Sie sind auf Seite 1von 2

Energy Division

Deadbreak Junctions
600/900 Amp 15/28-35 kV Class
The 600A/900A deadbreak junction is available in both 15/28 kV and 35 kV Class versions. Deadbreak junctions are used with 600/900A elbows and accessories for connecting, establishing loops, tapping, and facilitating apparatus change out. They are commonly used in pad-mounted apparatus, sectionalizing cabinets, and underground vaults, where there is a critical use of space, flexibility, and operability. Ratings  Voltage Class 15/28 kV
Max Rating Phase-to-Ground 16.2 kV Max Rating Phase-to-Phase 28 kV AC 1 Minute Withstand 45 kV DC 15 Minute Withstand 88 kV BIL and Full Wave Crest 140 kV Minimum Corona Level 21.5 kV (3pC)  Continuous 600/900A rms 24 Hour Overload 1,000A rms   Momentary: 600A 25,000 A symmetrical 10 cycles 600A 10,000 A symmetrical 3.00 sec 900A 40,000 A symmetrical 10 cycles 900A 10,000 A symmetrical 3.00 sec

The junction provides two, three, or four deadbreak interfaces bused together and encapsulated in a molded, peroxide-cured EPDM insulated rubber body, with an EPDM peroxide-cured semi-conductive outer shield. Optional stationary or adjustable mounting brackets are available, assembled with the junctions themselves. 900A ratings are achieved by ordering the copper version, but require copper cable and other copper constructed components. Ratings  Voltage Class 35 kV
Max Rating Phase-to-Ground 21.1 kV Max Rating Phase-to-Phase 36.6 kV AC 1 Minute Withstand 50 kV DC 15 Minute Withstand 103 kV BIL and Full Wave Crest 150 kV Minimum Corona Level 26 kV (3pC)  Continuous 600/900A rms 24 Hour Overload 1,000A rms   Momentary: 600A 25,000 A symmetrical 10 cycles 600A 10,000 A symmetrical 3.00 sec 900A 40,000 A symmetrical 10 cycles 900A 10,000 A symmetrical 3.00 sec

A fully shielded, submersible connection is offered, with conformance to IEEE Standard 386. These deadbreak junctions are therefore interchangeable with other manufacturers products that also comply with this standard. Features Available in 2, 3, 4 point configurations Deadfront, 15/28 kV or 35 kV, 600 or 900A Ratings EPDM molded rubber construction Optional corrosion resistant stainless steel (adjustable or stationary) mounting brackets for direct wall mounting

Maintenance free, fully shielded, submersible

Applications include padmount, indoor/ outdoor vault, subsurface Conforms to ANSI/IEEE Standard 386 Heavy duty U-straps provide secure mounting for junctions

100% Production Test


 Minimum Corona Level 21.5 kV (3pC) AC 1 Minute Withstand 45 kV 

100% Production Test


 Minimum Corona Level 26 kV (3pC)  AC 1 Minute Withstand 50 kV

Selection Information
Catalog Number Current Rating Size Material

Junction with U-Strap 15/28kV ELB-15/28-600-J2-AL ELB-15/28-600-J3-AL ELB-15/28-600-J4-AL ELB-15/28-900-J2-CU ELB-15/28-900-J3-CU ELB-15/28-900-J4-CU ELB-35-600-J2-AL ELB-35-600-J3-AL ELB-35-600-J4-AL ELB-35-900-J2-CU ELB-35-900-J3-CU ELB-35-900-J4-CU Junction with Stationary Bracket Included 15/28kV ELB-15/28-600-J2-AL-STD ELB-15/28-600-J3-AL-STD ELB-15/28-600-J4-AL-STD ELB-15/28-900-J2-CU-STD ELB-15/28-900-J3-CU-STD ELB-15/28-900-J4-CU-STD ELB-35-600-J2-AL-STD ELB-35-600-J3-AL-STD ELB-35-600-J4-AL-STD ELB-35-900-J2-CU-STD ELB-35-900-J3-CU-STD ELB-35-900-J4-CU-STD 600A 600A 600A 600/900A 600/900A 600/900A 600A 600A 600A 600/900A 600/900A 600/900A J2 J3 J4 J2 J3 J4 J2 J3 J4 J2 J3 J4 Aluminum Aluminum Aluminum Copper Copper Copper Aluminum Aluminum Aluminum Copper Copper Copper 600A 600A 600A 600/900A 600/900A 600/900A 600A 600A 600A 600/900A 600/900A 600/900A J2 J3 J4 J2 J3 J4 J2 J3 J4 J2 J3 J4 Aluminum Aluminum Aluminum Copper Copper Copper Aluminum Aluminum Aluminum Copper Copper Copper

35kV

35kV

Junction with Adjustable Bracket Included 15/28kV ELB-15/28-600-J2-AL-ADJ ELB-15/28-600-J3-AL-ADJ ELB-15/28-600-J4-AL-ADJ ELB-15/28-900-J2-CU-ADJ ELB-15/28-900-J3-CU-ADJ ELB-15/28-900-J4-CU-ADJ ELB-35-600-J2-AL-ADJ ELB-35-600-J3-AL-ADJ ELB-35-600-J4-AL-ADJ ELB-35-900-J2-CU-ADJ ELB-35-900-J3-CU-ADJ ELB-35-900-J4-CU-ADJ 600A 600A 600A 600/900A 600/900A 600/900A 600A 600A 600A 600/900A 600/900A 600/900A J2 J3 J4 J2 J3 J4 J2 J3 J4 J2 J3 J4 Aluminum Aluminum Aluminum Copper Copper Copper Aluminum Aluminum Aluminum Copper Copper Copper

35kV

Related test reports:


EDR-5508

Tyco Electronics Corporation 8000 Purfoy Road Fuquay Varina, NC 27526-9349 Tel: 800.327.6996 Fax: 800.527.8350 E-mail: naenergy@tycoelectronics.com http://energy.tycoelectronics.com/elbow www.tycoelectronics.com Copyright 2010 Tyco Electronics Corporation All rights reserved. 8-1773456-0 E377 03/10

All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these products is set forth in our standard terms and conditions of sale. TE (logo) and Tyco Electronics are trademarks. Other products, logos, and Company names mentioned herein may be trademarks of their respective owners. Energy Division a pioneer in the development of economical solutions for the electrical power industry. Our product range includes: Cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters.