified) A 35.0 C 40.0 Operating conditons: Power source: 220~240V 50Hz / 220V 60Hz Cooling: Return air temperature: 27C DB, 19C WB Outdoor temperature: 35C DB, 24 C WD Heating: Return air temperature: 20C DB, 15C WB Outdoor temperature: 7C DB, 6C WB Measuring place: Anechoic chamber Location of microphone
2m 1m Duct Suction Duct
L 31.0 38.0
Discharge
Discharge
1,5m
Microphone
1,5m
Microphone
The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.
The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.
FXDQ63NB
Octave band sound pressure level dB(0dB=0.0002bar)
4D060950
NOTE
1 2
3 4
Scale Over All (dB): HH (B, G, N is already rectified) A 36.0 C 42.0 Operating conditons: Power source: 220~240V 50Hz / 220V 60Hz Cooling: Return air temperature: 27C DB, 19C WB Outdoor temperature: 35C DB, 24 C WD Heating: Return air temperature: 20C DB, 15C WB Outdoor temperature: 7C DB, 6C WB Measuring place: Anechoic chamber Location of microphone
2m 1m Duct Suction Duct
L 32.0 39.0
Discharge
1,5m
Microphone
The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.
11
Fan characteristics
FXDQ40NB
3D046299C
FXDQ50NB
3D046300C
3 1
9
(mmH2O) 6
(Pa) 60
(mmH2O) 6
(mmH2O) 7 6 5
(Pa) 70 60 50
Up sta per limit (hightic pressu of extern ESP) re al
(mmH2O) 7 6 5 4
tern al
50
4
4
High (standard ESP)
40
40 30
30
l rna
3
3
20
2
2 20
U s ppe (sta tatic p r limit nda res of rd sure ext ESP ern a )
al xtern
3 2
10
Low (standard ESP)
10 (Pa)
Low (standard ESP)
al
(Pa) (mmH2O)
13
(mmH2O)
(mmH2O)
14 15 (mmH2O)
NOTES
NOTES
1 2
The remote control can be used to switch between high and low. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and high ESP via the remote control.
1 2
The remote control can be used to switch between high and low. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and high ESP via the remote control.
FXDQ63NB
3D046301C
(mmH2O) 7 6 5 4 3 2 1
(Pa) 70 60 50
(mmH2O) 7 6 5 4 3 2 1
40 30 20
rnal
10
Low (standard ESP)
(mmH2O)
(Pa) 11 12
13
19
(mmH2O)
NOTES
1 2
The remote control can be used to switch between high and low. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and high ESP via the remote control.
12
Fan characteristics
1
9
13