EASUN REYROLLE

The new era in overcurrent protection

EASUN REYROLLE
ARGUS PROTECTION
Wide range of IDMTL curves and DTL Three independent high set/low set characteristics Sensitive/restricted earth fault Delayed or instantaneous reset Low AC and DC burdens True RMS measurement

EASUN REYROLLE
ARGUS PROTECTION
Circuit breaker fail protection Trip circuit supervision Full communications to IEC 60870-5-103 Self supervision/monitoring features Combined 1A and 5A current inputs

EASUN REYROLLE
Harmonics Normal Reyrolle Protection With Harmonics

Reduced Sampling

EASUN REYROLLE
Characteristics-more than just IDMTL!

Time

Low set setting

IDMTL current setting

Highset setting (1)

Highset setting (2)

Current

EASUN REYROLLE
Improved grading margin - more than just IDMTL

EASUN REYROLLE Control features-more than just IDMTL


7 user programmable output contacts (expandable to 11) Output contacts can be self, hand or electrically reset 1 user programmable status input (expandable to 9) Operation in conjunction with an auto reclose controller Remote alteration of relays settings and configurations Remote control of circuit breakers

EASUN REYROLLE Applications-more than just IDMTL


Blocking schemes for faster clearance Busbar zone schemes for low cost busbar protection Delayed reset for flashing / pecking faults I summation for circuit breaker condition monitoring / maintenance Status inputs can be time lagged for pick-up and/or drop-off

EASUN REYROLLE
Flashing fault condition

EASUN REYROLLE

BUSZONE BLOCKING
BLOCKING
RELAY 4 LS TRIP DELAY>50ms

F1

F2

TRIP

RELAY 1 IDMTL TRIP

RELAY 2

RELAY 3

BLOCKING F1 - BUSBAR FAULT, RELAY 4 LOWSET TRIPS F2:- FEEDER FAULT, RELAY 1 STARTER INHIBITS RELAY 4 LOWSET

EASUN REYROLLE

BLOCKINGBLOCKING-FASTER FAULT CLEARANCE


FAULT

TRIP RELAY 1 RELAY 2 RELAY 1

BLOCKING

ALL RELAYS SET TO TRIP WITH A LOWSET TIME DELAY OF >50ms RELAY 1 LOWSET INHIBITED BY FAST STARTER OUTPUT OF RELAY 2 IDMTL CHARACTERISTICS PROVIDE A SLOWER BACK-UP PROTECTION

EASUN REYROLLE
Circuit breaker fail protection

Protection algorithm operated

Typical setting 1.5 - 2 x C.B. operating time

&
Trip output relays operated

DTL 1 0.01 - 20 s

DTL 2 0.01 - 20s

R1

R7

Output relay matrix

EASUN REYROLLE
Trip circuit supervision
+ve Fuse Trip contacts 52a S /T coil link - ve

External resistor

52a

Rho status input (50V)

52b

C.B.

R1

R7
External resistor = 2K7 ohms for 110V DC supply If the trip circuit is not healthy the relay LCD displays TRIP CCT FAIL

Output relay matrix

EASUN REYROLLE
Instrumentation and conditioning monitoring - more than just IDMTL
Ammeter displays showing primary or relay current magnitudes in each pole Indication of the condition of status inputs and output relays Trip count Summation of I values at the time of trip Starter pick-up/drop-off indication Time and date

EASUN REYROLLE
Instrumentation and condition monitoring
Primary Current Secondary Current
16 characters

A = 233.4 C = 234.0 a = 00.53 c = 00.53

B = 235.6 E = 000.7 b = 00.53 e = 00.00

Output Relays Trip Counter I2 Summation

Relay Status 1101010 No. of Operations 0023 Sum of I2 023178 (MA) 2

EASUN REYROLLE
The Argus fault recorder
Fault triggers data storage

Five fault records available from relay facia


04/25 14:26:38 Trip AE
Press > for more detailed scrolling fault data display

500 event records available over comms link

Five waveform records available over comms link

95/04/27 14:26:38.247 Pole A HIS Trip

Fault 0 <<< fault data >>>

EASUN REYROLLE

The new era in overcurrent protection

EASUN REYROLLE Directional Argus relay


All features of standard Argus range Bi-directional elements having separately settable forward and reverse criteria Built-in two stage circuit breaker fail logic Trip circuit supervision All five status inputs have associated timers which can be the lag pick-up or time lag drop-off Eleven user programmable output relays

