Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

1
ats eim cne nUEt oVs BCry N oS - mo Q idVD nRl X IVFS

Specifications
TECHNICAL SPECIFICATIONS
Cooling Heating Cooling Heating Cooling Heating Material Unit Height Width Depth mm mm mm kg Nr of Rows Fin Pitch Face Area mm m 200 900 620 27 3 1.5 0.176 12 10.5 9.5 8.5 44 15 62 kW kW kW kW kW kW
FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE

1-1

Capacity

4.5 5.0 0.160 0.147 0.182 0.168

5.6 6.3 0.165 0.152 0.185 0.170 Galvanised steel plate 200 900 620 28 3 1.5 0.176 12 Sirocco fan 12.5 11.0 10.0 44 15 130 Direct drive

7.1 8.0 0.181 0.168 0.192 0.179 200 1,100 620 31 3 1.5 0.227 12 16.5 14.5 13.0 44 15 130

1
1

Power Input (50Hz) Power Input (60Hz) Casing Dimensions

Weight Heat Exchanger

Unit Dimensions

Nr of Stages Fan Air Flow Rate Type Cooling High high m/min High Low Fan External static pressure Motor High Standard Output (high) Drive Cooling Sound Pressure Liquid (OD) Gas Drain Air Filter Refrigerant control Temperature control Safety devices Standard Accessories Standard Accessories High high dBA High Low Piping connections Type Diameter Type Diameter Diameter Sound absorbing insulation mm mm mm dBA dBA m/min m/min Pa Pa W

34 32 30 6.35 12.7

35 33 31 Flare connection 6.35 Flare connection 12.7 VP20 (I.D. 20/O.D. 26) Foamed polyethylene Removable/washable/Mildew proof Electronic expansion valve Microprocessor thermostat for cooling and heating Fuse Fan motor thermal protector Operation manual Installation manual Drain hose Sealing pads Clamps Washer Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air filter Product Quality Certificate

36 34 32 9.52 15.9

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

1
1-1
Notes

Specifications
TECHNICAL SPECIFICATIONS
FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE

Nominal cooling capacities are based on : indoor temperature : 27CDB, 19CWB, outdoor temperature : 35CDB, equivalent refrigerant piping : 7,5m (horizontal) Nominal heating capacities are based on : indoor temperature : 20CDB, outdoor temperature : 7CDB, 6CWB, equivalent refrigerant piping : 7.5m (horizontal) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. External static pressure is changeable to set by the remote control; this pressure means : high static pressure standard static pressure. The operation sound levels are conversion values in anechoic chamber. In practice, sound levels tend to be higher than the specified values due to ambient noise or reflection. When the suction place is changed to bottom suction, sound level will increase

3 1
1

1-2 ELECTRICAL SPECIFICATIONS (50HZ)


Power Supply Name Phase Frequency Voltage Current Minimum circuit amps (MCA) Full load amps (FLA) Voltage range Notes Minimum Maximum Hz V A

FXDQ40NBVE

FXDQ50NBVE

FXDQ63NBVE

VE 1~ 50 1.0 15 0.8 50 220-240 1.0 15 0.8 -10% +10% Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA is smaller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse, use a circuit breaker 1.1 15 0.9 50

Maximum fuse amps (MFA) A A V V

1-3 ELECTRICAL SPECIFICATIONS (60HZ)


Power Supply Name Phase Frequency Voltage Current Minimum circuit amps (MCA) Full load amps (FLA) Voltage range Notes Minimum Maximum Hz V A

FXDQ40NBVE

FXDQ50NBVE

FXDQ63NBVE

VE 1~ 60 220 1.1 15 0.9 60 220 1.3 15 1.0 -10% +10% Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits. Maximum allowable voltage range variation between phases is 2%. MCA/MFA : MCA = 1.25 x FLA MFA is smaller than or equal to 4 x FLA Next lower standard fuse rating minimum 15A Select wire size based on the MCA Instead of a fuse, use a circuit breaker 60 220 1.4 15 1.1

Maximum fuse amps (MFA) A A V V

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

Safety device settings

FXDQ20,25,32PB FXDQ40,50,63NB

1
2

Kit name PC boad (A1P) fuse Fan motor thermal protector

FXDQ20PB

FXDQ25PB

FXDQ32PB 250V 5A

FXDQ40NB

FXDQ50NB

FXDQ63NB

OFF: 250V 5A 5C OFF ON: 83 15C ON

4D060926

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

Options

FXDQ20,25,32PB FXDQ40,50,63NB Individual control systems


Kit name Wired remote control Infrared remote control H/P C/O FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE FXDQ40NBVE FXDQ50NBVE BRC1D52 BRC4C65 BRC4C66 BRC2C51 BRC3A61 FXDQ63NBVE

