Beruflich Dokumente
Kultur Dokumente
Page 1 of 3
http://www.bellgossett.com/Press/techtk699a.htm
3/27/2003
Page 2 of 3
signifi-cantly greater horse-power than those close to the plant. Controls-Each zone operates independently and requires its own variable speed controls. It is not recommended to mix constant speed and variable speed zones in the same system. Balance-Balance is a critical factor in the design and operation of a zone-pumped system. If the system is not properly balanced, the return distribution pipe may be over-pressurized. Over-pressurization will compound the system problems. Valves can lift off their seats, resulting in hunting and poor temperature control. Primary-secondary- tertiary (tertiary) pumpingsystems-Another variation of primary-secondary pumping is tertiary pumping (Fig. 3). Secondary pumps distribute the chilled water from the central plant to the connected buildings or zones. Individual buildings or zones are decoupled from the distribution loop through a tertiary bridge. A major advantage of tertiary pumping is that the individual zones are hydraulically and thermally decoupled. This allows the designer some flexi-bility to control each zone independently, relative to differential pressure and temper-ature. Zones may be a collection of coils, air handlers, or entire buildings. This advantage is ultimately expressed in district cooling and heating systems where individual users are decoupled through the means of gasketed plate heat exchangers (GPX). When GPX are used, cross contamination of HVAC fluids may also be prevented.The operator of the distribution system is isolated from the users and is not subjected to potential excessive static pressure. Design considerations- The addition of tertiary pumps may increase the initial-connected horsepower of the system, but the level of control is increased. Under the right conditions, overall operating cost can be reduced. To optimize the performance of a tertiary-pumped system, control of the tertiary bridge modulating valve is critical. Tertiary bridge design-The same design criteria used for the secondary bridge should be followed (Fig. 4). Temperature sensor locationsProper valve control requires that temperature sensors are located at the supply water temperature to the tertiary zone, T1; return temperature to the chiller plant, T2 (a low-flow bypass is maintained across the return control valve to provide an accurate water temperature); and the supply water temper-ature from the chiller plant, T3. Proper control permits the zone to operate at the highest possible temperature without control in the zone. This maximizes the flow through each coil and control valve providing better heat transfer and valve authority. Maximizing the flow in the tertiary also reduces the amount of water from the secondary. This reduces the flow in the secondary and may result in the reduction of the number of chillers on-line in the chiller plant. Secondary pumps-Secondary pumps are selected for present flow to minimize initial horsepower. The pressure drop across the control valve of the highest head zone must be included. Consideration should be given for future flow conditions. Careful selection will permit the use of present flow pumps under future conditions. Since the secondary pumps are typically the largest pumps in the system, adjustable frequency drives and controls should be considered if economically justifiable. Tertiary pumps- Tertiary pumps are selected based on the flow and head require-ments for the zone or building load. These pumps are often low horsepower and do not need to be of variable speed unless it is economically justi-fiable. If variable speed is elected, differential pressure sensors are located across the largest, farthest load and two-way control valve. Consideration must also be given to low flow conditions. These are similar to the design parameters for primary-secondary pumping systems. Zones close to the chiller plant may operate under high distribution piping differential head. If the differential head is sufficient at all times, tertiary pumps may not be required for the nearby zones. Primary variable speed pumping systems-This type of system is not a variation of primary-secondary pumping. The concept behind primary variable speed pumping is the elimination of the secondary pumps to reduce first cost, space requirements, and maintenance (Fig.5). Constant volume is no longer maintained through the chillers. Variable system flow is directly achieved through the modulation of flow through the chillers. Primary variable speed pumping systems are especially attractive in primary-pumped retrofit situations since space may not be available for additional pumps and piping. Design considerations- Control logic and sequencing for the pumps and chillers is the heart of this type of system. With the advent of more sophisticated micropro-cessor controls, the potential problems associated with under-flowing or overflowing the chillers can be addressed. Operation of the variable speed pumps is also provided through the microprocessor control. Chillers -Multiple chillers are required to maximize the turndown capacity of the chilled water plant. With only one chiller, the low-flow range is limited to the minimum flow of the single chiller. Multiple chillers lower the minimum flow limitation. The designer must know the minimum flow requirements for each chiller. Chillers of the same size, efficiency, and manufacture simplify the control sequence.
http://www.bellgossett.com/Press/techtk699a.htm
3/27/2003
Page 3 of 3
Close coordination with the chiller manufacturer is highly recom-mended, especially in retrofit appli-cations. Common pipe-The common pipe is not eliminated in primary variable speed pumping. It is modified into a low-flow bypass. To ensure that minimum flow is always maintained through the chiller, a bypass with a modulating control valve is employed. As loads diminish, system flow reduces. When the system flow approaches the minimum flow requirement of the chiller, the modulating twoway valve in the bypass opens. The sum of the flow in the system plus the flow in the bypass must exceed the minimum flow requirement of the chillers. Flowmeters are installed in both the supply and the bypass to calculate the flow sequence. Primary pumps-Primary variable speed pumps are selected in a manner similar to secondary pumps in primary-secondary pumping systems. Pumps should be of equal size and designed for parallel operation. Pumps with differing flow and head characteristics do not work well together in parallel. Careful selection will permit the use of present flow pumps under future conditions. Differential pressure sensor locations-The principle method of pump control is differential pressure transmitters. As with other variable speed systems, the largest, farthest loads are usually the most critical to monitor. Sensors close to the chiller plant provide valuable information for minimizing system differential pressure during low flow conditions. Conclusion There are many ways modern HVAC systems can be pumped. Each method has its own advantages and disadvantages to the user or operator (Table 1). The designer must consider present system use, plans for the future, cost considerations, and the ability level of the operator. With more tools in the toolbox, the engineer is better equipped to make the decision, Which system is the best for my client? This article is an abridged version of a Fluid Handling Staff article that was originally published in the October, 1998 issue of HPAC magazine. Part I appeared in the January, 1999 issue of Tech Talk. 4
Reprinted from TechTalk June 1999 Copyright 1999 by ITT Industries Read Next TechTalk Article Return to the University Press Page Return to the Fluid Handling University Homepage
http://www.bellgossett.com/Press/techtk699a.htm
3/27/2003
Page 1 of 3
http://www.bellgossett.com/Press/techtk699b.htm
3/27/2003
Page 2 of 3
condensate drainage equal to the system condensing rate. Failure to provide complete condensate drainage will lead to poor temperature control and possible water hammer. Any lift in the condensate return piping after the trap discharge requires a positive pressure to develop in the heat exchanger shell to provide condensate drainage. For this to occur, condensate must back up in the heat exchanger shell until enough tube surface is covered by condensate to build a positive steam pressure. When the positive steam pressure develops to move the condensate through the steam trap and up the vertical return line, over heating can occur on the tube side of the heat exchanger due to the positive steam pressure remaining in the shell. This results in a wide range of outlet fluid temperatures from the heat exchanger. A lift in the return line as shown above should be avoided on heat exchangers using a modulating control valve. A lift or back pressure in the steam trap return piping can flood the heat exchanger shell and cause severe water hammer as steam enters the flooded shell. The resulting water hammer can damage the steam trap, the steam regulating valve, the heat exchanger tubes and cause the gasket in the heat exchanger and trap to fail. Trap Installation The trap should be located below the heat exchanger shell to allow free flow of condensate into the trap. A strainer complete with a screen blow down valve should be installed ahead of the steam trap. A shut off valve should be provided in the trap discharge return line to isolate the unit for service. Unions should be provided to allow trap service or replacement. The return line from the trap discharge should be pitched into a vented condensate return unit. Vacuum Breakers Most steam to water heat exchangers provide a tapping in the shell to allow installation of a vacuum breaker. The vacuum breaker allows air to enter the shell when an induced vacuum occurs. Failure to install a vacuum breaker will allow the heat exchanger shell to operate at a negative pressure which may cause condensate to be held up in the shell. During light load, the heat exchanger will have a layer of steam at the top and air under the steam to provide just the right amount of heat. The vacuum breaker should be mounted on a vertical pipe 6 to 10 above the topping to provide a cooling