EASUN REYROLLE
Argus 2

CA - 90 Reverse operating zone Forward operating zone

CA - 180

Characteristic angle

CA - 90

EASUN REYROLLE
Characteristics
Reverse Zone Lagging Boundary CA + 90 Forward Zone Leading Boundary

MTA

Timing Characteristic
Reverse Zone Leading Boundary Forward Zone Lagging Boundary

CA - 90

Operate Characteristic

EASUN REYROLLE
ARGUS FAMILY OF RELAYS
Argus 2 - Directional overcurrent and earth fault with bi-directional elements Argus 3/4 - Integrated overcurrent, earth fault & autoreclose 4 shot autoreclose fully programmable with different sequences for phase fault, earth fault and from an external signal Argus 5/6 - Directional overcurrent and earth fault with autoreclose Argus 7 - Check synchronising relay with independent settings for check and system synchronising, dead line/bus switching and manual close guard feature Argus 8 - Under/over voltage relay

EASUN REYROLLE

EASUN REYROLLE
Key Features

Check and system synchronising relay for 50Hz or 60Hz systems Independent phase angle, slip frequency and slip timer settings Independent under voltage blocking and differential voltage blocking Split system detection with split timer Options for dead line and/or dead bus charging Integrated manual close guard function Line & bus voltage trimming

EASUN REYROLLE
Settings Check & system synchronising Phase angle 5 to 90 in 0.1 steps Slip frequency OFF, 0.020 to 2.000Hz in 0.005Hz steps Slip timer 0 to 100.0 seconds in 0.1 second steps

Voltage blocking Line & bus undervoltage OFF, 22 to 132V in 0.5V steps Differential voltage OFF, 0.5 to 44V in 0.5V steps

EASUN REYROLLE
Settings System split

OFF, 90 to 175 in 1 steps


Split timer 0 to 100.0 seconds in 0.1 second steps

Synchronising bypass Dead line & live bus, live line & dead bus, dead line & dead dead line or dead bus, dead line exclusive or dead bus bus,

Independent settings for line and bus, dead and live voltage levels Dead voltage 5 to 127V in 0.5V steps Live voltage 10 to 132V in 0.5V steps

EASUN REYROLLE
Check Sync Limits System Sync Limits 1

00
Nominal Voltage Live Volts VRunning Rotating Vectors VIncoming

Dead Volts

System Sync : Closure is allowed only on reducing phase angle difference

1800
System Split

EASUN REYROLLE
Close guard feature Prevents an operator from initiating a manual circuit breaker close before the check synchronising relay operates Removes the need for additional relays e.g. B66

EASUN REYROLLE
Control features 63.5 or 110Vac nominal voltage inputs 4 status inputs with pick-up/drop-off timers 7 user programmable output relays Output contacts can be self, hand or electrically reset 2 power supply ranges: 18 to 60Vdc 88 to 280Vdc, 110Vac

EASUN REYROLLE
Monitoring LED indications for: Protection healthy In synchronism (check or system) System split LCD display for local setting and monitoring Default settings for continuous display of instrumentation

EASUN REYROLLE
Monitoring Displays : Mode of operation Primary voltage Secondary voltage Line and bus frequency Phase angle and slip Line and bus status (live or dead) Voltage blocking Output relay and input status General alarms Waveform records and events stored Date and time

Mode = Chck & Sys LL LB: SysSync

VLINE = 11.212KV VBUS = 10.987KV

Phase = Slip =

47.3 0.04Hz

EASUN REYROLLE
Monitoring Event records Stores last 500 events with time and date stamping Available over the communications Waveform records 5 records of 1.5 seconds Records line and bus voltages Triggered by close output signal or status input

EASUN REYROLLE

EASUN REYROLLE
Argus 8 features
One, two or three phase measurement with 4 independent voltage elements, each of which can be set as either under or over voltage and set for either 1 or all pole operation Negative phase sequence overvoltage with 2 settings Neutral voltage displacement with 2 settings 4 independent frequency elements, each of which can be set as either under or overfrequency (AG8- 200 series only) Independent definite time delays for each element