3 1
3

Simplified remote control Remote control for hotel use

Centralized control system


Kit name Central remote control Unified on/off control Schedule timer FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE FXDQ40NBVE FXDQ50NBVE DCS302CA51 DCS301BA51 DST301BA51 FXDQ63NBVE

Other options
Kit name Adapter for wiring Wiring adapter for electrical appendices (1) Wiring adapter for electrical appendices (2) Remote sensor Installation box for adapter PCB. Electrical box with earth terminal 2 blocks 3 blocks FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE FXDQ40NBVE FXDQ50NBVE KRP1B56 KRP2A53 KRP4A54 KRCS01-1B KBP1BA101 KJB212AA KJB311AA DST301BA51 FXDQ63NBVE

Noise filter (for electromagnetic interface use only) External control adapter for outdoor unit (must be installed on indoor units) Insulation kit for high humidity KDT25N32

DTA104A53 KDT25N50 KDT25N63

4D060939

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

4
4-1

Capacity tables
Cooling capacity tables
TC: Total capacity;kW SHC: Sensible capacity;kW Indoor air temperature 19.0WB 27.0DB TC SHC 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 4.5 3.3 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 5.6 4.0 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9 7.1 4.9

FXDQ40,50,63NB

1
4

Unit size 40

50

63

Outdoor Nominal air temp. capacity CDB 4.5 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 5.6 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0 7.1 10.0 12.0 14.0 16.0 18.0 20.0 21.0 23.0 25.0 27.0 29.0 31.0 33.0 35.0 37.0 39.0

14.0WB 20.0DB TC SHC 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.0 2.5 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 3.8 3.1 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8 4.8 3.8

16.0WB 23.0DB TC SHC 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 3.6 2.8 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 4.5 3.5 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3 5.7 4.3

18.0WB 26.0DB TC SHC 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 4.2 3.3 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 5.2 3.9 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8 6.6 4.8

20.0WB 28.0DB TC SHC 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.8 3.2 4.7 3.2 4.7 3.2 4.6 3.2 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 6.0 4.0 5.9 4.0 5.8 4.0 5.7 3.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.6 4.9 7.5 4.8 7.4 4.8 7.2 4.7

22.0WB 30.0DB TC SHC 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.4 3.3 5.3 3.3 5.2 3.3 5.2 3.2 5.1 3.2 5.0 3.2 4.9 3.2 4.9 3.1 4.8 3.1 4.7 3.1 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.7 4.2 6.6 4.2 6.5 4.1 6.4 4.1 6.3 4.0 6.2 4.0 6.1 4.0 6.0 3.9 5.9 3.9 5.8 3.9 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.5 5.1 8.4 5.1 8.3 5.0 8.1 5.0 8.0 4.9 7.9 4.9 7.8 4.8 7.7 4.8 7.5 4.7 7.4 4.7

24.0WB 32.0DB TC SHC 5.9 3.5 5.8 3.5 5.8 3.5 5.7 3.5 5.6 3.4 5.5 3.4 5.5 3.4 5.4 3.3 5.3 3.3 5.3 3.3 5.2 3.3 5.1 3.2 5.0 3.2 5.0 3.2 4.9 3.1 4.8 3.1 7.4 4.1 7.3 4.1 7.2 4.1 7.1 4.0 7.0 4.0 6.9 4.0 6.8 4.0 6.7 3.9 6.6 3.9 6.6 3.9 6.5 3.8 6.4 3.8 6.3 3.8 6.2 3.7 6.1 3.7 6.0 3.7 9.3 5.7 9.2 5.6 9.1 5.5 9.0 5.4 8.8 5.4 8.7 5.3 8.7 5.3 8.5 5.2 8.4 5.1 8.3 5.1 8.2 5.0 8.1 4.9 7.9 4.9 7.8 4.8 7.7 4.8 7.6 4.7 ED39226A

