SIEYUAN
ap * Ip * Ca / Rp (1+ 3 * hx / hr)
3/8*(H+D+D1)
941.760 kN 0.4*1*588.6*0.7 164.81 kN V 1*0.4*1/3*(1+3*1.85/1.85)*588.6 313.920 kN 313.920 kN 4.75*3/8 1.781 m From Top 313.92*1.78125 559.17 kN.m So Earthquake is critical H L B h d L1 w c1 4.75 6.20 5.750 5.185 0.455 380 5.75 0.60 1.735 0.91 0.91*9.81*3.281^2 96.0 1.5 18 1 0.685 0.1 m m m m m mm m m m t/ft2 kN/m2 m kN/cum m m m
Geometry data
Height of Transformer Length of Transformer Transformer Foundation Length Transformer Foundation Width Assume thickness of Foundation Pad Supporting Wall Length Supporting Wall Width C/C Wheel Distance
Soil data
Allowable B.Capacity of soil
Depth of foundation Unit wt of backfill Foundation above NSL Foundation above Y.L Lean Concrete
D D1
IESCO
SIEYUAN
Volumes
Volume of Supporting Wall 5.75*0.6*(1.5-0.455+1-0.1)*2 13.421 m^3 5.75*0.6*(0.685)*2 4.727 1.15*0.3*0.3*4 0.311 5.75*5.185*(1.5-0.455-0.1+1) 57.988 m^3 57.98774375-13.4205 44.257 m^3 0.455*5.75*5.185 13.570 m^3 0.1*5.75*5.185 2.98 23.5*(13.4205+4.7265) 426.45 kN 0.3105*23.5 7.30 kN 23.5*(13.57+2.98) 388.93 kN 44.25674375*18 796.62 kN 588.60 kN 588.6+796.62+388.93+7.3+426.45 2207.90 kN
Volume of Tie Beam Dry volume Backfill Net Volume of Backfill Volume of raft Volume of Lean
Weights
Wt of Supporting Wall Wt. of Tie Beam Wt of raft Backfill Wt. Transformer Weight Total Compression on raft 60ton
Eccentricity
Eccentricity e B/6 559.17/2207.9 0.253 m 5.185/6 0.864 m e<B/6 5.185/2-0.253 2.340 m 5.185^2/6*5.75 25.76 m^3/m 2207.9/5.75/5.185+559.17/25.76 95.77 <96 kN/m2
Bearing Pressure
a Section modulus Max pressure induced at base Sx
Overturning
Destabilizing moment Total Wt. without Backfilling Stabilizing moment Fos against overturning Fos reqd against overturning MD/Mr MD Vr Mr F.OS 95.770 kN.m/m 426.45+7.3+388.93 822.68 kN 822.68*5.185/2 2365.210 kN.m/m 2365.21/95.77 24.697 1.50 Ok
IESCO
SIEYUAN
Structural Design
Max pressure at base due to dead load Max pressure at base due to Earthquake Factored Pressure Moment arm Factored Total moment R=Mu/(b*d^2) Steel ratio Min steel ratio Steel ratio used Area of steel reqd Bar size Area of bar Bar spacing reqd Use Provide Longitudinal/temperature/shrinkage Steel Provide Minimum steel ratio Area of steel reqd min b H Bar size Area of bar Bar spacing reqd qu*l2/2 P/B M/Sx q1+1.6*q2 q1 q2 qu l 2207.9/5.75/5.185 74.060 kN/m2 559.17/25.76 21.710 kN/m2 0.9*74.06+1.6*21.71 101.390 kN/m2 5.75/2-1.735/2-0.6/2 1.708 m 101.39*1.7075^2/2 147.80 kN-m/m 1.02 0.0043 0.0020 0.0043 1956.500 mm2/m 20 mm 284.000 mm2 145.16 mm/m 145 mm c/c #20@145mm c/c
0.002 0.002*1000*0.455*1000 910 mm2/m 13 mm 129 mm2 142 mm/m #13@142mm c/c 0.0030 1800.000 20 284.000 157.00 #20@157mm c/c 0.0020 1200.000 13 129.000 215.00 #13@215mm c/c
Wall reinforcement
Minimum Vertical Steel ratio used for wall Area of steel reqd Bar size Area of bar Bar spacing reqd Provide Minimum Horizontal Steel ratio used for wall Area of steel reqd Bar size Area of bar Bar spacing reqd Provide mm2 mm mm2 m on each face
NTDC
NESPAK
1.2 Table 16-H Ce*Cq*qs*Iw 0.76*1.2*1216/1000*1.15 1.280 kN/m2 8.000 m 1.28*8*8/2 40.960 kN.m
ap * Ip * Ca / Rp (1+ 3 * hx / hr)
3/8*H
1294.920 kN 0.22*1*1471.5*0.7 226.61 kN V 1*0.22*1/3*(1+3*0.6/0.6)*1471.5 431.640 kN 431.640 kN 8*3/8 1.500 m From Top 431.64*1.5 647.46 kN.m So Earthquake is critical H L B h d L1 w c1 8.00 6.20 6.75 6.75 0.45 375 5.33 0.60 1.76 0.71 0.71*9.81*3.281^2 75.0 1 18 0.6 0.2 0.1 m m m m m mm m m m t/ft2 kN/m2 m kN/cum m m m
