Beruflich Dokumente
Kultur Dokumente
www.leoni-industrial-projects.com
Product range
Telecommunication cables
Data- and Bus cables (copper and fiber optic)
Mining cables
Cables for special applications
Instrumentation- and control cables
Thermocouple extension and compensating cables
Power cables (low and medium voltage)
Content
Introduction
Product Guide UL 13, UL 2250 and UL 1277
Instrumentation Cable PLTC / ITC 300 V
Instrumentation Cable TC 600 V
Page
5
6
6
10
Datasheets
Instrumentation Cable 300 V
PVC jacket unshielded
RE-YwYw-fl
Single-pair
Single-triple
22
23
PVC-jacket, shielded
RE-Yw(St)Yw-fl
Single- & multi-pair, collective shield
Multi-pair, individual & collective shield (PiMF)
Single- & multi-triple, collective shield
Multi-triple, individual & collective shield (TiMF)
24
26
28
30
32
34
36
38
Content
www.leoni-industrial-projects.com
AL-laminated jacket
RE-Yw(St)Yw(L)Yw-fl
Single- & multi-pair, collective shield
Multi-pair, individual & collective shield (PiMF)
Single- & multi-triple, collective shield
Multi-triple, individual & collective shield (TiMF)
40
42
44
46
48
50
52
54
56
58
60
62
64
66
Instrumentation & Control Cables 600 V
PVC jacket, shielded
RE-Yw(St)Yw-fl
Multi-cores, collective shield, PVC jacket
68
General
General units
Conductors AWG and metric values by comparison
Color codes
Type designation
Abbreviation code
71
72
73
74
75
LEONI Kerpen GmbH can not be held responsible in any form whatsover for any
information provided by this publication. Printing errors excepted. Subject to alterations. Issue 20110208 - replaces issue 20081022
Table of Contents
www.leoni-industrial-projects.com
LEONI
Industrial Projects
your expert for a market that
requires maximum reliability
Table of Contents
www.leoni-industrial-projects.com
ICON UL Program
The product range of
instrumentation cables acc. to UL
www.leoni-industrial-projects.com
Instrumentation Cable
Common types
ICON Instrumentation Cable
unarmored
TC (UL 1277)
600 V
PVCw-insulation or XLPE-insulation
PVCw-jacket
armored
(L) shield
(L) shield
armored
unarmored
www.leoni-industrial-projects.com
300 V
Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket
unarmored
armored
(L) shielded
(L) shielded, armored
Technical data
Type of insulation/jacket
PVCw/PVCw
XLPE/PVCw
Conductor sizes
1. Unarmored types
RE-Yw(St)Yw-fl
Laying
RE-2X(St)Yw-fl
Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial 2)
Bending radius
2. Armored types
RE-Yw(St)YwSWAYw-fl
Laying
RE-2X(St)YwSWAYw-fl
Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial 2)
Bending radius
10 x cable diameter
RE-Yw(St)Yw(L)Yw-fl
Laying
RE-2X(St)Yw(L)Yw-fl
Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial
Bending radius
15 x cable diameter
RE-Yw(St)Yw(L)YwSWAYw-fl
Laying
RE-2X(St)Yw(L)YwSWAYw-fl
Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, for direct burial
Bending radius
15 x cable diameter
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
Temperature range
during operation
during installation
40 C up to 105 C
5 C up to 50 C
Sunlight resistance
Oil resistance
Application
40 C up to 90 C
5 C up to 50 C
ICEA S-72-532
For transmission of analogue and digital signals in instrument and control systems in complianc with NEC article
725.154; allowed for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and NEC
502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply
1)
2)
www.leoni-industrial-projects.com
300 V
Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket
unarmored
armored
(L) shielded
(L) shielded, armored
Construction
Product types
Unarmored types
Conductor
size
Conductor design
Armored types
AWG 20/7
7 x 0.320
AWG 18/7
7 x 0.404
AWG 16/7
7 x 0.490
AWG 14/7
7 x 0.620
Insulation materials
Cabling element 1)
without individual shield
Pair, Triple
PiMF, TiMF
Individual shield
Aluminum/plastic-tape over solid tinned copper drain wire, plastic-tape under and above shield
Wrapping
Overall shield
Inner jackets
L() shield
Armoring
PVCw, black
Outer jacket
PVCw
Color
Marking
2)
www.leoni-industrial-projects.com
300 V
Single & multi pair and single & multi triple, individual and/or overall shield, PVC-jacket
unarmored
armored
(L) shielded
(L) shielded, armored
Electrical Data at 20 C
300 V
Conductor sizes
nom.
AWG
AWG 20/7
AWG 18/7
AWG 16/7
Conductor resistance
max.
/km
35.8
22.8
14.3
min.
Mxkm
30.5
XLPE-insulation
min.
Mxkm
30.5
Inductance
max.
mH/km
Mutual capacitance
PVCw-insulation
Pair, Triple 1) 2)
PiMF, TiMF
max.
nF/km
200
200
XLPE-insulation
Pair, Triple 1) 2)
PiMF, TiMF
max.
nF/km
125
125
Test voltage
Core/core (Urms)
Core/shield (Urms)
1500
1500
300
Operating voltage
(Urms)
max.
1)
Values for cables with 1 element correspond to those for PiMF and TiMF resp.
Values for cables with >1 element -30 %.
2)
AWG 14/7
9.0
10
www.leoni-industrial-projects.com
Instrumentation Cable
Common types
ICON Instrumentation Cable
unarmored
TC (UL 1277)
600 V
PVCw-insulation or XLPE-insulation
PVCw-jacket
armored
(L) shield
(L) shield
armored
unarmored
www.leoni-industrial-projects.com
11
600 V
300 V
Technical data
Type of insulation/jacket
PVCw/PVCw
PVCwNC/PVCw
Conductor sizes
XLPE/PVCw
1. Unarmored types
RE-Yw(St)Yw-fl
Laying
RE-Yw4Y(St)Yw-fl
RE-2X(St)Yw-fl
Bending radius
10 x cable diameter
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
Temperature range
Sunlight resistance
Oil resistance
Application
during operation
during installation
40 C up to 90 C
5 C up to 50 C
UL 1581 Section 1200
ICEA S-73-532
For transmission of analogue and digital signals in instrument and control systems; UL listed tray cable in compliance
with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply
12
www.leoni-industrial-projects.com
600 V
300 V
Single
Single&&Multi
Multipair
pairand
andMulti
Multitriple,
triple,individual
individualand/or
and/oroverall
overallshield,
shield,PVC-jacket
PVC-jacket
unarmored
armored
Construction
Product types
Unarmored types
Conductor
size
Conductor design
AWG 18/7
7 x 0.404
Insulation materials
AWG 16/7
7 x 0.490
AWG 14/7
7 x 0.620
Cabling element 1)
without individual shield
Pair, Triple
PiMF, TiMF
Individual shield
Aluminum/plastic-tape over stranded tinned copper drain wire, plastic-tape under and above shield
Wrapping
Overall shield
Outer jacket
PVCw
Color
Marking
1)
www.leoni-industrial-projects.com
600 V
300 V
Electrical Data at 20 C
600 V
Conductor sizes
nom.
AWG
AWG 18/7
AWG 16/7
AWG 14/7
Conductor resistance
max.
/km
22.8
14.3
9.0
PVCw-insulation
min.
Mxkm
175
XLPE-insulation
min.
Mxkm
810
Inductance
max.
mH/km
0.7
Mutual capacitance
PVCw-insulation
Pair, Triple 1) 2)
PiMF, TiMF
max.
nF/km
170
170
XLPE-insulation
Pair, Triple 1) 2)
PiMF, TiMF
max.
nF/km
120
120
Test voltage
Core/core (Urms)
Core/shield (Urms)
Operating voltage
(Urms)
max.
1)
600
Values for cables with 1 element correspond to those for PiMF and TiMF resp.
Values for cables with > 1 element -30 %.
2)
13
14
www.leoni-industrial-projects.com
unarmored
TC (UL 1277)
600 V
PVCw-insulation or XLPE-insulation
PVCw-jacket
armored
(L) shield
(L) shield
armored
unarmored
www.leoni-industrial-projects.com
15
300 V
Technical data
Type of insulation/jacket
PVCw/PVCw
XLPE/PVCw
Cores
Conductor sizes
1. Unarmored types
RE-Yw(St)Yw-fl
Laying
RE-2X(St)Yw-fl
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations, or direct
burial2)
Bending radius
2. Armored types
RE-Yw(St)YwSWAYw-fl
Laying
RE-2X(St)YwSWAYw-fl
Recommended for outdoor installation, on racks, trays, in conduits, in dry and wet locations, or direct burial1)
Bending radius
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
Temperature range
during operation
during installation
40 C up to 105 C
5 C up to 50 C
Sunlight resistance
Oil resistance
Application
40 C up to 90 C
5 C up to 50 C
ICEA S-72-532
For transmission of analogue and digital signals in instrument and control systems in complianc with NEC article
725.154; allowed for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and NEC
502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply
1)
if applicable
16
www.leoni-industrial-projects.com
300 V
Construction
Product types
Unarmored types
Conductor
size
Conductor design
Armored types
AWG 20/7
7 x 0.320
AWG 18/7
7 x 0.404
AWG 16/7
7 x 0.490
AWG 14/7
7 x 0.620
Insulation materials
Cabling element 1)
without individual shield
Core
Wrapping
Overall shield
Inner jacket
PVCw, black
Galvanized steel wire armor; wire diameter depending on
cable diameter under armoring, at least 0.9 mm
Armoring
Outer jacket
PVCw
Color
Marking
2)
www.leoni-industrial-projects.com
17
300 V
300 V
Electrical Data at 20 C
300 V
Conductor sizes
nom.
AWG
AWG 20/7
AWG 18/7
AWG 16/7
Conductor resistance
max.
/km
35.8
22.8
14.3
min.
Mxkm
30.5
XLPE-insulation
min.
Mxkm
30.5
Inductance
max.
mH/km
Mutual capacitance
PVCw-insulation
CORE
max.
nF/km
200
XLPE-insulation
CORE
max.
nF/km
125
Test voltage
Core/core (Urms)
Core/shield (Urms)
1500
1500
300
Operating voltage
(Urms)
max.
AWG 14/7
9.0
18
www.leoni-industrial-projects.com
unarmored
TC (to UL 1277)
600 V
armored
(L) shield
(L) shield
armored
unarmored
www.leoni-industrial-projects.com
19
600 V
300 V
Single
Multi Core,
& Multi
overall
pair shield,
and Multi
PVC-jacket
triple, individual and/or overall shield, PVC-jacket
unarmored
armored
Technical data
Type of insulation/jacket
PVCw/PVCw
PVCwNC/PVCw
Core
Conductor sizes
XLPE/PVCw
1. Unarmored types
RE-Yw(St)Yw-fl
Laying
RE-Yw4Y(St)Yw-fl
RE-2X(St)Yw-fl
Bending radius
10 x cable diameter
Reaction to fire
Flame propagation
a) Test on single cable
b) Test on bunched cables
Temperature range
Sunlight resistance
Oil resistance
Application
during operation
during installation
40 C up to 90 C
5 C up to 50 C
UL 1581 Section 1200
ICEA S-73-532
For transmission of analogue and digital signals in instrument and control systems; UL listed tray cable in compliance
with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply
20
www.leoni-industrial-projects.com
Control
Cable
ICON Instrumentation Cable
according
to ULaccording
13 / 2250to UL 1277
Common types
600
300
VV
Multi core,
overall
PVC-jacket
Single
& Multi
pair shield,
and Multi
triple, individual and/or overall shield, PVC-jacket
unarmored
armored
Construction
Product types
Unarmored types
Conductor
size
Conductor design
mm
Insulation materials
AWG 16/7
7 x 0.404
AWG 14/7
7 x 0.620
Cabling element 1)
Core
Wrapping
Overall shield
Outer jacket
PVCw
Color
Marking
LEONI KERPEN ICON PLTC/ITC SIZE MATERIAL TYPE OF SHIELD UL Rated voltage
TEMPERATURE RATING SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING IN FEET
1)
www.leoni-industrial-projects.com
600 V
Control
Cable
ICON Instrumentation Cable
according
to ULaccording
13 / 2250 to UL 1277
Common types
600 V
300 V
Single
Multi core,
& Multi
overall
pair shield,
and Multi
PVC-jacket
triple, individual and/or overall shield, PVC-jacket
unarmored
armored
Electrical Data at 20 C
600 V
Conductor sizes
nom.
mm
AWG 18/7
AWG 16/7
AWG 14/7
Conductor resistance
max.
