PIPING
Standard Munchkin heater Traditional piping (zoning with valves) Space heating mode
Drawing 1A
zone valves
make-up water
P1
flow bypass valve
purging valves
V1
OFF
T/P
Munchkin heater
NOTES:
1. 2. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. Adjust flow bypass valve for the following minimum boiler flow rates in any operating mode: Munchkin model 80M: 3 gpm Munchkin model 140M: 5 gpm Munchkin model 199M: 7 gpm The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater is 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
3. 4. 5. 6. 7. 8.
Fig. 5-2
22
PIPING
Standard Munchkin heater Traditional piping (zoning with valves) Domestic water heating mode
Drawing 1B
zone valves
OFF OFF OFF OFF
make-up water
P1
purging valves flow bypass valve
V1
anti-scald mixing valve
T/P
Munchkin heater
NOTES:
1. 2. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. Adjust flow bypass valve for the following minimum boiler flow rates in any operating mode: Munchkin model 80M: 3 gpm Munchkin model 140M: 5 gpm Munchkin model 199M: 7 gpm The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater is 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
3. 4. 5. 6. 7. 8.
Fig. 5-3
23
PIPING
Standard Munchkin heater Traditional piping (zoning with circulators) Space heating Mode
Drawing 1C
P1
P2
T/P
Munchkin heater
NOTES: This drawing is meant to show system piping concept only. 1. Installer is responsible for all equipment & detailing required by local codes. 2. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and 3. downstream of all closely spaced tees. The ninimum pipe size for connecting a Super Stor water heater is 1 inch. 4. 5. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges 6. with full port ball valves for isolation. The anti-scald mixing valve shown on the domestic water heater is optional. 7. 8. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown. 9.
Fig. 5-4
24
PIPING
Standard Munchkin heater Preferred piping (zoning with circulators) Domestic water heating Mode
Drawing 1D
purging valves
P1
P2
T/P
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
Fig. 5-5
25
PIPING
Standard Munchkin heater Preferred piping (zoning with valves) Space heating mode
Drawing 2A
zone valves
make-up water
P2
closely spaced tees differential pressure bypass valve
purging valves
V1
anti-scald mixing valve
P1
T/P
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure drop operates by itself. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater is 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
Fig. 5-6
26
PIPING
Standard Munchkin heater Preferred piping (zoning with valves) Domestic water heating mode
Drawing 2B
zone valves
OFF OFF OFF OFF
make-up water
P2
closely spaced tees differential pressure bypass valve
purging valves
V1
anti-scald mixing valve
P1
T/P
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure drop operates by itself. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater is 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
Fig. 5-7
27
PIPING
Standard Munchkin heater Preferred piping (zoning with circulators) Space heating mode
Drawing 2C
P2
P1
T/P
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
Fig. 5-8
28
PIPING
Standard Munchkin heater Preferred piping (zoning with circulators) Domestic water heating mode
Drawing 2D
P2
P1
T/P
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
Fig. 5-9
29
PIPING
Standard Munchkin heater Preferred piping (multiple heaters / zoning with circulators) Space heating mode
space heating zone circuit
Drawing 2E
P2 PB1 PB2
T/P
T/P
Munchkin heater
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
Fig. 5-10
30
PIPING
circuit setter
T/P
zone valve
heat exchanger
air separator
Fig. 8-1
18
PIPING
Drawing 3A
zone valves
make-up water
purge
purge
P1
DHW temperature sensor outdoor temperature sensor
OFF
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure drop operates by itself.
Fig. 8-2
19
PIPING
Munchkin VISION 1 system (zoning with valves) Domestic water heating mode
Drawing 3B
zone valves
make-up water
purge
purge
P1
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure drop operates by itself.
Fig. 8-3
20
PIPING
Munchkin VISION 1 system (zoning with valves) Space heating mode (w/ submixing)
3-way (manually-set) mixing valve vent air handler
Drawing 3C
purge
balancing valve
P1
OFF
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown. Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure drop operates by itself. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.
Fig. 8-4
21
PIPING
Drawing 4A
P1
outdoor temperature sensor
OFF
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
Fig. 8-5
22
PIPING
Munchkin VISION 1 system (zoning with circulators) Domestic water heating mode
Drawing 4B
P1
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown.
Fig. 8-6
23
PIPING
Munchkin VISION 1 system (zoning with circulators) Space heating mode (w/ submixing)
3-way (manually-set) mixing valve vent air handler
Drawing 4C
P1
OFF
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Install a minimum of 12 diameters of straight pipe upstream of all circulators. A purging valve may be used in lieu of the ball valve / hose bib combination shown. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.
Fig. 8-7
24
PIPING
Munchkin VISION 1 system Drawing 4E (zoning with circulators) Space heating mode (3 fully reset supply temperatures)
vent medium temperature manifold station
make-up water
P1
OFF
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Do not use valve actuators on manifolds supplied by manually-set 3-way mixing vaalves. A purging valve may be used in lieu of the ball valve / hose bib combination shown. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.
Fig. 8-8
25
PIPING
Munchkin VISION 1 system Drawing 4F (zoning with circulators) Space heating mode (3 different supply temperatures)
vent 3-way manually-set mixing valve
air handler (higher temp.) vent low temperature manifold station high limit safety variable speed injection mixing purge
purge
make-up water
balancing valves
P1
OFF
T/P
P2
purge Super Stor indirect DHW tank thermal trap (w/ drain plug)
Munchkin heater
NOTES:
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. This drawing is meant to show system piping concept only. Installer is responsible for all equipment & detailing required by local codes. All closely spaced tees shall be within 4 pipe diameter center to center spacing. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. The minimum pipe size for connecting a Super Stor water heater is 1 inch. The minimum pipe size for connecting a Munchkin heater shall be 1.25 inches. All pumps are shown with isolation flanges and integral flow check valves. The alternative is standard flanges with full port ball valves and a separate flow check valve. The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119 F. Follow all instructions for installation of injection mixing system. A purging valve may be used in lieu of the ball valve / hose bib combination shown. Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.
Fig. 8-9
26