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

4
4-2

Capacity tables
Heating capacity tables
Outdoor air temperature CDB CWB -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 -19.8 -20.0 -18.8 -19.0 -16.7 -17.0 -14.7 -15.0 -12.6 -13.0 -10.5 -11.0 -9.5 -10.0 -8.5 -9.1 -7.0 -7.6 -5.0 -5.6 -3.0 -3.7 0.0 -0.7 3.0 2.2 5.0 4.1 7.0 6.0 9.0 7.9 11.0 9.8 13.0 11.8 15.0 13.7 Indoor air temperature CDB 20.0 21.0 kW kW 2.9 2.9 3.0 3.0 3.2 3.2 3.4 3.4 3.6 3.5 3.7 3.7 3.8 3.8 3.9 3.9 4.0 4.0 4.2 4.2 4.4 4.4 4.6 4.6 4.9 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 5.0 4.8 3.7 3.7 3.8 3.8 4.0 4.0 4.3 4.2 4.5 4.5 4.7 4.7 4.8 4.8 4.9 4.9 5.1 5.1 5.3 5.3 5.5 5.5 5.8 5.8 6.2 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 6.3 6.1 4.7 4.7 4.8 4.8 5.1 5.1 5.4 5.4 5.7 5.7 6.0 6.0 6.1 6.1 6.2 6.2 6.4 6.4 6.7 6.7 7.0 7.0 7.4 7.4 7.8 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7 8.0 7.7

FXDQ40,50,63NB

3
16.0 kW 3.0 3.0 3.2 3.4 3.6 3.7 3.8 3.9 4.0 4.2 4.4 4.7 4.9 5.1 5.2 5.4 5.6 5.6 5.6 3.7 3.8 4.1 4.3 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.9 6.2 6.4 6.6 6.8 7.0 7.1 7.1 4.7 4.9 5.1 5.4 5.7 6.0 6.1 6.3 6.5 6.8 7.0 7.5 7.9 8.1 8.4 8.7 8.9 9.0 9.0 18.0 kW 2.9 3.0 3.2 3.4 3.6 3.7 3.8 3.9 4.0 4.2 4.4 4.6 4.9 5.1 5.2 5.3 5.3 5.3 5.3 3.7 3.8 4.0 4.3 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.9 6.2 6.4 6.6 6.7 6.7 6.7 6.7 4.7 4.9 5.1 5.4 5.7 6.0 6.1 6.3 6.5 6.7 7.0 7.4 7.8 8.1 8.4 8.5 8.5 8.5 8.5 22.0 kW 2.9 3.0 3.2 3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.4 4.6 4.7 4.7 4.7 4.7 4.7 4.7 4.7 3.7 3.8 4.0 4.2 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.8 5.9 5.9 5.9 5.9 5.9 5.9 5.9 4.7 4.8 5.1 5.4 5.7 6.0 6.1 6.2 6.4 6.7 7.0 7.4 7.5 7.5 7.5 7.5 7.5 7.5 7.5 24.0 kW 2.9 3.0 3.2 3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4 3.7 3.8 4.0 4.2 4.5 4.7 4.8 4.9 5.1 5.3 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 4.7 4.8 5.1 5.4 5.7 5.9 6.1 6.2 6.4 6.7 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 7.0 ED39226A

Unit Size 40

Nominal capacity 5.0

1
4

50

6.3

63

8.0

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

5
5-1

Dimensional drawing & centre of gravity


Dimensional drawing

FXDQ40,50NB

500 (Suspension bolt pitch)

20 or more

20 or more

620

20 or more

300 or more (Service space of installation box for adaptor PCB)

900

300 or more (Service space) 50 or more

620

Ceiling A (Service space)

(All around) 22 - 4.7 hole 8 x P100 = 800 940 (Suspension bolt pitch) Suspension bolt 4 - M8 ~ M10
12.5 21 57.5

60

Adjustable (0~600)

90

880 860 4 x P150 = 600

130 90
47 90

63

550

300 or less

Allow view A Inspection door (Ceiling opening) 20-M5 Holes (All around)
50 20 10

50 170

200 170 153 80

100

300

900

300

18 - M4 Holes (All around)

30 33

23

280 330

150 100 90 80

7 x P100 = 700 780 800 820 (In case of back-suction)

20 - M5 Holes (All around)


200 180 160 100

7 x P100 = 700 780 800 820 (In case of bottom-suction)

130 100 90 80

Nr 1 2 3 4 5 6 7 8 9 10 11

Part name Liquid pipe connection port Gas pipe connection port Drain pipe connection port Drain hose (Accessory) Control box Transmission wiring connection Power supply connection Suspension bracket Inspection door Socket for drain Air filter (Accessory)

Description 6.4 Flare connection 12.7 Flare connection IVP20 (O.D. 26 / I.D. 20) I.D. 25 (Outlet)

NOTES

2 3

In case of back-suction, mount chamber cover to bottom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. Location of units name plate: control box cover. Mount the air filter at the suction side. (Select its color (gravity method) 50% or more). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D045494B