/km
35.8
22.8
14.3
min.
Mxkm
175
Insulation resistance at 15 C
PVCw-insulation
XLPE-insulation
min.
Mxkm
810
Inductance
max.
mH/km
Mutual capacitance
PVCw-insulation
Core
max.
nF/km
187
XLPE-insulation
Core
max.
nF/km
120
Test voltage
Core/core (Urms)
Core/shield (Urms)
Operating voltage
(Urms)
max.
600
21
22
www.leoni-industrial-projects.com
Instrumentation Cable
UL 13 / UL 2250
PLTC/ITC
105 C / 300 V
Power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to NEC
501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC 105 C SUN
RES PRODUCTION LOT CODE LENGTH MARKING IN FEET
Technical data
Flame propagation
- Test on single cable
- Test on bunched cables
Gas/vapor tightness outer
jacket
Limiting Oxygen Index (LOI)
Flammability temperature (FT)
Oil resistance
Sunlight resistance
Abbreviations
UL13 (VW-1)
UL 1685 (vertical tray)
NEC 501.15 (D) and (E)
ASTM D 2863 (min. 30 %)
ISO 4589-3 ann. A (min. +250 C)
ICEA S-73-532
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Instrumentation Cable
Inductance
L/R ratio max.
Flame Retardant, Sunlight
Test voltage Urms (core : core)
Resistant
Single-Pair,
PVC-Insulation,
Test
voltage Urms
(core : shield) PVC Jacket
max.
min.
max.
max.
Temperature range
-40C up to +105C
(during operation)
-5C up to +50C
(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
/km / /1000ft
M x km /
M x 1000ft
mH/km
H/
V
Operating voltage
RE-YwYw-fl
REYw
Yw
-fl
AWG 14
8.9 / 2.72
Instrumentation Cable
PVC insulation, heat resistant
PVC outer jacket, heat resistant
reduced flame propagation
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
UL 13 / UL 2250
1
60
PLTC/ITC
25
105 C / 300 V
40
1500
1500
300
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
0.51 / 20
1.02 / 40
8.0 / 0.32
88 / 60
79030013
0.38 / 15
0.89 / 35
6.5 / 0.26
66 / 50
79030012
0.38 / 15
0.89 / 35
6.0 / 0.24
55 / 40
79030011
0.30 / 12
0.89 / 35
5.2 / 0.20
40 / 30
79030010
AWG 16 /7
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
www.leoni-industrial-projects.com
23
Instrumentation Cable
UL 13 / UL 2250
PLTC/ITC
105 C / 300 V
Power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to NEC
501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC 105 C SUN
RES PRODUCTION LOT CODE LENGTH MARKING IN FEET
Technical data
Flame propagation
- Test on single cable
- Test on bunched cables
Abbreviations
UL13 (VW-1)
UL 1685 (vertical tray)
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
single element:
2 to 4 elements:
Instrumentation Cable
above 4 elements:
Inductance
L/R
ratio max.
Flame
Retardant, Sunlight Resistant
Test
voltage
Urms
(core : core)
Single-Triple,
PVC-Insulation,
PVC Jacket
nom.
Temperature range
-40C up to +105C
(during operation)
-5C up to +50C
(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
max.
max.
Operating
voltage
RE-YwYw-fl
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 16 /7
RT outer jacket
nom.
(mm / mils)
Yw
Yw
-fl
Instrumentation Cable
PVC insulation, heat resistant
PVC outer jacket, heat resistant
reduced flame propagation
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
187 / 57
187 / 57
187 / 57
mH/km
H/
V
RE-
UL 13 / UL 2250
PLTC/ITC
25105 C / 300 V
1
40
1500
1500
300
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
0.38 / 15
0.89 / 35
6.8 / 0.27
80 / 55
79030016
0.38 / 15
0.89 / 35
6.3 / 0.25
65 / 45
79030015
0.30 / 12
0.89 / 35
5.4 / 0.21
45 / 35
79030014
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
24
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
*)
PVC OS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Flame propagation
Temperature range
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
200 / 61
190 / 58
150 / 46
Abbreviations
REYw
(St)
Yw
-fl
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC outer jacket, heat resistant
reduced flame propagation
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
190 / 58
150 / 46
AWG 20
35.8 / 10.92
200 / 61
180 / 55
150 / 46
200 / 61
180 / 55
150 / 46
1
60
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
25
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
1
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.02 / 40
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
8.2 / 0.32
12.6 / 0.50
14.6 / 0.57
18.0 / 0.71
19.1 / 0.75
21.7 / 0.85
23.3 / 0.92
26.4 / 1.04
31.4 / 1.24
38.6 / 1.52
109 / 75
207 / 140
318 / 215
492 / 325
578 / 390
705 / 475
851 / 575
1095 / 740
1548 / 1040
2299 / 1545
79960628
79960629
79960630
79960631
79960632
79960633
79960634
79960635
79960636
79960637
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
6.7 / 0.26
10.8 / 0.43
12.5 / 0.50
14.8 / 0.58
16.1 / 0.64
18.2 / 0.72
18.8 / 0.74
21.1 / 0.83
25.4 / 1.01
30.3 / 1.20
69 / 55
146 / 95
217 / 145
297 / 195
384 / 260
460 / 310
533 / 355
680 / 455
1002 / 670
1433 / 955
79960000
79960001
79960002
79960254
79960003
79960255
79960004
79960005
79960006
79960007
0.89 / 35
2
0.38 / 15
1.02 / 40
0.38 / 15
1.27 / 50
Flame Retardant,4 Sunlight Resistant
6
0.38
/
15
1.27 / 50
Single & Multi-Pair, PVC-Insulation, Collective Shield, PVC Jacket
8
0.38 / 15
1.27 / 50
10
0.38
/
15
1.52 / 60
RE-Yw(St)Yw-fl
0.38 / 15
1.52 / 60
Geometrical data 12
0.38 / 15
1.52 / 60
No. of elements 16
RT of insulation
RT outer jacket
24
nom. 0.38 / 15
nom. 1.78 / 70
36
0.38 / 15
1.78 / 70
(mm / mils)
(mm / mils)
6.2 / 0.24
9.3 / 0.37
11.4 / 0.45
13.5 / 0.53
14.1 / 0.56
16.5 / 0.65
17.0 / 0.67
Outer 19.0
dia. / 0.75
23.1 / 0.91
approx.
(mm /28.6
in) / 1.07
AWG 16 /7
AWG 18 /7
Instrumentation
Cable
1
0.38 / 15
AWG 20 /7
1
2
4
6
8
10
12
16
24
36
RT = Radial Thickness
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.89 / 35
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
5.3 / 0.21
8.0 / 0.31
8.8 / 0.36
11.3 / 0.44
11.8 / 0.47
13.3 / 0.52
13.7 / 0.54
15.8 / 0.63
18.6 / 0.73
21.8 / 0.86
UL 13 / UL 2250
54 / 45
79960008
PLTC/ITC
105 / 75
79960009
171 / 115 105 C
79960010
/ 300 V
230 / 155
79960252
280 / 185
79960011
350 / 240
79960253
409 / 275
79960012
79960013
Weight518 / 350
Part
number
79960014
approx.776 / 505
Color
1086 / 720
79960015
(kg/km / lbs/1000ft)
black
39 / 35
76 / 55
109 / 75
160 / 110
194 / 130
225 / 155
263 / 175
355 / 240
488 / 325
693 / 460
79960016
79960017
79960018
79960250
79960019
79960251
79960020
79960021
79960022
79960023
26
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
SPOS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
Technical data
Flame propagation
Temperature range
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
200 / 61
Abbreviations
REYw
(St)
Yw
-fl
PiMF
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC outer jacket, heat resistant
reduced flame propagation
pair in metal foil
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
AWG 20
35.8 / 10.92
200 / 61
200 / 61
1
60
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
27
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
13.9 / 0.55
16.7 / 0.66
20.0 / 0.79
21.3 / 0.84
24.7 / 0.97
26.4 / 1.04
29.7 / 1.17
36.0 / 1.42
43.4 / 1.71
238 / 160
387 / 260
552 / 375
687 / 465
857 / 580
987 / 665
1271 / 855
1871 / 1285
2911 / 1960
79960638
79960639
79960640
79960641
79960642
79960643
79960644
79960645
79960646
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
12.1 / 0.48
14.2 / 0.56
17.3 / 0.69
18.4 / 0.72
20.8 / 0.82
21.6 / 0.85
24.8 / 0.98
29.4 / 1.16
35.4 / 1.40
170 / 115
259 / 170
388 / 255
470 / 310
570 / 370
641 / 420
861 / 565
1208 / 800
1792 / 1175
79960024
79960025
79960260
79960026
79960261
79960027
79960028
79960029
79960030
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
11.4 / 0.44
13.1 / 0.52
16.0 / 0.63
17.0 / 0.67
19.1 / 0.75
19.8 / 0.78
22.7 / 0.90
26.9 / 1.06
32.4 / 1.28
144 / 100
210 / 145
305 / 205
381 / 250
450 / 305
514 / 340
687 / 455
968 / 640
1411 / 935
79960031
79960032
79960258
79960033
79960259
79960034
79960035
79960036
79960037
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
8.9 / 0.36
11.2 / 0.44
13.1 / 0.52
13.7 / 0.54
16.0 / 0.63
16.6 / 0.65
18.5 / 0.73
21.8 / 0.86
26.4 / 1.04
94 / 65
152 / 345
209 / 135
253 / 165
310 / 210
357 / 240
455 / 300
662 / 415
936 / 615
79960038
79960039
79960256
79960040
79960257
79960041
79960042
79960043
79960044
AWG 16 /7
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
28
www.leoni-industrial-projects.com
Instrumentation Cable
UL 13 / UL 2250
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
*)
PVC OS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC outer jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
-fl
(during installation)
reduced flame propagation
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
190 / 58
150 / 46
200 / 61
190 / 58
150 / 46
60
40
AWG 20
35.8 / 10.92
200 / 61
180 / 55
150 / 46
200 / 61
180 / 55
150 / 46
1
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
29
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
1
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.02 / 40
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
8.6 / 0.35
14.0 / 0.55
16.5 / 0.65
21.2 / 0.84
23.2 / 0.91
24.1 / 0.95
26.8 / 1.05
30.2 / 1.19
36.5 / 1.44
44.0 / 1.73
134 / 90
275 / 185
454 / 305
663 / 450
848 / 570
1010 / 680
1191 / 805
1546 / 1040
2274 / 1530
3349 / 2250
79960647
79960648
79960649
79960650
79960651
79960652
79960653
79960654
79960655
79960656
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.02 / 40
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
7.2 / 0.28
11.9 / 0.47
13.7 / 0.54
17.3 / 0.68
18.4 / 0.72
20.6 / 0.81
21.2 / 0.83
24.3 / 0.96
28.9 / 1.14
34.9 / 1.37
90 / 65
180 / 125
288 / 195
420 / 285
525 / 355
647 / 430
749 / 495
995 / 660
1400 / 945
2060 / 1385
79960045
79960046
79960047
79960266
79960048
79960267
79960049
79960050
79960051
79960052
AWG 16 /7
AWG 18 /7
1
0.38 / 15
!"#
0.89 / 35
6.5 / 0.26
66 / 50
79960053
2
0.38 / 15
1.27 / 50
10.8 / 0.43
170 / 115
79960054
)"
4
0.38
/
15
1.27
/
50
12.4
/
0.49
223
/
150
79960055
$
%
&'
(%
#"!*
6
0.38 / 15
1.27 / 50
15.2 / 0.60
315 / 215
79960264
?6KB
;
23!
