Page 9
Section 2 RATING STANDARDS
21
.
2.2
VOLTAGE RANGES
Kilovoltampcre and voltage ratings, and primary taps for single-phase and three-phase transformers and for
autotransformers, shall be in accordance with Table 2-1.
Transformers should operate over the voltage spread in the favorable zone as stated in Table 2-2.
Authorized Englneerinfl tnformaton t-e-1992
NOTE' lb conwrt self-cooled ratings above 500 kVA to ventilated foced-cooled ratings, increase the kVA ratings in the above table by one third. The auxiliary equipment shall remain operational. Authorized Engtneefinglntormatbnl-e-igga
voltages which are sometimes used may be interpreted in 1611,18 of the values $Mwn in Table 2-2, Tkble 2-3 has been prepared. It should be emphasized that all of the different vaIues on anyone line refer to the same value as defined
Table 2-1
Voltage Rating Of
Transformer, Volts 0350 0.500 6.750 1.0 1.5 2.0 3.0 5.0 7.5 10.0 15.0 25.0 37.5 50.0 75.0 100.0 167.0 250.0 333.0 500.0
Transfoimep!
120x240-120/240
480-l2{V240
X A
X A
X A
X A
X A
X D
....
XXXXXXXXXXXXXXCCC x
X x
x
X X
x
X X
x
X X
x
X X
x
X X
AAAAADDDDDEEFF
X X X
240/120
Voltage Rating of
Transformer, Volts
3.0
6.0
9.0
15.0 30.0 45.0 75.0 1125 150.0 225.0 300.0 500.0 750.0 1000 1500
480 - 208Y/120
600 - 208Y/120
Sec 4 2 1 2
.
. .
F
F
xxAAD0DDDDDBEE
a transformer having no primary taps transformer having two 5 percent fuU-capacity primary taps below rated voltage C-designates a transformer having two 5 percent full-capacity primary taps below rated voltage on the 240-volt winding and four 2.50 percent full-capacity primaiy taps below rated voltage on the 480-volt winding. D-designates a transformer having four 2 50 percent full-capacity primary taps below rated voltage and two 2.50 percent full-capacity primary taps above rated voltage. E-designates a transformer having two 2 50 percent full-capacity primary taps below rated voltage and two 2.50 percent full-capacity primary taps above rated voltage. F-designates a transformer having one 5 percent full-capacity primary tap below rated voltage and one 5 percent full-capacity primary tap above rated voltage.
.
X-designates
A-designates a