EASUN REYROLLE
Argus 8 product variants
AG8-101 to 103 - 2 pole device that may be configured for single phase under/overvoltage with direct neutral voltage displacement or 2 phasephase under/overvoltage with negative sequence overvoltage AG8-104 to 112 - 3 pole device that may be configured as three phase under/overvoltage, with negative sequence overvoltage and neutral voltage displacement, both values being established by analysis of the 3 phase inputs. Alternatively these relays may be configured as 2, phase-phase under/ overvoltagepoles and the third pole used for direct measurement of neutral displacement voltage

EASUN REYROLLE
Argus 8 product variants
AG8-201 to 203 - as 101 to 103 with single or 2 phase under/overfrequency AG8-204 to 212 - as 104 to 112 with 2 or 3 phase under/overfrequency

EASUN REYROLLE
Control features
63.5 or 110Vac nominal voltage inputs 2 pole relay has 4 status inputs with pick-up/drop-off timers and 7 user programmable output relays 3 pole relay has 1 status input, expandable to 5 or 9 and 7 or 11 user programmable output relays Output contacts can be self, hand or electrically reset 2 power supply ranges: 18 to 60Vdc 88 to 280Vdc, 110Vac

EASUN REYROLLE
Monitoring
LED indications for: Protection healthy Starter Trip LCD display for local setting and monitoring Default settings for continuous display of instrumentation

EASUN REYROLLE
Monitoring
Displays: Primary voltage Secondary voltage Negative sequence voltage Neutral voltage displacement Frequency Output relay and input status General alarms Waveform records and events stored Date and time Starter

EASUN REYROLLE
Monitoring
Event records Stores last 500 events with time and date stamping Available over the communications

Waveform records 5 records of 1 seconds Records line and bus voltages Triggered by close output signal or status input

EASUN REYROLLE
Monitoring

EASUN REYROLLE Communications

Communications to IEC870-5-103 Fibre optic with SMA connectors May be connected in a loop with 254 relays Fibre optic hub available for star configuration

EASUN REYROLLE Communications


Master / SCADA/ DCS

Ring configuration
IEC 870-5-103 communications

Sigma 3 Fibre optic to electric interface

Optical fibre loop


ARGUS
1
PROTECTION HEALTHY

ARGUS 1

OHMEGA ARGUS 2
PROTECTION HEALTHY

PROTECTION HEALTHY

ARGUS 2

PROTECTION HEALTHY

I>Is

TRIP I>Is TRIP I>Is T RIP I>Is T RIP

EASUN REYROLLE

Star configuration

Master / SCADA/ DCS

Sigma 1 Fibre optic hub


IEC 60870-5-103 protocol

ARGUS 1

PROTECTION HEALTHY

ARGUS
1
PROTECTION HEALTHY

ARGUS 2

PROTECTION HEALTHY

ARGUS 2

OHMEGA
PROTECTION HEALTHY

I>Is

TRIP I>Is TRIP I>Is T RIP I>Is T RIP

EASUN REYROLLE
NUMERICAL OVER CURRENT PROTECTION
MIT OVER CURRENT PROTECTION
PROTECTION HEALTHY

STARTER

TRIP

MIT 114
EASUN REYROLLE INDIA

MIT

EASUN REYROLLE
COMPACT IN SIZE (150mmx150mm) TRUE RMS MEASUREMENT SELF MONITORING (Watch Dog) SIX DIFFERENT CHARACTERISTICS (SI3, SI1, VI, EI, LTI,DTL) WIDE CURRENT SETTING(5 to 250% insteps of 5%)

EASUN REYROLLE
TIME MULTIPLIER SETTING insteps of 0.025 SELECTABLE RESET DELAY (0 to 60 Sec) READABLE MAN MACHINE INTERFACE SINGLE RELAY FOR 1A/5A RATINGS WIDE AUXILIARY SUPPLY RANGE 40 - 280V DC / 110V AC TRANSIENT FREE HIGHSET (50 to 2500%) TRANSIENT OVERREACH < 5% UPTO X/R RATIO 100

EASUN REYROLLE

THREE POLE VERSION


TWO POLE PHASE FAULT OVERCURRENT + 1 EARTH FAULT OVERCURRENT

FOUR POLE VERSION


THREE POLE PHASE FAULT OVERCURRENT + 1 EARTH FAULT OVERCURRENT

SIX OPTIONAL RELAYS (PROTECTION HEALTHY, STARTER, PHASE FAULT IDMT, EARTH FAULT IDMT, PHASE FAULT HIGHSET, EARTHFAULT HIGHSET)