"?23L5
8
0.38
/
15
1.52
/
60
16.7
/
0.66
413
/
270
79960056
10
0.38
/
15
1.52
/
60
18.6
/
0.74
492
/
330
79960265
%+,-'.+,/
0.38 / 15
1.52 / 60
19.2 / 0.76
564 / 380
79960057
4
12
16
0.38
/
15
1.52
/
60
21.5
/
0.85
722
/
485
79960058
2</<
>
>
1
,(
)
2<
24
0.38 / 15
1.78 / 70
26.1 / 1.03
1055 / 710
79960059
=
>
36
30.8 / 1.22
1518 / 1015
79960060
$ 0.38 / 15
$ 1.78 / 70
C$
C$
(< *
(< *
(<*
(56<5< <'&&&
*
5
?4";
'
&$&<'#
&$1E<%
%$<&$##
%&<%
,EE&&'
#
&$&<'#
'$&#<0&
1$,<&$0
E%<%
,EE&&#
0
&$&<'#
'$#,<%&
'&$%<&$0'
'%%<'&%
,EE&&
&$&<'#
'$#,<%&
'#$,<&$%&
#'%<'0%
,EE&##
1
&$&<'#
'$#,<%&
'$%<&$%
#&<',%
,EE&&0
'&
&$&<'#
'$#,<%&
'%$&<&$%E
'&<#'&
,EE&#
'#
&$&<'#
'$%#<&
'%$E<&$
,%<#%%
,EE&&%
'
&$&<'#
'$%#<&
',$1<&$,&
0,%<#&
,EE&&
#0
&$&<'#
'$%#<&
#&$E<&$1#
,&<0%%
,EE&&,
&$&<'#
'$,1<,&
#%$<'$&&
E1%<%
,EE&&1
30
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
STOS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC outer jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
-fl
(during installation)
reduced flame propagation
jacket
triple in metal foil
Min. bending radius - repeated TiMF
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
200 / 61
60
40
AWG 20
35.8 / 10.92
200 / 61
200 / 61
1
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
31
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
16.5 / 0.65
18.9 / 0.75
24.0 / 0.94
25.0 / 0.98
28.2 / 1.11
29.2 / 1.15
33.6 / 1.32
40.1 / 1.58
48.7 / 1.96
324 / 220
513 / 345
773 / 520
959 / 645
1162 / 785
1327 / 895
1766 / 1190
2550 / 1715
3756 / 2525
79960657
79960658
79960659
79960660
79960661
79960662
79960663
79960664
79960665
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
13.3 / 0.52
15.9 / 0.63
19.6 / 0.77
20.9 / 0.82
24.1 / 0.95
24.7 / 0.97
27.7 / 1.09
33.5 / 1.32
39.8 / 1.57
215 / 145
350 / 230
490 / 330
610 / 410
791 / 520
891 / 585
1145 / 755
1650 / 1110
2365 / 1590
79960069
79960070
79960272
79960071
79960273
79960072
79960073
79960074
79960075
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
12.3 / 0.48
14.2 / 0.56
18.0 / 0.71
19.1 / 0.75
21.5 / 0.85
22.7 / 0.89
25.3 / 1.00
30.1 / 1.19
36.3 / 1.43
172 / 115
260 / 175
395 / 270
491 / 325
585 / 395
702 / 465
898 / 595
1268 / 845
1840 / 1240
79960076
79960077
79960270
79960078
79960271
79960079
79960080
79960081
79960082
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
10.4 / 0.41
12.0 / 0.47
14.6 / 0.57
16.1 / 0.63
17.9 / 0.70
18.4 / 0.72
20.6 / 0.81
25.0 / 0.98
29.6 / 1.17
120 / 85
180 / 125
250 / 170
335 / 230
400 / 270
450 / 305
628 / 385
835 / 565
1190 / 800
79960083
79960084
79960268
79960085
79960269
79960086
79960087
79960088
79960089
AWG 16 /7
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
32
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
*)
PVC OS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Flame propagation
Temperature range
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
10 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
200 / 61
190 / 58
160 / 49
Abbreviations
REYw
(St)
Yw
SWA
Yw
-fl
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC inner jacket, heat resistant
steel wire armor
PVC outer jacket, heat resistant
reduced flame propagation
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
190 / 58
160 / 49
AWG 20
35.8 / 10.92
200 / 61
180 / 55
150 / 46
200 / 61
180 / 55
150 / 46
1
60
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
33
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 1
nom.
(mm / mils)
Dia. over
inner jacket 1
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
319 / 215
540 / 365
700 / 475
1097 / 740
1234 / 830
1440 / 970
1649 / 1100
2213 / 1490
2845 / 1915
4256 / 2860
AWG 14 /7
1
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.02 / 40
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
8.1 / 0.32
12.6 / 0.50
14.6 / 0.58
18.0 / 0.71
19.1 / 0.75
21.7 / 0.86
23.3 / 0.92
26.4 / 1.04
31.4 / 1.23
38.6 / 1.52
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.6
1.6
2
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
12.5 / 0.49
17.5 / 0.69
19.5 / 0.77
24.1 / 0.95
25.2 / 0.99
27.8 / 1.09
29.3 / 1.15
33.6 / 1.32
38.6 / 1.52
47.1 / 1.85
6.7 / 0.26
10.6 / 0.43
12.6 / 0.50
14.8 / 0.58
16.2 / 0.64
18.2 / 0.72
18.9 / 0.74
21.2 / 0.83
25.6 / 1.01
30.4 / 1.20
0.9
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.6
1.6
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
11.0 / 0.43
15.0 / 0.59
17.4 / 0.69
19.7 / 0.77
21.8 / 0.85
24.3 / 0.96
25.0 / 0.98
27.3 / 1.07
32.8 / 1.30
37.6 / 1.48
79840471
79840472
79840473
79840474
79840475
79840476
79840477
79840478
79840479
79840480
AWG 16 /7
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.89 / 35
0.38 / 15
1.27 / 50
0.38 / 15
1.27 / 50
0.38 / 15
1.27 / 50
0.38 / 15
1.52 / 60
0.38 / 15
1.52 / 60
0.38 / 15
1.52 / 60
0.38 / 15
1.52 / 60
0.38 / 15
1.78 / 70
Instrumentation
0.38 / 15
1.78Cable
/ 70
AWG 18 /7
1
0.38
/ 15
0.89 / 35
6.1 / 0.24
0.9
1.27 / 50
Flame Retardant,
Sunlight
Resistant
2
0.38 / 15
1.02 / 40
9.4 / 0.37
0.9
1.27 / 50
Single & Multi-Pair, PVC-Insulation, Collective Shield, Armor, PVC Jacket
4
0.38 / 15
1.27 / 50
11.3 / 0.45
0.9
1.52 / 60
6
0.38 / 15
1.27 / 50
13.4 / 0.53
0.9
1.52 / 60
RE-Yw(St)YwSWAYw-fl
8
0.38
/
15
1.27
/
50
14.2
/
0.56
0.9
1.52 / 60
Geometrical data
10
0.38 / 15
1.52 / 60
16.5 / 0.65
1.25
1.52 / 60
No. of
RT of
RT of inner
Dia. over
Dia. of
RT outer jacket
12
0.38
/
15
1.52
/
60
17.1
/
0.67
1.25
1.78 / 70
elements
insulation
jacket 1
inner jacket 1 armor wire
16
0.38
/
15
1.52
/
60
19.1
/
0.75
1.25
1.78 / 70
nom.
nom.
nom.
nom.
nom.
24
/ 15
/ 70
23.1 // in)
0.91
/ 70
(mm0.38
/ mils)
(mm1.78
/ mils)
(mm
(mm)1.25
(mm1.78
/ mils)
36
0.38 / 15
1.78 / 70
27.3 / 1.07
1.6
2.03 / 80
AWG 20 /7
1
0.30 / 12
0.89 / 35
5.3 / 0.21
0.9
1.02 / 40
2
0.30 / 12
1.02 / 40
8.0 / 0.31
0.9
1.27 / 50
4
0.30 / 12
1.02 / 40
9.2 / 0.36
0.9
1.27 / 50
6
0.30 / 12
1.27 / 50
11.3 / 0.44
0.9
1.52 / 60
8
0.30 / 12
1.27 / 50
11.9 / 0.47
0.9
1.52 / 60
10
0.30 / 12
1.27 / 50
13.3 / 0.52
0.9
1.52 / 60
12
0.30 / 12
1.27 / 50
13.8 / 0.54
0.9
1.52 / 60
16
0.30 / 12
1.52 / 60
15.9 / 0.63
1.25
1.78 / 70
24
0.30 / 12
1.52 / 60
18.6 / 0.73
1.25
1.78 / 70
36
0.30 / 12
1.52 / 60
21.9 / 0.86
1.25
1.78 / 70
RT = Radial Thickness
10.4 / 0.41
13.8 / 0.54
16.2 / 0.64
18.3 / 0.72
19.1 / 0.75
22.1 / 0.87
Outer dia.
23.2 / 0.91
25.2
/ 0.99
approx.
29.1 // in)
1.15
(mm
34.5 / 1.36
9.1 / 0.36
12.4 / 0.48
13.6 / 0.53
16.2 / 0.63
16.8 / 0.66
18.2 / 0.71
18.7 / 0.73
22.0 / 0.84
24.7 / 0.97
28.0 / 1.10
248 / 175
414 / 285
555 / 375
694 / 470
924 / 620
1097 / 740
1222 / 800
1402 / 945
2080 / 1400
UL
13 / UL
2696 / 1815
79840000
79840001
79840002
79840254
79840003
79840255
79840004
79840005
79840006
2250
79840007
PLTC/ITC
79840016
79840017
79840018
79840250
79840019
79840251
79840020
79840021
79840022
79840023
34
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
SPOS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
Technical data
Flame propagation
Temperature range
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
10 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
Abbreviations
REYw
(St)
Yw
SWA
Yw
-fl
PiMF
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC inner jacket, heat resistant
steel wire armor
PVC outer jacket, heat resistant
reduced flame propagation
pair in metal foil
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
200 / 61
60
40
AWG 20
35.8 / 10.92
200 / 61
200 / 61
1
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
35
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 1
nom.
(mm / mils)
Dia. over
inner jacket 1
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 14 /7
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
14.1 / 0.56
16.7 / 0.66
20.0 / 0.79
21.3 / 0.84
24.7 / 0.97
26.4 / 1.04
29.7 / 1.17
36.0 / 1.42
43.4 / 1.71
0.9
1.25
1.25
1.25
1.25
1.6
1.6
2
2
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
2.54 / 100
19.0 / 0.75
22.8 / 0.90
26.1 / 1.03
27.4 / 1.08
30.7 / 1.21
33.6 / 1.32
36.9 / 1.45
44.5 / 1.75
52.5 / 2.06
605 / 410
965 / 650
1234 / 830
1417 / 955
1692 / 1140
2106 / 1415
2518 / 1695
3763 / 2530
5166 / 3475
79840124
79840482
79840483
79840484
79840485
79840486
79840487
79840488
79840490
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
12.2 / 0.48
14.3 / 0.56
17.3 / 0.69
18.4 / 0.72
20.8 / 0.82
21.6 / 0.85
24.9 / 0.98
29.4 / 1.16
36.5 / 1.40
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.6
2
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
17.0 / 0.67
19.2 / 0.75
23.4 / 0.93
24.5 / 0.96
26.9 / 1.06
27.7 / 1.09
30.9 / 1.22
36.6 / 1.44
45.0 / 1.74
495 / 335
633 / 430
1014 / 665
1097 / 740
1272 / 860
1375 / 930
1692 / 1140
2422 / 1630
3645 / 2450
79840024
79840025
79840260
79840026
79840261
79840027
79840028
79840029
79840030
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
11.3 / 0.44
13.1 / 0.52
16.0 / 0.63
17.0 / 0.67
19.1 / 0.75
19.8 / 0.78
22.8 / 0.90
26.9 / 1.06
32.4 / 1.28
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
16.2 / 0.63
18.0 / 0.71
21.6 / 0.85
23.1 / 0.91
25.2 / 0.99
25.9 / 1.02
28.8 / 1.14
34.1 / 1.35
39.6 / 1.56
446 / 305
557 / 380
853 / 575
974 / 660
1117 / 755
1194 / 805
1454 / 980
2086 / 1405
2749 / 1855
79840031
79840032
79840258
79840033
79840259
79840034
79840035
79840036
79840037
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
9.2 / 0.36
11.2 / 0.44
13.1 / 0.52
13.8 / 0.54
16.0 / 0.63
16.6 / 0.65
18.6 / 0.73
21.8 / 0.86
26.8 / 1.04
0.9
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.6
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
13.6 / 0.53
16.1 / 0.63
18.0 / 0.70
18.7 / 0.73
21.6 / 0.85
22.7 / 0.89
24.7 / 0.97
27.9 / 1.10
34.0 / 1.33
332 / 230
455 / 310
556 / 380
615 / 415
854 / 575
934 / 630
1093 / 685
1383 / 935
2047 / 1380
79840038
79840039
79840256
79840040
79840257
79840041
79840042
79840043
79840044
AWG 16 /7
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
36
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/
*)
PVC OS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
SWA
(during installation)
steel wire armor
jacket
Yw
PVC outer jacket, heat resistant
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
-fl
reduced flame propagation
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
10 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
200 / 61
190 / 58
160 / 49
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
190 / 58
160 / 49
AWG 20
35.8 / 10.92
200 / 61
180 / 55
150 / 46
200 / 61
180 / 55
150 / 46
1
60
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
37
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 1
nom.