Geometry data
Height of Transformer Length of Transformer Transformer Foundation Length Transformer Foundation Width Assume thickness of Foundation Pad Supporting Wall Length Supporting Wall Width C/C Wheel Distance
Soil data
Allowable B.Capacity of soil
Depth of foundation Unit wt. of backfill Foundation above NSL Foundation above Y.L Lean Concrete
ABB
4 of 16
NETRACON Technology
NTDC
NESPAK
Volumes
Volume of Supporting Wall Volume of Tie Beam Dry volume Backfill Net Volume of Backfill Volume of raft 5.33*0.6*(1-0.45+0.6-0.1)*2 6.716 m^3 1.15*0.3*0.3*3 0.311 6.75*6.75*(1-0.45-0.1-0.2+0.6) 38.728 m^3 38.728125-6.7158 31.702 m^3 0.45*6.75*6.75 20.503 m^3 6.7158*23.5 157.82 kN 0.3105*23.5 7.30 kN 20.503125*23.5 481.82 kN 31.701825*18 570.63 kN 1471.50 kN 1471.5+570.63+481.82+7.3+157.82 2689.07 kN
Weights
Wt. of Supporting Wall Wt. of Tie Beam Wt. of raft Backfill Wt. Transformer Weight Total Compression on raft 150ton
Eccentricity
Eccentricity e B/6 647.46/2689.07 0.241 m 6.75/6 1.125 m e<B/6 6.75/2-0.241 3.134 m 6.75^2/6*6.75 51.26 m^3/m 2689.07/6.75/6.75+647.46/51.26 71.66 <75 kN/m2
Bearing Pressure
a Section modulus Max pressure induced at base Sx
Overturning
Destabilizing moment Total Wt. without Backfilling Stabilizing moment Fos against overturning Fos reqd against overturning MD/Mr MD Vr Mr F.OS 71.660 kN.m/m 157.82+7.3+481.82 646.94 kN 646.94*6.75/2 2183.420 kN.m/m 2183.42/71.66 30.469 1.50 Ok
ABB
5 of 16
NETRACON Technology
NTDC
NESPAK
Structural Design
Max pressure at base due to dead load Max pressure at base due to Earthquake Factored Pressure Moment arm Factored Total moment a assumed Area of steel reqd a Area of steel reqd Bar size Area of bar Bar spacing reqd Longitudinal/temperature/shrinkage Steel Provide Minimum steel ratio Area of steel reqd min b H Bar size Area of bar Bar spacing reqd qu*l /2
2
q1 q2 qu l
As = M*1000000/(0.9*fy*(d-a/2)) a = As*fy/(.85*fc'*b)
2689.07/6.75/6.75 59.020 kN/m2 647.46/51.26 12.630 kN/m2 0.9*59.02+1.6*12.63 73.330 kN/m2 6.75/2-1.76/2-0.6/2 2.195 m 73.33*2.195^2/2 176.65 kN-m/m 32.60 176.65*1000000/0.9/420/(375-32.6/2) 1365 mm2/m 1365*420/0.85/1000/21 32.12 mm 1,365 mm2/m 16 mm 200 mm2 147 mm/m
0.0018 0.0018*1000*0.45*1000 810 mm2/m 13 mm 129 mm2 160 mm/m #13@160mm c/c 0.0030 1800.000 mm2 13 mm 129.000 mm2 on each face Twice alternate as shown 286.00 in drawings #13@286mm c/c 0.0020 1200.000 mm2 13 mm 129.000 mm2 215.00 mm on each Face #13@215mm c/c
Wall reinforcement
Minimum Vertical Steel ratio used for wall Area of steel reqd Bar size Area of bar
Bar spacing reqd Provide Minimum Horizontal Steel ratio used for wall Area of steel reqd Bar size Area of bar Bar spacing reqd Provide
ABB
6 of 16
NETRACON Technology
NTDC
NESPAK
H =
t1 d1 =
0.325 285 1.28*10.35 13.25 kN for unit strip 21.2 kN for unit strip 0.75 x 1/6 ( 21) x 1000 x 285/1000 163.3 kN OK 10.35 9.45 0.90 0.325 0.325*1000-40 285 6.20 4.00 0.45 0.45*1000-75 375 m m m m mm m m m mm mm
Geometry data
Height of Fire wall Height of Fire wall at Y.L Hight of Fire wall below Y.L Thickness of Wall H1+H2 H H1 H2 t1 d1 L1 B h d
Length of Wall Fire wall Foundation Width Assume thickness of Foundation Pad
7 of 16