leg. This protects the vacuum breaker from dirt and extreme temperatures. Steam Regulator The choice of the temperature regulating valve includes self contained temperature regulators, pilot operated regulators and pneumatic regulators. The steam inlet pressure to the regulator must be higher than the required heat exchanger operating pressure to allow flow. The available steam pressure should be at least two times the heat exchanger operating pressure to provide modulation of the regulator for good temperature control. This will also provide the smallest size steam regulator. The steam regulator should be sized based on the maximum lb./hr. of steam required by the heat exchanger. To properly size the regulator, the available inlet steam pressure and the heat exchanger design operating pressure must be known. The steam regulator should not be oversized. Oversizing the regulator may cause the temperature to overshoot and the regulator will hunt more than a properly sized regulator. The steam regulator is normally smaller than the connecting inlet and outlet steam piping. Regulator InstallationA steam drip trap should be installed in the steam piping ahead of all steam regulating valves. Failure to install a drip trap will allow condensate to collect in the steam piping ahead of the regulator. As the regulator opens, the mix of condensate and steam passing through the regulator may cause water hammer that can destroy the diaphragms or bellows used to operate the regulator. A steam strainer should also be installed ahead of the regulators to prevent dirt from entering the valve. Dirt can deposit on the valve seat and not allow it to close tight. The steam strainer should be installed with the screen pocket horizontally. Installation with the screen down, as commonly piped for water service, will allow a condensate pocket to form in the steam line. This condensate pocket can carry into the main valve and cause water hammer or sluggish operation. Shut off valves, pressure gauges, a manual bypass and unions should be installed to allow proper servicing of the valves and strainers. When possible refer to the manufacturers installation manual for proper installation. The temperature sensing bulb should be installed as close as possible to the heat exchanger outlet. It is important that the full length of the temperature sensing bulb be inserted in the system piping. Any portion of the bulb installed in a no flow area will reduce the accuracy of temperature control. When the sensing bulb is installed in a separable well, heat transfer compound must be installed between the well and the sensing bulb to aid heat transfer. The tube side of the heat exchanger should have a continuous running recir-culation pump to provide continuous flow past the sensing bulb. A minimum 20% recirculation should be provided. Pilot operated regulators with a pressure pilot require a downstream pressure sensing line. The pressure sensing line connection should be connected in a non-turbulent area downstream of the main valve; a min-imum 10 pipe diameters downstream of the main valve is recommended. The steam pressure sensing connection can also be connected directly to the heat exchanger shell. Condensate Coolers When heat exchangers operate at high pressure, consideration should be given to the addition of a condensate cooler. The justification will depend on the size of the heat exchanger and the actual number of hours per day the unit will be in operation. With a condensate cooler, the discharge from the steam trap on the steam heat exchanger outlet is piped through a water-to-water heat exchanger. A second trap is then installed on the discharge of the water-to-water heat exchanger to maintain saturation pressure and prevent flashing and water hammer from occurring in the condensate cooler. A separate thermostatic trap is installed to allow direct air venting of the steam heat exchanger into the vented return line downstream of the condensate cooler. The water-to-water heat exchanger design differs from a steam heat exchanger. The water-to-water heat exchanger has internal baffles to direct the water flow across the tubes to improve heat transfer. Water-to-water heat exchangers are externally distin-guishable as the shell inlet and outlet tappings are the same size; steam heat exchangers have a large vapor opening in the top of the shell and a smaller condensate outlet in the bottom. The fluid in the condensate cooler tubes may be the inlet water to the steam heat exchanger tubes. When the initial temperature of the fluid is too high to cool the condensate below 212F, a separate fluid may be heated. Preheating domestic hot water or preheating boiler make up water are two possibilities. This article is reprinted from Fluid Handlings Steam Team Bulletin FHD-206.