(mm / mils)
Dia. over
inner jacket 1
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 14 /7
1
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.02 / 40
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
8.8 / 0.35
14.0 / 0.55
16.5 / 0.65
21.2 / 0.84
23.2 / 0.91
24.1 / 0.95
26.8 / 1.05
30.2 / 1.19
36.5 / 1.44
44.0 / 1.73
0.9
0.9
1.25
1.25
1.25
1.25
1.6
1.6
2
2
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
2.54 / 100
13.2 / 0.52
18.9 / 0.74
22.1 / 0.87
27.3 / 1.07
29.2 / 1.15
30.1 / 1.18
34.0 / 1.34
37.4 / 1.47
45.0 / 1.77
53.1 / 2.09
356 / 240
643 / 435
1000 / 675
1383 / 930
1632 / 1100
1820 / 1225
2330 / 1570
2814 / 1895
4131 / 2780
7265 / 4885
79840491
79840492
79840493
79840494
79840495
79840496
79840497
79840498
79840499
79840500
7.2 / 0.28
12.0 / 0.47
13.6 / 0.54
17.2 / 0.68
18.4 / 0.72
20.6 / 0.81
21.1 / 0.83
24.4 / 0.96
28.8 / 1.14
34.8 / 1.37
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
11.6 / 0.45
16.9 / 0.66
18.5 / 0.73
23.3 / 0.92
24.5 / 0.96
26.7 / 1.06
27.2 / 1.07
30.4 / 1.20
36.0 / 1.43
42.5 / 1.68
289 / 195
505 / 340
647 / 440
1043 / 705
1165 / 785
1354 / 915
1466 / 990
1823 / 1225
2626 / 1770
UL 13 /
3569 / 2430
79840045
79840046
79840047
79840266
79840048
79840267
79840049
79840050
79840051
2250
79840052
10.9 / 0.43
15.3 / 0.59
17.3 / 0.68
20.7 / 0.81
22.7 / 0.90
24.8 / 0.98
Outer
dia.
25.3 / 1.00
27.5
/ 1.09
approx.
33.2
(mm/ /1.31
in)
38.0 / 1.50
248 / 170
425 / 285
554 / 380
820 / 565
984 / 670
1140
/ 770
Weight
1225 / 825
1453
/ 1005
approx.
2156
/ 1455
(kg/km
/
2800
/ 1925
lbs/1000ft)
AWG 16 /7
1
2
4
6
8
10
12
16
24
36
0.38 / 15
1.02 / 40
0.38 / 15
1.27 / 50
0.38 / 15
1.27 / 50
0.38 / 15
1.52 / 60
0.38 / 15
1.52 / 60
0.38 / 15
1.52 / 60
0.38 / 15
1.52 / 60
0.38 / 15
1.78 / 70
0.38 / 15
1.78 / 70
Instrumentation
Cable
0.38 / 15
2.03 / 80
UL
AWG 18 /7
1
0.38
/ 15
0.89 / 35
Flame Retardant,
Sunlight
Resistant
6.5 / 0.26
0.9
1.27 / 50
2
0.38 / 15
1.27 / 50
10.9 / 0.43
0.9
1.27 / 50
Single & Multi-Triple, PVC-Insulation, Collective Shield, Armor, PVC Jacket
4
0.38 / 15
1.27 / 50
12.4 / 0.49
0.9
1.52 / 60
6
0.38
/
15
1.27
/
50
15.1
/
0.60
1.25
1.52 / 60
RE-Yw(St)YwSWAYw-fl
8
0.38
/
15
1.52
/
60
16.6
/
0.66
1.25
1.78 / 70
Geometrical data
0.38
1.52
/ 60
18.7over
/ 0.74
1.25 RT outer
1.78 jacket
/ 70
No. of 10
RT
of / 15
RT of
inner
Dia.
Dia. of
0.38 / 15
1.52 /160 inner
19.2jacket
/ 0.761 armor wire
1.25
1.78 / 70
elements12
insulation
jacket
16
0.38 / 15
1.52 / 60
21.4
/ 0.85
1.78
nom.
nom.
nom.
nom.1.25
nom./ 70
24
0.38
/
15
1.78
/
70
26.0
/
1.03
1.6
2.03
/ 80
(mm / mils)
(mm / mils)
(mm / in)
(mm)
(mm / mils)
36
0.38 / 15
1.78 / 70
30.8 / 1.22
1.6
2.03 / 80
AWG 20 /7
1
0.30 / 12
0.89 / 35
5.6 / 0.22
0.9
1.02 / 40
2
0.30 / 12
1.02 / 40
8.8 / 0.34
0.9
1.27 / 50
4
0.30 / 12
1.27 / 50
10.4 / 0.41
0.9
1.27 / 50
6
0.30 / 12
1.27 / 50
12.6 / 0.50
0.9
1.52 / 60
8
0.30 / 12
1.27 / 50
13.4 / 0.53
0.9
1.52 / 60
10
0.30 / 12
1.27 / 50
14.9 / 0.59
0.9
1.52 / 60
12
0.30 / 12
1.52 / 60
15.9 / 0.63
1.25
1.52 / 60
16
0.30 / 12
1.52 / 60
17.7 / 0.70
1.25
1.78 / 70
24
0.30 / 12
1.52 / 60
20.8 / 0.82
1.25
1.78 / 70
36
0.30 / 12
1.78 / 70
25.2 / 1.00
1.6
2.03 / 80
RT = Radial Thickness
9.4 / 0.37
13.2 / 0.51
14.8 / 0.58
17.5 / 0.69
18.3 / 0.72
19.8 / 0.78
21.4 / 0.84
23.8 / 0.94
26.9 / 1.06
32.4 / 1.28
194 / 135
319 / 215
421 / 290
560 / 380
616 / 415
706 / 475
910 / 615
1099 / 740
1388 / 945
2070 / 1420
PLTC/ITC
10579840053
C / 300 V
79840054
79840055
79840264
79840056
79840265
Part number
79840057
79840058
Color
79840059
black
79840060
79840061
79840062
79840063
79840262
79840064
79840263
79840065
79840066
79840067
79840068
38
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
For indoor and outdoor installation in cable trays or in raceways. Not recommended for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
STOS (UL) 105 C SUN RES PRODUCTION LOT CODE LENGTH
MARKING IN FEET
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
SWA
(during installation)
steel wire armor
jacket
PVC outer jacket, heat resistant
Min. bending radius - repeated Yw
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
-fl
reduced flame propagation
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
TiMF
triple in metal foil
10 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
200 / 61
60
40
AWG 20
35.8 / 10.92
200 / 61
200 / 61
1
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
39
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 1
nom.
(mm / mils)
Dia. over
inner jacket 1
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 14 /7
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
16.5 / 0.65
18.9 / 0.75
24.0 / 0.94
25.0 / 0.98
28.2 / 1.11
29.2 / 1.15
33.6 / 1.32
40.1 / 1.58
48.7 / 1.92
1.25
1.25
1.25
1.25
1.6
1.6
1.6
2
2.5
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.03 / 80
2.29 / 90
2.54 / 100
22.1 / 0.87
25.0 / 0.98
30.0 / 1.18
31.0 / 1.22
35.4 / 1.39
36.4 / 1.43
40.8 / 1.60
48.6 / 1.91
58.8 / 2.31
871 / 590
1166 / 785
1583 / 1065
1806 / 1215
2346 / 1580
2554 / 1720
3149 / 2120
4575 / 3075
6775 / 4555
79840501
79840502
79840503
79840504
79840505
79840506
79840507
79840508
79840509
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
12.9 / 0.52
15.9 / 0.63
19.6 / 0.77
20.8 / 0.82
23.5 / 0.95
24.2 / 0.97
27.7 / 1.09
33.4 / 1.32
39.7 / 1.57
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.6
2
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
17.8 / 0.71
21.5 / 0.84
25.7 / 1.01
26.9 / 1.06
30.0 / 1.19
30.2 / 1.21
34.9 / 1.38
40.6 / 1.61
48.2 / 1.91
550 / 380
875 / 590
1175 / 790
1370 / 930
1638 / 1105
1691 / 1165
2309 / 1590
3066 / 2065
4426 / 3005
79840069
79840070
79840272
79840071
79840273
79840072
79840073
79840074
79840075
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
11.8 / 0.48
14.1 / 0.56
17.9 / 0.71
19.0 / 0.75
22.9 / 0.85
22.2 / 0.89
25.3 / 1.00
30.0 / 1.19
36.2 / 1.43
0.9
0.9
1.25
1.25
1.25
1.25
1.6
1.6
2
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
16.7 / 0.67
19.0 / 0.75
24.0 / 0.95
25.1 / 0.99
29.0 / 1.09
28.2 / 1.13
32.5 / 1.29
37.2 / 1.47
44.7 / 1.77
486 / 340
634 / 430
1021 / 690
1147 / 775
1328 / 895
1472 / 995
1949 / 1325
2515 / 1690
3724 / 2500
79840076
79840077
79840270
79840078
79840271
79840079
79840080
79840081
79840082
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
10.1 / 0.41
11.9 / 0.47
14.5 / 0.57
16.0 / 0.63
17.9 / 0.70
18.3 / 0.72
19.5 / 0.81
24.9 / 0.98
29.6 / 1.17
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
14.5 / 0.58
16.8 / 0.66
19.4 / 0.76
21.6 / 0.85
24.0 / 0.94
24.4 / 0.96
25.6 / 1.05
30.9 / 1.22
36.9 / 1.45
381 / 265
505 / 345
648 / 435
877 / 595
1025 / 690
1091 / 740
1330 / 870
1703 / 1150
2490 / 1675
79840083
79840084
79840268
79840085
79840269
79840086
79840087
79840088
79840089
AWG 16 /7
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
40
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC*)
OS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(L)
(during installation)
aluminum tape
jacket
PVC outer jacket, heat resistant
Min. bending radius - repeated Yw
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
-fl
reduced flame propagation
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
15 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
190 / 58
160 / 49
200 / 61
180 / 55
150 / 46
0.75
200 / 61
180 / 55
150 / 46
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
41
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
No. of elements
AWG 16 /7
RT of insulation
nom.
(mm / mils)
RT of inner jacket 1
nom.
(mm / mils)
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
0.89 / 35
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
9.6 / 0.35
14.4 / 0.57
16.2 / 0.65
18.6 / 0.73
20.2 / 0.81
22.5 / 0.89
23.2 / 0.91
25.5 / 1.00
30.5 / 1.20
35.3 / 1.39
136 / 95
258 / 170
344 / 230
430 / 290
568 / 370
655 / 445
725 / 490
895 / 605
1290 / 870
1760 / 1185
79970000
79970001
79970002
79970254
79970003
79970255
79970004
79970005
79970006
79970007
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
0.89 / 35
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
9.0 / 0.35
12.7 / 0.50
15.3 / 0.60
17.3 / 0.68
18.0 / 0.71
20.8 / 0.82
21.4 / 0.84
23.4 / 0.92
28.0 / 1.10
32.2 / 1.27
120 / 85
180 / 125
280 / 190
360 / 245
415 / 280
530 / 360
585 / 395
715 / 485
1020 / 690
1380 / 930
79970008
79970009
79970010
79970252
79970011
79970253
79970012
79970013
79970014
79970015
1
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.89 / 35
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
0.89 / 35
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
8.0 / 0.31
11.3 / 0.44
12.5 / 0.49
15.1 / 0.59
15.7 / 0.62
17.1 / 0.67
17.6 / 0.69
20.2 / 0.80
22.9 / 0.90
26.2 / 1.03
95 / 65
145 / 100
190 / 130
275 / 185
310 / 210
355 / 240
395 / 270
520 / 350
675 / 455
915 / 615
79970016
79970017
79970018
79970250
79970019
79970251
79970020
79970021
79970022
79970023
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
42
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
SPOS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE
LENGTH MARKING IN FEET
Technical data
Flame propagation
Temperature range
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
15 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
Abbreviations
REYw
(St)
Yw
(L)
Yw
-fl
PiMF
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC inner jacket, heat resistant
aluminum tape
PVC outer jacket, heat resistant
reduced flame propagation
pair in metal foil
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
200 / 61
200 / 61
0.75
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
43
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
No. of elements
AWG 16 /7
RT of insulation
nom.
(mm / mils)
RT of inner jacket 1
nom.