NETRACON Technology
NTDC
NESPAK
Concrete data
fc' fy Concrete cover for foundation Concrete cover for Wall Unit wt of concrete
Volumes
Dry Volume of wall above Y.L Dry Volume of wall below Y.L Total Dry volume of Wall Volume of raft h*B t1*H1 t1*H2 = = = 0.325*9.45 3.071 0.325*0.9 0.293 0.2925+3.07125 3.364 0.45*4 1.800 m^3/m
Dry volume of Backfill Net Volume of Backfill Weights Dry Wt of wall Wt of raft Dry Wt of backfill Total weight of fdn+backfill Weight of mounting Post Insulator Weight of mounting tublor busbar Total Compression on raft
H1*B
= =
0.9*4 3.600 m^3/m 3.6-0.2925 3.308 m^3/m 3.36375*23.5 79.048 1.8*23.5 42.300 3.3075*18 59.535 59.535+42.3+79.048125 180.883 1.200 3.800 180.883125+1.2+3.8 185.883
P P e B/6
Eccentricity
Eccentricity 68.6/185.883125 0.370 m 4/6 0.667 m e<L/6 4/2-0.37 1.630 m 4^2/6 2.667 m^3/m 185.883125/4+68.6/2.667 72.19 kN/m2/m 72.19 <75 kN/m2
Bearing Pressure
a Section modulus Max pressure induced at base B/2-e B^2/6 a Sx
8 of 16
NETRACON Technology
NTDC
NESPAK
Sliding
Total sliding shear Resistance against sliding Fos against sliding Fos reqd against sliding V*H (Wt. of Wall & Foundation) Vr/Vs Vs Vr
Structural Design
Max pressure at base due to dead load Max pressure at base due to Wind Load Total Factore Presuure Moment arm Pad reinforcement Transverse/Main steel Factored Total moment Mu due to Self load & wind a assumed Area of steel reqd a Area of steel reqd Bar size Area of bar Bar spacing reqd Provided Longitudnal/temperature/shrinkage Steel Provide Minimum steel ratio Area of steel reqd min b H Bar size Area of bar Bar spacing reqd P/B M/Sx 0.9* q 1+1.6*q2 q1 q2 185.883125/4 46.48 68.6/2.667 25.73 0.9*46.48+1.6*25.73 75.281 4/2-0.325/2 1.838 kN/m2-m kN/m2-m kN/m2-m m
As = M*1000000/(0.9*fy*(d-a/2)) a = As*fy/(.85*fc'*b)
75.281*1.8375^2/2 127.09 kN-m/m 21.75 127.09*1000000/0.9/420/(375-21.75/2) 924 mm2/m 924*420/0.85/21/1000 21.75 mm 924 mm2/m 16 mm 200 mm2 200/924*1000 217 mm/m #16@217mm c/c
9 of 16
NETRACON Technology
NTDC
NESPAK
As = M*1000000/(0.9*fy*(d-a/2)) a = As*fy/(.85*fc'*b)
min b H
M Mn
68.600 kN-m 1000*420*285/1000/1000 119.70 kN-m M/Mn = 68.6/119.7 0.57 A Fire Rating 3 Hour has been adopted as per Section 705.4, of International Building Code 2000. Using group F-1 a concrete Cover 40mm has been adapted. An overcapacity has been provided under the guidance of determining the Fire Endurance of concrete elements, ACI 216R-81, Using the graph 2.1.2.1 for carbonate concrete and reinforcing bars, with u=40mm the fire rating of 3 Hours, M/Mn shoud be 0.65. So M/Mn is 0.57, which is less than M/Mn required= .65. The design therefore, qualifies for a fire rating at least 3 hrs. As*fy*d
10 of 16
NETRACON Technology
NTDC
NESPAK
Geometry data
Height of Transformer Length of Transformer Transformer Foundation Width Transformer Foundation Length Assume thickness of Foundation Pad Supporting Wall Length Supporting Wall Width C/C Wheel Distance hn B L t l w c1 8.00 6.20 6.50 6.50 0.45 5.33 0.60 1.76 m m m m m m m m
Soil data
Allowable B.Capacity of soil Depth of foundation Unit wt of backfill Foundation above NSL Lean Concrete d 0.71 75.0 1 18 0.3 0.2 21 420 60 23.50 8.000 41.885 62.011 62.011 t/ft2 kN/m2 m kN/cum m m Mpa Mpa mm kN/m2 m kN.m/m kN.m/m kN.m/m
Concrete data
fc' fy Concrete cover Unit wt of concrete
Moments