FXDQ63NB
300 or more (Service space of installation box for adaptor PCB) 1100 300 or more (Service space)
20 or more

10 20 50

620

50 or more

500 (Suspension bolt pitch)

20 or more

20 or more

620

Ceiling A (All around) 26 - 4.7 hole 10 x P100 = 1000 1140 (Suspension bolt pitch) Suspension bolt 4 - M8 ~ M10
12.5 21 57.5 60

(Service space)
300

1080 1060 6 x P150 = 900

130
47 90

63

550

300 or less

Adjustable (0~600)

20-M5 Holes (All around)

200 170 153 80

100

50 170

18 - M4 Holes (All around)

30 33

23

280 330

150 100 90 80

9 x P100 = 900 980 1000 1020 (In case of back-suction)

20 - M5 Holes (All around)


200 180 160 100

9 x P100 = 900 980 1000 1020 (In case of bottom-suction)

130 100 90 80

Nr 1 2 3 4 5 6 7 8 9 10 11

Part name Liquid pipe connection port Gas pipe connection port Drain pipe connection port Drain hose (Accessory) Control box Transmission wiring connection Power supply connection Suspension bracket Inspection door Socket for drain Air filter (Accessory)

Description 6.4 Flare connection 12.7 Flare connection VP20 (O.D. 26 / I.D. 20) I.D. 25 (Outlet)

NOTES

2 3

In case of back-suction, mount chamber cover to bottom side of the unit. In case of bottom-suction, mount chamber cover to back side of the unit. Location of units name plate: control box cover. Mount the air filter at the suction side. (Select its color (gravity method) 50% or more). It can not be equipped with air filter (accessory) when connecting duct to suction side. 3D045496C

10 20 50

VRV Systems Indoor Units

100 160 180

50 20 10

Allow view A Inspection door (Ceiling opening)

900

300

100 160 180

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

5
5-2

Dimensional drawing & centre of gravity


Centre of gravity

FXDQ40,50NB

3 1
5

4D043886J

FXDQ63NB

4D043887H

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

Piping diagram

FXDQ20,25,32PB FXDQ40,50,63NB

1
6

Gas side

Liquid side

Electronic expansion valve

Filter

Filter

Fan

Indoor heat exchanger

4D060927

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

7
7-1

Wiring diagram
Wiring diagram

FXDQ20,25,32PB FXDQ40,50,63NB

3 1
7

POWER SUPPLY
Note: 3 Input from outside Note: 1 Transmission wiring central remote control

Wired remote control

Control box
A1P C1 F1U HAP KPR M1F M1P Q1M Printed circuit board Capacitor (M1F) Fuse (F5A, 250V) Light emitting diode (service monitor-green) Magnetic relay (M1P) Motor (indoor fan) Motor (drain pump) Thermal protector (M1F embedded) R1T R2T R3T S1L T1R V1TR X1M X2M Y1E Thermistor (air) Thermistor (coil - 1) Thermistor (coil - 2) Float switch Transformer (220V/22V) Phase control circuit Terminal block Terminal block Electronic expansion valve Z1CZ2C R1T SS1 X16A X18A Noise filter (ferrite core) Wired remote control Thermistor (air) Selector switch (main/sub) Connector for optional parts Connector (adapter for wiring) Connector (wiring adapter for electrical appendices)

: Terminal
,

Colors:

BLK: BLU: GRY: GRN:

Black Blue Gray Green

ORG: PNK: PRP: RED:

Orange Pink Purple Red

WHT: YLW:

White Yellow

: Connector : Field wiring

3D060547
NOTES

1 2 3

In case of using central remote control, connect it to the unit in accordance with the attached installation manual. Remote control model varies according to the combination system, confirm enineering materials and catalogs, etc. before connecting. When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control. In details, refer to the installation manual attached to the unit.

VRV Systems Indoor Units

10

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

8
8-1

Sound data
Sound pressure spectrum
FXDQ50NB
Octave band sound pressure level dB(0dB=0.0002bar) Octave band sound pressure level dB(0dB=0.0002bar)

FXDQ40NB

1
8

Approximate threshold hearing for continuous noise

Approximate threshold hearing for continuous noise

Octave band center frequency (Hz)

Octave band center frequency (Hz)

4D060948
NOTE NOTE

4D060949
Air flow rate H 33.0 39.0

1 2

3 4

Scale Over All (dB): HH (B, G, N is already rectified) A 34.0 C 39.0 Operating conditons: Power source: 220~240V 50Hz / 220V 60Hz Cooling: Return air temperature: 27C DB, 19C WB Outdoor temperature: 35C DB, 24 C WD Heating: Return air temperature: 20C DB, 15C WB Outdoor temperature: 7C DB, 6C WB Measuring place: Anechoic chamber Location of microphone
2m 1m Duct Suction Duct