(mm / mils)
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
16.0 / 0.63
18.1 / 0.71
21.7 / 0.85
22.7 / 0.89
25.1 / 0.99
25.9 / 1.02
29.8 / 1.17
34.3 / 1.35
40.9 / 1.61
285 / 195
390 / 265
560 / 380
650 / 440
770 / 520
855 / 575
1130 / 760
1525 / 1025
2190 / 1475
79970024
79970025
79970260
79970026
79970261
79970027
79970028
79970029
79970030
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
15.1 / 0.59
17.0 / 0.67
20.3 / 0.80
21.3 / 0.84
23.4 / 0.92
24.1 / 0.95
27.7 / 1.09
31.8 / 1.25
37.8 / 1.49
250 / 170
330 / 225
480 / 325
555 / 375
650 / 440
710 / 480
940 / 635
1260 / 850
1800 / 1210
79970031
79970032
79970258
79970033
79970259
79970034
79970035
79970036
79970037
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
12.5 / 0.49
15.0 / 0.59
16.9 / 0.67
17.6 / 0.69
20.3 / 0.80
20.9 / 0.82
22.9 / 0.90
26.1 / 1.03
31.4 / 1.24
192 / 120
260 / 175
330 / 225
375 / 255
485 / 330
525 / 355
640 / 430
845 / 570
1220 / 820
79970038
79970039
79970256
79970040
79970257
79970041
79970042
79970043
79970044
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
44
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC*)
OS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(L)
(during installation)
aluminum tape
jacket
PVC outer jacket, heat resistant
Min. bending radius - repeated Yw
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
-fl
reduced flame propagation
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
15 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
190 / 58
160 / 49
200 / 61
180 / 55
150 / 46
0.75
200 / 61
180 / 55
150 / 46
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
45
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
No. of elements
AWG 16 /7
RT of insulation
nom.
(mm / mils)
RT of inner jacket 1
nom.
(mm / mils)
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.02 / 40
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
1.02 / 40
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
10.5 / 0.41
15.7 / 0.62
17.5 / 0.69
21.6 / 0.85
22.7 / 0.89
25.0 / 0.98
25.5 / 1.00
29.4 / 1.16
33.8 / 1.33
40.3 / 1.59
165 / 115
300 / 205
415 / 280
610 / 410
720 / 485
860 / 580
960 / 645
1270 / 855
1735 / 1170
2505 / 1685
79970045
79970046
79970047
79970266
79970048
79970267
79970049
79970050
79970051
79970052
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
0.89 / 35
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
9.6 / 0.38
14.6 / 0.57
16.3 / 0.64
19.0 / 0.75
21.0 / 0.83
23.0 / 0.91
23.5 / 0.93
25.8 / 1.02
31.0 / 1.22
35.8 / 1.41
130 / 90
255 / 175
340 / 230
460 / 310
580 / 390
685 / 465
760 / 515
945 / 635
1360 / 915
1865 / 1255
79970053
79970054
79970055
79970264
79970056
79970265
79970057
79970058
79970059
79970060
1
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.89 / 35
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
0.89 / 35
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
8.7 / 0.34
12.0 / 0.47
14.3 / 0.56
16.5 / 0.65
17.3 / 0.68
18.8 / 0.74
20.2 / 0.80
22.1 / 0.87
25.2 / 0.99
30.2 / 1.19
100 / 70
170 / 115
260 / 175
340 / 230
390 / 265
455 / 310
550 / 370
665 / 450
890 / 600
1280 / 860
79970061
79970062
79970063
79970262
79970064
79970263
79970065
79970066
79970067
79970068
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
46
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
STOS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE
LENGTH MARKING IN FEET
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(L)
(during installation)
aluminum tape
jacket
PVC outer jacket, heat resistant
Min. bending radius - repeated Yw
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
-fl
reduced flame propagation
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
TiMF
triple in metal foil
15 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
200 / 61
200 / 61
0.75
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
47
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
No. of elements
AWG 16 /7
RT of insulation
nom.
(mm / mils)
RT of inner jacket 1
nom.
(mm / mils)
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
17.1 / 0.67
20.2 / 0.80
23.9 / 0.94
25.2 / 0.99
29.0 / 1.14
29.6 / 1.17
32.7 / 1.29
38.9 / 1.53
45.2 / 1.78
335 / 230
515 / 350
700 / 475
830 / 560
1055 / 710
1160 / 780
1445 / 975
2075 / 1395
2860 / 1925
79970069
79970070
79970272
79970071
79970273
79970072
79970073
79970074
79970075
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
16.1 / 0.63
18.0 / 0.71
22.3 / 0.88
23.4 / 0.92
25.8 / 1.02
27.6 / 1.09
30.3 / 1.19
35.0 / 1.38
41.7 / 1.64
290 / 195
395 / 270
585 / 395
685 / 465
810 / 545
960 / 645
1180 / 795
1600 / 1075
2300 / 1550
79970076
79970077
79970270
79970078
79970271
79970079
79970080
79970081
79970082
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
14.2 / 0.56
15.8 / 0.62
18.4 / 0.72
20.4 / 0.80
22.2 / 0.87
22.7 / 0.89
24.9 / 0.98
29.9 / 1.18
34.5 / 1.36
230 / 155
300 / 205
390 / 265
510 / 345
590 / 400
645 / 435
790 / 535
1130 / 760
1530 / 1030
79970083
79970084
79970268
79970085
79970269
79970086
79970087
79970088
79970089
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
48
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
Application
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Inner jacket 2........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC*)
OS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(L)
(during installation)
aluminum tape
jacket
PVC inner jacket, heat resistant
Min. bending radius - repeated Yw
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
SWA
steel wire armor
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
Yw
PVC outer jacket, heat resistant
15 x cable diameter
Oil resistance
ICEA S-73-532
-fl
reduced flame propagation
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
190 / 58
160 / 49
200 / 61
180 / 55
150 / 46
0.75
200 / 61
180 / 55
150 / 46
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
49
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 2
nom.
(mm / mils)
Dia. over
inner jacket 2
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 16 /7
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
9.4 / 0.37
14.0 / 0.55
16.0 / 0.63
18.2 / 0.72
20.1 / 0.79
22.1 / 0.87
22.8 / 0.90
25.1 / 0.99
29.9 / 1.18
34.7 / 1.37
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.6
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
13.6 / 0.54
18.7 / 0.74
21.4 / 0.84
24.2 / 0.95
26.5 / 1.03
28.1 / 1.10
28.8 / 1.13
31.1 / 1.22
37.2 / 1.46
42.5 / 1.67
370 / 250
620 / 420
875 / 590
1070 / 720
1255 / 845
1415 / 950
1534 / 1020
1915 / 1290
2525 / 1695
3250 / 2185
79980000
79980001
79980002
79980254
79980003
79980255
79980004
79980005
79980006
79980007
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
8.9 / 0.35
12.5 / 0.49
14.9 / 0.59
16.8 / 0.66
17.6 / 0.69
20.5 / 0.81
20.7 / 0.81
22.8 / 0.90
26.1 / 1.03
31.6 / 1.24
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
13.1 / 0.52
17.2 / 0.68
19.6 / 0.77
22.8 / 0.90
23.6 / 0.93
26.5 / 1.04
26.7 / 1.05
28.8 / 1.13
33.3 / 1.31
38.9 / 1.53
345 / 235
530 / 355
675 / 455
950 / 640
1040 / 700
1250 / 840
1305 / 880
1505 / 1010
2145 / 1445
2775 / 1865
79980008
79980009
79980010
79980252
79980011
79980253
79980012
79980013
79980014
79980015
1
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.89 / 35
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
8.0 / 0.31
10.7 / 0.42
11.8 / 0.46
14.4 / 0.57
15.0 / 0.59
16.4 / 0.64
17.2 / 0.68
18.7 / 0.74
22.5 / 0.89
25.8 / 1.01
0.9
0.9
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.6
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
12.2 / 0.48
14.9 / 0.59
16.5 / 0.65
19.1 / 0.75
19.7 / 0.78
21.8 / 0.86
23.2 / 0.91
24.7 / 0.97
28.5 / 1.12
33.0 / 1.30
305 / 205
425 / 290
505 / 340
660 / 445
700 / 470
905 / 610
1000 / 670
1130 / 760
1455 / 975
2005 / 1350
79980016
79980017
79980018
79980250
79980019
79980251
79980020
79980021
79980022
79980023
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
50
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Inner jacket 2........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
SPOS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE
LENGTH MARKING IN FEET
Technical data
Flame propagation
Temperature range
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
15 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
Abbreviations
REYw
(St)
Yw
(L)
Yw
SWA
Yw
-fl
PiMF
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC inner jacket, heat resistant
aluminum tape
PVC inner jacket, heat resistant
steel wire armor
PVC outer jacket, heat resistant
reduced flame propagation
pair in metal foil
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
200 / 61
200 / 61
0.75
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
51
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 2
nom.
(mm / mils)
Dia. over
inner jacket 2
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 16 /7
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
16.1 / 0.63
17.7 / 0.70
21.3 / 0.84
22.3 / 0.88
24.7 / 0.97
25.5 / 1.00
29.2 / 1.15
33.7 / 1.33
40.3 / 1.59
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.6
2
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
2.29 / 90
21.5 / 0.85
23.7 / 0.93
27.3 / 1.07
28.3 / 1.11
30.7 / 1.21
32.7 / 1.29
36.5 / 1.44
41.5 / 1.63
48.9 / 1.92
835 / 560
1010 / 680
1310 / 880
1430 / 960
1625 / 1090
1975 / 1330
2420 / 1630
3030 / 2035
4110 / 2765
79980024
79980025
79980260
79980026
79980261
79980027
79980028
79980029
79980030
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
14.9 / 0.59
16.6 / 0.65
19.9 / 0.78
20.9 / 0.82
23.0 / 0.90
23.7 / 0.93
27.1 / 1.07
31.2 / 1.23
37.2 / 1.47
1.25
1.25
1.25
1.25
1.25
1.25
1.6
1.6
2
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
19.6 / 0.77
22.0 / 0.87
25.9 / 1.02
26.9 / 1.06
29.6 / 1.17
29.7 / 1.17
34.4 / 1.35
38.5 / 1.51
45.8 / 1.80
650 / 440
890 / 600
1175 / 790
1290 / 870
1470 / 990
1535 / 1030
2110 / 1420
2400 / 1615
3770 / 2535
79980031
79980032
79980258
79980033
79980259
79980034
79980035
79980036
79980037
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
12.4 / 0.49
16.6 / 0.65
16.7 / 0.66
17.5 / 0.69
20.3 / 0.80
20.8 / 0.82
22.8 / 0.90
26.2 / 1.03
31.4 / 1.24
0.9
1.25
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
17.1 / 0.67
22.0 / 0.87
22.7 / 0.89
23.5 / 0.92
26.3 / 1.03
26.7 / 1.05
28.8 / 1.13
33.4 / 1.31
38.7 / 1.52
515 / 350
845 / 565
920 / 620
995 / 670
1195 / 805
1264 / 845
1435 / 965
1975 / 1330
2565 / 1725
79980038
79980039
79980256
79980040
79980257
79980041
79980042
79980043
79980044
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
52
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Inner jacket 2........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC*)
OS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE LENGTH
MARKING IN FEET
*)
single element design without com wire
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(L)
(during installation)
aluminum tape
jacket
PVC inner jacket, heat resistant
Min. bending radius - repeated Yw
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
SWA
steel wire armor
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
Yw
PVC outer jacket, heat resistant
15 x cable diameter
Oil resistance
ICEA S-73-532
-fl
reduced flame propagation
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
190 / 58
160 / 49
200 / 61
180 / 55
150 / 46
0.75
200 / 61
180 / 55
150 / 46
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
53
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 2
nom.
(mm / mils)
Dia. over
inner jacket 2
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 16 /7
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.02 / 40
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
10.2 / 0.40
15.3 / 0.60
17.1 / 0.67
21.2 / 0.83
22.3 / 0.88
24.6 / 0.97
25.2 / 0.99
28.8 / 1.13
33.2 / 1.31
39.7 / 1.56
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.6
2
1.27 / 50
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.03 / 80
2.29 / 90
10.2 / 0.40
15.3 / 0.60
17.1 / 0.67
21.2 / 0.83
22.3 / 0.88
24.6 / 0.97
25.2 / 0.99
28.8 / 1.13
33.2 / 1.31
39.7 / 1.56
420 / 285
815 / 550
1015 / 680
1340 / 905
1490 / 1005
1705 / 1150
2050 / 1380
2520 / 1695
3150 / 2115
4595 / 3085
79980045
79980046
79980047
79980266
79980048
79980267
79980049
79980050
79980051
79980052
1
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
9.2 / 0.36
14.4 / 0.57
15.9 / 0.63
19.6 / 0.77
20.6 / 0.81
22.6 / 0.89
23.1 / 0.91
25.4 / 1.00
30.4 / 1.20
35.2 / 1.39
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.6
1.6
2
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.29 / 90
9.2 / 0.36
14.4 / 0.57
15.9 / 0.63
19.6 / 0.77
20.6 / 0.81
22.6 / 0.89
23.1 / 0.91
25.4 / 1.00
30.4 / 1.20
35.2 / 1.39
365 / 245
635 / 430
870 / 585
1180 / 795
1300 / 875
1465 / 985
1555 / 1045
2050 / 1380
2660 / 1790
3705 / 2490
79980053
79980054
79980055
79980264
79980056
79980265
79980057
79980058
79980059
79980060
1
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.89 / 35
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
8.3 / 0.33
11.8 / 0.46
13.9 / 0.55
16.1 / 0.63
16.9 / 0.66
18.4 / 0.72
18.8 / 0.74
21.7 / 0.85
24.8 / 0.98
29.6 / 1.17
0.9
0.9
0.9
1.25
1.25
1.25
1.25
1.25
1.25
1.6
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
8.3 / 0.33
11.8 / 0.46
13.9 / 0.55
16.1 / 0.63
16.9 / 0.66
18.4 / 0.72
18.8 / 0.74
21.7 / 0.85
24.8 / 0.98
29.6 / 1.17
320 / 215
490 / 330
630 / 425
875 / 590
980 / 660
1090 / 735
1155 / 775
1415 / 950
1740 / 1170
2560 / 1720
79980061
79980062
79980063
79980262
79980064
79980263
79980065
79980066
79980067
79980068
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
54
www.leoni-industrial-projects.com
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 16 , AWG 18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C), black
Metallic jacket.......................... aluminum tape, longitudinally overlapped and seamed
Inner jacket 2........................... heat resistant polyvinyl chloride PVC (105 C), black
Armor....................................... galvanized round steel wires
Communication element.......... stranded plain annealed copper wire, size AWG 22, PVC insulated,
colored orange
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG + 1C 22 AWG PVC/PVC
STOS (UL) 105 C SUN RES DIR BUR PRODUCTION LOT CODE
LENGTH MARKING IN FEET
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC inner jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(L)
(during installation)
aluminum tape
jacket
PVC inner jacket, heat resistant
Min. bending radius - repeated Yw
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
SWA
steel wire armor
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
Yw
PVC outer jacket, heat resistant
15 x cable diameter
Oil resistance
ICEA S-73-532
-fl
reduced flame propagation
Sunlight resistance
UL 1581 section 1200
TiMF
triple in metal foil
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 16
14.3 / 4.36
AWG 18
22.8 / 6.93
30.5 / 100 (at 15.6 C)
AWG 20
35.8 / 10.92
200 / 61
200 / 61
200 / 61
0.75
40
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
55
UL 13 / UL 2250
Instrumentation Cable
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 2
nom.
(mm / mils)
Dia. over
inner jacket 2
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 16 /7
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
16.6 / 0.65
18.4 / 0.72
23.6 / 0.93
24.6 / 0.97
28.4 / 1.12
29.0 / 1.14
32.1 / 1.26
38.3 / 1.51
45.2 / 1.78
1.25
1.25
1.25
1.6
1.6
1.6
1.6
2
2.5
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.29 / 90
2.54 / 100
22.6 / 0.89
24.4 / 0.96
29.6 / 1.16
30.6 / 1.20
35.7 / 1.40
36.3 / 1.43
39.4 / 1.55
46.9 / 1.85
55.3 / 2.18
915 / 615
1100 / 740
1515 / 1020
1844 / 1125
2290 / 1540
2420 / 1625
2815 / 1890
4055 / 2725
5745 / 3860
79980069
79980070
79980272
79980071
79980273
79980072
79980073
79980074
79980075
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
2.03 / 80
16.0 / 0.63
17.7 / 0.70
22.0 / 0.87
23.1 / 0.91
25.5 / 1.00
26.1 / 1.03
29.8 / 1.17
34.5 / 1.36
41.2 / 1.62
1.25
1.25
1.25
1.25
1.6
1.6
1.6
1.6
2
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.03 / 80
2.03 / 80
2.29 / 90
2.29 / 90
21.4 / 0.84
23.7 / 0.93
28.0 / 1.10
29.1 / 1.14
32.7 / 1.29
33.3 / 1.31
25.4 / 1.46
42.3 / 1.66
49.8 / 1.96
830 / 560
1020 / 685
1355 / 910
1480 / 995
1965 / 1320
2035 / 1370
2465 / 1655
3120 / 2095
4265 / 2870
79980076
79980077
79980270
79980078
79980271
79980079
79980080
79980081
79980082
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
14.1 / 0.55
15.5 / 0.61
18.1 / 0.71
20.1 / 0.79
22.0 / 0.87
22.4 / 0.88
24.7 / 0.97
29.4 / 1.16
34.0 / 1.34
0.9
1.25
1.25
1.25
1.25
1.25
1.25
1.6
1.6
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
1.78 / 70
2.03 / 80
2.29 / 90
18.8 / 0.74
21.1 / 0.83
24.4 / 0.96
26.1 / 1.03
28.0 / 1.10
28.4 / 1.12
30.7 / 1.21
36.7 / 1.44
41.8 / 1.64
610 / 410
830 / 560
1040 / 700
1210 / 815
1370 / 920
1425 / 960
1650 / 1110
2400 / 1615
3040 / 2045
79980083
79980084
79980268
79980085
79980269
79980086
79980087
79980088
79980089
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
56
www.leoni-industrial-projects.com
UL 1277
Instrumentation Cable
TC
90 C / 600 V
UL-listed tray cable in compliance with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG 18
Insulation.................................. heat resistant polyvinyl chloride PVC (90 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Outer jacket.............................. heat resistant polyvinyl chloride PVC (90 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON TC nE mAWG OS UL THHW*) 600V 90 C (194
F) SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING
IN FEET
*)
90 C DRY / 75 C WET (AWG 16, 18)
Technical data
Flame propagation
Temperature range
- Test on single cable
UL 1581, sec. 1080 (VW-1 test)
-40C up to +90C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
Abbreviations
REYw
(St)
Yw
-fl
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC outer jacket, heat resistant
reduced flame propagation
AWG 14
8.9 / 2.72
AWG 16
14.3 / 4.36
175 / 570 (at 15 C)
AWG 18
22.8 / 6.93
170 / 52
155 / 48
125 / 39
170 / 52
155 / 48
125 / 39
0.7
40
2000
170 / 52
155 / 48
125 / 39
60
2000
Operating voltage
600
25
www.leoni-industrial-projects.com
57
UL 1277
Instrumentation Cable
TC
90 C / 600 V
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
1
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.14 / 45
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
9.4 / 0.37
14.8 / 0.58
17.2 / 0.68
20.5 / 0.81
23.0 / 0.91
26.0 / 1.02
27.2 / 1.07
30.8 / 1.21
36.7 / 1.44
46.0 / 1.81
118 / 80
255 / 165
368 / 245
525 / 350
698 / 460
847 / 575
978 / 665
1261 / 835
1775 / 1180
2749 / 1850
7996C320
7996C321
7996C322
7996C323
7996C324
79030067
7996C325
7996C326
7996C328
7996C418
1
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.14 / 45
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
8.6 / 0.34
12.8 / 0.50
15.6 / 0.61
18.5 / 0.73
19.7 / 0.78
23.5 / 0.93
24.6 / 0.97
27.7 / 1.09
33.0 / 1.30
39.9 / 1.57
95 / 65
181 / 120
284 / 190
401 / 270
480 / 320
643 / 440
734 / 485
965 / 620
1307 / 865
1877 / 1270
7996C310
7996C311
7996C312
7996C313
7996C314
7996C425
7996C315
7996C316
7996C318
7996C426
1
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.14 / 45
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
8.1 / 0.32
11.9 / 0.47
14.5 / 0.57
17.2 / 0.68
18.3 / 0.72
21.9 / 0.86
22.8 / 0.90
25.7 / 1.01
30.5 / 1.20
36.8 / 1.45
82 / 60
151 / 105
236 / 165
332 / 220
390 / 265
529 / 360
599 / 395
760 / 515
1050 / 695
1494 / 1015
7996C300
7996C301
7996C302
7996C303
7996C304
7996C433
7996C305
7996C306
7996C308
7996C434
AWG 16 /7
AWG 18 /7
RT = Radial Thickness
58
www.leoni-industrial-projects.com
UL 1277
Instrumentation Cable
TC
90 C / 600 V
UL-listed tray cable in compliance with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG 18
Insulation.................................. heat resistant polyvinyl chloride PVC (90 C)
Color code................................ black, white, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Outer jacket.............................. heat resistant polyvinyl chloride PVC (90 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON TC nE mAWG SPOS UL THHW*) 600V 90 C (194
F) SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING
IN FEET
*)
90 C DRY / 75 C WET (AWG 16, 18)
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL 1581, sec. 1080 (VW-1 test)
-40C up to +90C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC outer jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
-fl
(during installation)
reduced flame propagation
jacket
pair in metal foil
Min. bending radius - repeated PiMF
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
AWG 16
14.3 / 4.36
175 / 570 (at 15 C)
AWG 18
22.8 / 6.93
170 / 52
170 / 52
170 / 52
60
0.7
40
2000
25
2000
Operating voltage
600
www.leoni-industrial-projects.com
59
UL 1277
Instrumentation Cable
TC
90 C / 600 V
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
16.3 / 0.64
19.0 / 0.75
23.9 / 0.94
25.5 / 1.00
28.9 / 1.15
30.3 / 1.19
34.3 / 1.35
41.0 / 1.61
51.4 / 2.05
295 / 195
450 / 295
708 / 445
852 / 565
1031 / 705
1167 / 755
1506 / 975
2159 / 1400
3294 / 2235
7996C350
7996C351
7996C352
7996C353
7996C419
7996C354
7996C355
7996C357
7996C420
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
14.8 / 0.58
17.2 / 0.68
20.5 / 0.81
23.0 / 0.91
26.0 / 1.02
27.2 / 1.07
30.8 / 1.21
36.7 / 1.44
46.0 / 1.81
234 / 160
332 / 215
466 / 305
651 / 415
771 / 525
860 / 575
1104 / 720
1562 / 1025
2396 / 1620
7996C340
7996C341
7996C342
7996C343
7996C427
7996C344
7996C345
7996C347
7996C428
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
13.9 / 0.55
16.1 / 0.63
19.2 / 0.76
20.5 / 0.81
24.4 / 0.96
25.5 / 1.00
28.7 / 1.13
34.2 / 1.35
41.4 / 1.63
202 / 135
281 / 185
396 / 260
485 / 320
650 / 445
724 / 475
923 / 600
1294 / 845
1832 / 1235
7996C330
7996C331
7996C332
7996C333
7996C436
7996C334
7996C335
7996C337
7996C437
AWG 16 /7
AWG 18 /7
RT = Radial Thickness
60
www.leoni-industrial-projects.com
UL 1277
Instrumentation Cable
TC
90 C / 600 V
UL-listed tray cable in compliance with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG 18
Insulation.................................. heat resistant polyvinyl chloride PVC (90 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Outer jacket.............................. heat resistant polyvinyl chloride PVC (90 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON TC nE mAWG OS UL THHW*) 600V 90 C (194
F) SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING
IN FEET
*)
90 C DRY / 75 C WET (AWG 16, 18)
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL 1581, sec. 1080 (VW-1 test)
-40C up to +90C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC outer jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
-fl
(during installation)
reduced flame propagation
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
Mutual capacitance
single element:
2 to 4 elements:
above 4 elements:
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
min.
nom.
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
AWG 16
14.3 / 4.36
175 / 570 (at 15 C)
AWG 18
22.8 / 6.93
170 / 52
155 / 48
125 / 39
170 / 52
155 / 48
125 / 39
0.7
40
2000
170 / 52
155 / 48
125 / 39
60
2000
Operating voltage
600
25
www.leoni-industrial-projects.com
61
UL 1277
Instrumentation Cable
TC
90 C / 600 V
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
1
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
9.9 / 0.39
16.4 / 0.65
18.8 / 0.74
24.7 / 0.97
26.4 / 1.04
29.8 / 1.17
30.7 / 1.21
34.8 / 1.37
41.6 / 1.64
52.2 / 2.06
150 / 105
329 / 225
506 / 345
795 / 540
973 / 660
1183 / 805
1369 / 925
1775 / 1200
2536 / 1715
3894 / 2630
7996C380
7996C381
7996C382
7996C383
7996C384
7996C421
7996C385
7996C386
7996C388
7996C422
1
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
9.0 / 0.35
14.9 / 0.59
17.1 / 0.67
22.3 / 0.88
23.8 / 0.94
26.8 / 1.06
27.7 / 1.09
31.3 / 1.23
37.4 / 1.47
46.8 / 1.84
115 / 90
260 / 175
380 / 260
604 / 410
728 / 480
883 / 600
1012 / 670
1303 / 860
1843 / 1220
2849 / 1925
7996C370
7996C371
7996C372
7996C373
7996C374
7996C429
7996C375
7996C376
7996C378
7996C430
1
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
8.5 / 0.33
13.9 / 0.55
15.9 / 0.63
19.7 / 0.78
22.1 / 0.87
24.9 / 0.98
25.7 / 1.01
29.0 / 1.14
34.5 / 1.36
41.8 / 1.65
100 / 75
218 / 150
311 / 215
447 / 305
592 / 400
714 / 485
815 / 555
1044 / 710
1457 / 985
2098 / 1415
7996C360
7996C361
7996C362
7996C363
7996C364
7996C439
7996C365
7996C366
7996C368
7996C440
AWG 16 /7
AWG 18 /7
RT = Radial Thickness
62
www.leoni-industrial-projects.com
UL 1277
Instrumentation Cable
TC
90 C / 600 V
UL-listed tray cable in compliance with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG 18
Insulation.................................. heat resistant polyvinyl chloride PVC (90 C)
Color code................................ black, white, red, continuously numbered on white core (1, 2, 3..) for multielement
Individual shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Outer jacket.............................. heat resistant polyvinyl chloride PVC (90 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON TC nE mAWG STOS UL THHW*) 600V 90 C (194
F) SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING
IN FEET
*)
90 C DRY / 75 C WET (AWG 16, 18)
Technical data
Abbreviations
REInstrumentation Cable
Flame propagation
Temperature range
Yw
PVC insulation, heat resistant
- Test on single cable
UL 1581, sec. 1080 (VW-1 test)
-40C up to +90C
(St)
collective shield
(during
operation)
- Test on bunched cables
UL 1685 (vertical tray)
Yw
PVC outer jacket, heat resistant
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
-fl
(during installation)
reduced flame propagation
jacket
triple in metal foil
Min. bending radius - repeated TiMF
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
7.5 x cable diameter
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
AWG 16
14.3 / 4.36
175 / 570 (at 15 C)
AWG 18
22.8 / 6.93
170 / 52
170 / 52
170 / 52
60
0.7
40
2000
25
2000
Operating voltage
600
www.leoni-industrial-projects.com
63
UL 1277
Instrumentation Cable
TC
90 C / 600 V
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
2.79 / 110
18.0 / 0.71
21.9 / 0.86
27.2 / 1.07
29.1 / 1.15
32.9 / 1.30
34.0 / 1.34
38.6 / 1.52
47.8 / 1.88
57.9 / 2.28
371 / 245
634 / 410
904 / 585
1132 / 740
1370 / 925
1565 / 1020
2029 / 1325
3112 / 2030
4456 / 3010
7996C410
7996C411
7996C412
7996C413
7996C423
7996C414
7996C415
7996C417
7996C424
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
16.3 / 0.64
18.7 / 0.74
24.5 / 0.96
26.2 / 1.03
29.5 / 1.16
30.5 / 1.20
34.6 / 1.36
41.3 / 1.63
51.8 / 2.04
289 / 195
427 / 290
681 / 460
841 / 565
1015 / 690
1144 / 770
1475 / 965
2107 / 1385
3225 / 2180
7996C400
7996C401
7996C402
7996C403
7996C431
7996C404
7996C405
7996C407
7996C432
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.03 / 80
2.79 / 110
15.3 / 0.60
17.5 / 0.69
22.9 / 0.90
24.5 / 0.96
27.6 / 1.09
28.5 / 1.12
32.2 / 1.27
38.5 / 1.52
48.2 / 1.90
250 / 170
357 / 245
571 / 375
700 / 475
845 / 570
942 / 615
1207 / 790
1715 / 1125
2628 / 1775
7996C390
7996C391
7996C392
7996C393
7996C441
7996C394
7996C395
7996C397
7996C442
AWG 16 /7
AWG 18 /7
RT = Radial Thickness
64
www.leoni-industrial-projects.com
UL 13 / UL 2250
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, continuously numbered
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC OS (UL) 105 C
SUN RES PRODUCTION LOT CODE LENGTH MARKING IN FEET
Technical data
Flame propagation
- Test on single cable
- Test on bunched cables
Gas/vapor tightness outer
jacket
Limiting Oxygen Index (LOI)
Flammability temperature (FT)
Oil resistance
Sunlight resistance
Abbreviations
UL13 (VW-1)
UL 1685 (vertical tray)
NEC 501.15 (D) and (E)
ASTM D 2863 (min. 30 %)
ISO 4589-3 ann. A (min. +250 C)
ICEA S-73-532
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
Temperature range
-40C up to +105C
(during operation)
-5C up to +50C
(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
REYw
(St)
Yw
-fl
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
200 / 61
60
40
AWG 20
35.8 / 10.92
200 / 61
200 / 61
1
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
65
UL 13 / UL 2250
PLTC/ITC
105 C / 300 V
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 70
8.2 / 0.32
9.3 / 0.37
11.5 / 0.45
12.6 / 0.49
14.4 / 0.57
14.9 / 0.59
16.9 / 0.67
20.7 / 0.82
24.2 / 0.95
109 / 75
162 / 110
241 / 165
303 / 205
365 / 250
417 / 285
554 / 375
794 / 335
1156 / 780
79960666
79960667
79960668
79960669
79960670
79960671
79960672
79960673
79960674
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.02 / 40
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
7.2 / 0.28
7.8 / 0.33
9.1 / 0.36
11.0 / 0.45
11.8 / 0.48
12.2 / 0.50
13.4 / 0.55
16.8 / 0.67
19.0 / 0.75
78 / 55
117 / 80
152 / 105
208 / 140
246 / 170
270 / 190
352 / 240
516 / 350
719 / 485
79960546
79960547
79960548
79960549
79960550
79960551
79960552
79960553
79960554
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
6.2 / 0.25
7.2 / 0.30
8.3 / 0.32
9.0 / 0.41
10.8 / 0.43
11.1 / 0.45
12.2 / 0.50
14.7 / 0.59
17.1 / 0.67
59 / 40
85 / 65
119 / 80
143 / 115
192 / 130
217 / 150
271 / 185
374 / 255
541 / 365
79960555
79960556
79960557
79960558
79960559
79960560
79960561
79960562
79960563
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.89 / 35
0.89 / 35
0.89 / 35
1.02 / 40
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
5.3 / 0.22
6.0 / 0.24
6.8 / 0.27
8.2 / 0.32
8.8 / 0.35
8.9 / 0.36
10.6 / 0.42
12.4 / 0.49
13.8 / 0.49
39 / 35
56 / 45
85 / 55
110 / 75
125 / 85
132 / 95
190 / 130
255 / 175
345 / 235
79960564
79960565
79960566
79960567
79960568
79960569
79960570
79960571
79960572
AWG 16 /7
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
66
www.leoni-industrial-projects.com
UL 13 / UL 2250
PLTC/ITC
105 C / 300 V
UL-listed power limited tray cable in compliance with NEC article 725.154, for use in hazardous classified locations class I and class II division 2 acc. to
NEC 501.10(B) and NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct burial.
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG
18 , AWG 20
Insulation.................................. heat resistant polyvinyl chloride PVC (105 C)
Color code................................ black, continuously numbered
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Inner jacket 1........................... heat resistant polyvinyl chloride PVC (105 C)
Armor....................................... galvanized round steel wires
Outer jacket.............................. heat resistant polyvinyl chloride PVC (105 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON PLTC/ITC nE mAWG PVC/PVC OS (UL) 105 C
SUN RES PRODUCTION LOT CODE LENGTH MARKING IN FEET
Technical data
Flame propagation
Temperature range
- Test on single cable
UL13 (VW-1)
-40C up to +105C
(during operation)
- Test on bunched cables
UL 1685 (vertical tray)
-5C up to +50C
Gas/vapor tightness outer
NEC 501.15 (D) and (E)
(during installation)
jacket
Min. bending radius - repeated
Limiting Oxygen Index (LOI) ASTM D 2863 (min. 30 %)
bending
Flammability temperature (FT) ISO 4589-3 ann. A (min. +250 C)
10 x cable diameter
Oil resistance
ICEA S-73-532
Sunlight resistance
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
AWG 14
8.9 / 2.72
Abbreviations
REYw
(St)
Yw
SWA
Yw
-fl
AWG 16
AWG 18
14.3 / 4.36
22.8 / 6.93
30.5 / 100 (at 15.6 C)
200 / 61
200 / 61
60
40
AWG 20
35.8 / 10.92
200 / 61
200 / 61
1
25
1500
1500
Operating voltage
300
www.leoni-industrial-projects.com
67
UL 13 / UL 2250
PLTC/ITC
105 C / 300 V
RT of
insulation
nom.
(mm / mils)
RT of inner
jacket 1
nom.
(mm / mils)
Dia. over
inner jacket 1
nom.
(mm / in)
Dia. of
armor wire
nom.
(mm)
RT outer jacket
Outer dia.
Weight
Part number
nom.
(mm / mils)
approx.
(mm / in)
approx.
(kg/km /
lbs/1000ft)
Color
black
AWG 14 /7
2
4
6
8
10
12
16
24
36
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
0.51 / 20
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.78 / 60
8.2 / 0.32
9.3 / 0.37
11.5 / 0.45
12.5 / 0.49
14.4 / 0.57
14.9 / 0.59
16.9 / 0.67
20.7 / 0.82
24.7 / 0.97
0.9
0.9
0.9
0.9
0.9
0.9
1.25
1.25
1.25
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
1.78 / 70
12.6 / 0.49
13.7 / 0.54
16.4 / 0.64
17.4 / 0.68
19.3 / 0.76
19.8 / 0.78
23.0 / 0.90
26.8 / 1.05
30.7 / 1.21
320 / 215
399 / 270
554 / 375
635 / 430
741 / 500
806 / 545
1143 / 770
1501 / 1010
1991 / 1340
79840510
79840511
79840512
79840513
79840514
79840515
79840516
79840517
79840518
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
1.02 / 40
1.02 / 40
1.02 / 40
1.27 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
7.2 / 0.30
7.8 / 0.30
9.0 / 0.40
11.0 / 0.50
11.8 / 0.50
12.2 / 0.50
13.4 / 0.60
16.8 / 0.70
19.0 / 0.80
0.9
0.9
0.9
0.9
0.9
0.9
0.9
1.25
1.25
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
1.78 / 70
11.6 / 0.45
12.2 / 0.50
13.4 / 0.53
15.9 / 0.64
16.7 / 0.67
17.1 / 0.69
18.3 / 0.74
22.9 / 0.91
25.1 / 0.99
268 / 185
313 / 225
378 / 260
501 / 345
557 / 385
614 / 415
697 / 485
1106 / 745
1371 / 925
79840440
79840441
79840442
79840443
79840444
79840445
79840446
79840447
79840448
2
4
6
8
10
12
16
24
36
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.38 / 15
0.89 / 35
1.02 / 40
1.02 / 40
1.02 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
6.2 / 0.30
7.2 / 0.30
8.3 / 0.30
9.0 / 0.40
10.8 / 0.40
11.1 / 0.50
12.2 / 0.50
14.7 / 0.60
17.2 / 0.70
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
1.25
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
1.78 / 70
10.5 / 0.41
11.6 / 0.47
12.7 / 0.49
13.4 / 0.58
15.2 / 0.62
16.0 / 0.64
17.1 / 0.69
19.6 / 0.78
23.3 / 0.91
226 / 155
276 / 195
331 / 225
423 / 285
455 / 330
528 / 355
610 / 410
749 / 515
1129 / 765
79840449
79840450
79840451
79840452
79840453
79840454
79840455
79840456
79840457
2
4
6
8
10
12
16
24
36
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.30 / 12
0.89 / 35
0.89 / 35
1.02 / 35
1.02 / 40
1.02 / 40
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
5.3 / 0.20
6.0 / 0.20
7.1 / 0.30
7.6 / 0.30
8.6 / 0.40
8.9 / 0.40
10.2 / 0.40
12.3 / 0.50
13.8 / 0.50
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
1.02 / 40
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.27 / 50
1.52 / 60
1.52 / 60
9.1 / 0.36
10.3 / 0.41
11.5 / 0.43
12.0 / 0.49
13.0 / 0.52
13.3 / 0.53
14.6 / 0.59
17.2 / 0.68
18.7 / 0.73
176 / 125
219 / 160
259 / 180
319 / 215
335 / 235
371 / 255
457 / 310
575 / 395
706 / 475
79840458
79840459
79840460
79840461
79840462
79840463
79840464
79840465
79840466
AWG 16 /7
AWG 18 /7
AWG 20 /7
RT = Radial Thickness
68
www.leoni-industrial-projects.com
UL 1277
TC
90 C / 600 V
UL-listed tray cable in compliance with NEC article 336, for use in hazardous classified locations class I and class II division 2 acc. to NEC 501.10(B) and
NEC 502.10(B).
Recommended for indoor and outdoor installation, on racks, trays, in conduits, in dry and wet locations; for direct burial.
(Please note the relevant legal / local installation requirements).
Construction
Conductor................................ plain annealed copper wire, stranded, size: AWG 14 , AWG 16 , AWG 18
Insulation.................................. heat resistant polyvinyl chloride PVC (90 C)
Color code................................ black, continuously numbered
Wrapping.................................. at least 1 layer of plastic tape
Collective shield....................... plastic coated aluminum tape in contact with tinned copper drain wire
Outer jacket.............................. heat resistant polyvinyl chloride PVC (90 C), black, blue for intrinsically
safe systems
Cable marking.......................... LEONI KERPEN ICON TC nE mAWG OS UL THHW*) 600V 90 C (194
F) SUN RES DIR BUR PRODUCTION LOT CODE LENGTH MARKING
IN FEET
*)
90 C DRY / 75 C WET (AWG 16, 18)
Technical data
Flame propagation
- Test on single cable
- Test on bunched cables
Gas/vapor tightness outer
jacket
Limiting Oxygen Index (LOI)
Flammability temperature (FT)
Sunlight resistance
Abbreviations
UL 1581, sec. 1080 (VW-1 test)
UL 1685 (vertical tray)
NEC 501.15 (D) and (E)
ASTM D 2863 (min. 30 %)
ISO 4589-3 ann. A (min. +250 C)
UL 1581 section 1200
Electrical Properties at 20 C
Conductor cross-section (AWG)
Conductor resistance
Insulation resistance
max.
min.
Mutual capacitance
nom.
Inductance
L/R ratio max.
Test voltage Urms (core : core)
max.
max.
Temperature range
-40C up to +90C
(during operation)
-5C up to +50C
(during installation)
Min. bending radius - repeated
bending
7.5 x cable diameter
/km / /1000ft
M x km /
M x 1000ft
nF/km /
nF/1000ft
mH/km
H/
V
REYw
(St)
Yw
-fl
Instrumentation Cable
PVC insulation, heat resistant
collective shield
PVC outer jacket, heat resistant
reduced flame propagation
AWG 14
8.9 / 2.72
AWG 16
14.3 / 4.36
175 / 570 (at 15 C)
AWG 18
22.8 / 6.93
170 / 52
170 / 52
170 / 52
60
0.7
40
2000
25
2000
Operating voltage
600
www.leoni-industrial-projects.com
69
UL 1277
TC
90 C / 600 V
Geometrical data
No. of elements
RT of insulation
nom.
(mm / mils)
AWG 14 /7
RT outer jacket
nom.
(mm / mils)
Outer dia.
approx.
(mm / in)
Weight
approx.
(kg/km / lbs/1000ft)
Part number
Color
black
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.14 / 45
1.14 / 45
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
9.5 / 0.37
10.8 / 0.42
12.8 / 0.50
14.7 / 0.57
16.9 / 0.66
17.5 / 0.69
19.3 / 0.76
24.8 / 0.97
28.2 / 1.11
124 / 85
183 / 125
293 / 180
346 / 240
429 / 290
485 / 330
619 / 425
950 / 640
1358 / 905
79960600
79960601
79960602
79960603
79960604
79960605
79960606
79960607
79960608
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.14 / 45
1.14 / 45
1.14 / 45
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
2.03 / 80
8.6 / 0.34
9.9 / 0.39
11.7 / 0.46
12.7 / 0.50
15.4 / 0.60
15.8 / 0.62
17.5 / 0.69
22.5 / 0.88
25.4 / 0.99
98 / 70
143 / 100
199 / 135
246 / 170
326 / 220
365 / 255
461 / 310
713 / 480
979 / 660
79960610
79960611
79960612
79960613
79960614
79960615
79960616
79960617
79960618
2
4
6
8
10
12
16
24
36
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
0.76 / 30
1.14 / 45
1.14 / 45
1.14 / 45
1.14 / 45
1.52 / 60
1.52 / 60
1.52 / 60
1.52 / 60
2.03 / 80
8.1 / 0.32
9.3 / 0.36
10.9 / 0.42
12.0 / 0.47
14.6 / 0.57
14.7 / 0.58
16.2 / 0.64
19.8 / 0.78
23.6 / 0.92
83 / 60
117 / 80
163 / 110
203 / 140
269 / 185
297 / 200
372 / 250
523 / 355
786 / 530
79960619
79960620
79960621
79960622
79960623
79960624
79960625
79960626
79960627
AWG 16 /7
AWG 18 /7
RT = Radial Thickness
70
General
General
www.leoni-industrial-projects.com
General
www.leoni-industrial-projects.com
71
General units
Length
1 mil
1 inch (in)
1 foot (ft.)
=
=
=
0.0254
25.4
0.305
mm
mm
m
1
1
1
1
=
=
=
=
0.914
1.61
1.61
1.85
m
km
km
km
Volume
1 cubic inch (in3)
1 cubic foot (ft3)
=
=
16.39
0.0283
cm
m3
1
1
1
1
=
=
=
=
yard (yd)
mile (mi.)
statute mile (mi.)
intern. naut. mile (sm)
0.765
159
3.79
4.55
Force
1 poundal (pdl)
1 pound-force (lbf)
1 Brit. ton-force
=
=
=
0.1 38
4.448
9964
Power
1 horsepower (H.P.)
0.746
Pressure
1 bf/in2 (psi)
1 lbf/ft2
1 lbf/yd2
1 lbf/in2 (psi)
=
=
=
=
0.06895
0.000479
0.0000532
0.703
Area
1 circ. mil (CM)
1 MCM
1 square inch (in2)
=
=
=
1
1
1
=
=
=
0.0929
0.836
2.59
m2
m2
km2
0.62
1.62
F/km
m3
l
l
l
1
1
1
1
0.62
3.28
3.28
3.28
N
N
N
Mass
1 ounce (oz)
1 pound (lb)
1 Brit. ton (long ton)
1 US ton (short ton)
=
0.0284
=
0.454
= 1016
= 907
kg
kg
kg
kg
kW
Energy
1 Brit. therm. unit (BU)
1 Brit. therm. unit
= 1055
=
0.000293
J
kWh
bar
bar
bar
kp/cm2
=
=
=
=
0.0005067 mm2
0.5067
mm2
645.16
mm2
6.895
47.9
5.32
0.0703
prefix
Piko
Nano
Mikro
Milli
Zenti
Dezi
=
=
=
=
M km
dB/km
pF/m
dB/km
/km
N/m2
N/m2
N/m2
at
abridged
mark
p
n
m
c
d
sub multiple
power
1012
109
106
103
102
101
name
billionth *
milliardth *
millionth
thousandth
hundredth
tenth
General
72
www.leoni-industrial-projects.com
AWG
30
28
26
24
22
20
18
16
14
12
Conductor size
Metric
No. of wires
mm
0.051
1
0.081
1
0.128
1
0.205
1
0.324
1
1
0.5 1)
0.517
1
1
0.75 1)
0.82
1
1
1.0 1)
1.3
1
1
1.5 1)
2.1
1
2.5
1
3.3
1
4.0
1
Conductor-
mm
0.254
0.320
0.404
0.511
0.643
0.8
0.813
1.0
1.02
1.13
1.29
1.37
1.63
1.76
2.05
2.26
Electrical resistance2)
EN 50288-7 )
UL 134)
/km
/1000 ft.
/km
/1000 ft.
361
110
228
69.3
154
46.9
97.6
29.7
56.3
17.2
36.8
11.2
35.2
10.7
25.0
7.6
22.3
6.8
18.5
5.6
14.0
4.3
12.3
3.76
8.79
2.67
7.56
2.31
5.52
1.68
4.70
1.43
Conductor-
mm
0.579
0.729
0.9
0.919
1.11
1.16
1.29
1.46
1.59
1.85
2.01
2.32
2.58
Electrical resistance2)
EN 50288-7 )
UL 134)
/km
/1000 ft.
/km
/1000 ft.
91.1
27.8
57.6
17.6
36.8
11.2
35.8
11.0
25.0
7.6
22.8
6.9
18.5
5.6
14.2
4.36
12.3
3.76
8.94
2.72
7.56
2.31
5.63
1.72
4.70
1.43
AWG
24
22
20
18
16
14
12
1)
Conductor size
Metric
No. of wires
mm
0.205
7
0.327
7
7
0.51)
0.517
7
7
0.75 1)
0.82
7
7
1.0 1)
1.3
7
7
1.5 1)
2.1
7
1)
7
2.5
3.3
7
4.0
7
2)
The value for the electrical resistance is given for 20 C (68.0 F).
The value for the electrical resistance according to EN 50288-7 is for the finished cables with multi pairs/triples.
3)
4)
The value for the electrical resistance according to UL 13 is calculated for one pair/triple and an assembly of pairs/triples.
General
www.leoni-industrial-projects.com
Color Codes
Color code of instrumentation and instrumentation control cables according to UL 13, UL 1277
Color code of standardized product program.
Cabling element
Pair **
Triple **
black
continuously numbered 1, 2, 3
for multi-core cables,
starting with 1 in the center
black/white
black/white/red
black
continuously numbered 1, 2, 3
for multi-core cables,
starting with 1 in the center
black/white
black/white/red
continuously numbered on white core 1, 2, 3
for multi-element cables,
starting with 1 in the center
Core *
Rated voltage
300 V
Rated voltage
600 V
* If specified green-yellow core principally applied as last element in the outer layer.
** Identification scheme for elements with and without individual screen.
Further color codes on request.
73
74
General
www.leoni-industrial-projects.com
Type designation
The type designations of LEONI's instrumentation- and
thermocouple cables are read as follows:
type abbreviation
number of cabling elements
type of cabling element
conductor size in mm AWG
Examples
RE-2Y(St)YMYSWAY-fl 24 x 3 x AWG TiMF 300 V
Instrumentation cable (RE), 24 triples (3), conductor size AWG,
insulation of PE (2Y), individual TiMF and overall screen (St),
inner sheath of PVC (Y), lead sheath (M), inner sheath made of PVC
(Y), steel wire armour (SWA), outer sheath of PVC (Y-fl),
rated voltage 300 V.
Core no figure
Pair 2
Triple 3
Individual screened pair PiMF
Individual screened triple TiMF
RT-Yw(St)YwSWAYw-fl 8 x 2 x AWG KX 300 V
Thermocouple extension (RT-), 8 pairs (2), conductor AWG, conductor material (KX), insulation of heat resistant PVC (Yw),
overall screen (St), inner sheath made of heat resistant PVC (Yw),
steel wire armour (SWA), outer sheath made of heat resistant PVC (Yw),
rated voltage 300 V.
RE-2X(St)H 8 x 2.5 mm CI 500 V
Instrumentation control cable (RE-),
Zero halogen with Circuit Integrity (CI),
8 cores, conductor size 2.5 mm, insulation of XLPE (2X),
overall screen (St), outer sheath made of Zero halogen,
flame-retardant compound (H), rated voltage 500 V.
RE-2X(L)2Y4YSWA2Y 12 x 2 x AWG, PiMF 300 V
Instrumentation cable (RE), 12 pairs 2, conductor size AWG,
insulation made of XLPE (2X), individual screen (PiMF),
multi layer sheath (L)(2Y), steel wire armour (SWA),
outer sheath made of PE (2Y), rated voltage 300 V.
General
www.leoni-industrial-projects.com
Abbreviation code
RE-2Y(St)YMYSWAY-fl TiMF
Cable type
Instrumentation and instrumentation control cable
Thermocouple extension or compensating cable
Code
RERT-
-v
Yw
Yv
2Y
2X
H
2G
4Y
(ST)
(L)
C
K
PiMF
TiMF
(C)
Metal sheath
Sheath made of lead
Armor
Galvanized round steel wires
Galvanized round steel wires with counter helix made of galvanized steel tape
Galvanized flat steel wires with counter helix made of galvanized steel tape
Double layer made of galvanized steel tapes
Braid made of galvanized round steel wires
SWA
RG
FG
B
Q
Further properties
Circuit Integrity (resistance to fire)
CI
-fl
75
PM Industrial/en/Rev1/09