Technical Data
Capacidade Nominal: 4 a 10 TR - 60 Hz
Capacidad Nominal: 4 a 10 TR - 60 Hz
Nominal Capacity: 4 to 10 TR - 60 Hz
ndice
1 - NOMENCLATURA ................................................................................................................................................. 4
2 - PAINEL SOFT-TOUCH .......................................................................................................................................... 4
3 - CARACTERSTICAS TCNICAS GERAIS e DADOS FSICOS 60Hz ................................................................. 5
4 - DIMENSES DAS UNIDADES .............................................................................................................................. 6
4.1 - 30AJ 004 e 005 ............................................................................................................................................. 6
4.2 - 30AJ 010 ....................................................................................................................................................... 6
5 - DADOS ELTRICOS ............................................................................................................................................. 7
6 - DADOS DE PERFORMANCE ................................................................................................................................. 8
7 - CURVA DE PERDA DE CARGA - TROCADOR DE PLACAS ................................................................................. 9
7.1 - 30AJ 004 E 005 ............................................................................................................................................. 9
7.2 - 30AJ 010 ....................................................................................................................................................... 9
8 - CIRCUITO ELTRICO ......................................................................................................................................... 10
8.1 - Unidades 30AJ 220V .................................................................................................................................. 10
8.2 - Unidades 30AJ - 380V ................................................................................................................................ 12
9 - SEQNCIA DE TESTE ...................................................................................................................................... 14
10 - CONSIDERAES PARA PREVENO DOS TROCADORES DE CALOR ....................................................... 15
1. NOMENCLATURA
30
AJ
004
38
Resfriadores de pequena
capacidade com
condensao a ar
AJ Acqua Jnior
Reviso de projeto
Capacidade Nominal TR
004 = 3.76 TR
005 = 4.27 TR
010 = 9.50 TR
Opo S = Standard
Freqncia: 6 = 60 Hz
Voltagem:
22 = 220V
38 = 380V
2. PAINEL SOFT-TOUCH
1 Indicador de unidade ligada
2 Indicador de compressor em funcionamento
3 Indicador de temporizador antireciclo ativado
4 Indicador do protetor de congelamento ativado
5 Indicador de abertura do pressostato
6 Boto Ligar
7 Boto Desligar
8 Alimentao elctrica habilitada
004
3.76
005
010
4.27
9.50
220-380V / 3ph / 60Hz
24V / 1ph / 60Hz
1
1
1
1
1
1
R-22
3.6
3.0
6.9
115
130
250
Scroll
ZR47
ZR57
SM120
1
3600
Petrobrs CP32RH, Suniso 3GS
1.24
1.95
3.25
Trocador de Calor de placas de Ao Inox Soldado
B25x22
B25x22
V45x20
1
1
2.28
2.58
5.74
3.7
4.7
5.8
1
1
1 1/2
BSP
1/1
0.86
0.86
2.2
2
15
9.52
Gold Fin comTubos de Cobre Corrugados Internamente
6
6
10
Axial
3...660
6600
6600
11200
Motor Monofsico Tipo PSC
220V/ 1F/ 60Hz
850
850
880
1/6
1/6
1/2
NEMA48
6
Abre - 426/ Fecha - 320
Abre - 27/ Fecha - 67
4
NOTA: Para alimentao eltrica da unidade, deve ser colocado um interruptor termomagntico. Toda a instalao eltrica
dever cumprir com as normas eltricas locais. As unidades resfriadoras so para uso exclusivo de comforto. Sua aplicao
em industrias invalida a garantia.
Estas unidades s podem ser conectadas com as unidades correspondentes Fan Coil de marca Carrier. As unidades so
previstas com o uso de compressor Scroll. Estes compressores so sensveis ao sentido de giro. Um excessivo rudo ou
presses iguais indicam uma rotao inversa. Desconecte eltricamente a unidade e troque a sequncia de fases da
alimentao. O funcionamento com sentido de giro invertido invalida a garantia.
5
SENTIDO DO AR
SENTIDO DE GIRO
ENTRADA DE GUA
SENTIDO
DO AR
SADA DE GUA
ACESSO VLVULA DE
EXPENSO
SADA DE GUA
198
342
380/60
342
380/60
220/60
198
342
380/60
220/60
198
220/60
418
242
418
242
418
242
VENTILADOR
DADOS TCNICOS
Legenda
RLA
LRA
MOPA
KW
FP
KVAr
CIRCUITOA
19,8
33,1
8,2
17,2
7,2
14,3
5
0,42
SM120
59,6
124,0
0,76 2,5
4,2 0,87
ZR57
46,0
91,0
ZR47
2,2
2,2
1,3
1,3
1,3
1,3
1/6
1/6
1/6
1/6
0,75
0,75
0,123
0,123
0,123
0,123
22,0
35,3
9,5
18,5
8,5
15,6
11,5
11,5
5,1
5,1
4,3
4,3
40
50
25
25
16
25
MOPA[A]
RLA[A] LRA[A] KW FP KVAr QTDE RLA[A] P [CV] KWTOTAL RLATOTAL [A] KWTOTAL [W]
COMPRESSOR
DADOS TCNICOS
TENSO [ V ] / [Hz]
ALIMENTAO/ FREQUNCIA
Observaes Importantes
Dados obtidos do catlogo tcnico de compressores do Fornecedor
1 - Os valores de RLA, KW, FP, RLA TOTAL e KW TOTAL mostrados na tabela referem-se a dados nominais de operao da unidade em regime.
Temperatura de Suco: 45F (7.2C) / Temperatura de Condensao: 130F (54.4C) - Condio ARI.
2 - Os valores de MOPA mostrados na tabela foram calculados a partir dos valores mximos de operao da unidade.
3 - Os valores indicados na coluna KVAr so dimensionados para os compressores quando da necessidade de correo de fator de potncia para 0.92.
4 - Todos os compressores so do tipo Scroll seguido de sua capacidade.
10
05
04
UNIDADE
30AJ
5. DADOS ELTRICOS
Cap.
LWT
10 C
9C
8C
7C
6C
5C
LWT
25
CAP. Consumo Consumo Vazo no
Compressor Evaporador
kW
kW
kW
l/s
13.66 3.538
3.039
0.652
15.50 4.264
3.763
0.739
34.93 8.863
8.379
1.66
14.12 3.569
3.070
0.674
16.00 4.309
3.808
0.764
35.92 8.958
8.473
1.71
14.58 3.595
3.095
0.696
16.52 4.357
3.855
0.789
36.95 9.055
8.570
1.76
15.01 3.624
3.124
0.717
17.04 4.403
3.901
0.814
38.00 9.161
8.675
1.81
15.50 3.656
3.156
0.742
17.57 4.450
3.948
0.840
39.06 9.269
8.783
1.86
15.98 3.689
3.188
0.765
18.13 4.502
3.999
0.867
40.11 9.375
8.889
1.91
Capacidade de refrigerao
Temperatura de sada de gua
Tamanho
da
Unidade
30AJ
004
005
010
004
005
010
004
005
010
004
005
010
004
005
010
004
005
010
30
CAP. Consumo Consumo Vazo no
Compressor Evaporador
kW
kW
kW
l/s
13.10 3.856
3.364
0.624
14.88 4.607
4.114
0.709
33.45 9.462
8.983
1.59
13.53 3.887
3.396
0.646
15.23 4.656
4.163
0.733
34.38 9.553
9.075
1.64
13.97 3.917
3.425
0.667
15.87 4.707
4.213
0.758
35.36 9654
9.175
1.69
14.40 3.947
3.454
0.688
16.37 4.756
4.261
0.782
36.38 9.765
9.285
1.73
14.87 3.980
3.488
0.711
16.89 4.805
4.310
0.807
37.37 9.866
9.386
1.78
15.34 4.014
3.521
0.734
17.50 4.927
4.434
0.837
38.41 9.972
9.492
1.83
35
CAP. Consumo Consumo Vazo no
Compressor Evaporador
kW
kW
kW
l/s
12.48 4.190
3.707
0.595
14.20 4.958
4.473
0.677
31.90 10.092
9.620
1.52
13.01 4.205
3.721
0.621
14.66 5.007
4.521
0.700
32.77 10.175
9.702
1.56
13.34 4.258
3.774
0.637
15.16 5.062
4.576
0.724
33.71 10.273
9.800
1.61
13.76 4.290
3.806
0.658
15.64 5.111
4.625
0.748
34.70 10.386
9.913
1.66
14.22 4.327
3.843
0.680
16.13 5.163
4.676
0.771
35.62 10.481
10.007
1.70
14.66 4.361
3.876
0.701
16.68 5.224
4.737
0.798
36.60 10.590
10.115
1.75
40
CAP. Consumo Consumo Vazo no
Compressor Evaporador
kW
kW
kW
l/s
11.85 4.540
4.065
0.565
13.47 5.313
4.837
0.642
30.28 10.748
10.282
1.44
12.27 4.581
4.106
0.586
13.93 5.366
4.890
0.665
31.12 10.830
10.364
1.48
12.68 4.613
4.138
0.606
14.41 5.424
4.947
0.688
32.01 10.923
10.457
1.52
13.10 4.649
4.174
0.626
14.87 5.471
4.994
0.710
32.92 11.025
10.558
1.57
13.54 4.692
4.216
0.647
15.35 5.525
5.047
0.734
33.80 11.117
10.650
1.61
13.96 4.728
4.252
0.668
15.86 5.587
5.109
0.758
34.74 11.224
10.756
1.66
45
CAP. Consumo Consumo Vazo no
Compressor Evaporador
kW
kW
kW
l/s
11.20 4.911
4.446
0.534
12.71 5.684
5.217
0.606
28.62 11.459
11.001
1.36
11.61 4.954
4.489
0.554
13.16 5.740
5.273
0.628
29.41 11.534
11.075
1.40
11.99 4.988
4.523
0.573
13.60 5.792
5.325
0.649
30.25 11.622
11.163
1.44
12.40 5.029
4.563
0.593
14.04 5.843
5.376
0.671
31.10 11.716
11.257
1.48
12.83 5.073
4.607
0.594
14.51 5.895
5.427
0.694
31.93 11.801
11.342
1.52
13.24 5.111
4.645
0.633
14.99 5.958
5.489
0.717
32.82 11.908
11.448
1.57
6. DADOS DE PERFORMANCE
8. CIRCUITO ELTRICO
8.1 - Unidades 30AJ 220V
10
11
12
13
9. SEQNCIA DE TESTE
Se P1 e P2 forem pressionados nos primeiros 5 segundos
quando os indicadores estiverem ligados, sera iniciado um
teste, compondo 10 etapas.
Durante esta sequncia, as luzes L1, L2, L3 e L4 exibiro
o nmero da etapa dentro da sequncia, enquanto L5 dar
informaes referente a cada passo.
14
Bloqueio do sistema de bombas e segurana para fazer com que a mquina pare caso ocorra alguma
falha no sistema de circulao de gua.
Nas localizaes onde as temperatures chegam abaixo 0C, utilize Glycol para evacuar o sistema.
Uso da proporo adequada de Glycol quando operam a uma temperatura de sada de gua inferior a
4.5C.
Mnimo volume de gua no sistema: 12 l./ton. para aplicaes de ar condicionado e 24 l/ton. para
aplicaes de processos.
Deve-se evitar as seguintes solues: Cloro > 300mg/l, Sulfites livres de cloro, Solues com PH < 7.
O circuito de gua dever contar com um tanque de expanso ou algum dispositivo para evitar danos a
tubulao.
15
ndice
1 - NOMENCLATURA ............................................................................................................................................... 18
2 - PANEL SOFT-TOUCH .......................................................................................................................................... 18
3 - CARACTERSTICAS TCNICAS GENERALES y DATOS FISICOS 60Hz ........................................................ 19
4 - DIMENSIONES DE LA UNIDAD ........................................................................................................................... 20
4.1 - 30AJ 004 e 005 ........................................................................................................................................... 20
4.2 - 30AJ 010 ..................................................................................................................................................... 20
5 - DATOS ELCTRICOS ......................................................................................................................................... 21
6 - DATOS DE PERFORMANCE ............................................................................................................................... 22
7 - CADA DE PRESIN EN EL ENFRIADOR DE PLACAS ...................................................................................... 23
7.1 - 30AJ 004 E 005 ........................................................................................................................................... 23
7.2 - 30AJ 010 ..................................................................................................................................................... 23
8 - CIRCUITO ELCTRICO ....................................................................................................................................... 24
8.1 - 30AJ 220V ................................................................................................................................................... 24
8.2 - 30AJ - 380V ................................................................................................................................................. 26
9 - SECUENCIA DE PRUEBA ................................................................................................................................... 28
10 - CONSIDERACIONES PARA EL CUIDADO DE LOS INTERCAMBIADORES ..................................................... 29
1. NOMENCLATURA
30
AJ
004
38
Opcin S = Estndar
Frecuencia: 6 = 60 Hz
Tensin:
22 = 220V
38 = 380V
2. PANEL SOFT-TOUCH
1 Indicador de equipo encendido
2 Indicador de compresor en marcha
3 Indicador de temporizador antireciclo activado
4 Indicador de protector de congelamiento activado
5 Indicador de apertura de presostato
6 Pulsador de encendido
7 Pulsador de apagado
8 Indicador de alimentacin elctrica habilitada
18
4. DIMENSIONES DE LA UNIDAD
4.1 - 30AJ 004 e 005
SENTIDO DE AIRE
SENTIDO DE GIRO
ENTRADA DE AGUA
SENTIDO DE
AIRE
SALIDA DE AGUA
ACCSESO A VALV.
DE EXP.
Antes de colocar el equipo en el local verifique los siguientes aspectos (todos los modelos):
a) El piso debe soportar el peso de la unidad en operacin (Ver item 2- en Datos Fsicos). Consulte el proyecto
estructural del edificio o normas aplicables para la verificacin de la carga admisible. Instale refuerzos si es necesario.
b) Prever el suficiente espacio para servicios de mantenimiento. El frente del equipo debe permanecer libre para permitir
el flujo de aire y el acceso al interior de la unidad.
4.2 - 30AJ 010
SENTIDO DE AIRE
ENTRADA DE AGUA
SALIDA DE AGUA
Antes de colocar el equipo en el local verifique los siguientes aspectos (todos los modelos):
a) El piso debe soportar el peso de la unidad en operacin (Ver item 2- en Datos Fsicos). Consulte el proyecto
estructural del edificio o normas aplicables para la verificacin de la carga admisible. Instale refuerzos si es necesario.
b) Prever el suficiente espacio para servicios de mantenimiento. El frente del equipo debe permanecer libre para permitir
el flujo de aire y el acceso al interior de la unidad.
20
198
342
380/60
342
380/60
220/60
198
342
380/60
220/60
198
220/60
418
242
418
242
418
242
VENTILADOR
DATOS TECNICOS
Leyenda
RLA
LRA
MOPA
KW
FP
KVAr
CIRCUITOA
19,8
33,1
8,2
17,2
7,2
14,3
5
0,42
SM120
59,6
124,0
0,76 2,5
4,2 0,87
ZR57
46,0
91,0
ZR47
2,2
2,2
1,3
1,3
1,3
1,3
1/6
1/6
1/6
1/6
0,75
0,75
0,123
0,123
0,123
0,123
22,0
35,3
9,5
18,5
8,5
15,6
11,5
11,5
5,1
5,1
4,3
4,3
40
50
25
25
16
25
MOPA[A]
DATOSTECNICOS COMPLEMENTARIOS
RLA[A] LRA[A] KW FP KVAr Cantidad RLA[A] P [CV] KWTOTAL RLATOTAL [A] KWTOTAL [W]
COMPRESOR
DATOS TECNICOS
TENSIN [ V ] / [Hz]
ALIMENTACIN / FRECUENCIA
OBSERVACIONES IMPORTANTES:
Datos obtenidos del catlogo tcnico de compresores del proveedor.
1 -Los valores RLA, KW, FP, RLA TOTAL y KW TOTAL mostrados en la tabla se refieren a datos nominales de operacin de la unidad en rgimen.
Temperatura de succin: 45F (7.2C) / Temperatura de condensacin: 130F (54.4C) - Condicin ARI.
2 - Los valores de MOPA mostrados en la tabla fueron calculados a partir de los valores mximos de operacin de la unidad.
3 - Los valores indicados en la columna KVAr son dimensionados para los compresores cuando es necesaria correccin del Factor de Potencia para 0.92.
4 - Todos los compresores son del tipo Scroll.
10
05
04
UNIDAD
30AJ
5. DATOS ELCTRICOS
21
22
Cap.
LCWT
LWT Tamao
Unidad
30AJ
004
5C
005
010
004
6C
005
010
004
7C
005
010
004
8C
005
010
004
9C
005
010
004
10 C
005
010
kW
3.538
4.264
8.863
3.569
4.309
8.958
3.595
4.357
9.055
3.624
4.403
9.161
3.656
4.450
9.269
3.689
4.502
9.375
30
25
CAP. Potencia Potencia
Caudal
CAP.
Potencia
Caudal
Compresor Evaporador
Compresor Evaporador
kW
kW
kW
l/s
kW
kW
l/s
13.10 3.856
3.364
0.624
12.48
3.039
0.652
14.88 4.607
4.114
0.709
14.20
3.763
0.739
33.45 9.462
8.983
1.59
31.90
8.379
1.66
13.53 3.887
3.396
0.646
13.01
3.070
0.674
15.23 4.656
4.163
0.733
14.66
3.808
0.764
34.38 9.553
9.075
1.64
32.77
8.473
1.71
13.97 3.917
3.425
0.667
13.34
3.095
0.696
15.87 4.707
4.213
0.758
15.16
3.855
0.789
35.36 9654
9.175
1.69
33.71
8.570
1.76
14.40 3.947
3.454
0.688
13.76
3.124
0.717
16.37 4.756
4.261
0.782
15.64
3.901
0.814
36.38 9.765
9.285
1.73
34.70
8.675
1.81
14.87 3.980
3.488
0.711
14.22
3.156
0.742
16.89 4.805
4.310
0.807
16.13
3.948
0.840
37.37 9.866
9.386
1.78
35.62
8.783
1.86
15.34 4.014
3.521
0.734
14.66
3.188
0.765
17.50 4.927
4.434
0.837
16.68
3.999
0.867
38.41 9.972
9.492
1.83
36.60
8.889
1.91
Capacidad de enfriamiento
Temperatura de salida del agua
kW
13.66
15.50
34.93
14.12
16.00
35.92
14.58
16.52
36.95
15.01
17.04
38.00
15.50
17.57
39.06
15.98
18.13
40.11
CAP. Potencia
kW
4.190
4.958
10.092
4.205
5.007
10.175
4.258
5.062
10.273
4.290
5.111
10.386
4.327
5.163
10.481
4.361
5.224
10.590
Potencia
35
40
Potencia
Caudal
CAP. Potencia Potencia
Caudal CAP.
Compresor Evaporador
Compresor Evaporador
kW
l/s
kW
kW
kW
l/s
kW
3.707
0.595
11.85 4.540
4.065
0.565
11.20
4.473
0.677
13.47 5.313
4.837
0.642
12.71
9.620
1.52
30.28 10.748
10.282
1.44
28.62
3.721
0.621
12.27 4.581
4.106
0.586
11.61
4.521
0.700
13.93 5.366
4.890
0.665
13.16
9.702
1.56
31.12 10.830
10.364
1.48
29.41
3.774
0.637
12.68 4.613
4.138
0.606
11.99
4.576
0.724
14.41 5.424
4.947
0.688
13.60
9.800
1.61
32.01 10.923
10.457
1.52
30.25
3.806
0.658
13.10 4.649
4.174
0.626
12.40
4.625
0.748
14.87 5.471
4.994
0.710
14.04
9.913
1.66
32.92 11.025
10.558
1.57
31.10
3.843
0.680
13.54 4.692
4.216
0.647
12.83
4.676
0.771
15.35 5.525
5.047
0.734
14.51
10.007
1.70
33.80 11.117
10.650
1.61
31.93
3.876
0.701
13.96 4.728
4.252
0.668
13.24
4.737
0.798
15.86 5.587
5.109
0.758
14.99
10.115
1.75
34.74 11.224
10.756
1.66
32.82
kW
4.911
5.684
11.459
4.954
5.740
11.534
4.988
5.792
11.622
5.029
5.843
11.716
5.073
5.895
11.801
5.111
5.958
11.908
Potencia
45
Potencia
Caudal
Compresor Evaporador
kW
l/s
4.446
0.534
5.217
0.606
11.001
1.36
4.489
0.554
5.273
0.628
11.075
1.40
4.523
0.573
5.325
0.649
11.163
1.44
4.563
0.593
5.376
0.671
11.257
1.48
4.607
0.594
5.427
0.694
11.342
1.52
4.645
0.633
5.489
0.717
11.448
1.57
6. DATOS DE PERFORMANCE
DIAGRAMA ELCTRICO
24
AMR - AMARILLO
AZL - CELESTE
BRC - BLANCO
CNZ - GRIS
LRJ - NARANJA
MRM - MARRON
PRT - NEGRO
ROS - ROSA
VIO - VIOLETA
VRD - VERDE
VRM - ROJO
CODIFICACIONES DE
COLORES
8. CIRCUITO ELCTRICO
25
DIAGRAMA ELCTRICO
AMR - AMARILLO
AZL - CELESTE
BRC - BLANCO
CNZ - GRIS
LRJ - NARANJA
MRM - MARRON
PRT - NEGRO
ROS - ROSA
VIO - VIOLETA
VRD - VERDE
VRM - ROJO
CODIFICACIONES DE
COLORES
3,8A
DIAGRAMA ELCTRICO
26
AMR - AMARILLO
AZL - CELESTE
BRC - BLANCO
CNZ - GRIS
LRJ - NARANJA
MRM - MARRON
PRT - NEGRO
ROS - ROSA
VIO - VIOLETA
VRD - VERDE
VRM - ROJO
CODIFICACIONES DE
COLORES
27
IMPORTANTE:
OBSERVAR ESO,
EL NEUTRAL
DEBE ESTAR
ENCENDIDO EN L2.
DIAGRAMA ELCTRICO
AMR - AMARILLO
AZL - CELESTE
BRC - BLANCO
CNZ - GRIS
LRJ - NARANJA
MRM - MARRON
PRT - NEGRO
ROS - ROSA
VIO - VIOLETA
VRD - VERDE
VRM - ROJO
CODIFICACIONES DE
COLORES
9. SECUENCIA DE PRUEBA
Si durante los 5 segundos iniciales en que permanecen
encendidos todos los indicadores, se presionan
simultneamente P1 y P2, se pasa al estado de prueba que
consta de una secuencia de 10 pasos.
Durante esta secuencia, las luces indicadoras L1, L2, L3
y L4 sealaran el nmero de paso dentro de la secuencia,
mientras que L5 dar informacin relacionada con cada paso.
28
Realizacin del enclavamiento del sistema de bombeo y seguridades que provoque la detencin de la
mquina en el caso de algn inconveniente en el sistema de circulacin de agua.
En zonas donde la temperatura desciende por debajo de 0C, utilizar glicol o evacuar el sistema.
Utilizacin de la proporcin adecuada de glicol cuando operen a una temperatura de salida de agua
menor a 4,5C.
Volumen mnimo de agua en el sistema de 12lts./ton. en aplicaciones de aire acondicionado y
24lts./ton. en aplicaciones de proceso.
Instalacin de tanque acumulador en caso de no satisfacer los requerimientos mnimos de volmenes
de agua. (Consultar Manual Carrier de Aire Acondicionado, Tercera Parte).
Debern evitarse las soluciones: Cloruros > 300mg/l, Sulfitos libres de cloro, Soluciones con PH < 7.
El circuito de agua deber contar con un tanque de expansin o algn dispositivo para evitar los golpes
de ariete en la tubera.
No eliminar ningn elemento de proteccin de la unidad.
29
Contents
1 - NOMENCLATURE ................................................................................................................................................ 32
2 - PANEL SOFT-TOUCH .......................................................................................................................................... 32
3 - GENERAL TECHNIQUES CHARACTERISTICS and PHYSICAL DATA 60Hz ................................................... 33
4 - UNIT DIMENSIONS ............................................................................................................................................. 34
4.1 - 30AJ 004 e 005 ........................................................................................................................................... 34
4.2 - 30AJ 010 ..................................................................................................................................................... 34
5 - ELECTRICAL DATA ............................................................................................................................................. 35
6 - PERFORMANCE DATA ........................................................................................................................................ 36
7 - PRESSURE DROP IN THE PLATE EXCHANGER ............................................................................................... 37
7.1 - 30AJ 004 E 005 ........................................................................................................................................... 37
7.2 - 30AJ 010 ..................................................................................................................................................... 37
8 - ELECTRICAL CIRCUIT ........................................................................................................................................ 38
8.1 - 30AJ 220V ................................................................................................................................................... 38
8.2 - 30AJ - 380V ................................................................................................................................................. 40
9 - TEST SEQUENCE ............................................................................................................................................... 42
10 - CONSIDERATIONS ON THE EXCHANGERS CARE .......................................................................................... 43
1. NOMENCLATURE
30
AJ
004
38
Project Revision
Nominal Capacity TR
004 = 3.76 TR
005 = 4.27 TR
010 = 9.50 TR
Option S = Standard
Frequency: 6 = 60 Hz
Voltage:
22 = 220V
38 = 380V
2. PANEL SOFT-TOUCH
1 Machine in operation
2 Cut-off by thermostat
3 Machine stopped by timer
4 Cut-off alarm due to freezing temperature
5 Cut-off alarm due to protection
6 ON button
7 OFF button
8 Indication of energized machine (enabled)
32
004
3.76
005
010
4.27
9.50
220-380V / 3ph / 60Hz
24V / 1ph / 60Hz
1
1
1
1
1
1
R-22
3.6
3.0
6.9
115
130
250
Scroll
ZR47
ZR57
SM120
1
3600
Petrobrs CP32RH, Suniso 3GS
1.24
1.95
3.25
Blaze Plate Heat Exchange (Stain Steel)
B25x22
B25x22
V45x20
1
1
2.28
2.58
5.74
3.7
4.7
5.8
1
1
1 1/2
BSP
1/1
0.86
0.86
2.2
2
15
9.52
Gold Fin with cooper pipes corrugated internally
6
6
10
Axial
3...660
6600
6600
11200
Single-Phase Engine Type PSC
220V/ 1F/ 60Hz
850
850
880
1/6
1/6
1/2
NEMA48
6
Open - 426 / Close - 320
Open - 27 / Close - 67
4
NOTE: For the unit power supply, it is necessary to install a thermo-magnetic circuit breaker. All the electric installation shall
comply with the local electric regulations. The chillers are for comfort use only. Their use for industrial and/or process
applications make the warranty void.
These units can be connected only to their corresponding Carrier fan-coil units. The units are supplied with scroll compressors,
which are sensible to their rotation direction. Excessive noise or equalized pressures indicate a reverse rotation. Disconnect
the unit from the power supply, and change the supply phase sequence. The operation in reverse rotation makes the warranty
void.
33
4. UNIT DIMENSIONS
4.1 - 30AJ 004 e 005
AIR DIRECTION
ROTATION DIRECTION
WATER INLET
THREAD
AIR DIRECTION
WATER OUTLET
THREAD
ACCESS TO THE
EXPANSION VALVE
Before placing the unit on the site check the following items (all models):
a) The floor shall bear the weight of the unit in operation. (See item Physical Data). Refer to the structural project of the
building for the applicable regulations concerning the admissible load. If required, reinforce the structure.
b) Choose a location with space enough to allow repairs and general maintenance services. The front of the equipment
shall be free to allow the air flow and the access to the unit inside.
4.2 - 30AJ 010
AIR DIRECTION
WATER INLET
WATER OUTLET
2 THREADS
Before placing the unit on the site check the following items (all models):
a) The floor shall bear the weight of the unit in operation. (See item Physical Data). Refer to the structural project of the
building for the applicable regulations concerning the admissible load. If required, reinforce the structure.
b) Choose a location with space enough to allow repairs and general maintenance services. The front of the equipment
shall be free to allow the air flow and the access to the unit inside.
34
198
342
380/60
342
380/60
220/60
198
342
380/60
220/60
198
220/60
MIN.
418
242
418
242
418
242
MAX.
TECHNICAL DATA
FAN
Legends
RLA
LRA
MOPA
KW
FP
KVAr
CIRCUIT A
19,8
33,1
8,2
17,2
7,2
14,3
5
0,42
SM120
59,6
124,0
0,76 2,5
4,2 0,87
ZR57
46,0
91,0
ZR47
2,2
2,2
1,3
1,3
1,3
1,3
1/6
1/6
1/6
1/6
0,75
0,75
0,123
0,123
0,123
0,123
22,0
35,3
9,5
18,5
8,5
15,6
11,5
11,5
5,1
5,1
4,3
4,3
40
50
25
25
16
25
MOPA[A]
COMPLEMENTARYTECHNICAL DATA
RLA[A] LRA[A] KW FP KVAr Quant. RLA[A] P [CV] KWTOTAL RLATOTAL [A] KWTOTAL [W]
TECHNICALDATA
POWERSUPPLY/ FREQUENCY
NOMINAL
COMPRESSOR
VOLTAGE [ V ] / [HZ]
IMPORTANT NOTES
Data from the supplier's technical catalog.
1 - RLA, KW, RLA TOTAL and KW TOTAL refer to nominal operation data with the unit in operation.
Suction temperature: 45F (7.2C) / Condensation temperature: 130F (54.4C) - ARI conditions.
2 - MOPA values shown in the table were calculated taking into consideration the maximum operation values of the unit.
3 - Values show in the KVAr column be dimensioned to the compressors when is necessary to correct the POWER FACTOR to 0.92.
4 - All compressors are Scroll.
10
05
04
30AJ
UNIT
5. ELECTRICAL DATA
35
36
Cap.
LCWT
10 C
9C
8C
7C
6C
5C
LWT
kW
13.66
15.50
34.93
14.12
16.00
35.92
14.58
16.52
36.95
15.01
17.04
38.00
15.50
17.57
39.06
15.98
18.13
40.11
30AJ
004
005
010
004
005
010
004
005
010
004
005
010
004
005
010
004
005
010
25
30
35
40
45
kW
3.538
4.264
8.863
3.569
4.309
8.958
3.595
4.357
9.055
3.624
4.403
9.161
3.656
4.450
9.269
3.689
4.502
9.375
kW
3.856
4.607
9.462
3.887
4.656
9.553
3.917
4.707
9654
3.947
4.756
9.765
3.980
4.805
9.866
4.014
4.927
9.972
kW
4.190
4.958
10.092
4.205
5.007
10.175
4.258
5.062
10.273
4.290
5.111
10.386
4.327
5.163
10.481
4.361
5.224
10.590
kW
4.540
5.313
10.748
4.581
5.366
10.830
4.613
5.424
10.923
4.649
5.471
11.025
4.692
5.525
11.117
4.728
5.587
11.224
kW
11.20
12.71
28.62
11.61
13.16
29.41
11.99
13.60
30.25
12.40
14.04
31.10
12.83
14.51
31.93
13.24
14.99
32.82
kW
4.911
5.684
11.459
4.954
5.740
11.534
4.988
5.792
11.622
5.029
5.843
11.716
5.073
5.895
11.801
5.111
5.958
11.908
Consumption Consumption Evaporator CAP. Consumption Consumption Evaporator CAP. Consumption Consumption Evaporator CAP. Consumption Consumption Evaporator CAP. Consumption Consumption Evaporator
Cooling capacity
Leaving water temperature
CAP.
Unit
Size
6. PERFORMANCE DATA
ELECTRICAL DIAGRAM
38
AMR - YELLOW
AZL - BLUE
BRC - WHITE
CNZ - GRAY
LRJ - ORANGE
MRM - BROWN
PRT - BLACK
ROS - PINK
VIO - VIOLET
VRD - GREEN
VRM - RED
COLORS CODIFICATION
LEGEND:
BC - CONTROL TERMINAL BLOCK
LPS - LOW PRESSURE SWITCH
BF - POWER TERMINAL BLOCK
PC - DISPLAY (IHM)
COMP - COMPRESSOR
PLC - ELECTRONIC BOARD
CAP - CAPACITOR
TR - TRANSFORMER
CB - PUMP CONTACT
OFM - OUTDOOR FAN MOTOR
CC - COMPRESSOR CONTACTOR
VS - VALVE SOLENOID
CH - CRANCKASE HEATER
RT1 - LIVING WATER TEMPERATURE SENSOR
F - FUSE
RT2 - ENTERING WATER TEMPERATURE SENSOR
FS - FLOW SWITCH
PA - SET POINT TEMPERATURE ADJUST
HPS - HIGH PRESSURE SWITCH
* - ACESSORY
ICD - REMOTE SWITCH
-- -- -- CONNECT MADE IN FIELD
C - COMMON TERMINAL
BS - SENSOR TERMINAL BLOCK
PTC - COMPRESSOR TERMIC PROTECTOR (ONLY IN SOME MODELS)
3 - IF THE UNIT TURN OFF BY SOME REASON, THEN THE LED N3 WILL BE ILUMINATED INDICATING
THAT THIS UNIT WILL TURN ON IN THE NEXT 4 MINUTES, 30 SEC, BEFORE THE FINISHING OF THE
MINUTES, THE LED N3 WILL BEGIN BLINK ANNOUCING THE CONCLUSION OF TIMER.
1 - CONNECT ELECTRICAL BRIDGE BETWEEN TERMINALS 5 AND IN4, IF WANT TO WORK IN LOW
TEMPERATURE (7C).
NOTES:
8. ELECTRICAL CIRCUIT
39
ELECTRICAL DIAGRAM
AMR - YELLOW
AZL - BLUE
BRC - WHITE
CNZ - GRAY
LRJ - ORANGE
MRM - BROWN
PRT - BLACK
ROS - PINK
VIO - VIOLET
VRD - GREEN
VRM - RED
COLORS CODIFICATION
LEGEND:
BC - CONTROL TERMINAL BLOCK
LPS - LOW PRESSURE SWITCH
BF - POWER TERMINAL BLOCK
PC - DISPLAY (IHM)
COMP - COMPRESSOR
PLC - ELECTRONIC BOARD
CAP - CAPACITOR
TR - TRANSFORMER
CB - PUMP CONTACT
OFM - OUTDOOR FAN MOTOR
CC - COMPRESSOR CONTACTOR
VS - VALVE SOLENOID
CH - CRANCKASE HEATER
RT1 - LIVING WATER TEMPERATURE SENSOR
F - FUSE
RT2 - ENTERING WATER TEMPERATURE SENSOR
FS - FLOW SWITCH
PA - SET POINT TEMPERATURE ADJUST
HPS - HIGH PRESSURE SWITCH
* - ACESSORY
ICD - REMOTE SWITCH
-- -- -- CONNECT MADE IN FIELD
C - COMMON TERMINAL
BS - SENSOR TERMINAL BLOCK
PTC - COMPRESSOR TERMIC PROTECTOR (ONLY IN SOME MODELS)
OFC - CONDENSER CONTACTOR
E1 - OVERLOAD RELAY (ADJUST 3,8A)
3 - IF THE UNIT TURN OFF BY SOME REASON, THEN THE LED N3 WILL BE ILUMINATED INDICATING
THAT THIS UNIT WILL TURN ON IN THE NEXT 4 MINUTES, 30 SEC, BEFORE THE FINISHING OF THE
MINUTES, THE LED N3 WILL BEGIN BLINK ANNOUCING THE CONCLUSION OF TIMER.
1 - CONNECT ELECTRICAL BRIDGE BETWEEN TERMINALS 5 AND IN4, IF WANT TO WORK IN LOW
TEMPERATURE (7C).
NOTES:
ELECTRICAL DIAGRAM
40
AMR - YELLOW
AZL - BLUE
BRC - WHITE
CNZ - GRAY
LRJ - ORANGE
MRM - BROWN
PRT - BLACK
ROS - PINK
VIO - VIOLET
VRD - GREEN
VRM - RED
COLORS CODIFICATION
LEGEND:
BC - CONTROL TERMINAL BLOCK
LPS - LOW PRESSURE SWITCH
BF - POWER TERMINAL BLOCK
PC - DISPLAY (IHM)
COMP - COMPRESSOR
PLC - ELECTRONIC BOARD
CAP - CAPACITOR
TR - TRANSFORMER
CB - PUMP CONTACT
OFM - OUTDOOR FAN MOTOR
CC - COMPRESSOR CONTACTOR
VS - VALVE SOLENOID
CH - CRANCKASE HEATER
RT1 - LIVING WATER TEMPERATURE SENSOR
F - FUSE
RT2 - ENTERING WATER TEMPERATURE SENSOR
FS - FLOW SWITCH
PA - SET POINT TEMPERATURE ADJUSTE
HPS - HIGH PRESSURE SWITCH
* - ACESSORY
ICD - REMOTE SWITCH
-- -- -- CONNECT MADE IN FIELD
C - COMMON TERMINAL
BS - SENSOR TERMINAL BLOCK
PTC - COMPRESSOR TERMIC PROTECTOR (ONLY IN SOME MODELS)
3 - IF THE UNIT TURN OFF BY SOME REASON, THEN THE LED N3 WILL BE ILUMINATED INDICATING
THAT THIS UNIT WILL TURN ON IN THE NEXT 4 MINUTES, 30 SEC, BEFORE THE FINISHING OF THE
MINUTES, THE LED N3 WILL BEGIN BLINK ANNOUCING THE CONCLUSION OF TIMER.
1 - CONNECT ELECTRICAL BRIDGE BETWEEN TERMINALS 5 AND IN4, IF WANT TO WORK IN LOW
TEMPERATURE (7C).
NOTES:
41
IMPORTANT:
TO LOOK THAT THE
NEUTRAL SHOULD BE
CONECTED IN L2.
ELECTRICAL DIAGRAM
AMR - YELLOW
AZL - BLUE
BRC - WHITE
CNZ - GRAY
LRJ - ORANGE
MRM - BROWN
PRT - BLACK
ROS - PINK
VIO - VIOLET
VRD - GREEN
VRM - RED
COLORS CODIFICATION
LEGEND:
BC - CONTROL TERMINAL BLOCK
LPS - LOW PRESSURE SWITCH
BF - POWER TERMINAL BLOCK
PC - DISPLAY (IHM)
COMP - COMPRESSOR
PLC - ELECTRONIC BOARD
CAP - CAPACITOR
TR - TRANSFORMER
CB - PUMP CONTACT
OFM - OUTDOOR FAN MOTOR
CC - COMPRESSOR CONTACTOR
VS - VALVE SOLENOID
CH - CRANCKASE HEATER
RT1 - LIVING WATER TEMPERATURE SENSOR
F - FUSE
RT2 - ENTERING WATER TEMPERATURE SENSOR
FS - FLOW SWITCH
PA - SET POINT TEMPERATURE ADJUST
HPS - HIGH PRESSURE SWITCH
* - ACESSORY
ICD - REMOTE SWITCH
-- -- -- CONNECT MADE IN FIELD
C - COMMON TERMINAL
BS - SENSOR TERMINAL BLOCK
PTC - COMPRESSOR TERMIC PROTECTOR (ONLY IN SOME MODELS)
OFC - CONDENSER CONTACTOR
E1 - OVERLOAD RELAY (ADJUST 2,2A)
3 - IF THE UNIT TURN OFF BY SOME REASON, THEN THE LED N3 WILL BE ILUMINATED INDICATING
THAT THIS UNIT WILL TURN ON IN THE NEXT 4 MINUTES, 30 SEC, BEFORE THE FINISHING OF THE
MINUTES, THE LED N3 WILL BEGIN BLINK ANNOUCING THE CONCLUSION OF TIMER.
1 - CONNECT ELECTRICAL BRIDGE BETWEEN TERMINALS 5 AND IN4, IF WANT TO WORK IN LOW
TEMPERATURE (7C).
NOTES:
9. TEST SEQUENCE
If P1 and P2 are pressed during the first 5 seconds when
the indicators are on, a test status will start, comprising 10
steps.
During this sequence, the lights L1, L2, L3 and L4 will
exhibit the number of the step within the sequence, while L5
will provide information related to each step.
42
Interlocking of the pump and safety systems to cause the machine to stop in case of any failure in the
water circulation system.
In locations where the temperatures decrease to below 0C, use glycol to evacuate the system.
Use of the proper rate of Glycol when operating at a leaving water temperature below 4.5C.
Minimum water volume in the system: 12 l./ton. for air conditioning applications and 24 l/ton. for process
applications.
Installation of an accumulator tank in case it does not meet the minimum requirements of water volumes
(Refer to Carrier Air Conditioning Manual, Third Part).
The solutions must be prevented: Chlorines > 300mg/l, Chlorine-free sulphite, solutions with PH < 7.
The water circuit shall count on an expansion tank or a device to prevent the pressure surges in the
piping.
Do not remove any protective device from the unit.
43
A critrio da fbrica, e tendo em vista o aperfeioamento do produto, as caractersticas daqui constantes podero ser alteradas a qualquer momento sem aviso prvio.
El fabricante se reserva lo derecho de descontinuar o cambiar las especificaciones a cualquier tiempo, sin aviso y sin incurrir en ningn tipo de obligacin.
Manufacturer reserves the right to discontinue or change at any time specifications without notice and without incurring obligations.