Height of Transformer Moment dt Transverse wind Moment dt Transverse wind & soil Pressure at Top of Footing Pad Net Moment at base So Earthquake is critical
ABB
11 of 16
NETRACON Technology
NTDC
NESPAK
Weights
Dry Wt of Supporting Wall Wt of raft Backfill Wt. Transformer Weight Total Compression on raft 97.699 446.794 571.592 1471.500 2587.584 kN kN kN kN kN
Eccentricity
Eccentricity e L/6 0.024 m 1.033 m e<L/6 3.226 45.771 73.967 74.000 m m^3/m kN/m2/m <75 kN/m2
Bearing Pressure
a Section modulus Max pressure induced at base
Overturning
Destabilizing moment Stabilizing moment Fos against overturning Fos reqd against overturning 73.967 kN.m/m 8409.649 kN.m/m 113.695 1.50 Ok 194.099 kN 544.493 kN 2.805 1.50
Sliding
Total sliding shear Resistance against sliding Fos against sliding Fos reqd against sliding
Structural Design
Overload factor Max pressure at base Moment arm Design M due to pressure Factored Total moment due to Self load & wind Steel ratio Min steel ratio Steel ratio used Area of steel reqd Bar size Area of bar Bar spacing reqd Use Provide 1.60 74.000 2.070 158.541 253.67 0.0020 0.0020 0.0020 900.000 16 200.000 222.22 222 #16@222mm c/c kN/m2 kN-m/m kN-m/m
ABB
12 of 16
NETRACON Technology
NTDC
NESPAK
Wall reinforcement
Minimum Vertical Steel ratio used for wall Area of steel reqd Bar size Area of bar Bar spacing reqd Provide Minimum Horizontal Steel ratio used for wall Area of steel reqd Bar size Area of bar Bar spacing reqd Provide 0.0030 1800.000 13 129.000 286.00 #13@286mm c/c 0.0020 1200.000 16 200.000 166.00 #16@166mm c/c mm2 mm mm2 on each face
mm2 mm mm2
ABB
13 of 16
NETRACON Technology
NTDC
NESPAK
Geometry data
Height of Fire wall Height of Fire wall at Y.L Hight of Fire wall below Y.L Thickness of Wall Length of Wall Fire wall Foundation Width Assume thickness of Foundation Pad hn h1 h2 t1 L1 B t2 10.20 9.50 0.70 0.30 6.20 3.70 0.45 m m m m m m m
Soil data
Allowable B.Capacity of soil Depth of foundation Unit wt of backfill 0.71 75.00 1 18 T/ft2 kN/m2 m 3 kN/m
Concrete data
fc' fy Concrete cover Unit wt of concrete 21 300 60 23.50 Mpa Mpa mm kN/m2
Moments
Height of wall above Y.L Moment dt Transverse wind & soil Pressure at Y.L Moment dt Transverse wind & soil Pressure at Top of Footing Pad Net Moment at base So Wind load is critical 9.500 59.064 72.499 72.500 m kN.m/m kN.m/m kN.m/m
14 of 16
NETRACON Technology
NTDC
NESPAK
Eccentricity
Eccentricity e L/6 0.465 m 0.617 m e<L/6 1.385 2.282 73.904 74.000 m m^3/m kN/m2/m <75 kN/m2
Bearing Pressure
a Section modulus Max pressure induced at base
Overturning
Destabilizing moment Stabilizing moment Fos against overturning Fos reqd against overturning 72.500 kN.m/m 288.373 kN.m/m 3.978 1.50 Ok 12.435 kN/m 111.038 kN/m 8.930 1.50 Ok 806.045 kN 826.582 kN Thickness is Ok
Sliding
Total sliding shear Resistance against sliding Fos against sliding Fos reqd against sliding
Structural Design
Overload factor Max pressure at base Moment arm Pad reinforcement Design M due to pressure Factored Total moment Mu due to Self load & wind Steel ratio Min steel ratio Steel ratio used Area of steel reqd Bar size Area of bar Bar spacing reqd Provide 1.60 74.000 kN/m2 1.700 106.930 171.09 0.0018 0.0020 0.0020 900.000 16 200.000 222.00 #16@222mm c/c kN-m/m kN-m/m
15 of 16
NETRACON Technology
NTDC
NESPAK
16 of 16
NETRACON Technology