Variable Volume Fundamentals Copyright 1999 by ITT Industries Read Next TechTalk Article Return to the University Press Page Return to the Fluid Handling University Homepage
Page 3 of 3
http://www.bellgossett.com/Press/techtk699b.htm
3/27/2003
Page 1 of 2
bonus you deserve. Before you even start, youll want to remove power to the equipment. All shops have some type of lock-out/tag-out procedure. Follow them completely; all the way through tag removal. This is absolutely necessary, because if you occasionally forget to remove your tags, someone else will get in the habit of removing them for you, usually while youre still working on the equipment. Make sure you remove all sources of power. Some motors, such as at hospitals, also have an emergency power source. Isolate that source from the pump too. More will be mentioned as we go through the servicing proce-dures. Were not quite ready yet to start disas-sembling our pump. To ensure that the whole process runs smoothly, lets take a few steps before proceeding. It would be nice to have an exploded diagram of the pump before we begin. One reason for this is so well know where to put all the extra parts we have left over when were done. They have to go somewhere. Manufacturers dont usually add parts that dont have any function. An exploded diagram like the one shown in Figure 1 is especially helpful. It not only illustrates the pump, it also gives us the proper part names. Therefore, if we need to order a replacement, we know what to call it besides a thing-amuh-jig. Bell &Gossett and some other manufacturers have made these diagrams available over the Internet. Just check their websites and youll be surprised at all the information that can make your job easier. You will even find valuable service instructions. Points of Service Were going to look at the three main areas for service. They are: lubrication seal replacement alignment. Lubrication is probably the single most important step in a maintenance program to keep a pump running without problems. Obviously, the manufacturers recommendations as to the type of lubricant and proper lubri-cation intervals are the best place to start. Its a starting point; not the final word. The reason I say that is the manufacturer doesnt know how his equipment is being used. How its used will affect how much you lubricate it. A couple of factors that affect the lubri-cation schedule are how often you run, or dont run the pump. What type of environment is it in? Is it hot, dirty, and dusty? Or is the pump lucky enough to reside in a cool, dry, location? You can see that the answer to, How often should I lubricate a pump? is, it all depends. Not much of an answer. So heres where experience comes into play. The more you know about the system, the better youre able to protect it. If youre lacking in experience, dont worry, you have something else to rely on: common sense. To help you determine a lubrication schedule, check your records to see how the system is performing. What have you done in the past to maintain the system? Where have you been successful, or unsuccessful in the past? If you dont know, you dont have a good set of records. So now, you need to start a log. There are a few things you want to put in that log: suction pressure, discharge pressure, how the pump is running (Hot? Noisy?), when was it lubricated? Youre going to lubricate the bearings on occasion. Generally there are two types of bearings: sleeve bearings and ball bearings. Everything about them is different. One of the best ways to determine when to lubricate either type is based on how hot theyre running. If you have a way to measure the temperature, great. If not, youll want to err on the side of lubricating them too often. After all, the cost of grease or oil is small compared to the time and cost of replacing the bearings. Lets start with the ball bearings. Before you start pumping grease into the grease fitting, check to see if theres a plug in the grease relief hole. If there is, remove it. You dont want to pump new grease into the bearings with no way of removing the old grease. Too
http://www.bellgossett.com/Press/techtk699c.htm
3/27/2003
Page 2 of 2
much grease can be just as harmful as too little grease. You want to keep pumping new grease in until you start to see all the old grease come out. Youre done greasing that bearing, but do you want to put the grease plug back in? Many people will simply throw the relief hole plug away for fear the next person will forget to remove it before they start to pump in grease. In fact, some manufacturers wont even thread the hole to keep the plug from getting jammed in the hole. For sleeve bearings youre going to want to add oil. Not just any oil, mind you. Once again, use what the manufacturer recommends. This will be a non-detergent oil. Theres an important reason for this. Oil evaporates - detergent doesnt. As the oil evaporates, the concentration of the detergent becomes stronger. You can see that each time you replenish the oil, you add even more detergent to the oil. Once the oil is added, it is absorbed by a wick that deposits it where its needed, between the sleeve bearing and the shaft to maintain a thin film of oil between the two. The wick has an important job. Therefore, youll want to inspect it. If its scored or burnt, replace it. If it feels waxy, it can no longer do its job effectively. The most likely reason for disassembling a pump is to replace the seals. Even if seal replacement isnt your reason for disassembly, its a good idea to replace the seal while you have the pump apart. That seal kit you bought contains all the parts you need. Replace the whole thing and not just an individual part. When you remove the seal, put on your detectives hat. Ask yourself why the seal wore the way it did. Were there grooves in the seal? This could be a sign of a high concentration of suspended or dissolved solids. Suspended solids less than 10 microns will get between the two seal faces. Maybe you need to choose a seal that is more tolerant of these solids. Maybe you need to determine if theres a way to remove these solids from the system. Your chemical concentration may be too high. A seal has two highly polished surfaces mated up to each other. Sure, no liquid is suppose to leak between the two surfaces, but it does -it has to. The thin film of liquid between the two surfaces heats up due to friction. The heat is then removed when the liquid evaporates. You never see that evaporation because its extremely small. But, like the oil in the sleeve bearing, the chemicals are left behind. They can then cause grooving in the seal. If you find that youre replacing seals often, perhaps you need to look at the type of seal youre using. If you cant remove the high concentration of chemicals, perhaps you need a seal that is more tolerant of the high concentration. Other factors that will affect seal selection are pH levels and temperature. The last word on seals is that theyre most often damaged during their installation. Be especially careful when putting the seal in. Dont touch its surface with dirty hands. Use soapy water to slide the seal on the shaft, since petroleum products may affect the seal. Try not to chip the seal when placing it on the shaft. And dont run the seal dry. Open the service valves to flood the pump cavity before running the pump. As you disassemble the pump, youll have to deal with gasket surfaces. Whenever youre dealing with a gasket surface, be careful not to scratch these machined surfaces. It may cause a leak path. And always use new gaskets when putting the pump back together. Keep It Straight Alignment is a concern for flexibly coupled pumps. The couplers job is to transmit power from the motor shaft to the pump shaft. It can also take up minor misalignment. The key word here is minor. Exactly how much has been determined by the coupler manufacturer based on several factors, so use their recommendations. How you check alignment is basically determined by rpm. The lower the rpm, the less sophisticated a method you can use. At 1,750 rpm you can get away with aligning the shafts with just a straight edge and taper gauges. At 3,500 youll want to use a dial indicator. For higher rpm and greater accuracy, you may need a laser. Check that the pump and motor shafts rotate around the same axis. This means you have to check the parallel and angular alignment as in figures 2 and 3. To change these alignments, youll have to place or remove shims from under the motor and move the motor from side to side. After youve placed shims under the motor, tighten the motor down to check alignment again. Its always better to use fewer, larger shims than a larger number of thin shims. After youve placed the pump in service, recheck the alignment when the pump reaches its operating temperature. Obviously, theres a lot to cover when servicing a centrifugal pump. Here, weve just touched on some of the main areas of concern. Along with that, my final advice is to use common sense and be methodical when working so as to not damage the pump - or yourself. This article is an abridged version of a Little Red Schoolhouse Staff article that originally appeared in the March, 1999 issue of Contracting Business.
Reprinted from TechTalk June 1999 Copyright 1999 by ITT Industries Read Next TechTalk Article Return to the University Press Page Return to the Fluid Handling University Homepage
http://www.bellgossett.com/Press/techtk699c.htm
3/27/2003
Page 1 of 2
http://www.bellgossett.com/Press/techtk699d.htm
3/27/2003
Page 2 of 2
head. Gauge readings at shutoff are 12 psi suction pressure and 46 psi discharge pressure. When the 3-way valve is fully open to the coil, the suction pressure is still 12 psi and the discharge pressure is 44 psi. When the 3-way valve is fully open to the bypass, the suction pressure is still 12 psi, but the discharge pressure is 40 psi. Whats the problem? Whats the solution? First, you must analyze the pump readings. Shutoff head is (discharge pressure -suction pressure) x 2.31 = (46 psi - 12 psi) x 2.31 = 78.5 ft. of water The 78.5 ft. at shutoff and the pump curve (Fig. 1) confirms the impeller diameter as 81/ 2 inches. With the 3-way valve fully open to the coil: Pump head = (44 psi - 12 psi) x 2.31 = 74 ft. of water The intersection of 74 ft. of head and the 81/ 2-in. impeller curve on Fig. 1 indicates a flow of 51 gpm. The horsepower required is 13/4. With the 3-way valve open to the bypass, the pump head is calculated as follows: Pump head = (40 psi - 12 psi) x 2.31 = 64.7 ft. of water. The intersection of 64.7 ft. of head and the 81/2 inch impeller curve on Fig. 1 indicates a flow of 80 gpm. The horse-power required is 21/ 3. The problem - too much flow because the resistance to flow in the bypass circuit is too low. The solution - increase the resistance in the bypass circuit by 9.3 ft. of water (74 -64.7) so the resistance through the bypass circuit is the same as the resistance through the coil. The flow and the horse-power will then be reduced to the same as that flowing through the coil, eliminating breaker trips. Understanding the information provided on the pump curves by the pump manufacturer and taking some simple gauge readings are of great help in analyzing pumped system problems. This article is an abridged version of a Little Red Schoolhouse Staff article that originally appeared in the November, 1998 issue of Contracting Business.
Reprinted from TechTalk June 1999 Copyright 1999 by ITT Industries Read Next TechTalk Article Return to the University Press Page Return to the Fluid Handling University Homepage
http://www.bellgossett.com/Press/techtk699d.htm
3/27/2003
Page 1 of 1
Reprinted from TechTalk June 1999 Copyright 1999 by ITT Industries Return to the University Press Page Return to the Fluid Handling University Homepage
http://www.bellgossett.com/Press/techtk699e.htm
3/27/2003