Air flow rate H 32.0 38.0

L 30.0 37.0

1 2

3 4

Scale Over All (dB): HH (B, G, N is already rectified) A 35.0 C 40.0 Operating conditons: Power source: 220~240V 50Hz / 220V 60Hz Cooling: Return air temperature: 27C DB, 19C WB Outdoor temperature: 35C DB, 24 C WD Heating: Return air temperature: 20C DB, 15C WB Outdoor temperature: 7C DB, 6C WB Measuring place: Anechoic chamber Location of microphone
2m 1m Duct Suction Duct

L 31.0 38.0

Discharge

Discharge

1,5m

Microphone

1,5m

Microphone

The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.

The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.

FXDQ63NB
Octave band sound pressure level dB(0dB=0.0002bar)

Approximate threshold hearing for continuous noise

Octave band center frequency (Hz)

4D060950
NOTE

1 2

3 4

Scale Over All (dB): HH (B, G, N is already rectified) A 36.0 C 42.0 Operating conditons: Power source: 220~240V 50Hz / 220V 60Hz Cooling: Return air temperature: 27C DB, 19C WB Outdoor temperature: 35C DB, 24 C WD Heating: Return air temperature: 20C DB, 15C WB Outdoor temperature: 7C DB, 6C WB Measuring place: Anechoic chamber Location of microphone
2m 1m Duct Suction Duct

Air flow rate H 34.0 40.5

L 32.0 39.0

Discharge

1,5m

Microphone

The operation condition is external static pressure 15 Pa. Operation noise differ with operation and ambient conditions.

11

VRV Systems Indoor Units

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

Fan characteristics

FXDQ40NB

3D046299C

FXDQ50NB

3D046300C

3 1
9

(mmH2O) 6

(Pa) 60

(mmH2O) 6

(mmH2O) 7 6 5

(Pa) 70 60 50
Up sta per limit (hightic pressu of extern ESP) re al

(mmH2O) 7 6 5 4
tern al

Up sta per lim (hightic press it of exte ESP) ure rnal

50

High (high ESP)

External static pressure

4
4
High (standard ESP)

Low (high ESP)

External static pressure

40

High (high ESP)

40 30

30
l rna

3
3

High (standard ESP)

20

te f ex it o re r limpressu ESP) e p Up tatic dard s tan (s

2
2 20

U s ppe (sta tatic p r limit nda res of rd sure ext ESP ern a )

e it of er lim sure Low tic presP) sta h ES (hig

al xtern

x of e mit e er li ssur Lowatic preSP) st igh E (h

3 2

10
Low (standard ESP)

al it of extern Lower lim sure static pres ESP) (standard

10 (Pa)
Low (standard ESP)

Low (high ESP)

extern Lower limit of static pressure) (standard ESP

al

(Pa) (mmH2O)

9 10 11 12 Air flow rate (m3/min)

13

(mmH2O)

(mmH2O)

10 11 12 13 Air flow rate (m3/min)

14 15 (mmH2O)

NOTES

NOTES

1 2

The remote control can be used to switch between high and low. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and high ESP via the remote control.

1 2

The remote control can be used to switch between high and low. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and high ESP via the remote control.

FXDQ63NB

3D046301C

(mmH2O) 7 6 5 4 3 2 1

(Pa) 70 60 50

(mmH2O) 7 6 5 4 3 2 1

Up sta per li (hig tic pre mit of h ES ssur exte P) e rnal

External static pressure

High (high ESP)

40 30 20

High (standard ESP)


nal xter of e limit ssure Low r e ) Upp tic pre rd ESP (high ESP) sta anda (st
Lower limit of exte static pressure (standard ESP) rnal

te of e x r limit re Lowetic pressu sta h ESP) (hig

rnal

10
Low (standard ESP)

(mmH2O)

(Pa) 11 12

13

14 15 16 17 18 Air flow rate (m3/min)

19

(mmH2O)

NOTES

1 2

The remote control can be used to switch between high and low. The air flow is set to standard before leaving the factory. It is possible to switch between standard ESP and high ESP via the remote control.

VRV Systems Indoor Units

12

Indoor Units SLIM CONCEALED CEILING UNIT FXDQ-NBVE

Fan characteristics

1
9

13

VRV Systems Indoor Units