Current in Multiples of (I r )

.5 .7 1 2 3 4 5 7 10 12 20 30

Long Delay Response & Short Delay with I2 T Response Curve & Instantaneous/Maintenance Mode Setting

2 HOURS

10000 9000 8000 7000 6000 5000

Circuit Breaker Time/Current Curves (Phase Current)


1.15

1 HOUR

4000 3000

SERIES G L - Frame Circuit Breakers Catalog Types: LGC, LGU, LGX, GLE, GLS, GLH, GLC, GLU, GLX, LGE, LGS & LGH Circuit Breakers, 3 & 4 Poles
Available Sensors (In): 250A 400A 600A 630A Ir A B C D E F G H
In

2000

250A 100A 125A 150A 160A 175A 200A 225A 250A

400A 160A 200A 225A 250A 300A 315A 350A 400A

600A 250A 300A 315A 350A 400A 450A 500A 600A

630A 250A 300A 315A 350A 400A 500A 600A 630A

1000 900 800 700 600 500 400 300

Maximum T otal Clearing Time

Notes: 1. Curve accuracy applies from -20 C to + 55 C ambient. Temperatures above + 85 C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40 C, refer to Cutler-Hammer. 2. Application frequency is 50/60 Hz. 3. There is a memory effect that can act to shorten the Long Delay. If the breaker trips on a Long Delay overload and is quickly reset, the memory cap will still have charge and a subsequent overload will cause the breaker to trip in a shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 5. The left portion of the curve is shown as a multiple of the Long Delay Setting. (Long Delay Pick Up = 115% of Ir). Range is 110 - 120%.

200

1 MINUTE

100 90 80 70 60 50 40 30

Available Long Delay Time: 2,4,7,10,12,15,20,24 sec. Shown @ 6x I r 2,4,7,15,24 seconds +0/-30%

20

TIME IN SECONDS

. .
Minimum T otal Clearing Time
15

6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 7. The Short Delay Pick Up has nine settings/positions; 2-8, 10 and 12. 8. Short Delay I2T band has a tolerance of + 15%. 9. Breakpoint back to FLAT response occurs @ 8x Ir for upper line of the I2T curve.

24

10 9 8 7 6 5 4 3

.
7

Curves in this Family: Long Delay Response and Short Delay with Flat Response - TC01207004E Long Delay Response and Short Delay with I2t Response - TC01207005E Ground Fault Response Curve - TC01207006E ______________________________________________________________ Long Delay Response and Short Delay with Flat Response and Instantaneous / Maintenance Mode Setting - TC01207011E Long Delay Response and Short Delay with I2t Response and Instantaneous / Maintenance Mode Setting - TC01207012E Ground Fault Response Curve and Instantaneous / Maintenance Mode Setting - TC01207013E Instantaneous / Maintenance Mode Setting - TC01207014E

.
4 3

.
2 4

2
1 .9 .8 .7 .6 .5 .4 .3

Legend for Time Current Curves for Series G L- Frame Circuit Breakers - 5722B41

12

8
.2

I T Short Delay (See Note 8)


.1 .09 .08 .07 .06 .05 .04 .03

Available Short Delay Pick Up Settings 2-8, 10 & 12 X I r + 5% (See Notes 7 and 10)
10

.
67 ms

See Note 9
.02

.01

.5

.7

10

12

20

30

40

50

70

100

Current in Multiples of (I r ) I T
2

Trip Style

Long Delay Response & Short Delay with I2 T Response Curve & Instantaneous/Maintenance Mode Setting

Curve Number:
Printed in U.S.A.

TC01207012E
May 2008